U.S. EXPERIENCE WITH SPRINKLERS AND OTHER AUTOMATIC FIRE EXTINGUISHING EQUIPMENT

Size: px
Start display at page:

Download "U.S. EXPERIENCE WITH SPRINKLERS AND OTHER AUTOMATIC FIRE EXTINGUISHING EQUIPMENT"

Transcription

1 U.S. EXPERIENCE WITH SPRINKLERS AND OTHER AUTOMATIC FIRE EXTINGUISHING EQUIPMENT John R. Hall, Jr. February 2010 National Fire Protection Association Fire Analysis and Research Division

2 U.S. EXPERIENCE WITH SPRINKLERS AND OTHER AUTOMATIC FIRE EXTINGUISHING EQUIPMENT John R. Hall, Jr. February 2010 National Fire Protection Association Fire Analysis and Research Division

3 Abstract Automatic sprinklers are highly effective elements of total system designs for fire protection in buildings. They save lives and property, producing large reductions in the number of deaths per thousand fires, in average direct property damage per fire, and especially in the likelihood of a fire with large loss of life or large property loss. When sprinklers are present in the fire area, they operate in 93% of all reported structure fires large enough to activate sprinklers, excluding buildings under construction. When they operate, they are effective 97% of the time, resulting in a combined performance of operating effectively in 91% of reported fires where sprinklers were present in the fire area and fire was large enough to activate sprinklers. In homes (including apartments), wet-pipe sprinklers operated effectively 96% of the time. When wet-pipe sprinklers are present in structures that are not under construction and excluding cases of failure or ineffectiveness because of a lack of sprinklers in the fire area, the fire death rate per 1,000 reported structure fires is lower by 83% for home fires, where most structure fire deaths occur, and the rate of property damage per reported structure fire is lower by 40-70% for most property uses. In homes (including apartments), wet-pipe sprinklers were associated with a 74% lower average loss per fire. Also, when sprinklers are present in structures that are not under construction and excluding cases of failure or ineffectiveness because of a lack of sprinklers in the fire area, 95% of reported structure fires have flame damage confined to the room of origin compared to 74% when no automatic extinguishing equipment is present. When sprinklers fail to operate, the reason most often given (53% of failures) is shutoff of the system before fire began. (All statistics are based on fires reported to U.S. fire departments, excluding buildings under construction.) Keywords: fire sprinklers; fire statistics; automatic extinguishing systems; automatic suppression systems Acknowledgements The National Fire Protection Association thanks all the fire departments and state fire authorities who participate in the National Fire Incident Reporting System (NFIRS) and the annual NFPA fire experience survey. These firefighters are the original sources of the detailed data that make this analysis possible. Their contributions allow us to estimate the size of the fire problem. We are also grateful to the U.S. Fire Administration for its work in developing, coordinating and maintaining NFIRS. For more information about the National Fire Protection Association, visit or call To learn more about the One-Stop Data Shop go to or call Copies of this report are available from: National Fire Protection Association One-Stop Data Shop 1 Batterymarch Park Quincy, MA osds@nfpa.org phone: NFPA No. USS14 Copyright 2010, National Fire Protection Association, Quincy, MA

4 Executive Summary Automatic sprinklers are highly effective and reliable elements of total system designs for fire protection in buildings. In , sprinklers operated in 93% of all reported structure fires large enough to activate sprinklers, excluding buildings under construction and buildings without sprinklers in the fire area. When sprinklers operate, they are effective 97% of the time, resulting in a combined performance of operating effectively in 91% of all reported fires where sprinklers were present in the fire area and fire was large enough to activate them. The combined performance for the more widely used wet pipe sprinklers is 92%, while for dry pipe sprinklers, the combined performance is only 79%. In homes (including apartments), wet-pipe sprinklers operated effectively 96% of the time. By comparison, combined performance is 60% for dry chemical systems, 79% for carbon dioxide systems, 81% for foam systems, and 88% for halogen systems. (Wet chemical systems may be included with dry chemical systems or with other special hazard systems.) These most current statistics are based on fires reported to U.S. fire departments, excluding buildings under construction and cases of failure or ineffectiveness because of a lack of sprinklers in the fire area and after some recoding between failure and ineffectiveness based on reasons given. When wet-pipe sprinklers are present in structures that are not under construction and excluding cases of failure or ineffectiveness because of a lack of sprinklers in the fire area, the fire death rate per 1,000 reported home structure fires is lower by 83% and the rate of property damage per reported structure fire is lower by 40-70% for most property uses. In homes (including apartments), wet-pipe sprinklers were associated with a 74% lower average loss per fire. Also, when sprinklers are present in structures that are not under construction and excluding cases of failure or ineffectiveness because of a lack of sprinklers in the fire area, 95% of reported structure fires have flame damage confined to the room of origin compared to 74% when no automatic extinguishing equipment is present. Of reported structure fires in health care properties, an estimated 57% showed sprinklers present, with higher percentages for hospitals (71%) and nursing homes (65%) and a much lower percentage for clinics and doctor s offices (28%). Sprinklers were also reported as present in half or more of all reported fires in laboratories (60%), manufacturing facilities (52%), theaters (50%), and prisons and jails (50%). In every other property use, more than half of all reported fires had no sprinklers. The few surveys that have been done of sprinkler presence in general, not limited to fires, have found that in any property group, the percentage of buildings with sprinklers is much higher than the percentage of reported fires with sprinklers present. Sprinklers apparently are still rare in many of the places where people are most exposed to fire, including educational properties, offices, most stores, and especially homes, where most fire deaths occur. There is considerable potential for expanded use of sprinklers to reduce the loss of life and property to fire. When sprinklers fail to operate, the reason most often given (53% of failures) was shutoff of the system before fire began, as may occur in the course of routine inspection maintenance. Other leading reasons were inappropriate system for the type of fire (20%), lack of maintenance (15%), and manual intervention that defeated the system (9%). Only 2% of sprinkler failures were attributed to component damage. U.S. Experience With Sprinklers, 2/10 i NFPA Fire Analysis and Research, Quincy, MA

5 When sprinklers operate but are ineffective, the reason usually had to do with an insufficiency of water applied to the fire, either because water did not reach the fire (43% of cases of ineffective performance) or because not enough water was released (31%). Other leading reasons were inappropriate system for the type of fire (12%), manual intervention that defeated the system (5%), and lack of maintenance (4%). Only 4% of cases of sprinkler ineffectiveness were attributed to component damage. When people are fatally injured in spite of the operation of wet-pipe sprinklers, the victims often had special vulnerabilities that are less often found with fatal victims of home fires in general. For example, 93% of fatal victims in home fires with wet-pipe sprinkler operation were located in the area of fire origin, where they could have suffered fatal injuries before sprinkler activation, compared to 53% of fatal home fire victims in general; 30% of fatal victims in home fires with wet-pipe sprinkler operation had their clothing on fire, compared to 7% of fatal home fire victims in general; 50% of fatal victims in home fires with wet-pipe sprinkler operation were age 65 or older, compared to 28% of fatal home fire victims in general; and 37% of fatal victims in home fires with wet-pipe sprinkler operation returned to the fire after escaping, compared to 19% of fatal home fire victims in general. U.S. Experience With Sprinklers, 2/10 ii NFPA Fire Analysis and Research, Quincy, MA

6 Table of Contents Executive Summary i Table of Contents iii List of Tables v Fact Sheet vii Before You Read the Report: Some Introductory Notes on Incident 1 Coding and Analysis Presence of Sprinklers and Other Automatic Extinguishing Equipment 3 Automatic Extinguishing Equipment Type 7 Automatic Extinguishing Equipment Reliability and Effectiveness 11 Automatic Extinguishing Equipment Impact 39 Other Issues 47 Concluding Points 53 Appendix A: How National Estimates Statistics Are Calculated 55 Appendix B: Sprinkler-Related Data Elements in NFIRS Appendix C: Multiple-Death Fires in Fully Sprinklered Properties 65 Appendix D: Selected Incidents 67 U.S. Experience With Sprinklers, 2/10 iii NFPA Fire Analysis and Research, Quincy, MA

7 U.S. Experience With Sprinklers, 2/10 iv NFPA Fire Analysis and Research, Quincy, MA

8 List of Tables Table 1. Presence of Sprinklers and Other Automatic Extinquishing Equipment 5 in Structure Fires Table 2. Table A. Table B. Type of Automatic Extinguishing Equipment Reported as Percentage of All Structure Fires Where Equipment Was Present and of Known Type, by Property Use 9 Non-Confined Fires With Areas of Origin That Could be Room Larger Than the Sprinkler Design Area for the Space 14 Combined Sprinkler Performance vs. Sprinkler Success in Confining Fire to Room of Origin 16 Table C. Reasons for Failure or Ineffectiveness as Percentages of All Cases of Failure 17 or Ineffectiveness, for All Structures and All Sprinklers Table D. Leading Areas of Origin for Fires in One- or Two- Family Dwellings 20 Table 3. Table 4. Automatic Extinguishing Equipment Reliability and Effectiveness, by Property Use 22 Reasons for Failure to Operate When Fire Was Large Enough to Activate Equipment and Equipment Was Present in Area of Fire 28 Table 5. Reasons for Ineffectiveness When Fire Was Large Enough to Activate 31 Equipment and Equipment Was Present in Area of Fire, by Property Use Table 6. Extent of Flame Damage, for Sprinklers Present vs. Automatic Extinguishing 34 Equipment Absent Table 7. Number of Sprinklers Operating 35 Table 8. Sprinkler Effectiveness Related to Number of Sprinklers Operating 37 Table 9. Estimated Reduction in Civilian Deaths per Thousand Fires Associated 43 With Wet Pipe Sprinklers, by Property Use Table 10. Characteristics of Fatal Victims When Wet Pipe Sprinklers Operate vs. 44 All Conditions Table 11. Estimated Reduction in Average Direct Property Damage per Fire 45 Associated With Wet Pipe Sprinklers Table E. Non-Fire Sprinkler Activations and Major Property Use Group 48 Table F. Non-Fire Sprinkler Activations by Likelihood of Water Release and 48 Major Property Use Group U.S. Experience With Sprinklers, 2/10 v NFPA Fire Analysis and Research, Quincy, MA

