SiNGle ZoNe MeGa inverter Wall MouNteD engineering MaNual
|
|
|
- Gervais Cameron
- 9 years ago
- Views:
Transcription
1 SiNGle ZoNe MeGa inverter Wall MouNteD engineering MaNual Single Zone Mega Inverter Wall Mounted 3/4 ton, 1 ton, 1 1/2 ton, and 2 ton
2 Proprietary Data Notice This document, as well as all reports, illustrations, data, information, and other materials is the property of LG Electronics U.S.A., Inc., and are disclosed by LG Electronics U.S.A., Inc., only in confidence. This document is for design purposes only. EM-SZ_Mega_Mega115V For continual product development, LG Electronics U.S.A., Inc., reserves the right to change specifications without notice. LG Electronics U.S.A., Inc.
3 about lg electronics LG Electronics is a global leader and technology innovator in consumer electronics, mobile communications, and home appliances. LG Electronics comprises five business units Home Entertainment, Mobile communications, Air conditioning, Business Solutions, and Home Appliance. LG is one of the world s leading producers of flat panel televisions, audio and video products, mobile handsets, air conditioners, and washing machines. LG s commercial air conditioning business unit was established in 1968 and has built its lineup of residential and commercial products to include VrF, multi-zone, duct-free split systems, packaged terminal air conditioners (PtAcs), and room air conditioners. In 2011, the air conditioning and energy solutions business unit grew to include LEd lighting and solar products. For more information, visit Duct-free Split (DfS) Systems LG HVAc systems offer a range of solutions that are cost efficient, quiet and attractive. duct-free Split (dfs) systems are split into indoor and outdoor units, and provide a smart alternative to both central HVAc and window-mounted air conditioners. these inverter heat pump systems are available in a variety of configurations to suit different cooling and heating situations. Installation by a qualified HVAc contractor is safe and easy little to no duct work or sheet metal is required. inverter Systems LG Single Zone Mega Inverter Wall Mounted air-source systems offer the opportunity to minimize ductwork in the same configuration. the system offers zoning without the need for zone damper systems. the LG Single Zone Mega Inverter Wall Mount system s advanced controls provide exceptional building dehumidification and temperature control, and can rapidly adapt system operating parameters to the ever changing building load. the LG Single Zone Mega Inverter Wall Mounted system is easy to design, install, and maintain. the modular design allows occupants to control their environmental condition, providing individualized control of the set-point temperature and allowing occupants to condition only the occupied zones. Quality commitment LG is committed to the success of dfs projects. We provide industry leading technical support during installation and commissioning. LG offers a variety of classes designed for installers and servicers to ensure that every dfs system installation is completed successfully. classes are conducted at LG s training centers and in field locations at various times throughout the year and upon special request. introduction Due to our policy of continuous product innovation, some specifi cations may change without notifi cation. 3
4 Table of Contents Single Zone Mega Inverter Wall Mounted Engineering Manual Architectural Appeal... 6 Product Features and Benefits... 8 Unit Nomenclature... 9 General Data Single Zone Mega Inverter Pairing Table Single Zone Mega 115V Inverter Specifications Electrical Data Single Zone Mega Inverter Outdoor Units Outdoor Unit Dimensions LSU090HEV, LSU120HEV LSU180HEV LSU240HEV LSU090HXV, LSU120HXV Indoor Unit Dimensions LSN090HEV LSN120HEV LSN180HEV, LSN240HEV LSN090HXV, LSN120HXV Acoustic Data Single Zone Mega Inverter Outdoor Units Single Zone Mega 115V Inverter Outdoor Units Single Zone Mega Inverter Indoor Units Single Zone Mega 115V Inverter Indoor Units Refrigerant Flow Diagrams LSN090HEV/LSU090HEV LSN120HEV/LSU120HEV LSN180HEV/LSU180HEV LSN240HEV/LSU240HEV LSN090HXV/LSU090HXV LSN120HXV/LSU120HXV Wiring Diagram LSU090HEV, LSU120HEV LSU180HEV LSU240HEV LSU090HXV, LSU120HXV LSN090HEV, LSN120HEV LSN180HEV, LSN240HEV LSN090HXV, LSN120HXV Accessories Performance Data Cooling Capacity Heating Capacity Equipment Selection Procedure LS090HEV/LS120HEV LS180HEV/LS240HEV LS090HXV/LS120HXV Building Ventilation Design Guide Placement Considerations Single Zone Mega Inverter Wall Mounted Outdoor Installation Refrigerant Piping Design Design Guideline Summary Selecting Field-Supplied Copper Tubing Installation & Layout Best Practices Refrigerant Piping System Layout Piping Connection Electrical Connections Mechanical Specifications Acronyms Table of Symbols This symbol indicates a potentially hazardous situation which, if not avoided, may result in death or serious injury. This symbol indicates additional helpful information such as an explanation, a comment, or a clarification about the subject. This symbol indicates a recommendation or tip. Recommendations instruct the user to apply the suggested practice to ensure the best operating results in order to achieve the maximum benefit of the product. Tips contain practical information that may help the user solve a problem or describe actions that may save time. 4
5 Introduction Architectural Appeal on page 6
6 Architectural Appeal Convergence of Technological Innovation with Flexibility and Style Single Zone Mega Inverter Wall Mounted Engineering Manual Benefits of Single Zone Mega Inverter Wall Mounted Inverter technology Available in 9,000, 12,000 (HEV and HXV), 18,000 and 24,000 (HEV only) Btu/h capacities All-season use - heat pump models for both cooling and heating capabilities Operating ranges for Outdoor units (HEV) of 64 F to 118 F (DB) for cooling; 23 F to 65 F (WB) for heating Operating ranges for Outdoor units (HXV) of 14 F to 118 F (DB) for cooling; 14 F to 65 F (WB) for heating Operating ranges for all model Indoor Units of 53 F to 75 F (WB) for cooling; 60 F to 86 F (DB) for heating Quiet operation inside and outside Duct-Free Split system Single Zone Mega Inverter Wall Mounted Choosing an LG Single Zone Mega Inverter Wall Mounted product provides a system designer an edge to engineer a system with individual control, and design flexibility with advanced controls. The Single Zone Mega Inverter Wall Mounted Outdoor and Indoor units are available in a nominal capacity range of 3/4 to 2 tons. These are best suited for applications with zones that require heating or cooling, such as residential, and small business office buildings. Single Zone Mega Inverter Wall Mounted Outdoor and Indoor units are available in V/60Hz/1Ph, as well as, 115V/60Hz/1Ph. Adaptable and Flexible The Single Zone Mega Inverter Wall Mounted DFS System allows cooling or heating for the entire residence or just a single room without the need for evasive ductwork. There is no tearing down of walls or altering the homes appearance. Long refrigerant piping lengths allow for extra design flexibility in indoor unit installation. These units may be used for a number of residential or commercial environments such as: Older homes New home construction Office buildings Restaurants Hospitals / Medical facilities Schools Nursing homes Retail establishments Houses of worship Inverter Technology Inverter variable-speed DFS Systems are measurably quieter and consume less energy than conventional air conditioners. The Inverter compressor ramps up or down to match the required room capacity and maintain the comfort level. When the selected temperature is reached, the inverter compressor operates at low speed to maintain that comfort level, thereby using less energy. 6 Introduction
7 Product data Product Features and Benefits on page 8 Unit Nomenclature on page 9 General Data on page 10 Electrical Data on page 17 Outdoor Unit Dimensions on page 18 Indoor Unit Dimensions on page 22 Acoustic Data on page 26 Refrigerant Flow Diagrams on page 30 Wiring Diagrams Outdoor Units on page 34 Wiring Diagrams Indoor Units on page 38 Accessories - LG Monitoring View Diagnostic Software on page 40
8 Product Features and Benefits Single Zone Mega Inverter Wall Mounted Engineering Manual Single Zone Mega Inverter Wall Mounted Single Zone Mega Inverter Wall Mounted units are equipped with inverter components that offer superior load matching and long piping installation. The product works for optimizing power consumption in residential and small office buildings. Utilizing multiple indoor wall mounted units each with custom temperature controls allow for precise temperature settings in each zone of the building. Single Zone Mega Inverter Wall Mounted allows flexibility in interior design and complements any decor. Low Sound Levels When outdoor units operate fully loaded, they have one of the quietest sound levels in the industry. Sound is almost undetectable during off-peak operation. To promote a quiet, comfortable environment, the LG Single Zone Mega Inverter Wall Mounted indoor units operate at sound levels as low as 23 db(a) (HXV units) and outdoor units as low as 47 db(a) at full load. LG customers often ask if the outdoor unit is running after commissioning is complete. All rotating components are soft-started by the controller using digitally controlled inverters, which reduce undesirable noise caused by fans and compressors cycling on and off. Comfort Control at Its Best Tight temperature control through precise load matching maximizes the time that the indoor units remove moisture. Unlike traditional air conditioning control systems, which use thermostatic controls to maintain room temperatures, LG Single Zone Mega Inverter controls continuously adjust the indoor unit fan speed and refrigerant flow, indirectly providing lower and more consistent humidity levels in the conditioned space. The longer the indoor coil temperature is below the dew-point of the room in conjunction with air movement across the coil, the space humidity level will vary little, compared to technologies that cycle fans and compressors on and off multiple times per hour. The outdoor unit responds by varying the compressor speed and outdoor fan motors as needed to maintain system operating pressure. As a result, the Single Zone Mega Inverter Wall Mount system delivers precise space temperature control. Inverter Driven The rotary (9k/12k Btu/h systems) and twinrotary (18k/24k Btu/h systems) compressor is optimized to maximize compressor efficiency, which reduces power consumption and monthly utility bills. This latest inverter technology allows the LG Single Zone Mega Inverter Wall Mounted outdoor unit to vary the compressor motor shaft speed to deliver an appropriate amount of cooling to the indoor unit. Precise refrigerant volume delivery translates into long periods with coil surface temperatures below dew point and minimizes compressor and fan component run time. Occupants remain comfortable while utility costs are reduced. Simplified Installation Cooling and heating applications that use the LG Single Zone Mega Inverter Wall Mounted product simplify and reduce the mechanical and control system design time. The designer no longer has to be concerned with interconnecting chilled and condenser water piping, air-distribution duct systems, matching and selecting chillers, towers, pumps, coils, fans, air handlers, or Variable Air Volume (VAV) boxes. Operating Range The Single Zone Mega Inverter Wall Mounted product has a nominal capacity range of 3/4 to 2 tons (depending on outdoor/indoor units). Operating ranges include: Mega (HEV) Outdoor Units Cooling: 64 F DB to 118 F DB Heating: 23 F WB to 65 F WB Mega 115V (HXV) Outdoor Units Cooling: 14 F DB to 118 F DB Heating: 14 F WB to 65 F WB Compact Size Single Zone Mega Inverter Wall Mounted outdoor units have the following footprints: LSU090HEV, LSU120HEV (WxHxD (in.)): 28 1/4 x 19 1/32 x 9 1/16 LSU180HEV (WxHxD (in.)): 30 5/16 x 21 1/2 x 11 5/16 LSU240HEV (WxHxD (in.)): 34 1/4 x 25 13/16 x 12 19/32 LSU090HXV, LSU120HXV (WxHxD (in.)): 28 1/4 x 19 1/2 x 9 1/16 Heat Transfer Efficiency Fin Design with GoldFin Coating All Single Zone Mega Inverter Wall Mounted outdoor units are provided with large surface coils made of copper tubes with louvered aluminum fins designed to maximize unit operating efficiency over a wide range of ambient conditions. Standard from the factory, every LG Single Zone Mega Inverter Wall Mounted outdoor coil fin surface is coated with LG s exclusive GoldFin anti-corrosive coating designed to prevent natural surface corrosion of the aluminum fins. This maintains heat transfer properties of the coil for an extended time. A hydrophilic coating is applied to the outdoor unit coil fin surface over the GoldFin coating. This coating enhances the development of heavier water droplets gathering on the fin surface. As a result, the droplets roll off the fin surfaces, delaying the point when frost forms on the coil surface during heating operation. This coating also makes it possible to easily clean the outdoor unit coil using a mild soap. Other Features Inverter variable speed compressor Jet Cool (HEV/HXV) / Jet Heat (HXV) Dehumidifying mode Chaos Wind Auto restart Auto operation Self-cleaning indoor coil Condensate sensor connection Smaller footprint Precision load matching Meets AHRI 210/240 8 Product Data
9 Unit Nomenclature Single Zone Mega Wall Mounted Indoor and Outdoor Units Family LS= Mega LS N 090 HEV Type N = Indoor Wall Mount Unit U = Outdoor Heat Pump Unit Nominal Capacity (Nominal cooling capacity in Btu/h) 090 = 9, = 12, = 18, = 24,000 Indoor/Outdoor Product HEV = Mega HXV = Mega 115V Product Data Product Data 9
10 General Data Single Zone Mega Inverter Pairing Table The following table shows the available outdoor and indoor unit, along with the factory provided controller. Table 1: Single Zone Mega Inverter Pairing Table Outdoor Unit Model/ Btu/h Indoor Unit Model/ Btu/h Controller LSU090HEV / 9,000 LSU120HEV / 12,000 LSN090HEV / 9,000 LSN120HEV / 12,000 AKB Single Zone Mega Inverter Wall Mounted Engineering Manual LSU180HEV / 18,000 LSN180HEV / 18,000 AKB LSU240HEV / 24,000 LSN240HEV / 24,000 AKB Single Zone Mega 115V Inverter Pairing LSU090HXV / 9,000 LSU120HXV / 12,000 LSN090HXV / 9,000 LSN120HXV / 12,000 AKB Product Data
