Operating Instructions (Compact) Issue 11/04. sinamics SINAMICS G110

Size: px
Start display at page:

Download "Operating Instructions (Compact) Issue 11/04. sinamics SINAMICS G110"

Transcription

1 Operating Instructions (Compact) Issue /4 sinamics SINAMICS G

2 Warnings, Cautions and Notes Issue /4 The Compact version of the Operating Instructions will cover the majority of typical applications. It is valid for inverters firmware versions. and.. For full details please refer to the Operating Instructions and the Parameter List. Warnings, Cautions and Notes The following Warnings, Cautions and Notes are provided for your safety and as a means of preventing damage to the product or components in the machines connected. Specific Warnings, Cautions and Notes that apply to particular activities are listed at the beginning of the relevant chapters and are repeated or supplemented at critical points throughout these chapters. Please read the information carefully, since it is provided for your personal safety and will also help prolong the service life of your SINAMICS G Inverter and the equipment you connect to it.! WARNING This equipment contains dangerous voltages and controls potentially dangerous rotating mechanical parts. Non-compliance with Warnings or failure to follow the instructions contained in this manual can result in loss of life, severe personal injury or serious damage to property. Only suitable qualified personnel should work on this equipment, and only after becoming familiar with all safety notices, installation, operation and maintenance procedures contained in this manual. The successful and safe operation of this equipment is dependent upon its proper handling, installation, operation and maintenance. The DC link of all SINAMICS G modules remains at a hazardous voltage level for 5 minutes after all voltages have been disconnected. Therefore always wait for 5 minutes after disconnecting the inverter from the power supply before carrying out work on any modules. The drive unit discharges itself during this time. The mains input, DC and motor terminals carry dangerous voltages even if the inverter is inoperative, wait 5 minutes to allow the unit to discharge after switching off before carrying out any installation work. During the parameter download with the STARTER commissioning tool or from the BOP to the inverter, the digital output may produce a spurious signal. Prior to performing a download to the inverter appropriate counter-measures must be taken to ensure that any suspended load is secured, for example, by the use of external brakes or the load being lowered to ground level and secured. SINAMICS G 2 Operating Instructions (Compact)

3 Issue /4 Warnings, Cautions and Notes NOTES This equipment is capable of providing internal motor overload protection in accordance with UL58C section 42 (refer to P6 and P335). I 2 t monitoring is ON by default. Motor overload protection can also be provided using an external PTC via a digital input. This equipment is suitable for use in a circuit capable of delivering not more than, symmetrical amperes (rms), for a maximum voltage of 23 V when protected by an H or K type fuse, a circuit breaker or self-protected combination motor controller. Use Class 75 C copper wire only with the cross-sections as specified in Section 2. The maximum permissible ambient temperature is, depending on the equipment, 4 C or 5 C (refer to Section 2.). Before installing and commissioning, please read these safety instructions and warnings carefully and all the warning labels attached to the equipment. Make sure that the warning labels are kept in a legible condition and replace missing or damaged labels. SINAMICS G Operating Instructions (Compact) Operating Instructions (Compact) 3

4 Warnings, Cautions and Notes Issue /4 SINAMICS G 4 Operating Instructions (Compact)

5 Issue /4 Contents Contents Installation Clearance distances for mounting Mounting dimensions Electrical Installation Technical specifications Power terminals Control terminals Block diagram Factory setting Specific factory settings for the analog version Specific factory settings for the USS version DIP switches... 4 Communications Establishing communications SINAMICS G STARTER... 5 BOP (Option) Buttons and their Functions Changing parameters using as an example P3 "Access level" Cloning parameters with the BOP Commissioning Quick commissioning Commissioning the application Serial interface (USS) Selection of command source Digital inputs (DIN) Digital output (DOUT) Selection of frequency setpoint Analog input (ADC) Motor potentiometer (MOP) Fixed frequency (FF) JOG Ramp-function generator (HLG) Reference / limit frequencies Motor control Inverter/motor protection Inverter-specific functions Series commissioning Parameter reset to factory setting Displays and messages LED status display Fault messages and Alarm messages SINAMICS G Operating Instructions (Compact) 5