9 U.S. Experience With Sprinklers, 2/10 vi NFPA Fire Analysis and Research, Quincy, MA

10 One-Stop Data Shop Fire Analysis and Research Division 1 Batterymarch Park, Quincy, MA osds@nfpa.org U.S. Experience with Sprinklers Sprinklers save lives and protect property from fires. Compared to properties without automatic extinguishing equipment The death rate per fire in sprinklered homes is lower by 83%. For most property uses, damage per fire is lower by 40-70% in sprinklered properties. Flame damage was confined to the room of origin in 95% of fires in sprinklered properties vs. 74% in fires with no automatic extinguishing equipment. Damage per Fire With and Without Sprinklers, Eating or drinking Educational Health care* Home including Apartment Hotel or motel $12,000 $18,000 $7,000 $8,000 $3,000 $17,000 $4,000 $19,000 $9,000 $42,000 Without automatic extinguishing equipment With sprinklers Store or office $44,000 $26,000 $0 $20,000 $40,000 $60,000 $80,000 $100,000$120,000 *Health care refers to hospitals, nursing homes, clinics, doctor s offices, and mental retardation facilities. Sprinklers are reliable and effective. In reported structure fires large enough to activate them, sprinklers operated in 93% of fires in sprinklered properties. Wet pipe sprinklers operated in 95% of these fires vs. 83% for dry pipe sprinklers. In reported structure fires large enough to activate them, sprinklers operated and were effective in 91% of fires in sprinklered properties. Wet pipe sprinklers operated and were effective in 92% of fires vs. 79% for dry pipe sprinklers. NOTE: NFPA s Fire Sprinkler Initiative: Bringing Safety Home is a nationwide effort to encourage the use of home fire sprinklers and the adoption of fire sprinkler requirements for new construction. See Statistics are based on U.S. reported fires excluding buildings under construction. Sprinklered properties exclude properties with no sprinklers in fire area. U.S. Experience With Sprinklers, 2/10 vii NFPA Fire Analysis And Research, Quincy, MA

11 The graph below is based on the 7% of fires in sprinklered properties (roughly 1,000 fires per year) in which the sprinkler should have operated but did not. Reasons When Sprinklers Fail to Operate System shut off before fire 53% Inappropriate system for fire 20% Lack of maintenance 15% Manual intervention defeated system 9% Damaged component 2% 0% 10% 20% 30% 40% 50% 60% In fires where sprinklers operated, they were effective in 97% of the cases. The graph below is based on the other 3% (roughly 400 fires per year), in which the sprinkler was ineffective. Reasons When Sprinklers Are Ineffective Water did not reach fire 43% Not enough water released 31% Inappropriate system for fire 12% Manual intervention defeated system Damaged component Lack of maintenance 5% 4% 4% 0% 10% 20% 30% 40% 50% Usually only 1 or 2 sprinklers are required to control the fire. When wet pipe sprinklers operated, 89% of reported fires involved only 1 or 2 sprinklers. For dry pipe sprinklers, 74% involved only 1 or 2 sprinklers. Statistics are based on U.S. reported fires excluding buildings under construction. Sprinklered properties exclude properties with no sprinklers in fire area. U.S. Experience With Sprinklers, 2/10 viii NFPA Fire Analysis And Research, Quincy, MA

12 Before You Read the Report: Some Introductory Notes on Incident Coding and Analysis See Appendix A for general information on the statistical methodology and see Appendix B for a detailed overview of data elements related to automatic extinguishing equipment. Here are some important points on incident coding and analysis that apply to this report: Fires excluded from analysis Fires in buildings with reported structure status of under construction are excluded. No fire protection systems or features can be expected to perform as designed in a building that is under construction. Statistics on reliability, effectiveness, and performance exclude partial systems as identified by reason for failure and ineffectiveness equal to equipment not in area of fire. Not all partial systems will be so identified, and the codes and standards for this equipment do not require coverage in all areas. For example, concealed spaces and exterior locations may not be required to have coverage. Missing choices and misleading labels when coding presence or type of automatic extinguishing report The established generic name of automatic extinguishing equipment is misleading, because many if not most such equipment is designed to control fires and not to fully extinguish them. There is no code for wet chemical system, which was mandated as the type of non-waterbased system to be used in eating and drinking establishments shortly after the coding rules were set for NFIRS Version 5.0, the current version of the U.S. Administration s National Fire Incident Reporting System. 1 Wet chemical systems may be coded as dry chemical systems, foam systems, or other special hazard systems and are probably more common than all of these other systems. Fire extinguishers are not automatic equipment and should not be coded but sometimes are reported under any of several types of automatic extinguishing equipment. There was no way to code automatic extinquishing equipment as unknown during 1999 to 2003, although there was the option of leaving the field blank. During that period, the U.S. Fire Administration advised that unknowns should be reported as no equipment present. 2 This arrangement had the potential to severely understate the presence of automatic extinguishing equipment. However, the estimates for 2002 and 2003 are not substantially lower than either the pre-1999 estimates or the three years of estimates from 2004 and later. Therefore, this potential problem seems to have had little effect in practice. 1 NFIRS compiles fire incident and casualty reports from participating U.S. local fire departments. NFPA s national estimates are based on NFIRS data and estimated totals from the annual NFPA fire experience survey of U.S. fire departments. 2 U.S. Fire Administration, NFIRS Coding Questions, revised January 2, 2002, p.13. U.S. Experience With Sprinklers, 2/10 1 NFPA Fire Analysis and Research, Quincy, MA

13 Recoding of sprinkler performance based on reasons for failure or ineffectiveness. The coding of reasons for failure or ineffectiveness has been used in this analysis to recode system performance entries. Unknown reasons have been proportionally allocated to avoid the dubious alternative assumption that the coded performance is correct if no reason is given for the performance. If Performance = Not Effective And Reason = System shut off Not in area of fire If Performance = Failed to Operate And Reason = Not enough agent Agent didn t reach fire Not in area of fire Then Change to: Performance = Failed to operate Presence = No; Performance not applicable Then Change to: Performance = Not effective Performance = Not effective Presence = No; Performance not applicable Note that this recoding will not address partial sprinkler systems where there were sprinklers in part or all of the fire area unless the system is ineffective because of fire spread to or from uncovered areas. U.S. Experience With Sprinklers, 2/10 2 NFPA Fire Analysis and Research, Quincy, MA

14 Presence of Sprinklers and Other Automatic Extinguishing Equipment Of reported structure fires in health care properties, an estimated 57% showed sprinklers present, with higher percentages for hospitals (71%) and nursing homes (65%) and a much lower percentage for clinics and doctor s offices (28%). Sprinklers were also reported as present in half or more of all reported fires in laboratories (60%), manufacturing facilities (52%), theaters (50%), and prisons and jails (50%). In every other property use, more than half of all reported fires had no sprinklers. In , only 7% of reported structure fires had any type of automatic extinguishing equipment present. By , this percentage had risen by about half, to 10%. Before 1999, the type of automatic extinguishing equipment was not reported, and so it is not possible to show the trend in sprinkler presence. It is possible to show the trend in presence of automatic extinguishing equipment generally and to show how sprinkler presence compares to automatic extinguishing equipment presence in the most recent years. See Table 1 for percentage of reported structure fires, excluding buildings under construction, in which automatic extinguishing equipment was present for the year groups of and Table 1 also shows percentage of fires with any type of sprinkler reported present for 2003 to The following properties where large numbers of people routinely are present show less than one-third of reported fires in properties with sprinklers present in : Every type of public assembly property except theaters Educational properties Clinics and doctor s offices Homes including apartments Every type of store or office except department stores Most fires in storage properties are not in warehouses but are in garages, barns, silos, and small outbuildings. It is these types of buildings that drive the very low percentage of reported fires with automatic extinguishing equipment in all storage properties combined. In , sprinklers were reported in only 5% of fires in homes (including apartments). Clearly, there is great potential for expanded installation. The 2007 American Housing Survey included a question about sprinkler presence in homes. 4 The survey indicated 3.9% of occupied year-round housing units had sprinklers. A much smaller percentage of single family homes had sprinklers as compared to multi-unit housing. Sprinklers were present in: 3 Some fires after 1999 are coded as confined fires, which are fires confined to cooking vessel, chimney or flue, furnace or boiler, incinerator, commercial compactor, or trash receptacle. Confined fires permit limited reporting with most data fields not required and usually left blank. Confined fires permit limited reporting with most data fields not required and usually left blank. Confined fires combine with very low sprinkler usage to make estimates for one- and two-family dwellings too volatile and uncertain to list separately, and so estimates are provided only for all homes combined 4 American Housing Survey 2007, U.S. Department of Commerce and U.S. Department of Housing and Urban Development, September 2008, Table 1C-4, 2-4, and U.S. Experience With Sprinklers, 2/10 3 NFPA Fire Analysis and Research, Quincy, MA

