Electrical practices: construction and demolition sites

Size: px
Start display at page:

Download "Electrical practices: construction and demolition sites"

Transcription

1 FACT SHEET Electrical practices: construction and demolition sites This fact sheet provides an overview of the requirements shown in AS/NZS 3012: 2010 Electrical installations construction and demolition sites (AS/ NZS 3012), which is called up as a mandatory standard by clause 163 of the Work Health and Safety Regulation 2011 (WHS Regulation). AS/NZS 3012 has replaced the Electrical Practices for Construction Work Code of Practice 2007, which was revoked with the introduction of the WHS Regulation on 1 January The standard sets out minimum requirements for the design, construction and testing of electrical installations that supply electricity to appliances and equipment on construction and demolition sites, and for the in-service testing of portable, transportable and fixed electrical equipment. Note: Electrical work carried out on electrical installations and electrical equipment used on construction and demolition sites must also be carried out in accordance with AS/NZS 3000: 2007 Wiring rules, except as varied by AS/NZS 3012 where applicable additional controls apply. Supply (Refer to section 2 of AS/NZS 3012) Construction wiring must be supplied from: an electricity distributor s main an existing switchboard in the permanent installation of the premises a low voltage generator complying with the principles of AS2790, which must be installed in accordance with AS 3010, or an inverter complying with the requirements of AS/NZS Construction wiring must: not be tied, bundled, or grouped with permanent wiring not be fixed to free standing fences that have no fixed posts (or equivalent means of support) be protected against mechanical damage (medium or heavy duty or corrugated conduit of insulating material, armoured cable, flexible electrical hose) be marked and be readily distinguishable from permanent wiring by using iridescent yellow tape spaced at intervals not exceeding five metres and marked with the words construction wiring be positioned to avoid crossing roadways or access ways where cranes, high loads or heavy machinery may travel. If this is not possible, an effective means to minimize the risk of vehicular contact with the overhead wiring system must be provided (such as insulated flagged catenary wires six metres on either side of the overhead wiring and 0.6 metres below the lowest point of the overhead electrical cable). Please note, all construction wiring, including overhead type, must be insulated. February 2013

2 Switchboards installed on construction and demolition sites (Refer to section 2.3 of AS/NZS 3012) Switchboard installation and location: must be installed in accordance with AS/NZS 3000: 2007 Wiring rules must be readily accessible and must be protected from damage during the course of the construction or demolition work must be mounted on a pole, post, wall, floor or other structure of stable and free standing design that takes into account any external forces that may be exerted on the switchboard must be marked with the source of the supply and where it originates from for multi-level buildings, be positioned in a manner that eliminates the need for flexible cords or cables to be run between floor levels. Note: Alternative switchboard construction and supply system (plug and socket arrangement) is shown in Appendix K of AS/NZS Switchboard construction Switchboards must be constructed of robust material capable of withstanding mechanical damage. The enclosure of the switchboard must have a minimum degree of protection of IP23 *. Energized (live) parts must be effectively protected at all times against contact by workers. An insulated or covered tie bar must be provided for anchorage of flexible cords to prevent strain on the plugs and socket outlets. Switchboard doors must not be of the removable type (unless with a tool) and be fitted with a locking facility (for locking overnight or when not in use). They must also be fitted with means for retaining the door in the open position. Switchboards must have a cut out (not sharp to prevent cables being cut, ie by providing brushing or plastic hose around it) in the bottom plate to allow safe entry of electrical leads with the door closed. A label must be fixed to the switchboard stating KEEP CLOSED RUN ALL LEADS THROUGH BOTTOM. If more than one switchboard is located on a site, markings must be provided to distinguish one switchboard from another. Switchboards must be marked with an electric shock symbol and a danger sign (as per below) warning workers of the presence of energized or live parts within the switchboard. * Note: IP23 refers to the degree of protection provided by the enclosures of electrical equipment. According to AS60529: 2004 Degrees of protection provided by enclosures (IP Code), IP23 refers to an enclosure (in this case an electrical switchboard) that is protected against access to hazardous parts with a finger and also protected against water spraying. 2

3 Isolating switches, RCDs, socket outlets, auxiliary socket outlet panels, portable socket outlet panels, generators and inverters (Refer to section of AS/NZS 3012) Isolating switches/main switches Each switchboard must be provided with one marked isolating switch which, if switched off, will interrupt supply to all final sub-circuits and sub-mains originating from the switchboard, including socket outlets mounted on the switchboard. The switchboard must be provided with a means to prevent electrical equipment from being inadvertently energized while undertaking work on electrical installations (provision for fitting a padlock or located within a lockable space or enclosure). Main switchboard isolating switches must be marked MAIN SWITCH and the distribution board isolating switches must be marked DISTRIBUTION BOARD ISOLATING SWITCH. RCDs ** All final sub-circuits of construction wiring must be protected at the switchboard where the sub-circuits originate by a residual current device (RCD), with a maximum rated residual current of 30mA, that operates in all live (active and neutral) conductors. All appliances, luminaries and other electrical equipment must be supplied from an RCD protected circuit that is fixed at the switchboard or incorporated into the socket-outlet or incorporated into a portable socket-outlet assembly. Socket outlets Socket outlets must be rated at not less than 10A. Single-phase socket outlets must be individually controlled by a double-pole switch (active and neutral conductors are switched). Portable socket outlet assemblies (PSOA) must comply with AS/NZS 3190 and be of class H (should be marked with these requirements) must have an overload protective device, RCD and plugs intended for connection of low-voltage socket-outlet flexible cable feeding the PSOA must be the heavy duty sheathed type not longer than 2m. ** Note: Testing and inspection requirements are discussed further in this fact sheet. 3

