2 This Guidance Notes is prepared by the Occupational Safety and Health Branch Labour Department This edition July 2005 This Guidance Notes is issued free of charge and can be obtained from offices of the Occupational Safety and Health Branch of the Labour Department. It can also be downloaded from website of the Labour Department at For enquiries about addresses and telephone numbers of the offices, please call This Guidance Notes may be freely reproduced for advertising, endorsement or commercial purposes. Please acknowledge the source as Guidance Notes on Ventilation and Maintenance of Ventilation Systems, published by the Labour Department.

3 Guidance Notes on Ventilation and Maintenance of Ventilation Systems

4 Foreword Efficient ventilation and proper maintenance of ventilation systems help provide a comfortable working environment for workers and avoid various invisible health hazards in buildings and workplaces. This Guidance Notes provides a general reference on ventilation and maintenance of ventilation systems. It helps to comply with the requirements laid down in the Section for ventilation under the Occupational Safety and Health Regulation. Functions of Ventilation 1. Ventilation is a process by which air is removed from and supplied to premises simultaneously. Its functions are: (a) to supply fresh air to meet the respiratory needs of the occupants; (b) to remove airborne contaminants such as dusts, mists, gases, vapours, tobacco smoke, body odours and bacteria which may pose health hazards or nuisance to the occupants; and (c) to maintain the temperature and humidity within an acceptable range that is appropriate to the activities on the premises. Guidance Notes on Ventilation and Maintenance of Ventilation Systems Fresh Air Composition 2. 'Fresh air' normally means air from outside the building. It should be, as far as possible, free from any contamination. The composition of pure dry air is: Oxygen 20.94% by volume Carbon dioxide 0.03% by volume Nitrogen & inert gases 79.03% by volume Dirty air O 2 CO 2 N 2 H 2 O Clean air 1

5 Guidance Notes on Ventilation and Maintenance of Ventilation Systems Ventilation Requirement 3. Ventilation requirements for different workplaces are varied because of different indoor activities and building designs. The basic methods for control of airborne contaminants are: elimination or control of sources fresh air supply of contaminants proper air distribution air filtration (purification) removal of contaminated air No Smoking 4. Sources of contaminants can be found inside and outside the workplace. Examples of indoor sources are new furniture and fittings which may emit volatile organic compounds, human bodies which give off odours and carbon dioxide, cigarette smoking, renovation work, etc. A no-smoking policy should be implemented in workplaces. Where smoking is allowed, it should be limited to a designated and isolated area which is equipped with an independent exhaust arrangement. Outdoor contaminants, such as dusts and vehicle exhaust, can get into workplaces through fresh air intake points. Thus, the intake points should be away from sources of contaminants, and fresh air should be filtered or cleaned before being supplied to the workplace. Workplace A Workplace B 2

6 5. For general workplaces where there is no smoking, the fresh air should be supplied at a rate of 0.3 to 0.5 cubic metres per minute per person. Where smoking is allowed, the supply rate should be more than 0.9 cubic metres per minute per person. In workplaces where hazardous air contaminants are produced, fresh air should be supplied and polluted air be removed at rates which can control the contaminant levels to those not causing adverse health effects. Local exhaust is usually recommended. Factors needed to be taken into account in designing the ventilation requirement include: the nature of the operations or activities the toxicity and rate of generation of hazardous substances the degree of expected occupancy the design of the premises. Readers may find some recommendations of fresh air supply rate for various activities in the appendix. 6. In a workplace without a specific source of contamination, the adequacy of ventilation can be measured indirectly with a carbon dioxide index method. As the concentration of carbon dioxide increases with human activities, background levels of other contaminants also increase. Carbon dioxide level frequently exceeding 1000 ppm (although carbon dioxide at such a level is not a health concern) could be a useful indicator for review of the ventilation supply distribution and the activities going on, especially when there is a complaint. Guidance Notes on Ventilation and Maintenance of Ventilation Systems ppm CO2 7. Where contaminant sources can be localised, the contaminants should be removed from the location before it spreads into the occupied zone. This can be achieved through control of local air movement by creation of pressure differentials, by exhaust fans or by careful location of inlet diffusers and air return inlets. 3

7 Guidance Notes on Ventilation and Maintenance of Ventilation Systems 8. A combination of sufficient outdoor air supply, good air distribution, air filtering and contaminated air removal can provide a cost effective means to the control of airborne contaminants. Thermal Environment 9. Thermal comfort perceived by a person depends on environmental and personal factors. Environmental factors which can be controlled by a ventilation system include air temperature, relative humidity and air speed. 10. In air-conditioned work environments, most workers carrying out light activities may feel comfortable when air temperature is maintained between 20 o C to 24 o C in the winter and 23 o C to 26 o C in the summer Winter 20 o C - 24 o C Summer 23 o C - 26 o C 11. People who perform light activities in moderate temperatures can accept a wide range of relative humidity. The indoor relative humidity should be kept between 40 % to 70 % to avoid workers feeling dry eyes and throat at low humidity and prevent flourishing growth of micro-organisms at high humidity. R.H. 40% - 70% 4

8 12. Either draught or stagnant air is unsatisfactory. The air speed at workstations should lie between 0.1 to 0.25 metres per second. People in warmer environments can withstand higher air speed m/s Guidance Notes on Ventilation and Maintenance of Ventilation Systems Health Effects 13. A poorly designed ventilation system or inadequate ventilation may induce irritability, impair concentration and performance, and cause fatigue and headache. 14. Poor maintenance of a ventilation system will increase power consumption and running costs, and lower its performance, leading to accumulation of air contaminants and deviation from the optimum indoor environmental conditions. 5

