The Strode Park Foundation. Fire Risk Assessment for Footprints

Size: px
Start display at page:

Download "The Strode Park Foundation. Fire Risk Assessment for Footprints"

Transcription

1 The Strode Park Foundation Fire Risk Assessment for Footprints Passed by Executive Health and Safety Committee Authors Paul Clayson AIOSH and Julia Creaser AIOSH July 015 Page 1 of 3 016

2 Executive Summary The main areas of concern that have become apparent as a result of this fire risk assessment and that are in need of prompt attention are: - 1. Archive material needs to be removed from loft space. Fire extinguishers required 3. Fire blankets required 4. Smoke seals around doors need replacing 5. Viewing panel required in door at top of landing 6. Front door requires turn lock and to be connected to nurse call system, when it is installed 7. PEEP s to be written for each child with regard to the new fire training taking place in May 8. Door frame needs filling 9. Extra fire signage required for noted areas 10. Fire instruction notice required for fire exit in bedroom corridor 11. Procedure required to ensure dryer lint trap is cleaned out regularly and documented 1. Training required for all staff when new evacuation procedure is put in place on May PEEP s required for all residents this will come into place with new procedures 14. To be reviewed when fire evacuation procedures change in May 015 (review in July) Page of 3 016

3 Contents 1. Background Fire Risk Assessment Premises Overview Fire Hazards & Ignition Sources Summary of Significant Findings People at Risk Control Measures Detection and Warning Fire Fighting Escape Routes and Evacuation Arrangements Housekeeping Emergency Lighting Signs and Notices Maintenance and Other Risks Information Instruction and Training Records Review Action plan... 1 Appendix... Page 3 of 3 016

4 1. Background On the 0th March 015, Julia Creaser and Paul Clayson undertook a full fire safety risk assessment at Footprints residential home. The establishment provides living, sleeping and eating facilities for up to 6 young people and respite children. The premises are owned, managed and staffed by Strode Park Foundation. The purpose of this assessment was to identify any significant fire hazards within the premises and highlight any areas for immediate or long-term improvement. An action plan with timescales is attached to assist in the prioritisation of any such actions (also see priority ratings below). This assessment replicates the requirements made in the appropriate Regulatory Reform manual, Fire Risk Assessment, residential care premises issued by HM Government. The observations and any recommendations made are only pertinent to the conditions found at the time of the assessment or review. Regular inspections and risk assessment reviews are required to ensure that appropriate standards are maintained. Wherever a recommendation has been made within this risk assessment, a priority rating has been assigned which translates as: - Priority Ratings 0 No action required 1 Urgent Complete within 1 week of assessment date Complete within 1 month of assessment date 3 Complete within 3 months of assessment date 4 Complete within 6 months of assessment date 5 Complete within 1 months of assessment date RRO Care Home Online Version 1, July 009. Page 4 of 3 016

5 . Fire Risk Assessment.1 Premises Overview Name & address of premises Note. Does the site have a completion certificate from the local authority Building Inspector (new buildings) Type of premises Owned by Managed by Footprints Stodmarsh Road Canterbury Kent. CT3 4AP Residential and respite care services for children and young adults with disabilities Strode Park Foundation Laura Pearce Designated person Premises used out of normal office hours? Type of structure Number of lift shafts 0 Use of premises Total number of people A breakdown of the total number of people employed at the premises and residents living at premises Occupancy profile Maximum number of persons in the most highly occupied compartment or area of the premises at a given time John Cotterill Accommodation for 6 children/young adults with private bedrooms, hoists and electric beds with shared dining and lounge areas. There are bedrooms upstairs as well as lounge areas for staff and residents and a meeting room. There are various buildings in the garden area including two respite rooms, garden sheds, maintenance sheds and a hot tub room. Use No Offices Sleeping accommodation Living / lounge areas Internal smoking areas Industrial kitchens Kitchenettes Manufacturing processes Workshops Hot work e.g. welding Flammable substance storage Other: 31 employees 6 residents Total 37 Monday - Friday Saturday - Sunday Page 5 of 3 016

6 . Fire Hazards & Ignition Sources GROUND FLOOR All bedrooms Main kitchen Laundry Manager s office Seniors office Medical room Dining room Lounges Bathrooms WCs Corridors Linen cupboard Sensory room Quiet room Other rooms Room / area Fuel source(s) Ignition source(s) Clothing Bed linen Furnishings Curtains Clients personal electrical equipment Wiring Electric heater Cooking oil Gas Foods Kitchen appliances Wiring Washing machine/ dryer Wiring Linen/clothing Electrical equipment Paper Furnishings Wall hangings (e.g. curtains, leaflet holders, pictures). Clothing TV, computers, and other electrical equipment Flammable products in cleaners cupboards, medical or rooms Wiring Linen Faulty electrical equipment or wiring Unauthorised smoking Arson Electric heater Faulty hobs, cookers or fryers Faulty electrical equipment or wiring Unauthorised smoking Faulty electrical equipment Faulty wiring Self combusting laundry Blocked vent on dryer or lint screen Smoking materials Faulty electrical equipment or wiring Unauthorised smoking Arson Self combusting linen Page 6 of 3 016

7 Internal electrical distribution cupboard and main exterior electrical incomer and distribution board Exterior garden sheds External residents shed Boiler Room (Internal) Garden area External store rooms Bin Areas including any skips present FIRST FLOOR Miscellaneous combustibles (wood, paper, rubbish etc.). Decorating materials Gas, oil, electricity White spirit and/or discarded cooking oil Gas, electricity Garden refuse including leaf accumulations Garden sheds and contents Substances given off by faults in battery rooms Wiring Faulty electrical equipment or wiring Faulty boiler Arson Fireworks (seasonal) Smoking Sparking from tool or object striking hard surface (if gas present) Overload of electrical sockets Room / area Fuel source(s) Ignition source(s) Clothing Faulty electrical Bed linen equipment or wiring Furnishings Unauthorised Curtains smoking Clients personal electrical Arson equipment Electric heater Wiring Electric heater All bedrooms permanent, respite and staff sleep over Meeting Room Bathroom Linen Cupboard Residents lounge Staff room Store room WC Other Areas Clothing Computers, other electrical equipment Bed linen Furnishings Curtains Staff personal electrical equipment Wiring Faulty electrical equipment or wiring Unauthorised smoking Arson Room / area Fuel source(s) Ignition source(s) Pitched roof voids Wooden beams and joists Items stored in roof voids without authorisation, e.g. paper, cardboard Wiring Electrical equipment Wiring fault Unauthorised smoking Page 7 of 3 016

8 Substantial quantities of oxidising materials, oxygen cylinders or any other hazardous material found at the site? Room / area Fuel source(s) Ignition source(s) Bedroom Oxygen cylinder Faulty wiring Faulty electrical equipment Arson..1 Summary of Significant Findings Main ignition sources Based on use of premises and occupancy profile High risk area(s) Based on use of premises, occupancy profile and findings during assessment Smoking materials (accidental fire started by staff) Boilers and heaters Electrical appliances and wiring (if faulty) Cooking processes, e.g. hobs and cookers (if cooking equipment faulty) Arson Oxygen cylinder Sleeping accommodation Kitchen Boiler room Main electrical incomer Laundry Ref Recommendation(s) Priority - None 0.3 People at Risk The following people have been identified as regular users of the premises and as such are likely to be at risk in the event of a fire occurring. Type of people No Comments Employees Agency staff Agency staff work alongside SPF staff Visitors / guests Cleaning staff All visitors and guests sign in and are escorted in building Page 8 of 3 016

