Residential AirConditioning R-22. Roger D. Holder, CM, MSME

Size: px
Start display at page:

Download "Residential AirConditioning R-22. Roger D. Holder, CM, MSME"

Transcription

1 Refrigeration Piping & Charging Residential AirConditioning R-22 Roger D. Holder, CM, MSME Refrigeration is the process of moving heat from one location to another by the use of refrigerant in a closed cycle. The piping and tubing system must be designed, installed and maintained to provide proper flow of refrigerant in both liquid and gaseous states.

2 2 2

3 Piping & Tubing 3 Refrigeration Piping Refrigeration is the process of moving heat from one location to another by the use of refrigerant in a closed cycle. The piping and tubing system must be designed, installed and maintained to provide proper flow of refrigerant in both liquid and gaseous states. A successful refrigeration system depends on a good piping design and an understanding of the required accessories. The first skill that any refrigeration apprentice mechanic learns is to make a soldered joint. Running pipe is so common a task that its critical importance in system performance is often overlooked. Tubing Inspection & Leak Check The object of a good visual inspection of system tubing design is to note obvious oil traps. Also look for long vertical suction lengths without p traps and inadequate OD tubing size If the system is known to be leaking or if oil is present around mechanical fittings, solder joints, gaskets or seals, recover the refrigerant and repair the leaks. Pressurize the system with a residual amount of refrigerant and dry nitrogen using the recommended test pressure on data plate. Maximum test pressures should be approximately 150 psi for high-pressure AC/R systems. In chiller applications, controlled hot water or heater blankets will raise pressure adequately for a leak check, which should never exceed 10 psi for low pressure chillers. After a thorough inspection with a good leak detector, apply a deep vacuum to 500 microns. A good triple evacuation, with dry nitrogen and then deep vacuum is the preferred method. Piping Basic Principles Refrigeration piping involves extremely complex relationships in the flow of refrigerant and oil. Fluid flow is the study of the flow of a gas or a liquid, and the inter-relationship of velocity, pressure, friction, density and the work required to cause the flow. The design of a refrigeration piping system is a continuous series of compromises. It is desirable to have 3

4 4 maximum capacity at minimum cost, as well as proper oil return. Since oil must pass through the compressor cylinders to provide lubrication, a small amount of oil is always circulating with the refrigerant. Oil and refrigerant vapor, however, do not mix readily, and the oil can be properly circulated through the system only if the mass velocity of the refrigerant vapor is great enough to sweep the oil along. To ensure oil circulation adequate velocities of refrigerant must be maintained in the suction and discharge lines, and in the evaporator. The design of refrigerant piping systems should: Ensure proper refrigerant feed to evaporators. Provide practical refrigerant line sizes without excessive pressure drop. Prevent excessive amounts of lubricating oil from being trapped in any part of the system. Protect the compressor at all times from loss of lubricating oil. Prevent liquid refrigerant or oil slugs from entering the compressor during operating and idle time. Maintaining a clean and dry system. Refrigerant Line Velocities Economics, pressure drop, noise, and oil entrapment require establishing feasible design velocities in refrigerant lines. Suction line 700 to 4000 fpm Discharge line 500 to 3500 fpm Condenser drain line 100 fpm or less Liquid line 125 to 450 fpm Higher gas velocities are sometimes found in relatively short suction lines, on comfort air conditioning or other applications where the operating time is only 2000 to 4000 hours per year and where low initial cost of the system may be more significant than low operating cost. In the Industrial refrigeration applications where equipment runs continuously, should be designed with low refrigerant velocities for most efficient compressor performance and low equipment operating cost. Care must be taken that the velocities is not to low that oil is taped in the refrigeration lines. Liquid line from condenser to receivers should be sized for 100 fpm or less to ensure positive 4

5 5 gravity flow without incurring backup of liquid flow. Liquid lines from receivers to evaporator should be sized to maintain velocities below 300 fpm, thus minimizing or preventing liquid hammer when solenoids or other electrically operated valves are used. Refrigerant Line Sizing In sizing refrigerant lines, cost considerations favor keeping line size as small as possible. However, suction and discharge line pressure drops cause loss of compressor capacity and increased power use. Excessive liquid line pressure drops can cause the liquid refrigerant to flash, resulting in faulty expansion valve operation. Refrigeration systems are designed so that friction pressure losses do not exceed a pressure differential equivalent to a corresponding change in the saturation boiling temperature. The primary measure for determining pressure drop is a change in saturation temperature. Pressure drop in refrigerant lines causes a reduction in system efficiency. Correct sizing must be based on minimizing cost and maximizing efficiency. Pressure drop calculations are determined as normal pressure loss associated with a change in saturation temperature of the refrigerant. Typically, the refrigeration system will be sized for pressure losses of 2ºF or less for each segment of the discharge, suction, and liquid lines. An HFC refrigerant liquid line is sized for pressure losses of 1ºF or less. Discharge lines should be designed to: Avoid trapping oil at part-load operation. Prevent condensed refrigerant and oil from draining back to the head of the compressor. Have carefully selected connections from a common line to multiple compressors. Avoid developing excessive noise or vibration from hot-gas pulsation, compressor vibration, or both. When sizing discharge lines, considerations similar to those applied to the suction line are observed. Pressure loss in discharge lines increases the required compressor power per unit of refrigeration and decreases the compressor capacity by increasing the compression ratio. While the discharge line pressure drop is not as critical as that of the suction line, the accepted maximum values are 4 psi for R-12 and 6 psi for R-22. The same minimum gas velocities of 500 feet per minute in horizontal runs and 1000 feet per minute in vertical runs with upward gas flow are observed. The maximum acceptable gas velocity, based on noise considerations, is 4000 feet per minute. 5

6 Condenser Drain Line 6 The line between a condenser (not providing liquid subcooling) and a liquid receiver, when such an arrangement is used, must be carefully sized. While it is almost impossible to oversize such a line, under sizing is to be avoided. An undersized line can restrict the flow of refrigerant to the extent that some of it is held in the condenser. If some of the condenser surface is flooded, the capacity is reduced. These causes the head pressure to rise and decrease the overall system capacity. At the same time, the power to drive the compressor rises. There are a few points that the piping designer should keep in mind. Condenser drain line velocity should be 100 fpm or less. The distance from the condenser to receiver should be as short as possible. The condenser must be located above the receiver. If the system is equipped with an air-cooled condenser and a liquid receiver, it is good practice to locate the receiver within the building. Some means should be provided to isolate the receiver from the condenser during cold weather shutdown, such as a combination check and relief valve. Receiver Refrigerant receivers are vessels used to store excess refrigerant while still allowing circulation throughout the system. Receivers perform the following functions: Provide pumpdown storage capacity when another part of the system must be serviced or the system must be shut down for an extended time. In some water-cooled condenser systems, the condenser also serves as a receiver if the total refrigerant charge does not exceed its storage capacity. Handle the excess refrigerant charge that occurs with air-cooled condensers using the flooding type condensing pressure control. Accommodate a fluctuating charge in the low side. Drain the condenser of liquid. Maintain an adequate affective condensing surface on system where the operating charge in the evaporator and or condenser varies for different loading conditions. When an evaporator is fed with a thermal expansion valve, hand expansion valve, or low-pressure float, the operating charge in the evaporator varies considerably depending on the loading. During low load, the evaporator requires a larger charge since the boiling is not as intense. When the load 6

7 7 increases, the operating charge in the evaporator decreases, and the receiver must store excess refrigerant. Hold the full charge of the idle circuit on systems with multicircuit evaporators that shut off the liquid supply to one or more circuits during reduced load. Receiver Design Considerations Receiver should be close to the condenser. If there is any doubt about the line size, use the larger of the sizes. Always adhere to the minimum vertical dimension required to overcome friction. Install a pressure relief device on top of each receiver and on condenser. The surge receiver pressure relief device is piped together with condensers. Size the receiver to hold 40 to 125% of refrigerant charge depending on system load variance. When a through type receiver is used, the liquid must always flow from the condenser to the receiver. The piping must provide free flow of liquid from the condenser to the receiver by equalizing the pressure between the two. If a vent is not used, the piping between condenser and receiver is sized so that liquid flows in one direction and gas flows in the opposite direction. Sizing the condensate drain line for 100 fpm liquid velocity is usually adequate to attain this flow. Piping should slop at least 0.25 in/ft and eliminate any natural liquid traps. The condensate drain line should be sized so that the velocity does not exceed 100 fpm. Please consult the manufacturer s literature for making receiver capacity comparisons when changing refrigerants. Liquid Lines Pressure drop should not be so large as to cause gas formation in the liquid line or insufficient liquid pressure at the liquid feed device. Systems are normally designed so that the pressure drop in the liquid line, due to friction, is not greater than that corresponding to about a 1º to 2ºF change in saturation temperature. Pressure drop (in psig) for a change of 1ºF saturation at 100ºF condensing pressure: (R-508B is at 10ºF): 7