15 1.5% of single family detached homes, 1.9% of single family homes, whether detached or attached, 10.6% of all housing units in multi-unit buildings, 2.9% of housing units in buildings with 2-4 units, 5.8% of housing units in buildings with 5-9 units, 12.1% of housing units in buildings with units, 16.3% of housing units in buildings with units, and 27.3% of housing units in buildings with 50 or more units. Sprinklers are installed in 13.0% of housing units in buildings that were constructed no more than four years ago. This is more than triple the percentage for all housing units. No statistics are provided on sprinkler installation specifically in recently constructed single family homes, but detached single-family homes are a larger share of recently built housing units than of total housing units (70% vs. 63%). This strongly suggests that single family homes are part of the recent jump in sprinkler installation. Sprinkler presence percentages are higher in the West region than in other regions and lower in rural areas than in non-rural areas. To underscore the principal finding, more than 1 million single family detached dwellings now have fire sprinklers. The Home Fire Sprinkler Coalition, formed in 1996, developed a variety of educational materials about the benefits of home fire sprinklers. These materials address common questions and misconceptions. They may be accessed through their web site Because sprinkler systems are so demonstrably effective, they can make a major contribution to fire protection in any property. NFPA 101, Life Safety Code; NFPA 1, Fire Code; and NFPA 5000, Building Construction and Safety Code, have required sprinklers in all new one- and two-family dwellings, all nursing homes, and many nightclubs since the 2006 editions. The 2009 edition of the International Residential Code, also added requirements for sprinklers in one- and two-family dwellings, effective January This protection can be expected to increase in areas that adopt and follow these codes. NFPA is supporting adoption of these requirements through its Fire Sprinkler Initiative (see The few surveys that have been done of sprinkler presence in general, not limited to fires, have found that in any property group, the percentage of buildings with sprinklers is much higher than the percentage of reported fires with sprinklers present. Sprinklers apparently are still rare in many of the places where people are most exposed to fire, including educational properties, offices, most stores, and especially homes, where most fire deaths occur. There is considerable potential for expanded use of sprinklers to reduce the loss of life and property to fire. As with detection/alarm systems and all other fire protection features, in property classes where sprinklers are not required, they will tend to go first into the properties that can afford them most, not the high-risk fire-prone properties that would benefit most from their presence. U.S. Experience With Sprinklers, 2/10 4 NFPA Fire Analysis and Research, Quincy, MA

16 Table 1. Presence of Sprinklers and Other Automatic Extinguishing Equipment in Structure Fires, vs Number of Structure Fires With Equipment Present and Percentage of Total Structure Fires in Property Use Any Automatic Extinguishing Equipment Any Sprinkler Property Use All public assembly 4,380 (26%) 7,650 (49%) 3,040 (19%) Fixed-use amusement place 150 (18%) 170 (29%) 150 (24%) Variable-use amusement place 140 (16%) 270 (22%) 260 (22%) Religious property 90 (5%) 280 (15%) 270 (14%) Library or museum 110 (28%) 190 (28%) 180 (28%) Eating or drinking establishment 3,240 (29%) 4,730 (58%) 1,380 (17%) Passenger terminal 60 (35%) 180 (28%) 110 (16%) Theater 110 (35%) 140 (51%) 140 (50%) Educational property 1,820 (24%) 2,250 (34%) 2,010 (31%) Health care property 4,400 (68%) 4,010 (61%) 3,770 (57%) Nursing home 2,060 (76%) 2,060 (70%) 1,910 (65%) Hospital 1,650 (74%) 1,210 (77%) 1,110 (71%) Clinic or doctor s office 70 (29%) 200 (28%) 200 (28%) Prison or jail 430 (19%) 290 (51%) 290 (50%) All residential 11,110 (3%) 26,980 (8%) 25,820 (7%) Home (including apartment) 8,440 (2%) 21,110 (5%) 20,130 (5%) Hotel or motel 1,690 (35%) 1,900 (48%) 1,790 (45%) Dormitory or barracks 620 (29%) 1,670 (46%) 1,550 (42%) Rooming or boarding home 230 (17%) 970 (33%) 950 (32%) Board and care home NA (NA) 900 (43%) 790 (38%) Store or office 5,230 (21%) 6,090 (30%) 4,660 (23%) Grocery or convenience store 1,190 (27%) 2,030 (44%) 1,010 (22%) Laundry or dry cleaning or 310 (13%) 350 (19%) 340 (18%) other professional service Service station or motor 230 (6%) 230 (10%) 170 (7%) vehicle sales or service Department store 1,100 (52%) 610 (43%) 560 (39%) Office 1,470 (25%) 1,210 (32%) 1,170 (31%) Laboratory 120 (48%) 110 (65%) 100 (60%) Manufacturing facility 6,400 (50%) 4,070 (57%) 3,740 (52%) All storage 1,090 (3%) 950 (4%) 920 (4%) Warehouse excluding cold 740 (22%) 510 (38%) 510 (38%) storage** All structures 37,100 (7%) 53,940 (10%) 44,310 (9%) NA Category not defined in fire incident data prior to *Also includes development disability facilities. In , this category also includes care of physically inconvenienced and excludes doctor s office and care of aged facilities without nursing staff. **In , includes general warehouse, textile storage, processed food storage except cold storage and storage of wood, paper, plastics chemicals, and metals. Notes: These are structure fires reported to U.S. municipal fire departments and so exclude fire reported only to Federal or state agencies or industrial fire brigades. Post-1998 estimates are based only on fires reported in Version 5.0 of NFIRS and include fires reported as confined fires. Estimates are not shown for because of lower participation in NFIRS Version 5.0 in those years. After 1998, buildings under construction are excluded. Source: NFIRS and NFPA survey. U.S. Experience With Sprinklers, 2/10 5 NFPA Fire Analysis and Research, Quincy, MA

17 U.S. Experience With Sprinklers, 2/10 6 NFPA Fire Analysis and Research, Quincy, MA

18 Automatic Extinguishing Equipment Type In reported fires, most automatic extinguishing equipment is recorded as sprinklers, and most sprinklers are wet pipe sprinklers. Table 2 shows the percentage of non-confined and confined fires, excluding buildings under construction, by type of automatic extinguishing equipment for each of the major property groups and some subgroups. 5 Percentage calculations are based only on fires where automatic extinguishing equipment presence and type were known and reported. In Version 5.0 of NFIRS, if multiple systems are present, the system coded is supposed to be the one system designed to protect the hazard where the fire started. Some type of sprinklers were present in 82% of fires where automatic extinguishing equipment was present. Wet pipe sprinklers accounted for 73% of all systems and so outnumbered dry pipe sprinklers by roughly 10-to-1. The major property class with the largest share for dry pipe sprinklers was storage, where dry pipe sprinklers accounted for 20% of the systems cited. Cold storage was the only property class for which dry pipe sprinklers constituted a majority (in this case, 53%) of systems cited. For public assembly properties, there was a 40% to 60% split between sprinklers and other types of automatic extinguishing equipment, respectively. Dry chemical systems accounted for 40% of the systems present. Eating or drinking establishments (the dominant part of public assembly) had a 29% to 71% split between sprinkler systems and other types of automatic extinguishing equipment, respectively. Dry chemical systems accounted for 47% of total systems in eating or drinking establishments, compared to a 29% share for all sprinklers combined. Note that wet chemical systems have no clearly identified equipment type category but have been the mandated type of system for eating and drinking establishments for roughly a decade. It seems likely that most of the dry chemical systems reported are either wet chemical systems or dry chemical extinguishers, which should not be reported as any type of automatic equipment. Public assembly properties, especially eating and drinking establishments, have the highest percentages for both dry chemical systems (40% and 47%, respectively) and other special hazard systems (11% and 12%, respectively), both of which probably are dominated by wet chemical systems, for which there is no labeled category. Roughly ten years ago, the applicable standards for eating and drinking establishments required that dry chemical systems be replaced by wet chemical systems. It seems likely that some wet chemical systems will be coded as other special hazard systems and some will be coded as dry chemical systems, the latter being the well-defined equipment type closest to a wet chemical system. It would be useful to have a better sense of what kind of equipment is coded as other special hazard systems. There are some types of automatic extinguishing equipment that do not fit exactly into any of the defined categories, such as equipment using wet chemicals. It is also 5 Some fires after 1999 are coded as confined fires, which are fires confined to cooking vessel, chimney or flue, furnace or boiler, incinerator, commercial compactor, or trash receptacle. Confined fires permit limited reporting with most data fields not required and usually left blank. Confined fires combine with very low sprinkler usage to make estimates for one- and two-family dwellings too volatile and uncertain to list separately, and so estimates are provided only for all homes combined U.S. Experience With Sprinklers, 2/10 7 NFPA Fire Analysis and Research, Quincy, MA

19 possible that some fires will be coded as other special hazard system when they really involved automatic extinguishing equipment of one of the defined types. The category also could be used for some devices that are not automatic and so should not be coded as automatic extinguishing equipment present, such as portable extinguishers. Some insight into what is being coded under other special hazard systems comes from a check of uncoded narratives for the three restaurant fires in recent years in Minnesota where such equipment was reported. (The narratives on these fires were part of a data set provided for a special analysis described on p. 49.) One fire involved a wet chemical system, and another involved an undefined hood system, which could have involved wet or dry chemical agents. The third fire involved use of portable extinguisher and should not have been coded as automatic extinguishing equipment present. U.S. Experience With Sprinklers, 2/10 8 NFPA Fire Analysis and Research, Quincy, MA

20 Table 2. Type of Automatic Extinguishing Equipment Reported as Percentage of All Fires Where Equipment Was Present and of Known Type, by Property Use Structure Fires Reported to U.S. Fire Departments Property Use Fires per year with any automatic extinguishing equipment All sprinklers Wet pipe sprinklers Dry pipe sprinklers Other sprinklers* All public assembly 7,650 40% 34% 2% 4% Fixed-use amusement place % 82% 3% 1% Variable-use amusement place % 84% 13% 0% Religious property % 86% 4% 7% Library or museum % 92% 5% 2% Eating or drinking establishment 4,730 29% 23% 2% 4% Passenger terminal % 35% 22% 1% Theater % 95% 3% 1% Educational property 2,250 89% 80% 6% 3% Health care property** 4,010 94% 81% 12% 1% Nursing home 2,060 93% 78% 15% 1% Hospital 1,210 92% 85% 6% 1% Clinic or doctor s office % 95% 3% 1% Prison or jail % 87% 10% 2% All residential 26,980 96% 87% 7% 2% Home (including apartment) 21,110 95% 86% 6% 3% Hotel or motel 1,900 94% 85% 6% 3% Dormitory or barracks 1,670 93% 77% 14% 1% Rooming or boarding house % 88% 11% 0% Board and care home % 82% 7% 0% Store or office 6,090 77% 67% 7% 3% Grocery or convenience store 2,030 50% 44% 3% 3% Laundry or dry cleaning or other % 85% 9% 1% professional service Service station or motor vehicle % 70% 5% 1% sales or service Department store % 78% 12% 1% Office 1,210 97% 85% 7% 4% Laboratory % 69% 2% 21% Manufacturing facility 4,070 92% 79% 10% 3% All storage % 75% 20% 2% Warehouse excluding cold storage % 82% 15% 1% All structures*** 53,940 82% 73% 7% 3% * Includes deluge and pre-action sprinkler systems and may include sprinklers of unknown or unreported type. ** Nursing home, hospital, clinic, doctor s office, or development disability facility *** Includes some property uses that are not shown separately. Note: These are based on structure fires reported to U.S. municipal fire departments in NFIRS Version 5.0 and so exclude fires reported only to Federal or state agencies or industrial fire brigades. Row totals are shown in the leftmost column of percentages, and sums may not equal totals because of rounding error. In Version 5.0 of NFIRS, if multiple systems are present, the system coded is supposed to be the one system designed to protect the hazard where the fire started. This field is not required if the fire did not begin within the designed range of the system. Buildings under construction are excluded. Source: NFIRS and NFPA survey. U.S. Experience With Sprinklers, 2/10 9 NFPA Fire Analysis and Research, Quincy, MA