9 Contractors Anyone with hearing impairment All contractors sign in so staff are aware of the area they are working in Anyone with visual impairment Service user - young people Service users higher risk considerations. Are users with poor mobility accommodated on the ground floor? Service user - learning difficulty Service user - physical disability Others, e.g. external health professionals One service user has an oxygen cylinder There are two bedrooms on the first floor. At present one is for a permanent child who is able to mobilise. Appropriate numbers of staff for emergency evacuation if required All residents have hoists and emergency exits in their rooms All other people sign in and out of the building. Trespassers The house has perimeter fencing Ref Recommendations Priority - None 0 Page 9 of 3 016

10 .4 Control Measures.4.1 Detection and Warning All premises must have fire detection and warning systems fitted and there are few if any exceptions to this. The system should incorporate fire detection devices, a control panel, audible and / or visual alarms and manually operated break-glass boxes as a means of ensuring the early detection of fire and safe and prompt escape of a site s inhabitants. The majority of detectors at care homes should be smoke type, the principle being that these give the quickest detection and alarm activation time in the event of any fire starting. Heat detectors should be used in areas where smoke detectors would result in false alarms. An L1, detection system throughout premises should be used at care homes to give the quickest possible alert of a fire condition. The following system exists within this particular premises: - System model Concept FS01 Control panel location(s) By front door on wall System maintained by System Category, e.g. L1 Note. For reference BS stipulation s state that in an L1 system all areas need to be covered save for the following: - Is this acceptable for the risks present? KT Fire L1 Type(s) of automatic fire detection Type(s) of automatic fire warning Type(s) of automatic fire fighting Does kitchen have appropriate fire detection and damper systems within their extract systems and are extract fans interlocked with the main detection system and turn off in the event of a fire alert? Smoke Heat Flame Audible siren/bells Visual strobe / flashing light Vibrating pad Pager (allows for delayed alarm) Water sprinkler CO suppression Foam suppression No specialist extraction due to being domestic appliance. Are any fire alarm zones within the site greater than 000m and if so, does the site have an addressable fire panel? Are there any large voids in pitched roofs or are Page 10 of No There are large voids and there

11 there flat roof ceiling voids over 800mm and if so has detection been fitted within them? is no detection fitted. Area full of archive material. Does the alarm system have a back-up battery? Is there an audible alarm in the boiler room? Can the alarm be heard clearly in all parts of the site? All manual call points within 45m distance? Date of last weekly system (bell) test? Has it been done within the last 7 days? Is a different call point used (in rotation) for the test? Date of last service (must be within last six months as per BS5839-1) Records up to date No 11th February 015 Ref Recommendations Priority 1 Archive material needs to be removed from loft space Page 11 of 3 016

12 .4. Fire Fighting This can be used if, for example, an exit is blocked due to fire and escape needs to be made via it, or if a fire starts that is small enough to be tackled and put out by trained staff as long as it is safe for them to do so and before it can get larger. The following equipment exists within these particular premises: Types of equipment Water Carbon dioxide Fire blankets Location(s) Portable Fire Fighting Equipment maintained by: - Date of last service (annual as per BS5306-3: 003) Records up to date See Appendix 1 Plan of Footprints KT Fire Ltd 11th February 015 Ref Recommendations Priority Fire extinguishers required: Foam and water extinguisher by seniors office Foam extinguisher in kitchen 1 Water and CO by emergency exit by kitchen 3 Fire blanket required: By seniors office Jemini Suite Exit by kitchen Exit in bedroom corridor Entrance to bedroom corridor By fire panel Upstairs landing Upstairs kitchenette area Upstairs fire exit door (meeting room) Escape Routes and Evacuation Arrangements Page 1 of 3 016

13 Main access to building Front door Alternative means of escape Fire Exits: First floor from meeting room Ground floor end of bedroom corridor Exit by kitchen Entrance/exit to Jemini suite Travel distances acceptable? Is compartmentation acceptable for the layout and size of the premises? Is structural integrity of compartmentation acceptable, e.g. are there any holes/breaches in compartment walls, any missing sections?. Is the protection of escape routes acceptable, e.g. doors, windows, door co-ordinators, magnetic locks, selfclosers, smoke seals? No Smoke seals around doors need attention: Utility room door Rm 1Bedroom door Rm 6 Bedroom door Bedroom Jemini Suite (left as you go into building) Hook bedroom door Door between kitchenette and meeting room upstairs Viewing panel required for door at top of landing leading to residents lounge etc. Front door is at present a fire escape route but is often locked with the key either in the door of hanging at the side of the door. This is not appropriate. Wall and ceiling coverings of escape routes acceptable, e.g. Class 0? Are all escape routes free from obstructions? Evacuation Arrangements and Procedures in Case of Fire Number of daytime staff on duty? Number of night time staff on duty? Page 13 of 3 016

14 On Call Rota on view Is there a written fire evacuation procedure that covers daytime and night time fire evacuation procedures and is it reviewed and if necessary updated at regular intervals Is the current staffing level considered adequate enough to ensure the safe and prompt evacuation of service users to a place of safety within a reasonable time Are there any employees or service users who need assistance to evacuate from the building? e.g. wheelchair users If yes, does each one have a written Personal Emergency Evacuation Plan? Is there a signing in / out system for visitors and contractors? Are contractors and other visitors, e.g. Social Care or Health Visitors, briefed on fire evacuation procedures when they arrive at the site? Are visitors chaperoned throughout their visit? Are external routes to the assembly point acceptable and do they lead to a place of safety? Fire assembly point location(s) acceptable, e.g. sufficiently far enough away and in a safe place to prevent harm to persons from smoke, radiated heat, fire or any traffic in the area? No Fire assembly point in patio area by hot tub Ref Recommendations Priority 4 Smoke seals around doors need replacing on six doors 1 5 Viewing panel required in door at top of landing 6 7 Front door requires turn lock and to be connected to nurse call system when it is installed PEEP s to be written for each child with regard to the new fire training (May 1st) 8 Door frame needs filling Housekeeping Page 14 of 3 016

15 Good housekeeping is an essential part of effective fire safety management and ensures that unwanted fire load does not build up at a site and that emergency escape routes and exits are kept clear at all times. The following table describes the standard of housekeeping found at this site: Are housekeeping standards acceptable? Ref Recommendations Priority - None Emergency Lighting All means of escape must be adequately lit to ensure the safe escape of persons from a place of danger to a place of safety during a fire or other emergency, especially where there is no natural light available such as in internal rooms or corridors or during the hours of darkness. Emergency lighting Each exit door (within m) Emergency lighting appropriate Escape routes Intersections of corridors Outside each final exit and on external escape routes Emergency escape signs All escape routes have external emergency lighting Emergency lighting appropriate Page 15 of appropriate All escape routes have external emergency lighting Emergency lighting appropriate Stairways so each flight receives adequate light Changes in floor level N/A Windowless rooms and toilet accommodation exceeding 8m Fire fighting equipment Fire alarm call points Boiler room Equipment that would need to be shut down in an emergency i.e. first aid point Lighting near all fire fighting equipment At all exits with appropriate lighting Boiler room indoors upstairs Loft space above Jemini suite Loft space above SM s room Emergency lighting appropriate Lifts Stair lift only N/A Halls or other areas greater than 60m All hallways have appropriate emergency lighting All emergency lit signage appropriate Lighting near all fire fighting equipment At all exits with appropriate lighting Light in corridor outside boiler room cupboard Emergency lighting appropriate All hallways have appropriate emergency