8 8 Liquid subcooling is the only method of overcoming the liquid line pressure losses in order to guarantee liquid at the expansion device in the evaporator. If the subcooling is insufficient, flashing will occur within the liquid line and degrade the efficiency of the system. Friction pressure drops in the liquid line are caused by accessories such as solenoid valves, filter driers, and hand valves, as well as by the piping and fittings between the receiver outlet and the refrigerant feed device at the evaporator. Liquid line risers are also a source of pressure loss. The loss due to a riser is approximately psi per foot of liquid lift. The total loss is the sum of all friction losses plus the pressure loss from liquid risers. Refrigeration systems that have no liquid risers and have the evaporator below the condenser and/or receiver benefit from a gain in pressure due to liquid weight. They can thus tolerate larger friction losses without flashing. When flashing occurs, the overall efficiency is reduced and the system may malfunction. The only way to reduce the effect of pressure loses and friction is by subcooling the refrigerant. Suction Lines Suction lines are more critical than liquid and discharge line from a design and construction standpoint. They should be designed to: Provide a minimum pressure drop at full load. Return oil from the evaporator to the compressor under minimum load conditions. Prevent oil from draining from an active evaporator into an idle one. A pressure drop in the suction line reduces a system s capacity by forcing the compressor to operate at a lower suction pressure, in order to maintain a desired evaporating temperature in the coil. As the suction pressure is decreased, each pound of refrigerant returning to the compressor occupies a greater volume, and the weight of the refrigerant pumped by the compressor decreases. For example, a typical low 8

9 9 temperature R-502 compressor at -40ºF evaporating temperature will lose almost 6% of its rated capacity for each 1 psi suction line pressure drop. Normally accepted design practice is to use a suction line pressure drop equivalent to a 2ºF change in saturation temperature. Of equal importance in sizing the suction line is the necessity of maintaining adequate velocities to properly return oil to the compressor. Studies have shown that oil is most viscous in a system after the suction vapor has warmed up a few degrees from the evaporating temperature, so that the oil is no longer saturated with the refrigerant. This condition occurs in the suction line after the refrigerant vapor has left the 9

10 10 evaporator. Movement of the oil through suction lines is dependent on both the mass and velocity of the suction vapor. As the mass or density decreases, higher velocities are required to force the oil along. Nominal minimum velocities of 700 fpm in horizontal suction lines and 1500 fpm in vertical suction lines have been recommended and used successfully for many years as suction line sizing design standards. Use of the one nominal velocity provided a simple and convenient means of checking velocities. However, tests have shown that in vertical risers the oil tends to crawl up the inner surface of the tubing, and the larger the tubing, the greater velocity required in the center of the tubing to maintain tube surface velocities that will carry the oil. The exact velocity required in the vertical line is dependent on both the evaporating temperature and the line size, and under varying conditions, the specific velocity required might be either greater or less than 1500 fpm. An HFC refrigerant, however, is designed for 1500 fpm or greater. Always pitch vapor lines in the direction of flow, 1/2 inch per ten-foot of suction line. P traps for uphill oil return should be used after the first 6- foot and every 12-foot thereafter. It is good practice to use an inverted trap just before entering the compressor. Double Risers On systems equipped with capacity control compressors, or where tandem or multiple compressors are used with one or more compressor cycled off for capacity control, a single suction line riser may result in either unacceptably high or low gas velocities. A line properly sized for light load conditions may have too high a pressure drop at maximum load, and if the line is sized based on full load condition, then velocities may not be adequate conditions to move oil through the tubing at light load. On air conditioning applications where somewhat higher pressure drops at maximum load conditions can be tolerated without any major penalty in overall system performance, it is usually preferable to accept the additional pressure drop imposed by a single vertical riser. However, on medium or low temperature applications where pressure 10

11 11 drop is more critical and where separate risers from individual evaporators are not possible, a double riser may be necessary to avoid an excessive loss of capacity. A typical double riser has a small and large riser. The two should be sized so that the total cross-sectional area is equivalent to the cross-section area of a single riser that would have both satisfactory gas velocity and acceptable pressure drop at maximum load conditions. The larger is trapped and the smaller line must be sized to provide adequate velocities and acceptable pressure drop when the entire minimum load is carried in the smaller riser. Another method of suction oil return is the use of a double riser, as shown in Figure 1. Oil return is accomplished with this method at minimum loads. In addition, excessive pressure drop at full load is avoided. The small riser A is sized to return oil under minimum capacity conditions. Riser B which, may be larger, is sized so pressure drop through both risers during full load conditions is adequate. Traps with minimum oil holding capacity are recommended. 11

12 12 Suction Line Double Risers Sizing Single Riser Size Double Riser Sizes 2/3, 1/3 1 1/8 =.83 7/8 and 3/4 = /8 = /8 and 7/8 = /8 = /8 and 7/8 = /8 = /8 and 1 3/8 = /8 = /8 and 1 5/8 = /8 = /8 and 1 5/8 = 6.55 Defrost Gas Supply Lines Sizing refrigeration lines to supply defrost gas to one or more evaporator is an estimate at best. The parameters associated with sizing the defrost gas lines are related to allowable pressure drop and refrigerant flow rate during defrost. Design professionals typically use approximately two times the evaporator load for effective refrigerant flow rate to determine line-sizing requirements. The pressure drop is not as critical during the defrost cycle, and many engineers have used velocity as criterion for determining line size. The effective condensing temperature and average temperature of the gas must be determined. The velocity determined at saturated conditions will give a conservative line size. It is recommended that initial sizing be based on twice the evaporator flow rate and that velocities from 1000 to 2000 fpm be used for determining the defrost gas supply line size. Refrigerant Line Capacity Tables & Equivalent Lengths Of Valves & Fittings Refrigerant line capacity tables are based on unit pressure drop per 100 ft length of straight pipe or per combination of straight pipe, fitting, and valves with friction drop equivalent to a 100 ft length of straight pipe. Generally, pressure drop through valves and fittings is determined by establishing the equivalent straight length of pipe of the same size with the same friction drop. Alternately, one rule of thumb is to add 50% to the calculated pipe length to account for pressure drops from fittings and valves. 12

13 13 Expansion & Contraction Temperature change will expand and contract all refrigeration piping material. Techniques must allow for expansion and contraction changes to prevent stresses that may buckle, bend or rupture the refrigerant piping. he two common methods of taking care of expansion and contraction in copper piping are the expansion loops or pipe offsets. During the installation of the line, care must be taken that the line maintains a perfect alignment. On average, copper s coefficient of expansion is inch per inch per degree Fahrenheit. Thus, expansion of copper is 1.25 inch per 100 feet per 100ºF change. For example, a copper compressor discharge line of 75 feet long at 225ºF could have a temperature change of 150ºF in a 70ºF room. Therefore, 1.25 X 1.55 (temperature change per 100ºF) X.75 (length per 100 feet) will equal inches of expansion. The 75 foot long line would now be approximately 75 feet, 1-1/2 inches long. Location & Arrangement of Piping Refrigerant lines should be as short and direct as possible to minimize tubing and refrigerant requirements and pressure drops. Plan piping for a minimum number of joints, using as few elbows and other fitting as possible, but provide sufficient flexibility to absorb compressor vibration and stresses due to thermal expansion and contraction. 13

