CHAPTER 29 PLUMBING SYSTEMS

Size: px
Start display at page:

Download "CHAPTER 29 PLUMBING SYSTEMS"

Transcription

1 CHAPTER 29 SYSTEMS Note: The amendments to Chapter 29 are different than the 2009 Seattle Building Code and are not marked with margin bars or arrows. SECTION 2901 GENERAL [P] Scope. The provisions of this chapter and the ((International)) Uniform Plumbing Code shall govern the erection, installation, alteration, repairs, relocation, replacement, addition to, use or maintenance of plumbing equipment and systems. Toilet and bathing rooms shall be constructed in accordance with Section Plumbing systems and equipment shall be constructed, installed and maintained in accordance with the ((International)) Uniform Plumbing Code. Private sewage disposal systems shall conform to the International Private Sewage Disposal Code Health codes. In food preparation, serving and related storage areas, additional fixture requirements may be dictated by state and local health codes. SECTION 2902 MINIMUM FACILITIES [P] Minimum number of fixtures. Plumbing fixtures shall be provided for the type of occupancy and in the minimum number shown in Table Types of occupancies not shown in Table shall be ((considered)) determined individually by the building official based on the occupancy which most nearly resembles the proposed occupancy. The number of occupants shall be determined by this code. Occupancy classification shall be determined in accordance with Chapter 3. Plumbing fixtures need not be provided for unoccupied buildings or facilities. [P] Fixture calculations. To determine the occupant load of each sex, the total occupant load shall be divided in half. To determine the required number of fixtures, the fixture ratio or ratios for each fixture type shall be applied to the occupant load of each sex in accordance with Table Fractional numbers resulting from applying the fixture ratios of Table shall be rounded up to the next whole number. For calculations involving multiple occupancies, such fractional numbers for each occupancy shall first be summed and then rounded up to the next whole number. Exception: The total occupant load shall not be required to be divided in half where approved statistical data indicate a distribution of the sexes of other than 50 percent of each sex. No. CLASSIFICATION OCCUPANCY DESCRIPTION 1 Assembly (continued) [P] TABLE MINIMUM NUMBER OF REQUIRED FIXTURES a (See Sections and ) Theaters and other A-1 d buildings for the performing arts and motion pictures Nightclubs, bars, taverns, dance halls and buildings for similar A-2 d purposes A-3 d Restaurants, banquet halls and food courts Auditoriums without permanent seating, art galleries, exhibition halls, museums, lecture halls, libraries, arcades and gymnasiums Passenger terminals and transportation facilities Places of worship and other religious services WATER CLOSETS (((URINALS SEE SECTION OF THE (continued) LAVATORIES MALE FEMALE MALE FEMALE BATHTUBS/ SHOWERS ((DRINKING FOUNTAINS e, f (SEE SECTION OF THE ((OTHER)) (( 500)) (( 500)) (( 500)) (( 500)) (( 1,000)) (( 1,000)) 2012 SEATTLE BUILDING CODE 603

2 No. CLASSIFICATION OCCUPANCY DESCRIPTION 1 Assembly A-4 A-5 2 Business B 3 Educational E 4 Factory and industrial 5 Institutional F-1 and F-2 [P] TABLE (continued) MINIMUM NUMBER OF REQUIRED FIXTURES a (See Sections and ) Coliseums, arenas, skating rinks, pools and tennis courts for indoor sporting events and activities Stadiums, amusement parks, bleachers and grandstands for outdoor sporting events and activities WATER CLOSETS (((URINALS SEE SECTION OF THE LAVATORIES MALE FEMALE MALE FEMALE 75 for 1,500 and 1 per 120 for 1, for 1,500 and 1 per 120 for 1, for 1,520 and 1 per 60 for 1, for 1,520 and 1 per 60 for 1,520 Buildings for the transaction of business, professional services, other services involving 25 for 50 and 50 for the merchandise, remainder 50 office buildings, banks, light industrial and similar uses Educational facilities Structures in which occupants are engaged in work fabricating, assembly or processing of products or materials (continued) BATHTUBS/ SHOWERS ((DRINKING FOUNTAINS e, f (SEE SECTION OF THE ((OTHER)) SEATTLE BUILDING CODE for the first 80 and 80 for the remainder ((50)) (( 1,000)) (( 1,000)) (( 100)) (( 100)) See Section ((411)) of the ((International)) Uniform Plumbing Code (( 400)) I-1 Residential care (( 100)) Hospitals, ambulatory nursing home care recipient b room c room c 15 (( 100)) sink g )) (( 100)) (( )) I-2 Employees, other than residential care b Visitors, other than residential care (( 500)) (( )) I-3 Prisons b cell cell 15 (( 100)) I-3 I-4 Reformatories, detention centers and correctional (( 100)) centers b Employees b (( 100)) (( )) Adult day care and (( 100)) child day care

3 No. CLASSIFICATION OCCUPANCY DESCRIPTION 6 Mercantile M 7 Residential 8 Storage R-1 R-2 [P] TABLE continued MINIMUM NUMBER OF REQUIRED FIXTURES a (See Sections and ) Retail stores, service stations, shops, salesrooms, markets and shopping centers Hotels, motels, boarding houses (transient) Dormitories, fraternities, sororities and boarding houses (not transient) R-2 Apartment house R-3 R-3 ((R-4)) S-1 S-2 One- and two-family dwellings Congregate living facilities with 16 or fewer persons ((Congregate living facilities with 16 or fewer persons)) Structures for the storage of goods, warehouses, storehouses and freight depots, low and moderate hazard WATER CLOSETS (((URINALS SEE SECTION OF THE LAVATORIES MALE FEMALE MALE FEMALE BATHTUBS OR SHOWERS ((DRINKING FOUNTAINS e, f (SEE SECTION OF THE (( 1,000)) sleeping sleeping sleeping ((OTHER)) sink g )) (( )) (( 100)) dwelling dwelling dwelling dwelling dwelling dwelling a. The fixtures shown are based on one fixture being the minimum required for the number of persons indicated or any fraction of the number of persons indicated. The number of occupants shall be determined by this code. b. Toilet facilities for employees shall be separate from facilities for inmates or care recipients. c. A single-occupant toilet room with one water closet and one lavatory serving not more than two adjacent patient sleeping s shall be permitted where such room is provided with direct access from each patient sleeping and with provisions for privacy. d. The occupant load for seasonal outdoor seating and entertainment areas shall be included when determining the minimum number of facilities required. ((e.the minimum number of required drinking fountains shall comply with Table and Chapter 11. f. Drinking fountains are not required for an occupant load of 15 or fewer. g. For business and mercantile occupancies with an occupant load of 15 or fewer, service sinks shall not be required.)) (( )) (( )) ((1 kitchen sink per dwelling ; 1 automatic clothes washer connection per 20 dwelling s)) ((1 kitchen sink per dwelling ; 1 automatic clothes washer connection per dwelling )) (( 100)) (( 10)) (( 10)) (( 8)) (( 100)) See Section ((411)) of the ((International)) Uniform Plumbing Code (( 1,000)) 2012 SEATTLE BUILDING CODE 605