11 General Data Single Zone Mega Inverter Specifications Table 2: Unit General Data Type Single Zone Mega Inverter System (Model IDU/ODU) LS090HEV (LSN090HEV/LSU090HEV) LS120HEV (LSN120HEV/LSU120HEV) Nominal Cooling Capacity (Btu/h) 8,500 12,000 Cooling Power Input 1 (kw) Nominal Heating Capacity (Btu/h) 9,000 12,000 Heating Power Input 1 (kw) Cooling COP EER SEER HSPF Power Supply (V / Hz / Ø) /60/1 ODU Operating Range Cooling ( F DB) Heating ( F WB) IDU Operating Range Cooling ( F WB) Heating ( F DB) Indoor Temperature Setting Range Cooling ( F) Heating ( F) Unit Data Refrigerant Type 2 R410A Refrigerant Control Capillary Tube IDU Sound Pressure 3 ± 3 db(a) (H/M/L) 39/33/25 39/33/25 ODU Sound Pressure ± 3 db(a) Indoor Unit (Net/Shipping Weight lbs.) 16/21 20/25 Outdoor Unit (Net/Shipping Weight lbs.) 52/56 49/53 Power/Communication Cable 4 (No. x AWG) 4 x 18 Compressor Compressor Type (Qty) Single Rotary (1) Single Rotary (1) Fan Indoor Type (Qty) Cross Flow (1) Outdoor Type (Qty) Propeller (1) Motor/Drive Brushless Digitally Controlled/Direct Airflow Rate Indoor - Max/H/M/L (CFM) 318/276/226/ /353/272/212 Outdoor - Max (CFM) Product Data Product Data 11
12 General Data Single Zone Mega Inverter Specifications Table 2: Unit General Data (Continued) Single Zone Mega Inverter Wall Mounted Engineering Manual Type Single Zone Mega Inverter System (Model IDU/ODU) LS090HEV (LSN090HEV/LSU090HEV) LS120HEV (LSN120HEV/LSU120HEV) Piping Liquid Line (in, OD) 1/4 1/4 Vapor Line (in, OD) 3/8 3/8 Condensation Line (OD ID) 27/32 5/8 27/32 5/8 Additional Refrigerant Charge (oz/ft) Pipe Length (Minimum / Maximum) (ft) / / 49.2 Piping Length (no add l refrigerant, ft) Max Elevation Difference (ft) EEV: Electronic Expansion Valve Power wiring is field supplied and must comply with the applicable local and national codes. This unit comes with a dry helium charge. This data is rated 0 ft above sea level, with 24.6 ft of refrigerant line per indoor unit and a 0 ft level difference between outdoor and indoor units. All capacities are net with a combination ratio between %. Cooling capacity rating obtained with air entering the indoor coil at 80ºF dry bulb (DB) and 67ºF wet bulb (WB); and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB). Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 60ºF wet bulb (WB); and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB). 1 Power Input is rated at high speed. 2 Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608 of CAA. 3 Sound Pressure levels are tested in an anechoic chamber under ISO Standard All power/communication cable to be minimum 18 AWG, 4-conductor, stranded, shielded and must comply with applicable and national code. 5 Piping lengths are equivalent. 12 Product Data
13 General Data Single Zone Mega Inverter Specifications Table 3: Unit General Data Type Single Zone Mega Inverter System (Model IDU/ODU) LS180HEV (LSN180HEV/LSU180HEV) LS240HEV (LSN240HEV/LSU240HEV) Nominal Cooling Capacity (Btu/h) 17,000 22,000 Cooling Power Input 1 (kw) Nominal Heating Capacity (Btu/h) 19,000 22,000 Heating Power Input 1 (kw) Cooling COP EER SEER HSPF Power Supply (V / Hz / Ø) /60/1 ODU Operating Range Cooling ( F DB) Heating ( F WB) IDU Operating Range Cooling ( F WB) Heating ( F DB) Indoor Temperature Setting Range Cooling ( F) Heating ( F) Unit Data Refrigerant Type 2 R410A Refrigerant Control Capillary Tube IDU Sound Pressure 3 ± 3 db(a) (H/M/L) 42/40/35 45/40/35 ODU Sound Pressure ± 3 db(a) Indoor Unit (Net/Shipping Weight lbs.) 28/30 28/34 Outdoor Unit (Net/Shipping Weight lbs.) 72/77 92/104 Power/Communication Cable 4 (No. x AWG) 4 x 18 Compressor Compressor Type (Qty) Twin Rotary (1) Twin Rotary (1) Fan Indoor Type (Qty) Cross Flow (1) Outdoor Type (Qty) Propeller (1) Motor/Drive Brushless Digitally Controlled/Direct Airflow Rate Indoor - Max/H/M/L (CFM) 629/512/441/ /600/494/388 Outdoor - Max (CFM) 1,342 1,766 Product Data Product Data 13
14 General Data Single Zone Mega Inverter Specifications Table 3: Unit General Data (Continued) Single Zone Mega Inverter Wall Mounted Engineering Manual Type Single Zone Mega Inverter System (Model IDU/ODU) LS180HEV (LSN180HEV/LSU180HEV) LS240HEV (LSN240HEV/LSU240HEV) Piping Liquid Line (in, OD) 1/4 1/4 Vapor Line (in, OD) 1/2 5/8 Condensation Line (OD ID) 27/32 5/8 27/32 5/8 Additional Refrigerant Charge (oz/ft) Pipe Length (Minimum / Maximum) (ft) / / 65.6 Piping Length (no add l refrigerant, ft) Max Elevation Difference (ft) EEV: Electronic Expansion Valve Power wiring is field supplied and must comply with the applicable local and national codes. This unit comes with a dry helium charge. This data is rated 0 ft above sea level, with 24.6 ft of refrigerant line per indoor unit and a 0 ft level difference between outdoor and indoor units. All capacities are net with a combination ratio between %. Cooling capacity rating obtained with air entering the indoor coil at 80ºF dry bulb (DB) and 67ºF wet bulb (WB); and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB). Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 60ºF wet bulb (WB); and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB). 1 Power Input is rated at high speed. 2 Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608 of CAA. 3 Sound Pressure levels are tested in an anechoic chamber under ISO Standard All power/communication cable to be minimum 18 AWG, 4-conductor, stranded, shielded and must comply with applicable and national code. 5 Piping lengths are equivalent. 14 Product Data
15 General Data Single Zone Mega 115V Inverter Specifications Table 4: Unit General Data Type Single Zone Mega Inverter System (Model IDU/ODU) LS090HXV (LSN090HXV/LSU090HXV) LS120HXV (LSN120HXV/LSU120HXV) Cooling Capacity (Min/Rated/Max) (Btu/h) 1,023 / 8,500 / 13,785 1,023 / 12,000 / 13,785 Cooling Power Input 1 (kw) Heating Capacity (Min/Rated/Max) (Btu/h) 1,023 / 10,900 / 22,178 1,023 / 13,000 / 22,178 Heating Power Input 1 (kw) COP EER SEER HSPF Power Supply (V / Hz / Ø) 115/60/1 ODU Operating Range Cooling ( F DB) Heating ( F WB) IDU Operating Range Cooling ( F WB) Heating ( F DB) Indoor Temperature Setting Range Cooling ( F) Heating ( F) Unit Data Refrigerant Type 2 R410A Refrigerant Control EEV IDU Sound Pressure 3 ± 3 db(a) (H/M/L/Sleep) 39/33/23/19 39/33/23/19 ODU Sound Pressure ± 3 db(a) Indoor Unit (Net/Shipping Weight lbs.) 23/26 23/26 Outdoor Unit (Net/Shipping Weight lbs.) 67/79 67/79 Power/Communication Cable 4 (No. x AWG) 4 x 18 Compressor Compressor Type (Qty) Single Rotary (1) Single Rotary (1) Fan Indoor Type (Qty) Cross Flow (1) Outdoor Type (Qty) Propeller (1) Motor/Drive Brushless Digitally Controlled/Direct Airflow Rate Indoor - Max/H/M/L (CFM) 335/272/212/ /272/212/124 Outdoor - Max (CFM) 1,000 1,000 Product Data Product Data 15
16 General Data Single Zone Mega 115V Inverter Specifications Table 4: Unit General Data (Continued) Single Zone Mega Inverter Wall Mounted Engineering Manual Type Single Zone Mega Inverter System (Model IDU/ODU) LS090HXV (LSN090HXV/LSU090HXV) LS120HXV (LSN120HXV/LSU120HXV) Piping Liquid Line (in, OD) 1/4 1/4 Vapor Line (in, OD) 3/8 3/8 Condensation Line (OD ID) 27/32 5/8 27/32 5/8 Additional Refrigerant Charge (oz/ft) Pipe Length (Minimum/Maximum) (ft) / / 49.2 Piping Length (no add l refrigerant, ft) Max Elevation Difference (ft) EEV: Electronic Expansion Valve Power wiring is field supplied and must comply with the applicable local and national codes. This unit comes with a dry helium charge. This data is rated 0 ft above sea level, with 24.6 ft of refrigerant line per indoor unit and a 0 ft level difference between outdoor and indoor units. All capacities are net with a combination ratio between %. Cooling capacity rating obtained with air entering the indoor coil at 80ºF dry bulb (DB) and 67ºF wet bulb (WB); and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB). Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 60ºF wet bulb (WB); and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB). 1 Power Input is rated at high speed. 2 Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608 of CAA. 3 Sound Pressure levels are tested in an anechoic chamber under ISO Standard All power/communication cable to be minimum 18 AWG, 4-conductor, stranded, shielded and must comply with applicable and national code. 5 Piping lengths are equivalent. 16 Product Data
17 Electrical Data Single Zone Mega and Mega 115V Inverter Outdoor Units Table 5: V, 60Hz, 1-Phase Single Zone Mega Inverter Outdoor Units Unit Model Nos. Nom. Tons Compressor Qty Compressor(A) Cool/Heat Fan Qty ODU Fan(A) MCA(A) MOP(A) LSU090HEV 3/ / LSU120HEV / LSU180HEV 1 1/ / LSU240HEV / For component model nos. see the specification table on pages Voltage tolerance is ±10%. Maximum allowable voltage unbalance is 2%. MSC = Maximum Starting Current. MCA = Minimum Circuit Ampacity. Maximum Overcurrent Protectin (MOP) is calculated as follows: (Largest motor FLA x 2.25) + (Sum of other motor FLA) rounded down to the nearest standard fuse size. Table 6: 115V, 60Hz, 1-Phase Single Zone Mega 115V Inverter Outdoor Units Unit Model Nos. Nom. Tons Compressor Qty Compressor(A) Cool/Heat Fan Qty ODU Fan(A) MCA(A) MOP(A) LSU090HXV 3/4 1 10/ LSU120HXV / For component model nos. see the specification table on page 15 Voltage tolerance is ±10%. Maximum allowable voltage unbalance is 2%. MSC = Maximum Starting Current. MCA = Minimum Circuit Ampacity. Maximum Overcurrent Protectin (MOP) is calculated as follows: (Largest motor FLA x 2.25) + (Sum of other motor FLA) rounded down to the nearest standard fuse size. Product Data Product Data 17
18 OUTDOOR UNIT DIMENSIONS LSu090HEV, LSu120HEV 9-1/4 10-1/16 Single Zone Mega Inverter Wall Mounted Engineering Manual 2-1/4 2-3/16 7/ /32 Ø17-3/8 4 1 Unit: inch 10-1/2 28-1/4 2-3/16 9-1/ /8 Item No. Part Name Remarks Return Air Grille 18-1/4 28-1/4 18 Product data
19 OUTDOOR UNIT DIMENSIONS LSu180HEV 21-1/ / / / / /1 Ø18 2 Product Data 4-3/ / /16 6-3/ / /32 Item No. Part Name Return Air Grille 11-5/16 5 Unit: inch Remarks Product data 19
20 OUTDOOR UNIT DIMENSIONS LSu240HEV 25-13/ / /32 Single Zone Mega Inverter Wall Mounted Engineering Manual 3 3-3/32 1 Ø20-29/32 Unit: inch 11-29/ /32 2-3/ /16 Return Air Grille Item No. Part Name Remarks 21-1/2 6-5/ /4 20 Product data
21 . OUTDOOR UNIT DIMENSIONS LSu090HXV, LSu120HXV 9 9/32 9 1/ /32 Ø17 6/ /4 18 7/ /4 2 1/4 7/ / / / / /32 Product Data Return Air Grille Unit: inch Product data 21
22 INDOOR UNIT DIMENSIONS LSN090HEV Left rear piping Single Zone Mega Inverter Wall Mounted Engineering Manual 5-11/16 7-9/ /16 7-9/16 Ø2-9/16 Ø2-9/16 Installation Plate 5 Right rear piping Unit: inch Unit Outline 14-7/8 Place a level on raised tab 14-7/8 Return Air Grille Hole Item No. Part Name Remarks / /4 7-1/ Product data
23 INDOOR UNIT DIMENSIONS LSN120HEV 3 Unit Outline Ø2-9/16 Left Rear Piping /4 5-1/ /16 Place a level on raised tab 5 Installation Plate 2 Ø2-9/16 Right Rear Piping 9-5/8 8-1/4 4 Item No. Part Name Hole Return Air Grille Remarks 23 Product data Product Data /8 4-13/ /4 Unit: inch
24 INDOOR UNIT DIMENSIONS LSN180HEV, LSN240HEV Ø2-13/16 Left rear piping Single Zone Mega Inverter Wall Mounted Engineering Manual 2-11/16 2-3/16 Measuring Tape 4-3/32 Hanger 8-3/32 Installation Plate Measuring Tape Right rear piping Ø2-13/16 5 Unit: inch Place a level on raised tab Unit Outline 18-3/ /32 Return Air Grille Item No. Part Name Remarks 12-13/ / /16 24 Product data
25 INDOOR UNIT DIMENSIONS LSN090HXV, LSN120HXV Left rear piping 6-29/32 8-9/ /4 3-3/4 Right rear piping Installation Plate Ø2-25/32 Ø2-25/ / /32 Unit Outline 2-5/ /16 Place a level on raised tab 29/ / /32 8-9/32 3 Product Data Unit: inch Return Air Grille Product data 25
26 Acoustic Data Single Zone Mega Inverter Outdoor Units Sound Pressure Levels Figure 1: Mega Inverter Sound Measurement Table 7: Mega Inverter Outdoor Units - Sound Levels Single Zone Mega Inverter Wall Mounted Engineering Manual 26 Product Data Figure 2: LSU090HEV Octave Band Sound Pressure Level (0dB = 20μPa) Figure 4: LSU180HEV Octave Band Sound Pressure Level (0dB = 20μPa) ft Approximate Hearing Threshold Approximate Hearing Threshold LSU090HEV Octave Band Center Frequency (Hz) LSU180HEV NC-65 NC-60 NC-55 NC-50 NC-45 NC-40 NC-3 5 NC-3 0 NC-25 NC-20 NC-15 NC-65 NC-60 NC-55 NC-50 NC-45 NC-40 NC-3 5 NC-3 0 NC-25 NC-20 NC Octave Band Center Frequency (Hz) Model Figure 3: LSU120HEV Figure 5: LSU240HEV Octave Band Sound Pressure Level (0dB = 20μPa) Octave Band Sound Pressure Level (0dB = 20μPa) LSU120HEV NC-65 NC-60 NC-55 NC-50 NC-45 NC-40 NC-3 5 NC NC-25 Approximate NC-20 Hearing Threshold NC Octave Band Center Frequency (Hz) Sound Levels [db(a)] Max LSU090HEV 47 LSU120HEV 47 LSU180HEV 51 LSU240HEV 53 LSU240HEV NC-65 NC-60 NC-55 NC-50 NC-45 NC-40 NC-3 5 NC-3 0 NC-25 Approximate Hearing NC Threshold NC Octave Band Center Frequency (Hz)
27 Sound Pressure Levels Acoustic Data Single Zone Mega 115V Inverter Outdoor Units Figure 6: Mega 115V Inverter Sound Measurement Table 8: Mega 115V Inverter Outdoor Units - Sound Levels 3.28 ft Sound Levels [db(a)] Model Max LSU090HXV 47 LSU120HXV 47 Figure 7: LSU090HXV Figure 8: LSU120HXV 80 LSU090HXV 80 LSU120HXV Octave Band Sound Pressure Level (0dB = 20μPa) Approximate Hearing Threshold Octave Band Center Frequency (Hz) NC-65 NC-60 NC-55 NC-50 NC-45 NC-40 NC-35 NC-30 NC-25 NC-20 NC-15 Octave Band Sound Pressure Level (0dB = 20μPa) Approximate Hearing Threshold Octave Band Center Frequency (Hz) NC-65 NC-60 NC-55 NC-50 NC-45 NC-40 NC-35 NC-30 NC-25 NC-20 NC-15 Product Data Product Data 27
28 Acoustic Data Single Zone Mega Inverter Indoor Units Sound Pressure Levels Figure 9: Mega Inverter Sound Measurement Figure 11: LSN180HEV Unit: Feet 80 LSN180HEV Single Zone Mega Inverter Wall Mounted Engineering Manual Figure 10: LSN090HEV, LSN120HEV Octave Band Sound Pressure Level (0dB = 20μPa) Microphone Table 9: Mega Inverter Indoor Units - Sound Levels Sound Levels [db(a)] Model H M L LSN090HEV LSN120HEV LSN180HEV LSN240HEV LSN090HEV, LSN120HEV Octave Band Sound Pressure Level (0dB = 20μPa) Octave Band Center Frequency (Hz) Figure 12: LSN240HEV Octave Band Sound Pressure Level (0dB = 20μPa) LSN240HEV Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz) 28 Product Data