4 Auxiliary socket outlet Assemblies (ASOP) must be: of robust construction to withstand mechanical damage and have a minimum IP23 rating located at a height of 1.2 to two metres above the floor level and be securely mounted to a fixed structure or a structure designed for that purpose supplied by an RCD protected circuit at the switchboard it originates from provided by a clearly marked isolating switch that controls the incoming supply. Incoming supply cable must have a minimum cross sectional area of 4mm 2 provided by means to relieve strain on plug and socket outlets of flexible cables. Example of an ASOP Cord extension sets (commonly known as extension leads) A flexible cord must be the heavy duty sheathed type (not green in colour) and each conductor in the flexible cord must be no less than 1mm 2 in cross-sectional area. The plug and socket on either side of a cord extension set must be compliant with the relevant standard for their construction. The maximum length of a flexible cord, for a given conductor cross-sectional area, must comply with table 1 below. A cord extension set must not to be joined so that the total length of any combination exceeds the relevant maximum value specified in table 1. Note: Electrical portable outlets devices (EPODS), for example domestic type power boards, double adaptors and three pin plug adaptors (piggyback), are not allowed on construction and demolition sites. Table 1: (Maximum lengths of flexible cords and flexible cables) as per AS/NZS 3012: 2010 Electrical installations construction and demolition sites. Table 1: Maximum length of most commonly used single phase cord extension set Current rating (A) Conductor size (mm 2 ) Maximum length (metres) / Note: Lengths quoted for flexible cords are taken from AS/NZS 3199 and are based on a voltage drop of 5% of 230V at rated current for the conductor size. 4

5 Generators and inverters Low voltage generators (complying with AS 2790) must be connected in accordance with AS/NZS All sub-mains, sub-circuits and switchboards supplied by a generator must be protected as per requirements outlined in this summary. Generators and inverters providing electrical supply via permanently connected RCDs must have a maximum tripping current of 30mA Isolated winding generators and isolated inverters must only be used to supply a separated circuit for electrical equipment installed in accordance with AS/NZS 3000: 2007 Wiring rules, and each winding must supply not more than one item of Class I (earthed conductive parts) electrical equipment. Lighting, lift shafts, transportable structures (Refer section of AS/NZS 3012) Lighting Where more than one lighting circuit is installed, the lighting circuits must be distributed between RCDs. The recommended minimum lighting level for walkways is 40 lx, and 160 lx *** for general areas. Lamps in luminaires must be protected against mechanical damage. Emergency lighting must be sufficient to allow the safe egress of all workers from the site. It must be capable of running for a minimum of one hour in case of loss of normal lighting in the area. Edison screw type lamp holders must be connected to the supply with the neutral conductor connected to the outer contact. Festoon lighting must be connected to an Extra low Voltage power source (<50 V a.c). It must be suspended at a minimum height of 2.5m or above or directly below the ceiling. Portable luminaries (eg flood light tripods) must have a minimum degree of protection (refer to AS 60529), a mechanical guard on the lamp and adequate stability. Lift shafts Construction wiring dedicated to the installation of lift shaft equipment must be fed from a separate final sub-circuit at the switchboard and protected by 30mA RCD. Circuit breakers must be locked and tagged to prevent the inadvertent isolation of supply to the lift shaft by others onsite. False cars (guided work platforms) must be supplied from a minimum 230V, 20A socket outlet on a final subcircuit protected by a 30mA RCD. Supply cable must be of the heavy duty type, minimum conductor size 4mm 2. The supply cable must be installed in a way to minimize mechanical damage and of sufficient length to cover the full length of the lift shaft. Transportable structures Electrical installations of transportable structures must comply with AS/NZS 3001 and the following: The installations must be supplied from a sub-main or final sub-circuit originating at a circuit breaker on a switchboard and installed as construction wiring. The installations must be supplied from a flexible cord and plug with a specific socket outlet with a degree of protection not less than IPX4. They must also be individually protected by a circuit breaker of a rating not greater than the socket outlet and be RCD protected. The supply cord must have a minimum cross sectional area of 2.5mm 2 and not longer than 15 metres. All socket outlets (inside/outside) must be RCD protected and only be used for equipment and lighting within the transportable structure or immediately adjacent the exterior. (Note: double pole switches must be used for socket outlets.) *** lx: lux which is a measure of light illuminance and could be measured using a special hand held device. 5

6 Inspection, testing, record keeping (Refer to section of AS/NZS 3012) Inspection and testing All construction wiring, switchboards and transportable structures must be inspected and tested by a licensed electrical worker (electrician) following the initial installation and in a period not exceeding six months (refer to table 2). For new equipment, prior to the initial introduction it must be inspected for obvious damage before being placed into service. All other electrical equipment including power tools, flexible cords, cord extension sets (extension leads) and portable socket outlet assemblies and portable RCDs** must be tested and inspected according to the methods in AS/NZS 3760 and in a period not exceeding three months. Inspection and testing can be carried out by a competent person (trained in use of RCD testers and Portable Appliance Testers PAT) or a licensed electrician. **The RCD tests referred to above, test the tripping time which should be less than 300ms. A push button test is required every time a portable RCD unit is used, and monthly on fixed RCDs. This could be carried out by the user (worker) after being instructed on how to do it. For hire equipment, inspection prior to each hire and testing at not greater than monthly intervals. If hire equipment remains on site, then table 2 applies. Compliant equipment and equipment new to service must be fitted with a durable non-metallic tag that clearly states the date it was inspected and the next date of inspection. It should also include the name of the person that performed the verification and the standard it was tested to (AS/NZS 3760). Colour coded tags for each period are optional. Non-compliant equipment must be withdrawn from service immediately and labelled with suitable warning against further use. If sent for repairs, it must be re-tested once returned to site. Record keeping Records of inspection and tests must be kept for the duration of the construction/demolition job. The following should be recorded and be available for inspection at all times. Register of all equipment. Record of formal inspections and tests. Repairs register and record of faulty equipment, where applicable. Construction wiring must be inspected according to AS/NZS 3000: 2007 Wiring rules checklist, which includes, but is not limited to: visual inspection, continuity of earthing, insulation resistance, polarity, correct circuit connections and RCD trip time values. Note: electronic records (ie computer databases, excel spread sheets etc) are acceptable. Table 2: Periodic verification intervals (AS/NZS 3012: Electrical installations construction and demolition sites) Table 2: Inspection and testing intervals Equipment class Construction wiring, including switchboards Re-locatable structures, fixed and transportable equipment Portable equipment and flexible electrical cords (extension leads) Equipment in amenities and site offices Portable RCDs push button test Portable RCDs operating time Fixed RCDs push button test Fixed RCDs operating time Hire equipment Testing intervals Inspected and tested at time of installation, then re-inspected every 6 months 6 months 3 months 3 months Before each use of equipment 3 months 1 month 12 months Upon introduction to service, then in accordance with the testing intervals appropriate to the equipment class. 6