6 Installation Issue /4 Installation. Clearance distances for mounting The inverters can be mounted adjacent to each other. If they are mounted on top of each other, however, a clearance of mm has to be observed. SIDE OF CABINET ENCLOSURE FSA FSB FSC mm Flat Plate variant only mm SIDE OF CABINET ENCLOSURE 5 mm > mm 3 mm 5 mm Fig. - Clearance distances for mounting.2 Mounting dimensions Frame Size Drilling Dimensions H mm (Inch) W mm (Inch) Tightening Torque Bolts Nm (lbf.in) A 4 (5.5) 79 (3.) 2xM4 B 35 (5.3) 27 (5.) 4xM4 2,5 (22.2) C 4 (5.5) 7 (6.7) 4xM5 4, (35.4) Fig. -2 Mounting dimensions SINAMICS G 6 Operating Instructions (Compact)

7 Issue /4 2 Electrical Installation 2 Electrical Installation 2. Technical specifications Order No. 6SL32- AC 2-24 V %, Hz AB -2xy* 2-5xy* 3xy* 5xy* 7xy* 2-xy* 2-5xy* 22-2xy* 23-xy* KB -2xy* 2-5xy* 3xy* 5xy* 7xy* Frame Size A B C Inverter Output kw,2,25,37,55,75,,5 2,2 3, Rating hp,6,33,5,75,,5 2, 3, 4, Output Current (perm. ambient temp.) Input Current (23 V) A.9 (5 C).7 (5 C) 2.3 (5 C) 3.2 (5 C) 3.9 (4 ºC) 6. (5 C) 7.8 (4 ºC). (5 C) 3.6 (4 ºC) A Recommended A Fuse 3NA Input Cable mm 2, - 2,5, - 2,5, - 2,5, - 2,5,5-2,5 2,5-6, 2,5-6, 4, - 6, - AWG Output Cable mm 2, - 2,5, - 2,5, - 2,5, - 2,5, - 2,5,5-6,,5-6, 2,5-2,5 - AWG Tightening Torque of power terminals Nm (lbf.in).96 (8.5).5 (3.3) 2.25 (9.9) * the last digit of the Order No. depends x = A/B with integrated filter y = A analog version on hardware and software changes x = U without filter y = B USS version 2.2 Power terminals Fig. 2- Power Terminals 2.3 Control terminals Term. Designation Function DOUT- Digital output (-) 2 DOUT+ Digital output (+) 3 DIN Digital input 4 DIN Digital input 5 DIN2 Digital input Isolated output +24 V / 5 ma 7 - Output V Variant Analog USS 8 - Output + V RS485 P+ 9 ADC Analog input RS485 N- - Output V SINAMICS G Operating Instructions (Compact) 7

8 2 Electrical Installation Issue /4 2.4 Block diagram Fig. 2-2 Inverter block diagram SINAMICS G 8 Operating Instructions (Compact)

9 Issue /4 3 Factory setting 3 Factory setting The SINAMICS G frequency inverter has already been programmed at the factory (motor parameters P34, P35, P37, P3), for standard V/f applications on Siemens 4-pole asynchronous motors LA that have the same power rating as the inverters Further factory setting Command sources P7 see Section 3./3.2 Setpoint source P see Section 3./3.2 Motor cooling P335 = (self-cooled) Motor current limit P64 = 5% Min. frequency P8 = Hz Max. frequency P82 = 5 Hz Ramp-up time P2 = s Ramp-down time P2 = s Control mode V/f P3 = (V/f with linear characteristic) 3. Specific factory settings for the analog version Digital input Terminals Parameter Function Command source 3, 4, 5 P7 = 2 Digital input Setpoint source 9 P = 2 Analog input Digital input 3 P7 = ON / OFF (I/O) Digital input 4 P72 = 2 Reverse ( ) Digital input 2 5 P73 = 9 Fault reset (Ack) Control method - P727 = Siemens standard control Fig. 3- Connections, analog version SINAMICS G Operating Instructions (Compact) 9

