Fireplace / Chimney Code Requirements CABO One and Two Family Dwelling Code
|
|
- Richard Bridges
- 7 years ago
- Views:
Transcription
1 Q: How far does a chimney have to extend above a roof? Section 1001 Masonry Chimneys ermination. Chimneys shall extend at least 2 feet (610 mm) higher than any portion of the building within 10 feet (3048 mm), but shall not be less than 3 feet (914 mm) above the point where the chimney passes through the roof. 3'-0" min 10'-0" min 24" min 10'-0" min 24" min
2 Q: What are the requirements for clearances from combustible framing members to masonry fireplaces/chimneys? Section 1001 Masonry Chimneys Chimney clearances. A portion of a masonry chimney located in the interior of the building or within the exterior wall of the building shall have a minimum air space clearance to combustibles of 2 inches (51 mm). Chimneys located entirely outside the exterior walls of the building, including chimneys that pass through the soffit or cornice, shall have a minimum air space clearance of 1 inch (25 mm). he air space shall not be filled, except to provide firestopping in accordance with Section Exception: Masonry chimneys equipped with a chimney lining system listed and labeled for use in chimneys in contact with combustibles in accordance with UL 1777, and installed in accordance with the manufacturer s installation instructions, are permitted to have combustible material in contact with their exterior surfaces. However, this shall not eliminate the requirement for noncombustible firestopping in accordance with Section Section 1003 Masonry Fireplaces Fireplace clearance. Wood or combustible framing shall not be placed within 2 inches (51 mm) of the outside face of a masonry fireplace and not less than 6 inches (153 mm) from the inside surface of the nearest flue lining. Wood framing and other combustible material shall not be placed within 2 inches (51 mm) of the back surface of a masonry fireplace.
3 Q: What are the requirements for hearths and hearth s? Section 1003 Masonry Fireplaces material. s shall be of masonry or concrete at least 2 inches (51 mm) thick and supported by noncombustible materials and reinforced to carry its own weight and all imposed loads. he hearth shall be readily distinguishable from the surrounding floor. Combustible forms and centers used during the construction of the hearth shall be removed after the construction is complete. Exception: When the bottom of the firebox opening is raised at least 8 inches (203 mm) above the top of the hearth, a hearth of not less than 3/8 inch thick (9.5 mm) brick, concrete, stone, tile or other approved noncombustible material may be used he hearth and the hearth shall extend a minimum of 36 inches (914 mm) from the back of the firebox to the end of the hearth. s shall extend at least 16 inches (406 mm) in front of and at least 8 inches (203 mm) beyond each side of the fireplace opening. Where the fireplace opening is 6 square feet (0.557 m 2 ) or larger, the hearth shall extend at least 20 inches (508 mm) in front of and at least 12 inches (305 mm) beyond each side of the fireplace opening. Less than 6 sq. ft. 8" min 16" min 8" min slab thickness 20" min 36" min. Masonry or concrete 2" min. thickness (self supporting) 6 sq. ft. or more Brick Firebox Sectional Side View on Wood Floor 12" min 20" min 12" min
4 Q: What are the required clearances to combustible woodwork and mantels around a fireplace opening? Section 1003 Masonry Fireplaces Combustible materials. Woodwork or other combustible materials shall not be placed within 6 inches (153 mm) of a fireplace opening. Combustible material within 12 inches (305 mm) of the fireplace opening shall not project more than 1/8 inch (3.2 mm) for each 1 inch (25 mm) distance from such opening. CROSS SECION OF MANEL Also applies to mantel above fireplace opening. 2" clearance min. wallboard Masonry Wood studs wallboard Wood trim or other combustible material Fireplace opening Projection line Combustible trim shall not extend beyond projection line when it is within 6-12" of fireplace opening. 1/8" projection of combustible material permitted for each inch distance from fireplace opening. 3/4" max projection at 6" from fireplace opening progresses to: 1 1/2" max projection at 12" from fireplace opening Drawings are for illustrative purposes only. Do not scale. 6" min clearance from opening. No combustibles permitted Front of mantel 12" from opening Beyond 12 " combustible materials not regulated.
5 Q: Does a fireplace require an exterior air supply? Yes Section 1006 Exterior Air Supply Exterior air. Factory-built or masonry fireplaces covered in this chapter shall be equipped with an exterior air supply to assure proper fuel combustion Exterior air intake. he exterior air intake shall be capable of providing all combustion air from the exterior of the dwelling or from spaces within the dwelling ventilated with outside air, such as crawl or attic space. he exterior air intake shall not be located within the garage of the dwelling. he exterior air intake shall be covered with a corrosion-resistant screen of 1/4 inch (6.4 mm) mesh Passageway. he combustion air passageway shall be a minimum of 6 square inches (3870 mm 2 ) and not more than 55 square inches (0.035 m 2 ) Inlet. he exterior air inlet is permitted to be located in the sides of the firebox chamber, or within 24 inches (610 mm) of the firebox opening on or near the floor. he inlet shall be closable and designed to prevent burning material from dropping into concealed combustible spaces.