7 Appendix 1 Guide to arrangement of switchboards, construction wiring and equipment Refer to Appendix J of AS/NZS 3012:

8 Appendix 2 AS/NZS 3012: 2010 Electrical installations: construction and demolition sites checklist Inspection checklist Inspected by Inspection date (DD/MM/YYYY) / / Clause AS/NZS 3012 requirements / 1.2 All wiring installed according to AS3000 Wiring rules in addition to AS3012 requirements All electrical equipment and lighting supplied from a 30mA RCD protected circuit breaker(s) Source of supply identified Switchboard readily accessible (ab) Switchboard of robust construction with a minimum IP23 rating (c) Live parts effectively protected and a warning sign attached along an electric shock symbol (d) Insulated tie bar for extension leads to prevent strain on socket/outlet (e) Switchboard door is lockable, non-removable without a tool and fitted with a retention device to stay in open position (e) Switchboard has means of safe entry of leads and a label: KEEP CLOSED RUN LEADS THROUGH BOTTOM Switchboard mounted on a pole, structure, wall or suitably designed free standing design Switchboard has a main isolation switch capable of isolating all downstream circuits Main switch capable of being locked or within a lockable space Main switch labelled appropriately: MAIN SWITCH or DISTRIBUTION BOARD ISOLATION SWITCH or similar Construction wiring installed in appropriate conduit to protect against mechanical damage Construction wiring labelled with yellow tape with words construction wiring at distances not longer than 5m Extension leads supported by stands or insulated hooks Adequate lighting provided for safe work Lighting is mechanically protected Emergency lighting adequate for safe exit of workers (if applicable) If a lift shaft is present, the final sub-circuit feeding it is locked and tagged to prevent inadvertent isolation of supply. 2.9 Socket outlets in site sheds and other transportable structures are RCD protected Portable equipment including power leads are inspected at three-monthly intervals Portable RCD s trip time is tested every 3 months Switchboards, wiring and site sheds are inspected at six-monthly intervals Register available for equipment and includes records of testing and tagging, RCD trip time results and list of repaired equipment. Action required Re-inspected by Compliance date (DD/MM/YYYY) / / Note: For more information and guidance material on construction work carried out in the vicinity of overhead wiring that is not classified as construction wiring discussed in this bulletin, safeworkaustralia.gov.au and search for Code of practice: Working in the vicinity of overhead and underground electric lines. The Guide: Work near underground assets (catalogue no. WC01419) provides more information for work carried out near underground assets (eg power lines, telecommunications, gas, water). It can be accessed at workcover.nsw.gov.au or by clicking on the following link: Guide: Work near underground assets. 8

9 Disclaimer This publication may contain work health and safety and workers compensation information. It may include some of your obligations under the various legislations that WorkCover NSW administers. To ensure you comply with your legal obligations you must refer to the appropriate legislation. Information on the latest laws can be checked by visiting the NSW legislation website legislation.nsw.gov.au This publication does not represent a comprehensive statement of the law as it applies to particular problems or to individuals or as a substitute for legal advice. You should seek independent legal advice if you need assistance on the application of the law to your situation. WorkCover NSW Catalogue No. WC03959 WorkCover Publications Hotline WorkCover NSW, Donnison Street, Gosford, NSW 2250 Locked Bag 2906, Lisarow, NSW 2252 WorkCover Assistance Service Website workcover.nsw.gov.au ISBN Copyright WorkCover NSW 0213

ELECTRICAL PRACTICES FOR CONSTRUCTION WORK

ELECTRICAL PRACTICES FOR CONSTRUCTION WORK CONTRACTOR S CHECKLIST ELECTRICAL PRACTICES FOR CONSTRUCTION WORK 2007 WorkCover. Watching out for you. New South Wales Government Disclaimer This publication contains information regarding occupational

More information

Electrical Practices for Construction Work

Electrical Practices for Construction Work 1. Purpose Electrical Practices for Construction Work The purpose of this Code is to provide practical guidance and set minimum safety requirements for electrical practices on all construction sites in

More information

Electrical installations on construction sites

Electrical installations on construction sites Industry standard Electrical installations on construction sites Edition No. 3 January 2011 The information presented in the Industry Standard Electrical installations on construction sites is intended

More information

This Guideline does not address electrical equipment in the following categories:

This Guideline does not address electrical equipment in the following categories: Policy Hierarchy link Responsible Officer Contact Officer Superseded Documents HS418 Portable Electrical Equipment Inspection, Testing and Tagging Guideline Work Health and Safety Act 2011 Work Health

More information

Heading FACT SHEET. Overview. www.safeworkaustralia.gov.au

Heading FACT SHEET. Overview. www.safeworkaustralia.gov.au ELECTRICAL RISKS AT THE WORKPLACE Heading FACT SHEET Overview This fact sheet provides general guidance for persons conducting a business or undertaking (PCBUs) and workers on managing electrical risks

More information

CHECKING AND TESTING ELECTRICAL INSTALLING WORK

CHECKING AND TESTING ELECTRICAL INSTALLING WORK CHECKING AND TESTING ELECTRICAL INSTALLING WORK Department of Consumer and Employment Protection Energy Safety Preface It is a requirement of the Electricity (Licensing) Regulations 1991 that all electrical

More information

Trial Exams C. Standards and Regulations. Examination No: GH-08-C- 1 hour and 5 minutes plus 10 minutes reading time

Trial Exams C. Standards and Regulations. Examination No: GH-08-C- 1 hour and 5 minutes plus 10 minutes reading time Trial Exams C Standards and Regulations Examination No: GH-08-C- This test is intended to gauge your knowledge of essential information contained within AS/CA S009:2013. To qualify for an allpication to

More information

FREQUENTLY ASKED QUESTIONS TESTING AND TAGGING OF ELECTRICAL EQUIPMENT

FREQUENTLY ASKED QUESTIONS TESTING AND TAGGING OF ELECTRICAL EQUIPMENT FREQUENTLY ASKED QUESTIONS TESTING AND TAGGING OF ELECTRICAL EQUIPMENT HAS THE LAW CHANGED REGARDING TESTING AND TAGGING OF ELECTRICAL EQUIPMENT? Yes, Simplified safety regulations for electrical equipment