16 lighting The following emergency lighting configuration exists within these particular premises: - Maintained and Non-maintained Type of system e.g. maintained, nonmaintained, generator, mixed. Location(s) Equipment maintained by Are emergency lighting units located at all higher risk areas? Date of last service (must be within last 6 months)? Records up to date? See Appendix KT Fire 11th February 015 Ref Recommendations Priority - None Signs and Notices Do all of the fire safety signs and notices comply with the Health and Safety (Signs and Signals) Regulations 1996 and other applicable guidance documents e.g. BS 5499, the FPA Guide to Fire Safety Signs? Are there adequate fire exit signs? Are site specific fire action notices displayed? Are there adequate fire action notices (site specific and general)? Signage needs to be placed outside seniors office to show direction of travel in case of emergency. Directional signage is not appropriate above front door emergency exit Signage required in down stairs lounge area and dining area regarding direction of emergency exit Signage required between upstairs kitchenette area and meeting room. No fire instruction notice at emergency exit by children s bedrooms. No No No Page 16 of 3 016

17 Ref Recommendations Priority 9 Extra fire signage required for areas noted 1 10 Fire instruction notice required for fire exit in bedroom corridor 1.5 Maintenance and Other Risks Are there any acetylene or gas cylinders at the site (e.g. LPG type)? Are there any oxygen or other types of medical gas cylinders at the site? Is there a permit to work system in use at the site and are staff aware of how it works? Has appropriate equipment been PAT tested? Does the site have lightening protection and has this been tested? Note. This system is subject to annual testing and inspection as detailed and laid down in BS6651. Has the electrical system been tested in the last 5 years? Does the site have gas-fuelled systems and are they maintained? Has the kitchen s cooker extraction vent for fat fryer etc been deep cleaned in the last 3, 6 or 1 months? Are the dryers in the laundry room/s lint traps cleaned/vacuumed weekly? Are ashtrays emptied into metal-lipped bins at the end of the day? Are there any garden sheds or other structures located close to the main buildings? If so, is there a chance that due to their proximity to the site, a fire within them may spread into the main building via windows (radiation), via overhanging roofs (flat or pitched) or by No One oxygen cylinder in one child s bedroom testing carried out annually No No Non applicable as domestic oven No procedure Not applicable as non smoking home hot tub shed located close to building. Page 17 of 3 016

18 any other means (e.g. burning brands)? Ref Recommendations Priority 11 Procedure required to ensure dryer lint trap cleaned out regularly and documented.6 Information Instructions and Training Is there an established fire emergency plan as per Section 7. of the RRO? Is the plan written down and available? If yes, is it appropriate? Is there appropriate cooperation and coordination re fire emergency and evacuation procedures, with any other undertaking that may be on the site, e.g. day centres, special needs, mobility for the elderly organisations? Are employees familiar with the evacuation plan? Are evacuation drills conducted and have they so far meet with the standards outlined and required in Section.4.3 of this document? Records up to date? Have all staff been given suitable information, instruction and training to satisfy the requirements for service users evacuation contained in Section.4.3 of this document? Have fire wardens been nominated? Not applicable Is there an adequate number? Have the nominated fire wardens been given enhanced training (e.g. able to supervise other, all staff as per above) to satisfy the requirements for service users evacuation contained in Section.4.3 of this document? Page 18 of 3 016

19 Have all employees been given a basic level of fire safety awareness training in other fire safety matters such as use of extinguishers, raising the alarm, identification of fire hazards, procedure for reporting hazards etc.? Ref Recommendations Priority 1 Training required for all staff when new evacuation procedure is put in place on May Records Type of record No Comments Fire register Personal emergency egress plans (PEEP) Monthly fire safety inspections Employee fire safety induction Employee training records Are fire records kept for at least three years for insurance purposes? Ref Recommendations Priority 13 PEEPS required for all residents this will come into place with new procedures.8 Review This risk assessment should be reviewed: Following any structural or material changes to the premises; Following a change in the nature of work practices or processes; Following changes in staff levels or disposition; Following a sizeable change in the type of clients being accommodated at this site, e.g. the site moves from a moderate number of immobile and mentally adept clients to a large number of wheelchair and/or dementia sufferers. Following a near miss or actual fire; In any case it is recommended at intervals not exceeding 1 months. Page 19 of 3 016

20 Ref Recommendations Priority 7 To be reviewed when fire evacuation procedures change in May 015 (review in July) Page 0 of 3 016

21 3. Action plan Priority Ratings 0 No action required 1 Urgent Complete within 1 week of assessment date Complete within 1 month of assessment date 3 Complete within 3 months of assessment date 4 Complete within 6 months of assessment date 5 Complete within 1 months of assessment date Recommendation Reference No. Recommendation Priority To be Actioned by Archive material needs to be removed LP 1 from loft space Fire extinguishers required KT Fire / PC 1 3 Fire blankets required 1 KT Fire / PC 4 Smoke seals around doors need PC 1 replacing 5 Viewing panel required in door at top of KT Fire / PC landing Front door requires turn lock and to be PC 6 connected to nurse call system, when it is installed PEEP s to be written for each child with LP 7 regard to the new fire training taking place in May 8 Door frame needs filling 1 PC 9 Extra fire signage required for noted areas 10 Fire instruction notice required for fire exit in bedroom corridor Procedure required to ensure dryer lint 11 trap is cleaned out regularly and documented Training required for all staff when new 1 evacuation procedure is put in place on May 015 To be reviewed when fire evacuation 13 procedures change in May 015 (review in July) END OF REPORT 1 1 PC PC LP VW JTC Date Completed Page 1 of 3 016

22 Appendix KEY Intrumescent strip required at top of door Smoke Alarm Heat detector Fire Exit Water Extinguisher CO Extinguisher Foam Extinguisher Fire Blanket Alarm Bell Break Glass Emergency Light Oxygen Cylinder Fire blanket required Door not appropriate for linen cupboard requires fire door EB Signage Viewing required panel required from KT in Fire door Fire blanket required Fire blanket required Signage required Intrumescent strip required for door Page of 3 016

23 Signage required in area for emergency exits Intrumescent strip required in places around door Door frame needs filling Light bulb out in airing cupboard Wires hanging from ceiling light Fire blanket required No fire fighting equipment foam extinguisher required Fire blanket required Intrumescent strip required in places around door Fire blanket required Directional sign needs replacing pointing in wrong direction Intrumescent strip required in places around door Fire extinguishers required Fire blanket required KEY Smoke Alarm Heat detector Fire Exit Water Extinguisher CO Extinguisher Foam Extinguisher Fire Blanket Alarm Bell Break Glass Emergency Light Oxygen Cylinder Query whether this is a fire exit as always locked No fire instruction notice Signage required in room for emergency exits Fire blanket required Intrumescent strip required in places around door Page 3 of Fire blanket required

