1 Installation and Maintenance Manual IM Group: Controls Part Number: IM 963 Date: July 2010 Supercedes: IM 963 Daikin Magnitude TM Chiller Unit Controller BACnet Communication Module (MS/TP, IP, Ethernet) Daikin Magnitude Frictionless Centrifugal Chiller, Single-Compressor Model WME NOTICE Use this manual to physically install the Daikin Applied BACnet Communication Module into the Daikin Daikin Magnitude Chiller unit controller and connect the unit controller to your network. Use the appropriate Daikin Applied Engineering Data (ED), known as the Protocol Information document, to integrate the unit into your network. The Protocol Information document contains addressing details, BACnet protocol information, and a list of the data points available to the network. See the Reference Documents section of this manual for Protocol Information document numbers. Magnitude Chiller control integration literature is available from your local Daikin Applied sales representative and Daikin Applied
2 Contents Figures Figures... 2 Revision History... 3 Reference Documents... 3 Limited Warranty... 3 General Information... 4 Hazard Identification Messages... 4 Description... 5 Application... 5 Component Data... 6 Light Emitting Diodes (LEDs)... 6 BACnet Network Connector... 7 J8 Jumper... 7 Installation... 8 Contents of the BACnet Communication Module Kit... 8 Installing a new BACnet Communication Module... 8 Replacing an Existing BACnet Communication Module... 9 Integration Introduction BACnet MS/TP Addressing BACnet MS/TP Configuration Changing the BACnet MS/TP Data Transmission Rate BACnet MS/TP Configurable Parameters BACnet IP Addressing BACnet IP Configuration BACnet IP Configurable Parameters BACnet Ethernet Configuration BACnet Ethernet Configurable Parameters Service Information...18 Troubleshooting General BACnet IP BACnet MS/TP Parts List Figure 1. BACnet Communication Module Attached to Chiller Unit Controller... 5 Figure 2. BACnet Communication Module Components... 6 Figure 3. OITS Display of Network Parameters BAS Figure 4. OITS Display of Network Parameters BAS IM 963-1
3 Revision History IM 963 April 2010 Initial release IM July 2010 Changed kit part number in Parts List. Reference Documents Number Company Title Source ANSI/ASHRAE American Society of BACnet A Data Communication Protocol for Building Heating, Refrigerating and Air-Conditioning Engineers Automation and Control Networks OM 1034 Daikin Applied Magnitude Frictionless Centrifugal Chiller Operation and Maintenance Manual ED Daikin Applied Magnitude Chiller Unit Controller Protocol Information, BACnet and LONWORKS Networks ED Daikin Applied Magnitude Chiller Unit Controller Protocol Information, BACnet Protocol Implementation Conformance Statement (PICS) Limited Warranty Consult your local Daikin Applied Representative for warranty details. Refer to Form Y. To find your local Daikin Applied Representative, go to Notice Copyright 2013 Daikin Applied, Minneapolis MN. All rights reserved throughout the world. Daikin Applied reserves the right to change any information contained herein without prior notice. The user is responsible for determining whether this software is appropriate for his or her application. The following are tradenames or registered trademarks of their respective companies: BACnet from the American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.; Windows from Microsoft Corporation; and Magnitude from Daikin Applied. IM
4 General Information This manual contains the information you need to install the BACnet Communication Module on a Magnitude Frictionless Centrifugal Chiller Unit Controller, incorporate it into the BACnet network, and maintain it. Hazard Identification Messages! DANGER Dangers indicate a hazardous situation which will result in death or serious injury if not avoided.! WARNING Warnings indicate potentially hazardous situations, which can result in property damage, severe personal injury, or death if not avoided.! CAUTION Cautions indicate potentially hazardous situations, which can result in personal injury or equipment damage if not avoided.! WARNING Electric shock hazard. Can cause personal injury or equipment damage. This equipment must be properly grounded. Connections and service to the Magnitude Chiller Unit Controller must be performed only by personnel knowledgeable in the operation of the equipment being controlled.! CAUTION Static sensitive components. Can cause equipment damage. Discharge any static electrical charge by touching the bare metal inside the control panel before performing any service work. Never unplug cables, circuit board terminal blocks, or power plugs while power is applied to the panel. NOTICE This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with this instruction manual, may cause interference to radio communications. It has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his or her own expense. Daikin Applied disclaims any liability resulting from any interference or for the correction thereof. 4 IM 963-1
5 Description The BACnet Communication Module incorporates a Magnitude Chiller Unit Controller into a BACnet local area network (LAN) and provides access to the unit controller parameters via BACnet MS/TP, BACnet IP, or BACnet Ethernet. See Table 2 for a detailed description of each network connection. The BACnet Communication Module attaches to the upper left section of the Magnitude Chiller s main unit controller circuit board. This area is labeled BAS Interface Board (see Figure 1.) The main unit controller circuit board itself is labeled Chiller I/O Backplane and will be referred to as such for the remainder of this document. Figure 1. BACnet Communication Module Attached to Chiller Unit Controller BACnet communication module (attached) Application The BACnet Communication Module connects the Magnitude Chiller Unit Controller to a building automation system (BAS) on a BACnet local area network. It is the interface for the exchange of BACnet objects between the network and the unit controller. Refer to the Magnitude Frictionless Centrifugal Chiller Operation & Maintenance Manual (OM 1034) for unit controller details. For a complete list of available BACnet points, refer to the Magnitude Chiller Unit Controller - Protocol Document, ED (all literature available on IM
6 Component Data Figure 2 shows the important features of the BACnet Communication Module, which include the LED locations, network connections, and J8 jumper. Figure 2. BACnet Communication Module Components Common BACnet MS/TP Network Connector + - BACnet IP/Ethernet Network Connector D2 D4 Ethernet LED D5 J8 Jumper D7 D9 D8 Light Emitting Diodes (LEDs) The BACnet Communication Module has six LEDs to indicate communication activity and data transmission status. These indicators are visible when the communication module is connected to the Magnitude Chiller I/O Backplane and the unit is powered on. See Figure 2 for LED locations and Table 1 for descriptions of LED activity. 6 IM 963-1
7 Table 1. Description of LED Activity LED Color Meaning D2 Green Communication module supports a BACnet network. If present, this LED will always be lit when 5VDC power (supplied from the chiller unit controller) is present. D4 Yellow Indicates local 3.3 VDC power is present. D5 Yellow Flashes when the communication module transmits data to the chiller unit controller. D7 Green Flashes when the communication module receives data from the chiller unit controller. D8 Green Flashes when the communication module receives data from the BACnet network. D9 Yellow Flashes when the communication module transmits data to the BACnet network. BACnet Network Connector The BACnet communication module can be used to connect to a BACnet MS/TP, BACnet IP, or BACnet Ethernet network. There are two separate network connectors available, depending on the type of network that is connected. See Table 2 below. Table 2. BACnet Network Connection Details Network BACnet MS/TP Connector Type An RS485 connector links the BACnet Communication Module to the MS/TP network. The connector port has three pins: +, -, and Common. Pin 1 COM Common (isolated from host controller) Pin 2 Tx/Rc + EIA485 Transmit/Receive Positive BACnet IP or BACnet Ethernet Pin 3 Tx/Rc - EIA485 Transmit/Receive Negative An RJ45 connector links the BACnet Communication Module to the BACnet IP or BACnet Ethernet network. The LEDs for this connector function as follows: Green This LED flashes to indicate Ethernet activity. If configured for MS/TP, this LED does not flash green, even if it is connected to an active Ethernet port. Yellow This LED indicates the port speed. The communication module always operates in full-duplex mode. If the output is Off, the speed is 10 mbps. If the output is On, the speed is 100 mbps. 16-Pin Header The 16-pin header connects the Chiller I/O Backplane to the BACnet communication module through the bottom of the communication module. The pins are on located on the back side of the of the communication module. J8 Jumper The BACnet Communication Module has a built-in terminating resistor labeled J8 on the circuit board. The communication module ships with the jumper installed, providing 120 Ohms of end-ofline resistance to the network. Typically, a network is terminated at each end of each segment. However, it is the responsibility of the system installer/integrator to recommend whether or not to terminate a device within the network. If the device does not require terminating resistance, or if an external terminating resistor is used, the jumper on J8 should be removed. See Figure 2 for location. IM