10 3 Factory setting Issue /4 3.2 Specific factory settings for the USS version Inputs Terminals Parameter Function Command source P7 = 5 Via the USS protocol Setpoint source P = 5 Frequency input via the USS protocol USS address 8, 9 P2 = USS address = USS baud rate P2 = 6 USS baud rate = 96 bps USS-PZD length P22 = 2 Two 6-bit words are in the PZD section of the USS telegram. Fig. 3-2 Connections, USS version SIMATIC S7-2 Bus termination G G G max. 3 SINAMICS Fig. 3-3 Example, USS bus 3.3 DIP switches The default motor base frequency of the SINAMICS G inverter is 5 Hz. For motors, which are designed for a base frequency of 6 Hz, the inverters can be set to this frequency via a DIP switch. Bus termination on USS variant It is necessary to terminate the last inverter on the network bus. This is achieved by setting the Bus Termination DIP switches (DIP switches 2 and 3) on the front of the inverter to the Bus Termination position (ON position). A common V reference (terminal ) is required between all devices on the USS bus. Fig. 3-4 Motor Base Frequency DIP Switch and Bus Termination SINAMICS G Operating Instructions (Compact)

11 Issue /4 4 Communications 4 Communications 4. Establishing communications SINAMICS G STARTER The following optional components are additionally required in order to establish communications between STARTER and SINAMICS G: PC <-> frequency inverter connecting kit (order no 6SL3255-AA-2AA) BOP, as far as the USS standard settings already kept in the Sinamics G shall be changed (order no 6SL3255-AA-4BA) PC <-> SINAMICS G connecting Kit SINAMICS G USS settings, refer to Section 6.2., Page 7. STARTER Menu, Options --> Set PG/PC interface --> Select "PC COM-Port (USS)" --> Properties --> Interface "COM", select a baud rate NOTE The USS parameter settings in the SINAMICS G frequency inverter and the settings in STARTER must match! SINAMICS G Operating Instructions (Compact)

12 5 BOP (Option) Issue /4 5 BOP (Option) 5. Buttons and their Functions Panel/ Button Function Effects Indicates Status Start converter Stop converter Change direction Jog motor The LCD displays the settings currently used by the converter. Pressing the button starts the converter. This button is disabled by default. Activate the button: P7 = or P79 =... 5 OFF OFF2 Pressing the button causes the motor to come to a standstill at the selected ramp down rate. This button is disabled by default. Activate the button: P7 = or P79 =... 5 Pressing the button twice (or once long) causes the motor to coast to a standstill. This function is always enabled. Press this button to change the direction of rotation of the motor. Reverse is indicated by a minus (-) sign or a flashing decimal point. Disabled by default. Activate the button: P7 = or P79 = In the " Power-on/Ready" state, when this key is pressed, the motor starts and rotates with the pre-set jog frequency. The motor stops when the button is released. Pressing this button when the motor is running has no effect. This button can be used to view additional information. It works by pressing and holding the button. It shows the following, starting from any parameter during operation:. DC link voltage (indicated by d units V) 2. output frequency (Hz) 3. output voltage (indicated by o units V). 4. The value selected in P5 (If P5 is set to show any of the above ( - 3) then this will not be shown again). Functions Additional presses will toggle around the above displays. Jump Function From any parameter (rxxxx or Pxxxx) a short press of the Fn button will immediately jump to r, you can then change another parameter, if required. Upon returning to r, pressing the Fn button will return you to your starting point. Acknowledgement If alarm and fault messages are present, then these can be acknowledged by pressing key Fn. Access Pressing this button allows access to the parameters. parameters Increase value Decrease value Pressing this button increases the displayed value. Pressing this button decreases the displayed value. SINAMICS G 2 Operating Instructions (Compact)

13 Issue /4 5 BOP (Option) 5.2 Changing parameters using as an example P3 "Access level" Step Result on display Press to access parameters 2 Press until P3 is displayed 3 Press to access the parameter value level 4 Press or to the required value (example: 3) 5 Press to confirm and store the value 6 Now access level 3 is set and all level to level 3 parameters are visible to the user. SINAMICS G Operating Instructions (Compact) 3