6 Q: What are the requirements for factory built fireplaces? Section 1004 Factory-Built Fireplaces Installation. Factory-built fireplaces that consist of a firechamber assembly, one or more chimney sections, a roof assembly and other parts as tested and listed as an assembly by an approved agency may be installed when complying with all the following provisions: 1. he fire chamber assembly is installed to provide clearance to combustible materials not less than set forth in the listing. 2. he chimney sections are installed to provide clearance to combustible material not less than specified in the listing and if the fireplace chimney extends through floors and ceilings, factory-furnished firestops or firestop spacers shall be installed. Portions of chimneys which extend through rooms or closets are to be enclosed to avoid personal contact, contact of combustible material, and damage to the chimney. 3. s shall not be less than 3/8-inch thick (9.5 mm) asbestos, hollow metal, stone, tile or other approved noncombustible material. Such hearth s may be placed on combustible subflooring or finish flooring. he hearth shall be readily distinguished from the surrounding floor. 4. s shall extend not less than 16 inches (406 mm) in front of and at least 8 inches (203 mm) beyond both sides of the fireplace opening. 5. Factory-built fireplaces shall be installed in accordance with their listing and the manufacturer's installation instructions. 6. he supporting structure for a hearth shall be at the same level as the supporting structure for the fireplace unit unless otherwise authorized by the listing. Section 1002 Factory-Built Chimneys General. Factory-built chimneys shall conform to the conditions of their listing and the manufacturer's instructions. Factory-built chimneys that are listed as part of an assembly with factory-built fireplaces shall conform to Section
7 Q: What are the requirements for factory built fireplace stoves (wood burning stoves)? Section 1005 Factory-Built Fireplace Stoves General. Factory-built fireplace stoves, consisting of a freestanding fire chamber assembly, that have been tested and are listed by a nationally recognized testing laboratory, shall be installed in accordance with the requirements of said listing and the manufacturer's instructions. he supporting structure for a hearth shall be at the same level as the supporting structure for the fireplace unit.
8 Q: What are the minimum requirements for corbeling of masonry chimney walls? Section Masonry Chimneys Re Section Corbeling. Corbeling of masonry chimney walls is permitted within certain limitations. When the corbel is used for the support of a chimney built into the wall, the maximum projection for each course is limited to the lesser of one-half the unit height or one-third the unit depth, as shown in Figures 604.3a and a. Masonry chimneys must not be corbeled more than 6 inches (153 mm) from a wall or foundation, nor be corbeled from a wall or foundation which is less than 12 inches (305 mm) in thickness, unless the corbel projects equally on both sides, as shown in Figure b. D H Max. corbel 1/3 D or 1/2 H of unit, whichever is less Fig a Masonry Corbeling Limitations Per Course D (depth) Fireclay liner Airspace 4" solid masonry units Fireclay liner Airspace 4" solid masonry units 1/2 H or 1/3 D, whichever is less H (height) 12" min. 6" max. corbel t 1/2 t max. corbel Fig a Individual Corbels Fig b Corbeling from Foundation Wall
9 Section 1003 Masonry Fireplaces See able on next page for dimensions and requirements Bond beam K Mortar cap 2'-0" min. Masonry cap Brick E Block P Effective flue area R Clearance 10'-0" min. L Bond beam K Flashing 8" Width of fireplace opening B Plan view Flue lining S Anchorage Mortar cap Bond beam K Bond beam K J Horizontal reinforcing ties S Detail for full masonry wall Anchorage 2'-0" min. Clearance R 10'-0" min. Flashing Horizontal reinforcing ties Vertical reinforcing 1 1/2" min. grout between 4" concrete masonry and clay flue lining J H Wall M thickness N Parge with mortar Veneer tie clearance R S Anchorage 2 1/2" bolts each strap Anchor strap Flue liner 6" min. G Smoke chamber H Vertical reinforcing E A Firebox wall thickness slab thickness Ash dump optional clean out Footing width 1/2" min. L Lintel 20" min firebrick 8" min. F C D slab reinforcing hermal distance 21" min. Fireplace opening height 18" min. grade Measure height of freestanding fireplace from top of footing R 1/2" min. Footing depth For SI: 1 inch = 25.4 mm Clearance Lintel C F 20" min. 8" min. Horizontal reinforcing ties 4" thick masonry units Vertical reinforcing 20" lap if spliced to footing dowels Firebox wall thickness Bars in concrete footing J H E Footing width 6" around free standing fireplace Natural grade Brick Firebox and Chimney Sectional Side View on Wood Floor Figure Fireplace and Chimney Details Brick Firebox and Block Chimney Sectional Side View on Concrete Slab Drawings are for illustrative purposes only. Do not scale or submit as plans for permit. 1