21 Table 2. (Continued) Type of Automatic Extinguishing Equipment Reported as Percentage of All Fires Where Equipment Was Present and of Known Type, by Property Use Structure Fires Reported to U.S. Fire Departments Property Use All systems other than sprinklers Dry chemical system* Carbon dioxide (CO2) system Halogen type system* Foam system Other special hazard system* All public assembly 60% 40% 3% 3% 4% 11% Fixed-use amusement place 15% 14% 0% 0% 0% 1% Variable-use amusement place 3% 2% 0% 0% 0% 1% Religious property 3% 2% 0% 0% 0% 1% Library or museum 1% 1% 0% 0% 0% 0% Eating or drinking establishment 71% 47% 3% 3% 5% 12% Passenger terminal 42% 41% 0% 0% 0% 1% Theater 1% 1% 0% 0% 0% 0% Educational property 11% 8% 0% 0% 1% 2% Health care property** 6% 4% 1% 0% 0% 1% Nursing home 7% 5% 1% 0% 0% 0% Hospital 8% 5% 0% 0% 0% 3% Clinic or doctor s office 2% 0% 0% 0% 0% 1% Prison or jail 2% 1% 0% 0% 0% 0% All residential 4% 2% 0% 0% 0% 2% Home (including apartment) 5% 2% 0% 0% 0% 2% Hotel or motel 6% 2% 0% 0% 0% 4% Dormitory or barracks 7% 5% 0% 0% 1% 1% Rooming or boarding home 2% 1% 0% 0% 0% 0% Board and care home 11% 4% 0% 0% 4% 3% Store or office 23% 15% 2% 1% 2% 4% Grocery or convenience store 50% 31% 4% 1% 6% 7% Laundry or dry cleaning 5% 0% 0% 0% 0% 4% Service station or motor 24% 20% 0% 1% 0% 2% vehicle sales or service Department store 9% 8% 0% 0% 0% 0% Office 3% 1% 1% 0% 0% 0% Laboratory 8% 2% 4% 1% 0% 1% Manufacturing facility 8% 2% 4% 0% 0% 1% All storage 3% 1% 0% 0% 0% 2% Warehouse excluding cold storage 1% 0% 0% 0% 0% 0% Cold storage 0% 0% 0% 0% 0% 0% All structures*** 18% 11% 1% 1% 1% 4% * Dry chemical system may include wet chemical systems, because there is no category designated for wet chemical systems. Halogen type system includes non-halogenated suppression systems that operate on the same principle. Other special hazard system may include automatic extinguishing systems that are known not to be sprinklers but otherwise are of unknown or unreported type. ** Nursing home, hospital, clinic, doctor s office, or development disability facility. *** Includes some property uses that are not shown separately. Note: These are based on structure fires reported to U.S. municipal fire departments in NFIRS Version 5.0 and so exclude fires reported only to Federal or state agencies or industrial fire brigades. Row totals are shown in the leftmost column of percentages, and sums may not equal totals because of rounding error. In Version 5.0 of NFIRS, if multiple systems are present, the system coded is supposed to be the one system designed to protect the hazard where the fire started. This field is not required if the fire did not begin within the designed range of the system. Building under construction are excluded. Source: NFIRS and NFPA survey. U.S. Experience With Sprinklers, 2/10 10 NFPA Fire Analysis and Research, Quincy, MA

22 Automatic Extinguishing Equipment Reliability and Effectiveness In order to estimate the reliability and effectiveness of any type of automatic extinguishing equipment, the database must first be edited to remove fires, buildings, and systems where operation cannot be expected, such as small fires, buildings under construction, and partial installations. Table 3 shows the percentage of non-confined and confined structure fires, excluding buildings under construction and incidents with partial systems not in area of fire, where fires were too small to activate operational automatic extinguishing equipment. Table 3 also shows, for fires large enough to activate equipment, the percentage of fires where equipment operated, the percentage of operating equipment cases where equipment was effective, and the percentage of fires where equipment operated effectively. This is shown for: All sprinklers Wet pipe sprinklers Dry pipe sprinklers Dry chemical systems (which probably includes and may be dominated by wet chemical systems and may include some miscoded portable extinguishers), Carbon dioxide systems (which may include some wet chemical systems and some miscoded portable extinguishers), Foam systems (which may include some wet chemical systems and some miscoded portable extinguishers), and Halogen systems (which may include some wet chemical systems and some miscoded portable extinguishers). Property use classes are shown only if they accounted for at least 100 projected fires per year with the specific type of automatic extinguishing equipment present. For most property use groups and most types of automatic extinguishing equipment, the majority of reported fires were too small to activate operational equipment. When automatic extinguishing equipment was present, the percentages of fires too small to activate operating equipment, based on overall reported structure fires, were as follows: 65% for all sprinklers, 65% for wet pipe sprinklers, 70% for dry pipe sprinklers, 61% for dry (or possibly wet) chemical systems, 43% for carbon dioxide systems, 66% for foam systems, and 59% for halogen systems. Sprinklers in the area of fire failed to operate in only 7% of reported structure fires large enough to activate sprinklers. Failure rates are equal to 100% minus the percentage of systems that operated, which is the percentage shown in Table 3A. The other estimated failure rates corresponding to percentage operating rates shown in Table 3A are: 5% for wet pipe sprinklers, U.S. Experience With Sprinklers, 2/10 11 NFPA Fire Analysis and Research, Quincy, MA

23 17% for dry pipe sprinklers, 26% for dry (or possibly wet) chemical systems, 17% for carbon dioxide systems, 3% for foam systems, and 4% for halogen systems. For major property classes and sprinklers, the estimated failure rates range from a low of 4% for residential properties, public assembly properties and stores and offices to a high of 32% for educational properties and 29% for storage properties. The estimated failure rates for wet pipe sprinklers specifically were 25% for educational properties and 16% for storage properties. For sprinklers that operated, their performance was deemed effective in 97% of the cases. For all confined or non-confined fires large enough to activate sprinklers, excluding buildings under construction, sprinklers operated effectively 91% of the time. The percentages of effective operation for all structures were as follows for other types of automatic extinguishing equipment: 92% for wet pipe sprinklers, 79% for dry pipe sprinklers, 60% for dry (or possibly wet) chemical systems, 79% for carbon dioxide systems, 81% for foam systems, and 88% for halogen systems. Wet pipe sprinklers are both much more reliable than dry pipe sprinklers (95% vs. 83%) and slightly more effective when they operate (98% vs. 95%), resulting in a much higher percentage of effective operation (92% vs. 79%). Operating effectiveness is much lower for dry (or possibly wet) chemical systems than for any other type of automatic extinguishing equipment (60% vs %) and is especially low (51%) for eating or drinking establishments, which account for most of the fires reported with this type of equipment. Eating or drinking establishments also account for most fires reported with carbon dioxide, foam, or halogen systems. These installations may all include a high proportion of misclassified wet chemical systems or portable extinguishers, because carbon dioxide, foam, and halogen systems are rarely appropriate for eating or drinking establishments. A disadvantage of measuring automatic extinguishing equipment effectiveness by judgments made in incident reports is the ambiguity and subjectivity of the criterion of effective, which has never been precisely defined, let alone supported by an operational assessment protocol that could be executed consistently by different people. Also, confined fires usually have these details unreported, and so their few fires with details reported will be weighted far more heavily, after allocation of unknowns, than will non-confined fires. The majority of sprinkler failures occurred because the system was shut off. Table 4 provides the percentages of reasons for failure, after recoding, by type of automatic extinguishing system and property use. Other or unclassified reason for failure is treated as an unknown and allocated. U.S. Experience With Sprinklers, 2/10 12 NFPA Fire Analysis and Research, Quincy, MA

24 For all types of sprinklers combined: 53% of failures to operate were attributed to the equipment being shut off, 20% were because the equipment was inappropriate for the type of fire, 15% were because of lack of maintenance, 9% were because manual intervention defeated the equipment, and 2% were because a component was damaged. If manual intervention occurs before fire begins, one would expect that to be coded as system shut off before fire. If manual intervention occurs after sprinklers operate, one would expect that to constitute ineffective performance, not failure to operate. What is left is manual intervention after fire begins but before sprinklers operate, but we do not know whether that is the only condition associated with this coding. Only 2% were because of a failing of the equipment rather than a failing of the people who designed, selected, maintained, and operated the equipment. If these human failings could be eliminated, the overall sprinkler failure rate would drop from the estimated 7% of reported fires to less than 0.2%. That is the kind of sprinkler failure rate reported by Marryatt 6 for Australia and New Zealand, where high standards of maintenance are reportedly commonplace. Training can sharply reduce the likelihood of three other causes of failure system defeating due to manual intervention, lack of maintenance, and installation of the wrong system for the hazard. Most cases of sprinkler ineffectiveness were because water did not reach the fire (43%) or because not enough water was released (31%). Table 5 provides distributions of reasons for ineffectiveness, by property class and type of automatic extinguishing equipment. In Table 5, two of the reasons for ineffectiveness are (extinguishing) agent did not reach the fire and not enough (extinguishing) agent was released. For sprinklers, the agent is water. In addition to the two reasons cited, other reasons for sprinkler ineffectiveness for all structures were inappropriate equipment for the type of fire (12%), defeating due to manual intervention (5%), damage to a system component (4%), and lack of maintenance (4%). There are a number of different ways in which water may not reach the fire. One is shielded fires such as rack storage in a property with ceiling sprinklers only. Another is fire spread above exposed sprinklers, through unsprinklered concealed spaces, or via exterior surfaces. Another reason would be a deep-seated fire in bulk storage. A different kind of problem would be droplet sizes that are too small to penetrate the buoyant fire plume and reach the seat of the fire. Insufficient water can be released if there are problems with the system s water supply. This reason for ineffectiveness can also overlap with other reasons, such as inappropriate equipment (if, for example, the hazard has changed under the equipment and now requires a higher water flow density than is provided by the now inappropriate equipment) and defeating by manual intervention (if, for example, the sprinklers are turned off prematurely so that insufficient water reaches the fire). Insufficient water also could be one of the reasons that could be cited if a flash 6 H.W. Marryatt, Fire: A Century of Automatic Sprinkler Protection in Australia and New Zealand, , 2 nd edition, Victoria, Australia: Australian Fire Protection Association, U.S. Experience With Sprinklers, 2/10 13 NFPA Fire Analysis and Research, Quincy, MA