FIRE SAFETY RISK ASSESSMENT

FIRE SAFETY RISK ASSESSMENT FIRE SAFETY RISK ASSESSMENT For small single occupancy premises Premises Hertco Ltd ACME House, Old London Road, Hertford SG17 7LD Fire Safety Risk Assessment for Small Premises Introduction Regulatory

More information

SBR FIRE RISK ASSESSMENT

SBR FIRE RISK ASSESSMENT SBR FIRE RISK ASSESSMENT Report of audit and inspection Premises Details Occupier Premises Address Premises Description Times premises are in use Use and maximum no. people present The British School of

More information

Fire Risk Assessment Safety Checklist

Fire Risk Assessment Safety Checklist Fire Risk Assessment Safety Checklist This checklist has been prepared to help you comply with The Regulatory Reform Fire Safety Order 2005 What is the Regulatory Reform (Fire Safety) Order 2005? The Regulatory

More information

Fire Risk Assessment For Simple Premises

Fire Risk Assessment For Simple Premises Fire Risk Assessment For Simple Premises Responsible Person (Employer or other person having control of the relevant premises) Company / Premises Name Address of Premises Postcode Primary Use of Premises

More information

For use by landlords of small premises Premises Address

For use by landlords of small premises Premises Address fire risk assessment For use by landlords of small premises Premises Address FIRE RISK ASSESSMENT for use by landlords of small premises Person having control of the premises: Name of landlord (if different):

More information

Fire Safety Risk Assessment

Fire Safety Risk Assessment 1 Sources of ignition The main sources of ignition in Cass building are: PAF arrange for the fixed electrical installation to be tested in accordance with the British Standards. Test certificates are kept

More information

FIRE RISK ASSESSMENT

FIRE RISK ASSESSMENT REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT This template has been provided to assist the Responsible Person with the preparation of a Fire Risk Assessment and is not intended for commercial

More information

1.0 APPOINTMENTS 2.0 FIRE RISK ASSESSMENTS

1.0 APPOINTMENTS 2.0 FIRE RISK ASSESSMENTS Fire Risk assessment 1.0 APPOINTMENTS 1.1 Responsible Person. In compliance with the Regulatory Reform (Fire Safety) Order 2005 (FSO) the School s Head, Mrs J M Miles is appointed as the Responsible Person

More information

FIRE RISK ASSESSMENT

FIRE RISK ASSESSMENT The Regulatory Reform (Fire Safety) Order 2005 FIRE RISK ASSESSMENT Employer or other responsible person Name of Premises Address Post Code Telephone N o Name of Assessor(s) Date of Assessment Date of

More information

For use by landlords of small premises Premises Address

For use by landlords of small premises Premises Address fire risk assessment For use by landlords of small premises Premises Address FIRE RISK ASSESSMENT for use by landlords of small premises Person having control of the premises: Name of landlord (if different):

More information

Fire Safety Risk Assessment Checklist for Residential Care Premises

Fire Safety Risk Assessment Checklist for Residential Care Premises Checklist for Residential Care Premises Name of Premises: Address of Premises: Name of Responsible Person: What area / location does the assessment cover? Does the assessment cover the whole site YES or

More information

Fire precautions in dwellings. Private sector housing Providing homes building communities

Fire precautions in dwellings. Private sector housing Providing homes building communities Fire precautions in dwellings Private sector housing Providing homes building communities Version 3 Published by Norwich City Council August 2011 Contents Page Introduction 1 2 Types of dwellings (A) Shared

More information

Action required (Please tick) If you answered YES, record Action Points at STEP 4

Action required (Please tick) If you answered YES, record Action Points at STEP 4 RECORD OF FIRE SAFETY RISK ASSESSMENT Building Name & Use: Address: Postcode: Name of person(s) with fire safety duties: Name and contact details of assessor: Date of Assessment: 6 th February 2011 Laurel

More information

PRACTICAL FIRE SAFETY GUIDANCE

PRACTICAL FIRE SAFETY GUIDANCE PRACTICAL FIRE SAFETY GUIDANCE FOR SMALL BED AND BREAKFAST AND SELF-CATERING PREMISES PRACTICAL FIRE SAFETY GUIDANCE FOR SMALL BED AND BREAKFAST AND SELF-CATERING PREMISES The Scottish Government, Edinburgh,

More information

RESIDENTS FIRE SAFETY INFORMATION PACK

RESIDENTS FIRE SAFETY INFORMATION PACK RESIDENTS FIRE SAFETY INFORMATION PACK MARIE CURIE SCEAUX GARDENS ESTATE LONDON SE5 THE CONTENTS OF YOUR PACK Section Page No. 1. 3. Introduction Here we will explain the purpose of the Fire Safety Information

More information

1. Fire Safety Policy and Responsibilities. Consult the Employer s Fire Safety Policy and establish responsibilities of staff for fire safety.

1. Fire Safety Policy and Responsibilities. Consult the Employer s Fire Safety Policy and establish responsibilities of staff for fire safety. Management Checklist 1. Fire Safety Policy and Responsibilities. Consult the Employer s Fire Safety Policy and establish responsibilities of staff for fire safety. 2. Fire Hazard and Risk Assessment. Use

More information

Fire Safety Log Book

Fire Safety Log Book Fire Safety Log Book Company... Address........ Responsible Person. Competent Person. Date Started For Additional Information: Safety Management (UK) Ltd Holme Suite, Clawthorpe Hall Business Centre, Burton

More information

1.1. EMERGENCY PROCEDURE On discovering a fire or being informed of an emergency;

1.1. EMERGENCY PROCEDURE On discovering a fire or being informed of an emergency; Fire Action Plan FIRE ACTION PLAN SEStran aims to provide and maintain safe & healthy working conditions, equipment and systems of work for all our employees, and to provide such information, training

More information

FIRE RISK ASSESSMENT. The Workplace Fire Precautions Legislation

FIRE RISK ASSESSMENT. The Workplace Fire Precautions Legislation FIRE RISK ASSESSMENT The Workplace Fire Precautions Legislation The Fire Precautions (Workplace) Regulations 1997 The Fire Precautions (Workplace)(Amendment) Regulations 1999 The Management of Health and

More information

Grasshoppers Rugby Football Sports and Social Club. The Fire Risk Assessment

Grasshoppers Rugby Football Sports and Social Club. The Fire Risk Assessment Grasshoppers Rugby Football Sports and Social Club The Fire Risk Assessment Revision 1 Dated: 15th February 2013 CONTENTS 1. PREMISES DETAILS 2. PREMISES PLAN 3. HAZARDS 4. HISTORY 5. MITIGATING THE EFFECTS

More information

London Borough of Barnet. Fire Safety in Houses in Multiple Occupation. A Guide to Landlords

London Borough of Barnet. Fire Safety in Houses in Multiple Occupation. A Guide to Landlords London Borough of Barnet Fire Safety in Houses in Multiple Occupation A Guide to Landlords March 2016 Contents Introduction p.3 Summary of main requirements p.3 Fire Safety Precautions p.4 Protecting the

More information

RESIDENTS FIRE SAFETY INFORMATION PACK

RESIDENTS FIRE SAFETY INFORMATION PACK RESIDENTS FIRE SAFETY INFORMATION PACK CASTLEMEAD CAMBERWELL ROAD LONDON SE5 THE CONTENTS OF YOUR PACK Section Page No. 1. 3. Introduction Here we will explain the purpose of the Fire Safety Information