14 14 Arrange refrigerant piping so that normal inspection and servicing of the compressor and other equipment is not hindered. Do not obstruct the view of the oil level sight glass, or run piping so that it interferes with the removal of compressor cylinder head, end bells, access plates, or any internal parts. Suction line piping to the compressor should be arranged so that it will not interfere with removal of the compressor for servicing. You must provide adequate clearance for insulation installation between the piping, wall, and hangers. Use sleeves that are sized to permit installation of both pipe and insulation through floor, walls, or ceilings. Set the sleeves prior to pouring of concrete or erection of brickwork. Piping must not interfere with passages or obstruct headroom, windows, or doors. Refer to ASHRAE Standard 15, Safety Code for Mechanical Refrigeration, and other governing local codes for restrictions that may apply. Protection Against Damage To Piping Protection against damage is necessary, particularly for small lines, which have a false appearance of strength. Where traffic is heavy, provide protection against impact from pedestrian and motorized traffic. Piping Insulation All piping joints and fittings should be thoroughly leak tested before insulation is sealed. Suction lines should be insulated to prevent sweating and heat gain. Insulation covering lines on which moisture can condense or lines subjected to outside conditions must be vapor sealed to prevent any moisture travel through the insulation, or condensation in the insulation. Although the liquid line ordinarily does not require insulation, the suction and liquid lines can be insulated together. The liquid line should be insulated to minimize heat gain if it passes through an area of higher temperature. Hot gas discharge lines usually are not insulated, however, they should be insulated if the heat dissipated is objectionable or if necessary to prevent injury from high temperature surfaces. 14

15 15 Vibration & Noise in Piping Two undesirable effects of vibration of refrigerant piping are: 1) physical damage to the piping, which may result in the breaking of brazed joints and consequent loss of charge; and 2) transmission of noise through the piping itself and through building construction with which the piping may come into direct physical contact. Both can be eliminated or minimized by proper piping design and installation. Using Manufacturer s Pressure Drop & Velocity Charts Always size for pressure drop first, then velocity. On the top right of the pressure drop chart in Figure 8-3, you will find tons of refrigeration or cooling capacity calibrated in Btu per hour up to 1 ton, and in tons of cooling from 1 ton to 100 tons. You start the sizing procedure by drawing a straight line from your system s designated capacity through the diagonal lines on the right side of the chart. The diagonal lines represent: The evaporator temperature, used to size the suction line. The discharge line temperature, used to size the hot gas discharge. The liquid lines diagonal line, used to size the liquid line. 15

16 16 The diagonal lines on the left of the chart represent the actual tubing sizes that will be derived by your calculation. Starting at the bottom line, representing 3/8" OD Type L copper tubing and increasing in size up through 6-1/8. Draw a horizontal line from each intersection of tonnage and each of the three diagonal lines, horizontally across through the tubing sizes. On the bottom left of the chart you will find the pressure drop graph. The three horizontal lines represent condenser coil temperature applications. The curved diagonal lines are pressure drop in psi per 100 ft. When you have determined necessary condenser coil temperature follow the horizontal line to the required pressure drop. Draw a line straight up until it intersects with the horizontal line used to determine tubing size. If it falls in between two sizes then your size is the tubing size up and to the left. For example, let s size for a 6-ton R-134a medium temperature walkin refrigerator using the chart in your book: 16

17 17 First, find 6 tons on the top right of your chart and draw a vertical line straight down through all of the diagonal lines. Medium temperature requires a 20 F evaporator so draw a line from the diagonal line designated 20 F horizontally all the way across the chart. Do the same from the diagonal line labeled Discharge Line. And again from the diagonal line labeled Liquid Line. The suction line pressure drop maximum for medium temperature is 1-1/2 psi so the suction line size will be 1-5/8". We require a 3psi pressure drop for our liquid line so the line size is 5/8". The hot gas discharge line is a bit more forgiving, 10 psi or less, so 1-1/8" will work adequately. The velocity chart is very similar to the pressure drop chart and is used in the same way. The idea is to confirm the sizes you found on the pressure chart by cross checking with the applicable velocities on the velocity chart. If you plot the same temperature variables on the velocity chart, you ll find the sizes chosen will fall between minimum and maximum velocities recommended for each refrigeration line. There are exceptions and sometimes economical compromises on many close-coupled and field fabricated systems. It is these exceptions that may need careful consideration before retrofit. 17

18 18 18

19 19 19

20 20 20

21 21 21

22 22 22

23 23 23

24 24 24

25 25 25

26 26 404A 26

27 27 27

28 28 402A 28

29 29 29

30 30 30

31 31 31

32 32 32

33 33 Charging Residential Air Conditioning R-22 Different types of metering devices have different ways of charging. A Thermostatic Expansion Valve (TXV) is charged to the subcooling of the liquid line leaving the condenser. A fixed orifice is charged to the superheat of the suction line leaving the evaporator. To under stand why this is, it requires an understanding of the physical properties of the refrigeration cycle. The four main components of the refrigeration cycle include: Compressor Condenser Metering Devices Evaporator These four components are divided into sections and explained in depth as follows. Compressor The Compressor compresses a low-pressure superheated gas into a high-pressure superheated gas. If the suction gas is not superheated, the compressor can be damaged. The compressor pulls the refrigerant out of the evaporator and pushes it though a condenser. The act of compression is performed by any one of the following six types of compressors: a reciprocating piston, rotary, scroll, screw, centrifugal, and sonic compressors. Of the six, the reciprocating and scroll compressors are the two most frequently found in a residential air conditioning system. The mass flow rate produced by a compressor is equal to the mass of the suction gas pulled in by the compressor. The compressor s out put is equally only to its intake because the mass flow must be equal. The process of compression, through mass flow, raises the temperature and pressure of the refrigerant. The result of the temperature increase is superheat. Pressure and temperature of the refrigerant must be higher than the condensing temperature. The refrigerant temperature must be 33

34 34 higher so heat can flow into the condensing medium. This process explains the necessary relationship between the increased pressure and the rise in temperature. If the pressure and temperature is not increased through compression, there is no heat transferred from the refrigerant to the condensing medium. The compressor has a maximum inlet temperature of about 70 degrees and outlet of about 225 degrees. Inlet refrigerant gas cools the compressor motor. Desuperheating (heat leaving the refrigerant gas) of refrigerant begins as it is discharged. From a compressor and pushed into a condenser. Condenser The condenser removes heat and changes a high-pressure vapor into a high-pressure liquid. As the superheated (high-pressure) gas is pushed into the condenser, it is desuperheated, that is the temperature is reduced to saturated pressure-temperature. The refrigerant does not start to change state until the temperature reaches saturated pressure-temperature. The only variable that can change the temperature is a pressure change. (See table 1) At saturation pressure-temperature point, the change of state becomes latent heat (invisible or hidden heat). Latent heat is a lack of rise or fall of temperature during a change of state (saturation). When the temperature does not rise or fall it is at saturation and the change of state process begins. Refrigerant continues to change state at one pressure-temperature. The only variable that can change a temperature is a pressure change. If a temperature change occurs a pressure change occurs. If a pressure change occurs a temperature change occurs. At the change of state the refrigerant liquid and vapor are at the same temperature. This is defined as equilibrium contact. The temperatures of the liquid and vapors will stay the same until the temperature of the refrigerant starts to drop. Temperature of the refrigerant start to drop once 98% to 99% of the refrigerant becomes a liquid. This is called subcooling. Subcooling is a temperature below saturated pressuretemperature. (See table 1) Subcooling is a measurement of how much liquid is in the condenser. In air conditioning, it is important to measure subcooling because the longer the liquid stays in the condenser, the greater the sensible (visible) heat loss. 34

35 35 Low subcooling means that a condenser is empty. High subcooling means that a condenser is full. Over filling a system increases, pressure due to the liquid filling of a condenser that shows up as high subcooling. To move the refrigerant from condenser to the liquid line, it must be pushed down the liquid line to a metering device. If a pressure drop occurs in the liquid line and the refrigerant has no subcooling, the refrigerant will start to re-vaporize (change state from a liquid to a vapor) before reaching the metering devise. Refrigerant 22 Liquid line Saturated temperate - Temperature = subcooling 200 psig = 101 degrees - 96 degrees = 5 degrees 210 psig = 105 degrees - 90 degrees = 15 degrees 240 psig = 114 degrees - 98 degrees = 16 degrees (Table 1) Metering Devices A metering device is a pressure drop point, which has two jobs: 1. Holds refrigerant back in a condense; and 2. Feeds refrigerant into the evaporator. When high-pressure liquid enters a metering device, pressure starts to drop, as the temperature remains the same until it reaches saturation pressure-temperature. At this time both the pressure and temperature continues to drop to evaporator pressuretemperature. (See table 2) Low-pressure liquid that is leaving the metering device is boiling at saturated pressure-temperature. The process of a refrigerant changing its state (from a liquid to a vapor) in the metering device is called flash gas. Flash gas is what cools the refrigerant liquid in the metering device. A system with no subcooling 35