25 fire or a fire with several points of origin overwhelms the system or if an explosion reduces the water flow but does not cause complete system failure. Reasons for ineffectiveness are different for wet pipe sprinklers and dry pipe sprinklers, with dry pipe sprinklers having 60% of cases attributed to not enough water released compared to 25% for wet pipe sprinklers. Because the design of dry pipe sprinklers assures a delayed release of water, it is not surprising that when such systems are ineffective, an insufficiency of water is usually involved. Even a well-maintained, complete, appropriate system requires the support of a well-considered integrated design for all the other elements of the building s fire protection. Unsatisfactory sprinkler performance can result from an inadequate water supply or faulty building construction. More broadly, unsatisfactory fire protection performance can occur if the building s design does not address all five elements of an integrated system slowing the growth of fire, automatic detection, automatic suppression, confining the fire, and occupant evacuation. Effectiveness should be measured relative to the design objectives for a particular system. For most rooms in most properties, sprinklers are designed to confine fire to the room of origin. Table A. Non-Confined Fires With Areas of Origin That Could Be Room Larger Than the Sprinkler Design Area for the Space, as Percent of Total Non-Confined and Confined Structure Fires for Buildings Not Under Construction and With Sprinklers in Fire Area Percentage of Structure Fires Reported to U.S. Fire Departments Property Use Large Assembly Area (At Least 100 People) Sales, Showroom or Performance Area Storage Room, Area, Tank or Bin Shipping, Receiving or Loading Area Unclassified Storage Area All Areas Combined Eating or drinking 1.0% 0.2% 1.7% 0.2% 1.2% 4.3% establishment Public assembly excluding eating 2.4% 0.7% 0.9% 0.2% 0.8% 5.0% or drinking establishment Educational 1.3% 0.3% 0.6% 0.0% 0.7% 2.9% Health care property* 0.1% 0.0% 0.5% 0.0% 0.3% 0.9% Home (including apartment) 0.0% 0.0% 0.2% 0.0% 0.2% 0.4% Hotel or motel 1.6% 0.0% 0.3% 0.0% 0.5% 1.4% Store or office 0.1% 5.7% 2.2% 2.1% 2.2% 12.2% Manufacturing facility 0.1% 0.0% 2.5% 2.1% 1.7% 6.4% Warehouse excluding cold 0.1% 0.3% 5.0% 12.4% 9.9% 27.7% storage * Hospital, clinic, doctor s office, nursing home and development disability facility. Note: Percentages are defined as non-confined fires with indicated area of origin divided by total non-confined and confined fires with any area of origin. Percentages sum left to right and may not equal totals in last column because of rounding. Fires reported as confined fires are excluded from the numerator because such fires could not be large enough to exceed the sprinkler design area. Statistics are based on structure fires reported to U.S. municipal fire departments and so exclude fires reported only to Federal or state agencies or industrial fire brigades. Statistics exclude buildings under construction and fires with sprinklers not in fire area reported as reason for failure or ineffectiveness of automatic extinguishing equipment. Source: NFIRS and NFPA survey. U.S. Experience With Sprinklers, 2/10 14 NFPA Fire Analysis and Research, Quincy, MA

Structure Fires in Laboratories. Marty Ahrens Fire Analysis and Research Division National Fire Protection Association

Structure Fires in Laboratories. Marty Ahrens Fire Analysis and Research Division National Fire Protection Association Structure Fires in Laboratories Marty Ahrens Fire Analysis and Research Division National Fire Protection Association February 2016 National Fire Protection Association, 1 Batterymarch Park, Quincy, MA

More information

HIGH-RISE BUILDING FIRES

HIGH-RISE BUILDING FIRES HIGH-RISE BUILDING FIRES John R. Hall, Jr. September 2013 National Fire Protection Association Fire Analysis and Research Division HIGH-RISE BUILDING FIRES John R. Hall, Jr. September 2013 National Fire

More information

U.S. EXPERIENCE WITH NON-WATER-BASED AUTOMATIC FIRE EXTINGUISHING EQUIPMENT

U.S. EXPERIENCE WITH NON-WATER-BASED AUTOMATIC FIRE EXTINGUISHING EQUIPMENT U.S. EXPERIENCE WITH NON-WATER-BASED AUTOMATIC FIRE EXTINGUISHING EQUIPMENT John R. Hall, Jr. October 2012 National Fire Protection Association Fire Analysis and Research Division U.S. EXPERIENCE WITH

More information

FIRES IN HEALTH CARE FACILITIES

FIRES IN HEALTH CARE FACILITIES FIRES IN HEALTH CARE FACILITIES Marty Ahrens November 2012 (Revised April 2013) National Fire Protection Association Fire Analysis and Research Division FIRES IN HEALTH CARE FACILITIES Marty Ahrens November

More information

HOME FIRES INVOLVING HEATING EQUIPMENT

HOME FIRES INVOLVING HEATING EQUIPMENT HOME FIRES INVOLVING HEATING EQUIPMENT John R. Hall, Jr. October 2013 National Fire Protection Association Fire Analysis and Research Division HOME FIRES INVOLVING HEATING EQUIPMENT John R. Hall, Jr. October

More information

Smoke Alarms in U.S. Home Fires

Smoke Alarms in U.S. Home Fires Smoke Alarms in U.S. Home Fires September 2015 Marty Ahrens September 2015 National Fire Protection Association Abstract Smoke alarms provide a critical early warning of fire, allowing additional time

More information

Home ELECTRICAL FIRES

Home ELECTRICAL FIRES Home ELECTRICAL FIRES John R. Hall, Jr. April 2013 National Fire Protection Association Fire Analysis and Research Division Home ELECTRICAL FIRES John R. Hall, Jr. April 2013 National Fire Protection Association

More information

A Few Facts at the Household Level

A Few Facts at the Household Level A Few Facts at the Household Level Fire Analysis and Research Division July 2009 National Fire Protection Association Fire Analysis and Research Division For more information about the National Fire Protection

More information

Smoke Alarms in U.S. Home Fires

Smoke Alarms in U.S. Home Fires Smoke Alarms in U.S. Home Fires Marty Ahrens September 2011 National Fire Protection Association Fire Analysis and Research Division Smoke Alarms in U.S. Home Fires Marty Ahrens September 2011 National

More information

PATTERNS OF FIREFIGHTER FIREGROUND INJURIES

PATTERNS OF FIREFIGHTER FIREGROUND INJURIES PATTERNS OF FIREFIGHTER FIREGROUND INJURIES Michael J. Karter, Jr. December 2013 National Fire Protection Association Fire Analysis and Research Division PATTERNS OF FIREFIGHTER FIREGROUND INJURIES Michael

More information

WHAT YOU NEED TO KNOW ABOUT INSURING A HOME WITH FIRE SPRINKLERS

WHAT YOU NEED TO KNOW ABOUT INSURING A HOME WITH FIRE SPRINKLERS WHAT YOU NEED TO KNOW ABOUT INSURING A HOME WITH FIRE SPRINKLERS A GUIDE FOR PROPERTY & CASUALTY INSURANCE PROFESSIONALS HomeFireSprinkler.org FIRE THE LARGEST SINGLE CAUSE OF PROPERTY LOSS Fire is the

More information

DEATHS AND INJURIES DUE TO NON-FIRE BURNS

DEATHS AND INJURIES DUE TO NON-FIRE BURNS DEATHS AND INJURIES DUE TO NON-FIRE BURNS John R. Hall, Jr. April 2009 National Fire Protection Association Fire Analysis and Research Division Abstract In 2003-2007, an estimated 224,200 burn injuries

More information

Fire Loss in the United States During 2014

Fire Loss in the United States During 2014 Fire Loss in the United States During 2014 September 2015 Hylton J.G. Haynes September 2015 National Fire Protection Association Abstract U.S. fire departments responded to an estimated 1,298,000 fires

More information

One- and Two-Family Residential Building Fires

One- and Two-Family Residential Building Fires Topical Fire report SerieS Volume 10, Issue 7 / June 2010 One- and Two-Family Residential Building Fires These topical reports are designed to explore facets of the U.S. fire problem as depicted through

More information

Fire Sprinkler Contractor General Liability Application

Fire Sprinkler Contractor General Liability Application Scottsdale Insurance Company Home Office: One Nationwide Plaza Columbus, Ohio 43215 Adm. Office: 8877 North Gainey Center Drive Scottsdale, Arizona 85258 Scottsdale Indemnity Company Home Office: One Nationwide

More information

Medical Facility Fires

Medical Facility Fires Topical Fire Report Series Volume 9, Issue 4 / May 2009 Medical Facility Fires These short topical reports are designed to explore facets of the U.S. fire problem as depicted through data collected in

More information

It is also an integral component of the Municipal Fire Protection Information Survey (MFPISS).