More information

GUIDE TO THE MAINTENANCE, INSPECTION AND TESTING OF PORTABLE EQUIPMENT (ELECTRICAL APPLIANCES AND TOOLS) IN THE WORKPLACE

GUIDE TO THE MAINTENANCE, INSPECTION AND TESTING OF PORTABLE EQUIPMENT (ELECTRICAL APPLIANCES AND TOOLS) IN THE WORKPLACE GUIDE TO THE MAINTENANCE, INSPECTION AND TESTING OF PORTABLE EQUIPMENT (ELECTRICAL APPLIANCES AND TOOLS) IN THE WORKPLACE ET 215:2008 ELECTRO-TECHNICAL COUNCIL OF IRELAND 2008 Page 1 of 6 Published by

More information

Trade of Electrician. Three-phase Distribution Boards And Socket Circuits

Trade of Electrician. Three-phase Distribution Boards And Socket Circuits Trade of Electrician Standards Based Apprenticeship Three-phase Distribution Boards And Socket Circuits Phase 2 Module No. 2.3 Unit No. 2.3.2 COURSE NOTES Created by Charlie Walsh - Athlone TC Revision

More information

AS/NZS 3000:2007 Amendment 2

AS/NZS 3000:2007 Amendment 2 AS/NZS 3000:2007 Amendment 2 Published 14 December 2012 Under Victorian legislation the day a revised standard is published it becomes the requirement. The aim of this document is to highlight the important

More information

NZECP 14: 1995 ISSN 0114-0663 COVER PAGE

NZECP 14: 1995 ISSN 0114-0663 COVER PAGE NZECP 14: 1995 ISSN 0114-0663 COVER PAGE NZECP 14:1995 NEW ZEALAND ELECTRICAL CODE OF PRACTICE FOR CONTROL PROTECTION AND SWITCHBOARDS Issued by the Office of The Chief Electrical Engineer, Energy and

More information

What equipment needs RCD protection? 3. Testing and tagging of electrical equipment 6. Protectively earthed and double insulated equipment 8

What equipment needs RCD protection? 3. Testing and tagging of electrical equipment 6. Protectively earthed and double insulated equipment 8 ELECTRICAL SAFETY CONTENTS Introduction 2 Residual current devices 2 What equipment needs RCD protection? 3 Risk assessment examples 4 RCD testing 5 Testing and tagging of electrical equipment 6 Testing

More information

RCD Inspection Log Book

RCD Inspection Log Book RCD Inspection Log Book This book is the property of: Commenced: / /. Completed: / /. 2 Clipsal Australia Pty Ltd Clipsal Australia Pty Ltd 3 4 Clipsal Australia Pty Ltd Clipsal Australia Pty Ltd 5 6 Clipsal

More information

Listed are common requirements that apply to existing solar installations when altered, added to or reconfigured.

Listed are common requirements that apply to existing solar installations when altered, added to or reconfigured. SOLAR ALTERATIONS REQUIREMENTS August 2015 These requirements address typical alterations to solar installations; they cannot address every scenario. In Victoria, an alteration to a solar installation

More information

Electrical Safety Tips. Help us keep you safe

Electrical Safety Tips. Help us keep you safe Electrical Safety Tips Help us keep you safe To help you stay safe when using electricity, ActewAGL has compiled these electrical safety tips. For natural gas safety tips please see ActewAGL s natural

More information

Electrical safety of grid-connected solar installations in Western Australia December 2011

Electrical safety of grid-connected solar installations in Western Australia December 2011 Electrical safety of grid-connected solar installations in Western Australia December 2011 Level 1, 303 Sevenoaks Street (cnr Grose Avenue) Cannington, Western Australia 6107 PO Box 135 Cannington WA 6987

More information

DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations)

DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations) DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations) DETAILS OF THE CLEINT Client and address ADDRESS OF THE INSTALLATION Installation

More information

ELECTRICAL INSTALLATION CONDITION REPORT (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations)

ELECTRICAL INSTALLATION CONDITION REPORT (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations) Original Certificate DETAILS OF THE CLIENT Certificate reference: ELECTRICAL INSTALLATION CONDITION REPORT (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations) Name: Address: PURPOSE

More information

FIRST STOP SAFETY 1 PAT-IT. Portable Appliance Tester. User Manual. Issue 1.6

FIRST STOP SAFETY 1 PAT-IT. Portable Appliance Tester. User Manual. Issue 1.6 FIRST STOP 1 PAT-IT Portable Appliance Tester User Manual Issue 1.6 First Stop Safety 11 Glaisdale Road Northminster Business Park Upper Poppleton York YO26 6QT t: 01904 791050 f: 01904 780054 e: info@firststopsafety.co.uk

More information

ELECTRICAL SAFETY. The standard unit for measuring electrical current.

ELECTRICAL SAFETY. The standard unit for measuring electrical current. ELECTRICAL SAFETY Introduction The following sections provide general safety guidelines and procedures for electrical safety. This chapter covers the following topics: TOPIC PAGE General Electrical Safety

More information

CHAPTER 4 UTILITY SYSTEMS ELECTRICAL. Utility Systems Electrical. Main Panel

CHAPTER 4 UTILITY SYSTEMS ELECTRICAL. Utility Systems Electrical. Main Panel CHAPTER 4 UTILITY SYSTEMS ELECTRICAL Utility Systems Electrical The electrical supply to your home begins outside, where you will see either an overhead feed and piping down the side of your home or (if

More information

MEM10019 Select circuit protection devices by type and rating, fit to switchboards and install earthing

MEM10019 Select circuit protection devices by type and rating, fit to switchboards and install earthing MEM10019 Select circuit protection devices by type and rating, fit to switchboards and install earthing Release: 1 MEM10019 Select circuit protection devices by type and rating, fit to switchboards and

More information

Common Electrical Hazards in the Workplace Including Arc Flash. Presented by Ken Cohen, PhD, PE & CIH (Ret.)