4 Private offices. Fixtures only accessible to private offices shall not be counted to determine compliance with this section Urinals. Where urinals are provided, one water closet less than the number specified may be provided for each urinal installed, except the number of water closets in such cases shall not be reduced to less than one quarter (25 percent) of the minimum specified. For men's facilities serving 26 or more persons, not less than one urinal shall be provided. [P] Family or assisted-use toilet and bath fixtures. Fixtures located within family or assisted-use toilet and bathing rooms required by Section are permitted to be included in the number of required fixtures for either the male or female occupants in assembly and mercantile occupancies. [P] Separate facilities. Where plumbing fixtures are required, separate facilities shall be provided for each sex. Exceptions: 1. Separate facilities shall not be required for dwelling s and sleeping s. 2. Separate facilities shall not be required in structures or tenant spaces with a total occupant load, including both employees and customers, of 15 or less. 3. Separate facilities shall not be required in mercantile occupancies in which the maximum occupant load is 100 or less. [P] Family or assisted-use toilet facilities serving as separate facilities. Where a building or tenant space requires a separate toilet facility for each sex and each toilet facility is required to have only one water closet, two family/assisted-use toilet facilities shall be permitted to serve as the required separate facilities. Family or assisted-use toilet facilities shall not be required to be identified for exclusive use by either sex as required by Section [P] Employee and public toilet facilities. Customers, patrons and visitors shall be provided with public toilet facilities in structures and tenant spaces intended for public utilization. The number of plumbing fixtures located within the required toilet facilities shall be provided in accordance with Section for all users. Employees shall be provided with toilet facilities in all occupancies. Employee toilet facilities shall either be separate or combined employee and public toilet facilities. Exception: Public toilet facilities shall not be required in open or enclosed parking garages. Toilet facilities shall not be required in parking garages where there are no parking attendants. [P] Access. The route to the public toilet facilities required by Section shall not pass through kitchens, food preparation areas, unpackaged food storage areas, storage rooms or closets. Access to the required facilities shall be from within the building or from the exterior of the building. Access to toilets serving multiple tenants shall be through a common use area and not through an area controlled by a tenant. All routes shall comply with the accessibility requirements of this code. The public shall have access to the required toilet facilities at all times that the building is occupied. For other requirements for plumbing facilities, see Chapter Food preparation areas. Toilet rooms shall not open directly into a room used for the preparation of food for service to the public or residents of Group R-2 boarding homes and residential treatment facilities licensed by Washington state. [P] Location of toilet facilities in occupancies other than malls. In occupancies other than covered and open mall buildings, the required public and employee toilet facilities shall be located not more than one story above or below the space required to be provided with toilet facilities, or conveniently in a building adjacent thereto on the same property, and the path of travel to such facilities shall not exceed a distance of 500 feet (152 m). Exception: The location and maximum travel distances to required employee facilities in factory and industrial occupancies are permitted to exceed that required by this section, provided that the location and maximum travel distance are approved. [P] Location of toilet facilities in malls. In covered and open mall buildings, the required public and employee toilet facilities shall be located not more than one story above or below the space required to be provided with toilet facilities, and the path of travel to such facilities shall not exceed a distance of 300 feet ( mm). In mall buildings, the required facilities shall be based on total square footage (m 2 ) within a covered mall building or within the perimeter line of an open mall building, and facilities shall be installed in each individual store or in a central toilet area located in accordance with this section. The maximum travel distance to central toilet facilities in mall buildings shall be measured from the main entrance of any store or tenant space. In mall buildings, where employees toilet facilities are not provided in the individual store, the maximum travel distance shall be measured from the employees work area of the store or tenant space. [P] Pay facilities. Where pay facilities are installed, such facilities shall be in excess of the required minimum facilities. Required facilities shall be free of charge. [P] Door locking. Where a toilet room is provided for the use of multiple occupants, the egress door for the room shall not be lockable from the inside of the room. This section does not apply to family or assisted-use toilet rooms. [P] Signage. Required public facilities shall be designated by a legible sign for each sex. Signs shall be readily visible and located near the entrance to each toilet facility. Signs for accessible toilet facilities shall comply with Section [P] Directional signage. Directional signage indicating the route to the public facilities shall be ((posted in accordance with Section Such signage shall be)) SEATTLE BUILDING CODE

5 * located in a corridor or aisle, at the entrance to the facilities for customers and visitors. [P] Drinking fountain location. Drinking fountains shall not be required to be located in individual tenant spaces provided that public drinking fountains are located within a travel distance of 500 feet of the most remote location in the tenant space and not more than one story above or below the tenant space. Where the tenant space is in a covered or open mall, such distance shall not exceed 300 feet. Drinking fountains shall be located on an accessible route. Drinking fountains shall not be located in toilet rooms Drinking fountain number. Occupant loads over 30 shall have one drinking fountain for 150 occupants, then one for each additional 500 occupants. Exceptions: 1. Sporting facilities with concessions serving drinks shall have one drinking fountain for each 1,000 occupants. 2. A drinking fountain need not be provided in drinking or dining establishments Multistory buildings. Drinking fountains shall be provided on each floor having more than 30 occupants in schools, dormitories, auditoriums, theaters, offices and public buildings Penal institutions. Penal institutions shall have one drinking fountain on each cell block floor and one on each exercise floor Dwelling s. Dwelling s shall be provided with a kitchen sink Water closet space requirements. The water closet stool in all occupancies shall be located in a clear space not less than 30 inches (762 mm) in width, with a clear space in front of the stool of not less than 24 inches (610 mm) Water. Each required sink, lavatory, bathtub and shower stall shall be equipped with hot and cold running water necessary for its normal operation SEATTLE BUILDING CODE 607