8 Installation The following section describes how to field install a new BACnet Communication Module or replace an existing BACnet Communication Module on the Magnitude Chiller I/O backplane (i.e. unit controller main circuit board) so that it can be incorporated into the BACnet network.! CAUTION Electrostatic discharge hazard. Can cause equipment damage. This equipment contains sensitive electronic components that may be damaged by electrostatic discharge from your hands. Before you handle a communications module, you need to touch a grounded object, such as the metal enclosure, in order to discharge the electrostatic potential in your body. Contents of the BACnet Communication Module Kit The following is the list of items included in the field-installed kit: The BACnet Communication Module BACnet MS/TP Network connector (attached to communication module) J8 jumper (attached to communication module) Two screws Installation Manual IM 963 Installing a new BACnet Communication Module Follow these steps to install a new BACnet Communication Module on the Magnitude Chiller I/O backplane.! WARNING Electric shock hazard. Can cause personal injury or equipment damage. This equipment must be properly grounded. Only personnel knowledgeable in the operation of the equipment being controlled must perform connections and service to the unit controller. 1. Remove power from the Magnitude Chiller Unit Controller. 2. Connect the BACnet Communication Module to the upper left corner of the chiller I/O backplane, in the area labeled BAS Interface Board (see Figure 1). Carefully align the holes on the communication module with the two standoffs attached to the chiller I/O backplane.! CAUTION Carefully align the holes on the communication module with the standoffs on the chiller I/O backplane. Powering up the controller with the communication module installed upside down can cause damage to the communication module. 3. Using the two screws that came with the communication module kit, attach the communication module to the standoffs located on the chiller I/O backplane. 4. Connect the communication module to the network (see Figure 2 for location of network connection). 5. Apply power to the unit controller. 8 IM 963-1
9 Replacing an Existing BACnet Communication Module Follow these steps to remove an existing BACnet Communication Module from the chiller I/O backplane and replace it with a new BACnet Communication Module.! WARNING Electric shock hazard. Can cause personal injury or equipment damage. This equipment must be properly grounded. Only personnel knowledgeable in the operation of the equipment being controlled must perform connections and service to the Magnitude Chiller Unit Controller. 1. Remove power from the unit controller. 2. Locate the communication module. It is situated at the upper left corner of the chiller I/O backplane (see Figure 1). 3. Remove the network cable connector from the communication module. 4. Remove the two screws holding the communication module in place. 5. Grasp the communication module and carefully pull it from the chiller I/O backplane. 6. Install the new communication module (see Steps 1-3 from previous section). 7. Re-attach the two screws to secure the communication module to the chiller I/O backplane. 8. Insert the network cable connector into the communication module. 9. Apply power to the unit controller. IM
10 Integration Introduction Once the BACnet Communication Module has been properly installed on the unit controller, it is then possible to integrate the unit controller into a building automation system (BAS) via the BACnet network. The addressing and configuration process is described separately for each protocol (BACnet MS/TP, BACnet IP, and BACnet Ethernet) in the following sections. The BACnet Communication Module can be configured using the Magnitude chiller unit controller Operator Interface Touch Screen (OITS) display. The unit is ready to operate after you have configured the parameter values of the unit controller for your particular network. Refer to the Magnitude Chiller Operation and Maintenance Manual (OM 1034) for default values and unit controller OITS operating instructions. Refer to Daikin Applied Protocol Document ED for descriptions of all the available BACnet parameters. Figures 3 and 4 show the chiller unit controller OITS display screens with the corresponding network parameters available for configuration. These two screens (titled BAS1 and BAS2) are accessed by pressing the BAS button at the top of the column on the right-hand side of the main unit controller OITS display. Note: Refer to the Magnitude Chiller Operation and Maintenance Manual (OM 1034) for details regarding accessing and using the unit controller OITS display. BACnet MS/TP Addressing The BACnet MS/TP Media Access Control (MAC) address is a one-octet address that must be set during the BACnet Communication Module configuration. The MAC address must be unique to the MS/TP network and have a valid range of Additionally, there are certain parameters that must be set properly to verify communication between Magnitude Chiller Unit Controller and the MS/TP network. Table 3 provides details about these addressing parameters. See your system integrator for additional information regarding proper BACnet MS/TP addressing. BACnet MS/TP Configuration 1. Open the Magnitude chiller unit controller OITS display screen. 2. Press the SET button, located at the bottom of the screen. 3. Press the BAS button from the top of the column on the right-hand side of the screen. 4. Press the 1 button, located to the right of the BAS Network Protocol field. The BAS Network Protocol field should now be highlighted (see Figure 3). 5. Press the Change button. 6. If prompted, enter the password 100 and press Enter. Otherwise, proceed to step Press the Change button. 8. Select BACnet MSTP from the drop-down menu. 9. Press the Enter button. 10. Press the BAS button to access the second BAS screen (BAS2). 11. Set the BACnet MS/TP MAC Address within the valid range of Verify the baud rate of the unit controller (see next section, Changing the BACnet Data Transmission Rate, for details). 13. Modify the remaining BACnet parameters as necessary. See Table 3 for a complete list. 10 IM 963-1
11 14. Cycle power to the unit controller. Changing the BACnet MS/TP Data Transmission Rate The options for baud rate (in bps) include: 9600, 19200, 38400, The factory default baud rate is bps. Follow the steps below to change the baud rate for desired network speed via the OITS display: 1. If you are at the BAS2 screen, proceed to Step 4 (see Figure 4). 2. If you are on the BAS1 screen, press the BAS button and proceed to Step From any other screen, press the SET button once and then press the BAS button twice. 4. Press the 5 button, located to the right of the BACnet MS/TP - Baud Rate field. The BACnet MS/TP - Baud Rate field should now be highlighted. 5. Press the Change button. 6. If prompted, enter the password 100 and press Enter. Otherwise, proceed to step Press the Change button. 8. Press the desired baud rate from the drop-down menu. 9. Press the Enter button. The new baud rate will take effect in approximately 60 seconds. BACnet MS/TP Configurable Parameters Table 3 defines the BACnet Communication Module network parameters that are configurable via the unit controller OITS display. Additional parameters are also configurable from the Building Automation System (BAS). For a complete list of available BACnet points, refer to the Magnitude Chiller Unit Controller Protocol Document, ED15117 (available on The following parameters are all read from the unit controller during the communication module s initialization phase. If any parameter in Table 3 (except BAS Network Protocol and English/Metric) is changed at via the unit controller OITS display during run-time, the update is automatically applied to the BACnet communication module as soon as the change is received. Change parameters as required for your network. At a minimum, you must set the following before establishing network communication between the unit controller and the BAS: 1. BAS Network Protocol 2. Device Instance 3. MAC Address 4. Verify the correct baud rate and change if necessary IM