36 has more gas that is flashed and less capacity. 36 Evaporators The refrigerant enters the evaporator as a boiling low-pressure liquid at saturated pressure-temperature. It continues to boil at one temperature as long as the pressure remains the same. If there is not a pressure change in the evaporator, there will not be a temperature change in the refrigerant changing state. At saturation, refrigerant absorbs latent heat, which is a change of state heat. The refrigerant changes state at one temperature (for any one pressure) from the beginning of the evaporator until the entire liquid refrigerant has become a vapor. The only variable that can change a temperature is a pressure change. If a temperature change occurs a pressure change occurs. In latent heat, the liquid and vapor are at the same temperature due to equilibrium contact. When heat is added to the gas, past saturation pressuretemperature, it is called superheat. (See Table 2) Superheat is an indication of how full the evaporator is of liquid refrigerant. High superheat means the evaporator is empty. Low superheat means the evaporator is full. There have been reports that liquid refrigerant can still be boiling with 2 degrees of superheat. Superheat should never be observed below 4 degrees or a compressor failure may occur. The superheat gas is pulled into the compressor were it starts the cycle again. Refrigerant 22 suction line Saturated temperate - Temperature = superheat 58 psig = 32 degrees - 44 degrees = 12 degrees 64 psig = 37 degrees - 47 degrees = 10 degrees 70 psig = 41 degrees - 50 degrees = 9 degrees (Table 2) 36

37 Charging Methods 37 Before charging of a residential air conditioning system, two temperatures must be recorded: 1. Condensing air inlet dry bulb temperature. 2. Evaporator air inlet wet bulb temperature. Wet bulb temperature is a measurement of the heat contained within air. Air may have many different wet bulb temperatures for one dry bulb temperature, depending on relative humidity of the air. Different types of metering devices have different ways of charging. Thermostatic Expansion Valve R-22 A/C with a Thermostatic Expansion Valve (TXV) is charged to the subcooling of the liquid line leaving the condenser because the superheat is fixed. The superheat is fixed at 8 to 12 degrees in most residential air conditioning systems. Subcooling is the amount of liquid held back in the condenser. This allows the liquid to give up more heat, below saturated pressure- temperature. For every one degree of subcooling at the same condensing pressure, capacity will increase.5 percent. Increasing subcooling with an increase of discharge pressure and compression ratio, decrease capacity. Add 5 degrees of subcooling for every 30 feet of liquid line lift. To measure subcooling: 1. Obtain refrigerant saturation pressure-temperature. Take a pressure reading of the liquid line leaving the condenser. Refrigerant saturation temperature is the pressuretemperature when the refrigerant is turning from a high-pressure vapor into a highpressure liquid (giving up heat). At saturation pressure-temperature, both liquid and vapor are at the same temperature. 2. Convert pressure to temperature with a pressure temperature chart. 3. Take a temperature reading at the leaving liquid line of the condenser. 4. Compare both, the saturated temperature and leaving liquid line temperature. Subtracting one from the other, the difference is the amount the refrigerant has cooled past saturated temperature. This is subcooling. (See table 1) This four-step procedure is known as subcooling. Manufacturers should be able to 37

38 38 identify the amounts of subcooling they have designed into a system. A low charge will give a low subcooling. An overcharge will give a high subcooling along with a high compression ratio. Do not worry about a few bubbles in the sight glass. Sight glasses will not always be clear with a full charge. The zeotropes refrigerant group is known for their fractionation. It is possible to never have a clear sight glass. To determine what the subcooling should be in a system (see table 3). Subcooling for A/C with TXV R-22 Evaporator Inlet Air Temperature Fahrenheit Wet Bulb Outside Air Temperature DB (Table 3) degrees Fixed Orifice R-22 A/C with a fixed orifice is charged to the superheat of the suction line leaving the evaporator. Superheat is the gas temperature above the saturated temperature. Superheat can be split into two types of heat: 1. Superheat of the evaporators; and 2. Total superheat entering the compressor. The evaporators superheat must be figured at the evaporator outlet not at the compressor inlet. Total superheat is figured at the compressor inlet. To measure evaporator superheat: 1. Take a pressure reading of the suction line-leaving evaporator to get refrigerant saturation pressure-temperature. Refrigerant saturation temperature is the pressure- 38

39 39 temperature when the refrigerant is turning from a low-pressure liquid to a lowpressure vapor (absorbing heat). At saturation pressure-temperature, both liquid and vapor are at the same temperature. 2. Convert pressure to temperature with a pressure temperature chart. If reading is obtained at the compressor, not at the evaporator leaving line, you may have to add a few pounds of pressure due to pressure drop in the suction line. 3. Take a temperature reading at the leaving suction line of the evaporator. 4. Compare both, the saturated temperature and the leaving suction line temperature. Subtracting one from the other, the difference is the amount the refrigerant gas has heated past saturated temperature. This is superheat. (See table 2) This four-step procedure is known as superheat. Manufacturers should be able to identify the amounts of superheat they have designed into a system. A low charge will give a high superheat. An overcharge will give a low superheat along with a higher compression ratio. To determine what superheat in a system should be, see (table 4). Superheat for A/C with fixed Orifice R-22 Evaporator Inlet Air Temperature Fahrenheit Wet Bulb Outside Air Temperature DB (Table 4) degrees 39

40 Total Superheat Method 40 Some residential air-conditioning system with fixed orifice may be charged by the total superheat method. Various equipment manufacturers furnish charts with their units that explain the proper procedures to the installing or servicing technician. This method, similar to evaporator superheat method, is effective only when the indoor conditions are within 2F of desired indoor comfort conditions and the suction pressure and temperature is stabilized. To measure total superheat: 1. Read and record the outdoor ambient air-dry bulb temperature entering the condenser. 2. Read and record suction line pressure and temperature at the suction service valve or service port at compressor. 3. From Table 5, the reading at the intersection of vapor pressure and outdoor ambient temperature should coincide with the actual vapor line temperature. 4. If the vapor line temperature is not the same, adjust the refrigerant charge. Adding R-22 will raise suction pressure and lower suction line temperature. Removing R-22 will lower suction pressure and raise suction line temperature. Caution: If adding R-22 increases both suction pressure and temperature, the unit is overcharged. This method is very useful when performing preventive maintenance or corrective 40

41 41 service on residential air conditioning. Remember to always refer to the manufacturer s recommendations whenever possible. Vapor pressure at service valve Outdoor T Vapor line T at compressor F Refrigeration The use of sight glass for charging is common in refrigeration. It is better to charge a system first by measuring the operating condition (discharge and suction pressures, suction line temperature, compressor amps, super heat, subcooling and coils temperature deferential) before using the liquid line sight glass. If the sight glass is close to the exit of the condenser or if there is very little subcooling at the sight glass, bubbles may be present even when the system is properly charged. If a system is charged to full sight glass, overcharging may be the result, decreasing efficiency. Note: Follow the manufacturer recommendation for superheat and subcooling. 41

42 42 A Thermostatic Expansion Valve (TXV) is designed to maintain a constant superheat. Over charging a TXV will rise subcooling, increases system pressures, and decreases system efficiency. Under charging a TXV will decrease subcooling, increases superheat, decrease system capacity, and lower refrigerant velocity leaving oil in the evaporator. An Automatic Expansion Valve (AXV) is a constant evaporator pressure valve and not normally used in A/C. A fixed orifices is the simplest metering devise made and the most critical to charge. Over charging fixed orifices will lower superheat, increases pressures, decrease efficiency, and flood the compressor with liquid refrigerant. Under charge, the fixed orifices will raise superheat, lower pressure, lower capacity, and lower refrigerant velocity leaving oil in the evaporator. Always refer to the manufacturer recommendations on charging fixed orifices. The process of charging to superheat and subcooling improves an air conditioning system s efficiency, capacity and lessens equipment failures. Always let system stabilize (10 to 20 minutes) after adjusting the charge, this takes time but improves efficiency and capacity. Remember when changing refrigerants all superheat and subcooling adjustments have to be checked and recorded. The procedure of recording adjustments is called Baselining. This procedure not only saves time, money, and aggravation but it is a sign of a professional. Roger D. Holder, CM, BSME, Is the owner of R D Holder Eng in Bakersfield CA, , He also is a Refrigeration and Air Conditioning specialist at National Technical Transfer Inc., P. O. Box 4558 Englewood, CO (800)