29 Sound Pressure Levels Acoustic Data Single Zone Mega 115V Inverter Indoor Units Figure 13: Mega 115V Inverter Sound Measurement Unit: Feet Figure 14: LSN090HXV, LSN120HXV 80 LSN090HXV LSN120HXV Microphone Table 10: Mega 115V Inverter Indoor Units - Sound Levels Sound Levels [db(a)] Model H M L Sleep LSN090HXV LSN120HXV Octave Band Sound Pressure Level (0dB = 20μPa) Octave Band Center Frequency (Hz) Product Data Product Data 29
30 Refrigerant Flow Diagrams LSN090HEV/LSU090HEV LSN120HEV/LSU120HEV Indoor Unit Outdoor Unit Liquid Side Single Zone Mega Inverter Wall Mounted Engineering Manual Th1 Heat Exchanger (Evaporator) Th2 Th3 2-Way Valve Gas Side 3-Way Valve Accumulator Compressor Capillary Tube Heat Exchanger (Condenser) Th4 Reversing Valve LOC Description PCB Connector Th 1 Indoor air temperature thermistor CH-TH1(Indoor) Th 2 Water level sensor (Option) CH-TH2 (Indoor) Th 3 Evaporating middle temperature thermistor CH-TH3 (Indoor) Th 4 Discharge pipe temperature thermistor CN-TH2 (Outdoor) Th 5 Heat exchanger temperature thermistor CN-TH1 (Outdoor) Th 6 Outdoor air temperature thermistor CN-TH1 (Outdoor) Th5 Cooling Heating Th6 30 Product Data
31 Refrigerant Flow Diagrams LSN180HEV/LSU180HEV Indoor Unit Outdoor Unit Liquid Side Th2 Th3 2-Way Valve Capillary Tube Th1 Heat Exchanger (Evaporator) Heat Exchanger (Condenser) Th6 Th5 Gas Side Th4 3-Way Valve Accumulator Reversing Valve Compressor LOC Description PCB Connector Th 1 Indoor air temperature thermistor CH-TH1(Indoor) Th 2 Water level sensor (Option) CH-TH2 (Indoor) Th 3 Evaporating middle temperature thermistor CH-TH3 (Indoor) Th 4 Discharge pipe temperature thermistor CN-TH2 (Outdoor) Th 5 Heat exchanger temperature thermistor CN-TH1 (Outdoor) Th 6 Outdoor air temperature thermistor CN-TH1 ( Outdoor) Cooling Heating Product Data Product Data 31
32 Refrigerant Flow Diagrams LSN240HEV/LSU240HEV Indoor Unit Outdoor Unit Liquid Side Single Zone Mega Inverter Wall Mounted Engineering Manual Th1 Heat Exchanger (Evaporator) Th2 Th3 2-Way Valve Gas Side 3-Way Valve Accumulator Compressor Capillary Tube Heat Exchanger (Condenser) Th4 Reversing Valve LOC Description PCB Connector Th 1 Indoor air temperature thermistor CH-TH1 (Indoor) Th 2 Water level sensor (Option) CH-TH2 (Indoor) Th 3 Evaporating middle temperature thermistor CH-TH3 (Indoor) Th 4 Discharge pipe temperature thermistor CN-TH2 (Outdoor) Th 5 Heat exchanger temperature thermistor CN-TH1(Outdoor) Th 6 Outdoor air temperature thermistor CN-TH1(Outdoor) Th5 Cooling Heating Th6 32 Product Data
33 Refrigerant Flow Diagrams LSN090HXV/LSU090HXV LSN120HXV/LSU120HXV Indoor Unit Outdoor Unit Liquid Side 2-Way Valve EEV Th1 Heat Exchanger (Evaporator ) Th2 Heat Exchanger (Condenser) Th5 Th4 Gas Side 3-Way Valve Accumulator Compressor Th3 Reversing Valve Cooling Heating Product Data LOC. Description P C B C onnector T h1 Indoor air temperature thermistor C N-T H1(Indoor) Th2 Evaporating middle temperature thermistor CN-TH2 (Indoor) Th3 Discharge pipe temperature thermistor CN-TH2 (Outdoor) Th4 Condensing middle temperature thermistor CN-TH1 (Outdoor) Th5 Outdoor air temperature thermistor CN-TH1 (Outdoor) EEV : Electronic Expansion Valve Product Data 33
34 Single Zone Mega Inverter Wall Mounted Engineering Manual Wiring Diagram LSU090HEV, LSU120HEV Single Zone Mega Inverter 34 Product Data
35 Product Data Single Zone Mega Inverter Wiring Diagram LSU180HEV Product Data 35
36 Single Zone Mega Inverter Wall Mounted Engineering Manual Wiring Diagram LSU240HEV Single Zone Mega Inverter 36 Product Data
37 Product Data Single Zone Mega 115V Inverter Wiring Diagram LSU090HXV, LSU120HXV 250V 250V 250V Product Data 37
38 Single Zone Mega Inverter Wall Mounted Engineering Manual Wiring Diagram LSN090HEV, LSN120HEV LSN180HEV, LSN240HEV Single Zone Mega Inverter ASNW183CSA7 (LSN180HEV), ASNW243CSA7 (LSN240HEV) 38 Product Data
39 Product Data Single Zone Mega 115V Inverter Wiring Diagram LSN090HXV, LSN120HXV MEZ Product Data 39
40 Accessories LG Monitoring View (LGMV) Diagnostic Software and Cable Single Zone Mega Inverter Wall Mounted Engineering Manual LGMV software allows the service technician or commissioning agent to connect a computer USB port to the outdoor unit main printed circuit board (PCB) using an accessory cable without the need for a separate interface device. The main screen for LGMV allows the user to view the following real time data on one screen: Actual inverter compressor speed Target inverter compressor speed Actual outdoor fan speed Target outdoor unit fan speed Actual superheat Inverter compressor current value Outdoor air temperature Actual high pressure/saturation temperature Actual low pressure/saturation temperature Suction temperature Inverter compressor discharge temperature Outdoor coil pipe temperature Liquid line pipe temperature Inverter compressor operation indicator light Four-way reversing valve operation Additional information that can be gathered from the main screen: 1. Graph: Graphic shows the following: Compressors showing actual speeds IDUs Low and high pressures indicator light Pressure graph showing actual low pressure and actual high pressure levels Error code display Operating mode indicator Total number of connected indoor units (for multi zone systems) Communication indicator lights Unit error code Indoor unit capacity Indoor unit operating mode Indoor unit fan speed Indoor unit room temperature Indoor unit inlet pipe temperature Indoor unit outlet pipe temperature Temperature sensors Four-way reversing valve Outdoor fans showing status and speeds 2. Setting: Converts metric values to imperial values. 3. Making Data: Recording of real time data to a separate file created to be stored on the user s computer. 4. Loading Data: Recorded data from a saved.csv file can be loaded to create an LGMV session. 5. Electrical Data: The lower half of main screen is changed to show the following: Inverter compressor - Amps - Volts - Power Hz - Inverter control board fan Hz Figure 15: MV Diagnostic Screen 40 Product Data
41 Accessories LG Monitoring View (LGMV) Diagnostic Software and Cable - Continued The software is available in a high version with all of the features listed above. The low version has all features as the high version without Target High Pressure and Target Low Pressure values shown on main screen. In lieu of connecting to the ODU, user has the option to connect to IDU with the use of a USB to RS-485 connector kit. When connected through IDU, user will not be able to record data. This software can be used to both commission new systems and troubleshoot existing systems. LGMV data can be recorded to a.csv file and ed to an LG representative to assist with diagnostic evaluations. Recommended Minimum PC Configuration: CPU: Pentium IV 1.6 GHz Operating System: Windows NT/2000/XP/Vista Main Memory: 256 MB Hard Disk: 600 MB when operating Web Browser: Internet Explorer 5.0 Figure 16: MV Diagnostic Screen - High Version Product Data Product Data 41
42 Single Zone Mega Inverter Wall Mounted Engineering Manual This page intentionally left blank. 42 Product Data
43 PERFORMANCE DATA Cooling Capacity Data on page 44 Heating Capacity Data on page 47
44 Performance Data Cooling Capacity LSN090HEV/LSU090HEV Single Zone Mega Inverter Wall Mounted Engineering Manual Outdoor air temp. ( F DB) Indoor Air Temp. F DB/ F WB 64/53 68/57 72/61 77/64 80/67 86/72 90/75 TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI DB = Dry Bulb Temperature ( F) WB = Wet Bulb Temperature ( F) TC = Total Capacity (kbtu/h). SC = Sensible Capacity (kbtu/h) PI = Power Input (kw) (includes compressor, indoor fan motor and outdoor fan motor). LSN120HEV/LSU120HEV Outdoor air temp. ( F DB) NOTES 1. All capacities are net, evaporator fan motor heat is deducted. 2. Grey shading Indicates reference data. When operating at this temperature, these values can be different by discontinuous operation. 3. Direct interpolation is permissible. Do not extrapolate 4. Capacities are based on the following conditions: - Interconnecting Piping Length 24.6 ft - Level Difference of Zero. - Indoor Air Temperature :80 F (26.7 C) DB / 67 F (19.4 C) WB - Outdoor Air Temperature :95 F (35.0 C) DB / 75 F (23.9 C) WB Indoor Air Temp. F DB/ F WB 64/53 68/57 72/61 77/64 80/67 86/72 90/75 TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI DB = Dry Bulb Temperature ( F) WB = Wet Bulb Temperature ( F) TC = Total Capacity (kbtu/h). SC = Sensible Capacity (kbtu/h) PI = Power Input (kw) (includes compressor, indoor fan motor and outdoor fan motor). NOTES 1. All capacities are net, evaporator fan motor heat is deducted. 2. Grey shading Indicates reference data. When operating at this temperature, these values can be different by discontinuous operation. 3. Direct interpolation is permissible. Do not extrapolate 4. Capacities are based on the following conditions: - Interconnecting Piping Length 24.6 ft - Level Difference of Zero. - Indoor Air Temperature :80 F (26.7 C) DB / 67 F (19.4 C) WB - Outdoor Air Temperature :95 F (35.0 C) DB / 75 F (23.9 C) WB 44 Product Data
45 Performance Data Cooling Capacity LSN180HEV/LSU180HEV Outdoor air temp. ( F DB) Indoor Air Temp. F DB/ F WB 64/53 68/57 72/61 77/64 80/67 86/72 90/75 TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI DB = Dry Bulb Temperature ( F) WB = Wet Bulb Temperature ( F) TC = Total Capacity (kbtu/h). SC = Sensible Capacity (kbtu/h) PI = Power Input (kw) (includes compressor, indoor fan motor and outdoor fan motor). LSN240HEV/LSU240HEV Outdoor air temp. ( F DB) NOTES 1. All capacities are net, evaporator fan motor heat is deducted. 2. Grey shading Indicates reference data. When operating at this temperature, these values can be different by discontinuous operation. 3. Direct interpolation is permissible. Do not extrapolate 4. Capacities are based on the following conditions: - Interconnecting Piping Length 24.6 ft - Level Difference of Zero. - Indoor Air Temperature :80 F (26.7 C) DB / 67 F (19.4 C) WB - Outdoor Air Temperature :95 F (35.0 C) DB / 75 F (23.9 C) WB Indoor Air Temp. F DB/ F WB 64/53 68/57 72/61 77/64 80/67 86/72 90/75 TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI DB = Dry Bulb Temperature ( F) WB = Wet Bulb Temperature ( F) TC = Total Capacity (kbtu/h). SC = Sensible Capacity (kbtu/h) PI = Power Input (kw) (includes compressor, indoor fan motor and outdoor fan motor). NOTES 1. All capacities are net, evaporator fan motor heat is deducted. 2. Grey shading Indicates reference data. When operating at this temperature, these values can be different by discontinuous operation. 3. Direct interpolation is permissible. Do not extrapolate 4. Capacities are based on the following conditions: - Interconnecting Piping Length 24.6 ft - Level Difference of Zero. - Indoor Air Temperature :80 F (26.7 C) DB / 67 F (19.4 C) WB - Outdoor Air Temperature :95 F (35.0 C) DB / 75 F (23.9 C) WB Product Data Product Data 45
46 Performance Data Cooling Capacity LSN090HXV/LSU090HXV Single Zone Mega Inverter Wall Mounted Engineering Manual Outdoor air temp. ( F DB) Outdoor air temp. ( F DB) Indoor Air Temp. F DB/ F WB 64/53 68/57 72/61 77/64 80/67 86/72 90/75 TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI DB = Dry Bulb Temperature ( F) WB = Wet Bulb Temperature ( F) TC = Total Capacity (kbtu/h). SC = Sensible Capacity (kbtu/h) PI = Power Input (kw) (includes compressor, indoor fan motor and outdoor fan motor). LSN120HXV/LSU120HXV Indoor Air Temp. F DB/ F WB 64/53 68/57 72/61 77/64 80/67 86/72 90/75 TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI DB = Dry Bulb Temperature ( F) WB = Wet Bulb Temperature ( F) TC = Total Capacity (kbtu/h). SC = Sensible Capacity (kbtu/h) PI = Power Input (kw) (includes compressor, indoor fan motor and outdoor fan motor). NOTES 1. All capacities are net, evaporator fan motor heat is deducted. 2. Grey shading Indicates reference data. When operating at this temperature, these values can be different by discontinuous operation. 3. Direct interpolation is permissible. Do not extrapolate 4. Capacities are based on the following conditions: - Interconnecting Piping Length 24.6 ft - Level Difference of Zero. - Indoor Air Temperature :80 F (26.7 C) DB / 67 F (19.4 C) WB - Outdoor Air Temperature :95 F (35.0 C) DB / 75 F (23.9 C) WB NOTES 1. All capacities are net, evaporator fan motor heat is deducted. 2. Grey shading Indicates reference data. When operating at this temperature, these values can be different by discontinuous operation. 3. Direct interpolation is permissible. Do not extrapolate 4. Capacities are based on the following conditions: - Interconnecting Piping Length 24.6 ft - Level Difference of Zero. - Indoor Air Temperature :80 F (26.7 C) DB / 67 F (19.4 C) WB - Outdoor Air Temperature :95 F (35.0 C) DB / 75 F (23.9 C) WB 46 Product Data
47 Performance Data Heating Capacity LSN090HEV/LSU090HEV Outdoor Air Indoor Air Temp. F DB Temperature ( F DB) ( F WB) TC PI TC PI TC PI TC PI TC PI TC PI TC PI DB = Dry Bulb Temperature ( F) WB = Wet Bulb Temperature ( F) TC = Total Capacity (kbtu/h). PI = Power Input (kw) (includes compressor, indoor fan motor and outdoor fan motor). NOTES 1. All capacities are net, evaporator fan motor heat is deducted. 2. Direct interpolation is permissible. Do not extrapolate 3. Capacities are based on the following conditions: - Interconnecting Piping Length 24.6 ft - Level Difference of Zero. - Indoor Air Temperature :70 F(21.1 C) DB / 60 F(15.6 C) WB - Outdoor Air Temperature : 47 F(8.3 C) DB / 43 F(6.1 C) WB Product Data LSN120HEV/LSU120HEV Outdoor Air Indoor Air Temp. F DB Temperature ( F DB) ( F WB) TC PI TC PI TC PI TC PI TC PI TC PI TC PI DB = Dry Bulb Temperature ( F) WB = Wet Bulb Temperature ( F) TC = Total Capacity (kbtu/h). PI = Power Input (kw) (includes compressor, indoor fan motor and outdoor fan motor). NOTES 1. All capacities are net, evaporator fan motor heat is deducted. 2. Direct interpolation is permissible. Do not extrapolate 3. Capacities are based on the following conditions: - Interconnecting Piping Length 24.6 ft - Level Difference of Zero. - Indoor Air Temperature :70 F(21.1 C) DB / 60 F(15.6 C) WB - Outdoor Air Temperature : 47 F(8.3 C) DB / 43 F(6.1 C) WB Product Data 47