12 Table 3. BACnet MS/TP Configuration Parameters Parameter Value (Range)/Definition Initial Value/Note BAS Network Protocol Device Instance MAC Address 1 Object Name Baud Rate 1 Max Masters Max Info Frames English / Metric BACnet MSTP/This point sets the desired network protocol /Device Instance of the BACnet communication module / This is the MS/TP address of the BACnet communication module. The allowable range of characters for the device object name is 1 to 31 characters. /If an empty string is read from the controller, the initial value is used. The device object name is visible to BACnet as the object name of the device object / Data transfer speed / This variable specifies the highest possible address for master. nodes and must be set to less than or equal to / This variable specifies the maximum number of information frames the BACnet communication module may send before it must pass the token. English (0)-Metric(1)/Determines the type of units that are passed through the BACnet network. 1 Parameter only available via the unit controller OITS display None/Set this value to BACnet MS/TP. The unit controller must be reset after changing this parameter. 3000/This must be unique throughout the entire BACnet network. If a value greater than is read from the controller, the following default value will be used: address. Address = the last two octets of the MAC Address. 1/ Each device on the BACnet network must have a unique MS/TP address. Magnitude/ This name must be unique throughout the entire BACnet network. If an empty string is read from the controller, the BACnet communication module uses the following default: MTE Chiller UCA-address Where address is the MAC address. Changing the device object name may affect the operation of other BACnet devices on the network that have previously discovered the device. The BACnet communication module may take up to 60 seconds before this change is recognized. A power cycle is not needed English/To set the unit for Metric, set this variable to Metric. Cycle power to the unit controller after changing this parameter. 12 IM 963-1
13 BACnet IP Addressing There are key parameters of the BACnet/IP MAC layer that require configuration prior to connecting the unit controller to the BACnet network. These parameters require configuration via the chiller unit controller OITS display. They are not accessible from the BACnet network or BAS. These parameters include: IP Address Subnet Mask UDP Port Default Gateway Address BBMD Address Foreign Device Time-To-Live There are other parameters available via the chiller unit controller OITS display (Device Instance and Device Name, for example) that are also configurable via the BACnet network or BAS. See Table 4 for details. Note: Refer to the Magnitude Chiller Operation and Maintenance Manual (OM 1034) for details regarding accessing and using the Magnitude Chiller Unit Controller OITS display. BACnet IP Configuration 1. Open the Magnitude chiller unit controller OITS display screen. 2. Press the SET button, located at the bottom of the screen. 3. Press the BAS button from the top of the column on the right-hand side of the screen. 4. Press the 1 button, located to the right of the BAS Network Protocol field. The BAS Network Protocol field should now be highlighted (see Figure 3). 5. Press the Change button. 6. If prompted, enter the password 100 and press Enter. Otherwise, proceed to step Press the Change button. 8. Select BACnet IP from the drop-down menu. 9. Press the Enter button. 10. Press the BAS button. 11. Modify the remaining BACnet parameters as necessary. See Table 4 for a complete list. 12. Cycle power to the unit controller. Note: Device Instance, IP Address and Object Name must all be unique throughout the network. BACnet IP Configurable Parameters Table 4 defines the network parameters of the BACnet Communication Module that must be configured in order to establish communication between Magnitude Chiller Unit Controller Unit and the BACnet IP network. These parameters are set using the unit controller OITS display. These parameters are all read from the Magnitude Chiller Unit Controller during the BACnet communication module s initialization phase. Change parameters as required for your network. IM
14 Table 4. BACnet/IP Parameters Name BAS Network Protocol Device Instance Object Name Network Address Subnet Mask UDP Port Value (Range)/Definition BACnet IP/This point sets the desired network protocol /Device Instance of the BACnet Communication Module. The allowable range of characters for the device object name is 1 to 31 characters./if an empty string is read from the unit controller, the Initial Value is used. The device object name is visible to the BACnet network as the object name of the device object. IP Address of the BACnet Communication Module Subnet Mask of the BACnet Communication Module (User Datagram Protocol) Identifies the application process in the destination unit Initial Value/Note None/Set this value to BACnet IP. Cycle power to the unit controller after changing this parameter. 3000/This must be unique throughout the entire BACnet network. If a value greater than is read from the unit controller, the following default value is used: address. Where address is the last two octets of the MAC address. Magnitude/ This name must be unique throughout the entire BACnet network. If an empty string is read from the controller, the BACnet card will use the following default: MTE Chiller UCA-address Where address is the Ethernet MAC address. Changing the device object name may affect the operation of other BACnet devices on the network that have previously discovered the device. The BACnet Communication Module takes up to 60 seconds before this change is recognized. A power cycle is not needed / If the IP address is changed via the unit controller OITS display during run-time, the update is automatically applied to the BACnet Communication Module as soon as the change is received. The IP address is checked for validity as an IP address and against the Subnet Mask. If the address is not valid, the BACnet Communication Module does not enable BACnet/IP communications. The device does not initiate or respond to BACnet messages. If the IP address is changed at run-time and the address is not a valid IP address, the change is ignored. The existing address remains in effect. Changing the IP address may affect the operation of other BACnet devices on the network that may be dependent on objects within the device / If the Subnet Mask is changed, the update is automatically applied to the BACnet Communication Module as soon as the change is received. The Subnet Mask is checked for validity against the IP address. If the Subnet Mask is not valid, the BACnet Communication Module does not enable BACnet/IP communications. The device does not initiate or respond to BACnet messages. If the Subnet Mask is changed at run-time and the Subnet Mask is not a valid Subnet Mask, the change is ignored. The existing mask remains in effect Changing the Subnet Mask may affect the operation of other BACnet devices on the network that may be dependent on objects within the device / If the UDP Port is changed, the update is automatically applied to the BACnet Communication Module as soon as the change is received. Changing the UDP Port may affect the operation of other BACnet devices on the network if they are dependent on objects within the device. 14 IM 963-1
15 Name Default Gateway BBMD IP Address Foreign Device Time English / Metric Value (Range)/Definition Gateway address IP Address for the BACnet Broadcast Management Device (BBMD) if used / The time, in seconds, within which the foreign device must re-register with the BBMD. If it does not re-register, the BBMD removes it from its Foreign Device Table (FDT) and discontinues forwarding messages to the foreign device. English (0)- Metric(1)/Determines the type of units that are passed through the BACnet network. Initial Value/Note None / If the default gateway address is changed, the update is automatically applied to the BACnet Communication Module as soon as the change is received. Changing the default gateway address may affect the operation of other BACnet devices on the network if they are dependent on objects within the device. None / If the BBMD address is not 0, the BACnet Communication Module sends a Register-Foreign-Device message to the address. If the result code returned is X 0000, the BACnet Communication Module renews the registration at the period defined by the Foreign Device Time-To-Live value. If the BBMD address is changed, the update is automatically applied to the BACnet Communication Module as soon as the change is received. If the new value is 0, the existing signup is no longer refreshed and will be allowed to expire. In other words, when a BBMD IP address is defined here, a Register- Foreign-Device message is sent to register the chiller unit controller s IP address with the BBMD. This message is continuously sent out before the Foreign Device Time expires. If the new value is non-zero, a Register-Foreign- Device message is sent to the BBMD address that has been defined by this parameter. Changing the BBMD address may affect the operation of other BACnet devices on the network if they are dependent on objects within the device. 0/ If the Foreign Device Time-To-Live (FDTTL) is changed, the update is automatically applied to the BACnet Communication Module as soon as the change is received. If the new value is different from the existing value, a Register-Foreign-Device message is sent to the BBMD address. A minimum TTL of 15 seconds is enforced to avoid excessive network traffic. English/To set the unit for Metric, set this variable to Metric. Cycle power to the unit controller after changing this parameter. BACnet Ethernet Configuration 1. Open the Magnitude chiller unit controller OITS display screen. 2. Press the SET button, located at the bottom of the screen. 3. Press the BAS button from the top of the column on the right-hand side of the screen. 4. Press the 1 button, located to the right of the BAS Network Protocol field. The BAS Network Protocol field should now be highlighted (see Figure 3). 5. Press the Change button. 6. If prompted, enter the password 100 and press Enter. Otherwise, proceed to step Press the Change button. IM