43 43 43

Characteristics of Evaporators

Characteristics of Evaporators Characteristics of Evaporators Roger D. Holder, CM, MSME 10-28-2003 Heat or Energy In this paper, we will discuss the characteristics of an evaporator coil. The variance of the operational condenses of

More information

Troubleshooting an Air Conditioning system. R D Holder Eng. Roger D Holder MSME

Troubleshooting an Air Conditioning system. R D Holder Eng. Roger D Holder MSME Troubleshooting an Air Conditioning system R D Holder Eng. Roger D Holder MSME Troubleshooting of an air conditioning system is a step by step procedure. I have found that a 4 step procedure is the best

More information

Refrigeration Basics 101. By: Eric Nelson

Refrigeration Basics 101. By: Eric Nelson Refrigeration Basics 101 By: Eric Nelson Basics Refrigeration is the removal of heat from a material or space, so that it s temperature is lower than that of it s surroundings. When refrigerant absorbs

More information

Why and How we Use Capacity Control

Why and How we Use Capacity Control Why and How we Use Capacity Control On refrigeration and air conditioning applications where the load may vary over a wide range, due to lighting, occupancy, product loading, ambient weather variations,

More information

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES After studying this unit, the reader should be able to explain the purpose of the condenser in a refrigeration system. describe differences

More information

UNDERSTANDING REFRIGERANT TABLES

UNDERSTANDING REFRIGERANT TABLES Refrigeration Service Engineers Society 1666 Rand Road Des Plaines, Illinois 60016 UNDERSTANDING REFRIGERANT TABLES INTRODUCTION A Mollier diagram is a graphical representation of the properties of a refrigerant,

More information

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm. Table V Troubleshooting Checklist for Refrigeration Systems TROUBLE POSSIBLE CAUSE CORRECTIVE MEASURE High condensing pressure. Low condensing pressure. Air or non-condensable gas in system. Inlet water

More information

SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS

SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS 2009 Tecumseh Products Company. All rights reserved. Page 1 of 8 Refrigerant R22 is widely used for residential and commercial air conditioning, as

More information

How To Understand Evaporator

How To Understand Evaporator SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES After studying this unit, the reader should be able to Define high-, medium-, and low-temperature refrigeration.

More information

How To Design A Refrigeration System

How To Design A Refrigeration System AIRAH Refrigeration (in HVAC) Back to Basics For the First Time Terms of Reference What this session is NOT about Detailed Refrigeration Design Detailed analysis of various Refrigants properties Comparison

More information

DESIGN STANDARDS SECTION 23 60 00

DESIGN STANDARDS SECTION 23 60 00 PART 1 - GENERAL 1.01 Work included: A. Piping, tubing and fittings. B. Piping specialties. C. Special duty valves. D. Refrigerants. E. Chillers. F. Refrigerant monitors. 1.02 General requirements: A.

More information

It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents.

It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents. The System Evaluation Manual and Chiller Evaluation Manual have been revised and combined into this new book; the Air Conditioning and Refrigeration System Evaluation Guide. It will be available soon as

More information

Any Service Technician Can Fix It A Good Service Technician Can Figure Out What s Wrong With It.

Any Service Technician Can Fix It A Good Service Technician Can Figure Out What s Wrong With It. I Dave s Statement If the thermostat calls for cooling, and the furnace fan is running properly, and the coil airflow is adequate, and the condenser fan is running properly, and the condenser airflow is

More information

Troubleshooting HVAC/R systems using refrigerant superheat and subcooling

Troubleshooting HVAC/R systems using refrigerant superheat and subcooling Troubleshooting HVAC/R systems using refrigerant superheat and subcooling Application Note Troubleshooting and servicing refrigeration and air conditioning systems can be a challenging process for both

More information

Refrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions

Refrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions Refrigerant Changeover Guidelines R-22 to R-407C Leading the Industry with Environmentally Responsible Refrigerant Solutions Emerson Climate CFC Technologies, Inc. does not advocate the HCFC wholesale

More information

Geothermal Alliance of Illinois. TXVs Theory and Fundamentals John Haug Senior Application Engineer Emerson Climate Technologies - Flow Controls

Geothermal Alliance of Illinois. TXVs Theory and Fundamentals John Haug Senior Application Engineer Emerson Climate Technologies - Flow Controls Geothermal Alliance of Illinois TXVs Theory and Fundamentals John Haug Senior Application Engineer Emerson Climate Technologies - Flow Controls Thermal Expansion Valve Topics Anatomy Operation Terms &

More information

INSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX

INSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX Fan Coil Replacement Coil Kit EBX & EBXX These instructions must be read and understood completely before attempting installation. These instructions covers the installation of replacement coil kit into

More information

Refrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions

Refrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions Refrigerant Changeover Guidelines R-22 to R-407C Leading the Industry with Environmentally Responsible Refrigerant Solutions Copeland does not CFC advocate the wholesale changeover of HCFC HCFC refrigerants

More information

Automobile Air Conditioning Primer

Automobile Air Conditioning Primer Automobile Air Conditioning Primer An air conditioner is basically a refrigerator without the insulated box. It uses the evaporation of a refrigerant, like Freon, to provide cooling. The mechanics of the

More information

Refrigeration Installation 101

Refrigeration Installation 101 Refrigeration Installation 101 Hundreds of Installations Refrigerated Cases 2 Compressor Racks 3 Condensing Units 4 Walk-in Boxes 5 Some were done very well 6 Some had some issues... 7 8 Some seemingly

More information

Chapter 2 P-H Diagram Refrigeration Cycle Analysis & Refrigerant Flow Diagram

Chapter 2 P-H Diagram Refrigeration Cycle Analysis & Refrigerant Flow Diagram Chapter 2 P-H Diagram Refrigeration Cycle Analysis & Refrigerant Flow Diagram Copy Right By: Thomas T.S. Wan 温 到 祥 著 Sept. 3, 2008 All rights reserved Industrial refrigeration system design starts from

More information

Contents and Nomenclature

Contents and Nomenclature DX Coils Contents and Nomenclature Nomenclature... 1 Evaporator Coil Types EN... 2 EF... 2 ER... 2 EJ... 3 EK... 3 Evaporator Construction Connections... 4 Tubing... 4 Headers... 5 Tube Supports... 5 Coil

More information

POLICY BULLETIN Tecumseh Compressor Company Compressor Group

POLICY BULLETIN Tecumseh Compressor Company Compressor Group to Bulk Milk Coolers and Other System Page 1 of 5 Overall reliability can be enhanced if there exists a complete understanding of the features, system design, installation requirements, processing, charging

More information

Engineering Recommendation on: Accumulators Revised 6-17-99 Issued January 10, 1979 Page 1 of 7

Engineering Recommendation on: Accumulators Revised 6-17-99 Issued January 10, 1979 Page 1 of 7 Issued January 10, 1979 Page 1 of 7 Accumulators have long been recognized by the industry as an effective means of maintaining good system balance by storing excess refrigerant as the condenser or evaporator

More information

Solenoid Valves and Their Importance in Refrigeration Systems. October 2007

Solenoid Valves and Their Importance in Refrigeration Systems. October 2007 Solenoid Valves and Their Importance in Refrigeration Systems October 2007 Overview Introduction Solenoid valves play an important role within refrigeration and air conditioning systems, controlling the

More information

ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014

ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014 ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014 Explanation of the refrigeration cycle. Compressors. Benefits and operating characteristics. -Reciprocating