More information

FIRE RISK ASSESSMENT WORKED EXAMPLE

FIRE RISK ASSESSMENT WORKED EXAMPLE FIRE RISK ASSESSMENT WORKED EXAMPLE 1 PREMISES PARTICULARS BE-INT05 Premises Name S M Enterprises Address Small Place Medium Road Anywhere Tel no: 01234 567890 Date of Risk Assessment 1 st July 2011 Use

More information

How To Write A Fire Risk Assessment

How To Write A Fire Risk Assessment Fire Safety Risk Assessment This form is to aid you in carrying out a fire safety risk assessment of a property. The form is separated in to two parts: Part 1 initial assessment form and guidance notes

More information

UCL FIRE RISK ASSESSMENT POLICY& ARRANGEMENTS

UCL FIRE RISK ASSESSMENT POLICY& ARRANGEMENTS Fire Safety Technical Guide UCL FIRE RISK ASSESSMENT POLICY& ARRANGEMENTS 1.0. BACKGROUND 1.1. The Regulatory Reform (Fire Safety) Order (known Fire Safety Order) applies to England and Wales (Northern

More information

FIRE DETECTION AND ALARM SYSTEMS

FIRE DETECTION AND ALARM SYSTEMS HMO Information Sheet No 1 FIRE DETECTION AND ALARM SYSTEMS 1. Introduction When a property is in multiple occupation, the risk of fire breaking out is greater than in an ordinary single family home. Some

More information

Fire risk assessment a guide for businesses

Fire risk assessment a guide for businesses Fire risk assessment a guide for businesses Disclaimer Cornwall Fire and Rescue Service provide this guide to assist businesses to improve fire safety in their premises, but stress the person completing

More information

UPP Residential Services Fire Risk Assessment

UPP Residential Services Fire Risk Assessment UPP Residential Services Fire Risk Assessment TS11151-R02-DRAFT1 15 August 2011 for: Keynes College University Road Canterbury Kent Recommended latest review date 14 August 2011 Executive summary This

More information

Dennis Fire Department Fire Prevention Mark Dellner Fire Chief

Dennis Fire Department Fire Prevention Mark Dellner Fire Chief Dennis Fire Department Fire Prevention Mark Dellner Fire Chief FIRE SAFETY INSPECTION GUIDELINES FOR COMMERCIAL PROPERTIES (MA Fire Prevention Regulations 527 CMR, MGL Chapter 148) FIRE PREVENTION CHECKLIST-

More information

ISLE OF MAN FIRE & RESCUE SERVICE FIRE PRECAUTIONS LOGBOOK. Website www.iomfire.com

ISLE OF MAN FIRE & RESCUE SERVICE FIRE PRECAUTIONS LOGBOOK. Website www.iomfire.com ISLE OF MAN FIRE & RESCUE SERVICE FIRE PRECAUTIONS LOGBOOK Website www.iomfire.com ADDRESS OF PREMISES FIRE CERTIFICATE No. (where applicable).. LOCATION OF LOG BOOK. CONTENTS OF LOG BOOK Useful telephone

More information

Fire Evacuation Procedures Network Building, 97 Tottenham Court Road, London, W1

Fire Evacuation Procedures Network Building, 97 Tottenham Court Road, London, W1 Network Building Fire Safety Management Plan & Fire Evacuation Procedures Contents 1.0 Introduction 2.0 Means of Escape in Case of Fire 3.0 Means for Giving Warning in Case of Fire 4.0 Means for Fighting

More information

RESIDENTS FIRE SAFETY INFORMATION PACK

RESIDENTS FIRE SAFETY INFORMATION PACK RESIDENTS FIRE SAFETY INFORMATION PACK PERRONET HOUSE PRINCESS STREET LONDON SE1 THE CONTENTS OF YOUR PACK Section Page No. 1. 3. Introduction Here we will explain the purpose of the Fire Safety Information

More information

Fire Safety Requirements for Child Care Centre

Fire Safety Requirements for Child Care Centre Fire Safety Requirements for Child Care Centre A. Restrictions on Location Child care centre shall not be located : - (a) (b) in any premises designed for residential use; in any industrial building, warehouses,

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005. Fire Risk Assessment. 145 Drury Lane Covent Garden London WC2B 5TA

REGULATORY REFORM (FIRE SAFETY) ORDER 2005. Fire Risk Assessment. 145 Drury Lane Covent Garden London WC2B 5TA REGULATORY REFORM (FIRE SAFETY) ORDER 2005 Fire Risk Assessment 145 Drury Lane Covent Garden London WC2B 5TA Annex A (informative) Model pro-forma for documentation of the fire risk assessment for premises

More information

Hotel Fire Safety for staff

Hotel Fire Safety for staff Teaching Guide Hotel Fire Safety for staff Seattle Fire Department Fire Prevention Division Hotel Fire Safety Instructor Outline Introduction Goals: To ensure that hotel employees are knowledgeable in

More information

The Imperial College Healthcare NHS Trust. A guide to your onsite key worker accommodation

The Imperial College Healthcare NHS Trust. A guide to your onsite key worker accommodation The Imperial College Healthcare NHS Trust A guide to your onsite key worker accommodation Welcome to the accommodation at the Imperial College Healthcare NHS Trust. We hope you enjoy your stay. This guide

More information

SPECIFIC GUIDANCE FOR A HOUSE IN MULTIPLE OCCUPATION (HMO) CONVERTED ENTIRELY INTO SELF CONTAINED FLATS

SPECIFIC GUIDANCE FOR A HOUSE IN MULTIPLE OCCUPATION (HMO) CONVERTED ENTIRELY INTO SELF CONTAINED FLATS Document F SPECIFIC GUIDANCE FOR A HOUSE IN MULTIPLE OCCUPATION (HMO) CONVERTED ENTIRELY INTO SELF CONTAINED FLATS This document is intended as a specific guide for persons who own, manage or control Houses

More information

Fire Risk Assessment for Simple Premises Guidance Notes

Fire Risk Assessment for Simple Premises Guidance Notes Fire Risk Assessment for Simple Premises Guidance Notes The UK s national fire safety organisation Protecting people, property, business and the environment Introduction This guide and the accompanying

More information

Bastille Court 2 Paris Garden London SE1 8ND Telephone: 020 7902 5314 Fax: 020 7902 5301 E-mail: training@thefpa.co.uk Web: http://www.thefpa.co.