It is also an integral component of the Municipal Fire Protection Information Survey (MFPISS). Coding 1 of 13 Conducting a simplified risk assessment (SRA) of the community is the precursor to determining the most appropriate programs and activities to deliver to the public. It is also an integral

More information

Performance of Smoke Detectors and Sprinklers in Residential and Health-Care Occupancies

Performance of Smoke Detectors and Sprinklers in Residential and Health-Care Occupancies Performance of Smoke Detectors and Sprinklers in Residential and Health-Care Occupancies James A. Milke, Ph.D., P.E., A.J. Campanella, Cathleen T. Childers and Brittany D. Wright Department of Fire Protection

More information

HOME CHRISTMAS TREE AND HOLIDAY LIGHT FIRES. John R. Hall, Jr. November 2013

HOME CHRISTMAS TREE AND HOLIDAY LIGHT FIRES. John R. Hall, Jr. November 2013 HOME CHRISTMAS TREE AND HOLIDAY LIGHT FIRES John R. Hall, Jr. November 2013 HOME CHRISTMAS TREE AND HOLIDAY LIGHT FIRES John R. Hall, Jr. November 2013 Abstract NFPA estimates that Christmas trees, both

More information

US FIRE DEPARTMENT PROFILE 2013

US FIRE DEPARTMENT PROFILE 2013 US FIRE DEPARTMENT PROFILE 2013 Hylton J. G. Haynes Gary P. Stein November 2014 National Fire Protection Association Fire Analysis and Research Division US FIRE DEPARTMENT PROFILE 2013 Hylton J. G. Haynes

More information

U.S. FIRE SERVICE FATALITIES IN STRUCTURE FIRES, 1977-2009

U.S. FIRE SERVICE FATALITIES IN STRUCTURE FIRES, 1977-2009 U.S. FIRE SERVICE FATALITIES IN STRUCTURE FIRES, 1977-2009 Rita F. Fahy, Ph.D. June 2010 National Fire Protection Association Fire Analysis and Research Division For more information about the National

More information

Daycare Center Fires

Daycare Center Fires U.S. Fire Administration TOPICAL FIRE RESEARCH SERIES Volume 2, Issue 15 November 2001 (Rev. March 2002) Daycare Center Fires FINDINGS S An estimated 325 fires occur in daycare centers/facilities each

More information

Attic Fires in Residential Buildings

Attic Fires in Residential Buildings Topical Fire report SerieS Volume 11, Issue 6 / January 2011 Attic Fires in Residential Buildings These topical reports are designed to explore facets of the U.S. fire problem as depicted through data

More information

Uses of Energy. Residential- homes Commercial - buildings Industry and Manufacturing Transportation- cars, trucks, planes, etc.

Uses of Energy. Residential- homes Commercial - buildings Industry and Manufacturing Transportation- cars, trucks, planes, etc. Uses of Energy Residential- homes Commercial - buildings Industry and Manufacturing Transportation- cars, trucks, planes, etc. links page recent statistics The United States is a highly developed and industrialized

More information

In 1980, the National Fire Protection Association (NFPA)

In 1980, the National Fire Protection Association (NFPA) Topical Fire Report Series Volume 10, Issue 4 / January 2010 Hotel and Motel Fires These topical reports are designed to explore facets of the U.S. fire problem as depicted through data collected in the

More information

Section 9 Major Urban Fire

Section 9 Major Urban Fire Section 9 Major Urban Fire Table of Contents WHY MAJOR URBAN FIRES ARE A THREAT...9-2 HAZARD PROFILE...9-3 HISTORY OF MAJOR URBAN FIRES...9-4 POTENTIAL DAMAGES AND LOSSES...9-5 MAJOR URBAN FIRE MITIGATION

More information

DEPARTMENT OF CONSUMER AND INDUSTRY SERVICES DIRECTOR'S OFFICE

DEPARTMENT OF CONSUMER AND INDUSTRY SERVICES DIRECTOR'S OFFICE DEPARTMENT OF CONSUMER AND INDUSTRY SERVICES DIRECTOR'S OFFICE CERTIFICATION OF FIRMS FOR FIRE ALARM SYSTEMS AND FIRE SUPPRESSION SYSTEMS IN STATE-REGULATED FACILITIES (By authority conferred on the state

More information

MAINTENANCE AND SERVICE OF AUTOMATIC FIRE EXTINGUISHING SYSTEMS

MAINTENANCE AND SERVICE OF AUTOMATIC FIRE EXTINGUISHING SYSTEMS FIRE DEPARTMENT Bureau of Fire Protection and Life Safety www.cityofsanmateo.org 1900 O Farrell, Suite 140 San Mateo, CA 94403-1332 (650) 522-7940 FAX: (650) 522-7941 TDD: (650) 522-7047 MAINTENANCE AND

More information

Development of a Risk-Based Decision Support Tool to Assist Fire Departments in Managing Unwanted Alarms SupDet 2013 Conference

Development of a Risk-Based Decision Support Tool to Assist Fire Departments in Managing Unwanted Alarms SupDet 2013 Conference Development of a Risk-Based Decision Support Tool to Assist Fire Departments in Managing Unwanted Alarms SupDet 2013 Conference John R. Hall, Jr. Fire Analysis & Research Division National Fire Protection

More information

FIRE SERVICE PERFORMANCE MEASURES

FIRE SERVICE PERFORMANCE MEASURES FIRE SERVICE PERFORMANCE MEASURES Jennifer D. Flynn November 2009 National Fire Protection Association Fire Analysis and Research Division FIRE SERVICE PERFORMANCE MEASURES Jennifer D. Flynn November 2009

More information

Concord Department of Fire and Life Safety FIRE MARSHAL S OFFICE

Concord Department of Fire and Life Safety FIRE MARSHAL S OFFICE Concord Department of Fire and Life Safety FIRE MARSHAL S OFFICE September 1, 2005 Fire Suppression Operations in Residential Occupancies equipped with Residential Fire Sprinkler Systems. Since human beings

More information

MARKETING HOMES PROTECTED BY FIRE SPRINKLER SYSTEMS

MARKETING HOMES PROTECTED BY FIRE SPRINKLER SYSTEMS MARKETING HOMES PROTECTED BY FIRE SPRINKLER SYSTEMS A GUIDE FOR REAL ESTATE PROFESSIONALS HomeFireSprinkler.org HOME FIRE SPRINKLER SYSTEMS A GROWING TREND THAT S HERE TO STAY If you re marketing a home

More information

In accordance with NFPA 30, these containers are not to store Class I flammable liquids.

In accordance with NFPA 30, these containers are not to store Class I flammable liquids. In accordance with NFPA 30, these containers are not to store Class I flammable liquids. Zurich recommends storing these containers in dedicated liquid storage rooms, detached buildings, or in listed dispensing

More information

MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY

MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY State Fire Marshal Division 444 Cedar Street, Suite 145, St. Paul, Minnesota 55101-5145 Phone: 651/201-7200 FAX: 651/215-0525 TTY: 651/282/6555 Internet: http://www.fire.state.mn.us

More information

CHAPTER 29 PLUMBING SYSTEMS

CHAPTER 29 PLUMBING SYSTEMS CHAPTER 29 SYSTEMS Note: The amendments to Chapter 29 are different than the 2009 Seattle Building Code and are not marked with margin bars or arrows. SECTION 2901 GENERAL [P] 2901.1 Scope. The provisions

More information

THE TOTAL COST OF FIRE IN THE UNITED STATES

THE TOTAL COST OF FIRE IN THE UNITED STATES THE TOTAL COST OF FIRE IN THE UNITED STATES John R. Hall, Jr. March 2014 National Fire Protection Association Fire Analysis and Research Division THE TOTAL COST OF FIRE IN THE UNITED STATES John R. Hall,

More information

Table 200.5.10.1 PARKING SPACE RATES AND PARKING SPACE OCCUPANCY

Table 200.5.10.1 PARKING SPACE RATES AND PARKING SPACE OCCUPANCY Table 200.5.10.1 PARKING SPACE RATES AND PARKING SPACE OCCUPANCY. AM = 6 a.m. to Noon. Adult Education School Adult Entertainment (A) in Policy Area 1 (PA1), Policy Area 2 (PA2) Policy Area 3 (PA3) at

More information

New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings

New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings Note: This information addresses complex issues in a summary fashion. Consideration should be given to the official version of the

More information

Chapter 16.130 PLUMBING CODE

Chapter 16.130 PLUMBING CODE DISSCUSSION ITEM 3 ATTACHMENT E Chapter 16.130 PLUMBING CODE 16.130.100 Plumbing Code - Incorporation. There is incorporated by reference, for purpose of adopting regulations, provisions, conditions, terms,

More information

Home Structure Fires Involving Christmas Trees

Home Structure Fires Involving Christmas Trees Home Structure Fires Involving Christmas Trees November, 2015 Marty Ahrens November 2015 National Fire Protection Association Abstract Christmas trees are a traditional part of the Christmas holiday. They

More information

H O M E F I R E S P R I N K L E R S S A V E L I V E S, M O N E Y A N D W A T E R A G U I D E F O R W A T E R P U R V E Y O R S

H O M E F I R E S P R I N K L E R S S A V E L I V E S, M O N E Y A N D W A T E R A G U I D E F O R W A T E R P U R V E Y O R S H O M E F I R E S P R I N K L E R S S A V E L I V E S, M O N E Y A N D W A T E R A G U I D E F O R W A T E R P U R V E Y O R S HomeFireSprinkler.org F I R E T H E L A R G E ST S I N G L E C AU S E O F

More information

ANNUAL FIRE PROTECTION SUMMARY INFORMATION REPORTING GUIDE Revised: May 2011

ANNUAL FIRE PROTECTION SUMMARY INFORMATION REPORTING GUIDE Revised: May 2011 ANNUAL FIRE PROTECTION SUMMARY INFORMATION REPORTING GUIDE Revised: May 2011 Organizations responsible for maintaining property under stewardship of DOE and the Administrator, NNSA, will seek concurrence

More information

Fire Safety In High Rise Building

Fire Safety In High Rise Building Fire Safety In High Rise Building CLASSIFICATION OF BUILDINGS AS PER NATIONAL BUILDING CODE 1. GROUPING. Group A - Residential : Lodgings, Dwellings, Dormitories, Flats, Hotels. Group B Group C - Educational

More information

Clothes Dryer Fires in Residential Buildings (2008 2010)

Clothes Dryer Fires in Residential Buildings (2008 2010) Topical Fire report SerieS Volume 13, Issue 7 / August 2012 Clothes Dryer Fires in Residential Buildings (2008 2010) These topical reports are designed to explore facets of the U.S. fire problem as depicted

More information

Fire Sprinkler Fact Sheet

Fire Sprinkler Fact Sheet Fire Sprinkler Fact Sheet Because of changes in residential construction technology, improved building code requirements - especially for electrical and smoke alarm systems, as well as consumer behavior

More information

MOTOR FUEL DISPENSING SAFETY

MOTOR FUEL DISPENSING SAFETY STRATEGIC OUTCOMES PRACTICE TECHNICAL ADVISORY BULLETIN January 2010 MOTOR FUEL DISPENSING SAFETY Fire! Not an alarm anyone wants to hear, especially not when the fire is burning at a major fuel source.