10 Section 1003 Masonry Fireplaces ABLE REQUIREMENS FOR MASONRY FIREPLACES AND CHIMNEYS IEM LEER 1 REQUIREMENS slab thickness A 4" B 8" fireplace opening < 6 sq. ft. (each side of opening) 12" fireplace opening 6 sq. ft. C 16" fireplace opening < 6 sq. ft. (front of opening) 20" fireplace opening 6 sq. ft. slab reinforcing D Reinforced to carry its own weight and all imposed loads. hickness of wall of firebox E 10" solid brick or 8" where a firebrick lining is used. Joints in firebrick 1/4" max. Distance from top of opening to throat F 8" Smoke chamber edge of shelf G Rear wall - thickness 6" Front and sidewall - thickness 8" Chimney H Four No. 4 full length bars for chimney up to 40" wide. Vertical reinforcing 2 Add two No. 4 bars for each additional 40" or fraction of width or each additional flue. Horizontal reinforcing 2 J 1/4" ties at 18" and two ties at each bend in vertical steel. Bond beams K No specified requirements. Fireplace lintel L Noncombustible material. Walls with flue lining M Brick with grout around lining or 1/2" airspace 4" min. from flue lining to outside face of chimney. Walls with unlined flue N 8" solid masonry. Distances between adjacent flues See Section Effective flue area (based on area P See Section of fireplace opening) Clearances R Wood frame See Sections and Combustible material See Section Above roof 2' at 10' Anchorage 2 S Strap 3/16" x 1" Number 2 Embedment into chimney 12" hooked around outer bar w/6" ext. Fasten to 4 joists Bolts wo 1/2" diameter. Footing hickness 12" min. Width 6" each side of fireplace wall. For SI: 1 inch = 25.4 mm, 1 foot = mm. 1 2 he letters refer to Figure Not required in Seismic Zone 0, 1 or 2. 2
CHIMNEYS AND FIREPLACES
CHAPTER 10 CHIMNEYS AND FIREPLACES > > Pursuant to ORS 215.730, if a single-family dwelling located on forest-zoned lands has a chimney or chimneys, each chimney shall have a spark arrester. SECTION R1001
More information780 CMR 60.00 CHIMNEYS, FIREPLACES AND SOLID FUEL-BURNING APPLIANCES
780 CMR 60.00 CHIMNEYS, FIREPLACES AND SOLID FUEL-BURNING APPLIANCES 780 CMR 6001 MASONRY CHIMNEYS 6001.1 General. Masonry chimneys shall be constructed, anchored, supported and reinforced as required
More informationCHIMNEYS AND FIREPLACES
CAPER 10 CIMNEYS AND FIREPLACES SECION R1001 MASONRY CIMNEYS R1001.1 General. Masonry chimneysshall be constructed, anchored, supported and reinforced asrequired in thischapterand the applicable provisions
More informationTFL CUSTOM FIREPLACES WITH MASONRY BRICK LININGS. standard INSTALLATION SPECIFICATION INTO TIMBER FRAMING
6.CW.1A TFL CUSTOM FIREPLACES WITH MASONRY BRICK LININGS wood or gas standard INSTALLATION SPECIFICATION INTO TIMBER FRAMING The Fireplace Ltd is able to design and fabricate custom brick open masonry
More informationRepair of Earthquake-Damaged Masonry Fireplace Chimneys SOUTH NAPA EARTHQUAKE RECOVERY ADVISORY
Repair of Earthquake-Damaged Masonry Fireplace Chimneys SOUTH NAPA EARTHQUAKE RECOVERY ADVISORY Purpose and Intended Audience The August 24, 2014 South Napa Earthquake has again served as a reminder that
More informationExcerpts from the Canadian National Building Code (NBC)
Excerpts from the Canadian National Building Code (NBC) Reproduced here with Permission of the Copyright Owner, the National Research Council of Canada, Institute for Research in Construction. For more
More informationCertification: Building Plans Examiner. Exam ID: B3
Certification: Building Plans Examiner Exam ID: B3 Scope: A Building Plans Examiner will be responsible for reviewing submitted plans to determine if they meet the requirements of the various Building
More informationSuperform Products Ltd.
TYPICAL CORNER REINFORCING NOTE : SEE ENGINEERED REBAR SCHEDULES SUPPLIED BY THE MANUFACTURER STEEL REINFORCEMENT WALL CORNER 90 Copyright 2012 Sept. 2012 5.1.1 Rebar Spacing 6" 12" Max. Load LB./FT. 2000
More informationCOMMONLY USED RESIDENTIAL BUILDING CODES
COMMONLY USED RESIDENTIAL BUILDING CODES INTERNATIONAL RESIDENTIAL CODE (2009) form revised 5/10 FOUNDATION 1. DESIGN OF FORMWORK. Section 1906.1 IBC 2009, Section R404.1.2.3.6 IRC 2009, ACI 318 Section
More information1997 Uniform Administrative Code Amendment for Earthen Material and Straw Bale Structures Tucson/Pima County, Arizona
for Earthen Material and Straw Bale Structures SECTION 70 - GENERAL "APPENDIX CHAPTER 7 - EARTHEN MATERIAL STRUCTURES 70. Purpose. The purpose of this chapter is to establish minimum standards of safety
More informationCarroll County Bureau of Permits and Inspection Residential Code Compliance Guidelines
Carroll County Bureau of Permits and Inspection Residential Code Compliance Guidelines The following list of code requirements is intended to assist you in complying with the Code of Public Local Laws
More informationResidential Deck Safety, Construction, and Repair
Juneau Permit Center, 4 th Floor Marine View Center, (907)586-0770 This handout is designed to help you build your deck to comply with the 2006 International Residential Building code as modified by the
More informationRESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS
RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS The following guidelines are intended to assist with the permit acquisition process with regard to Plumbing Alterations. Not all information, or additional
More informationRESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings
More informationPOST AND FRAME STRUCTURES (Pole Barns)
POST AND FRAME STRUCTURES (Pole Barns) Post and frame structures. The following requirements serve as minimum standards for post and frame structures within all of the following structural limitations:
More informationFIRE AND SMOKE PROTECTION FEATURES
CHAPTER 7 FIRE AND SMOKE PROTECTION FEATURES SECTION 70 GENERAL 70. Scope. The provisions of this chapter shall govern the materials, systems and assemblies used for structural fire resistance and fire-resistance-rated
More information4. ANCHOR BOLTS AND STRAPS a. ½" anchor bolts shall be embedded 7" into concrete a maximum of 6' on center and 12" from corners and ends of plates.