9 Guidance Notes on Ventilation and Maintenance of Ventilation Systems 15. Furthermore, a poorly designed or maintained ventilation system will enhance dispersion of air contaminants, particularly micro-organisms dislodged from the dirty filters or grills of the system. These organisms may cause health hazards to the occupants of the premises. These include: (a) Legionnaires' disease Legionnaires' disease is a type of bacterial infection caused by Legionella pneumophila. It may be contracted by inhaling droplets which contain viable legionella bacteria from the fresh water cooling towers of airconditioning systems. Most reported cases have occurred in the 40 to 70 age group. The symptoms include high fever, chills, headache, muscle pain, and cough. This disease may not always be severe and in community outbreaks, mild cases may be recognised. (b) Humidifier fever This may be caused by inhaling water droplets from contaminated humidifiers, but the definite pathogen is unknown. It is said to be related to growth of bacteria, fungi or algae in the air filters. These organisms or their associated endotoxins may trigger complaints in sensitive individuals. The symptoms, including fever, general malaise, lethargy and aches, may occur 4 to 8 hours after starting work. After a break away from work, e.g. holiday, these symptoms will generally disappear. 6

10 16. Poor ventilation is a significant contributor to a phenomenon, known as 'Sick Building Syndrome'. The occupants of the building may complain of sore throat, headache, sore dry eyes, dry blocked nose, lethargy, general malaise and vague upper respiratory discomfort. There are no definite causes for the syndrome. Many factors have been suggested for the sick building syndrome. Stress may result from psycho-social factors such as poor relationship with colleagues and extremes of workload. Repetitive tasks and boredom are also stressful. Inhalation of solvent vapour from correcting fluid or corresponding thinner and side-stream smoke in a poorly ventilated building may cause vague discomfort. Furthermore, the physical environmental factors including lighting, humidity, noise and office layout may also be the contributing factors to stress and health complaints. Complaints are more likely from locations where population densities are higher, and symptoms are more likely to appear in the afternoon than in the morning. In general, people feel better when they are away from work. Guidance Notes on Ventilation and Maintenance of Ventilation Systems 7

11 Guidance Notes on Ventilation and Maintenance of Ventilation Systems Methods of Ventilation 17. Basically, methods to achieve the ventilation requirements may come under two categories: (a) Natural ventilation, and (b) Mechanical ventilation (i) induced dilution ventilation, i.e. stale air is extracted from the premises by exhaust fans whereas outside air infiltrates into the premises through available openings (ii) forced dilution ventilation, i.e. where air is forced into the premises by air blowers commonly via ducting systems. Natural Ventilation 18. Natural ventilation is the movement of air into and out of the premises through windows, doors or any openings without any mechanical aid. The rate of air exchange in this type of ventilation is inevitably unsteady as it is governed by geographical, meteorological and many other factors which are very often beyond the occupants' control. Natural ventilation is suitable only for control of modest heat load and very low emission of less toxic contaminants. Out In 19. Adequacy of air inlets and outlets is of great importance to natural ventilation. As a reference, premises relying entirely on natural ventilation should have openings of at least 5 to 10% of the floor area to obtain adequate ventilation in the summer. 8

12 Mechanical Ventilation 20. Induced dilution ventilation In this type of ventilation, contaminated air is extracted from the premises by propeller fans. The air pressure inside the premises is lower than outside. Air therefore infiltrates into the premises through openings. Proper arrangements of air inlets and outlets are of vital importance to such systems. In principle, cross ventilation should be effected as far as practicable. Sufficient replacement air is essential in maintaining the efficiency of the exhaust fan and avoiding the indoor air pressure being too negative. Exhaust Air Replacement Air Guidance Notes on Ventilation and Maintenance of Ventilation Systems 21. Forced dilution ventilation In this type of ventilation, air (preferably filtered and conditioned) is blown into the premises for ventilation. It is important to site the air inlets away from sources of contaminants. The system usually consists of a fan, a cooling/heating unit and a ducting system by which air is distributed to the required positions. Duct Air outlet Fan 9

13 Guidance Notes on Ventilation and Maintenance of Ventilation Systems 22. Dilution ventilation together with natural ventilation is suitable for the control of heat load and moderate emission of gases and vapours of low toxicity. It is, however, not advisable to apply this type of ventilation to hazardous operations as the volume of air necessary for dilution may be too high to be practicable. Maintenance of Mechanical Ventilation Systems 23. In using mechanical systems for ventilation, it is important to minimise any health hazard to the occupants. To achieve this, the following points should be observed: Proper inspection, cleaning, testing and maintenance schedules should be drawn up and followed. Replace air filters regularly. Inspect all components of the ventilation system for cleanliness and microbial growth regularly, and clean them as required. Test the performance of the system against the design specifications and make necessary adjustment or repair. If water cooling towers are used, they should be so maintained, e.g. use of biocides as appropriate, as to prevent the growth of micro-organisms. 24. Consult a competent ventilation maintenance agency for the proper maintenance of your ventilation system. Further Information If you have any queries about this booklet, please contact the Occupational Health Service of the Labour Department. Address : 15/F Harbour Building, 38 Pier Road, Central, Hong Kong Telephone : Facsimile : Website : Information on the services offered by the Occupational Safety and Health Council can be obtained through hotline If you have any complaints about unsafe workplaces and practices, please call the Labour Department s occupational safety and health complaint hotline at

14 Appendix Fresh air supply rate for general work activities in air-conditioned workplaces. (A) For places where the number of persons present is normally constant. Types of work activity Open plan offices, schools (non-smoking) Private offices (with moderate smoking), laboratories Conference rooms or offices (with heavy smoking) Canteens, restaurants Minimum fresh air supply rate (m 3 /min/person) (based on the seating capacity and the number of employees) Remark The normal daily working hours or hours of stay are long e.g. 8 hours On average, people may not stay in the area for a long period Guidance Notes on Ventilation and Maintenance of Ventilation Systems (B) For places where the number of persons may vary from time to time. Types of work activity Shops, supermarkets department stores Kitchen (Restaurants) Minimum fresh air supply rate (m 3 /m 2 floor area / min.) Remark Generally no smoking Additional exhaust for working areas are required Note: Local exhaust should be provided if harmful substances are generated. 11

PHOTOCOPYING. 2. Electrostatic photocopying

PHOTOCOPYING. 2. Electrostatic photocopying May 2005 T his guide is intended to help employers and employees assess the health risks associated with photocopying in their workplace. Such assessments can be no more than an examination of what, in

More information

HVAC Systems and Indoor Air Quality. Douglas K. Spratt, M.Sc., P.Eng.