More information

COMPUTER ROOMS AND OTHER ELECTRONIC EQUIPMENT AREAS

COMPUTER ROOMS AND OTHER ELECTRONIC EQUIPMENT AREAS COMPUTER ROOMS AND OTHER ELECTRONIC EQUIPMENT AREAS John R. Hall, Jr. March 2012 National Fire Protection Association Fire Analysis and Research Division COMPUTER ROOMS AND OTHER ELECTRONIC EQUIPMENT AREAS

More information

WHAT'S CHANGED OVER THE PAST 30 YEARS?

WHAT'S CHANGED OVER THE PAST 30 YEARS? WHAT'S CHANGED OVER THE PAST 3 YEARS? Rita F. Fahy Paul R. LeBlanc Joseph L. Molis Fire Analysis and Research Division National Fire Protection Association June 27 National Fire Protection Association,

More information

FIRE SPRINKLER TALKING POINTS

FIRE SPRINKLER TALKING POINTS An Overview of the Issues FIRE SPRINKLER TALKING POINTS Because of changes in residential construction technology, improved building code requirements especially for electrical and smoke alarm systems

More information

Automatic fire-extinguishing systems for commercial cooking

Automatic fire-extinguishing systems for commercial cooking Automatic fire-extinguishing systems for commercial cooking Leading Items First Ignited in Eating and Drinking Establishment Structure Fires, 2000-2004 Annual Averages Cooking materials, incl. food and

More information

University Housing Fires (2007-2009)

University Housing Fires (2007-2009) Topical Fire report SerieS Volume 12, Issue 9 / August 2011 University (2007-2009) These topical reports are designed to explore facets of the U.S. fire problem as depicted through data collected in the

More information

We hope these Frequently Asked Questions will be of use both to municipal officials and fire inspectors.

We hope these Frequently Asked Questions will be of use both to municipal officials and fire inspectors. September 14, 2012 Dear AMM Member: Please see the attached Fire Code Frequently Asked Questions. This document was compiled by the Office of the Fire Commissioner at the AMM s request to help clarify

More information

Exit Routes, Emergency Action Plans, Fire Prevention Plans, and Fire Protection. OSHA Office of Training and Education 1

Exit Routes, Emergency Action Plans, Fire Prevention Plans, and Fire Protection. OSHA Office of Training and Education 1 Exit Routes, Emergency Action Plans, Fire Prevention Plans, and Fire Protection OSHA Office of Training and Education 1 Introduction Fires and explosions kill more than 200 and injure more than 5,000 workers

More information

Fire Sprinkler Incentive Act of 2003

Fire Sprinkler Incentive Act of 2003 A Tax Incentive For Life Safety Fire Sprinkler Incentive Act of 2003 Ad Hoc Committee Members American Fire Sprinkler Association Campus Firewatch Congressional Fire Services Institute International Association

More information

UL 300 Standard. RS 1021 (9/13) 2013 Nationwide Mutual Insurance Company Page 1 of 6 All Rights Reserved

UL 300 Standard. RS 1021 (9/13) 2013 Nationwide Mutual Insurance Company Page 1 of 6 All Rights Reserved Summary Fire test standard UL 300 has been a major factor in significant changes in how commercial cooking operations are protected from fire. This report looks at the background of UL 300 and changes

More information

Ontario Association of Fire Chiefs Position Paper Residential Fire Sprinklers

Ontario Association of Fire Chiefs Position Paper Residential Fire Sprinklers Ontario Association of Fire Chiefs Position Paper Residential Fire Sprinklers The Ontario Association of Fire Chiefs (OAFC) supports changes to the Ontario Building Code to require that all new residential

More information

Home Fire Sprinkler Facts vs. Myths

Home Fire Sprinkler Facts vs. Myths Home Fire Sprinkler Facts vs. Myths MYTH: Home fire sprinklers can malfunction and cause severe water damage to my home. They re more of a liability than a help! FACT: It is extremely rare for home fire

More information

General Safety & Health Standards Published by the Division of Building Safety In Cooperation with the Idaho Industrial Commission

General Safety & Health Standards Published by the Division of Building Safety In Cooperation with the Idaho Industrial Commission General Safety & Health Standards Published by the Division of Building Safety In Cooperation with the Idaho Industrial Commission Local Fire Alarm 064. FIRE ALARM SYSTEMS 01. Scope 02. Definitions 03.

More information

OCFRD TENT STANDARD 6000. This Standard operates under the authority of Orange County, Florida Ordinance and State Statutes.

OCFRD TENT STANDARD 6000. This Standard operates under the authority of Orange County, Florida Ordinance and State Statutes. 1. Authority Orange County Fire Rescue Department Tents & Membrane Structures Office of The Fire Marshall - 109 E. Church Street, Lower Level - Orlando, Florida 32801-3319 Phone: 407-836-0004 Fax: 407-836-8310

More information

Use Of Residential Fire Sprinklers In New Housing Projects

Use Of Residential Fire Sprinklers In New Housing Projects STAFF REPORT ACTION REQUIRED Use Of Residential Fire Sprinklers In New Housing Projects Date: May 22, 2007 To: From: Wards: Reference Number: Community Development and Recreation Toronto Fire Services

More information

CHAPTER 9 FIRE PROTECTION SYSTEMS

CHAPTER 9 FIRE PROTECTION SYSTEMS CHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 GENERAL 901.1 Scope. Provisions of this chapter shall govern the application, design, installation, testing and maintenance of automatic sprinklers, standpipes

More information

A study of the nature of fire risks in tall buildings

A study of the nature of fire risks in tall buildings A study of the nature of fire risks in tall buildings David Charters and Carl Sherwood BRE Global 12 th March 2013 Part of the BRE Trust Overview 1. Introduction 2. Challenges of tall buildings 3. Analysis

More information

Equipment Breakdown. The extended property coverage you need for the equipment you rely on.

Equipment Breakdown. The extended property coverage you need for the equipment you rely on. Equipment Breakdown The extended property coverage you need for the equipment you rely on. Equipment Breakdown When it comes to protecting the equipment and machinery you need to keep your business operating

More information

NFPA Fire Fighter II

NFPA Fire Fighter II State of Oregon Department of Public Safety Standards and Training NFPA Fire Fighter II Task Book Task Book Assigned To: Name DPSST Fire Service # Department Name Date Initiated Signature of Department

More information

Fire-Rated Glass and Glazing START

Fire-Rated Glass and Glazing START Fire-Rated Glass and Glazing START www.pilkington.com/fire Fire-Rated Glass and Glazing Pilkington Fire Protection Glass North America 946 Kane Street, Suite A Toledo, OH 43612 Provider Number: J200 Course

More information

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable

More information

SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS

SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS I. APPLICATION AND DEFINITIONS 1.01 Authorization for Standards 1.02 Application of Standards 1.03 Definitions

More information

Electrical Classification

Electrical Classification Electrical Classification Using NFPA 70 and NFPA 499 to Classify Hazardous Locations Electrical classifications are established in accordance with the National Electrical Code, NFPA 70, also referred to

More information

HOME FIRE PROTECTION SYSTEMS SPRINKLER SYSTEMS IN INDUSTRY

HOME FIRE PROTECTION SYSTEMS SPRINKLER SYSTEMS IN INDUSTRY HOME FIRE PROTECTION RESIDENTIAL FIRE SPRINKLER SYSTEMS SPRINKLER SYSTEMS IN INDUSTRY Sh Schools, office buildings, factories, and other commercial buildings have benefited from fire protection sprinkler

More information

Schedule A. Residential and Seasonal Dwellings. for estimating value of construction in the Township of North Kawartha

Schedule A. Residential and Seasonal Dwellings. for estimating value of construction in the Township of North Kawartha Schedule A Classification of buildings used for estimating value of construction in the Township of North Kawartha Estimated cost of Construction per square foot Residential and Seasonal Dwellings Single

More information

Fraternity and Sorority House Fire Safety

Fraternity and Sorority House Fire Safety Fraternity and Sorority House Fire Safety Buddy Dewar Director of Regional Operations National Fire Sprinkler Association 850-222-2070 How To Manage Greek Housing Fire Sprinkler Retrofit Brief Overview.