GENERAL CODE REQUIREMENTS (BASEMENTS) 1. FOOTINGS a. Footings shall be below frost line depth (42"). b. For an 8" foundation wall, footings shall be no less than 8" deep and 16" wide. c. Steel reinforcement
More informationNCMA TEK CONCRETE MASONRY FOUNDATION WALL DETAILS. TEK 5-3A Details (2003)
NCMA TEK National Concrete Masonry Association an information series from the national authority on concrete masonry technology CONCRETE MASONRY FOUNDATION WALL DETAILS TEK 5-3A Details (2003) Keywords:
More informationThis handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances.
Basement Finishing Guide Community Development Department Building Inspections Division 5200 85 th Avenue North / Brooklyn Park, MN 55443 Phone: (763) 488-6379 / Fax: (763) 493-8171 6/15 www.brooklynpark.org
More informationGas Stoves. H15-10 Direct Vent Gas Stove. Model H15-NG10 H15-LP10. Approved Venting Systems
H15-10 Direct Vent Gas Stove Model H15-NG10 H15-LP10 Fuel Type Natural Gas Propane Minimum Supply Pressure 5.0 W.C. (1.25 kpa) 12.0 W.C. (3.00 kpa) Manifold Pressure - High 3.8 W.C. (0.95 kpa) 11 W.C.
More informationInstallation Instructions
Installation Instructions Pedestal Models FS 500 LE FS 800 LE Insert Models IS 500 LE IS 800 LE Pecan Engineering Pty Ltd 13 Acorn Road Dry Creek South Australia 5094 Email info@pecan-eng.com.au Phone:
More informationFinal inspections are completed by site visit only. Access to fenced yards shall be planned.
ROOFING RESIDENTIAL BUILDING INSPECTIONS DEPARTMENT www.ci.blaine.mn.us This handout is intended only as a guide and is based in part on the 2015 Minnesota State Building Code, Blaine City ordinances,
More informationFIRE AND SMOKE PROTECTION FEATURES
CHAPTER 7 FIRE AND SMOKE PROTECTION FEATURES SECTION 70 GENERAL 70. Scope. The provisions of this chapter shall govern the materials, systems and assemblies used for structural fire resistance and fire-resistance-rated
More informationCHAPTER 6 CONSTRUCTION TYPES
CHAPTER 6 CONSTRUCTION TYPES SECTION 601 GENERAL 601.1 Scope. Provisions of this chapter shall govern the classification of construction type by materials and fire resistance of its elements and the use
More informationFoundations 65 5 FOUNDATIONS. by Richard Chylinski, FAIA and Timothy P. McCormick, P.E. Seismic Retrofit Training
Foundations 65 5 FOUNDATIONS by Richard Chylinski, FAIA and Timothy P. McCormick, P.E. 66 Foundations Foundations 67 FOUNDATIONS Let's assume that the retrofit has been done correctly from the roofline
More informationMANUFACTURED HOUSING USED AS DWELLINGS
MANUFACTURED HOUSING USED AS DWELLINGS SECTION AE101 SCOPE AE101.1 General. These provisions shall be applicable only to a manufactured home used as a single dwelling unit and shall apply to the following:
More informationBUILDING PERMIT SPECIFICATIONS
BUILDING PERMIT SPECIFICATIONS The below noted requirements are based upon La Plata County Building Code. These specifications are not intended as a complete set of requirements, but are intended to provide
More informationHCD DSA OSHPD 1 2 1/AC AC SS SS/CC 1 2 3 4 2013 CALIFORNIA BUILDING CODE 199
CALIFORNIA BUILDING CODE MATRIX ADOPTION TABLE CHAPTER 7 FIRE AND SMOKE PROTECTION FEATURES (Matrix Adoption Tables are non-regulatory, intended only as an aid to the user. See Chapter for state agency
More informationState of Connecticut Department of Public Health RADON PROGRAM
State of Connecticut Department of Public Health RADON PROGRAM Scope The Connecticut Department of Public Health (DPH) Radon Program is providing this information for contractors who decide to build radon
More informationPRE-ASSEMBLED INSTALLATION INSTRUCTIONS FOR PACB SERIES COAL FIRED OVENS
PRE-ASSEMBLED INSTALLATION INSTRUCTIONS FOR PACB SERIES COAL FIRED OVENS OVENS MANUFACTURED BY: EARTHSTONE OVENS-6717 SAN FERNANDO RD GLENDALE CA 91201 TELEPHONE: 800-840-4915 818-553-1134 FAX: 818-553-1133
More information(This report is endorsed) Industrivej 20, 9900 Frederikshavn, Danmark
Spectrum Laboratories Ltd is accredited by International Accreditation New Zealand (formerly Telarc). The tests reported herein have been performed in accordance with the terms of our accreditation. This
More informationResidential Decks. Planning and Development Services Department
Building Safety Division 8500 Santa Fe Drive Overland Park, KS 66212 (913) 895-6225 Fax (913) 895-5016 Email: permitservices@opkansas.org Planning and Development Services Department Residential Decks
More informationMark Cramer Inspection Services, Inc.