Common Electrical Hazards in the Workplace Including Arc Flash. Presented by Ken Cohen, PhD, PE & CIH (Ret.) Common Electrical Hazards in the Workplace Including Arc Flash Presented by Ken Cohen, PhD, PE & CIH (Ret.) 1 What s New In February 1972, OSHA incorporated the 1971 edition of the National Fire Protection

More information

Electrical safety and you

Electrical safety and you Electrical safety and you A brief guide Introduction Electricity can kill or severely injure people and cause damage to property. Every year many accidents at work involving electric shock or burns are

More information

Preventative Maintenance & Statutory Testing

Preventative Maintenance & Statutory Testing Preventative Maintenance & Statutory Testing Emergency Evacuation Lighting - Inspection and Maintenance It is an Occupational Health and Safety Act requirement that employers have a legal duty of care

More information

Top Commercial / Residential Electrical Requirements *

Top Commercial / Residential Electrical Requirements * Department of Community Development Building Division 4800 West 92 nd Avenue Westminster, Colorado 80031 For Information call (303) 658-2075 Fax (303) 706-3922 www.westminsterpermits.com Top Commercial

More information

ELECTRICAL TESTING PROCEDURE

ELECTRICAL TESTING PROCEDURE Document uncontrolled when printed Procedure ID no 0464/05 ELECTRICAL TESTING PROCEDURE This procedure is applicable to: All Department of Education and Children's Services employees. DOCUMENT CONTROL

More information

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132

More information

Trouble-shoot and repair faults in low voltage electrical apparatus and circuits

Trouble-shoot and repair faults in low voltage electrical apparatus and circuits UEENEEG108A Trouble-shoot and repair faults in low voltage electrical apparatus and circuits AS3000:2007 & AS3017:2007 Summary MANUFACTURING AND ENGINEERING DIVISI M & E UEENEEG108A TESTING Before any

More information

In the context of this document, the following definitions apply:

In the context of this document, the following definitions apply: UON Key Risk Area: KRA 3.7 Electrical Testing and Tagging 1. Purpose To provide guidance for managing the risks associated with University activities where electrical equipment is used and to ensure compliance

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to

More information

Annual testing programme will be reported, by the department, as part of the annual hazard review process due to be completed by 31 March each year.

Annual testing programme will be reported, by the department, as part of the annual hazard review process due to be completed by 31 March each year. HR Heath and Safety Policy Health and Safety Electrical Appliances Testing and Inspection Policy The University of Auckland provides for specific safe operating practices for the safety testing and inspection

More information

Electrical safety code of practice 2013. Managing electrical risks in the workplace

Electrical safety code of practice 2013. Managing electrical risks in the workplace Electrical safety code of practice 2013 Managing electrical risks in the workplace This Queensland code of practice has been approved by the Attorney-General and Minister for Justice and commences on 1

More information

Transformers from 25va to 500kva. Standard despatch in days not weeks

Transformers from 25va to 500kva. Standard despatch in days not weeks Transformers from 25va to 500kva Standard despatch in days not weeks JMS Transformers Ltd 20 Ivatt Way Westwood Business Park Peterborough PE3 7PG UK Tel: +44 (0)1733 760000 Fax +44 (0)1733 760004 e-mail:

More information

Electrical Hazards. Power Tools. Extension Cords

Electrical Hazards. Power Tools. Extension Cords Electrical Hazards Electrical hazards can be found in nearly every roofing work site. Whether the hazard is posed by worn or damaged power tools or cords, improperly grounded tools or equipment, or the

More information

FARM SAFETY STARTER GUIDE

FARM SAFETY STARTER GUIDE Property of FARM SAFETY STARTER GUIDE Disclaimer This publication may contain occupational health and safety and workers compensation information. It may include some of your obligations under the various

More information

Electrical Wiring Methods, Components and Equipment for General Use. Approved for Public Release; Further Dissemination Unlimited

Electrical Wiring Methods, Components and Equipment for General Use. Approved for Public Release; Further Dissemination Unlimited Electrical Wiring Methods, Components and Equipment for General Use Approved for Public Release; Further Dissemination Unlimited At the completion of this unit you shall be able to: 1. Utilize section

More information

See Table of Amendments

See Table of Amendments Title: Electrical Safety Procedure Version 1.2 TRIM file number Short description Relevant to Authority Responsible officer Responsible office 06/XXXX A procedure on ensuring the safe and reliable supply

More information

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D 12 - ELECTRIC SERVICE HANDBOOK SECTION D METER REQUIREMENTS This chapter gives you information on Central Lincoln s metering requirements. It's divided into three sections: General requirements This section

More information

Guidance notes for the installation of electrical supply in mobile trailers for breast screening

Guidance notes for the installation of electrical supply in mobile trailers for breast screening NHS Breast Cancer Screening Programme Cancer Screening Programmes Guidance notes for the installation of electrical supply in mobile trailers for breast screening B Mansfield, CP Lawinski NHSBSP PUBLICATION

More information

Electrical Grounding. Appendix C

Electrical Grounding. Appendix C Appendix C Electrical Grounding Low-Voltage Equipment Grounding The most frequently cited Office of Safety and Health Administration (OSHA) electrical violation is improper occupational grounding of equipment

More information

MISCELLANEOUS ELECTRICAL JOBS REQUIRING PERMITS

MISCELLANEOUS ELECTRICAL JOBS REQUIRING PERMITS MISCELLANEOUS ELECTRICAL JOBS REQUIRING PERMITS 01. SAFETY INSPECTION of service equipment at FPL Power Source 02. Construction GFI power outlets (Temp Pole for Construction) 03. 90 day temporary power

More information

DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS

DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS MIOSHA-STD-1313 (10/15) 6 Pages For further information Ph: 517-284-7740 www.michigan.gov/mioshastandards DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS

More information

Residual Current Devices. Switching on to Safety

Residual Current Devices. Switching on to Safety Residual Current Devices Switching on to Safety Contents What is a Residual Current Device? 2 Types of RCDs 3 Switchboard RCDs 3 1 Residual Current Devices Socket outlet RCDs 4 Portable RCDs 4 Changes

More information

NZQA registered unit standard 15848 version 6 Page 1 of 5. Demonstrate and apply knowledge of safeguards for use with portable electrical appliances

NZQA registered unit standard 15848 version 6 Page 1 of 5. Demonstrate and apply knowledge of safeguards for use with portable electrical appliances Page 1 of 5 Title Demonstrate and apply knowledge of safeguards for use with portable electrical appliances Level 2 Credits 3 Purpose This unit standard covers knowledge of safeguards used in conjunction

More information

St Peter s College ELECTRICAL SAFETY. B. University Safety Office Policy Statement S4/10, Working safely with Electricity.