HVAC Systems and Indoor Air Quality. Douglas K. Spratt, M.Sc., P.Eng. HVAC Systems and Indoor Air Quality Douglas K. Spratt, M.Sc., P.Eng. The 5 Senses Architecture Electrical Structural Mechanical Hearing Seeing Smelling Feeling Tasting HVAC Systems are Dynamic Heat Gains

More information

Indoor Air Quality Issues for Hotels

Indoor Air Quality Issues for Hotels Indoor Air Quality Issues for Hotels Chai chen Chao DEA 670 Spring, 2000 Thermal Control Relative Humidity Winter Temperature Summer Temperature 30% 68.5 F - 76.0 F 74.0 F - 80.0 F 40% 68.5 F - 75.5 F

More information

University of Texas at Dallas Indoor Air Quality Policy for University Buildings. Effective Date: October 1, Summary

University of Texas at Dallas Indoor Air Quality Policy for University Buildings. Effective Date: October 1, Summary University of Texas at Dallas Indoor Air Quality Policy for University Buildings Effective Date: October 1, 2005 Summary Sridhar Hanumanthaiah, Industrial Hygienist, EH&S Esequiel (Zeke) Barrera, Director,

More information

Information paper 20. Prepared by: David Clark. book:

Information paper 20. Prepared by: David Clark. book: Information paper 20 Ventilation rates in offices and natural mechanical Prepared by: David Clark A paper referenced in the book: Cundall Johnston & Partners LLP. 2013 Issue 1.0: 29 July 2013 This information

More information

GENERAL VENTILATION HSG202

GENERAL VENTILATION HSG202 GENERAL VENTILATION G U I D A N C E F O R E M P L O Y E R S HSG202 Crown copyright 2000 Applications for reproduction should be made in writing to: Copyright Unit, Her Majesty's Stationery Office, St.

More information

FOREWORD OF THE SERIES

FOREWORD OF THE SERIES FOREWORD OF THE SERIES Many people believe that occupational health problems only occur in factories and offices are comfortable and generally healthy. This is not so. There are various health risks which,

More information

Mechanical and Natural Ventilation

Mechanical and Natural Ventilation BBSE3006: Air Conditioning and Refrigeration II http://www.hku.hk/bse/bbse3006/ Mechanical and Natural Ventilation Dr. Sam C. M. Hui Department of Mechanical Engineering The University of Hong Kong E-mail:

More information

Information Sheet. It will also be of interest to designers, suppliers, manufacturers and installers of water based systems, plant and equipment.

Information Sheet. It will also be of interest to designers, suppliers, manufacturers and installers of water based systems, plant and equipment. Legionnaires Disease Information Sheet This information sheet provides a general overview of Legionnaires disease and is aimed at employers and persons who have control of a place of work. It will also

More information

A Simple Guide to Health Risk Assessment Office Environment Series OE 5/2003

A Simple Guide to Health Risk Assessment Office Environment Series OE 5/2003 A Simple Guide to Health Risk Assessment Office Environment Series OE 5/2003 Occupational Safety and Health Branch Labour Department Occupational Safety and Health Council Contents Introduction 1 Office

More information

Why Measure Carbon Dioxide Inside Buildings? By Rich Prill, Washington State University Extension Energy Program

Why Measure Carbon Dioxide Inside Buildings? By Rich Prill, Washington State University Extension Energy Program Why Measure Carbon Dioxide Inside Buildings? By Rich Prill, Indoor air quality Workers and students spend about half their waking hours at work or school. Therefore, maintaining adequate indoor air quality

More information

INDOOR AIR QUALITY INTRODUCTION WHAT ARE THE SYMPTOMS OF SICK BUILDING SYNDROME? WHEN DID POOR INDOOR AIR QUALITY BECOME A PROBLEM?

INDOOR AIR QUALITY INTRODUCTION WHAT ARE THE SYMPTOMS OF SICK BUILDING SYNDROME? WHEN DID POOR INDOOR AIR QUALITY BECOME A PROBLEM? INDOOR AIR QUALITY Public Employees Occupational Safety and Health Program Richard J. Codey Acting Governor November, 2004 INTRODUCTION The average person sends approximately 90% of their time indoors.

More information

THE APPLICATION OF OZONE FOR AIR TREATMENT: CASE STUDY OF A BINGO HALL HVAC SYSTEM

THE APPLICATION OF OZONE FOR AIR TREATMENT: CASE STUDY OF A BINGO HALL HVAC SYSTEM 1 Application Note AT-102 THE APPLICATION OF OZONE FOR AIR TREATMENT: CASE STUDY OF A BINGO HALL HVAC SYSTEM Lawrence B. Kilham 1 and Randall M. Dodd 2 1 Eco Sensors, Inc. Santa Fe, New Mexico, USA larry@ecosensors.com

More information

Case Study: PPM Technology s Mini IAQ Profile Monitor system used by ice rinks to monitor levels of harmful gases.

Case Study: PPM Technology s Mini IAQ Profile Monitor system used by ice rinks to monitor levels of harmful gases. Case Study: PPM Technology s Mini IAQ Profile Monitor system used by ice rinks to monitor levels of harmful gases. Ice rinks and arenas vulnerable to harmful pollutants. Indoor Air Quality (IAQ) is a significant

More information

This guidebook is prepared by the Occupational Safety and Health Branch Labour Department

This guidebook is prepared by the Occupational Safety and Health Branch Labour Department This guidebook is prepared by the Occupational Safety and Health Branch Labour Department This edition June 2011 This guidebook is issued free of charge and can be obtained from offices of the Occupational

More information

INDOOR AIR QUALITY ASSESSMENT. Massachusetts Department of Developmental Services 436 Dwight Street Springfield, Massachusetts

INDOOR AIR QUALITY ASSESSMENT. Massachusetts Department of Developmental Services 436 Dwight Street Springfield, Massachusetts INDOOR AIR QUALITY ASSESSMENT Massachusetts Department of Developmental Services 436 Dwight Street Springfield, Massachusetts Prepared by: Massachusetts Department of Public Health Bureau of Environmental