16 8. Select BACnet Ethernet from the drop-down menu. 9. Press the Enter button. 10. Modify the remaining BACnet parameters as necessary. See Table 5 for a complete list. 11. Cycle power to the unit controller. Note: Device Instance and Object Name must be unique throughout the network. BACnet Ethernet Configurable Parameters Table 5 defines the network parameters of the BACnet Communication Module that must be configured in order to establish communication between Magnitude Chiller Unit Controller Unit and the BACnet IP network. These parameters must be set using the unit controller OITS display. The BACnet Ethernet MAC Address can also be read via the unit controller OITS display. Table 5. BACnet Ethernet Parameters Name Value (Range)/Definition Initial Value/Note BAS Network Protocol Device Instance Object Name BACnet Ethernet/ This point sets the desired network protocol /Device Instance of the BACnet Communication Module. The allowable range of characters for the device object name is 1 to 31 characters./if an empty string is read from the unit controller, the Initial Value is used. The device object name is visible to the BACnet network as the object name of the device object. None/Set this value to BACnet Ethernet. Cycle power to the unit controller after changing this parameter. 3000/This must be unique throughout the entire BACnet network. If a value greater than is read from the unit controller, the following default value is used: address Where address is the last two octets of the MAC address. Magnitude/ This name must be unique throughout the entire BACnet network. If an empty string is read from the controller, the BACnet card will use the following default MTE Chiller UCA-address Where address is the MAC address. Changing the device object name may affect the operation of other BACnet devices on the network that have previously discovered the device. The BACnet Communication Module takes up to 60 seconds before this change is recognized. A power cycle is not needed. Note: If unit controller application software requires uploading in the field, the network configuration parameters revert to their default values. Please contact the Daikin Applied Chiller Technical Response Center at for assistance with upgrading unit controller application software. 16 IM 963-1
17 Figure 3. OITS Display of Network Parameters BAS1 Figure 4. OITS Display of Network Parameters BAS2 IM
18 Service Information Troubleshooting General If you can control the unit from the chiller unit controller OITS display, but you are not able to communicate with unit via the BACnet network/bas workstation, follows these steps: Check the network wiring Verify BAS Network Protocol is set correctly using the chiller unit controller OITS display. Check the network parameters and verify that they are correct and that there are no duplicate devices on the network. Verify that the serial cable is connected from the CPU to the chiller I/O backplane board at J16 (ribbon cable) is connected. Reduce (isolate) the network to one single unit controller. Once this small network is working properly, continue to add more devices to the network. BACnet IP If Protocol Type is set to BACnet IP, use the standard TCP/IP suite of protocols to check your connectivity with other devices. Using the PC s Windows Command Prompt, type ping <IP address of the BACnet Communications Module>. If you get a response from that IP address, you are connected to the BACnet Communication Module. If you do not get a response, verify the BACnet Communication Module and the PC network settings. BACnet MS/TP BACnet MS/TP-specific communication errors could result from one or more of the following conditions below. Follow these steps: Verify that there are no duplicate MAC Addresses and/or Device-IDs on the network. Check that no more than two network bias resistors are installed. Confirm that all terminations exist and/or remove any invalid terminations, particularily in the middle of the bus. Verify that polarity is correct (a single node can disrupt the MS/TP network.) Check that there are no more than 32 devices installed in a single segment (using standard transceivers.) Verify correct topology (e.g. a star topology rather than a straight bus topology) may impact physical medium (Layer 1). You should carefully follow the EIA-485 specifications (see If the BACnet Communication Module still does not respond, contact the Daikin Applied Controls Customer Support Group at 866-4MCQUAY ( ). Parts List Description BACnet Communication Module kit (kit includes communication module with attached network connector, screws, and Installation Manual) Part Number IM 963-1
19 This document contains the most current product information as of this printing. For the most current product information, please go to All Daikin equipment is sold pursuant to Daikin Applied's Standard Terms and Conditions of Sale and Limited Warranty. (800)
MicroTech III Rooftop and Self Contained Unit Controller BACnet Communication Module (MS/TP)
Installation and Maintenance Manual IM 917-1 Group: Controls Part Number: IM 917 Date: October 2009 Supercedes: IM 917 MicroTech III Rooftop and Self Contained Unit Controller BACnet Communication Module
More informationMicroTech II McQuay Maverick II Rooftop Unit Controller BACnet Communication Module (MS/TP)
Installation and Maintenance Manual IM 852 Group: Controls Part Number: IM 852 Date: June 2007 Supercedes: New MicroTech II McQuay Maverick II Rooftop Unit Controller BACnet Communication Module (MS/TP)
More informationMicroTech II Chiller Unit Controller BACnet Communication Module (MS/TP)
Installation and Maintenance Manual IM 736-3 Group: Controls Part Number: IM 736 Date: June 2006 Supercedes: IM 736-2 MicroTech II Chiller Unit Controller BACnet Communication Module (MS/TP) WSC WDC WPV
More informationPortable BACnet /IP to MS/TP Router
Portable BACnet /IP to MS/TP Router Installation Instructions TL-BRTRP-0 Part No. 24-10414-2, Rev. F Issued April 2016 Refer to the QuickLIT website for the most up-to-date version of this document. Applications
More informationSHEET. BASautomation. BAS Router BACnet Multi-Network Router. BAS Router
BAS Router d a t a SHEET BAS Router BACnet Multi-Network Router The BAS Router provides stand-alone routing between BACnet networks such as BACnet/IP, BACnet Ethernet, and BACnet MS/TP thereby allowing
More informationServiceTools for MicroTech II Version 2.0 Applied Terminal Systems User Manual
User Manual UM 732-2 Group: Controls Part Number: UM 732-2 Date: May 2004 Supersedes: UM 732-1 ServiceTools for MicroTech II Version 2.0 Applied Terminal Systems User Manual 2004 McQuay International Contents
More informationE-Mon Communication Gateway Utility Instructions for BACnet/mstp
E-Mon Communication Gateway Utility Instructions for BACnet/mstp The E-Mon Communication Gateway utility will allow you to configure the Device Instance (Node ID) and other parameters needed for your BACnet/mstp
More informationPlanning BACnet networks
Digital Designer s Guide Application Note AN0404A Revision B About this application note Related reference materials Required software This application note describes the principles behind planning a BACnet
More informationBACnet Automation Interface Module (Network Version)
Sense +V Tx Rx LAN LINK Over ARCNET KBaud BACnet Rx BACnet Tx Archive Valid Port S Tx Port S Rx Low Battery Network- Enhanced Access Default MSTP PTP = Download Required on Rnet and Port S IP Address IP
More informationManagement Software. Web Browser User s Guide AT-S106. For the AT-GS950/48 Gigabit Ethernet Smart Switch. Version 1.0.0. 613-001339 Rev.