More information

Rusty Walker, Corporate Trainer Hill PHOENIX

Rusty Walker, Corporate Trainer Hill PHOENIX Refrigeration 101 Rusty Walker, Corporate Trainer Hill PHOENIX Compressor Basic Refrigeration Cycle Evaporator Condenser / Receiver Expansion Device Vapor Compression Cycle Cooling by the removal of heat

More information

Skills Canada National Competition Instructions and Competition Details 38 Refrigeration and Air Conditioning / Post - Secondary May 27-30, 2015 -

Skills Canada National Competition Instructions and Competition Details 38 Refrigeration and Air Conditioning / Post - Secondary May 27-30, 2015 - Skills Canada National Competition Instructions and Competition Details / Post - Secondary May 27-30, 2015 - Saskatoon 1. Test Project Details This project is designed to test the range of skills used

More information

Technical Training Associates Presents. Commercial Refrigeration Equipment Servicing Part 1

Technical Training Associates Presents. Commercial Refrigeration Equipment Servicing Part 1 Technical Training Associates Presents Commercial Refrigeration Equipment Servicing Part 1 By Jim Johnson A Practical Approach To The Fundamentals Of Walk-Ins, Reach-In and, Display Cases: Restaurant,

More information

COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers

COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers COMMERCIAL HVAC CHILLER EQUIPMENT Air-Cooled Chillers Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics. They

More information

AIR CONDITIONING TECHNOLOGY

AIR CONDITIONING TECHNOLOGY AIR CONDITIONING TECHNOLOGY PART 9 Water Cooled Condensers & Cooling Towers IN LAST month s article we looked at how Air Cooled Condensers are used to transfer the total heat of rejection from the air

More information

C. starting positive displacement pumps with the discharge valve closed.

C. starting positive displacement pumps with the discharge valve closed. KNOWLEDGE: K1.04 [3.4/3.6] P78 The possibility of water hammer in a liquid system is minimized by... A. maintaining temperature above the saturation temperature. B. starting centrifugal pumps with the

More information

Refrigerant Changeover Guidelines HCFC R-22 to HFC R-404A/R-507. Leading the Industry with Environmentally Responsible Refrigerant Solutions

Refrigerant Changeover Guidelines HCFC R-22 to HFC R-404A/R-507. Leading the Industry with Environmentally Responsible Refrigerant Solutions Refrigerant Changeover Guidelines HCFC R-22 to HFC R-404A/R-507 Leading the Industry with Environmentally Responsible Refrigerant Solutions Copeland does not advocate the wholesale changeover of HCFCs

More information

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety

More information

CONTAMINANT REMOVAL FROM CENTRIFUGAL SYSTEMS

CONTAMINANT REMOVAL FROM CENTRIFUGAL SYSTEMS CONTAMINANT REMOVAL FROM CENTRIFUGAL SYSTEMS BULLETIN 240-10-3 June 2004 Supersedes June 1983 Many centrifugal systems get little maintenance. As a result they operate with the refrigerant highly contaminated

More information

Specific Volume of Liquid (Column 7). The volume per unit of mass in cubic feet per pound.

Specific Volume of Liquid (Column 7). The volume per unit of mass in cubic feet per pound. Steam Tables What They Are How to Use Them The heat quantities and temperature/ pressure relationships referred to in this Handbook are taken from the Properties of Saturated Steam table. Definitions of

More information

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2

More information

Overview. Introduction Cooling Tower Basics Principles of Operation Types of Cooling Towers Common Applications Design Considerations

Overview. Introduction Cooling Tower Basics Principles of Operation Types of Cooling Towers Common Applications Design Considerations Stephen Lowe ASHRAE Hampton Roads Chapter Past President AECOM Design Mechanical Engineering Discipline Manager, Virginia Beach Division Professional Engineer Commonwealth of Virginia, NCEES BSME University

More information

Ground-breaking conversion of critical Data Room WaterChiller from R22 to R422D / MO29

Ground-breaking conversion of critical Data Room WaterChiller from R22 to R422D / MO29 Ground-breaking conversion of critical Data Room WaterChiller from R22 to R422D / MO29 A refrigerant retrofit project, involving the conversion of a large Data Room cooling system from R22 to R422D (DuPont

More information

Heating Water by Direct Steam Injection

Heating Water by Direct Steam Injection Heating Water by Direct Steam Injection Producing hot water by direct steam injection provides a solution where large volumes of hot water at precise temperatures are required, and where energy and space

More information

RS-52 (R428A) RS-52: PHYSICAL PROPERTIES RS-52 R502 Molecular weight 107.5 111.6 Temperature glide o C 0.5 0.2 Boiling point (1 atm)

RS-52 (R428A) RS-52: PHYSICAL PROPERTIES RS-52 R502 Molecular weight 107.5 111.6 Temperature glide o C 0.5 0.2 Boiling point (1 atm) RS-52 (R428A) COMPOSITION % HFC 125 77.5 HFC 143a 20.0 R600a 1.9 R290 0.6 HCFC replacement Temperature glide R22, 502 & interim blends Approximately 0.8 o C Drop-in or long term Both Lubricant MO/AB/POE

More information

Heat Recovery In Retail Refrigeration

Heat Recovery In Retail Refrigeration This article was published in ASHRAE Journal, February 2010. Copyright 2010 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org. This article may not

More information

MAXIMUM HEAT LOAD TEMPERATURE TESTING ( Differential Temperature Testing )

MAXIMUM HEAT LOAD TEMPERATURE TESTING ( Differential Temperature Testing ) MAXIMUM HEAT LOAD TEMPERATURE TESTING ( Differential Temperature Testing ) The Concept Maximum Heat Load Temperature Testing is a powerful air-conditioning diagnostic and evaluation technique. It is also

More information

Low GWP Replacements for R404A in Commercial Refrigeration Applications

Low GWP Replacements for R404A in Commercial Refrigeration Applications Low GWP Replacements for R404A in Commercial Refrigeration Applications Samuel YANA MOTTA, Mark SPATZ Honeywell International, 20 Peabody Street, Buffalo, NY 14210, Samuel.YanaMotta@honeywell.com Abstract

More information

HS-901(A) BASIC STEAM HEATING SYSTEMS

HS-901(A) BASIC STEAM HEATING SYSTEMS HS-901(A) BASIC HEATING SYSTEMS One-Pipe Two-Pipe Basic Steam Heating Systems One-pipe steam heating system EQUALIZER SAFETY FACTOR STATIC HEAD PRESSURE DROP 2" HEATING UNIT 15" DRIP CONNECTION In a one-pipe,

More information

Table Z. Troubleshooting Chart for Air Conditioners. Cause

Table Z. Troubleshooting Chart for Air Conditioners. Cause Troubleshooting Chart for Air Conditioners Type of Unit Complaint Cause With open-type compressor Electric motor will not start Power failure Check circuit for power source Compressor stuck Locate cause

More information

CENTRAL HEAT PUMP AND AIR CONDITIONER INSTALLATION

CENTRAL HEAT PUMP AND AIR CONDITIONER INSTALLATION Technology Fact Sheet CENTRAL HEAT PUMP AND AIR CONDITIONER INSTALLATION Buildings for the 21st Century Buildings that are more energy-efficient, comfortable, and affordable that s the goal of DOE s Office

More information

TRAINING, EXAMINATION AND CERTIFICATION

TRAINING, EXAMINATION AND CERTIFICATION TECHNICAL STANDARDS & SAFETY AUTHORITY TRAINING, EXAMINATION AND CERTIFICATION REFRIGERATION OPERATOR CLASS B CERTIFICATION & EXAMINATION GUIDE REVISED EDITION 2 CERTIFICATIONS PERSUANT TO THE OPERATING

More information

Glossary of Heating, Ventilation and Air Conditioning Terms

Glossary of Heating, Ventilation and Air Conditioning Terms Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment

More information

Testing methods applicable to refrigeration components and systems

Testing methods applicable to refrigeration components and systems Testing methods applicable to refrigeration components and systems Sylvain Quoilin (1)*, Cristian Cuevas (2), Vladut Teodorese (1), Vincent Lemort (1), Jules Hannay (1) and Jean Lebrun (1) (1) University