More information

Mould Mould A Basic Guide

Mould Mould A Basic Guide Mould A Basic Guide Summary Mould is a fact of life. Moulds will grow practically everywhere people live and work. Mould is recognized as an occupational hazard for indoor workers as well as outdoor workers

More information

Radford University. Indoor Air Quality Management Plan

Radford University. Indoor Air Quality Management Plan Radford University Indoor Air Quality Management Plan Spring 2015 Introduction Concerns with Indoor Air Quality (IAQ) have increased since energy conservation measures were instituted in office buildings

More information

Indoor Air Quality- What You Need to Know

Indoor Air Quality- What You Need to Know Indoor Air Quality- What You Need to Know Overview Indoor air quality (IAQ) concerns present ever-mounting problems to facility managers and health and safety personnel. From toxic mold to carbon dioxide

More information

SYNOPSIS. Improve Indoor Air Quality and Reduce Costs With Demand Controlled Ventilation. In this issue...

SYNOPSIS. Improve Indoor Air Quality and Reduce Costs With Demand Controlled Ventilation. In this issue... VOLUME THREE NUMBER FOUR SYNOPSIS A N H V A C N E W S L E T T E R F O R B U I L D I N G O W N E R S A N D M A N A G E R S In this issue... Demand Controlled Ventilation How CO2-based DCV effectively maintains

More information

IEQ-15 Air Distribution System

IEQ-15 Air Distribution System AIM OF CREDIT To encourage and recognise the design and maintenance of air distribution systems that minimise the risk of particulate and microbial contamination to the internal air supply. CREDIT CRITERIA

More information

Yes. Do you breathe clean air? Blueair Aware The Intelligent Air Quality Monitor

Yes. Do you breathe clean air? Blueair Aware The Intelligent Air Quality Monitor Yes Do you breathe clean air? No Blueair Aware The Intelligent Air Quality Monitor Blueair Aware Puts you in control of the air you breathe Connect with your clean air Knowing what s in the air you breathe

More information

PEOSH. Indoor Air Quality Training for Asthma-Friendly Schools Part I PEOSH Indoor Air Quality Standard Overview. Eric Weren, MSIH

PEOSH. Indoor Air Quality Training for Asthma-Friendly Schools Part I PEOSH Indoor Air Quality Standard Overview. Eric Weren, MSIH PEOSH Indoor Air Quality Training for Asthma-Friendly Schools Part I PEOSH Indoor Air Quality Standard Overview Eric Weren, MSIH Public Employees Occupational Safety and Health Unit IAQ Asthma-Friendly

More information

INDUSTRIAL VENTILATION AND SYSTEM TROUBLESHOOTING

INDUSTRIAL VENTILATION AND SYSTEM TROUBLESHOOTING INDUSTRIAL VENTILATION AND SYSTEM TROUBLESHOOTING Industrial Ventilation, Putting the Pieces Together Industrial Ventilation First Edition of the Industrial Ventilation Manual was published in 1951.

More information

A Simple Guide to Health Risk Assessment Office Environment Series OE 6/2003

A Simple Guide to Health Risk Assessment Office Environment Series OE 6/2003 A Simple Guide to Health Risk Assessment Office Environment Series OE 6/2003 Occupational Safety and Health Branch Labour Department Occupational Safety and Health Council Contents Introduction 1 Chemicals

More information

Biological Contamination in the HVAC System

Biological Contamination in the HVAC System Biological Contamination in the HVAC System by Chin S. Yang, Ph.D. P & K Microbiology Services, Inc. Cherry Hill, New Jersey The heating, ventilating, and air-conditioning system (HVAC) in a building is

More information

INVESTIGATION OF INDOOR AIR QUALITY PROBLEMS IN UNIVERSITY OFFICES WITH A QUESTIONNAIRE

INVESTIGATION OF INDOOR AIR QUALITY PROBLEMS IN UNIVERSITY OFFICES WITH A QUESTIONNAIRE INVESTIGATION OF INDOOR AIR QUALITY PROBLEMS IN UNIVERSITY OFFICES WITH A QUESTIONNAIRE Maneerat Ongwandee a, Namphung Dungkokkruad b a Faculty of Engineering, Mahasarakham University, Mahasarakham 44150,

More information

This booklet is prepared by the Occupational Safety and Health Branch, Labour Department. First edition January 2006

This booklet is prepared by the Occupational Safety and Health Branch, Labour Department. First edition January 2006 This booklet is prepared by the Occupational Safety and Health Branch, Labour Department First edition January 2006 This booklet is issued free of charge and can be obtained from offices of the Occupational

More information

INDOOR AIR QUALITY ASSESSMENT

INDOOR AIR QUALITY ASSESSMENT INDOOR AIR QUALITY ASSESSMENT Massachusetts Criminal Justice Training Council at the Boylston Town Offices Building 221 Main Street Boylston, Massachusetts Prepared by: Massachusetts Department of Public

More information

"An Office Building Occupant's Guide to Indoor Air Quality"

An Office Building Occupant's Guide to Indoor Air Quality "An Office Building Occupant's Guide to Indoor Air Quality" Office of Air and Radiation (OAR) Indoor Environments Division (6609J) Washington, DC 20460 EPA-402-K-97-003, October 1997 Contents A Summary

More information

PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE

PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE APPLICATION NOTE TI-138 TSI s IAQ-CALC TM Indoor Air Quality Meter and TH-CALC TM Thermohygrometer calculate Percent Outdoor Air (%OA). In order to take

More information

Workplace (Health,Safety and Welfare) Regulations 1992

Workplace (Health,Safety and Welfare) Regulations 1992 Document type INFORMATION PAPER Reference HEALTH AND SAFETY Issuing function EMPLOYMENT RELATIONS & UNION SERVICES Date of issue Workplace (Health,Safety and Welfare) Regulations 1992 THE CHARTERED SOCIETY

More information

Concept & Guidelines for Process Fume Filtration

Concept & Guidelines for Process Fume Filtration Technical Information Bulletin Concept & Guidelines for Process Fume Filtration 1. Concept and Benefits 2. Air Quality Verification 3. Application Specific Filtration Methods 4. Equipment Selection Matrix