14 5 BOP (Option) Issue /4 5.3 Cloning parameters with the BOP A single parameter set can be uploaded from an inverter SINAMICS G and then downloaded into another SINAMICS G inverter. To clone a parameter set from one inverter to another, the following procedure should be performed: Upload (SINAMICS G BOP). Connect the BOP to the inverter SINAMICS G which parameters you wish to copy. 2. Ensure that it is safe to stop the inverter. 3. Stop the inverter. 4. Set parameter P3 to Set parameter P to 3 to enter Cloning Mode. 6. Set parameter P82 to to start the upload from the Inverter to the BOP. 7. During the upload BUSY will be displayed. 8. The BOP and the inverter will not react to any commands during upload. 9. If the upload has been completed successfully, the BOP display will return to normal and the inverter will return to a ready state.. If the upload has failed: Attempt another upload or perform a factory reset.. The BOP can now be removed from the inverter. Download (BOP SINAMICS G). Connect the BOP to the SINAMICS G inverter, in which the parameter set is to be downloaded. 2. Ensure power is applied to the inverter. 3. Set parameter P3 to Set parameter P to 3 to enter Cloning Mode. 5. Set parameter P83 to to start the download from the BOP to the inverter. 6. During the download BUSY will be displayed. 7. During download the BOP and the inverter will not react to any commands during download. 8. If the download has been completed successfully, the BOP display will return to normal and the inverter will return to a ready state. 9. If the download has failed: Attempt another download or perform a factory reset.. The BOP can now be removed from the inverter. NOTE The following important restrictions should be considered when using the Cloning procedure: Only the current dataset is uploaded to the BOP. Once the cloning procedure has started, it cannot be interrupted. It is possible to copy data from inverters of different power and voltage ratings. During download, if the data is not compatible with the inverter (e.g. different firmware releases) the default values for the parameter will be written to the inverter. During the cloning process any data already held by the BOP is overwritten. If the download or upload of data fails, the inverter will not function correctly. SINAMICS G 4 Operating Instructions (Compact)

15 Issue /4 6 Commissioning 6 Commissioning 6. Quick commissioning START The quick commissioning function will adapt the inverter to the motor and will set important technological parameters. The quick commissioning can be omitted if a 4-pole LA Siemens motor will be used, which matches the rating data of the frequency inverter. In order to have access to all motor parameters it is recommended to set the user access level P3=3 (see 5.2) Parameters, designated with a * offer more setting possibilities than are actually listed here. Refer to the parameter list for additional setting possibilities. Factory setting P = Commissioning parameter * Ready Quick commissioning 3 Factory setting NOTE P should be set to in order to parameterize the data of the motor rating plate. P =... Europe/ North America (enters the default motor base frequency and power settings hp/kw) P = Europe [kw], frequency default 5 Hz North America [hp], frequency default 6 Hz 2 North America [kw], frequency default 6 Hz P =, 2 NOTE For P = or, the setting of the DIP switch must be in line with the value of P (refer to the parameter list). NOTICE Motor parameters must be accurately configured for motor overload protection to operate correctly above 5 Hz. P34 =... P34 =... Rated motor voltage 23 V (Nominal motor voltage [V] from rating plate) The rated motor voltage on the rating plate must be checked, regarding the star/delta circuit configuration to ensure that it matches with the circuit connection configured at the motor terminal board P35 =... P35 =... Rated motor current (Nominal motor current [A] from rating plate) P3 P34 P37 P35 P38 P3 P37 =... P37 =... Rated motor power (Nominal motor power [kw/hp] from rating plate) If P = or 2, value will be in kw. If P =, value will be in in hp. FU-spec. FU-spec. SINAMICS G Operating Instructions (Compact) 5

16 6 Commissioning Issue /4 P38 =... P38 =... Rated motor cosphi (Nominal motor power factor (cos ) from rating plate) If the setting is, the value is automatically calculated P = : P38 no significance, no entry required. P39 =... P39 =... Rated motor efficiency (Nominal motor efficiency in [%] from rating plate) Setting causes internal calculation of value. P =, 2: P39 no significance, no entry required. P3 =... Rated motor frequency (Nominal motor frequency in [Hz] from rating plate) Pole pair number recalculated automatically if parameter is changed. 5. Hz P3 =... Rated motor speed (Nominal motor speed in [rpm] from rating plate) Setting causes internal calculation of value. NOTE For slip compensation, the input is absolutely necessary. FU-spec. P335 =... Motor cooling (Selects motor cooling system used) Self-cooled: Using shaft mounted fan attached to motor Force-cooled: Using separately powered cooling fan P64 =... Motor overload factor (Motor overload factor in [%] relative to P35) 5 % This defines the limit of the maximum output current as a % of the rated motor current (P35). P7 =... Selection of command source (see Section "Selection of command source") 2 / 5 Factory default setting BOP (keypad) 2 Terminal 5 USS P =... Selection of frequency setpoint (see Section "Selection of frequency setpoint") MOP setpoint 2 Analog setpoint 3 Fixed frequency 5 USS 2 / 5 P8 =... Min. frequency (enters the minimum motor frequency in Hz). Hz Sets minimum motor frequency at which motor will run irrespective of frequency setpoint. The value set here is valid for both clockwise and anticlockwise rotation. P82 =... Max. frequency (enters the maximum motor frequency in Hz) Sets maximum motor frequency at which motor will run irrespective of the frequency setpoint. The value set here is valid for both clockwise and anticlockwise rotation. 5. Hz P2 =... Ramp-up time (enters the ramp-up time in s). s Time taken for motor to accelerate from standstill up to maximum motor frequency (P82) when no rounding is used. P2 =... Ramp-down time (enters the deceleration time in s). s Time taken for motor to decelerate from maximum motor frequency (P82) down to standstill when no rounding is used P35 =... OFF3 ramp-down time (enters the fast stop ramp-down time in s) Defines ramp-down time from maximum frequency to standstill for OFF3 command. 5. s SINAMICS G 6 Operating Instructions (Compact)