Mark Cramer Inspection Services, Inc. 492 Twentieth Avenue, Indian Rocks Beach, FL 34635-2970 (727) 595-4211 Fax (727) 596-7583 Certified Member #12085 American Society of Home Inspectors Construction
More informationSingle Family Residential Basement Finish
How to Use This Guide Building Guide Pottawattamie County Planning & Development Department Building & Safety Division Single Family Residential Basement Finish Provide two (2) sets of plans and complete
More informationICC-ES Evaluation Report Reissued September, 2010 This report is subject to re-examination in one year.
ICC-ES Evaluation Report ESR-2270 Reissued September, 2010 This report is subject to re-examination in one year. www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council
More informationISO Types 1-6: Construction Code Descriptions
ISO 1 Frame (combustible walls and/or roof) Class 1B Buildings where the exterior walls are wood or other combustible materials, including construction where the combustible materials are combined with
More informationAcross America. Wood & Coal Brochure
Across America Wood & Coal Brochure Rev. Sep. 2011 Bay Series... A series of well built high heat performers featuring decorative side windows and full view glass door with airwash system to help keep
More informationThe better way to build TM. Installation Manual. FOUNDATION SIPs & FROST WALLS SIPs
The better way to build TM Installation Manual FOUNDATION SIPs & FROST WALLS SIPs February 2016 PWF FOUNDATION & FROST WALL SIPs Installation Manual Table of Contents Topics General Requirements...................................
More informationGuidelines for Earthquake Bracing Residential Water Heaters
Guidelines for Earthquake Bracing Residential Water Heaters Department of General Services Division of the State Architect In accordance with the Health and Safety Code Section 19215, the Division of the
More informationGuidelines for Earthquake Bracing of Residential Water Heaters
Guidelines for Earthquake Bracing of Residential Water Heaters Department of General Services Division of the State Architect 1102 Q Street, Suite 5100 Sacramento, CA 95814 Phone: (916) 324-7099 Fax: (916)
More informationCity of Tucson and Pima County Arizona Building Code Appendix Chapter 72 Straw-Bale Structures
City of Tucson and Pima County Arizona Building Code Appendix Chapter 72 Straw-Bale Structures SECTION 7201 - PURPOSE The purpose of this appendix chapter is to establish minimum prescriptive standards
More informationThe Lambton County Homeowner's BUILDING PERMIT INFORMATION GUIDE
The Lambton County Homeowner's BUILDING PERMIT INFORMATION GUIDE BUILDING SERVICES DEPARTMENT 789 Broadway Street, Box 3000 Wyoming, ON N0N 1T0 Telephone: 519 845-0801 Toll-free: 1-866-324-6912 Fax: 519
More informationHURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES
HURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES 101 Retrofits Required. Pursuant to Section 553.844 553.884, Florida Statutes, strengthening of existing site-built,
More informationSTANDARD OPEN PATIO COVER
STANDARD OPEN PATIO COVER BUILDING & SAFETY DIVISION 201 E. LA HABRA BLVD. LA HABRA, CA 90631 62-90-9710 Call Before You Dig 1-800-227-2600 PLEASE NOTE: This information Bulletin is made available to assist
More informationTYPICAL PATIO COVERS 111
City of Laguna Niguel Building Division 30111 Crown Valley Pkwy Laguna Niguel, CA 92677 (949) 362-4360 FAX 362-4369 www.cityoflagunaniguel.org TYPICAL PATIO COVERS 111 PLEASE NOTE: This information Bulletin
More informationAdditions and Alterations
Additions and Alterations Addition and alteration construction is a miscellaneous grouping of home improvement and renovation projects that are generally geared toward the enhancement of an existing principal
More informationChapter. Restoration of Damaged Structures
5 Chapter Restoration of Damaged Structures Bringing back a damaged structure to its pre-earthquake state and original strength is called restoration. This is the first step of building rehabilitation.