Bastille Court 2 Paris Garden London SE1 8ND Telephone: 020 7902 5314 Fax: 020 7902 5301 E-mail: training@thefpa.co.uk Web: http://www.thefpa.co. Bastille Court 2 Paris Garden London SE1 8ND Telephone: 020 7902 5314 Fax: 020 7902 5301 E-mail: training@thefpa.co.uk Web: http://www.thefpa.co.uk Fire Risk Assessment Course Health & Safety at Work Inspectorate,

More information

LANCASTER UNIVERSITY. MANUAL OF SAFETY Section 29 POLICY ON FIRE RISK ASSESSMENTS

LANCASTER UNIVERSITY. MANUAL OF SAFETY Section 29 POLICY ON FIRE RISK ASSESSMENTS LANCASTER UNIVERSITY MANUAL OF SAFETY Section 29 POLICY ON FIRE RISK ASSESSMENTS 1 Introduction 1.1 The Fire Precautions (Workplace) Regulations, require the University to carry out fire risk assessments

More information

Healthcare Help Supporting Health Providers. Module 2 Resources for Fire Warden Refresher Training HH.NET LTD

Healthcare Help Supporting Health Providers. Module 2 Resources for Fire Warden Refresher Training HH.NET LTD Healthcare Help Supporting Health Providers Module 2 Resources for Fire Warden Refresher Training HH.NET LTD Introduction This training shows what to do if you find fire. People might panic.... People

More information

Name Of Occupancy Date. Yes No Describe

Name Of Occupancy Date. Yes No Describe FIRE PREVENTION INSPECTION CHECKLIST For Class A Occupancy (For Assembly Buildings, Bars, Restaurants, Gyms, Churches, Arenas, Theatres or wherever people gather) Name Of Occupancy Date Physical Address

More information

Fire Risk Assessment for

Fire Risk Assessment for Regulatory Reform (Fire Safety) Order 2005 The Management of Health and Safety at Work Regulations 1999 Fire Risk Assessment for Tokyo Diner Restaurant 2 Newport Place London WC2H 7JJ Prepared by Robert

More information

Fire safety advice for landlords

Fire safety advice for landlords YOU CAN PREVENT IT Fire safety advice for landlords Introduction Each year there are over 50,000 fires in dwellings in the UK. These result in around 300 hundred fatalities and several thousand serious

More information

Fire Risk Assessment

Fire Risk Assessment Fire Risk Assessment London House School of English 63-65 Westgate Bay Avenue Westgate-on-Sea Kent CT8 8SW UK Tel: +44 (0) 1843 831 216 Fax: +44 (0) 1843 831 100 Email: enquiries@london-house.co.uk Website:

More information

Your responsibilities if you have an automatic fire alarm. A handy guide for owners and responsible persons

Your responsibilities if you have an automatic fire alarm. A handy guide for owners and responsible persons Your responsibilities if you have an automatic fire alarm A handy guide for owners and responsible persons Kent Fire and Rescue Service Contents Your responsibilities if you have an automatic fire alarm

More information

Fire Safety Challenges and Solutions. Claire Guise Health and Safety Manager

Fire Safety Challenges and Solutions. Claire Guise Health and Safety Manager Fire Safety Challenges and Solutions Claire Guise Health and Safety Manager Marie Curie Cancer Care (UK Wide) 9 Palliative Care Hospices (owned) Facilities Manager in place (NEBOSH General Certificate

More information

Fire safety for landlords

Fire safety for landlords Fire safety for landlords Acting Acting to to Protect & Save Are you a landlord and confused about your responsibilities towards fire safety? The law and regulations can often seem complicated and grey.

More information

Fire Policy and Procedures. Cañada Blanch Spanish School

Fire Policy and Procedures. Cañada Blanch Spanish School Fire Policy and Procedures Cañada Blanch Spanish School SUMMARY 1. Introduction (p. 3) 2. Roles and responsibilities (p. 3) -- Headteacher -- Fire Team -- All staff -- Contractors 3. Fire procedures (p.

More information

CITY OF LONDON SCHOOL FOR GIRLS FIRE SAFETY, PROCEDURE AND RISK ASSESSMENT POLICY

CITY OF LONDON SCHOOL FOR GIRLS FIRE SAFETY, PROCEDURE AND RISK ASSESSMENT POLICY CITY OF LONDON SCHOOL FOR GIRLS FIRE SAFETY, PROCEDURE AND RISK ASSESSMENT POLICY This policy was written in July 2014 and will be agreed by the Board of Governors in October 2014. To be reviewed by June

More information

MINIMUM STANDARDS FOR HIGH-RISE BUILDINGS

MINIMUM STANDARDS FOR HIGH-RISE BUILDINGS CHAPTER 93 MINIMUM STANDARDS FOR HIGH-RISE BUILDINGS Note: Chapter 93 is entirely Seattle amendments to the International Fire Code and is not underlined. Point of Information The requirements of this

More information

Fire Safety Policy and Procedure

Fire Safety Policy and Procedure Fire Safety Policy and Procedure Approved by Audit & Risk Committee Approved Date April 2014 Version no. 3 Review Date April 2015 Page 1 of 20 CONTENTS 1.0 Introduction 2.0 Policy Statement 3.0 Fire Safety

More information

NORTH BIRMINGHAM ACADEMY

NORTH BIRMINGHAM ACADEMY NORTH BIRMINGHAM ACADEMY FIRE AND EVACUATION PROCEDURES FIRE DRILLS: These are carried out once a term. Observations and details of each drill are recorded in the logbook, which is kept by the Assistant

More information

FURNITURE & FURNISHINGS - FIRE SAFETY STANDARDS

FURNITURE & FURNISHINGS - FIRE SAFETY STANDARDS Fire Safety Technical Guide FURNITURE & FURNISHINGS - FIRE SAFETY STANDARDS 1.0. Introduction 1.1. Furniture and furnishings may significantly increase fire spread in rooms and those circulation spaces,

More information

Building Control. Householder Guidance Leaflet No. 29. Fire detection in dwellings

Building Control. Householder Guidance Leaflet No. 29. Fire detection in dwellings Building Control Householder Guidance Leaflet No. 29 Fire detection in dwellings This leaflet is one of a series produced by the Hertfordshire Building Control Technical Forum GUIDANCE NOTE FOR HOME OWNERS

More information

Carrying Out and Recording a Fire Risk Assessment

Carrying Out and Recording a Fire Risk Assessment Carrying Out and Recording a Fire Risk Assessment This document provides information which appropriate persons (or those carrying out a fire risk assessment on their behalf) may find helpful when completing

More information

Gatehouse School. Fire Risk Assessment

Gatehouse School. Fire Risk Assessment Gatehouse School Fire Risk Assessment DATE: 6th October 2014 REVIEW DATE: October 2015 INDEX 1. Premises Particulars 2. General Statement of Policy 3. Management Systems 4. General Description of Premises

More information

FIRE RISK ASSESSMENT SW13 0HA

FIRE RISK ASSESSMENT SW13 0HA FIRE RISK ASSESSMENT at Carmichael Court Grove Road London SW13 0HA ON BEHALF OF Farrar Property Management Date of assessment: 14/01/2013 Recommended review date: January 2015 CONTENTS 1.0 INTRODUCTION

More information

FIRE SAFETY IN THE HOME

FIRE SAFETY IN THE HOME FIRE SAFETY IN THE HOME 2 Did you know? You re four times more likely to die in a fire if you don t have a smoke alarm that works. Around half of home fires are caused by cooking accidents. Two fires a

More information

The terms hazard and risk are often used, which we define as the following:

The terms hazard and risk are often used, which we define as the following: Fire Safety Last updated in October 2010 This information sheet aims to give safety reps a basic understanding of fire safety and fire risk assessments under the current law. More detailed information

More information

EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM

EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM REGULATORY STANDARD: OSHA - 29CFR1910.36-29CFR1910.38-29CFR1910.157-29CFR1910.165 NFPA-10 BASIS: The OSHA Emergency Action Planning and the