St Peter s College ELECTRICAL SAFETY. B. University Safety Office Policy Statement S4/10, Working safely with Electricity. St Peter s College ELECTRICAL SAFETY References: A. Peninsula Business Services Guidance Note 4-1, Electrical Safety. B. University Safety Office Policy Statement S4/10, Working safely with Electricity.

More information

Ontario Electrical Safety Code 25 th Edition/ 2012

Ontario Electrical Safety Code 25 th Edition/ 2012 Ontario Electrical Safety Code 25 th Edition/ 2012 Ted Olechna Director, Codes and Standard Chief Engineer 1 What I Will Cover ESA s role is as the regulator Highlight of 2012 Code changes The Code and

More information

Intertek Research & Performance Testing Technical Report S64604 Issue 1 Page 1 of 17. Report issued by: S64604 Issue 1

Intertek Research & Performance Testing Technical Report S64604 Issue 1 Page 1 of 17. Report issued by: S64604 Issue 1 Intertek Research & Performance Testing Technical Report S64604 Issue 1 Page 1 of 17 TECHNICAL REPORT Client: Stephen Curtler Electrical Safety Council 18 Buckingham Gate London SW1E 6LB Report issued

More information

Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016. Underground branch circuit feeding a detached garage:

Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016. Underground branch circuit feeding a detached garage: Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016 * Garage construction requires permits (electrical, building) * Permits must be applied for at the time. * Dial

More information

Section B: Electricity

Section B: Electricity Section B: Electricity We use mains electricity, supplied by power stations, for all kinds of appliances in our homes, so it is very important to know how to use it safely. In this chapter you will learn

More information

NEW ZEALAND ELECTRICAL CODE OF PRACTICE REPAIR AND MAINTENANCE OF DOMESTIC ELECTRICAL APPLIANCES BY THE OWNER OF THE APPLIANCE

NEW ZEALAND ELECTRICAL CODE OF PRACTICE REPAIR AND MAINTENANCE OF DOMESTIC ELECTRICAL APPLIANCES BY THE OWNER OF THE APPLIANCE NZECP 50:2004 ISSN 0114-0663 NEW ZEALAND ELECTRICAL CODE OF PRACTICE FOR REPAIR AND MAINTENANCE OF DOMESTIC ELECTRICAL APPLIANCES BY THE OWNER OF THE APPLIANCE Issued by: Deputy Secretary Energy Safety

More information

REB 1 REB 3 REB 5 REB 6 REB 8 REB 10 REB 12 REB 16

REB 1 REB 3 REB 5 REB 6 REB 8 REB 10 REB 12 REB 16 REB 1 REB 3 REB 5 REB 6 REB 8 REB 10 REB 12 REB 16 Manually Operated Electronic Speed Controller Single Phase For all applications using suitably specified single-phase induction motor fans 1 GENERAL The

More information

FAQs-Main switchboard design criteria

FAQs-Main switchboard design criteria FAQs-Main switchboard design criteria Q: What is the Australian standard for main switchboards? Current Australian standard is AS/NZS 3439.1: 2002 originating from IEC 60439. The new series of standard

More information

chapter8 Testing and commissioning Unit 2 outcome 2

chapter8 Testing and commissioning Unit 2 outcome 2 Testing and commissioning chapter8 Unit 2 outcome 2 It is important that electricians are not just able to construct; they should also be able to recognise faults and take action to help prevent them.

More information

Union County Public Schools. Facilities Department. Electrical. Safe Work Practices

Union County Public Schools. Facilities Department. Electrical. Safe Work Practices 1 Union County Public Schools Facilities Department Electrical Safe Work Practices 2 Purpose In accordance with OSHA Standards 1910.331-335, safety-related work practices shall be used by Union County

More information

STANDARDS AUSTRALIA/STANDARDS NEW ZEALAND

STANDARDS AUSTRALIA/STANDARDS NEW ZEALAND AS/NZS 3000/Amdt 1/-07-30 STANDARDS AUSTRALIA/STANDARDS NEW ZEALAND Amendment to AS/NZS 3000:2007 Electrical installations (known as the Australian/New Zealand Wiring Rules) REVISED TEXT The 2007 edition

More information

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting 12 SOLAR PHOTOVOLTAIC POWER by John Ware IT IS PLANNED for BS 7671:2008 to include a new Section 712 providing additional requirements for safety applicable to solar photovoltaic (pv) power supply systems.

More information

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV 1. SCOPE This document details PowerSystems requirements for electrical testing of HV Equipment up to and including 33kV. 2. ISSUE RECORD This is a Reference document. The current version of Controlled

More information

Fire Protection Notice No. 9 ELECTRICAL SAFETY

Fire Protection Notice No. 9 ELECTRICAL SAFETY Fire Protection Notice No. 9 ELECTRICAL SAFETY Because electricity is one of the most controllable forms of energy it can also be one of the safest. But, as industry and commerce draw ever more heavily

More information

HOW TO CORRECTLY CONNECT DEEP CYCLE BATTERIES AND CHOOSE THE RIGHT CABLE SIZING

HOW TO CORRECTLY CONNECT DEEP CYCLE BATTERIES AND CHOOSE THE RIGHT CABLE SIZING HOW TO CORRECTLY CONNECT DEEP CYCLE BATTERIES AND CHOOSE THE RIGHT CABLE SIZING There are several ways to wire multiple batteries to achieve the correct battery voltage or capacity for a particular DC

More information

INFRARED QUARTZ WALL HEATER

INFRARED QUARTZ WALL HEATER INFRARED QUARTZ WALL HEATER MODEL NO: IQ2000 PART NO: 6939004 MOUNTING & OPERATION INSTRUCTIONS GC0715 INTRODUCTION Thank you for purchasing this CLARKE Infrared Wall Heater. Before attempting to use this