More informationResidential Inspection Guidelines
Residential Inspection Guidelines 201 Pre-Pour Foundation Dimensions Building Location Certificate - if required in the building consent Construction and Advice Notes Check the building dimensions against
More informationChapter 6 ROOF-CEILING SYSTEMS
Chapter 6 ROOF-CEILING SYSTEMS Woodframe roof-ceiling systems are the focus of this chapter. Cold-formed steel framing for a roof-ceiling system also is permitted by the IRC but will not be discussed;
More informationMAJESTIC. OUTDOOR / INDOOR WOOD FIREPLACES Model: ODSR36A OWNERS INSTALLATION & OPERATING INSTRUCTIONS. KEEP THESE INSTRUCTIONS FOR FUTURE REFERANCE.
MAJESTIC OUTDOOR / INDOOR WOOD FIREPLACES Model: ODSR36A OWNERS INSTALLATION & OPERATING INSTRUCTIONS. KEEP THESE INSTRUCTIONS FOR FUTURE REFERANCE. CONTENTS Part 1: Safety Information Part 2: Installation
More informationTechnical Notes 3B - Brick Masonry Section Properties May 1993
Technical Notes 3B - Brick Masonry Section Properties May 1993 Abstract: This Technical Notes is a design aid for the Building Code Requirements for Masonry Structures (ACI 530/ASCE 5/TMS 402-92) and Specifications
More informationRESIDENTIAL FOUNDATION GUIDELINE Johnson County, KS
RESIDENTIAL FOUNDATION GUIDELINE Johnson County, KS Johnson County Building Officials Association January 2008 Residential Foundation Guideline Foundation designs for one-and two-family dwellings may use
More informationLAYING BLOCK AND BRICK
LAYING BLOCK AND BRICK Products highlighted in this section: SAKRETE Type N Mortar Mix SAKRETE Type S Mortar Mix Brick And Block Laying Basics The first step in building a brick or block wall is to construct
More informationCOMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression
More informationFoundation Experts, LLC Specializes in Foundation Repair and Waterproofing
1 Most basements show some signs of leaking and cracking. Through the years, problems with water, poor soils, grading, drainage and possible settling affect the integrity of a basement. Being able to recognize
More informationPre-Drywall Inspection Report
SM MEDALLION INSPECTIONS helping people make informed decisions Pre-Drywall Inspection Report 5657 Garden Valley Place Milton, Georgia 30024 Prepared for Betsy and Paul Dougherty January12, 2015 Medallion
More information2009 IECC Update. Scope. Content. International Energy Conservation Code
2009 IECC Update International Energy Conservation Code Scope The code applies to both residential and commercial buildings. In the code, the United States is divided into eight climate zones which are
More informationCALIFORNIA BUILDING CODE
CALIFORNIA BUILDING CODE NONSTRUCTURAL DESIGN REQUIREMENTS This section contains portions of the California Building Code which relate to basic minimum nonstructural design requirements for a residence.
More informationChapter 3 FOUNDATIONS AND FOUNDATION WALLS
Chapter 3 FOUNDATIONS AND FOUNDATION WALLS This chapter discusses foundations and foundation walls constructed using the two most common foundation materials concrete and masonry. Although the IRC permits
More informationUncovered Decks & Porches
Uncovered Decks & Porches Building Guides for Homeowners Why Do I need a Permit? D I D Y O U K N O W? As owner-builder you are the responsible party of record on such a permit. If your work is being performed
More informationINTERNATIONAL RESIDENTIAL CODE 2006 Third Edition
WASHINGTON STATE BUILDING CODE CHAPTER 51-51 WAC INTERNATIONAL RESIDENTIAL CODE 2006 Third Edition Washington State Building Code Council Copies of the State Building Codes and complete copies of the 2006
More informationIntroduction...COMB-2 Design Considerations and Examples...COMB-3
SECTION DIRECTORY General Information Introduction...COMB-2 Design Considerations and Examples...COMB-3 Combination Assembly Recommendations and Limitations Composite Configurations...COMB-4 Typical Sealant
More informationChapter 36 - STRAW BALE CONSTRUCTION SECTION 3601 - PURPOSE. SECTION 3602 - SCOPE. SECTION 3603 - DEFINITIONS.
Austin City Code - Volume II TITLE 25 LAND DEVELOPMENT\CHAPTER 25-12 TECHNICAL CODES\ARTICLE 1: UNIFORM BUILDING CODE\25-12-3 LOCAL AMENDMENTS TO THE BUILDING CODE Chapter 36 - STRAW BALE CONSTRUCTION
More informationPDmB, Inc. Definitions
Page 1 of 11 Definitions S Satisfactory Meets industry standards for proper material and installation NP Not Present Condition or item was not present at time of inspection NI Not Inspected Condition or
More informationBasic Requirements for Residential Plan Review _
Basic Requirements for Residential Plan Review _ Below you will find the basic requirements for your plan submittal. General: Drawn to scale Plan Size minimum: 9 x 12 Designer, Engineer, or Architect name,
More informationLIFE SAFETY UPDATE. FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc.
LIFE SAFETY UPDATE FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc. The purpose of this update is as follows: Remind all state
More information2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property
2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property A brief summary of the most used code references for residential wiring State of Idaho Division of Building Safety Electrical
More informationThe replacement or modification of existing windows shall comply with the following requirements:
City of La Habra Heights Building Division 1245 N. Hacienda Road La Habra Heights, CA 90631 Office: (562) 694-6302 ext. 228 Fax: (562) 690-5010 WINDOW REPLACEMENT 2010 CALIFORNIA RESIDENTIAL CODE (CRC)
More informationMUNICODE SERVICES LTD.