17 Issue /4 6 Commissioning P3 =... P39 = END Control mode (enters the required control mode) V/f with linear characteristic 2 V/f with quadratic characteristic 3 V/f with programmable characteristic End of quick commissioning (means: the start of the motor calculation) No quick commissioning (no motor calculations) End quick commissioning, with factory reset of all other settings 2 End quick commissioning, with factory reset of I/O settings 3 End quick commissioning, without reset of all other settings NOTE For P39 =,2,3 P34 is internally set to and the appropriate data calculated (refer to the parameter list P34). P39=3 is useful in case of motor change End of quick commissioning/ drive setting If additional functions must be implemented at the drive inverter, use the following Section "Commissioning the application". We recommend this procedure for drives with a high dynamic response. 6.2 Commissioning the application START An application is commissioned to adapt/optimize the frequency inverter - motor combination to the particular application. The frequency inverter offers numerous functions - but not all of these are required for the particular application. These functions can be ignored when commissioning the application. A large portion of the possible functions are described here; refer to the parameter list for additional functions. Parameters, designated with a * offer more setting possibilities than are actually listed here. Refer to the parameter list for additional setting possibilities. P3 = 3 User access level * Standard (Allows access into most frequently used parameters) 2 Extended (Allows extended access e.g. to inverter I/O functions) 3 Expert (for expert use only) Factory setting 6.2. Serial interface (USS) P2 =... P2 =... P22 =... P23 =... USS baud rate Sets baud rate for USS communication. USS address Sets unique address for inverter. USS PZD length Defines the number of 6-bit words in PZD part of USS telegram. USS PKW length 27 Defines the number of 6-bit words in PKW part of USS telegram. 6 2 Possible Settings: 3 2 baud 4 24 baud 5 48 baud 6 96 baud 7 92 baud baud baud SINAMICS G Operating Instructions (Compact) 7

18 6 Commissioning Issue / Selection of command source P7 =... Selection of command source 2 / 5 P7 G AIN G USS Settings Selects digital command source. X X Factory fault setting X X BOP (keypad) 2 Terminal 2 X X See USS 5 X See Digital inputs (DIN) P7=... Function of digital input Terminal 3 P72 =... Function digital input Terminal 4 2 P73 =... Function digital input 2 Terminal 5 9 P74 =... Function digital input 3 Via analog input (AIN version only) Terminals 9, FF selection (5, 6) not possible P724 =... Debounce time for digital inputs 3 Defines debounce time (filtering time) used for digital inputs. No debounce time 2.5 ms debounce time ms debounce time ms debounce time P727 =... 2-wire/3wire control method Determines the control method using the terminals Siemens Standard (Start / Direction) 2-wire (FWD / REV) 2 3-wire (FWD P / REV P) 3 3-wire (Start P / Direction) Possible Settings: Digital input disabled ON / OFF 2 ON Reverse / OFF 3 OFF2 coast to standstill 4 OFF3 quick ramp-down 9 Fault acknowledge JOG right JOG left 2 Reverse 3 MOP up (increase frequency) 4 MOP down (decrease frequency) 5 Fixed setpoint (Direct selection) 6 Fixed setpoint (Direct selection + ON) 2 Local/remote 25 DC brake enable 29 External trip See P727 for redefinition of settings, 2, 2 "P" denotes "Pulse"; "FWD" denotes "FORWARD"; "REV" denotes "REVERSE" Redefined Digital Inputs Settings P7 P74 P727= Siemens standard control P727= 2-wire control P727=2 3-wire control P727=3 3-wire control ON/OFF ON_FWD STOP ON_PULSE 2 ON REV/OFF ON_REV FWDP OFF/HOLD 2 REV REV REVP REV DIN channel Kl.6 P24 Kl.7 V Debounce time for digital inputs... 3 P724 (3) Function of digital input P7 () V 24 V T & r722 r722 CO/BO: Binary input values Function SINAMICS G 8 Operating Instructions (Compact)