48 Performance Data Heating Capacity Single Zone Mega Inverter Wall Mounted Engineering Manual LSN180HEV/LSU180HEV Outdoor Air Indoor Air Temp. F DB Temperature ( F DB) ( F WB) TC PI TC PI TC PI TC PI TC PI TC PI TC PI DB = Dry Bulb Temperature ( F) WB = Wet Bulb Temperature ( F) TC = Total Capacity (kbtu/h). PI = Power Input (kw) (includes compressor, indoor fan motor and outdoor fan motor). LSN240HEV/LSU240HEV NOTES 1. All capacities are net, evaporator fan motor heat is deducted. 2. Direct interpolation is permissible. Do not extrapolate 3. Capacities are based on the following conditions: - Interconnecting Piping Length 24.6 ft - Level Difference of Zero. - Indoor Air Temperature :70 F(21.1 C) DB / 60 F(15.6 C) WB - Outdoor Air Temperature : 47 F(8.3 C) DB / 43 F(6.1 C) WB Outdoor Air Indoor Air Temp. F DB Temperature ( F DB) ( F WB) TC PI TC PI TC PI TC PI TC PI TC PI TC PI DB = Dry Bulb Temperature ( F) WB = Wet Bulb Temperature ( F) TC = Total Capacity (kbtu/h). PI = Power Input (kw) (includes compressor, indoor fan motor and outdoor fan motor). NOTES 1. All capacities are net, evaporator fan motor heat is deducted. 2. Direct interpolation is permissible. Do not extrapolate 3. Capacities are based on the following conditions: - Interconnecting Piping Length 24.6 ft - Level Difference of Zero. - Indoor Air Temperature :70 F(21.1 C) DB / 60 F(15.6 C) WB - Outdoor Air Temperature : 47 F(8.3 C) DB / 43 F(6.1 C) WB 48 Product Data
49 Performance Data Heating Capacity LSN090HXV/LSU090HXV Outdoor Air Indoor Air Temp. F DB Temperature ( F DB) ( F WB) TC PI TC PI TC PI TC PI TC PI TC PI TC PI DB = Dry Bulb Temperature ( F) WB = Wet Bulb Temperature ( F) TC = Total Capacity (kbtu/h). PI = Power Input (kw) (includes compressor, indoor fan motor and outdoor fan motor). LSN120HXV/LSU120HXV NOTES 1. All capacities are net, evaporator fan motor heat is deducted. 2. Direct interpolation is permissible. Do not extrapolate 3. Capacities are based on the following conditions: - Interconnecting Piping Length 24.6 ft - Level Difference of Zero. - Indoor Air Temperature :70 F(21.1 C) DB / 60 F(15.6 C) WB - Outdoor Air Temperature : 47 F(8.3 C) DB / 43 F(6.1 C) WB Product Data Outdoor Air Indoor Air Temp. F DB Temperature ( F DB) ( F WB) TC PI TC PI TC PI TC PI TC PI TC PI TC PI DB = Dry Bulb Temperature ( F) WB = Wet Bulb Temperature ( F) TC = Total Capacity (kbtu/h). PI = Power Input (kw) (includes compressor, indoor fan motor and outdoor fan motor). NOTES 1. All capacities are net, evaporator fan motor heat is deducted. 2. Direct interpolation is permissible. Do not extrapolate 3. Capacities are based on the following conditions: - Interconnecting Piping Length 24.6 ft - Level Difference of Zero. - Indoor Air Temperature :70 F(21.1 C) DB / 60 F(15.6 C) WB - Outdoor Air Temperature : 47 F(8.3 C) DB / 43 F(6.1 C) WB Product Data 49
50 Single Zone Mega Inverter Wall Mounted Engineering Manual This page intentionally left blank. 50 Product Data
51 Application Guidelines Equipment Selection Procedure on page 52 Building Ventilation Design Guide on page 54 Placement Considerations on page 56
52 Equipment Selection Procedure Single Zone Mega Inverter Wall Mounted Engineering Manual Cooling / Heating Correction Factors For the Single Zone Mega Wall Mounted system, calculate the equivalent length of the liquid line from the outdoor unit to the indoor unit. Also, determine the elevation difference of the indoor unit above or below the outdoor unit. Find corresponding cooling or heating capacity correction factors as shown in Figure 18 and Figure 19. Multiply the correction factors by the cooling or heating capacity obtained from the capacity tables using design conditions. The resultant is the NET cooling or heating capacity. Capacity Coefficient Factors Figure 17: Cooling Capacity Coefficient Factor for LS090HEV/LS120HEV/LS180HEV/LS240HEV Capacity(%) Figure 18: Heating Capacity Coefficient Factor for LS090HEV/LS120HEV/LS180HEV/LS240HEV Capacity(%) Cooling 24.6 Heating k,12k 18k,24k Total Pipe Length (ft) 9k,12k 18k,24k Total Pipe Length (ft) 52 Application Guidelines
53 Equipment Selection Procedure Capacity Coefficient Factors - Continued Figure 19: Cooling Capacity Coefficient Factor for LS090HXV/LS120HXV Cooling 100 Capacity (%) k,12k Total Pipe Length (ft) Figure 20: Heating Capacity Coefficient Factor for LS090HXV/LS120HXV Heating Capacity (%) k,12k Application Guidelines 24.6 Total Pipe Length (ft) Application Guidelines 53
54 Building Ventilation Design Guide Building Ventilation Design Guide ASHRAE 62.1 and local codes specify the minimum volume of outdoor air that must be provided to an occupied space. Outdoor air is required to minimize adverse health effects, and it provides acceptable indoor air quality for building occupants. The three methods of accomplishing this with single zone systems are summarized here. Single Zone Mega Inverter Wall Mounted Engineering Manual Disclaimer Although we believe that these building ventilation methods have been portrayed accurately, none of the methods have been tested, verified, or evaluated by LG Electronics, U.S.A., Inc., In all cases, the designer, installer, and contractor should understand if the suggested method is used, it is used at their own risk. LG Electronics U.S.A., Inc., takes no responsibility and offers no warranty, expressed or implied, of merchantability or fitness of purpose if this method fails to perform as stated or intended. For a complete copy of Standard , refer to the American Standard of Heating and Air Conditioning Engineers (ASHRAE) website at For more information on how to properly size a ventilation air pretreatment system, refer to the article, "Selecting DOAS Equipment with Reserve Capacity" by John Murphy, published in the ASHRAE Journal, April Method 1: Decoupled Dedicated Outdoor Air System (DDOAS) Provide a separate, dedicated outdoor-air system designed to filter, condition, and dehumidify ventilation air and deliver it directly to the conditioned space through a separate register or grille. This approach requires a separate independent ventilation duct system not associated with single zone systems (Figure 21). LG recommends using the DDOAS method in all installations. Advantages Does not add additional heating or cooling loads to indoor units. May be used with all single zone systems. The outdoor air unit may supply neutral air to the occupant space even when the single zone indoor unit fan changes speed or cycles on and off. DDOAS controls do not have to be interlocked with the single zone system. In lieu of installing localized smaller outside air treatment equipment throughout the building, this method centralizes the ventilation air source making service and filter changes easier and less disruptive for the building occupants. Third-party demand control ventilation controls are more readily accommodated. Figure 21: Decoupled Dedicated Outdoor System Diagram Disadvantages Ceiling space is required to accommodate ductwork between the centralized outdoor air unit and ceiling diffusers. Methodology illustrations are for examples only and do not depict actual indoor units for the specific outdoor unit pairing. These are generic illustrations to show ventilation design only! Intake Grill Ceiling Diffuser Wall Mount Inverter Outdoor Air Outdoor Air Unit / ERV 54 Application Guidelines
55 Building Ventilation Design Guide Method 2: Unconditioned Outdoor Air (Non-Ducted, Natural Ventilation) Natural ventilation devices, such as operable windows or louvers may be used to ventilate the building when local code permits. The open area of a window or the free area of a louver must meet the minimum percentage of the net occupied floor area (Figure 22). Advantages Occupants control the volume of the ventilation air manually. Useful for historic buildings that have no ceiling space available for outdoor air ductwork. May be used with all single zone systems. Disadvantages In some locations, it may be difficult to control humidity levels when windows are open. Thermal comfort levels may be substandard when windows are open. Indoor units may have to be oversized to account for the added heating and cooling loads when windows are open. Provides outdoor air to perimeter spaces only. Additional mechanical ventilation system may be required to satisfy requirements for interior spaces. Outdoor air loads may be difficult to calculate since the quantity of outdoor air is not regulated. May affect indoor unit proper operation when open. Figure 22: Unconditioned Outdoor Air (Non-Ducted) Method 3: Unconditioned Outdoor Air (Non-Ducted, Fan Assisted Ventilation) When approved by local codes, the fan assisted ventilation method uses exhaust fans to remove air from the building, and outdoor air is drawn into occupied spaces through a wall louver or gravity roof intake hood. Supply fans can also be used to push the outdoor air into the space and building positive pressure will vent the exhaust air through louvers or roof-mounted exhaust hoods. Outdoor air is neither cooled nor heated before entering the building (Figure 23). This may result in loss of building pressurization control, increasing infiltration loads with adverse effects. Advantages Outdoor air may be manually controlled by the occupant or automatic controls may be installed to open/close outdoor air dampers or to turn on/off ventilation fans. Useful for large open spaces like warehouses, garages, and workshops. Outdoor air volume is a known quantity. Air loads may be easier to calculate since fans will regulate the amount of outdoor air. May be used with all single zone systems.. Methodology illustrations are for examples only and do not depict actual indoor units for the specific outdoor unit pairing. These are generic illustrations to show ventilation design only! Disadvantages In some locations of the country, it may be difficult to control humidity levels while outdoor air louvers/hoods are opened. Thermal comfort levels may be substandard when louvers/hoods are opened. Indoor units may have to be oversized to account for the added heating/cooling loads when louvers/hoods are open. Hot, cold, and/or humid areas may be present if the outdoor air is not evenly distributed to the different spaces. Application Guidelines Methodology illustrations are for examples only and do not depict actual indoor units for the specific outdoor unit pairing. These are generic illustrations to show ventilation design only! Roof Fan OA Wall Louver Figure 23: Unconditioned Outdoor Air (Non-Ducted) Damper Application Guidelines 55
56 Placement Considerations Single Zone Mega Inverter Wall Mounted Single Zone Mega Inverter Wall Mounted Engineering Manual Selecting the Best Location Select a location for installing the outdoor unit that will meet the following conditions: Where the unit will not be subjected to direct thermal radiation from other heat sources. Where operating sound from the unit will not disturb inhabitants of surrounding buildings. Where the unit will not be exposed to direct, strong winds. Where there is enough strength to bear the weight of the unit. Include space for drainage to ensure condensate flows properly out of the unit when it is in heating mode. Include enough space for air flow and for service access. To avoid the possibility of fire, do not install the unit in an area where combustible gas may generate, flow, stagnate, or leak. Do not install the unit in a location where acidic solution and spray (sulfur) are often used. Do not use the unit in environments where oil, steam, or sulfuric gas are present. Install a fence to prevent vermin from crawling into the unit or unauthorized individuals from accessing it. To ensure the outdoor unit operates properly, certain measures are required in locations where there is a possibility of heavy snowfall or severe windchill or cold: 1. Prepare for severe winter wind chills and heavy snowfall, even in areas of the country where these are unusual phenomena. 2. Position the outdoor unit so that its airflow fans are not buried by direct, heavy snowfall. If snow piles up and blocks the airflow, the system may malfunction. 3. Remove any snow that has accumulated by 3-15/16 inches or more on the top of the outdoor unit. 4. Place the outdoor unit on a raised platform at least 19-11/16 inches higher than the average annual snowfall for the area. In environments where there is a possibility of heavy snow, the frame height must be more than two (2) times the amount of average annual snowfall, and should not exceed the width of the outdoor unit. If the frame width is wider than the outdoor unit, snow may accumulate. 5. Install a snow protection hood. 6. To prevent snow and heavy rain from entering the outdoor unit, install the suction and discharge ducts facing away from direct winds. Additionally, the following conditions should be taken into considerations when the unit operates in defrost mode: If the outdoor unit is installed in a highly humid environment (near an ocean, lake, etc.), ensure that the site is well-ventilated and has a lot of natural light. (Example: Install on a rooftop.) Sidewalks or parking lots near the outdoor unit may accumulate moisture after unit operates in defrost mode that can turn to ice. The indoor unit may take longer to provide heat, or heating performance will be reduced in winter if the unit is installed: 1. In a narrow, shady location. 2. Near a location that has a lot of ground moisture. 3. In a highly humid environment. 4. In an area in which condensate does not drain properly. 56 Application Guidelines