The Preserved Wood Foundation Guide MUNICODE SERVICES LTD. Prepared by MuniCode Services Ltd. Outline and Restrictions of this Guide The following information required for the construction of Preserved
More informationDEFAULT HEAT LOSS COEFFICIENTS
DEFAULT HEAT LOSS COEFFICIENTS SECTION A101 GENERAL REQUIREMENTS A101.1 Scope. The following defaults shall apply to Chapter 4 of both the (RE) and (CE) sections of the IECC. This chapter includes tables
More informationSPECIFICATION & INSTALLATION GUIDE FOR MASPORT LE4000 PROVINCIAL INSERT FIRE, NEW ZEALAND MODEL
SPECIFICATION & INSTALLATION GUIDE FOR MASPORT LE4000 PROVINCIAL INSERT FIRE, NEW ZEALAND MODEL Manufactured in New Zealand by: GLEN DIMPLEX AUSTRALASIA LIMITED PO Box 58-473 Botany Auckland 2163 Ph: 0800
More informationSample Drawing Package for One and Two Family Dwelling Applications
Sample Drawing Package for One and Two Family Dwelling Applications For a full list of submission requirements, refer to the relevant checklist for your application found on our website: http://vancouver.ca/home-property-development/application-forms-and-checklists.aspx
More informationHVAC Code Requirements
one and two family dwellings? Answer: SECTION 2001: GENERAL 2001.1 Air supply. Fuel-burning equipment shall be provided with a supply of air for fuel combustion, draft hood dilution and ventilation of
More informationFIRE-RESISTANCE-RATED CONSTRUCTION
CHAPTER 7 FIRE-RESISTANCE-RATED CONSTRUCTION SECTION 70 GENERAL 70. Scope. The provisions of this chapter shall govern the materials and assemblies used for structural fire resistance and fire-resistance-rated
More informationResidential Foundations and Basements
Residential Foundations and Basements Disclaimer All of the following information is based on the 2006 International Residential Code with Kentucky Amendments. As some information is paraphrased, article
More informationChapter 3 Pre-Installation, Foundations and Piers
Chapter 3 Pre-Installation, Foundations and Piers 3-1 Pre-Installation Establishes the minimum requirements for the siting, design, materials, access, and installation of manufactured dwellings, accessory
More informationFig. 2 WALL-TO-WALL PANEL CONNECTIONS CORNER WALL CONNECTION
SIPS SCREWS WITH MINIMUM 1" PENETRATION IN WOOD MEMBER IN SIP WALL PANEL CONNECTED TO @ 24" O.C. MAXIMUM OUTSIDE SKIN EACH SIDE OF FRAMING TYP. AS RECOMMENDED BY FOAM CORE AS EACH SIDE OF FRAMING TYP.
More informationBasement Development Construction requirements for the development of basements in residential dwellings.
PLANNING, PROPERTY AND DEVELOPMENT DEPARTMENT Basement Development Construction requirements for the development of basements in residential dwellings. June 2009 contents GENERAL INFORMATION 3 BUILDING
More informationThe Savannah Steel Series Wood Burning Stoves and Inserts
The Savannah Steel Series Wood Burning Stoves and Inserts The Savannah Steel Series Wood Burning Stoves The wood burning steel stove adds warmth and elegance to any décor. Designed with the latest wood
More informationCustom 30 x 20-8 Garage Plan Plan #g233 By SDS-CAD Specialized Design Systems
P O Box 34 Mendon, Utah Custom 30 x 20-8 Garage Plan Plan #g233 By Page 1 Title Page Page 2 Main Floor Plan Page 3 Foundation Plan Page 4 Elevation Views Page 5 Framing and Details Page 6 Typical Section
More informationMarch 14, 2007. Installation of Bay, Bow and Garden Windows
March 14, 2007 Re: Installation of Bay, Bow and Garden Windows Attached are the Atrium Companies, Inc recommendation for the installation of bay, bow and garden windows. These instructions were developed
More informationDetailing of Reinforcment in Concrete Structures
Chapter 8 Detailing of Reinforcment in Concrete Structures 8.1 Scope Provisions of Sec. 8.1 and 8.2 of Chapter 8 shall apply for detailing of reinforcement in reinforced concrete members, in general. For
More informationGeorgia Association of Home Inspectors
Georgia Association of Home Inspectors Standards of Practice for Framing Inspections OVERVIEW The purpose of the GAHI (Georgia Association of Home Inspectors) Standards of Practice for Framing Inspections
More information1/2" CDX PLY W/ 8d @ 6"/ 6"/ 12" 2x ROOF RAFTERS @ 16"OC W/ R-30 BATT. INSUL. (COMMON NAILS)
TYPE V CONSTRUCTION IS A CLASSIFICATION OF BUILDINGS BY CONSTRUCTION MATERIALS AND METHODS. IT IS THE LEAST RESTRICTIVE PERMITTED BY THE UNIFORM BUILDING CODE AND INCLUDES LIGHT, WOOD-FRAME CONSTRUCTION.
More informationKITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS
St. Louis County Department of Public Works Division of Code Enforcement KITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS This guideline is intended to provide the homeowner/contractor with the
More information6 RETROFITTING POST & PIER HOUSES
Retrofitting Post & Pier Houses 71 6 RETROFITTING POST & PIER HOUSES by James E. Russell, P.E. 72 Retrofitting Post & Pier Houses Retrofitting Post & Pier Houses 73 RETROFITTING POST AND PIER HOUSES This
More information201 WATER STREET FORWARDERS MUSEUM AND VISITORS INFORMATION CENTRE
STRUCTURAL INSPECTION REPORT DRAFT 201 WATER STREET FORWARDERS MUSEUM AND VISITORS INFORMATION CENTRE TOWN OF PRESCOTT Date: November 2013 GENIVAR No.: 131-20617-00 2611 Queensview Drive, Suite 300, Ottawa,
More informationWood Burning Safety Guide
Wood Burning Safety Guide CONTENTS Burning Wood Safely...5 Chimney and Stovepipe Cleaning...8 Chimneys for Wood Stoves...1 Cleaning System...8 Clearances...5 Creosote...8 Disposal of Ashes...8 Draft...2
More information2010 Residential Water Heater Replacement Check List
2010 Residential Water Heater Replacement Check List The intent of this check list is to provide installers a general reference for the enforcement of code requirements in the Greater San Diego Area. This
More informationRESIDENTIAL MASONRY A BEST PRACTICES GUIDE
RESIDENTIAL MASONRY A BEST PRACTICES GUIDE Build With Brick Build With Boral CONTENTS BRICK :01 MASONRY CEMENT :03 MASONRY SAND :04 WALL TIES :05 STEEL LINTELS :07 DRAINAGE WALL SYSTEM :09 FLASHING :11
More informationHow To Build A Basement House
Single Family Basement Finish Purpose of Guide The purpose of this guide is to assist you in the permit process for your project. This handout is intended as a basic plan submittal under the 2009 International
More informationCHAPTER 14 BUILDING CODE
CHAPTER 14 BUILDING CODE 14.01 ADOPTED STANDARDS 14.02 BUILDING INSPECTOR 14.03 BUILDING PERMIT REQUIRED 14.04 BUILDING INSPECTIONS 14.05 NEW METHODS AND MATERIALS 14.06 CITY NOT LIABLE 14.07 ROOM HEATERS,
More informationOctober 6, 2009. (B) the vantage point from which the crawl space was inspected; and
535.228. Standards of Practice: Minimum Inspection Requirements for Structural Systems (a) Foundations. The inspector shall: (1) inspect slab surfaces, foundation framing components, subflooring, and related
More informationFIRE-RESISTANCE-RATED CONSTRUCTION
CHAPTER 7 FIRE-RESISTANCE-RATED CONSTRUCTION SECTION 70 GENERAL 70. Scope. The provisions of this chapter shall govern the materials and assemblies used for structural fire resistance and fire-resistance-rated
More informationPolicy on Water Heater Installations Policy No. UPC 510-1-94 Effective: September 1, 1995 Revised: February 10, 1996
CITY OF SAN JOSE BUILDING DIVISION POLICY Policy on Water Heater Installations Policy No. UPC 510-1-94 Effective: September 1, 1995 Revised: February 10, 1996 All new and replacement water heaters installed
More informationFlorida Building Code 2004 SECTION 1009 STAIRWAYS AND HANDRAILS
Florida Building Code 2004 SECTION 1009 STAIRWAYS AND HANDRAILS 1009.1 Stairway width. The width of stairways shall be determined as specified in Section 1005.1, but such width shall not be less than 44
More informationElevating Your House. Introduction CHAPTER 5
CHAPTER 5 Elevating Your House Introduction One of the most common retrofitting methods is elevating a house to a required or desired Flood Protection Elevation (FPE). When a house is properly elevated,
More informationSTRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM
Chapter 9 STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM 9.1 BACKGROUND Steel is widely used in the construction of multi-storey buildings. However, steel construction is seldom used and is traditionally
More informationK. D. FRAME ASSEMBLY FOR CLOSED STEEL STUD WALLS...Ins 10. FRAME INSTALLATION DETAILS FOR CLOSED STEEL STUD WALLS...Ins 11
K. D. FRAME ASSEMBLY FOR MASONRY WALLS...........................Ins 2 FRAME INSTALLATION DETAILS FOR MASONRY WALLS......................Ins 3 INSTALLING EXISTING MASONRY WALL ANCHORS IN FRAME..................Ins
More informationRECOMMENDED PRACTICES FOR MASONRY FIREPLACE AND CHIMNEY CONSTRUCTION.
Published by the New York State Concrete Masonry Association NEW YORK STATE CONCRETE MASONRY ASSOCIATION # RECOMMENDED PRACTICES FOR MASONRY FIREPLACE AND CHIMNEY CONSTRUCTION. INTRODUCTION A well constructed
More information