More information

Maintaining portable electric equipment in low-risk environments

Maintaining portable electric equipment in low-risk environments Maintaining portable electric equipment in low-risk environments Introduction This leaflet explains the simple and sensible precautions that need to be taken to prevent danger from portable or movable

More information

LUCCI AIRFUSION QUEST II CEILING FAN

LUCCI AIRFUSION QUEST II CEILING FAN LUCCI AIRFUSION QUEST II CEILING FAN WITH IR REMOTE INSTALLATION OPERATION MAINTENANCE WARRANTY INFORMATION CAUTION READ INSTRUCTIONS CAREFULLY FOR SAFE INSTALLATION AND FAN OPERATION. V1.0 QUEST II IR

More information

Contractor Connect Scheme Electrical Contractor and Worker Handbook

Contractor Connect Scheme Electrical Contractor and Worker Handbook Contractor Connect Scheme Electrical Contractor and Worker Handbook January 2016 Document release information Document number 13553681 Document title Revision status Contractor Connect Scheme handbook

More information

WORKING GUIDE 1996 FROM HOME. WorkCover. Watching out for you. New South Wales Government

WORKING GUIDE 1996 FROM HOME. WorkCover. Watching out for you. New South Wales Government WORKING FROM HOME GUIDE 1996 WorkCover. Watching out for you. New South Wales Government Disclaimer This publication may contain occupational health and safety and workers compensation information. It

More information

1 Introduction. 2 Hazards From Electricity

1 Introduction. 2 Hazards From Electricity Risk Assessment Application to Electrical Rigs A guide to assist the Competent Named person who will verify the safety of rigs consisting mainly of electrical equipment. 1 Introduction Every employer shall

More information

MANAGING ELECTRICAL RISKS IN THE WORKPLACE

MANAGING ELECTRICAL RISKS IN THE WORKPLACE MANAGING ELECTRICAL RISKS IN THE WORKPLACE Code of Practice MARCH 2015 Safe Work Australia is an Australian Government statutory agency established in 2009. Safe Work Australia consists of representatives

More information

Installation. Smart-UPS VT MGE Galaxy 3500. Maintenance Bypass Panel. 10-40 kva 400 V

Installation. Smart-UPS VT MGE Galaxy 3500. Maintenance Bypass Panel. 10-40 kva 400 V Installation Smart-UPS VT MGE Galaxy 3500 Maintenance Bypass Panel 10-40 kva 400 V Contents Safety.................................................. 1 Save these instructions...................................

More information

GUIDE TO THE AM2 EXAM

GUIDE TO THE AM2 EXAM AM2 GUIDE TO THE AM2 EXAM What is AM2? AM2 or the Achievement Measurement 2 is a practical performance skill test administered by the National Electrotechnical Training (NET). You must take the AM2 test

More information

3 IN 1 BATHROOM HEATER

3 IN 1 BATHROOM HEATER 3 IN 1 BATHROOM HEATER MODEL NO.: A515 - SH MINI FUNCTION: HEATER, EXHAUST FAN AND LIGHT Dear customers, Thank you for selecting the AUPU 3 in 1 Bathroom Heater. Please read all instructions before commencing

More information

Circuit Electrical Testing

Circuit Electrical Testing Safe Isolation Procedure Circuit Electrical Testing Site Safety Management It is essential from the outset that effective management and control of the system, apparatus and equipment used on site is achieved

More information

Achat 115MA full-range speaker. user manual

Achat 115MA full-range speaker. user manual Achat 115MA full-range speaker user manual Musikhaus Thomann Thomann GmbH Hans-Thomann-Straße 1 96138 Burgebrach Germany Telephone: +49 (0) 9546 9223-0 E-mail: info@thomann.de Internet: www.thomann.de

More information

The Electrical Safety Regulation (pre and post 1 January 2014)

The Electrical Safety Regulation (pre and post 1 January 2014) The Electrical Safety Regulation (pre and post 1 January 2014) The following table provides an overview comparison between the Electrical Safety Regulation 2002 (the ESR 2002) current as at 1 July 2013

More information

SCAFFOLDING AUGUST 2008. making a difference ERECTING, ALTERING AND DISMANTLING PART 1: PREFABRICATED STEEL MODULAR SCAFFOLDING

SCAFFOLDING AUGUST 2008. making a difference ERECTING, ALTERING AND DISMANTLING PART 1: PREFABRICATED STEEL MODULAR SCAFFOLDING ERECTING, ALTERING AND DISMANTLING SCAFFOLDING PART 1: PREFABRICATED STEEL MODULAR SCAFFOLDING INDUSTRY SAFETY STANDARD AUGUST 2008 making a difference New South Wales Government Disclaimer This publication

More information

INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1

INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1 City of Cotati Building Division 201 W. Sierra Ave. Cotati, CA 94931 707 665-3637 Fax 792-4604 INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1 Any PV system on a new structures should be included

More information

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

Submit shop drawings for equipment provided under this section Shop drawings shall indicate: Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,

More information

Bypass transfer switch mechanisms

Bypass transfer switch mechanisms Power topic #6013 Technical information from Cummins Power Generation transfer switch mechanisms > White paper By Gary Olson, Director, Power Systems Development This paper describes the configuration

More information

INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE SAFETY BULLETIN #23

INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE SAFETY BULLETIN #23 INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE SAFETY BULLETIN #23 GUIDELINES FOR WORKING WITH PORTABLE POWER DISTRIBUTION SYSTEMS AND OTHER ELECTRICAL EQUIPMENT "ADDENDUM C" WORKING WITH 480 VOLT SYSTEMS

More information

October Safety Subject

October Safety Subject October Safety Subject Electrical Hazards All electrical equipment should be kept in good repair. Replace defective equipment or have it repaired by a qualified person. Watch for wiring on appliances that

More information

Wiser Panel Meter, Model Number WISERCTPM200 Installer s Guide

Wiser Panel Meter, Model Number WISERCTPM200 Installer s Guide Instruction Bulletin EAV85226 08/2014 Wiser Panel Meter, Model Number WISERCTPM200 Installer s Guide Retain for future use. Product Description Kit Contents The Wiser Panel Meter is for use in energy management