19 Issue /4 6 Commissioning Digital output (DOUT) P73 =... Function of digital output * Defines source of digital output. 5 P748 = Invert digital output Allows the signals to be output to be inverted. Status of DOUT at logically active signal ( = Open; = Closed) Frequent settings: Active Status Not Active Active 2 Drive ready 3 Drive ready to run 4 Drive running 5 Drive fault active 6 OFF2 active 7 OFF3 active 8 Switch on inhibit active 9 Drive warning active Deviation between f set and f act < 3 Hz PZD control (P7=5) 2 Act. Freq P82 (f max ) 3 Warning: Motor current limit 4 Motor holding brake active* 5 Motor overload - - High High High High Low Low High High High High High High High High *Note: Motor holding brake active means the brake is open. (always) (always) DOUT channel Function of digital output P73 (5) Functions Invert digital outputs... P748 () - CO/BO: State of digital outputs r747 r DOUT+ 24 V DC 5 ma DOUT Selection of frequency setpoint P =... Selection of frequency setpoint No main setpoint MOP setpoint 2 Analog setpoint 3 Fixed frequency 5 USS 2 / 5 P G AIN G USS Settings X X X X see X see X X see X see 6.2. SINAMICS G Operating Instructions (Compact) 9

20 6 Commissioning Issue / Analog input (ADC) P757 =... P758 =... P759 =... Value x of ADC scaling Value y of ADC scaling. % This parameter represents the value of x as a % of P2 (reference frequency). Value x2 of ADC scaling V V P76 > < P758 < P76 > P758 > P76 % % 4 h max P76 P76 =... P76 =... Value y2 of ADC scaling. % This parameter represents the value of x2 as a % of P2 (reference frequency). Width of ADC deadband V Defines width of deadband on analog input. P758 min P76 P757 P757 = P76 P759 V x % V ADC channel KL8 + V KL9 KL A D P753 P757 P758 P759 P76 ADC scaling r754 P76 P = 2 ADC dead zone Setpoint.7 V 3.9 V r752 r722 r722.3 P74 = x Function Motor potentiometer (MOP) P3 =... P32 =... P4 =... Setpoint memory of the MOP Saves last motor potentiometer setpoint (MOP) that was active before OFF command or power down. MOP setpoint will not be stored MOP setpoint will be stored (P4 is updated) Inhibit negative MOP setpoints Neg. MOP setpoint is allowed Neg. MOP setpoint inhibited Setpoint of the MOP Determines setpoint for motor potentiometer control. MOP ramp-up and ramp-down times are defined by the parameters P2 and P2. 5. Hz Possible parameter settings for the selection of MOP: Selection P79 =, P7 = 2, P = DIN or P79 =, P7 = 2 P79 =, P7 =, P = or BOP P79 =, P7 = or P79 = P79 =, P7 = 5, P = or USS * ) P79 =, P7 = 5 or P79 = 5 *) SINAMICS G CPM USS only MOP up P72 = 3 (DIN) UP button USS control word r236 Bit3 MOP down P73 = 4 (DIN2) DOWN button USS control word r236 Bit4 SINAMICS G 2 Operating Instructions (Compact)

21 Issue /4 6 Commissioning Fixed frequency (FF) There are 2 types of fixed frequencies:. Direct selection (P7 P73 =5) 2. Direct selection + ON command (P7 P73 = 6) For P727 = 2, 3: if more than one setting 6 is used, each time the digital input (set to 6) receives a pulse, it will delatch the previously assigned fixed frequency thus overwriting the previously fixed frequency. For P727=, 2, 3: at least one of the digital inputs is requested to be assigned setting 6 to allow an ON command to be issued P =... Fixed frequency Defines the setpoint for the fixed frequency (FF) in Hz. Hinweis: Can be directly selected via DIN or USS (P7 = 5, 6). P2 =... Fixed frequency 2 Can be directly selected via DIN or USS (P7 = 5, 6). P3 =... Fixed frequency 3 Can be directly selected via DIN2 or USS (P7 = 5, 6) JOG. Hz 5. Hz. Hz P58 =... P6 =... JOG frequency 5. Hz Frequency in Hz when the motor is being jogged in the selected direction of rotation. JOG ramp-up/down time. s Ramp-up/down time. The JOG ramp-up is limited by P58. JOG P82 (f max ) P58 f P6 P6 t SINAMICS G Operating Instructions (Compact) 2