More information

ASTHMA REGIONAL COUNCIL

ASTHMA REGIONAL COUNCIL ASTHMA REGIONAL COUNCIL WHAT S THAT SMELL? Simple Steps to Tackle School Air Problems ARC is a coalition of governmental and community agencies dedicated to addressing the environmental contributors to

More information

Risk Assessment for the Prevention of Heat Stroke at Work

Risk Assessment for the Prevention of Heat Stroke at Work Risk Assessment for the Prevention of Heat Stroke at Work This booklet is prepared by the Occupational Safety and Health Branch Labour Department This edition March 2009 qüáë=äççâäéí=áë=áëëìéç=ñêéé=çñ=åü~êöé=~åç=å~å=äé=çäí~áåéç=ñêçã=çññáåéë=çñ

More information

Essam E. Khalil khalile1@asme.org

Essam E. Khalil khalile1@asme.org AIR-CONDITIONING SYSTEMS DEVELOPMENTS IN HOSPITALS: COMFORT, AIR QUALITY, AND ENERGY UTILIZATION Essam E. Khalil khalile1@asme.org PROFESSOR OF MECHANICAL ENGINEERING, CAIRO UNIVERSITY, EGYPT Abstract

More information

OFFICE COPYING MACHINES

OFFICE COPYING MACHINES National Occupational Health and Safety Commission OFFICE COPYING MACHINES December 1989 Australian Government Publishing Service Canberra WAP 89/029 GS 003-1989 Commonwealth of Australia 1989 ISBN 0 644

More information

BCA Green Mark for Restaurants

BCA Green Mark for Restaurants BCA Green Mark for Restaurants Updated: 10/5/2011 1 Point Allocations - BCA Green Mark for Restaurants (I) Energy Related Requirements Part 1 : Energy Efficiency Category Point Allocations Minimum 20 points

More information

Charles McCammon, Ph.D., CIH

Charles McCammon, Ph.D., CIH This Health Hazard Evaluation (HHE) report and any recommendations made herein are for the specific facility evaluated and may not be universally applicable. Any recommendations made are not to to be considered

More information

17/11/03 03450. Operating of the models: 90H AND 190H. USER MANUAL Read and save these instructions

17/11/03 03450. Operating of the models: 90H AND 190H. USER MANUAL Read and save these instructions Operating of the models: 90H AND 190H USER MANUAL Read and save these instructions 17/11/03 03450 TABLE OF CONTENTS CONGRATULATIONS! You have made an excellent choice! We have prepared this user manual

More information

Mitsubishi Electric Guide to Ventilation. Information Guide 46

Mitsubishi Electric Guide to Ventilation. Information Guide 46 Mitsubishi Electric Guide to Ventilation Information Guide 46 Information Guide 46 Mitsubishi Electric Guide to Ventilation This is an independent guide produced by Mitsubishi Electric to enhance the

More information

S29 Workplace Health & Safety Welfare - 1 / 5

S29 Workplace Health & Safety Welfare - 1 / 5 S29 Opening Statement Workplace Health & Safety Welfare The welfare facility is often an area that is overlooked when inspecting and maintaining plant and equipment. It is also an area that is often used

More information

Construction Indoor Air Quality Management Plans for LEED. Matt Gregg, PE, LEED AP

Construction Indoor Air Quality Management Plans for LEED. Matt Gregg, PE, LEED AP Construction Indoor Air Quality Management Plans for LEED Matt Gregg, PE, LEED AP Agenda What is a Construction IAQ Management Plan? What are the LEED Requirements? What is the Mechanical Contractor s

More information

Guidelines for Employers and Employees. Prevention of Human Swine Influenza (Influenza A H1N1)

Guidelines for Employers and Employees. Prevention of Human Swine Influenza (Influenza A H1N1) Guidelines for Employers and Employees Prevention of Human Swine Influenza (Influenza A H1N1) Human Swine Influenza (Influenza A H1N1) Human Swine Influenza (Influenza A H1N1) is mainly transmitted through

More information

Particulate Dust Factors determining health effects of particulates

Particulate Dust Factors determining health effects of particulates Particulates When we think about particulates, its not just dust. It is made up of a vast array of materials Most of the materials are not wholesome, such as; soot, dander, sand, smoke, fibers, insects,

More information

ASTACEA4 Inspect complex/central air conditioning systems

ASTACEA4 Inspect complex/central air conditioning systems Overview This Unit covers the competences required to inspect complex/central air conditioning systems as defined by the CIBSE TM 44 Figure 1.1: Summary of system types and their component parts. The air

More information

Pollution Solid waste Dust Air Emissions Managing Dust

Pollution Solid waste Dust Air Emissions Managing Dust Pollution Key environmental issues for furniture and timber product manufacturers are: Solid waste Dust Noise Liquid waste Hazardous materials including chemicals Air emissions and odour. Solid waste Solid

More information

PERCENT OUTDOOR AIR CALCULATION AND ITS USE

PERCENT OUTDOOR AIR CALCULATION AND ITS USE PERCENT OUTDOOR AIR CALCULATION AND ITS USE APPLICATION NOTE AF-138 (A4 The RH720 calculates Percent Outdoor Air (%OA. In order to take advantage of this feature, it is important to first understand what

More information

FOOD SAFETY I FACT SHEET Ventilation of Food Premises

FOOD SAFETY I FACT SHEET Ventilation of Food Premises Food Safety Standard 3.2.3 under the Food Standard Code contains the design and construction requirements for food premises. A component of the requirements is that food premises be provided with natural

More information

Percent Outdoor Air (%OA) Calculation and Its Use Application Note TI-138

Percent Outdoor Air (%OA) Calculation and Its Use Application Note TI-138 Indoor Air Quality Percent Outdoor Air (%OA) Calculation and Its Use Application Note TI-138 TSI s IAQ-CALC TM Indoor Air Quality Meter and TH-CALC TM Thermohygrometer calculate Percent Outdoor Air (%OA).