Management Software AT-S106 Web Browser User s Guide For the AT-GS950/48 Gigabit Ethernet Smart Switch Version 1.0.0 613-001339 Rev. A Copyright 2010 Allied Telesis, Inc. All rights reserved. No part of
More informationEthernet Radio Configuration Guide
Ethernet Radio Configuration Guide for Gateway, Endpoint, and Repeater Radio Units April 20, 2015 Customer Service 1-866-294-5847 Baseline Inc. www.baselinesystems.com Phone 208-323-1634 FAX 208-323-1834
More information1 Serial RS232 to Ethernet Adapter Installation Guide
Installation Guide 10/100 Mbps LED (amber color ) Link/Activity LED (green color ) 1. Introduction Thank you for purchasing this 1-port RS232 to Ethernet Adapter (hereinafter referred to as Adapter ).
More informationCNC File Transfer Box. Connecting the CNC File Transfer. CNC Transfer Program
CNC File Transfer Box The CNC File Transfer connects a serial CNC device to the network so files can be easily transferred from a computer to the CNC equipment. Any computer on the network can transfer
More informationUser Manual Revision 1.400 English Converter / Adapter Ethernet to RS232 / RS485 (Order Code: HD67038-2 HD67038-2-M HD67038-25 HD67038-25-M)
Document code: MN67038-2_ENG Revision 1.400 Page 1 of 25 User Manual Revision 1.400 English Converter / Adapter Ethernet to RS232 / RS485 (Order Code: HD67038-2 HD67038-2-M HD67038-25 HD67038-25-M) for
More informationWireless Router Setup Manual
Wireless Router Setup Manual NETGEAR, Inc. 4500 Great America Parkway Santa Clara, CA 95054 USA 208-10082-02 2006-04 2006 by NETGEAR, Inc. All rights reserved. Trademarks NETGEAR is a trademark of Netgear,
More informationDisclaimers. Important Notice
Disclaimers Disclaimers Important Notice Copyright SolarEdge Inc. All rights reserved. No part of this document may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means,
More information3.1 RS-232/422/485 Pinout:PORT1-4(RJ-45) RJ-45 RS-232 RS-422 RS-485 PIN1 TXD PIN2 RXD PIN3 GND PIN4 PIN5 T+ 485+ PIN6 T- 485- PIN7 R+ PIN8 R-
MODEL ATC-2004 TCP/IP TO RS-232/422/485 CONVERTER User s Manual 1.1 Introduction The ATC-2004 is a 4 Port RS232/RS485 to TCP/IP converter integrated with a robust system and network management features
More informationGUIDE. CTRLink. EIPR Skorpion Wired and Wireless IP Routers. EIPR Series
a p p l i c a t i o n GUIDE EIPR Series EIPR Skorpion Wired and Wireless IP Routers The EIPR links two Internet Protocol (IPv4) networks together passing appropriate traffic while blocking all other traffic.
More informationUser Manual. PePWave Surf / Surf AP Indoor Series: Surf 200, E200, AP 200, AP 400. PePWave Mesh Connector Indoor Series: MC 200, E200, 400
User Manual PePWave Surf / Surf AP Indoor Series: Surf 200, E200, AP 200, AP 400 PePWave Mesh Connector Indoor Series: MC 200, E200, 400 PePWave Surf AP Series: Surf AP 200-X, E200-X, 400-X PePWave Surf
More information3.5 EXTERNAL NETWORK HDD. User s Manual
3.5 EXTERNAL NETWORK HDD User s Manual Table of Content Before You Use Key Features H/W Installation Illustration of Product LED Definition NETWORK HDD Assembly Setup the Network HDD Home Disk Utility
More informationBIT COMMANDER. Serial RS232 / RS485 to Ethernet Converter
BIT COMMANDER Serial RS232 / RS485 to Ethernet Converter (Part US2000A) Copyrights U.S. Converters 1 Contents Overview and Features... 3 Functions..5 TCP Server Mode... 5 Httpd Client Mode.5 TCP Auto mode....6
More informationInstallation Instructions For Controllers with MS/TP Automatic MAC Addressing. Patent Pending 000-019-01
Installation Instructions For Controllers with MS/TP Automatic MAC Addressing Patent Pending 000-019-01 KMC Controls Important notices Disclaimer 2009, KMC Controls, Inc. TotalControl, BACstage and FullBAC
More informationP-2024. Quick Start Guide. VoIP Analog Telephone Adaptor DEFAULT LOGIN. IP Address http://192.168.5.1 Password 1234. Version 3.60 7/2007 Edition 1
P-2024 VoIP Analog Telephone Adaptor Quick Start Guide Version 3.60 7/2007 Edition 1 DEFAULT LOGIN IP Address http://192.168.5.1 Password 1234 Copyright 2007. All rights reserved. Overview Use your P-2024
More informationENET-710. ENET-710 - Ethernet Module ENET-710 JAN / 06 FOUNDATION
ENET-710 ENET-710 - Ethernet Module JAN / 06 ENET-710 FOUNDATION E N E T 7 1 0 ME smar www.smar.com Specifications and information are subject to change without notice. Up-to-date address information is
More informationBACnet. A Data Communication Protocol for Building Automation and Control Networks. for Acuvim II Series Power Meter
BACnet A Data Communication Protocol for Building Automation and Control Networks 1 BACnet Overview for Acuvim II Series Power Meter The Building Automation and Control Network (BACnet), described in the
More informationPhone Adapter. with 2 Ports for Voice-over-IP. Installation and Troubleshooting Guide. Model No. PAP2 Ver. 2. Voice
Phone Adapter with 2 Ports for Voice-over-IP Voice Installation and Troubleshooting Guide Model No. PAP2 Ver. 2 Copyright and Trademarks Specifications are subject to change without notice. Linksys is
More informationT3 Mux M13 Multiplexer
T3 Mux M13 Multiplexer User Manual [Type the abstract of the document here. The abstract is typically a short summary of the contents of the document. Type the abstract of the document here. The abstract