More information

1. Introduction 3. 2. Scope and Application 5

1. Introduction 3. 2. Scope and Application 5 Contents 1. Introduction 3 1.1 Reason for this Guide 1.2 Interpretation 1.3 Principles of fire safety 1.4 Legal provisions 2. Scope and Application 5 2.1 Scope of the Guide 2.2 Premises to which the Guide

More information

LINCOLNSHIRE FIRE AND RESCUE

LINCOLNSHIRE FIRE AND RESCUE LINCOLNSHIRE FIRE AND RESCUE FIRE RISK ASSESSMENT FOR SMALLER PREMISES AND THE WORKPLACE FIRE PRECAUTIONS LEGISLATION The Fire Precautions (Workplace) Regulations 1997 The Fire Precautions (Workplace)

More information

Fire Safety Log Book. Premises Name: Premises Address: Date From: Date To: Location of Log Book:

Fire Safety Log Book. Premises Name: Premises Address: Date From: Date To: Location of Log Book: Fire Safety Log Book Premises Name: Premises Address: Date From: Date To: Location of Log Book: CONTENTS PART 1 FIRE SAFETY ADVICE 1 PART 2 FIRE PRECAUTIONS 2 Section 1 Guidance on Fire Risks and Preventative

More information

Fire Risk Assessment Report

Fire Risk Assessment Report Fire Risk Assessment Report Fire Risk Assessment Report Company Site Address Contact details Site Contact Date of Assessment Date of Report St Augustines Priory Main School Building Hillcrest Rd, London

More information

Proposed changes to the Acceptable Solution for Building Code clause F7 (Warning Systems) Proposed amended Acceptable Solution for Warning Systems

Proposed changes to the Acceptable Solution for Building Code clause F7 (Warning Systems) Proposed amended Acceptable Solution for Warning Systems Proposed changes to the Acceptable Solution for Building Code clause F7 (Warning Systems) Appendix A Proposed amended Acceptable Solution for Warning Systems s in the grey boxes form part of the proposed

More information

Winnipeg Fire Department Fire Prevention Branch

Winnipeg Fire Department Fire Prevention Branch Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of

More information

Safety and Health Office WORKPLACE SAFETY CHECKLIST

Safety and Health Office WORKPLACE SAFETY CHECKLIST Location: Date: Inspected by: Safety and Health Office WORKPLACE SAFETY CHECKLIST WORK ENVIRONMENT Ventilation Removal of fumes and dust Temperature and humidity control Noise levels Vibration Lighting

More information

Oxford House Evacuation Plan SECTION 1. RESPONSIBILITIES. A. COOP Staff

Oxford House Evacuation Plan SECTION 1. RESPONSIBILITIES. A. COOP Staff Oxford House Evacuation Plan SECTION 1. RESPONSIBILITIES A. COOP Staff 1. COOP DIRECTOR will work with the UHDS Safety & Inspection Coordinator (SIC) to establish an emergency operation plan for the building.

More information

Property Accreditation Standards 2014/2015

Property Accreditation Standards 2014/2015 Property Accreditation Standards 2014/2015 Promoting responsible renting of student housing in the city of Southampton Letting period 1st July 2014 to 30th June 2015 Version 1, 10/12/2013 All properties

More information

Lee Baron FIRE RISK ASSESSMENT

Lee Baron FIRE RISK ASSESSMENT FIRE RISK ASSESSMENT, 13/21 Cantelupe Road, East Grinstead Prepared for: Lee Baron 7 Swallow Place Oxford Circus London W1B 2AG Prepared by: Violet McIntyre CMIOSH William Martin Compliance Solutions Limited

More information

FIRE SAFETY REGISTER. Premises Name: Premises Address: Fire Safety Manager: Contact No. Kerry County Fire Service www.kerrycoco.ie

FIRE SAFETY REGISTER. Premises Name: Premises Address: Fire Safety Manager: Contact No. Kerry County Fire Service www.kerrycoco.ie FIRE SAFETY REGISTER Premises Name: Premises Address: Fire Safety Manager: Contact No. Kerry County Fire Service www.kerrycoco.ie 1 CONTENTS Section Title Page 1.0 Introduction 3 2.0 Guidance for the completion

More information

CANTON FIRE DEPARTMENT

CANTON FIRE DEPARTMENT CANTON FIRE DEPARTMENT Dean Floyd Fire Chief FIRE SAFETY INSPECTION GUIDELINES FOR COMMERCIAL PROPERTIES FIRE PREVENTION CHECKLIST- To review prior to your inspection. 1. Is the address of your property

More information

BS5839 Part 1:2002 Overview

BS5839 Part 1:2002 Overview BS5839 Part 1:2002 Overview 1 Contents Introduction So why is the current standard being revised? The brief for the new standard Changes to structure of current Standard Enhanced certification of Fire

More information

c. As mandated by law, facilities must obtain and maintain valid zoning permits as well as permits for intended use.

c. As mandated by law, facilities must obtain and maintain valid zoning permits as well as permits for intended use. Walmart Standards for Suppliers Section 7. Health and Safety 7. Health and Safety Suppliers must provide workers with a safe and healthy work environment. Suppliers must take proactive measures to prevent

More information

FIRE SAFETY PRECAUTIONS

FIRE SAFETY PRECAUTIONS FIRE SAFETY PRECAUTIONS LOG BOOK PLEASE KEEP AVAILABLE 1 Business Name Premises Information Building / Unit Number Property Name Road: (Address Line 1) (Address Line 2) Locality: Town: Post Code: Name

More information

Introduction. Pre-Arrival. Arrival & Car Parking Facilities. Main Entrance, Reception & Ticketing Area

Introduction. Pre-Arrival. Arrival & Car Parking Facilities. Main Entrance, Reception & Ticketing Area Access Statement for Chester Backpackers - Chester Introduction We are a 35 bed, independent hostel situated in Chester. The Hostel is situated over 4 Floors and offers dormitory rooms to private en-suite

More information

MINNESOTA HEALTH CARE ENGINEERS IN ASSISTED LIVING FACILITIES

MINNESOTA HEALTH CARE ENGINEERS IN ASSISTED LIVING FACILITIES MINNESOTA HEALTH CARE ENGINEERS FIRE/LIFE SAFETY IN ASSISTED LIVING FACILITIES September 13, 2012 MINNESOTA HEALTH CARE ENGINEERS FIRE/LIFE SAFETY IN ASSISTED LIVING FACILITIES WELCOME Exits Restrooms

More information

CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES

CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES Review the following information pertaining to Construction Fire Safety Planning: B.C. Building Code Sections 8.1 up to and including Subsection 8.2.3 B.C.