6 SEATTLE BUILDING CODE

CHAPTER 29 PLUMBING SYSTEMS. [P] TABLE 2902.1 MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES a (See Sections 2902.2 and 2902.3) 1 per 40 for the

CHAPTER 29 PLUMBING SYSTEMS. [P] TABLE 2902.1 MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES a (See Sections 2902.2 and 2902.3) 1 per 40 for the CHAPTER 29 PLUMBING SYSTEMS > SECTION 2901 GENERAL [P] 2901.1 Scope. The provisions of this chapter and the Phoenix Plumbing Code shall govern the erection, installation, alteration, repairs, relocation,

More information

Chapter 16.130 PLUMBING CODE

Chapter 16.130 PLUMBING CODE DISSCUSSION ITEM 3 ATTACHMENT E Chapter 16.130 PLUMBING CODE 16.130.100 Plumbing Code - Incorporation. There is incorporated by reference, for purpose of adopting regulations, provisions, conditions, terms,

More information

LOCAL LAWS OF THE CITY OF NEW YORK FOR THE YEAR 2013. No. 110

LOCAL LAWS OF THE CITY OF NEW YORK FOR THE YEAR 2013. No. 110 LOCAL LAWS OF THE CITY OF NEW YORK FOR THE YEAR 2013 No. 110 Introduced by Council Members Mendez, Brewer, Chin, James, Lander, Richards, Rose, Rodriguez, Arroyo, and Mark-Viverito. A LOCAL LAW To amend

More information

DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION CODE

DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION CODE DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION CODE Filed with the Secretary of State on September 19, 2013 These rules take effect January 17, 2014 (By authority conferred

More information

How To Calculate Fixture Counts For A Building

How To Calculate Fixture Counts For A Building Calculating Plumbing Fixture Counts By Ronald L. Geren, AIA, CSI, CCS, CCCA, SCIP In 2005, New York City s legislature unanimously passed the Women s Restroom Equity Bill, which essentially requires that

More information

ACCESSIBILITY CHAPTER 11

ACCESSIBILITY CHAPTER 11 CHAPTER 11 ACCESSIBILITY SECTION 1101 GENERAL 1101.1 Scope. The provisions of this chapter shall control the design and construction of facilities for accessibility to physically disabled persons. 1101.2

More information

Revised: Previously Issued As: P/BC 2011-095 PLUMBING FIXTURES

Revised: Previously Issued As: P/BC 2011-095 PLUMBING FIXTURES INFORMATION BULLETIN / PUBLIC - BUILDING CODE REFERENCE NO.: LABC Sec. 2901 Effective: 01-01-2014 DOCUMENT NO. P/BC 2014-095 Revised: Previously Issued As: P/BC 2011-095 PLUMBING FIXTURES Section 2901

More information

Chapter 3: Use and Occupancy Classification

Chapter 3: Use and Occupancy Classification Chapter 3: Use and Occupancy Classification General Comments Chapter 3 provides for the classification of buildings, structures and parts thereof based on the purpose or purposes for which they are used.

More information

PLUMBING FIXTURES GUIDELINES

PLUMBING FIXTURES GUIDELINES COUNTY OF LOS ANGELES DEPARTMENT OF PUBLIC WORKS BUILDING & SAFETY DIVISION 2902 BUILDING CODE MANUAL Article 3 12-20-02 Page 1 of 6 PLUMBING FIXTURES GUIDELINES The following policy establishes guidelines

More information

CHAPTER 8. 2. Facilities for types of occupancies not shown on this table will be determined by the Administrative Authority.

CHAPTER 8. 2. Facilities for types of occupancies not shown on this table will be determined by the Administrative Authority. CHAPTER 8 800 PLUMBING FIXTURES 801 CONNECTIONS TO PLUMBING SYSTEM REQUIRED All plumbing fixtures and drains used to receive or discharge liquid wastes or sewage shall be connected to the drainage system

More information

BUILDING CODE MANUAL COUNTY OF LOS ANGELES DEPARTMENT OF PUBLIC WORKS BUILDING AND SAFETY DIVISION

BUILDING CODE MANUAL COUNTY OF LOS ANGELES DEPARTMENT OF PUBLIC WORKS BUILDING AND SAFETY DIVISION BUILDING CODE MANUAL COUNTY OF LOS ANGELES DEPARTMENT OF PUBLIC WORKS BUILDING AND SAFETY DIVISION Based on the 2014 LACBC #135 2902 Article 1 01-26-15 Page 1 of 6 MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES

More information

CHAPTER 9 FIRE PROTECTION SYSTEMS

CHAPTER 9 FIRE PROTECTION SYSTEMS CHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 GENERAL 901.1 Scope. Provisions of this chapter shall govern the application, design, installation, testing and maintenance of automatic sprinklers, standpipes

More information

(1) (a) through (1) (e) (iv) Remain the same.

(1) (a) through (1) (e) (iv) Remain the same. 24.301.301 CORPORO BY REFERECE OF UFORM PLUMBG CODE (1) he Department of Labor and ndustry adopts and incorporates by reference the Uniform Plumbing Code, 2006 2009 Edition, referred to as the Uniform

More information

City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov

City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov BUILDING CODE REQUIREMENTS FOR CHILD DAY CARE The purpose of this document is to provide the user with a basic level

More information

Table 200.5.10.1 PARKING SPACE RATES AND PARKING SPACE OCCUPANCY

Table 200.5.10.1 PARKING SPACE RATES AND PARKING SPACE OCCUPANCY Table 200.5.10.1 PARKING SPACE RATES AND PARKING SPACE OCCUPANCY. AM = 6 a.m. to Noon. Adult Education School Adult Entertainment (A) in Policy Area 1 (PA1), Policy Area 2 (PA2) Policy Area 3 (PA3) at

More information

2010 ADA Standards for Accessible Design. Department of Justice

2010 ADA Standards for Accessible Design. Department of Justice 2010 ADA Standards for Accessible Design Department of Justice September 15, 2010 Reproduction of this document is encouraged. This publication may be viewed or downloaded from the ADA website (www.ada.gov).