More informationGV-Data Capture V3 Series User's Manual
GV-Data Capture V3 Series User's Manual Before attempting to connect or operate this product, please read these instructions carefully and save this manual for future use. 2006 GeoVision, Inc. All rights
More informationMedical Vacuum Systems-PXMI
Medical Vacuum Systems-PXMI Please read and save these instructions. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing
More informationUPS Network Interface. Quick InstallationGuide
UPS Network Interface Quick InstallationGuide Version 1.1 March 1999 COPYRIGHT Copyright 1999 RINGDALE UK Limited. All rights reserved. No part of this publication may be reproduced, transmitted, transcribed,
More informationCrow Limited Warranty. Print Version 017
Crow Limited Warranty (Crow) warrants this product to be free from defects in materials and workmanship under normal use and service for a period of one year from the last day of the week and year whose
More informationUser s Manual TCP/IP TO RS-232/422/485 CONVERTER. 1.1 Introduction. 1.2 Main features. Dynamic DNS
MODEL ATC-2000 TCP/IP TO RS-232/422/485 CONVERTER User s Manual 1.1 Introduction The ATC-2000 is a RS232/RS485 to TCP/IP converter integrated with a robust system and network management features designed
More informationLifeSize Networker Installation Guide
LifeSize Networker Installation Guide November 2008 Copyright Notice 2006-2008 LifeSize Communications Inc, and its licensors. All rights reserved. LifeSize Communications has made every effort to ensure
More informationEthernet Adapter Owner's Manual
Corinex Intelligent PowerNet Corinex Intelligent PowerNet Ethernet Adapter Owner's Manual This Owner s Manual, as well as the software described in it, is furnished under license and may be used or copied
More informationProSafe Plus Switch Utility
ProSafe Plus Switch Utility User Guide 350 East Plumeria Drive San Jose, CA 95134 USA September 2010 202-10524-03 v1.0 ProSafe Plus Switch Utility User Guide 2010 NETGEAR, Inc. All rights reserved. No
More informationOPTICAL HEADEND PLATFORM OTOHP-NMS NETWORK MONITORING MODULE INSTRUCTION MANUAL
OPTICAL HEADEND PLATFORM OTOHP-NMS NETWORK MONITORING MODULE INSTRUCTION MANUAL Phone: (209) 586-1022 (800) 545-1022 Fax: (209) 586-1026 OTOHP-NMS Rev. X1 E-Mail: salessupport@olsontech.com www.olsontech.com
More informationAC 800M. EtherNet/IP DeviceNet Linking Device LD 800DN. Power and productivity for a better world TM SP1134
AC 800M EtherNet/IP DeviceNet Linking Device LD 800DN SP1134 Power and productivity for a better world TM AC 800M EtherNet/IP DeviceNet Linking Device LD 800DN NOTICE This document contains information
More informationDesigo V6.0 BACnet Router PXG3.M and PXG3.L Engineering and configuration Engineering
Desigo V6.0 BACnet Router PXG3.M and PXG3.L Engineering and configuration Engineering PDF help 2016-03-24 Building Technologies Edition notice Edition notice Technical specifications and availability subject
More informationRouteFinder SOHO. Quick Start Guide. SOHO Security Appliance. EDGE Models RF825-E, RF825-E-AP CDMA Models RF825-C-Nx, RF825-C-Nx-AP
RouteFinder SOHO SOHO Security Appliance EDGE Models RF825-E, RF825-E-AP CDMA Models RF825-C-Nx, RF825-C-Nx-AP Quick Start Guide RouteFinder RF825 Series Quick Start Guide RouteFinder SOHO Security Appliance
More informationScreenLogic Wireless Connection Kit. Installation Guide. pool/spa control system
pool/spa control system ScreenLogic Wireless Connection Kit Installation Guide P/N 520663 - Rev B 8 Technical Support Contact Technical Support at: Sanford, North Carolina (8 A.M. to 5 P.M.) Phone: (800)
More informationLevelOne IFE-0500 4-Port PoE + 1-Port TP Industrial Fast Ethernet Switch User Manual
LevelOne IFE-0500 4-Port PoE + 1-Port TP Industrial Fast Ethernet Switch User Manual Ver. 1.0.0-0711 1 FCC Warning This Equipment has been tested and found to comply with the limits for a Class-A digital
More informationLegal Disclaimers. For C-UL Listed applications, the unit shall be installed in accordance with Part 1 of the Canadian Electrical Code.
ACS5000 Networking Admin Interface Guide 1/21/2015 Legal Disclaimers Federal Communications Commission (FCC) Compliancy This equipment has been tested and found to comply with the limits for a Class B
More informationSetup Manual and Programming Reference. RGA Ethernet Adapter. Stanford Research Systems. Revision 1.05 (11/2010)
Setup Manual and Programming Reference Stanford Research Systems Revision 1.05 (11/2010) Certification Stanford Research Systems certifies that this product met its published specifications at the time
More informationAura SSD. for the 2013 Apple Mac Pro INSTALLATION GUIDE
Aura SSD for the 2013 Apple Mac Pro INSTALLATION GUIDE TABLE OF CONTENTS 1. INTRODUCTION...1 1.1 SYSTEM REQUIREMENTS 1.2 PACKAGE CONTENTS 1.3 ABOUT THIS MANUAL 2. INSTALLATION...2 2.1 PREPARING THE MAC
More informationMAKING MODERN LIVING POSSIBLE. AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS
MAKING MODERN LIVING POSSIBLE AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS How to Use This Guide Read this Guide completely as you install and start up your new AK-SC 255 controller.