More information

HVAC Systems. Alfred Woody, PE. Ventilation/Energy Applications, PLLC Norton Shores, Michigan

HVAC Systems. Alfred Woody, PE. Ventilation/Energy Applications, PLLC Norton Shores, Michigan HVAC Systems Alfred Woody, PE Ventilation/Energy Applications, PLLC Norton Shores, Michigan 231 798 3536 HVAC System Functions Control space temperature Heating Cooling Control space humidity Control airborne

More information

Federation of European Heating, Ventilation and Air-conditioning Associations

Federation of European Heating, Ventilation and Air-conditioning Associations Federation of European Heating, Ventilation and Air-conditioning Associations Address: Rue Washington 40 1050 Brussels Belgium www.rehva.eu info@rehva.eu Tel: +32 2 514 11 71 Fax: +32 2 512 90 62 Use of

More information

Indoor Environmental Quality Management Plan

Indoor Environmental Quality Management Plan Indoor Environmental Quality Management Plan Adopted by the Board of Education on March 12, 2012 1. Mission Statement School District of the Tomorrow River Indoor Environmental Quality Management Plan

More information

5th Edition. Food Service Workers Safety Guide. Prepared by the Canadian Centre for Occupational Health and Safety

5th Edition. Food Service Workers Safety Guide. Prepared by the Canadian Centre for Occupational Health and Safety 5th Edition Food Service Workers Safety Guide Prepared by the Canadian Centre for Occupational Health and Safety Summary Food preparation and service involves many safety and health hazards. Important

More information

DEA 350: HUMAN FACTORS: THE AMBIENT ENVIRONMENT (Spring 2008) HOMEWORK I PRINT THIS OUT AND HAND IT IN BY THE DUE DATE. [5 points per answer]

DEA 350: HUMAN FACTORS: THE AMBIENT ENVIRONMENT (Spring 2008) HOMEWORK I PRINT THIS OUT AND HAND IT IN BY THE DUE DATE. [5 points per answer] DEA 350: HUMAN FACTORS: THE AMBIENT ENVIRONMENT (Spring 2008) NAME: HOMEWORK I PRINT THIS OUT AND HAND IT IN BY THE DUE DATE Due Date: February 28th in class NOTE: Consult the course text and readings

More information

RECOMMENDATIONS FOR ENCLOSED ICE ARENA MANAGEMENT

RECOMMENDATIONS FOR ENCLOSED ICE ARENA MANAGEMENT RECOMMENDATIONS FOR ENCLOSED ICE ARENA MANAGEMENT PURPOSE Properly designed and operated indoor ice arenas can provide a safe environment for many recreational activities. However, indoor air quality problems

More information

Factors to be considered in Assessing the Risk of Outdoor Work under High Air Pollution Levels

Factors to be considered in Assessing the Risk of Outdoor Work under High Air Pollution Levels Introduction The Air Quality Health Index (AQHI) System, launched by the Environmental Protection Department (EPD), aims to communicate air pollution information to the public. Under the system, when the

More information

Manual 066 Requirements for Facilities For Sterile and Non-sterile Drug Manufacture

Manual 066 Requirements for Facilities For Sterile and Non-sterile Drug Manufacture 1 Purpose The purpose of this Guideline is to describe the requirements for meeting current Good Manufacturing Practice (cgmp) compliance requirements for new and upgraded facilities to be used for the

More information

Educational Performance, Environmental Management, and Cleaning Effectiveness in School Environments

Educational Performance, Environmental Management, and Cleaning Effectiveness in School Environments Educational Performance, Environmental Management, and Cleaning Effectiveness in School Environments By Michael A. Berry, Ph.D. 16 Charrington Place Chapel Hill, NC 27514 Phone: (919) 493-7409 E-mail:

More information

Workplace Health, Safety and

Workplace Health, Safety and Workplace Health, Safety and Welfare Code of Practice September 2004 Royal Free Hampstead NHS Trust & Royal Free & University College Medical School (Royal Free Campus) Workplace Page 1 of 7 CONTENTS 1.

More information

Energy and Mines Petroleum and Energy Branch 1395 Ellice Avenue Suite 360 Winnipeg MB R3G 3P2 CANADA

Energy and Mines Petroleum and Energy Branch 1395 Ellice Avenue Suite 360 Winnipeg MB R3G 3P2 CANADA Manitoba Energy and Mines Petroleum and Energy Branch 1395 Ellice Avenue Suite 360 Winnipeg MB R3G 3P2 CANADA PH: (204) 945-6577 PH: (204) 945-3760 FAX: (204) 945-0586 December 17, 1998 Informational Notice

More information

Planning Guidance for Food and Drink Establishments

Planning Guidance for Food and Drink Establishments Planning Guidance for Food and Drink Establishments ENVIRONMENT DIRECTORATE, CIVIC CENTRE, 44 YORK STREET, TWICKENHAM TW1 3BZ Planning Guidance for Food and Drink Establishments Introduction This guidance

More information

about your house How to Get the Ventilation That You Need in Your House Figure 1 Infiltration and exfiltration of air in a house

about your house How to Get the Ventilation That You Need in Your House Figure 1 Infiltration and exfiltration of air in a house about your house CE 64 How to Get the Ventilation That You Need in Your House Canadian houses are relatively airtight, and have been for years. The old farmhouses where people lived several generations

More information

Causes and Prevention of Symptom Complaints in Office Buildings: Distilling the Experience of Indoor Environment Quality Investigators

Causes and Prevention of Symptom Complaints in Office Buildings: Distilling the Experience of Indoor Environment Quality Investigators Causes and Prevention of Symptom Complaints in Office Buildings: Distilling the Experience of Indoor Environment Quality Investigators Mark J. Mendell, Richard C. Diamond, William J. Fisk Environmental

More information

Public Employees Occupational Safety and Health Program

Public Employees Occupational Safety and Health Program Public Employees Occupational Safety and Health Program Public Employer s Guide and Model Written Program for The Indoor Air Quality Standard (N.J.A.C. 12:100-13) (2007) Fred M. Jacobs, M.D., J.D. Jon

More information

SECTION 1: INTRODUCTION TO THE IAQ TOOL KIT... 1 SECTION 2: INTRODUCTION TO IAQ...