57 Placement Considerations Outdoor Installation General Mounting Securely attach the outdoor unit to a condenser pad, base rails, or other mounting platform that is securely anchored to the ground or building structure. Attach the ODU with a bolt and nut onto a concrete or rigid mount (Figure 24). Refer to installation manual and follow the applicable local code for clearance, mounting, anchor, and vibration attenuation requirements. Figure 24: Single Zone Mega Inverter Outdoor Unit Mounting Methods All referenced materials are to be field-supplied. Images are not to scale. Bolt Placement & Anti-Vibration Pad Foundation Top of Unit Piping connection Mounting Platform The underlying structure or foundation must be designed to support the weight of the unit. Avoid placing the unit in a low lying area where water may accumulate. When installing ODU on the wall, or roof top, anchor the mounting base securely using nails or wire with regard to wind and earthquake or vibration. Tie-Downs and Wind Restraints The strength of the Single Zone Mega Inverter frame is adequate to be used with field-provided wind restraint tie-downs. The overall tiedown configuration must be approved by a local professional engineer. Always refer to local code when designing a wind restraint system. Snow and Ice Conditions In climates that experience snow buildup, place the unit on a raised platform to ensure proper condenser airflow. The raised support platform must be high enough to allow the unit to remain above possible snow drifts. Mount the unit on a field-provided snow stand at a minimum height that is equal to the average annual snowfall, plus 20 inches. Design the mounting base to prevent snow accumulation on the platform in front or back of the unit case. If necessary, provide a field fabricated hood to keep snow and ice and/or drifting snow from accumulating on the coil surfaces. Use inlet and discharge duct or hoods to prevent snow or rain from accumulating on the fan inlet and outlet guards. Best practice prevents snow from accumulating on top of the unit. Consider tie-down requirements in case of high winds or where required by local codes. Application Guidelines When deciding on a location to place the outdoor unit, be sure to choose an area where run-off from defrost will not accumulate and freeze on sidewalks or driveways. Ambient Air Conditions Avoid exposing the outdoor unit to steam, combustible gases, or other corrosive elements. Avoid exposing the unit to discharge from boiler stacks, chimneys, steam relief ports, other air conditioning units, kitchen vents, plumbing vents, and other sources of extreme temperature, gases, or substances that may degrade performance or cause damage to the unit. When installing multiple outdoor units, avoid placing the units where discharge of one outdoor unit will blow into the inlet side of an adjacent unit. Application Guidelines 57
58 Placement Considerations Outdoor Installation Single Zone Mega Inverter Wall Mounted Outdoor Unit Clearance Proper airflow through the outdoor unit coil is critical for proper unit operation. When installing the outdoor unit, consider service, inlet, and outlet, and minimum allowable space requirements as illustrated in the diagrams below. All unit clearance measurements are in inches. Single Zone Mega Inverter Wall Mounted Engineering Manual Figure 25: Single Zone Mega Inverter Outdoor Unit Clearance Outdoor Unit Clearance When placing the outdoor unit near a fence, wall or other large obstacle, observe the clearance requirements as shown in Figure 27. This clearance ensures that heat radiation from the condenser is not restricted around the unit. Adhere to all clearance requirements if installing the unit on a roof. Be sure to level the unit and ensure that unit is adequately anchored. Consult local codes regarding rooftop mounting. Figure 26: Single Zone Mega Inverter Outdoor Unit Next to Wall - Clearance Unit: Inch Sunroof Outdoor Unit Wall Clearance Figure 27: Single Zone Mega Inverter Outdoor Unit Under Roof/Overhang Overhang Or Roof Do not place the unit where animals and/or plants will be in the path of the warm air; or where the warm air and/or noise will disturb neighbors. Unit: Inch 58 Application Guidelines
59 Refrigerant Piping Design & Layout Best Practices Refrigerant Piping Design on page 60 "Selecting Field-Supplied Copper Tubing" on page 61 "Refrigerant Piping System Layout" on page 62 "Piping Connection" on page 59 "Electrical Connections" on page 67 "Mechanical Specifications" on page 69 "Acronyms" on page 71
60 Refrigerant Piping Design Design Guideline Summary Device Connection Limitations A Single Zone Mega Inverter Wall Mounted system consists of one outdoor unit and one indoor unit. One of the most critical elements of a Single Zone Mega Inverter Wall Mounted system is the refrigerant piping. Table 11 below lists pipe length limits that must be followed in the design of a Single Zone Wall Mount refrigerant pipe system. Refer to Figure 28 for system layout. Single Zone Mega Inverter Wall Mounted Engineering Manual Table 11: Single Zone Mega Inverter Wall Mount Refrigerant Piping System Limitations Pipe Length (ELF = Equivalent Length of pipe in Feet) Elevation (All Elevation Limitations are Measured in Actual Feet) DFS System Layout Figure 28: Typical DFS System Layout Max Length = A Max Elevation = B Indoor unit Shortest total equivalent piping length Longest total equivalent piping length Piping Length (no additional refrigerant) Distance between fittings and indoor or outdoor units If outdoor unit is above indoor unit If outdoor unit is below indoor unit B A Outdoor unit LSU090HEV/ LSU120HEV LSU180HEV/ LSU240HEV LSU090HXV/ LSU120HXV 9.8 feet 9.8 feet 6.6 feet 49.2 feet 65.6 feet 49.2 feet 24.6 feet 24.6 feet 24.6 feet 20 inches 20 inches 20 inches 22.9 feet 32.8 feet 23 feet 22.9 feet 32.8 feet 23 feet Indoor unit A Unit = Feet Outdoor unit B 60 Refrigerant Design
61 Refrigerant Piping Design Selecting Field-Supplied Copper Tubing Table 12: Linear Thermal Expansion of Copper Tubing in Inches Pipe Fluid Temperature F Length Pipe length baseline temperature = 0 F. "Expansion of Carbon, Copper and Stainless Steel Pipe," The Engineers' Toolbox, Figure 29: Coiled Expansion Loops and Offsets. L R L Large Tubing U-bend (>3/4 in.) Loop Small Tubing U-bend (<3/4 in.) in.) Table 13: Radii of Coiled Expansion Loops and Developed Lengths of Expansion Offsets Anticipated Linear Expansion (LE) (inches) 1/ / / /2 4 Nominal Tube Size (OD) inches 1/4 3/8 1/2 3/4 R L R L R L R L R L R L R L R L R L Refrigerant Piping Design & Layout Best Practices 1 R = Centerline Length of Pipe. 2 L = Centerline Minimum Radius (inches). Refrigerant Design 61
62 Installation & Layout Best Practices Refrigerant Piping System Layout Definitions Physical Pipe Length: Actual length of straight segment(s) of pipe. Equivalent Pipe Length: Actual length of pipe plus equivalent lengths of elbows and valves. Single Zone Mega Inverter Wall Mounted Engineering Manual Layout Procedure 1. Draft a one-line diagram of the proposed piping system connecting outdoor unit to indoor unit. Follow the pipe limitations listed. Using Elbows Field-supplied elbows are allowed as long as they are designed for use with R410A refrigerant. The designer, however, should be cautious with the quantity and size of fittings used, and must account for the additional pressure losses in equivalent pipe length calculation. The equivalent pipe length of each elbow must be added to each pipe segment. See Table 14 for equivalent lengths. Field-Provided Isolation Ball Valves It is acceptable to install field-supplied ball valves with Schrader ports at the indoor unit. Full-port isolation ball valves with Schrader ports (positioned between valve and the indoor unit) rated for use with R410A refrigerant should be used on both the liquid and vapor lines. If valves are not installed and the indoor unit needs to be removed or repaired, the entire system must be shut down and evacuated. Obstacles When an obstacle, such as an I-beam or concrete T, is in the path of the planned refrigerant pipe run, it is best practice to route the pipe over the obstacle. If adequate space is not available to route the insulated pipe over the obstacle, then route the pipe under the obstacle. In either case, it is imperative the horizontal section of pipe above or below the obstacle be a minimum of three (3) times greater than the longest vertical rise (or fall) distance (Figure 30). 2. Calculate the physical length of each pipe segment and note it on the drawing. 3. Calculate the equivalent pipe length of each pipe segment. Table 14: Equivalent Piping Length for Piping Components Size (Inches) Component 1/4 3/8 1/2 5/8 3/4 Elbow (ft.) Position valves with a minimum distance of three (3) to six (6) inches of pipe on either side of the valve. Valves shall be easily accessible for service. If necessary, install drywall access doors or removable ceiling panels, and position the valves to face the access door or ceiling panel opening. Mount valves with adequate space between them to allow for placement of adequate pipe insulation around the valves. Recommended best practice is to clearly label and document locations of all service valves. The equivalent pipe length of each ball valve must be added to each pipe segment. Figure 30: Installing Piping Above and Below an Obstacle Above an obstacle. 3X Minimum Below an obstacle. 62 Refrigerant Design
63 Installation & Layout Best Practices Refrigerant Piping System Layout In-line Refrigeration Components Components such as oil traps, solenoid valves, filter-dryers, sight glasses, tee fittings, and other after-market accessories are not permitted on the refrigerant piping system between the outdoor unit and the indoor unit. Single Zone Mega Inverter Wall Mounted air-source systems are provided with redundant systems that assure oil is properly returned to the compressor. Sight-glasses and solenoid valves may cause vapor to form in the liquid stream. Over time, dryers may deteriorate and introduce debris into the system. The designer and installer should verify the refrigerant piping system is free of traps, sagging pipes, sight glasses, filter dryers, etc. No Pipe Size Substitutions Using a different size is prohibited and may result in a system malfunction or failure to work at all. Pipe Supports A properly installed pipe system should be adequately supported to avoid pipe sagging. Sagging pipes become oil traps that lead to equipment malfunction. Pipe supports should never touch the pipe wall; supports shall be installed outside (around) the primary pipe insulation jacket (seefigure 31). Insulate the pipe first because pipe supports shall be installed outside (around) the primary pipe insulation jacket. Clevis hangers should be used with shields between the hangers and insulation. Field provided pipe supports should be designed to meet local codes. If allowed by code, use fiber straps or split-ring hangers suspended from the ceiling on all-thread rods (fiber straps or split ring hangers can be used as long as they do not compress the pipe insulation). Place a second layer of insulation over the pipe insulation jacket to prevent chafing and compression of the primary insulation within the confines of the support pipe clamp. A properly installed pipe system will have sufficient supports to avoid pipes from sagging during the life of the system. As necessary, place supports closer for segments where potential sagging could occur. Maximum spacing of pipe supports shall meet local codes. If local codes do not specify pipe support spacing, pipe shall be supported as follows: Maximum of five feet (5 ) on center for straight segments of pipe up to 3/4" outside diameter size. Wherever the pipe changes direction, place a hanger within twelve (12) inches on one side and within twelve to nineteen (12 to 19) inches of the bend on the other side as shown in Figure 33. Figure 31: Pipe Hanger Details Figure 32: Typical Pipe Support Location Change in Pipe Direction Figure 33: Pipe Support at Indoor Unit ~ 12" 19" B Max. 12" Refrigerant Piping Design & Layout Best Practices A A + B ~ 12" 19" Refrigerant Design 63
64 Installation & Layout Best Practices Refrigerant Piping System Layout Pipe Sleeves at Penetrations LG requires that all pipe penetrations through walls, floors, and pipes buried underground be properly insulated and routed through an appropriate wall sleeve of sufficient size to prevent compression of refrigerant pipe insulation and free movement of the pipe within the sleeve (Figure 34). Underground refrigerant pipe shall be routed inside a protective sleeve to prevent insulation deterioration. Figure 34: Pipe Sleeve Options. Single Zone Mega Inverter Wall Mounted Engineering Manual Diameter of penetrations shall be determined by pipe diameter plus the thickness of the insulation. Underground Refrigerant Piping Refrigerant pipe installed underground should be routed inside a vapor tight protective sleeve to prevent insulation deterioration and water infiltration. Refrigerant pipe installed inside underground casing must be continuous without any joints. Underground refrigerant pipe must be located at a level below the frost line.(figure 35). Table 15: Utility Conduit Sizes (Inches) Liquid Pipe 1 Vapor Pipe 1 3/8 (1-1/8 2,3 ) 1/2 (2.0 2,4 ) 5/8 (2-1/8 2,4 ) 1/4 (1.0) /8 (1-1/8) OD pipe diameter in inches; Values in parenthesis () indicate OD of pipe with insulation jacket. 2 Diameter of pipe with insulation. Thickness of pipe insulation is typical. Actual required thickness may vary based on surrounding ambient conditions and should be calculated and specified by the design engineer. 3 Insulation thickness (value in parenthesis) = 3/8 inch. 4 Insulation thickness (value in parenthesis) = 3/4 inch. Figure 35: Typical Arrangement of Refrigerant Pipe and Cable(s) in a Utility Conduit. Model Vapor Line Insulation Material Liquid Line Pipe Sleeve Insulation Material Min. 18 Gauge Power/Communication Cable Table 16: Heat Pump Unit Refrigerant Pipe Connections (All Brazed Type) Liquid Conn. (inches) Vapor Conn. (inches) LSU090HEV, LSU120HEV 1/4 3/8 LSU180HEV 1/4 1/2 LSU240HEV 1/4 5/8 LSU090HXV, LSU120HXV 1/4 3/8 64 Refrigerant Design