More information

FIRE SAFETY ONLINE TRAINING

FIRE SAFETY ONLINE TRAINING INTRODUCTION This Fire Safety Training module is designed to teach you preventive measures that will eliminate or minimize causes of fire or fire hazards in the workplace, and to teach you proper emergency

More information

FIRE RISK ASSESSMENT PRINCIPLES A GUIDE FOR LICENSED PREMISES

FIRE RISK ASSESSMENT PRINCIPLES A GUIDE FOR LICENSED PREMISES NFG27 FIRE RISK ASSESSMENT PRINCIPLES A GUIDE FOR LICENSED PREMISES The Workplace Fire Precautions Legislation brings together existing Health & Safety and Fire Legislation to form a set of dedicated Fire

More information

(Sample) Building Emergency Plan

(Sample) Building Emergency Plan (Sample) Building Emergency Plan for XXXXXX 2815 Commons Way Cincinnati, OH 45221 August 2016 University of Cincinnati Department of Public Safety Department a 2 Table of Contents A. Introduction B. Components

More information

Gatehouse School. Fire Risk Assessment

Gatehouse School. Fire Risk Assessment 1 Gatehouse School Fire Risk Assessment DATE: 26 th October 2015 REVIEW DATE: October 2016 2 INDEX 1. Premises Particulars 2. General Statement of Policy 3. Management Systems 4. General Description of

More information

Additional Guidance. for application to. HM Government Guide to Fire Safety Risk Assessment Residential Care Premises

Additional Guidance. for application to. HM Government Guide to Fire Safety Risk Assessment Residential Care Premises Additional Guidance for application to HM Government Guide to Fire Safety Risk Assessment Residential Care Premises Good Practice Guidance 2016 Additional Guidance agreed between the National Association

More information

ENVIRONMENTAL HEALTH PROFESSIONAL PRACTICE VOL II CHAPTER III. HOUSES IN MULTIPLE OCCUPATION Space Standards

ENVIRONMENTAL HEALTH PROFESSIONAL PRACTICE VOL II CHAPTER III. HOUSES IN MULTIPLE OCCUPATION Space Standards ENVIRONMENTAL HEALTH PROFESSIONAL PRACTICE VOL II CHAPTER III HOUSES IN MULTIPLE OCCUPATION Space Standards ADOPTED HOUSING STANDARDS:CATEGORY F HOUSES Houses within this category would be of a low priority

More information

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Fire Alarm Systems Design. a guide to BS5839

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Fire Alarm Systems Design. a guide to BS5839 AVAILABLE TO DOWNLOAD ON THE APOLLO APP a guide to Fire Alarm Systems Design BS5839 Part1:2013 The Regulatory Reform (Fire Safety) Order (FSO) became law on 1 October 2006 Legally you must comply! What

More information

FIRE SAFETY GUIDANCE NOTE Regulatory Reform (Fire Safety) Order 2005

FIRE SAFETY GUIDANCE NOTE Regulatory Reform (Fire Safety) Order 2005 FIRE SAFETY GUIDANCE NOTE Regulatory Reform (Fire Safety) Order 2005 Number: GN66 This Guidance Note provides advice on the requirements of the Regulatory Reform (Fire Safety) Order 2005 and how to complete

More information

PRACTICAL FIRE SAFETY GUIDANCE FOR MEDIUM AND LARGE PREMISES PROVIDING SLEEPING ACCOMMODATION

PRACTICAL FIRE SAFETY GUIDANCE FOR MEDIUM AND LARGE PREMISES PROVIDING SLEEPING ACCOMMODATION PRACTICAL FIRE SAFETY GUIDANCE FOR MEDIUM AND LARGE PREMISES PROVIDING SLEEPING ACCOMMODATION Revised February 2008 Practical Fire Safety Guidance For Medium And Large Premises Providing Sleeping The guidance

More information

General Fire Code Requirements Within Commercial Tenant Spaces

General Fire Code Requirements Within Commercial Tenant Spaces FIRE DEPARTMENT in cooperation with Scope: General Fire Code Requirements Within Commercial Tenant Spaces This handout is designed to assist owners, architects, contractors and others in understanding

More information

TSA Conference Reducing the Risk of Fire to the Vulnerable Person through Telecare. London Fire Brigade

TSA Conference Reducing the Risk of Fire to the Vulnerable Person through Telecare. London Fire Brigade TSA Conference Reducing the Risk of Fire to the Vulnerable Person through Telecare London Fire Brigade Sheltered Accommodation Irene - Surrey Coroner s Court 9 th May 2014 HM Coroner Richard Travers highlighted

More information

Fire. The Fire Installers Mate. A guide to fire alarm systems design

Fire. The Fire Installers Mate. A guide to fire alarm systems design Fire The Fire Installers Mate A guide to fire alarm systems design BS 5839 Part 1:2002 A guide to BS 5839 Part 1:2002 Disclaimer This booklet is not intended to be a comprehensive guide to all aspects

More information

Call reduction guidance for false alarm/ unwanted fire signals

Call reduction guidance for false alarm/ unwanted fire signals Call reduction guidance for false alarm/ unwanted fire signals Acting to Protect & Save Introduction Devon & Somerset Fire & Rescue Service attend in excess of 20,000 incidents each year, approximately

More information

FIRE SAFETY FOR OFFICE WORKERS

FIRE SAFETY FOR OFFICE WORKERS FIRE SAFETY FOR OFFICE WORKERS This easy-to-use Leader s Guide is provided to assist in conducting a successful presentation. Featured are: INTRODUCTION: A brief description of the program and the subject

More information

Employers guide to fire safety

Employers guide to fire safety Employers guide to fire safety Produced jointly by the H.S.E. and the Home Office to give guidance to all employers on how to meet their legal obligations under the workplace directive The contents pages

More information

Q The Quoin Consultancy

Q The Quoin Consultancy Q The Quoin Consultancy Catholic Church of the Sacred Heart & St. John the Evangelist London Road, Bushey Hertfordshire WD23 1BA FIRE RISK ASSESSMENT CONTENTS REVIEW LOG SECTION 1.0 - INTRODUCTION 1.1

More information

DOMESTIC SMOKE ALARMS

DOMESTIC SMOKE ALARMS SOUTH AUSTRALIAN METROPOLITAN FIRE SERVICE HOME FIRE SAFETY INFORMATION For further advice contact the Community Safety Department South Australian Metropolitan Fire Service on 8204 3611 DOMESTIC SMOKE

More information

LONDON BOROUGH OF BROMLEY STANDARDS FOR HOUSES IN MULTIPLE OCCUPATION (HMO) INTRODUCTION

LONDON BOROUGH OF BROMLEY STANDARDS FOR HOUSES IN MULTIPLE OCCUPATION (HMO) INTRODUCTION LONDON BOROUGH OF BROMLEY STANDARDS FOR HOUSES IN MULTIPLE OCCUPATION (HMO) INTRODUCTION 1. Minimum Standards: This document sets out the minimum standards required in HMOs located within the London Borough

More information

Fire Safety Management Strategy 2015-2018

Fire Safety Management Strategy 2015-2018 Fire Safety Management Strategy 2015-2018 Introduction This strategy is a plan and method of approach to how Medway Council Housing Services (the council) will both continue to meet our statutory obligations

More information

Fire Risk Assessment. John Revington

Fire Risk Assessment. John Revington Fire Risk Assessment John Revington PRACTICAL APPLICATION Identifying Fire Hazardsand Managing Fire Precautions History of Fire Fires that have changed our lives History of Fire Theatre Royal - Exeter

More information

PRACTICAL FIRE SAFETY GUIDANCE FOR EDUCATIONAL AND DAY CARE FOR CHILDREN PREMISES

PRACTICAL FIRE SAFETY GUIDANCE FOR EDUCATIONAL AND DAY CARE FOR CHILDREN PREMISES PRACTICAL FIRE SAFETY GUIDANCE FOR EDUCATIONAL AND DAY CARE FOR CHILDREN PREMISES Revised February 2008 The guidance in this document has been jointly produced by the Scottish Government s Police and Community

More information