More information

ACCESSIBILITY CHAPTER 11

ACCESSIBILITY CHAPTER 11 CHAPTER 11 ACCESSIBILITY SECTION BC 1101 GENERAL 1101.1 Scope. The provisions of this chapter and Appendices E, N and P shall control the design and construction of facilities for accessibility to persons

More information

New York City Department of Buildings

New York City Department of Buildings The New NYC Building Code Chapter 11 Accessibility New York City Department of Buildings Technical Affairs Keith Wen, R.A. Copyright Materials This presentation is protected by US and International Copyright

More information

Schedule B to By-law 33-2009 Part A Fees Payable for Permits

Schedule B to By-law 33-2009 Part A Fees Payable for Permits Floor Area Calculation Floor area shall: Part A Fees Payable for Permits (Effective January 1, 2015) a) be calculated by measuring to the outer face of exterior walls and to the centre of party walls or

More information

Section 6. Off-street Bicycle Space Regulations

Section 6. Off-street Bicycle Space Regulations Section 6 Off-street Bicycle Space Regulations 6.1 Number of Bicycle Spaces 6.1.1 General Requirements Unless otherwise provided in Schedule C or a CD-1 By-law, in all districts, the number of spaces required

More information

Schedule B to By-law 33-2009

Schedule B to By-law 33-2009 Amended by By-law 8-2016 Note: This consolidation is prepared for convenience only. For accurate reference the original by-laws should be reviewed. Floor Area Calculation Floor area shall: Schedule B to

More information

Commercial Fee estimate The Building department will provide the actual fees at the time the permit is issued.

Commercial Fee estimate The Building department will provide the actual fees at the time the permit is issued. 1. Determine the occupancy, type of construction, and floor area (square footage) Commercial Fee estimate The Building department will provide the actual fees at the time the permit is issued. 2. Determine

More information

VENTILATION CHAPTER 4

VENTILATION CHAPTER 4 CHAPTER 4 VENTILATION SECTION 401 GENERAL 401.1 Scope. This chapter shall govern the ventilation of spaces within a building intended to be occupied. This chapter does not govern the requirements for smoke

More information

SECTION 903 AUTOMATIC SPRINKLER SYSTEMS

SECTION 903 AUTOMATIC SPRINKLER SYSTEMS Page 25 ABOUT CODE CORNER CCFS would like to remind you to check with your local Authority Having Jurisdiction (AHJ) for questions and opinions concerning your local Fire and Building Codes. The information

More information

R-40 Single-Family Residential

R-40 Single-Family Residential October 7, 2013 R-40 Single-Family Residential Description: This low-density district allows single-family structures on lots of at least 40,000 square feet (0.92 acres). Properties zoned R-40 are typically

More information

Attached (townhouses) SC P P 4.2.3(A)1 Duplex SE SE P Accessory Dwelling Unit (ADU) to a primary residence SC SC SC SC P 4.2.3(A)2

Attached (townhouses) SC P P 4.2.3(A)1 Duplex SE SE P Accessory Dwelling Unit (ADU) to a primary residence SC SC SC SC P 4.2.3(A)2 TABLE 1: ERMITTED USES BY ZONING DISTRICT Land Use : ermitted C: ermitted, subject to conditions SE: Special Exception SC: Special Exception, subject to conditions Zoning Districts NC 1,2,3,4 R I CMU GC

More information

The intent of this chapter in establishing the R-G Residential General District is as follows:

The intent of this chapter in establishing the R-G Residential General District is as follows: Atlanta, Georgia, Code of Ordinances >> PART III - CODE OF ORDINANCES LAND DEVELOPMENT CODE >> Part 16 - ZONING >> CHAPTER 8. - R-G RESIDENTIAL GENERAL DISTRICT REGULATIONS >> CHAPTER 8. - R-G RESIDENTIAL

More information

2012 Changes of the International Building Code Compared to the National Fire Protection Association- 101

2012 Changes of the International Building Code Compared to the National Fire Protection Association- 101 2012 Changes of the International Building Code Compared to the National Fire Protection Association- 101 For the Florida Building Commission And the Fire Code Advisory Council Introduction The scope of

More information

SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES (Adopted by the State of Oregon)

SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES (Adopted by the State of Oregon) SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES (Adopted by the State of Oregon) SECTION SR101 GENERAL SR101.1 General. Group SR occupancies shall comply with the provisions of this appendix

More information

R432. Health, Health Systems Improvement, Licensing. R432-5. Nursing Facility Construction. R432-5-1. Legal Authority. R432-5-2. Purpose.

R432. Health, Health Systems Improvement, Licensing. R432-5. Nursing Facility Construction. R432-5-1. Legal Authority. R432-5-2. Purpose. R432. Health, Health Systems Improvement, Licensing. R432-5. Nursing Facility Construction. R432-5-1. Legal Authority. This rule is promulgated pursuant to Title 26, Chapter 21. R432-5-2. Purpose. The

More information

ADA Scoping: New Construction

ADA Scoping: New Construction U. S. A CCESS B O A R D T E C H N I C A L G U I D E ADA Scoping: This guide provides an introduction to the scoping requirements that form the basis for the Department of Justice s 2010 ADA Standards and

More information

BY-LAW CONCERNING THE SANITATION AND MAINTENANCE OF DWELLING UNITS

BY-LAW CONCERNING THE SANITATION AND MAINTENANCE OF DWELLING UNITS CITY OF MONTRÉAL BY-LAW 03-096 BY-LAW CONCERNING THE SANITATION AND MAINTENANCE OF DWELLING UNITS As the municipal administration seeks to ensure that all Montrealers benefit from acceptable housing conditions;

More information

Chapter 20 Polk County Construction Code

Chapter 20 Polk County Construction Code Chapter 20 Polk County Construction Code 20.1 Purpose and Scope 20.2 Codes Adopted by Reference, and Amendments 20.3 Permits 20.4 Inspections and Investigations 20.5 Occupancy 20.6 Records 20.7 Debris

More information

TABLE 9.6.1 Lighting Power Densities Using the Space-by-Space Method(continued) TABLE 9.6.1 Lighting Power Densities Using the Space-by-Space Method