More information

Vacuum. How It Relates to Refrigeration And Air Conditioning Service

Vacuum. How It Relates to Refrigeration And Air Conditioning Service Vacuum How It Relates to Refrigeration And Air Conditioning Service Moisture In A Refrigeration System Visible Moisture Water Droplets Uncommon, but it can occur Invisible Moisture Water Vapor Found in

More information

5.2. Vaporizers - Types and Usage

5.2. Vaporizers - Types and Usage 5.2. Vaporizers - Types and Usage 5.2.1. General Vaporizers are constructed in numerous designs and operated in many modes. Depending upon the service application the design, construction, inspection,

More information

Refrigeration System Installation & Operation Manual

Refrigeration System Installation & Operation Manual Refrigeration System Installation & Operation Manual Manitowoc Foodservice Walk-In Division 2915 Tennessee Avenue North P.O. Box 550 Parsons, TN 38363 Phone: 800-225-9916 www.manitowocfsusa.com 550001058-3

More information

HVAC Systems: Overview

HVAC Systems: Overview HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct

More information

NFPA31FuelOilPiping 1 Revised 3-1-11

NFPA31FuelOilPiping 1 Revised 3-1-11 NFPA 31 Fuel Oil Piping, Installation and Testing Chapter 8 Fuel Piping Systems and Components 8.1 Scope. This chapter shall apply to piping systems and their components used to transfer fuel oil from

More information

THE PSYCHROMETRIC CHART AND ITS USE

THE PSYCHROMETRIC CHART AND ITS USE Service Application Manual SAM Chapter 630-16 Section 3A THE PSYCHROMETRIC CHART AND ITS USE Psychrometry is an impressive word which is defined as the measurement of the moisture content of air. In broader

More information

Chilled Water HVAC Systems

Chilled Water HVAC Systems Chilled Water HVAC Systems By Ron Prager, Brinco Mechanical Services, Inc. Types of water based systems: There are three types of HVAC systems that utilize water as a heat transfer medium. The first system,

More information

ON-VEHICLE INSPECTION

ON-VEHICLE INSPECTION Sight Glass I11244 ONVEHICLE INSPECTION 1. INSPECT REFRIGERANT VOLUME Observe the sight glass on the liquid tube. AC3 AC22F05 Test conditions: Running engine at 1,500 rpm Blower speed control switch: HI

More information

How much do you know about HVAC? Try testing yourself with the following questions and then take a look at the answers on the following page.

How much do you know about HVAC? Try testing yourself with the following questions and then take a look at the answers on the following page. Demystifying HVAC Test Your HVAC Knowledge By Ron Prager How much do you know about HVAC? Try testing yourself with the following questions and then take a look at the answers on the following page. 1)

More information

VACUUM REFRIGERATION SYSTEMS

VACUUM REFRIGERATION SYSTEMS VACUUM REFRIGERATION SYSTEMS CHILL VACTOR The Croll-Reynolds CHILL-VACTOR is a chiller that uses a vapor flashing process. Water has a pressure-temperature relationship which is its boiling point. If its

More information

Chapter 3.4: HVAC & Refrigeration System

Chapter 3.4: HVAC & Refrigeration System Chapter 3.4: HVAC & Refrigeration System Part I: Objective type questions and answers 1. One ton of refrigeration (TR) is equal to. a) Kcal/h b) 3.51 kw c) 120oo BTU/h d) all 2. The driving force for refrigeration

More information

R407C GUIDELINES FOR UTILIZATION OF. DATE: August 2009 REFERENCE DOCUMENT NO. RD-0005-E GUIDELINES FOR UTILIZATION OF R407C

R407C GUIDELINES FOR UTILIZATION OF. DATE: August 2009 REFERENCE DOCUMENT NO. RD-0005-E GUIDELINES FOR UTILIZATION OF R407C GUIDELINES FOR UTILIZATION OF R407C 2009 Tecumseh Products Company. All rights reserved. Page 1 of 6 After many years of testing and investigation, R407C is recognized as a suitable alternative refrigerant

More information

INSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL

INSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL INSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL MODELS: WA/WL44H WA/WLH WA/WL70*H NOTE: Electrical data presented in this manual supersedes any other data f the above listed models. Bard

More information

Tube Size and Component Selection

Tube Size and Component Selection Application Guide Tube Size and Component Selection for RAUC Split Systems (20 120 Tons) September 2001 SS-APG001-EN Preface This application guide provides refrigerant piping guidelines for Trane Model

More information

How To Clean Water From An Ammonia Refrigeration System

How To Clean Water From An Ammonia Refrigeration System Water Contamination and Water Removal in Industrial Ammonia Refrigeration Systems By Ray Ficker, PE Effects of Water Contamination Water contamination in an industrial ammonia refrigeration system can

More information

PIPES AND TUBES FOR HVAC PIPING AND EQUIPMENT

PIPES AND TUBES FOR HVAC PIPING AND EQUIPMENT PIPES AND TUBES FOR HVAC PIPING AND EQUIPMENT GENERAL INFORMATION 1.1 This section applies to piping systems for chilled water, hot water, condenser water, steam, condensate return, fuel oil, refrigerant

More information

Steam Coil Installation, Operation and Maintenance

Steam Coil Installation, Operation and Maintenance Steam Coil Installation, Operation and Maintenance Guidelines for the installation, operation and maintenance of the Heatcraft brand of steam heating coils manufactured by Luvata in Grenada, MS have been

More information

DIRECT STEAM INJECTION HOT WATER SYSTEMS FOR JACKETED HEATING

DIRECT STEAM INJECTION HOT WATER SYSTEMS FOR JACKETED HEATING By Philip Sutter Pick Heaters, Inc. DIRECT STEAM INJECTION HOT WATER SYSTEMS FOR JACKETED HEATING INTRODUCTION Many process plants currently use steam or hot water to heat jacketed devices such as tanks,

More information

M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A

M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A Bulletin 20-20.2 / July 2012 M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A ➀ ➁ ➂ Model Number Key M 2430 C L 1 - A - ➀ Unit Type M=Modular Nominal Capacity 2430=24000 to 30000

More information

D A T A S H E E T. TX6 Thermo Expansion Valves. Alco Controls TX6. Features. Introduction. Construction

D A T A S H E E T. TX6 Thermo Expansion Valves. Alco Controls TX6. Features. Introduction. Construction ALCO s series of Thermo -Expansion Valves are designed for air conditioning, chillers, rooftops, close control, A/C transportation, heat pumps, industrial cooling process and refrigeration applications.

More information

2. AIRCONDITIONING AND REFRIGERATION

2. AIRCONDITIONING AND REFRIGERATION 2. AIRCONDITIONING AND REFRIGERATION 1. INTRODUCTION Air Conditioning and Refrigeration is an important area where in lot of self-employment opportunities are available. Now a day there is hardly a house

More information

1932 Lexington Houston, Texas 77098-4220 (713) 524-4877. Recommendations for installation of cooling systems

1932 Lexington Houston, Texas 77098-4220 (713) 524-4877. Recommendations for installation of cooling systems 1932 Lexington Houston, Texas 77098-4220 (713) 524-4877 The purpose for this information is to provide a better understanding of the HVAC equipment, components, designs, and installations, of HVAC system

More information

MAC-120HE-01 Air-Cooled Chiller

MAC-120HE-01 Air-Cooled Chiller MAC-120HE-01 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 208/230-1-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-01

More information

Thermostatic expansion valves type TR6 REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Thermostatic expansion valves type TR6 REFRIGERATION AND AIR CONDITIONING. Technical leaflet Thermostatic expansion valves type REFRIGERATION AND AIR CONDITIONING Technical leaflet Thermostatic expansion valves, type Contents Page Introduction........................................................................................3

More information

8. Refrigeration. 4. Liquid. Refrigerant. 4. Liquid Refrigerant. Figure 8.1 Refrigeration system layout (single stage)

8. Refrigeration. 4. Liquid. Refrigerant. 4. Liquid Refrigerant. Figure 8.1 Refrigeration system layout (single stage) 2. Vapor 8. Refrigeration 4. Liquid 3. Condenser 5. Receiver 4. Liquid 1. Compressor 6. Throttling Device 12. Electricity 2. Vapor 8. Recirculator 4. Liquid 7. Liquid/Vapor 7. Liquid/Vapor 10. Warm Air