65 Installation & Layout Best Practices Piping Connection Single Zone Mega Inverter Connections Pipe Connection for a Single Zone Inverter System 1. Remove the tubing cover from the unit by loosening the fastening screws (Figure 36). 2. Align the center of the refrigerant pipe and corresponding connection as shown in Figure 37 and tighten the flare nut initially by hand. 3. Finish tightening the flare nut with a torque wrench until the wrench clicks. Follow the guidelines as outlined in Table 15 for the amount of torque to use. When tightening the flare nut with torque wrench, ensure the direction for tightening follows the arrow on the wrench. Table 17: Torque Wrench Tightening Outside Diameter (Inches) Torque (Lbs.-ft) 1/ / / / / Figure 36: Outdoor Unit Connection Cover Removal Terminal Block Piping connection 1(L1) 2(L2) 1(L1) 2(L2) 3 Power cord Figure 37: Heat Pump Outdoor Unit Piping Connection Cord clamp Power connecting cable Conduit cover Tubing cover Refrigerant Piping Design & Layout Best Practices Outdoor unit Gas side piping (Bigger diameter) Liquid side piping (Smaller diameter) Torque wrench Refrigerant Design 65
66 Installation & Layout Best Practices Refrigerant Piping System Layout Installation of Refrigerant Piping / Brazing Practices Keep the piping system free of contaminants and debris such as copper burrs, slag, or carbon dust during installation. Single Zone Mega Inverter Wall Mounted Engineering Manual All joints are brazed in the field. Single Zone Mega Inverter Wall Mounted refrigeration system components contain very small capillary tubes, small orifices, electronic expansion valves, oil separators, and heat exchangers that can easily become blocked. Proper system operation depends on the installer using best practices and utmost care while assembling the piping system (see Figure 38). While brazing, use a dry nitrogen purge operating at a minimum pressure of three (3) psig and maintain a steady flow. Blow clean all pipe sections with dry nitrogen prior to assembly. Use a tubing cutter, do not use a saw to cut pipe. De-burr and clean all cuts before assembly. Store pipe stock in a dry place. Keep pipe capped and clean. Use adapters to assemble different sizes of pipe. Do not use flux, soft solder, or anti-oxidant agents. Figure 38: Refrigerant Pipe Brazing. Refrigerant Piping Pipe to be brazed Nitrogen Taping Pressure-reducing Valve Use a 15% silver phosphorous copper brazing alloy to avoid overheating and produce good flow. Protect isolation valves, electronic expansion valves, and other heat-sensitive control components from excessive heat with a wet rag or a heat barrier spray product Refrigerant Piping System Insulation All refrigerant piping, field-provided isolation ball valves, service valves, and elbows shall be completely insulated using closed cell pipe insulation. The liquid and vapor lines must be insulated separately. To prevent heat loss/heat gain through the refrigerant piping, all refrigerant piping including liquid lines, and vapor lines shall be insulated separately. Insulation shall be a minimum 1/2 thick, and thickness needs to be increased based on ambient conditions and local codes. All insulation joints are to be glued with no air gaps. Insulation material must fit snugly against the refrigeration pipe with no air space between it and the pipe. Insulation passing through pipe hangers, inside conduit, and/or sleeves must not be compressed. Protect insulation inside hangers and supports with a second layer. All pipe insulation exposed to the sun and outdoor elements shall be properly protected with PVC, aluminum vapor barrier, or alternatively placed in a weather-resistant enclosure such as a pipe rack with a top cover; and meet local codes. The design engineer performs calculations to determine if the factory-supplied insulation jackets are sufficient to meet local codes and avoid sweating. Add additional insulation if necessary. Mark all pipes at the point where the insulation jacket ends. Remove the jacket. Install field provided insulation on the run-out and main trunk pipes first. Peel the adhesive glue protector slip from the insulation jacket and install the clam-shell jacket over the fitting. Valve 66 Refrigerant Design
67 Electrical Connections Outdoor Electrical Connection The procedure to connect electrical wiring for the Mega Inverter and Mega 115V Inverter is the same; however, the terminal block identification will be different for each model. Refer to Figure 39 for the Mega Inverter (HEV model) and Figure 40 for the Mega 115V Inverter (HXV model). Procedure 1. Remove the conduit cover from the unit by loosening the fastening screws (Figure 39 and Figure 40 (HXV)). 2. Take off the caps on the conduit panel. 3. Connect both the power supply and low voltage lines to the corresponding terminals on the terminal block. Use the circuit diagram posted inside the conduit cover as guidance. 4. Be sure to ground the unit by following local codes. 5. Allow for enough length (add several inches) for each wiring. 6. Secure the cable with the cord clamp. 7. Secure conduit tubes with lock nuts. 8. Refix the control cover to the original position with the fastening screw. Be sure that the wire color codes of the outdoor unit match those of the indoor unit. Be sure screws are tightly fastened. Loose wires can cause wires to burn out. Confirm that electrical capacity in sufficient prior to connecting wires. Verify that voltage is maintained at more than 90 percent of the rated voltage, as indicated on the name plate. Always install an earth leakage circuit breaker at a wet or moist site. Check the following in case of voltage drop: -- Vibration of a magnetic switch which can damage the contact point -- Broken fuse -- Overload of power during normal function Figure 39: Mega HEV Model - Electrical Connection to Outdoor Unit Terminal Block 1(L1) 2(L2) 1(L1) 2(L2) 3 Power cord Cord clamp Power connecting cable Conduit Cover Tubing Cover Figure 40: Mega HXV Model - Electrical Connection to Outdoor Unit Terminal Block L N 1(L) 2(N) 3 Power cord Cord clamp Power connecting cable Conduit Cover Electrical Connections & Mechanical Specifications Tubing Cover Refrigerant Design 67
68 Electrical Connections Outdoor Electrical Connection (Continued) Use of Circuit Breaker Outdoor units and indoor units must be provided power from separate breakers. Each outdoor unit must be provided a dedicated fused disconnect or breaker: Install a main shutoff switch that interrupts all power sources simultaneously. Single Zone Mega Inverter Wall Mounted Engineering Manual Always use a circuit breaker or time delay fuse when connecting electrical wiring to the unit (Figure 41). Comply with local codes while running wire from the indoor unit to the outdoor unit. Be sure to connect wire firmly. Separately wire the high and low voltage lines. Use heat-proof electrical wiring capable of withstanding temperatures up to 167 F. Use outdoor and waterproof connection cable rated up to 300V for the connection between indoor and outdoor unit. Do not allow wire to touch refrigerant tubing, the compressor or any moving parts. Figure 41: Circuit Breaker/Time Delay Fuse Connection Main Power Source Air Conditioner Circuit Breaker Use a circuit breaker Or time delay fuse 68 Refrigerant Design
69 Mechanical Specifications Single Zone Mega Inverter General LG Single Zone Mega Inverter Wall Mounted system comprises of a single outdoor unit connected to a single indoor unit with a single refrigerant circuit. An LG Single Zone Mega Inverter Wall Mounted system is a Duct-Free Split system that can operate in either cooling or heating mode. The system shall be capable of changing mode within a maximum time of three (3) minutes to ensure indoor temperature can be properly maintained. LG Single Zone Mega Inverter Wall Mounted is manufactured in a facility registered to ISO 9001 and ISO 14001, which is a set of standards applying to environmental protection set by the International Organization for Standardization (ISO). The units are listed by Intertek Electrical Testing Laboratories (ETL) and bear the ETL label. Wiring in these units are in accordance with the National Electrical Code (NEC). Temperature Ranges Single Zone Mega Operating ranges for outdoor unit of 64 F to 118 F (DB) for cooling; 23 F to 65 F (WB) for heating Operating ranges for indoor unit of 53 F to 75 F (WB) for cooling; 60 F to 86 F (DB) for heating Single Zone Mega 115V Operating ranges for outdoor unit of 14 F to 118 F (DB) for cooling; 14 F to 65 F (WB) for heating Operating ranges for indoor unit of 53 F to 75 F (WB) for cooling; 60 F to 86 F (DB) for heating Casing / Frame Outdoor unit is constructed with pre-coated metal (PCM). Indoor unit is constructed of heavy duty Acrylonitrile Butadiene Styrene (ABS) and High Impact Polystyrene (HIPS) plastic. Refrigerant System The refrigeration system consists of a single refrigeration circuit and uses R410A refrigerant. The outdoor unit is provided with factory installed components, including a refrigerant strainer, check valves, oil separator, accumulator, four-way reversing valve, capillary tube (HEV) or EEV (HXV), high and low side charging ports, service valves, and interconnecting piping. Refrigeration Oil Control Heat Pump outdoor units have a centrifugal oil separator and controls to ensure sufficient oil supply is maintained, and that oil does not travel with the refrigerant. Compressors The outdoor unit is equipped with one hermetic digitally controlled inverter driven rotary (9k/12k Btu/h systems) or twin-rotary (18k/24k Btu/h systems) compressor to modulate capacity (modulation in 1 Hz increments). Frequency ranges for the (HEV) outdoor units are: 9k Btu/h = 20 to 80 Hz 12k Btu/h = 20 to 90 Hz 18/24k Btu/h = 15 to 100 Hz Frequency ranges for the (HXV) outdoor units are: 9k Btu/h = 15 to 100 Hz 12k Btu/h = 15 to 100 Hz Over-current protection and vibration isolation are integrated with the compressor. Outdoor Unit Coil Heat Pump outdoor unit coils are of a nonferrous construction with louvered fins on copper tubing, and are protected with an integral coil guard. Coil fins have a factory applied corrosion resistant GoldFin material with hydrophilic coating. Fans and Motors The outdoor unit includes one direct drive, variable speed propeller type fan. The Brushless Digitally Controlled (BLDC) fan motor has inherent protection, permanently lubricated bearings, and variable speed with a maximum speed up to 950 rpm. Raised guards are provided to limit contact with moving parts. The outdoor unit has horizontal discharge airflow. Electrical The HEV model unit is available in a V 60 Hz, 1-phase power supply. The HXV model unit is available in a 115V 60 Hz, 1-phase power supply. The units are capable of operating within voltage limits of ±10% rated voltage, and include overcurrent protection. Controls The unit is factory wired with necessary electrical control components, integral microprocessors, printed circuit boards, thermistors, sensors, terminal blocks, and lugs for power wiring. Microprocessor-based algorithms provide component protection, soft-start capability, refrigeration system pressure, temperature, defrost, and ambient control. Electrical Connections & Mechanical Specifications Refrigerant Design 69
70 Single Zone Mega Inverter Wall Mounted Engineering Manual This page intentionally left blank. 70 Refrigerant Design
71 Acronyms Table 18: Table of Acronyms ABS Acrylonitrile Butadiene Styrene kw Kilo Watts AC Air Conditioner LED Light Emitting Diode ACP Advanced Control Platform LEED Leadership in Energy and Environmental Design ASHRAE AWG BLDC Btu/h BUS CFM DB db(a) DDOAS DI DFS DO DPST EEV ELF ETL H/M/L HIPS HVAC ID IDU ISO American Society of Heating, Refrigeration, and Air Conditioning American Wire Gauge Brushless Digitally Controlled British Thermal Units per hour Binary Unit System Cubic Feet per Minute Dry Bulb Decibels with A frequency weighting Decoupled Dedicated Outdoor Air System Digital Input Duct Free Split Digital Output Double-Pole Single-Throw (switch) Electronic Expansion Valve Equivalent Length in Feet Electronic Testing Laboratories High/Medium/Low High Impact Polystyrene Heating,Ventilation and Air Conditioning Innovations in Design (LEED Related) Indoor Unit International Organization for Standardization MBh MCA MOP MSC NC NEC NO ODU PCB PCM PDI PI PR PVC SW or S/W USB VAC VRF WB Thousands BTUs per hour Maximum Circuit Ampacity Maximum Overcurrent Protection Maximum Starting Current Noise Criterion (regarding Sound Pressure Levels) New Construction (LEED Related) Normally Closed National Electrical Code Number Outdoor Unit Printed Circuit Board Pre-Coated Metal Power Distribution Indicator Power Input Prerequisite (LEED Related) Polyvinyl Chloride Switch Universal Serial BUS Voltage Alternating Current Variable Refrigerant Flow Wet Bulb Electrical Connections & Mechanical Specifications Refrigerant Design 71
72 ISO 9001: 2008 LG ELECTRONICS INC. lg electronics commercial Air conditioning division Old Roswell Road Alpharetta, georgia lg electronics commercial products support USA Follow the prompts for commercial A/C products. EM-SZ_Mega_Mega115V Supersedes: DFS-EM-AL-001-US_014D09
Single-Zone Four-Way Ceiling-Cassette System Engineering Manual
Single-Zone Four-Way Ceiling-Cassette System Engineering Manual Single-Zone Four-Way Ceiling Cassette Heat Pump Systems 1.5 to 3.5 Tons LC187HV (18,000 Btu/h) LC247HV (24,000 Btu/h) LC367HV (36,000 Btu/h)
innovative comfort solutions
engineering and specifications Guide duct-free air conditioning systems Art cool inverter flex multi-split floor standing ceiling cassette PTAC PTHP through-the-wall innovative comfort solutions 1 AT LG,
technical data air conditioning systems RXS20-25-35E (single phase) FBQ-B8V1-B8V3B Split Heat Pump Condensing Units Split Sky Air
technical data RXS20-25-35E FBQ-B8V-B8V3B (single phase) Split Heat Pump Condensing Units air conditioning systems Split Sky Air Outdoor Units R-40A RXS-E2VB Split Sky Air Outdoor Units Features O u t
FTQ. Daikin Inverter Ducted Heat Pump
FTQ Daikin Inverter Ducted Heat Pump A TRADITIONAL CENTRAL AIR SYSTEM MADE BETTER WITH DAIKIN CONSTANT COMFORT INVERTER TECHNOLOGY. The Daikin Inverter Ducted Heat Pump line is a cost effective alternative
Air Conditioners Technical Data
Air Conditioners Technical Data O u t d o o r U n i t E E D E N 2-0 0 RX-JV Outdoor Unit RX-JV TABLE OF CONTENTS RX-JV Features............................................................. 2 2 Specifications.......................................................