SECTION 1: INTRODUCTION TO THE IAQ TOOL KIT... 1 SECTION 2: INTRODUCTION TO IAQ... August 2009 Table of Contents SECTION 1: INTRODUCTION TO THE IAQ TOOL KIT...1 SECTION 2: INTRODUCTION TO IAQ...2 IAQ Health Concerns... 2 IAQ Sensitivity... 3 What are the Common Causes of IAQ Problems?...

More information

Indoor air quality monitoring made easy

Indoor air quality monitoring made easy Indoor air quality monitoring made easy with the Fluke 985 Particle Counter Application Note Introduction Energy savings is top of facilities owners agenda. HVAC system tends to be the largest contributor

More information

Safety in Manual Handling Operations

Safety in Manual Handling Operations Safety in Manual Handling Operations Supermarkets Occupational Safety and Health Branch Labour Department This guidebook is prepared by the Occupational Safety and Health Branch Labour Department This

More information

A Presentation on ENVIRONMENTAL STEWARDSHIP

A Presentation on ENVIRONMENTAL STEWARDSHIP A Presentation on ENVIRONMENTAL STEWARDSHIP 1 It s Our Environment Lets Take Action 2 Introducing Environmental Stewardship Stewardship of the environment refers to protecting the environment through recycling,

More information

Building Science Corporation

Building Science Corporation 70 Main Street Phone (978) 589-5100 Westford, MA 01886 Fax (978) 589-5103 www.buildingscience.com Relative Humidity Joseph Lstiburek, Ph.D., P.Eng. Presented at Healthy Indoor Environments (Austin TX),

More information

Indoor Environmental Quality Management Plan. School District of Hartford Jt #1 Adopted: January 28, 2013 Reviewed: September 23, 2015

Indoor Environmental Quality Management Plan. School District of Hartford Jt #1 Adopted: January 28, 2013 Reviewed: September 23, 2015 Indoor Environmental Quality Management Plan School District of Hartford Jt #1 Adopted: January 28, 2013 Reviewed: September 23, 2015 Mission Statement School buildings will be kept in good repair, suitably

More information

3M Personal Safety Division 3M Center, Building 0235-02-W-75 St. Paul, MN, USA 55144-1000 651 733 1110

3M Personal Safety Division 3M Center, Building 0235-02-W-75 St. Paul, MN, USA 55144-1000 651 733 1110 3M Personal Safety Division 3M Center, Building 0235-02-W-75 St. Paul, MN, USA 55144-1000 651 733 1110 3 24 March 2014 Respiratory Protection for Exposures to Particulate Air Pollution Air pollution is

More information

The Control of Legionella Bacteria in Water Systems

The Control of Legionella Bacteria in Water Systems Health and Safety Policy The Control of Legionella Bacteria in Water Systems UHSP/24/CLBWS/08 This document sets out in more detail the arrangements for compliance with University Health and Safety Policy

More information

INDOOR AIR QUALITY POST-OCCUPANCY ASSESSMENT. Massachusetts Department of Revenue 100 TradeCenter, Suite 760 Woburn, MA

INDOOR AIR QUALITY POST-OCCUPANCY ASSESSMENT. Massachusetts Department of Revenue 100 TradeCenter, Suite 760 Woburn, MA INDOOR AIR QUALITY POST-OCCUPANCY ASSESSMENT Massachusetts Department of Revenue 100 TradeCenter, Suite 760 Woburn, MA Prepared by: Massachusetts Department of Public Health Bureau of Environmental Health

More information

NORSOK STANDARD H-001 Rev. 4, Nov. 2001. Heating, ventilation and air-conditioning

NORSOK STANDARD H-001 Rev. 4, Nov. 2001. Heating, ventilation and air-conditioning NORSOK STANDARD H-001 Rev. 4, Nov. 2001 Heating, ventilation and air-conditioning This NORSOK standard is developed by NTS with broad industry participation. Please note that whilst every effort has been

More information

Safety in Offices and other General Areas

Safety in Offices and other General Areas Safety in Offices and other General Areas 1. INTRODUCTION This document covers health and safety in offices and other 'general areas' including corridors, stairs, entrances, small kitchens and rest areas.

More information

Welcome to the safe@work Office and Business Module.

Welcome to the safe@work Office and Business Module. Welcome to the safe@work Office and Business Module. Have you read the General Module, completed the test and printed your safe@work General Award of Attainment? The Office and Business Module should be

More information

INDOOR AIR QUALITY ASSESSMENT INCIDENT RESPONSE. Sgt. William H. Carney Memorial Academy 247 Elm Street New Bedford, Massachusetts

INDOOR AIR QUALITY ASSESSMENT INCIDENT RESPONSE. Sgt. William H. Carney Memorial Academy 247 Elm Street New Bedford, Massachusetts INDOOR AIR QUALITY ASSESSMENT INCIDENT RESPONSE Sgt. William H. Carney Memorial Academy 247 Elm Street New Bedford, Massachusetts Prepared by: Massachusetts Department of Public Health Bureau of Environmental

More information

Smoke-Free Environments

Smoke-Free Environments Smoke-Free Environments A Booklet For Day Care Providers Clean AirCouncil Smoke-Free Environments Table of Contents Introduction A Letter From Clean Air Council....................... 1 Information on

More information

A Breath of Poor Air: Inspecting Indoor Air Quality in the Classroom Ashley Schopieray

A Breath of Poor Air: Inspecting Indoor Air Quality in the Classroom Ashley Schopieray INTRODUCTION A Breath of Poor Air: Inspecting Indoor Air Quality in the Classroom Ashley Schopieray In this lesson students will learn about IAQ (indoor air quality) and the substances that could be polluting

More information

Mechanical Ventilation with Heat Recovery for Commercial Applications

Mechanical Ventilation with Heat Recovery for Commercial Applications Mechanical Ventilation with Heat Recovery for Commercial Applications A CPD course by AIRFLOW DEVELOPMENTS LTD Presented by Steven Mulholland Specification Manager Airflow Developments Ltd Innovators and

More information

UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01

UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01 GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per

More information

Breathing The Air In Your Home Is Like Living In A Closed Jar. It s Enough To Make You Sick.