TABLE 9.6.1 Lighting Power Densities Using the Space-by-Space Method(continued) TABLE 9.6.1 Lighting Power Densities Using the Space-by-Space Method TABLE 9.6.1 Lighting Densities Using the -by- Method Atrium Common Types a First 40 ft in height Height above 40 ft Audience/Seating Area Permanent 0.03 per ft (height) 0.02 per ft (height) For auditorium

More information

2012 IBC & 2012 NFPA 101 Significant Means of Egress Changes. Questions. 1004.1 Design Occupant Load. 1005 - Means of Egress Capacity Determination

2012 IBC & 2012 NFPA 101 Significant Means of Egress Changes. Questions. 1004.1 Design Occupant Load. 1005 - Means of Egress Capacity Determination 2012 IBC & 2012 NFPA 101 Significant Means of Egress Changes Clay Aler, P.E. Principal caler@koffel.com Andrew M. Schneider, P.E. Senior Fire Protection Engineer aschneider@koffel.com Questions Submit

More information

General Safety & Health Standards Published by the Division of Building Safety In Cooperation with the Idaho Industrial Commission

General Safety & Health Standards Published by the Division of Building Safety In Cooperation with the Idaho Industrial Commission General Safety & Health Standards Published by the Division of Building Safety In Cooperation with the Idaho Industrial Commission Local Fire Alarm 064. FIRE ALARM SYSTEMS 01. Scope 02. Definitions 03.

More information

18-1. 18.2.1 Retail or Wholesale In conformity with the provisions of sub-section 18.3. 18.2.2 Art Gallery, Museum or Library In conformity with the

18-1. 18.2.1 Retail or Wholesale In conformity with the provisions of sub-section 18.3. 18.2.2 Art Gallery, Museum or Library In conformity with the 18-1 SECTION 18 - ZONE C-3: SETTLEMENT COMMERCIAL 18.1 Within a Zone C-3, no land shall be used and no building or structure shall be erected or used except for one or more of the listed in Column 1 below.

More information

KBC Chapter 34 : Applying the Kentucky Building Code to Existing and Historic Buildings

KBC Chapter 34 : Applying the Kentucky Building Code to Existing and Historic Buildings KBC Chapter 34 : Applying the Kentucky Building Code to Existing and Historic Buildings Presented by: Kentucky Department of Housing, Buildings, and Construction Kentucky Heritage Council Louisville Metro

More information

APPLICATION FOR NEW CONSTRUCTION

APPLICATION FOR NEW CONSTRUCTION CITY OF ELKINS 401 DAVIS AVE ELKINS WV 26241 Date Pd: Receipt #: Session #: PHIL ISNER BLDG INSPECTOR / CODE ENFORCEMENT OFFICER 304-636-1414 Ext 1431 APP. DATE APPLICATION FOR NEW CONSTRUCTION APPLICANT

More information

2016 BUILDING PERMIT FEES*

2016 BUILDING PERMIT FEES* 2016 PERMIT FEES* Fees are based on the cost of construction and shall be based on a value not less than the value determined using the Building Valuation Data Report published by ICC. Application Fee

More information

Occupancy Construction Egress

Occupancy Construction Egress GSD Guide to Building Code Basics Some Useful Things to Remember o c e a Occupancy Construction Egress Access Compiled and edited by: Mark Mulligan, Adjunct Associate Professor of Architecture, Felipe

More information

Indiana Building Rehabilitation Standard

Indiana Building Rehabilitation Standard Rule 8. Indiana Building Rehabilitation Standard 675 IAC 12-8-1 Definitions Sec. 1. The following definitions apply throughout this rule: (1) "Building code" means the Indiana Building Code under 675 IAC

More information

Common ADA Errors and Omissions in New Construction and Alterations

Common ADA Errors and Omissions in New Construction and Alterations U.S. Department of Justice Civil Rights Division Disability Rights Section Common ADA Errors and Omissions in New Construction and Alterations Introduction The ADA requires that new construction and alterations

More information

CITY OF TORONTO. BY-LAW No. 349-2008

CITY OF TORONTO. BY-LAW No. 349-2008 Authority: Licensing and Standards Committee Item 12.3, adopted as amended, by City of Toronto Council on April 28 and 29, 2008 Enacted by Council: April 29, 2008 CITY OF TORONTO BY-LAW No. 349-2008 To

More information

REGULATIONS for INSTALLATION, MAINTENANCE, and TESTING APPLICATION PACKET

REGULATIONS for INSTALLATION, MAINTENANCE, and TESTING APPLICATION PACKET REGULATIONS for INSTALLATION, MAINTENANCE, and TESTING FIRE SUPPRESSION SYSTEMS APPLICATION PACKET CITY OF NAPERVILLE 400 S. EAGLE STREET NAPERVILLE, Il 60540 PHONE: 630.420.6070 FAX: 630.420.6657 Fire

More information

BUILDING PERMIT SPECIFICATIONS

BUILDING PERMIT SPECIFICATIONS BUILDING PERMIT SPECIFICATIONS The below noted requirements are based upon La Plata County Building Code. These specifications are not intended as a complete set of requirements, but are intended to provide

More information

ARTICLE VIII SECTION 8.1 O-I OFFICE INSTITUTIONAL DISTRICT

ARTICLE VIII SECTION 8.1 O-I OFFICE INSTITUTIONAL DISTRICT ARTICLE VIII SECTION 8.1 O-I OFFICE INSTITUTIONAL DISTRICT 8.1.1. O-I DISTRICT SCOPE AND INTENT. Regulations in this section are the O-I district regulations. Article XIX should be consulted to determine

More information

SECTION XI OPINION OF PROBABLE COST

SECTION XI OPINION OF PROBABLE COST SECTION XI OPINION OF PROBABLE COST OPINION OF PROPABLE COSTS HARBOR ISLAND THE PAVILION 1) Provide a sprinkler system for the entire building. 8000 SF X $15/SF $120,000 2) Remove and replace existing

More information

VENTILATION CHAPTER 4

VENTILATION CHAPTER 4 CHAPTER 4 VENTILATION SECTION 1 GENERAL 1.1 Scope. This chapter shall govern the ventilation of spaces within a building intended to be occupied. This chapter does not govern the requirements for smoke

More information

*** THIS FILE INCLUDES ALL REGULATIONS ADOPTED AND PUBLISHED THROUGH THE *** *** NEW JERSEY REGISTER, VOL. 41, NO. 4, FEBRUARY 17, 2009 ***