More information

Decree of the Ministry of the Environment. on fire safety of garages

Decree of the Ministry of the Environment. on fire safety of garages E4 THE NATIONAL BUILDING CODE OF FINLAND Fire safety of garages Guidelines 2005 Decree of the Ministry of the Environment on fire safety of garages Adopted in Helsinki, 22 March 2005 Pursuant to the Decision

More information

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression

More information

UNWANTED FIRE ALARMS. April 2011. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471 www.nfpa.org

UNWANTED FIRE ALARMS. April 2011. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471 www.nfpa.org UNWANTED FIRE ALARMS April 2011 National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471 www.nfpa.org UNWANTED FIRE ALARMS April 2011 National Fire Protection Association, 1 Batterymarch

More information

The asbestos crisis Why Britain needs an eradication law

The asbestos crisis Why Britain needs an eradication law Why Britain needs an eradication law All-Party Parliamentary Group on Occupational Safety and Health The All-Party Parliamentary Group on Occupational Safety and Health believes that the time has come

More information

FIRE LOSS STATISTICAL CONSIDERATIONS IN RELATING FAILURE AND BUILDING DAMAGE TO THE BUILDING CODE OBJECTIVES

FIRE LOSS STATISTICAL CONSIDERATIONS IN RELATING FAILURE AND BUILDING DAMAGE TO THE BUILDING CODE OBJECTIVES FIRE LOSS STATISTICAL CONSIDERATIONS IN RELATING FAILURE AND BUILDING DAMAGE TO THE BUILDING CODE OBJECTIVES P.L. Senez*, K.D. Calder, Hsing H (Isabella) Li Sereca Fire Consulting Ltd., Canada INTRODUCTION

More information

The asbestos crisis. Why Britain needs an eradication Law. Background. Levels of mortality

The asbestos crisis. Why Britain needs an eradication Law. Background. Levels of mortality The asbestos crisis. Why Britain needs an eradication Law. The All-Party Parliamentary Group on Occupational Safety and Health believes that the time has come to put in place regulations requiring the

More information

Name Of Occupancy Date. Yes No Describe

Name Of Occupancy Date. Yes No Describe FIRE PREVENTION INSPECTION CHECKLIST For Class A Occupancy (For Assembly Buildings, Bars, Restaurants, Gyms, Churches, Arenas, Theatres or wherever people gather) Name Of Occupancy Date Physical Address

More information

Important Ontario Fire Code Information for Building Owners in the City of Windsor

Important Ontario Fire Code Information for Building Owners in the City of Windsor Important Ontario Fire Code Information for Building Owners in the City of Windsor This information is intended to be used a reference only. For a complete listing consult the Ontario Fire Code or contact

More information

Combustible Dust - Things that go Boom. W. Jon Wallace, CSP, MBA Workplace Group, LLC O: 919.933.5548 E: jwallace@workplacegroup.

Combustible Dust - Things that go Boom. W. Jon Wallace, CSP, MBA Workplace Group, LLC O: 919.933.5548 E: jwallace@workplacegroup. Combustible Dust - Things that go Boom W. Jon Wallace, CSP, MBA Workplace Group, LLC O: 919.933.5548 E: jwallace@workplacegroup.net Presentation Objectives After attending this presentation you will: Learn

More information

Appendix B Forms for Inspection, Testing, and Maintenance

Appendix B Forms for Inspection, Testing, and Maintenance Appendix B Forms for Inspection, Testing, and Maintenance This appendix is not a part of the requirements of this NFPA document but is included for informational purposes only. Forms need to be complete

More information

LCT 1025 (08/08) Copyright 2008 Harleysville Mutual Insurance Company Page 1 of 5 All rights reserved

LCT 1025 (08/08) Copyright 2008 Harleysville Mutual Insurance Company Page 1 of 5 All rights reserved Bonding and Grounding of Flammable Liquid Containers Provided by Harleysville s Risk Control Department 800-523-6344 ext 8100 www.harleysvillegroup.com/riskcontrol Summary The movement of volatile liquids,

More information

TEXT (CO Detection Commercial Buildings Final) Part 1228 of Title 19 NYCRR is amended by adding a new section 1228.4, to read as follows:

TEXT (CO Detection Commercial Buildings Final) Part 1228 of Title 19 NYCRR is amended by adding a new section 1228.4, to read as follows: TEXT (CO Detection Commercial Buildings Final) Part 1228 of Title 19 NYCRR is amended by adding a new section 1228.4, to read as follows: Section 1228.4. Carbon Monoxide Detection in Commercial Buildings

More information

FIRE PREVENTION PLAN

FIRE PREVENTION PLAN FIRE PREVENTION PLAN 1 FIRE PREVENTION PLAN OSHA s Fire Prevention Plan regulation, found at 29 CFR 1910.38(b) and 29 CFR 1926.24, requires Northern Clearing, Inc. to have a written fire prevention plan

More information

Agenda Item # Page f BILL 141 -THE HOME FIRE SPRINKLER ACT, 2004 RECOMMENDATION

Agenda Item # Page f BILL 141 -THE HOME FIRE SPRINKLER ACT, 2004 RECOMMENDATION il Agenda Item # Page f mm 3 3 1 I I CHAIR AND MEMBERS II To COMMUNITY AND PROTECTIVE SERVICES COMMITTEE SEPTEMBER 12,25 FROM JOHNKOBARDA FIRE CHIEF AND DIRECTOR OF PARAMEDIC SERVICES /ISUBJECT I BILL

More information

EPA RISK MANAGEMENT PROGRAM RULE TO IMPACT DISTRIBUTORS AND MANUFACTURERS

EPA RISK MANAGEMENT PROGRAM RULE TO IMPACT DISTRIBUTORS AND MANUFACTURERS EPA RISK MANAGEMENT PROGRAM RULE TO IMPACT DISTRIBUTORS AND MANUFACTURERS I. Introduction Under an EPA rule designed to prevent chemical accidents, certain distributors, formulators and manufacturers of

More information

St. John s University

St. John s University St. John s University Fire Safety Plan Founder s Village Townhouses Page 1 St. John s University Fire Safety Plan Part 1-Building Information Section Founder s Village Townhouses 8000 Utopia Parkway Jamaica

More information

Smoke Alarm Performance in Residential Structure Fires

Smoke Alarm Performance in Residential Structure Fires U.S. Fire Administration TOPICAL FIRE RESEARCH SERIES Volume 1, Issue 15 March 2001 (Rev. December 2001) Smoke Alarm Performance in Residential Structure Fires FINDINGS S Smoke alarms save lives and money.

More information

18-1. 18.2.1 Retail or Wholesale In conformity with the provisions of sub-section 18.3. 18.2.2 Art Gallery, Museum or Library In conformity with the

18-1. 18.2.1 Retail or Wholesale In conformity with the provisions of sub-section 18.3. 18.2.2 Art Gallery, Museum or Library In conformity with the 18-1 SECTION 18 - ZONE C-3: SETTLEMENT COMMERCIAL 18.1 Within a Zone C-3, no land shall be used and no building or structure shall be erected or used except for one or more of the listed in Column 1 below.

More information

Residential Sprinkler Systems

Residential Sprinkler Systems Residential Sprinkler Systems Sprinkler Systems in Industry Residential Sprinkler Myths and Facts Have you ever heard someone say "If one sprinkler head goes off, they all go off." or "The sprinklers may

More information

COMMON MYTHS ABOUT FIRE SPRINKLER PROTECTION

COMMON MYTHS ABOUT FIRE SPRINKLER PROTECTION "Water damage from a sprinkler system will be more extensive than fire damage." Water damage from a sprinkler system will be much less severe than the damage caused by water from firefighting hose-lines

More information

EACH CLASS of fire A, B, C, or D has a different source. Some

EACH CLASS of fire A, B, C, or D has a different source. Some Classes of Fires and Types of Extinguishers EACH CLASS of fire A, B, C, or D has a different source. Some principles apply to putting out all fires. However, certain procedures and products are used only

More information

HOME FIREFA 43 PROTECTION

HOME FIREFA 43 PROTECTION HOME FIREFA 43 Revised April 1997 (Supersedes FA 43 dated July, 1986 PROTECTION Residential Fire Sprinkler Systems Federal Emergency Management Agency U.S. Fire Administration This document was scanned

More information

AON SPRINKLER CERTIFICATION

AON SPRINKLER CERTIFICATION Form 1 Application for Approval of Basic Design Parameters for Automatic Sprinkler System Installations 1. Name of Protected Premises Site Name Address 2. Work to be Carried Out New System Extension or

More information

FOR CERTIFICATION AS PRESCRIBED BY THE STATE FIRE PREVENTION COMMISSION ON NOVEMBER 11, 2009 IN ACCORDANCE WITH THE STATE FIRE PREVENTION REGULATIONS

FOR CERTIFICATION AS PRESCRIBED BY THE STATE FIRE PREVENTION COMMISSION ON NOVEMBER 11, 2009 IN ACCORDANCE WITH THE STATE FIRE PREVENTION REGULATIONS EXAMINATION REQUIREMENTS FOR FIRE SUPPRESSION SYSTEM CERTIFICATION AS PRESCRIBED BY THE STATE FIRE PREVENTION COMMISSION ON NOVEMBER 11, 2009 IN ACCORDANCE WITH THE STATE FIRE PREVENTION REGULATIONS REGULATION

More information

Fire Safety Risk Assessment Checklist for Residential Care Premises

Fire Safety Risk Assessment Checklist for Residential Care Premises Checklist for Residential Care Premises Name of Premises: Address of Premises: Name of Responsible Person: What area / location does the assessment cover? Does the assessment cover the whole site YES or

More information

High Pressure Water Mist Systems: Alternative Solution For Critical Civil Applications

High Pressure Water Mist Systems: Alternative Solution For Critical Civil Applications International Water Mist Conference, London, United Kingdom,23-24 September, 2009 High Pressure Water Mist Systems: Alternative Solution For Critical Civil Applications Fire Fighting In Civil Applications

More information

Attached (townhouses) SC P P 4.2.3(A)1 Duplex SE SE P Accessory Dwelling Unit (ADU) to a primary residence SC SC SC SC P 4.2.3(A)2

Attached (townhouses) SC P P 4.2.3(A)1 Duplex SE SE P Accessory Dwelling Unit (ADU) to a primary residence SC SC SC SC P 4.2.3(A)2 TABLE 1: ERMITTED USES BY ZONING DISTRICT Land Use : ermitted C: ermitted, subject to conditions SE: Special Exception SC: Special Exception, subject to conditions Zoning Districts NC 1,2,3,4 R I CMU GC

More information

LIFE SAFETY UPDATE. FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc.

LIFE SAFETY UPDATE. FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc. LIFE SAFETY UPDATE FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc. The purpose of this update is as follows: Remind all state

More information

Inspection, Testing and Maintenance

Inspection, Testing and Maintenance Page 18 ABOUT CODE CORNER CCFS would like to remind you to check with your local Authority Having Jurisdiction (AHJ) for questions and opinions concerning your local Fire and Building Codes. The information

More information