More informationEPSON Network Image Express Card User s Guide
Network Scan Server English EPSON Network Image Express Card User s Guide All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form or
More informationTL-PS310U Single USB 2.0 Port MFP and Storage Server
TL-PS310U Single USB 2.0 Port MFP and Storage Server Rev: 2.0.0 1910010313 Contents Chapter 1 Introduction... 1 1.1 Product Overview...1 1.2 Network Management...1 1.3 Components and Features...1 1.4 Hardware
More information1. MOXA NPort Express TCP/IP to RS-232 server
GS_GSR_GCR_UserManual_App_E_MOXA_V01.doc / 17.08.2009 GeoSIG Ltd. Appendix E Page E-1 1. MOXA NPort Express TCP/IP to RS-232 server 1.1. General Explanations The NPort Express RS-232/422/485 Device server
More informationAXIS 205 Network Camera Goes anywhere your network goes
I N S T A L L A T I O N G U I D E Goes anywhere your network goes Introduction 1 Introduction Focus guide (see page 6) Status indicator (surrounding the focus ring) Focus ring (see page 6) Serial number
More informationSIP Proxy Server. Administrator Installation and Configuration Guide. V2.31b. 09SIPXM.SY2.31b.EN3
SIP Proxy Server Administrator Installation and Configuration Guide V2.31b 09SIPXM.SY2.31b.EN3 DSG, DSG logo, InterPBX, InterServer, Blaze Series, VG5000, VG7000, IP590, IP580, IP500, IP510, InterConsole,
More informationUSER GUIDE. Ethernet Configuration Guide (Lantronix) P/N: 2900-300321 Rev 6
KRAMER ELECTRONICS LTD. USER GUIDE Ethernet Configuration Guide (Lantronix) P/N: 2900-300321 Rev 6 Contents 1 Connecting to the Kramer Device via the Ethernet Port 1 1.1 Connecting the Ethernet Port Directly
More informationNetwork Management Card
Network Management Card AP9617 AP9618 AP9619 Installation and Quick-Start Manual How to Avoid Equipment Damage Disconnect UPS power You do not need to turn off a Symmetra or a Silcon model UPS to install
More informationMCR1900 Media Converter 19-Slot Chassis
MCR1900 Media Converter 19-Slot Chassis Installation Guide Part #5500304-11 Copyright Statement This document must not be reproduced in any way whatsoever, either printed or electronically, without the
More informationPePWave Surf Series PePWave Surf Indoor Series: Surf 200, AP 200, AP 400
PePWave Surf Series PePWave Surf Indoor Series: Surf 200, AP 200, AP 400 PePWave Surf Outdoor Series: Surf AP 200/400-X, PolePoint 400-X, Surf 400-DX User Manual Document Rev. 1.2 July 07 COPYRIGHT & TRADEMARKS
More informationChapter 6 Using Network Monitoring Tools
Chapter 6 Using Network Monitoring Tools This chapter describes how to use the maintenance features of your RangeMax Wireless-N Gigabit Router WNR3500. You can access these features by selecting the items
More informationChapter 6 Using Network Monitoring Tools
Chapter 6 Using Network Monitoring Tools This chapter describes how to use the maintenance features of your Wireless-G Router Model WGR614v9. You can access these features by selecting the items under
More informationBox Camera Series Hardware Manual
Encoder Firmware V4.06.09 User s Manual Box Camera Series Hardware Manual D21 (D21F / D21V) D22 (D22F / D22V) E21 (E21F / E21V) E22 (E22F / E22V) E23, E24, E25 2013/08/27 Table of Contents Precautions...
More informationQuick Start Guide. Cisco Small Business. 200E Series Advanced Smart Switches
Quick Start Guide Cisco Small Business 200E Series Advanced Smart Switches Welcome Thank you for choosing the Cisco 200E series Advanced Smart Switch, a Cisco Small Business network communications device.
More informationHow To Check If Your Router Is Working Properly
Chapter 6 Using Network Monitoring Tools This chapter describes how to use the maintenance features of your RangeMax Dual Band Wireless-N Router WNDR3300. You can access these features by selecting the
More informationFirst Steps. Remote Access Gateway IGW/922. with DIL/NetPC ADNP/9200
Remote Access Gateway IGW/922 with DIL/NetPC ADNP/9200 First Steps SSV Embedded Systems Dünenweg 5 D-30419 Hannover Phone: +49 (0)511/40 000-0 Fax: +49 (0)511/40 000-40 E-mail: sales@ssv-embedded.de Document
More informationxpico Wi-Fi Embedded Device Server Evaluation Kit Quick Start Guide
xpico Wi-Fi Embedded Device Server Evaluation Kit Quick Start Guide Part Number 900-685 Revision A June 2013 Copyright and Trademark Contacts 2013 Lantronix, Inc.. All rights reserved. No part of the contents
More informationSDN INSTRUCTIONS 07/10, Ver 1.2. Somfy Digital Network (SDN) Installation and Programming
Somfy Digital Network (SDN) Installation and Programming SSoomffyy SSyysst teemss IInncc.. 1 Table of Contents 1 General Information and Features... 3 1.1 ILT2 Motor... 3 1.2 SDN Switches... 4 1.3 ILT2
More informationEMBEDDED ACCESS CONTROL Hardware Installation Guide
EMBEDDED ACCESS CONTROL Hardware Installation Guide Lenel goentry Hardware Installation Guide, product version 1.00. This guide is item number DOC- ENHW-ENU, revision 1.003, April 2009 Copyright 2009 Lenel
More informationDebugging Network Communications. 1 Check the Network Cabling
Debugging Network Communications Situation: you have a computer and your NetBurner device on a network, but you cannot communicate between the two. This application note provides a set of debugging steps
More informationPerle Protocol Transparent Media Converter Modules
Perle Protocol Transparent Media Converter Modules Installation Guide C-4GPT-DSFP CM-4GPT-DSFP Part# 5500335-10 Overview This document contains instructions necessary for the installation and operation
More informationSecure Ethernet Gateway SEG-1 and SEG-M for IEI Access Systems Installation Manual
Secure Ethernet Gateway SEG-1 and SEG-M for IEI Access Systems Installation Manual Section 1: Introduction SECURITY WARNING: New SEG's shipped after April 2008 will have Telnet setup option enabled by
More information2 Setting Up the Hardware for a Wired Ethernet Network... 13. 3 Setting Up the Software for an Ethernet Network... 21
Contents 1 Networking Basics............................................... 1 Selecting a network connection........................................ 2 Wired Ethernet network...........................................
More informationVantage RADIUS 50. Quick Start Guide Version 1.0 3/2005
Vantage RADIUS 50 Quick Start Guide Version 1.0 3/2005 1 Introducing Vantage RADIUS 50 The Vantage RADIUS (Remote Authentication Dial-In User Service) 50 (referred to in this guide as Vantage RADIUS)
More informationQUICK START GUIDE CX-MC200LE-VZ
QUICK START GUIDE CX-MC200LE-VZ LTE/EV-DO Business-Grade Modem For use with Juniper Networks CX111 3G/4G Bridge with Enhanced Performance and Reliability GETTING READY TO USE YOUR CX-MC200LE-VZ MODEM Thank
More informationSoftware User Guide UG-461
Software User Guide UG-461 One Technology Way P.O. Box 9106 Norwood, MA 02062-9106, U.S.A. Tel: 781.329.4700 Fax: 781.461.3113 www.analog.com ezlinx icoupler Isolated Interface Development Environment
More informationOperating instructions. AS-i Profibus gateway AC1411 / AC1412 7390884/00 04/2014
Operating instructions AS-i Profibus gateway AC1411 / AC1412 7390884/00 04/2014 Contents 1 Preliminary note 4 1.1 Notes on this document 4 1.2 Symbols used 4 2 Safety instructions 4 2.1 General 4 2.2 Installation
More informationUSING YOUR DMX PROFUSION
Set Up Guide USING YOUR DMX PROFUSION io FOR 1 Connect 2 Set Up 3 Listen SIMPLE PERSONALIZED UNLIMITED ECONOMICAL LICENSED Welcome Thank you for choosing DMX to provide your Pandora listening experience
More informationSCREENLOGIC INTERFACE WIRELESS CONNECTION KIT
SCREENLOGIC INTERFACE WIRELESS CONNECTION KIT FOR INTELLITOUCH AND EASYTOUCH CONTROL SYSTEMS INSTALLATION GUIDE IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS Technical
More informationPLANET is a registered trademark of PLANET Technology Corp. All other trademarks belong to their respective owners.