*** THIS FILE INCLUDES ALL REGULATIONS ADOPTED AND PUBLISHED THROUGH THE *** *** NEW JERSEY REGISTER, VOL. 41, NO. 4, FEBRUARY 17, 2009 *** 5:23-7.1 Applicability The provisions of this subchapter shall apply to all buildings, including their associated sites and facilities, and portions thereof, unless exempted by this subchapter. This subchapter

More information

Florida Building Code 2004 SECTION 1009 STAIRWAYS AND HANDRAILS

Florida Building Code 2004 SECTION 1009 STAIRWAYS AND HANDRAILS Florida Building Code 2004 SECTION 1009 STAIRWAYS AND HANDRAILS 1009.1 Stairway width. The width of stairways shall be determined as specified in Section 1005.1, but such width shall not be less than 44

More information

Significant Changes to the 2013 California Building Code Chapter 11B accessibility standards

Significant Changes to the 2013 California Building Code Chapter 11B accessibility standards Significant Changes to the 2013 California Building Code Chapter 11B accessibility standards Last updated: 4/8/13 The Division of State Architect s (DSA) office has recently posted the Final Approved Express

More information

BUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS

BUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS DCD-0304 Identification # Rev. 9/08 County Date of Inspection NAME OF OPERATION BUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS ADDRESS TELEPHONE: CITY STATE ZIP BUILDING INSPECTORS CERTIFICATE

More information

The emergency provisions affect the following Building Code sections:

The emergency provisions affect the following Building Code sections: On August 1, 2012 new emergency chapter 11B code provisions became effective. Attached are copies of the emergency express terms and the applicable figures. The new requirements are underlined and deleted

More information

PLAN REVIEW AND APPROVAL FOR FOOD ESTABLISHMENTS PLUMBING REQUIREMENTS FOR FOOD ESTABLISHMENT PREMISES

PLAN REVIEW AND APPROVAL FOR FOOD ESTABLISHMENTS PLUMBING REQUIREMENTS FOR FOOD ESTABLISHMENT PREMISES PLAN REVIEW AND APPROVAL FOR FOOD ESTABLISHMENTS PLUMBING REQUIREMENTS FOR FOOD ESTABLISHMENT PREMISES Health Systems Protection Rev. 07/2006 35-05-20/06/07/18 OFFICE OF FOOD PROTECTION 417 FEDERAL ST

More information

American Academy of Physical Medicine and Rehabilitation Site Survey Report

American Academy of Physical Medicine and Rehabilitation Site Survey Report American Academy of Physical Medicine and Rehabilitation Site Survey Report Introduction and Background In early 2013, the Contract Meeting Manager for the American Academy of Physical Medicine and Rehabilitation

More information

How To Light A Building In The United States

How To Light A Building In The United States Commercial Lighting Requirements of the 2006 International Energy Conservation Code U.S. Department of Energy Building Energy Codes Program Eric Richman, PNNL Materials developed by: Eric Richman, PNNL

More information

CHAPTER 4 VENTILATION

CHAPTER 4 VENTILATION CHAPTER 4 VENTILATION SECTION 401 GENERAL 401.1 Scope. This chapter, in conjunction with the building code, shall govern the ventilation of spaces within a building intended to be occupied. Mechanical

More information

Schedule A. Residential and Seasonal Dwellings. for estimating value of construction in the Township of North Kawartha

Schedule A. Residential and Seasonal Dwellings. for estimating value of construction in the Township of North Kawartha Schedule A Classification of buildings used for estimating value of construction in the Township of North Kawartha Estimated cost of Construction per square foot Residential and Seasonal Dwellings Single

More information

SUBCHAPTER H: UTILITY SUBMETERING AND ALLOCATION 291.121-291.127 Effective January 6, 2011

SUBCHAPTER H: UTILITY SUBMETERING AND ALLOCATION 291.121-291.127 Effective January 6, 2011 Texas Commission on Environmental Quality Page 1 SUBCHAPTER H: UTILITY SUBMETERING AND ALLOCATION 291.121-291.127 Effective January 6, 2011 291.121. General Rules and Definitions. (a) Purpose and scope.

More information

MINIMUM STANDARDS FOR HIGH-RISE BUILDINGS

MINIMUM STANDARDS FOR HIGH-RISE BUILDINGS CHAPTER 93 MINIMUM STANDARDS FOR HIGH-RISE BUILDINGS Note: Chapter 93 is entirely Seattle amendments to the International Fire Code and is not underlined. Point of Information The requirements of this

More information

Commercial Energy Use Worksheet

Commercial Energy Use Worksheet Commercial Energy Use Worksheet Did you know? The City of Austin requires all commercial buildings that are 10,000 square feet or greater in size located within its city limits and served electricity by

More information

We hope these Frequently Asked Questions will be of use both to municipal officials and fire inspectors.

We hope these Frequently Asked Questions will be of use both to municipal officials and fire inspectors. September 14, 2012 Dear AMM Member: Please see the attached Fire Code Frequently Asked Questions. This document was compiled by the Office of the Fire Commissioner at the AMM s request to help clarify

More information

New York City Department of Buildings

New York City Department of Buildings The New NYC Building Code Chapter 10 Means of Egress New York City Department of Buildings Technical Affairs Fatma M. Amer, P.E. Copyright Materials This presentation is protected by US and International

More information

Common ADA Errors and Omissions in New Construction and Alterations

Common ADA Errors and Omissions in New Construction and Alterations Common ADA Errors and Omissions in New Construction and Alterations Learning Objectives Course Number: 6002 Credit Hours: 1 After completing this course you will have a better understanding of numerous

More information

Supplemental Plan Check Corrections Sheet for Bicycle Parking Ordinance (Effective 3/13/2013)

Supplemental Plan Check Corrections Sheet for Bicycle Parking Ordinance (Effective 3/13/2013) Supplemental Plan Check Corrections Sheet for Bicycle Parking Ordinance (Effective 3/13/2013) Plan Check PCIS application number: - - Job Address Zone: P.C. Engineer (E-mail: firstname.lastname@lacity.org)

More information

FIRE SPRINKLERS IN TOWNHOMES/CONDOMINIUMS

FIRE SPRINKLERS IN TOWNHOMES/CONDOMINIUMS CITY OF BLAINE SAFETY SERVICES Fire Inspections 10801 Town Square Drive Blaine MN 55449 Business Phone 763-785-6187 Fax 763-717-2634 City of Blaine Fire Prevention Inspection Policy FIRE SPRINKLERS IN