Breathing The Air In Your Home Is Like Living In A Closed Jar. It s Enough To Make You Sick. Breathing The Air In Your Home Is Like Living In A Closed Jar. It s Enough To Make You Sick. Introducing A Fresh Approach To Indoor Air Quality: ConsERV TM Blows The Lid Off Indoor Air Pollution - You

More information

The heart of your home. A guide to high-efficiency natural gas heating systems

The heart of your home. A guide to high-efficiency natural gas heating systems The heart of your home A guide to high-efficiency natural gas heating systems Table of contents Replace or repair? 3 Before you buy a new system 4 Options and accessories 8 Three steps to a new system

More information

CHAPTER 4 VENTILATION

CHAPTER 4 VENTILATION CHAPTER 4 VENTILATION SECTION 401 GENERAL 401.1 Scope. This chapter, in conjunction with the building code, shall govern the ventilation of spaces within a building intended to be occupied. Mechanical

More information

Displacement ventilation

Displacement ventilation General The displacement ventilation principle is the oldest form of ventilation and can be achieved without the use of fans. Air movement occurs by means of the density differences between supply air

More information

WORKING IN CONFINED SPACES GUIDELINES

WORKING IN CONFINED SPACES GUIDELINES WORKING IN CONFINED SPACES GUIDELINES Contents 1 Introduction... 2 2 Scope... 2 3 Definitions... 2 4 Responsibilities... 3 4.1 Permit Authoriser... 3 4.2 Permit Receiver... 3 4.3 Responsible UOW Officer...

More information

DEMAND CONTROL VENTILATION AND SRI LANKAN APPLICATION A CASE STUDY

DEMAND CONTROL VENTILATION AND SRI LANKAN APPLICATION A CASE STUDY 407 DEMAND CONTROL VENTILATION AND SRI LANKAN APPLICATION A CASE STUDY Jayasinghe C. (a), Batagoda J.H. (b) (a) Professor, Department of Civil Engineering, University of Moratuwa, Sri Lanka E-mail: chintha@civil.mrt.ac.lk

More information

Author's personal copy

Author's personal copy FEATURE Identifying general laboratory requirements using a control banding strategy In a previous article, 1 we described how we used two ANSI standards (Z10 and Z9.5) to develop an institutional Laboratory

More information

AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries

AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries Hot tips and cool ideas to save energy and money! Air conditioning units or systems are often used by foundries

More information

Appendix B: Specification of requirements, Technical procurement of heat recycling systems in existing apartment blocks 1

Appendix B: Specification of requirements, Technical procurement of heat recycling systems in existing apartment blocks 1 Appendix B: Specification of requirements Technical procurement of heat recycling systems in existing apartment blocks Objective To develop complete systems for recycling heat from ventilation air in existing

More information

HEATING, VENTILATION & AIR CONDITIONING

HEATING, VENTILATION & AIR CONDITIONING HEATING, VENTILATION & AIR CONDITIONING as part of the Energy Efficiency Information Grants Program Heating and cooling can account for approximately 23 % of energy use in pubs and hotels 1. Reducing heating

More information

Indoor Air Quality. 2. Test and identify sources that contribute to poor indoor air quality.

Indoor Air Quality. 2. Test and identify sources that contribute to poor indoor air quality. Why is indoor air quality a concern? Safe air quality, both indoors and outdoors, is very important for health. In addition to poor outdoor air quality, indoor air quality is also a concern. Some examples

More information

There are several types of air cleaning devices available, each designed to remove certain types of pollutants.

There are several types of air cleaning devices available, each designed to remove certain types of pollutants. Please Note: EPA neither certifies nor recommends particular brands of home air cleaning devices. While some home air cleaning devices may be useful in some circumstances, EPA makes no broad endorsement

More information

Demand controlled ventilation A case study for existing Swedish multifamily buildings

Demand controlled ventilation A case study for existing Swedish multifamily buildings Energy and Buildings 36 (2004) 1029 1034 Demand controlled ventilation A case study for existing Swedish multifamily buildings Vitalijus Pavlovas Department of Building Technology, Building Services Engineering,

More information

Taking care of your indoor environment

Taking care of your indoor environment AMBISALUD INDOOR ENVIRONMENTAL QUALITY CONSULTANTS Taking care of your indoor environment UNE EN ISO 9001:2008 SCOPE OF SERVICES AMBISALUD INSPECTION AND CONSULTANCY AUDITS, INSPECTIONS TECHNICAL STUDIES

More information

Which filter class for supply air is required in a typical HVAC system?

Which filter class for supply air is required in a typical HVAC system? Which filter class for supply air is required in a typical HVAC system? Thomas Carlsson, Technical Director, Magnus Johnsson, Vokes Air Table of Contents: Background 2 Energy Demand 2 Air Quality and PM

More information

Indoor air quality. Save energy by improving indoor air quality with innovative CO 2. sensors

Indoor air quality. Save energy by improving indoor air quality with innovative CO 2. sensors Indoor air quality Save energy by improving indoor air quality with innovative CO 2 sensors (ppm) 2000 CO 2 concentration With windows closed and without forced ventilation Effect on people Lack of concentration

More information

Wildfire Smoke and Your Health

Wildfire Smoke and Your Health PUBLIC HEALTH DIVISION http://public.health.oregon.gov Wildfire Smoke and Your Health When smoke levels are high, even healthy people may have symptoms or health problems. The best thing to do is to limit

More information

1. IDENTIFICATION OF SUBSTANCE/MIXTURE AND OF THE COMPANY/UNDERTAKING.

1. IDENTIFICATION OF SUBSTANCE/MIXTURE AND OF THE COMPANY/UNDERTAKING. P a g e 1 1. IDENTIFICATION OF SUBSTANCE/MIXTURE AND OF THE COMPANY/UNDERTAKING. 2925 MFG Place Ashtabula, OH 44005 Emergency Telephone Number 1-800-424-9300 Regulatory Information Number 1-440-994-5207

More information