Trademarks Copyright PLANET Technology Corp. 2004 Contents subject to revise without prior notice. PLANET is a registered trademark of PLANET Technology Corp. All other trademarks belong to their respective
More informationApplication & Quick-Start Guide
Model: CRMWIC Web Intelligent Controller 1 This document will illustrate various ways to connect and use a CRM-WIC as well as programming examples. When connecting CRM-WIC, the installer has several interface
More informationTo perform Ethernet setup and communication verification, first perform RS232 setup and communication verification:
PURPOSE Verify that communication is established for the following products programming option (488.2 compliant, SCPI only): DCS - M9C & DCS M130, DLM M9E & DLM-M9G & DLM M130, DHP - M9D, P series, SG,
More informationINTRODUCTION FEATURES OF THE ICM
INTRODUCTION The ICM, Internet Control Module, is a remote controller device accessible via the Internet that allows operational access to the IPS (and other base units available). Through the ICM you
More informationUniStream CPU-for-Panel
UniStream CPU-for-Panel Installation Guide USC-P-B10 Unitronics UniStream platform comprises control devices that provide robust, flexible solutions for industrial automation. This guide provides basic
More informationUser Manual IC-485AI 2002-09-27
User Manual IC-485AI Note: This equipment has been tested and found to comply ith the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable
More informationCS 326e F2002 Lab 1. Basic Network Setup & Ethereal Time: 2 hrs
CS 326e F2002 Lab 1. Basic Network Setup & Ethereal Time: 2 hrs Tasks: 1 (10 min) Verify that TCP/IP is installed on each of the computers 2 (10 min) Connect the computers together via a switch 3 (10 min)
More informationCABLE MODEM QUICK START
CABLE MODEM QUICK START This Quick Start describes how to connect your Zoom cable modem to a cable modem service. This lets your cable modem provide Internet access to a computer or other device connected
More informationLabelWriter. Print Server. User Guide
LabelWriter Print Server User Guide Copyright 2010 Sanford, L.P. All rights reserved. 08/10 No part of this document or the software may be reproduced or transmitted in any form or by any means or translated
More informationPrestige 660R-6x Read Me First
Prestige 660R-6x Read Me First Prestige Rear Panel Connections DSL PORT CONNECTION Connect the DSL port on the Prestige to the wall jack using the included DSL cable (telephone wire). Connect the micro
More informationWLAN600 Wireless IP Phone Administrator s Guide
WLAN600 Wireless IP Phone Administrator s Guide Trademark Acknowledgement All brand names are trademarks or registered trademarks of their respective companies. Disclaimer This document is supplied by
More informationBroadband Router ESG-103. User s Guide
Broadband Router ESG-103 User s Guide FCC Warning This equipment has been tested and found to comply with the limits for Class A & Class B digital device, pursuant to Part 15 of the FCC rules. These limits
More informationProCurve Networking. Troubleshooting WLAN Connectivity. Technical White paper
ProCurve Networking Troubleshooting WLAN Connectivity Technical White paper Introduction... 3 Identifying the Problem... 3 Troubleshooting Wireless Station Connection to AP... 4 Can Any Wireless Stations
More informationQuick Start Guide. Cisco Small Business. 300 Series Managed Switches
Quick Start Guide Cisco Small Business 300 Series Managed Switches Welcome Thank you for choosing the Cisco 300 Series Managed Switch, a Cisco Small Business network communications device. This device
More informationCongratulations on your HomePortal purchase. To install your HomePortal and configure your home network, follow these steps.
Notice to Users 2003 2Wire, Inc. All rights reserved. This manual in whole or in part, may not be reproduced, translated, or reduced to any machine-readable form without prior written approval. 2WIRE PROVIDES
More informationQuick Start Guide. WAP371 Wireless AC/N Dual Radio Access Point with Single Point Setup Quick Start Guide. Cisco Small Business
Quick Start Guide Cisco Small Business WAP371 Wireless AC/N Dual Radio Access Point with Single Point Setup Quick Start Guide Versión en Español para México en el CD Version en français sur CD Versione
More informationBusiness Audio System: Music & Messaging MP3 Player. by Grace Digital Audio. User Guide. Model No. GDI-USBM10
Business Audio System: Music & Messaging MP3 Player by Grace Digital Audio User Guide Model No. GDI-USBM10 User Guide Contents Introduction 2 Safety & General Use Information 2 Features 3 Set Up & Operation
More informationTable of Contents. Creating a VC1000 Network... 3
2 Table of Contents Creating a VC1000 Network... 3 Topology... 3 Unit ddressing... 4 Terminating Resistors... 5 Shielding... 5 Interconnecting the common... 6 ias Resistors... 6 VC1000 Hardware Configuration...
More informationTCP/IP MODULE CA-ETHR-A INSTALLATION MANUAL
TCP/IP MODULE CA-ETHR-A INSTALLATION MANUAL w w w. c d v g r o u p. c o m CA-ETHR-A: TCP/IP Module Installation Manual Page Table of Contents Introduction...5 Hardware Components... 6 Technical Specifications...
More informationOPERATION MANUAL. MV-410RGB Layout Editor. Version 2.1- higher
OPERATION MANUAL MV-410RGB Layout Editor Version 2.1- higher Table of Contents 1. Setup... 1 1-1. Overview... 1 1-2. System Requirements... 1 1-3. Operation Flow... 1 1-4. Installing MV-410RGB Layout
More informationDisclaimers. Important Notice
Disclaimers Disclaimers Important Notice Copyright SolarEdge Inc. All rights reserved. No part of this document may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means,
More informationBiPAC 7404V series. VoIP/(802.11g) ADSL2+ (VPN) Firewall Router. Quick Start Guide
BiPAC 7404V series VoIP/(802.11g) ADSL2+ (VPN) Firewall Router Quick Start Guide VoIP/(802.11g) ADSL2+ (VPN) Firewall Router For more detailed instructions on configuring and using the Billion VoIP/(802.11g)
More information47611-GB4. Quick-Start Guide 10/100/1000 Mbps 4-Port Gigabit Router IMPORTANT INSTRUCTIONS SAFETY INFORMATION PRE-INSTALLATION CHECKLIST
IMPORTANT INSTRUCTIONS 1. Read and understand all instructions. Follow all warnings and instructions marked on the product. 2. Do not use this product near water e.g., near a tub, wash basin, kitchen sink
More informationHLWLAN 802.11b/g/n Transceiver Kit
092524 RevB HLWLAN 802.11b/g/n Transceiver Kit Wireless Communications for OmniLogic Owner s Manual Contents Introduction...1 Installation...2 Configuration...6 Operation...8 Troubleshooting...9 HLWLAN
More informationChapter 3 Management. Remote Management
Chapter 3 Management This chapter describes how to use the management features of your ProSafe 802.11a/g Dual Band Wireless Access Point WAG102. To access these features, connect to the WAG102 as described
More informationOctal T1-10/100 RIOP Installation Guide
Octal T1-10/100 RIOP Installation Guide Compatible Systems Corporation 4730 Walnut Street Suite 102 Boulder, Colorado 80301 303-444-9532 800-356-0283 http://www.compatible.com Octal T1-10/100 RIOP Installation
More informationDocument Revision History: Network Guide 05DI-UGBACNG-12 Copyright Distech Controls Inc. First printing June 2010. Printed in Canada.
Network Guide Document Revision History: 1. Version 0.1 - Beta Release - March 2010 2. Version 1.0 Release to Market June 2010 3. Version 1.1 October 2010 4. Version 1.2 Added LONWORKS Network information
More information