More information

MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY

MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY State Fire Marshal Division 444 Cedar Street, Suite 145, St. Paul, Minnesota 55101-5145 Phone: 651/201-7200 FAX: 651/215-0525 TTY: 651/282/6555 Internet: http://www.fire.state.mn.us

More information

Upper Southampton Township Department of Licenses and Inspections 939 Street Rd. Southampton, Pa. 18966 Phone: 215-322-9700 Fax: 215-322-5842

Upper Southampton Township Department of Licenses and Inspections 939 Street Rd. Southampton, Pa. 18966 Phone: 215-322-9700 Fax: 215-322-5842 Upper Southampton Township Department of Licenses and Inspections 939 Street Rd. Southampton, Pa. 18966 Phone: 215-322-9700 Fax: 215-322-5842 APPLICATION for ZONING and BUILDING PERMIT APPLICATION INSTRUCTIONS:

More information

FIXTURES, FAUCETS AND FIXTURE FITTINGS

FIXTURES, FAUCETS AND FIXTURE FITTINGS CHAPTER 4 FIXTURES, FAUCETS AND FIXTURE FITTINGS SECTION 401 GENERAL 401.1 Scope. This chapter shall govern the materials, design and installation of plumbing fixtures, faucets and fixture fittings in

More information

Errata has been identified as follows:

Errata has been identified as follows: 2009 IFC Performing Commercial Fire Inspections Inventory Number: 1424S09 Second Printing; July 2014 Changes HAVE been made- Third Printing: September 2014 Errata has been identified as follows: 1. Page

More information

MEANS OF EGRESS CHAPTER 10

MEANS OF EGRESS CHAPTER 10 CHAPTER 10 MEANS OF EGRESS SECTION BC 1001 ADMINISTRATION 1001.1 General. Buildings or portions thereof shall be provided with a means of egress system as required by this chapter. The provisions of this

More information

MP 5.7 RESIDENTIAL SERVICES BUILDING STANDARD

MP 5.7 RESIDENTIAL SERVICES BUILDING STANDARD MP 5.7 RESIDENTIAL SERVICES BUILDING STANDARD Index Purpose... 3 Commencement.3 Application...3 Compliance..3 Associated Requirements... 3 Definitions... 4 Kitchen Facilities... 6 Laundry Facilities...

More information

Architectural Barriers

Architectural Barriers AB: Texas Accessibility Standards Architectural Barriers TEXAS ACCESSIBILITY STANDARDS (TAS) of the Architectural Barriers Act Article 9102, Texas Civil Statutes Prepared and Administered by the Policies

More information

FIRE AND LIFE SAFETY REQUIREMENTS FOR EXISTING BUILDINGS

FIRE AND LIFE SAFETY REQUIREMENTS FOR EXISTING BUILDINGS CHAPTER 46 FIRE AND LIFE SAFETY REQUIREMENTS FOR EXISTING BUILDINGS SECTION 4601 GENERAL 4601.1 Scope. The provisions of this chapter shall apply to existing buildings constructed prior to a state building

More information

Highway Requirements Part 4

Highway Requirements Part 4 Highway Requirements Part 4 INTRODUCTION CLASS A1 SHOPS 1. Almost half of all pedestrian accidents and a quarter of all vehicular accidents involve the presence of a parked vehicle. Stationary vehicles

More information

Page 1 of 6 COMPLIANCE CHECKLIST. > Long Term Care Facility - Nursing Unit

Page 1 of 6 COMPLIANCE CHECKLIST. > Long Term Care Facility - Nursing Unit COMPLIANCE CHECKLIST Page 1 of 6 > Long Term Care Facility - Nursing Unit The following checklist is for plan review of new long-term care facilities and new additions to existing long-term care facilities.

More information

A. Permitted uses. The following uses are permitted by right in the C-2 zone, subject to the limitations specified:

A. Permitted uses. The following uses are permitted by right in the C-2 zone, subject to the limitations specified: 1 of 8 4/6/2015 1:11 PM Sacramento City Code Up Previous Next Main Collapse Search Print No Frames Title 17 PLANNING AND DEVELOPMENT CODE Division II ZONING DISTRICTS AND LAND USE REGULATIONS Chapter 17.216

More information

VENTILATION CHAPTER 4

VENTILATION CHAPTER 4 CHAPTER 4 VENTILATION SECTION MC 401 GENERAL 401.1 Scope. This chapter shall govern the ventilation of spaces within a building intended to be occupied. This chapter does not govern the requirements for

More information

SECTION 434 ASSISTED LIVING FACILITIES

SECTION 434 ASSISTED LIVING FACILITIES SECTION 434 ASSISTED LIVING FACILITIES 434.1 Scope. Assisted living facilities shall comply with the following design and construction standards as described herein. Note: Other administrative and programmatic

More information

2012 Ontario Building Code Requirements for New Construction. Bradford West Gwillimbury Building Division March 5, 2012

2012 Ontario Building Code Requirements for New Construction. Bradford West Gwillimbury Building Division March 5, 2012 2012 Ontario Building Code Requirements for New Construction Bradford West Gwillimbury Building Division March 5, 2012 1 Ontario Building Code changes Applicable to permits applied for after December 31,

More information

Plumbing Code Statutes and Regulations February 2011 Labor Standards and Safety Division Mechanical Inspection

Plumbing Code Statutes and Regulations February 2011 Labor Standards and Safety Division Mechanical Inspection Plumbing Code Statutes and Regulations February 2011 Labor Standards and Safety Division Mechanical Inspection Jobs are Alaska s Future MECHANICAL INSPECTION CUSTOMER COUNTER LOCATIONS Main Office MI Anchorage

More information

APPENDIX A BUILDING SETBACKS AND HEIGHTS

APPENDIX A BUILDING SETBACKS AND HEIGHTS APPENDIX A BUILDING SETBACKS AND HEIGHTS A. SINGLE FAMILY DETACHED HOMES 1. Front Yard 18 0 minimum 2. Side Yard 6 0 minimum 3. Side Yard Corner Lots 10 0 minimum 4. Rear Yard 15 0 minimum 5. Building