More information

HOW HVAC WORKS. How HVAC. Works PAGE 1

HOW HVAC WORKS. How HVAC. Works PAGE 1 How HVAC Works PAGE 1 Heat - What is it? Heat is more than a physical concept - it is a feeling. Heat is taught to us at a very young age as a danger to be avoided. Yet, have you ever stopped and thought

More information

New Trends in the Field of Automobile Air Conditioning

New Trends in the Field of Automobile Air Conditioning New Trends in the Field of Automobile Air Conditioning E. Janotkova and M. Pavelek Department of Thermomechanics and Environmental Engineering Brno University of Technology, 61669 Brno, Czech Republic

More information

Air Conditioning 101. STN Presentation AC101

Air Conditioning 101. STN Presentation AC101 Air Conditioning 101 What is Refrigeration? Refrigeration is Cooling by the Removal of Heat Heat is Measured In BTU s A BTU is a British Thermal Unit It is the Amount of Heat to Raise One Pound of Water,

More information

LECTURE 28 to 29 ACCUMULATORS FREQUENTLY ASKED QUESTIONS

LECTURE 28 to 29 ACCUMULATORS FREQUENTLY ASKED QUESTIONS LECTURE 28 to 29 ACCUMULATORS FREQUENTLY ASKED QUESTIONS 1. Define an accumulator and explain its function A hydraulic accumulator is a device that stores the potential energy of an incompressible fluid

More information

Refrigeration Manual. Part 3 - The Refrigeration Load

Refrigeration Manual. Part 3 - The Refrigeration Load Refrigeration Manual Part 3 - The Refrigeration Load FOREWORD The practice of refrigeration undoubtedly goes back as far as the history of mankind, but for thousands of years the only cooling mediums were

More information

Creating Efficient HVAC Systems

Creating Efficient HVAC Systems Creating Efficient HVAC Systems Heating and Cooling Fundamentals for Commercial Buildings Heating, ventilating, and air conditioning (HVAC) systems account for nearly half of the energy used in a typical

More information

National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook

National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook Trainee:... Training Provider:... Year:... Trainee Contact no:... Competency Based Skill Training Logbook Introduction

More information

Refrigerant Changeover Guidelines R-502 to R-402A/R-408A. Leading the Industry with Environmentally Responsible Refrigerant Solutions

Refrigerant Changeover Guidelines R-502 to R-402A/R-408A. Leading the Industry with Environmentally Responsible Refrigerant Solutions Refrigerant Changeover Guidelines R-502 to R-402A/R-408A Leading the Industry with Environmentally Responsible Refrigerant Solutions Copeland does not advocate the wholesale CFC changeover of CFC HCFC

More information

System Trouble Shooting Fault Location REFRIGERATION AND AIR CONDITIONING. Fitters notes

System Trouble Shooting Fault Location REFRIGERATION AND AIR CONDITIONING. Fitters notes System Trouble Shooting Fault Location REFRIGERATION AND AIR CONDITIONING Fitters notes Contents Page Faults on refrigeration systems, general...3 Fault location without the use of instruments...3 Categorisation...3

More information

Scroll Compressor Development for Air-Source Heat Pump Water Heater Applications

Scroll Compressor Development for Air-Source Heat Pump Water Heater Applications Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Scroll Compressor Development for Air-Source Heat Pump Water Heater Applications

More information

Commercial refrigeration has been in the environmental. Refrigerant. as a. Basics Considerations PART 1:

Commercial refrigeration has been in the environmental. Refrigerant. as a. Basics Considerations PART 1: PART 1: CO 2 Commercial refrigeration has been in the environmental spotlight for more than a decade, especially as leakage studies have revealed the true effects of hydrofluorocarbon (HFC) emissions.

More information

Lesson. 11 Vapour Compression Refrigeration Systems: Performance Aspects And Cycle Modifications. Version 1 ME, IIT Kharagpur 1

Lesson. 11 Vapour Compression Refrigeration Systems: Performance Aspects And Cycle Modifications. Version 1 ME, IIT Kharagpur 1 Lesson Vapour Compression Refrigeration Systems: Performance Aspects And Cycle Modifications Version ME, IIT Kharagpur The objectives of this lecture are to discuss. Performance aspects of SSS cycle and

More information

Optimization of Water - Cooled Chiller Cooling Tower Combinations

Optimization of Water - Cooled Chiller Cooling Tower Combinations Optimization of Water - Cooled Chiller Cooling Tower Combinations by: James W. Furlong & Frank T. Morrison Baltimore Aircoil Company The warm water leaving the chilled water coils is pumped to the evaporator

More information

ENGINE COOLING SYSTEM

ENGINE COOLING SYSTEM ENGINE COOLING SYSTEM 1988 Toyota Celica 1987-88 TOYOTA Engine Cooling Systems Celica DESCRIPTION The basic liquid cooling system consists of a radiator, water pump, thermostat, cooling fan, pressure cap,

More information

Flushing and Cleaning the A/C System

Flushing and Cleaning the A/C System Flushing and Cleaning the A/C System Once an AC system has been contaminated or has suffered a failure, the most important part of the AC service to restore the cooling performance to the system = FLUSHING

More information

How Ground/Water Source Heat Pumps Work

How Ground/Water Source Heat Pumps Work How Ground/Water Source s Work Steve Kavanaugh, Professor Emeritus of Mechanical Engineering, University of Alabama Ground Source s (a.k.a. Geothermal s) are becoming more common as the costs of energy

More information

COMMERCIAL HVAC EQUIPMENT. Condensers and Cooling Towers

COMMERCIAL HVAC EQUIPMENT. Condensers and Cooling Towers COMMERCIAL HVAC EQUIPMENT Condensers and Cooling Towers Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics.

More information

Variable Capacity Compressors, a new dimension for refrigeration engineers to explore

Variable Capacity Compressors, a new dimension for refrigeration engineers to explore Variable Capacity Compressors, a new dimension for refrigeration engineers to explore By: Marcos G. Schwarz, VCC Group Leader Corporate Research & Development, EMBRACO SA Abstract: This paper presents

More information

CARING FOR YOUR WATER HEATER

CARING FOR YOUR WATER HEATER http://waterheatertimer.org/troubleshoot-rheem-tankless-water-heater.html Water Heater Inspections CARING FOR YOUR WATER HEATER Venting System (Direct Vent Only) The venting system should be inspected

More information

Equivalents & Conversion Factors 406 Capacity Formulas for Steam Loads 407 Formulas for Control Valve Sizing 408-409

Equivalents & Conversion Factors 406 Capacity Formulas for Steam Loads 407 Formulas for Control Valve Sizing 408-409 Engineering Data Table of Contents Page No. I II Formulas, Conversions & Guidelines Equivalents & Conversion Factors 406 Capacity Formulas for Steam Loads 407 Formulas for Control Sizing 408-409 Steam

More information

Steam System Efficiency. Bill Lumsden Leidos Engineering

Steam System Efficiency. Bill Lumsden Leidos Engineering Steam System Efficiency Bill Lumsden Leidos Engineering Steam System Efficiency Steam System Efficiency Key Take-aways: Review of the properties of ice, water, and steam Learn the basics of steam trap

More information

AABC Specifications for Testing and Balancing HVAC Systems

AABC Specifications for Testing and Balancing HVAC Systems AABC Specifications for Testing and Balancing HVAC Systems The Associated Air Balance Council (AABC) Total System Balancing Specifications for HVAC Testing, Balancing and Performance Verification TOTAL

More information

REMOTE AIR-COOLED CONDENSERS. Installation and Maintenance Data. Models 1-26. Bulletin H-IM-73A June 2000 Part Number 90800801.

REMOTE AIR-COOLED CONDENSERS. Installation and Maintenance Data. Models 1-26. Bulletin H-IM-73A June 2000 Part Number 90800801. Bulletin H-IM-73A June 2000 Part Number 90800801 Replaces H-IM-73 and H-IM-74 REMOTE AIR-COOLED CONDENSERS Models 1-26 Installation and Maintenance Data Table of Contents Inspection Installation... 3-4

More information

HVAC Calculations and Duct Sizing

HVAC Calculations and Duct Sizing PDH Course M199 HVAC Calculations and Duct Sizing Gary D. Beckfeld, M.S.E., P.E. 2007 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com An

More information

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating

More information