More information

Contractor s Safe Working Agreement

Contractor s Safe Working Agreement Contractor s Safe Working Agreement This statement provides details on how I/we, the Trade Contractor will manage the health and safety hazards associated with my/our work. ASSESSING WORKPLACE HEALTH AND

More information

Lift and Escalator Installations

Lift and Escalator Installations Buildings Department Practice Note for Authorized Persons, Registered Structural Engineers and Registered Geotechnical Engineers APP-29 Lift and Escalator Installations Building Works Requirements The

More information

DIOCESE OF LINCOLN GUIDELINES

DIOCESE OF LINCOLN GUIDELINES DIOCESE OF LINCOLN GUIDELINES FOR ELECTRICAL INSTALLATIONS INSIDE CHURCHES Diocesan Advisory Committee for the Care of Churches Revised March 2006 Electrical Installations inside Churches As with all

More information

Building Regulations P.4. Socket Outlets P.6. Other Considerations P.10. Training Seminars P.24

Building Regulations P.4. Socket Outlets P.6. Other Considerations P.10. Training Seminars P.24 1 Introduction For well over one hundred years the Wiring Regulations have provided the rules which must be followed to make sure that electrical installations are safe. The introduction of the 17 th Edition

More information

GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264

GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264 BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used

More information

Separation of common services (above and below ground) INDUSTRY BULLETIN. Background. Separation distances. Proximity of services below ground

Separation of common services (above and below ground) INDUSTRY BULLETIN. Background. Separation distances. Proximity of services below ground Government of Western Australia Department of Commerce Separation of common services (above and below ground) The purpose of this industry bulletin is to remind building practitioners of their responsibilities

More information

ALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR 1910.147 THE CONTROL OF HAZARDOUS ENERGY (LOCKOUT / TAGOUT) SECTION: 2400

ALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR 1910.147 THE CONTROL OF HAZARDOUS ENERGY (LOCKOUT / TAGOUT) SECTION: 2400 OSHA REGULATION: 29 CFR 90.7 THE CONTROL OF HAZARDOUS ENERGY (LOCKOUT / TAGOUT) DATE: 0/5/2008 DATE: /2/202 A. POLICY. This procedure follows requirements set forth in 29 CFR 90.7. 2. It is the policy

More information

ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST

ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST Name of School: OPTIONAL INFORMATION Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST Guidelines: This checklist

More information

USER MANUAL CHARGING STATIONS FOR ELECTRIC VEHICLES

USER MANUAL CHARGING STATIONS FOR ELECTRIC VEHICLES USER MANUAL CHARGING STATIONS FOR ELECTRIC VEHICLES 204.CAxxx 204.CBxxx 204.UBxxx 204.WBxxx MP36289 1 ZP90856-GB-6 INDICE 1 SYSTEM DESCRIPTION... 4 1.1 MODES OF OPERATION... 4 2 USER INTERFACE... 6 2.1

More information

High Voltage (HV) Electricity System Safety Rules and Associated Safety Guidance

High Voltage (HV) Electricity System Safety Rules and Associated Safety Guidance Annex I To Loughborough University (LU) Facilities Management (FM) Health and Safety Policy High Voltage (HV) Electricity System Safety Rules and Associated Safety Guidance 1. Introduction a. These Safety

More information

How To Keep An Eye On Electric Safety

How To Keep An Eye On Electric Safety Table of Contents Keep an Eye on Electric Safety................ 1 Safety in an Emergency...................... 1 Downed Power Lines...................... 1 Keep an Eye on Electric Safety Electricity is

More information

ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants. Installation instructions ESP M1/M1R mains protectors

ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants. Installation instructions ESP M1/M1R mains protectors ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants Installation instructions Contents Key points of installation Before installation Installation Installation check

More information

Determining the Cause of AFCI Tripping Branch/Feeder and Combination Arc Fault Circuit Interrupters Class 760

Determining the Cause of AFCI Tripping Branch/Feeder and Combination Arc Fault Circuit Interrupters Class 760 Data Bulletin Determining the Cause of AFCI Tripping Branch/Feeder and Combination Arc Fault Circuit Interrupters Class 760 Retain for future use. 0760DB0204 Replaces 0760DB0204 R09/07 Precautions DANGER

More information

Instruction Bulletin. MCS025 Sync-Check Module Installation Sheet

Instruction Bulletin. MCS025 Sync-Check Module Installation Sheet Instruction Bulletin 63230-216-244B1 LaVergne, TN, USA MCS025 Sync-Check Module Installation Sheet Retain for future use. DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Only qualified electrical

More information

Extension Cord Safety Policy

Extension Cord Safety Policy NATIONAL HIGH MAGNETIC FIELD LABORATORY Operated by Florida State University, University of Florida, Los Alamos National Laboratory Florida State University, 1800 East Paul Dirac Drive, Tallahassee, Florida

More information

Electrical Safety Products

Electrical Safety Products Electrical Safety Products Trelleborg Electrical Safety Products A safe working environment is important in all industries, but in the electrical generation and supply industry, it is paramount. Trelleborg

More information

SECTION 3(6) ELECTRICITY AT WORK

SECTION 3(6) ELECTRICITY AT WORK SECTION 3(6) ELECTRICITY AT WORK CONTENTS Page No Introduction Principal general duties Competent persons Frequency of Inspection and Testing Inspection of Portable Equipment Testing Documentation Privately

More information

The following components are common to most cubicles; this example is an ABB HK cubicle.

The following components are common to most cubicles; this example is an ABB HK cubicle. 4.0 CIRCUIT BREAKER CUBICLE Learning Objectives The circuit breaker cubicle is the component of the switchgear that holds the circuit breaker, and the controls and cabling for the distribution system.

More information

SAFETY OF SOLAR PANEL INSTALLATIONS IN VICTORIA REPORT

SAFETY OF SOLAR PANEL INSTALLATIONS IN VICTORIA REPORT SAFETY OF SOLAR PANEL INSTALLATIONS IN VICTORIA REPORT July 2010 Table of Contents Executive Summary... 3 Glossary of Acronyms and Phrases.....4 Introduction...5 Background 6 Electricity safety requirements

More information