More information

APPLICATION AND INFORMATION GUIDE FIRE ALARMS AND THE AMERICANS WITH DISABILITIES ACT

APPLICATION AND INFORMATION GUIDE FIRE ALARMS AND THE AMERICANS WITH DISABILITIES ACT APPLICATION AND INFORMATION GUIDE FIRE ALARMS AND THE AMERICANS WITH DISABILITIES ACT - NOW INCLUDING THE EXPECTED REVISIONS TO ADAAG - December 1994 (initial publication) August 1996 (revised) 0 This

More information

Life Safety Code Enabling References

Life Safety Code Enabling References SUPPLEMENT 4 Life Safety Code Enabling References Editor s Note: Supplement 4 provides users of NFPA 72, National Fire Alarm and Signaling Code, with a summary of requirements from NFPA 101, Life Safety

More information

Typical storey plan with two toilet clusters SANITARY PROVISION SANITARY PROVISION. Individual washroom. Standalone, unisex individual washroom

Typical storey plan with two toilet clusters SANITARY PROVISION SANITARY PROVISION. Individual washroom. Standalone, unisex individual washroom ACCESSIBLE TOILET REQUIREMENTS Code 2007 o Where toilets are provided at every level of a building Accessible individual washroom or WC compartment can be provided Disadvantage If WC compartment is provided,

More information

2012 NORTHERN NEVADA AMENDMENTS

2012 NORTHERN NEVADA AMENDMENTS 2012 NORTHERN NEVADA AMENDMENTS 2012 INTERNATIONAL BUILDING CODE 2012 INTERNATIONAL RESIDENTIAL CODE 2012 INTERNATIONAL MECHANICAL CODE 2012 INTERNATIONAL FUEL GAS CODE 2012 UNIFORM MECHANICAL CODE 2012

More information

Minimum Housing and Health Standards

Minimum Housing and Health Standards APPENDIX M.O. 57/2012 Minimum Housing and Health Standards Original version July 20, 1999. Revisions to Part lll, Housing Premises, sections 3 and 4, June 30, 2012 (all revisions are bolded and underlined).

More information

Accessibility Guide for Small Businesses

Accessibility Guide for Small Businesses . Accessibility Guide for Small Businesses June 2015 Second Edition Preface This document is intended to provide explanation and technical guidance to assist owners of small businesses of the accessibility

More information

WHEN IS A PERMIT REQUIRED?

WHEN IS A PERMIT REQUIRED? WHEN IS A PERMIT REQUIRED? Any owner, builder, contractor, or other authorized agent who intends to construct, enlarge, alter, repair, move, demolish, or change the occupancy of a building or structure,

More information

2006 IBC BUILDING CODE CHECKLIST FOR COMMERCIAL PROJECTS

2006 IBC BUILDING CODE CHECKLIST FOR COMMERCIAL PROJECTS 2006 IBC BUILDING CODE CHECKLIST FOR COMMERCIAL PROJECTS IBC CODE DESIGN CHECKLIST (EXCEPT 1 AND 2-FAMILY DWELLINGS AND TOWNHOUSES) (Transfer the resulting data on the building plans Life Safety & Building

More information

OFF-STREET PARKING REQUIREMENTS

OFF-STREET PARKING REQUIREMENTS Planning and Building Agency Planning Division 20 Civic Center Plaza P.O. Box 1988 (M-20) Santa Ana, CA 92702 (714) 647-5804 www.santa-ana.org OFF-STREET PARKING REQUIREMENTS Sec. 41-1300. Sec. 41-1301.

More information

City of Bettendorf Fire Alarm System Requirements

City of Bettendorf Fire Alarm System Requirements City of Bettendorf Fire Alarm System Requirements Section 907 of the 2009 Edition of the International Fire Code (IFC) and Section 10-7-3 of the Municipal Code provide fire alarm requirements. IFC Section

More information

Americans with Disabilities Act (ADA) Accessibility Guidelines for Buildings and Facilities

Americans with Disabilities Act (ADA) Accessibility Guidelines for Buildings and Facilities Appendix A to Part 1191 - Americans with Disabilities Act (ADA) Accessibility Guidelines for Buildings and Facilities Americans with Disabilities Act (ADA) Accessibility Guidelines for Buildings and Facilities

More information

SECTION 105 PERMITS. 2. Fences not over 6 feet (1829 mm) high. 3. Oil derricks.

SECTION 105 PERMITS. 2. Fences not over 6 feet (1829 mm) high. 3. Oil derricks. SECTION 105 PERMITS 105.1 Required. Any owner or authorized agent who intends to construct, enlarge, alter, repair, move, demolish, or change the occupancy of a building or structure, or to erect, install,

More information

Compliance Document for New Zealand Building Code Clause G1 Personal Hygiene Second Edition

Compliance Document for New Zealand Building Code Clause G1 Personal Hygiene Second Edition Compliance Document for New Zealand Building Code Clause G1 Personal Hygiene Second Edition Prepared by the Department of Building and Housing This Compliance Document is prepared by the Department of

More information

BEFORE THE COUNTY COMMISSION OF BERKELEY COUNTY, WEST VIRGINIA

BEFORE THE COUNTY COMMISSION OF BERKELEY COUNTY, WEST VIRGINIA 1 r!iii ii BEFORE THE COUNTY COMMISSION OF BERKELEY COUNTY WEST VIRGINIA IN RE: LOCATION OF EXOTIC ENTERTAINMENT (Originally adopted August 26 2004; Amended November 182004) Pursuant to 7-1-3jj Code of

More information

CHAPTER 4 VENTILATION

CHAPTER 4 VENTILATION CHAPTER 4 VENTILATION SECTION 1 GENERAL 1.1 Scope. This chapter shall govern the ventilation of spaces within a building intended to be occupied. Mechanical exhaust systems, including exhaust systems serving

More information

ARTICLE 10.00 C-1 COMMERCIAL ZONE

ARTICLE 10.00 C-1 COMMERCIAL ZONE ARTICLE 10.00 C-1 COMMERCIAL ZONE 10.01 PURPOSE The Commercial Zone is intended to provide for the broad range of commercial operations and services required for the proper and convenient functioning of

More information

KITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS

KITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS St. Louis County Department of Public Works Division of Code Enforcement KITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS This guideline is intended to provide the homeowner/contractor with the

More information