Residential and Light Commercial Air Conditioning Systems
Residential and Light Commercial Air Conditioning Systems Beautifully Designed to Save Engineering and Specifications Guide Beautifully Designed to Save As air conditioners have reached high levels of
ECO-AIR AIR CONDITIONING www.northamericanhvac.com
INDEX ACCESSORIES INSTALLATION... 3-7 LINE SETS... 3-7 GEOTHERMAL... 3-8 WIRING CABLE... 3-8 CIRCULATOR PUMPS (PRO-TECH MODEL)... 3-9 DC INVERTER SINGLE ZONE HEAT PUMP... 3-6 DC INVERTER TECHNOLOGY...
New Deluxe Wall Mounted Heat Pump Series EXTERIOS
New Deluxe Wall Mounted Heat Pump Series EXTERIOS May 2013 New Deluxe Wall Mounted Heat Pump Series Panasonic Adding New Air Conditioner Lineup Setting Another Mile Stone in the US Ductless Split History
Europe Inverter Single 50Hz(R410A) 5RMI0-04B(Replace : 5RMI0-04A)
Europe 50Hz(R410A) 5RMI0-04B(Replace : 5RMI0-04A) -50Hz(R410A) 1. Models line up 2. Nomenclature 3. Features & Benefits 4. Specifications 5. Dimensions 6. Wiring diagrams 7. Refrigerant cycle diagrams
PRODUCT CATALOG. Indoor Units
PRODUCT CATALOG Indoor Units Life s Good! From installation to maintenance, LG runs more than 60 global air conditioning academies, each provides training for air conditioning professionals. What is LG?
LG Air Conditioning Solutions COMFORT MADE EASY. COMFORT MADE BEAUTIFUL.
Residential Brochure LG Air Conditioning Solutions COMFORT MADE EASY. COMFORT MADE BEAUTIFUL. LG DUCT-FREE Split SYSTEMS BRING COMFORTING INNOVATION LG Duct-Free Split systems allow you to cool or heat
FHQ. Ceiling Suspended Heat Pump or Cooling Only
FHQ Ceiling Suspended Heat Pump or Cooling Only EXPERTISE AND INNOVATION Daikin s FHQ ceiling suspended SkyAir systems are ideal for applications without false ceilings. Installed from the structure, this
FCQ. Roundflow Cassette Heat Pump or Cooling Only
FCQ Roundflow Cassette Heat Pump or Cooling Only EXPERTISE AND INNOVATION Daikin s FCQ roundflow cassette SkyAir systems are ideal for open plan applications where variances in temperature and airflow
Residential and Light Commercial Air Conditioning Systems
Residential and Light Commercial Air Conditioning Systems Beautifully Designed to Save Engineering and Specifications Guide Beautifully Designed to Save As air conditioners have reached high levels of
PRODUCT CATALOG. You re looking at the future of VRF
PRODUCT CATALOG You re looking at the future of VRF From installation to maintenance, LG runs more than 60 global air conditioning academies, each provides training for air conditioning professionals.
FTXS. Wall Mount Heat Pump or Cooling Only
FTXS Wall Mount Heat Pump or Cooling Only EXPERTISE AND INNOVATION Daikin s FTXS SkyAir systems feature streamlined, wall mounted indoor units paired with quietly compact outdoor units. Available in both
york air-conditioning products Residential & VRF News 2015
york air-conditioning products Residential & VRF News 2015 york air-conditioning products Catalogue Content Split Systems Pag. High wall High Efficiency Inverter YWHJZH 09 to 24 K 6 High wall Inverter
HP switch LP switch Discharge thermo Comp. Surface thermo
1 Specifications Zubadan Model Name PUHZ-SHW80VHA PUHZ-SHW11VHA PUHZ-SHW11YHA Power supply (phase, cycle, voltage) 1φ, V, Hz 1φ, V, Hz 3φ, 0V, Hz Max. current A 9.5 35.0 13.0 Breaker size A 3 16 Outer
FBQ. DC Duct Heat Pump or Cooling Only
FBQ DC Duct Heat Pump or Cooling Only EXPERTISE AND INNOVATION Daikin s FBQ DC Duct systems offer a powerful solution, compact in design and easily concealed in a ceiling. With both cooling only and heat
LG Electronics AE Company, Commercial Air Conditioning
www.lgeaircon.com New concept Ecofriendly Highefficiency Heating solution Total heating & Hot water Solution for MULTI V LG Electronics AE Company, Commercial Air Conditioning 2 Yeouidodong, Yeongdeungpogu,
2010 Duct-Free Splits Line Card
2010 Duct-Free Splits Line Card Right Product for the Right Application 2010 Duct-Free Splits Right Product for the Right Application 1:1 2:1 to 4:1 9-24K High Walls 18-24/36/42/60K High Wall, Cassette,
Glossary of Heating, Ventilation and Air Conditioning Terms
Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment
LG Duct-Free Split Systems Product Overview. LG comfort solutions that you never thought possible
LG Duct-Free Split Systems Product Overview LG comfort solutions that you never thought possible TABLE OF CONTENTS Company Introduction Introduction 4 Duct Free System Introduction 6 Key Features 8 Duct-Free
SERVICE MANUAL MUZ-GE09NA MUZ-GE12NA MUZ-GE15NA MUZ-GE18NA MUZ-GE24NA MUY-GE09NA MUY-GE12NA MUY-GE15NA MUY-GE18NA MUY-GE24NA OUTDOOR UNIT
SPLIT-TYPE AIR CONDITIONERS Revision B: Descriptions regarding the outdoor fan motor have been corrected. Please void OBH549 REVISED EDITION-A. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH549 REVISED
Air Conditioners. Technical Data. Wall Mounted Unit. www.daikin.eu RX-JV/GV
Air Conditioners Technical Data Wall Mounted Unit www.daikin.eu RX-JV/GV Air Conditioners Technical Data Wall Mounted Unit www.daikin.eu RX-JV/GV TABLE OF CONTENTS RX-JV/GV 1 Features.............................................................
DUCTLESS MINI-SPLITS SINGLE & MULTI-ZONE HORIZONTAL AIR CONDITIONERS PORTABLE UNITS FREE MATCH COMPONENTS
DUCTLESS MINI-SPLITS SINGLE & MULTI-ZONE HORIZONTAL AIR CONDITIONERS PORTABLE UNITS FREE MATCH COMPONENTS AN EXCELLENT CHOICE IN COOLING, COMFORT AND CONVENIENCE Why choose a Mini-Split system? Installing
Split System Cooling Product Data
Split System Cooling Product Data XR17 4TTR7 2, 3, 4 & 5 Tons PUB. NO. 22-1884-01 Features and Benefits CLIMATUFF 2-stage scroll compressor Efficiency up to 18.0 SEER All Aluminum SPINE FIN coil DURATUFF
HVAC Systems: Overview
HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct
MAC-120HE-01 Air-Cooled Chiller
MAC-120HE-01 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 208/230-1-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-01
SERVICE MANUAL OUTDOOR UNIT MUZ-A09NA,- 1,- U1,- U2 MUZ-A12NA,- U1 MUZ-A15NA,- U1 MUZ-A17NA,- U1 MUY-A15NA MUY-A17NA MUY-A24NA,- 1,- U1,- U2
SPLIT-TYPE AIR CONDITIONERS Revision E: MUZ-GA24NA and MUY-GA24NA have been added. Please void OB451 REVISED EDITION-D. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OB451 REVISED EDITION-E Models MUZ-A09NA,-
Split System Cooling Product Data
Split System Cooling Product XL16i 1½ 5 Tons PUB. NO. 22-1890-01 Features and Benefits Climatuff compressor Efficiency up to 16.0 SEER and 9.0 HSPF All aluminum Spine Fin coil WeatherGuard fasteners Quick-Sess
SERVICE MANUAL OUTDOOR UNIT. No. OBH590 REVISED EDITION-B. Models HFC
SPLIT-TYPE AIR CONDITIONERS Revision B: MUZ-EF25/35/42/50VE - E2 and MUZ-EF25/35VEH - E2 have been added. Please void OBH590 REVISED EDITION-A. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH590 REVISED
Contents. Part 1 General Information... 1. Part 2 Outdoor Units... 9. Part 3 Installation... 50. Part 4 Troubleshooting 73
MCAC-VTSM-2013-03 R410a Full DC Inverter Mini VRF Contents Part 1 General Information... 1 Part 2 Outdoor Units... 9 Part 3 Installation... 50 Part 4 Troubleshooting 73 Part 5 Control System... 100 Manufacture
SERVICE MANUAL MUZ-GE25VA - E1 MUZ-GE25VAH - E1 MUZ-GE35VA - E1 MUZ-GE35VAH - E1 MUZ-GE42VA - E1 MUZ-GE42VAH - E1 MUZ-GE50VA - E1 MUZ-GE50VAH - E1
SPLIT-TYPE AIR CONDITIONERS Revision A: MUZ-GE42/50VA(H) - E1 has been added. Please void OBH516. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH516 REVISED EDITION-A Models MUZ-GE25VA - E1 MUZ-GE25VAH
ModPac II 1 to 5-Ton Vertical Wall Mount Air Conditioners Models AVPA12-20-24-30-36-42-48-60
ModPac II 1 to 5-Ton Vertical Wall Mount Air Conditioners Models AVPA12-20-24-30-36-42-48-60 General Description The Marvair ModPac II air conditioner is a vertical, wall mounted, cost effective air conditioner
Split System Heat Pump Product Data
Split System Heat Pump Product Silver 14 4A6H4 1 1 /2-5 Tons PUB. NO. 12-1175-07 Contents Features and Benefits 2 Model Nomenclature 3 General 4 Product Specifications 4 A-weighted Sound Power Level [db(a)]
Appendix - Controllers 179
Version: 200703 Appendix - Controllers 179 -3- -4- -5- -6- -7- -8- 2. Specifications 2.1 Specifications for inverter units item Model AB182ACERA Function cooling heating Capacity kw 5.01.8--5.8 5.22.0---6.2
LG AIR CONDITIONING SYSTEMS
LG AIR CONDITIONING SYSTEMS THE NEW STANDARD IN COMFORT INNOVATIVE COMFORT SOLUTIONS AT LG, WE BELIEVE COMFORT SHOULD ALWAYS BE BEAUTIFUL. 4 Table of Contents INTRODUCTION 04-07 ART COOL 08-11 SINGLE
2015 HVAC Excellence Educator Conference Variable Refrigerant Flow & Variable Refrigerant Temperature
2015 HVAC Excellence Educator Conference Variable Refrigerant Flow & Variable Refrigerant Temperature Slide 1 Residential Market Push for more efficiency Green Building Initiative R-22 & High Efficiency
ENGiNEERiNG AND SPECiFiCATioNS GuiDE
ENGiNEERiNG AND SPECiFiCATioNS GuiDE DuCT-FREE AiR CoNDiTioNiNG SySTEmS ART CooL inverter FLEx multi-split FLooR STANDiNG CEiLiNG CASSETTE PTAC PTHP THRouGH-THE-WALL LG Electronics, Air Conditioning Division
Operating Instructions Split System Air Conditioner
Operating Instructions Split System Air Conditioner Model No. Indoor Unit Type Indoor Unit Type Nominal Capacity 26 36 F2 Low Silhouette Ducted S-26PF2U6 S-36PF2U6 Connectable outdoor unit lineup This
Local Dealer: www.cebrands.com
Local Dealer: C.E. LLC - Miami, FL USA www.cebrands.com Res2012-Rev2 QUALITY YOU CAN FEEL Residential Product Line >TCA7,9 Tempstar SmartComfort TXT + Air Conditioner Featuring The Observer Communication
Portable Air Conditioner
Portable Air Conditioner Owner's Manual Model:3 in 1 12,000 Btu/h Series 3 Please read this owner s manual carefully before operation and retain it for future reference. CONTENTS 1. SUMMARY...1 2. PORTABLE
M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A
Bulletin 20-20.2 / July 2012 M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A ➀ ➁ ➂ Model Number Key M 2430 C L 1 - A - ➀ Unit Type M=Modular Nominal Capacity 2430=24000 to 30000
Installation Manual. Rental Services. Air Handling Units CHS-SVN01A-EN. July 2008
Installation Manual Rental Services Air Handling Units July 2008 CHS-SVN01A-EN Copyright 2008 Trane All rights reserved This document and the information in it are the property of Trane and may not be
Energy Efficiency. Energy Efficient Home Cooling:
Energy Efficiency Energy Efficient Home Cooling: Choosing an air conditioning system is an important decision. A poor choice may be costly to purchase and operate and yet fail to provide the desired cooling
Hitachi Air Conditioning. Engineered for tomorrow. Room Air Conditioning GENERAL CATALOGUE
Hitachi Air Conditioning Engineered for tomorrow. Room Air Conditioning GENERAL CATALOGUE Contents Page 04 Product Range 08-09 RAC Summit Wall Mounted 10 RAC Shirokuma Wall mounted 11 RAC S Series - Wall
Split System Heat Pump Product Data
Split System Heat Pump Product Data XL20i 4TWZ0024, 036, 048 & 060 with ComfortLink II and Charge Assist 2, 3, 4 & 5 Tons PUB. NO. 22-1826-01 Features and Benefits Two Climatuff compressors Efficiency
SINGLE PACKAGE VERTICAL AIR CONDITIONERS
SINGLE PACKAGE VERTICAL AIR CONDITIONERS AIR CONDITIONERS l HEAT PUMPS l ELECTRIC HEAT QUIETER BY DESIGN SIMPLE TO INSTALL CONCEALED INSTALLATION www.friedrich.com VERT-I-PAK ideal for extended stay properties,
Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty
Codes Room Air Conditioner range: Indoor unit alarm s If timer lamp flashes for 1 second on, 1 second off, this indicates pre heating on the coil during heating mode and is not an error. If timer lamp
LG Air conditioning Company Multi V Water Ⅱ. Air Conditioning Academy
LG Air conditioning Company Multi V Water Ⅱ Air Conditioning Academy 1.1 What is Multi V Water II? High Performance Prospect rights Water pipe Refrigerant pipe Indoor unit Beautiful Exterior Convenience
CLOSE CONTROL SYSTEM. PFD series provide you with highly reliable computer room cooling system. High Reliability
PFD-P250VM-E PUHY-P250YJM-A(-BS) PUHY-P500YSJM-A(-BS) PQHY-P250YHM-A CLOSE CONTROL SYSTEM MITSUBISHI ELECTRIC s Close Control System (PFD series) is specifically designed for computer rooms, laboratories
How To Make A High Efficiency Thermostat
Zoning with Variable Speed Mini-Split Systems Fujitsu Service Training Welcome - Thank you for attending Did you know? In 1940 only 42% of homes in the US had central heating In 1970 20% of homes had central
SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS
SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating
ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system.
ROOFTOP - HEAT PUMP UNIT Technical data Applies to Model YNRA R410A This document applies when installing into an air handler or as part of an air handling system. CONTENTS 1. General description... 2
Multi Air Conditioner SVC MANUAL(Exploded View)
Internal Use nly http://biz.lgservice.com Multi Air Conditioner SVC MANUAL(Exploded View) MDEL : A5UW306FA3 CAUTIN Before Servicing the unit, read the safety precautions in Standard SVC manual. nly for
R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power
R22. K Control. Indoor Unit. Nomenclature. PL H 3 G K H B Compatibility Unit style Heat Pump Horse Power Control Boost Heaters R22. K Control. Outdoor Unit. Nomenclature. PU H 3 Y K A Compatibility Outdoor
SECTION 15732 AIR CONDITIONING UNIT
SECTION 15732 AIR CONDITIONING UNIT PART 1 GENERAL 1.01 SUMMARY A. Section includes: 1. Packaged, split system air conditioning unit No. 1. 1.02 REFERENCES A. Air-Conditioning, Heating, and Refrigeration
UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01
GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per
Duct Free Split Air ConditionerS
Duct Free Split Air ConditionerS Quality, convenience, efficiency, quiet operation More stylish than a room air conditioner, gives you back your window space, and quieter than conventional central air
Submitted to Reference Approval Construction Unit Designation Schedule #
SUBMITTAL AQV09JA High Wall 9,000 Btu/h Heat Pump Nom Cooling Capacity (Btu/h) 9,000 SEER 20.0 Cool Capacity Range (Btu/h) 3,100 to 11,900 Nom Heating Capacity (Btu/h) 11,950 HSPF 10.0 Heating COP 3.7
Introduction To VRF: System Overview, Applications, & Savings Opportunities
Introduction To VRF: System Overview, Applications, & Savings Opportunities System Overview What is VRF? Zoning System Two-Pipe / Three Pipe System Packaged DDC Control Operates as a Heat Pump Simultaneous
SERVICE MANUAL MUZ-FE09NA MUZ-FE12NA MUZ-FE18NA OUTDOOR UNIT. No. OBH543 REVISED EDITION-A. Models HFC
SPLIT-TYPE AIR CONDITIONERS Revision A: MUZ-FE18NA has been added. Please void OBH543. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH543 REVISED EDITION-A Models MUZ-FE09NA MUZ-FE12NA MUZ-FE18NA Indoor
Single Zone LCD Thermostat Operating Instructions
Fan Cool Furnace *Heat Pump or Heat Strip On/Off F Single Zone LCD Thermostat Operating Instructions MODEL 3313192.XXX Cool/Furnace 3313193.XXX Cool/Furnace/Heat Pump 3313194.XXX Cool/Furnace/Heat Strip
For Residential & Light Commercial Applications. 4 Ton 8 Zone Multi Split Heat Pump System
For Residential & Light Commercial Applications 4 Ton 8 Zone Multi Split Heat Pump System EXPERTISE AND INNOVATION The Super Multi PLUS Split System is the ultimate, flexible solution for individual zone
Gree Solar Hybrid Hi Wall Inverter Air Conditioner
Gree Solar Hybrid Hi Wall Inverter Air Conditioner Utilize the natural power of the sun to heat or cool your home. Find out more at www.greeonline.com Why Choose a Solar Hybrid Inverter? The new Gree Solar
Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks
Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same
Characteristics of Evaporators
Characteristics of Evaporators Roger D. Holder, CM, MSME 10-28-2003 Heat or Energy In this paper, we will discuss the characteristics of an evaporator coil. The variance of the operational condenses of
HIGH-EFFICIENCY DUCTLESS INDOOR COMFORT
UP TO 15 SEER Performance MINI-SPLIT SYSTEM UNITS AIR CONDITIONING AND HEAT PUMPS COMPLETE ROOM COMFORT WITH EASY-TO-USE REMOTE CONTROL HIGH-EFFICIENCY DUCTLESS INDOOR COMFORT The Goodman brand offers
KSV70HRF. KSV70HRF - 7.1kW Split System Air Conditioner - Reverse Cycle
KSV70HRF RRP AUS $1,709.00 Split System Reverse Cycle air conditioner featuring inverter technology, clean front with LED display, Bio and active carbon filter, 2 way auto swing (up, down), remote (7.1kW
TWE+TTA TWE+TWA 6.25-20 T.R.
TWE+TTA TWE+TWA 6.25-20 T.R. Main features : TWE indoor unit : Convertible cabinet, vertical or horizontal. Adjustable speed pulley-belt drive centrifugal fan motor. Aluminium fin coil with copper-tubes.
Defining Quality. Building Comfort. Precision. Air Conditioning
Defining Quality. Building Comfort. Precision Air Conditioning Today s technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air
COIL INPUT SCREENS. ITEM NUMBER: Always use a 1 through? In this field you might also use a dash and place quantity of coils here.
COIL INPUT SCREENS Example of a Water Coil Input Screen: (*please see the appendix for an example of an Evaporator, Steam or Condenser Coil input screen) PHYSICAL DATA ITEM NUMBER: Always use a 1 through?
AIR-COOLED CONDENSERS Technical Guide
BN-ACCTB0306 March, 2006 AIR-COOLED CONDENSERS Technical Guide Monarch and Ambassador Series TABLE OF CONTENTS Overview... 2, 3 Features & Options... 3, 4 Three Solutions...5 Nomenclature...6 Condenser
ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014
ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014 Explanation of the refrigeration cycle. Compressors. Benefits and operating characteristics. -Reciprocating
Heating, Ventilation & Air Conditioning Equipment
FinAnswer Express Utah Incentive Catalog Effective as of May 19, 2012 Heating, Ventilation & Air Conditioning Equipment Rocky Mountain Power provides incentives for many types of energy-efficient technologies.
PANASONIC TROUBLE SHOOTING GUIDE
A General Guide To Room Style Products Pipework Pipe sizes and lengths should be as the relevant Technical Guide Both lines should be insulated No line accessories or oil traps should be fitted In cooling
CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. ELECTRICAL SCHEMATIC DIAGRAM 13 5. EXPLOSION VIEW 16 6
TCL WALL MOUNTED SPLIT-TYPE AIR CONDITIONERS SERVICE MANUAL No.TE080528 Models KFTHP-12 KFTHP-18 KFTHP-24 CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. ELECTRICAL
CoolTop. A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60
CoolTop A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60 Application CoolTop is a new, unique air conditioning unit especially designed for datacenters.
LG AIR CONDITIONERS 2014 Ducted Split System
Australia Pty Ltd. New South Wales / Head Office 2 Wonderland Drive EASTERN CREEK NSW 2766 PH : 02-8805-4000 FAX : 02-8805-4248 AUS-DU1309 Queensland 23 Terrace Place MURARRIE QLD 4172 PH : 07-3908-9000
SECTION 23 81 43 HEAT PUMPS
SECTION 23 81 43 HEAT PUMPS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop heat pumps. 1.2 REFERENCES A. American Society of Heating, Refrigerating and Air-Conditioning Engineers:
CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM 11 5. EXPLOSION VIEW 12 6.
TCL WALL MOUNTED SPLIT-TYPE AIR CONDITIONERS SERVICE MANUAL No.TE051220 Models TAC-09CHSA/GI TAC-12CHSA/GI CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM
Product Data. Split System Cooling 22-1904-1F-EN. March 2015
Product Data Split System Cooling 4TTR4018L1000A 4TTR4024L1000A 4TTR4025L1000A 4TTR4030L1000A 4TTR4031L1000A 4TTR4036L1000A 4TTR4037L1000A 4TTR4042L1000A 4TTR4043L1000A 4TTR4048L1000A 4TTR4060L1000A Note:
Greensource iseries HY Model Unitary Air Handler/Fan Coil
Engineering Submittal Sheet Overview Model Nomenclature HY 035 00-1 HY - HYDRONIC AIR HANDLER NOMINAL CAPACITY IN THOUSANDS OF BTUH VOLTAGE DESIGNATION 1 = 208-230/1/60 ELECTRIC HEAT KW 00 - NO ELECTRIC
CPX/HT Series. REFRIGERATED AND HIGH TEMPERATURE DRYER 12 to 2400 CFM. High-performance products. Designed for you!
CPX/HT Series REFRIGERATED AND HIGH TEMPERATURE DRYER 12 to 2400 CFM High-performance products. Designed for you! COMPRESSED AIR WATER CONTAMINATION Atmospheric air contains water in vapor form in different
Schedule 3(A) Room Air Conditioners
Schedule 3(A) Room Air Conditioners Revision : 1 Date : 21/08/15 1. Scope 1.1 This Standard specifies the energy labeling requirements for single-phase split air conditioners of the vapour compression
ARMSTRONG AIR HEAT PUMPS www.armstrongair.com
INDEX ELECTRIC FURNACE MODULAR AIR SYSTEM EFC/EFV... 5-10 electric Heat Kits... 5-11 evaporator coils EC1P / EM1P UPFLOW / COUNTERFLOW APPLICATIONS and upflow / horizontal applications (CASED)... 5-6 5-7
NEW 3-PIPE ECOi MF2 SERIES
NEW 3-PIPE ECOi MF2 SERIES SIMULTANEOUS HEATING AND COOLING VRF SYSTEM Internet Control Ready INTERNET CONTROL NEW Energy Environmentally friendly refrigerant R410A Down to -20 ºC in heating mode OUTDOOR
Heat Pump Product Brochure 2015/2016. Premier Series Hi-Wall Split Systems. Everyday Comfort
Heat Pump Product Brochure 2015/2016 Premier Series Hi-Wall Split Systems Everyday Comfort Everyday Innovation We design with you in mind. You ll find that Haier Heat Pump units are quiet, efficient and
Air conditioners Heating & Cooling
Air conditioners Heating & Cooling Replacement VRV Cost effective upgrade for R-22 s High efficiency Possibility to increase capacity Limited and planned downtime Limited and phased investment cost www.daikin.eu
How To Buy A Lennox Power System
HVAC for Schools A Comprehensive Look at Products for a Clean, Comfortable Learning Environment Why Schools Choose Lennox Even as resources for schools continue to be constrained, education leaders and
The ABC s of VRF: A Green HVAC Technology An Ideal Green School Solution. Presented by: Fujitsu General America, Inc.
The ABC s of VRF: A Green HVAC Technology An Ideal Green School Solution Presented by: Fujitsu General America, Inc. What to look for in a Green HVAC solution? What if your HVAC system could provide Individual
Ductless Heat Pumps. Gary Nordeen January 2009. www.nwbuildings.org/dhp.aspx [email protected]
Ductless Heat Pumps Gary Nordeen January 2009 www.nwbuildings.org/dhp.aspx [email protected] Outline Heat Pump Basics Ductless Heat Pumps Efficiency Advantages Commercial installations Planning (applications,
Heating, Ventilation & Air Conditioning Equipment
FinAnswer Express Wyoming Incentive Catalog Effective as of October 1, 2011 Heating, Ventilation & Air Conditioning Equipment Rocky Mountain Power provides incentives for many types of energy efficient
Creating Efficient HVAC Systems
Creating Efficient HVAC Systems Heating and Cooling Fundamentals for Commercial Buildings Heating, ventilating, and air conditioning (HVAC) systems account for nearly half of the energy used in a typical
APPLICATION GUIDE. Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application
APPLICATION GUIDE Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application Section Comparison of Latent Cooling Performance of Introduction Most commercial HVAC systems
A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures
R2-1 A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures W. Vance Payne and Piotr A. Domanski National Institute of Standards and Technology Building Environment
ECOCIAT. Domestic hot water heat recovery unit
Heat recovery unit Domestic hot water High energy efficiency with R410A Compact and quiet Scroll compressors Brazed-plate heat exchangers Heating Heat recovery ENVIRONMENTALLY HFC R410A PROTECTION DE FRIENDLY
NewAir AC-10100E / AC-10100H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS
NewAir AC-10100E / AC-10100H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS ELECTRICAL SAFETY This appliance is for indoor use only. Always turn off the unit and unplug
Ductless Mini-Split Systems. Comfort... where you need it, when you need it
Ductless Mini-Split Systems Comfort... where you need it, when you need it Ductless mini-splits THE COMFORT SOLUTION Ductless mini-split systems are a great solution to a wide variety of installation challenges,