22 6 Commissioning Issue / Ramp-function generator (HLG) P9 =... Skip frequency (entered in Hz). Hz Defines skip frequency which avoids effects of mechanical resonance and suppresses frequencies within +/- 2 Hz (skip frequency bandwidth). f out 2 Hz P2 =... P2 =... P3 =... P34 =... P35 =... Ramp-up time (enters the accelerating time in s) Ramp-down time (enters the deceleration time in s) Rump-up initial rounding time (entered in s) Rounding type Continuous smoothing Discontinuous smoothing. s. s. s P82 (f max ) f f P2 P9 f in P2 OFF3 ramp-down time Defines ramp-down time from maximum frequency to standstill for OFF3 command. t 5. s 6.2. Reference / limit frequencies P8 =... P82 =... P2 =... Min. frequency (entered in Hz). Hz Sets minimum motor frequency [Hz] at which motor will run irrespective of frequency setpoint. If the setpoint falls below the value of P8, then the output frequency is set to P8 taking into account the sign. Max. frequency (entered in Hz) 5. Hz Sets maximum motor frequency [Hz] at which motor will run irrespective of the frequency setpoint. If the setpoint exceeds the value P82, then the output frequency is limited. The value set here is valid for both clockwise and anticlockwise rotation. Reference frequency (entered in Hz) 5. Hz The reference frequency in Hertz corresponds to a value of %. This setting should be changed if a maximum frequency of higher than 5 Hz is required. It is automatically changed to 6 Hz if the standard 6 Hz frequency was selected using the DIP5/6 switch or P. NOTE This reference frequency effects the setpoint frequency since both the analog setpoints (% P2) as well as the frequency setpoints via USS (4H P2) refer to this value Motor control P3 =... Control mode The control type is selected using this parameter. For the "V/f characteristic" control type, the ratio between the frequency inverter output voltage and the frequency inverter output frequency is defined. V/f with linear 2 V/f with quadratic characteristic 3 V/f with programmable characteristic ( P32 P325) SINAMICS G 22 Operating Instructions (Compact)

23 Issue /4 6 Commissioning P3 =... Continuous boost (entered in %) 5. % Voltage boost as a % relative to P35 (rated motor current) and P35 (stator resistance). P3 is valid for all V/f characteristics (refer to P3). At low output frequencies, the effective resistance values of the winding must be taken into account in order to maintain the motor flux. V Boost voltage Linear V/f Vmax Validity range Vn (P34) V ConBoost, actual V V ConBoost,5 Boost Output voltage Normal V/f (P3 = ) ON OFF f P3 active t t t f Boost,end fn (P36) (P3) f max (P82) f P3 =... Acceleration boost (entered in %). % Voltage boost for accelerating/braking as a % relative to P35 and P35. P3 only results in a voltage boost when ramping-up/ramp-down and generates an additional torque for accelerating/braking. Contrary to parameter P32, that is only active for the st acceleration operation after the ON command, P3 is effective each time that the drive accelerates or brakes. P32 =... Starting boost (entered in %). % Voltage boost when starting (after an ON command) when using the linear or quadratic V/f characteristic as a % relative to P35 (rated motor current) or P35 (stator resistance). The voltage boost remains active until ) the setpoint is reached for the first time and 2) the setpoint is reduced to a value that is less than the present ramp-function generator output. P32 =... Programmable V/f freq.. Hz coord. Sets V/f coordinates (P32/32 to P324/325) to define V/f characteristic. P32 =... P322 =... P323 =... P324 =... P325 =... Programmable V/f volt. coord. Programmable V/f freq. coord. 2 Programmable V/f volt. coord. 2 Programmable V/f freq. coord. 3 Programmable V/f volt. coord. 3. Hz. Hz. Hz. Hz. Hz P334 =... Slip compensation activation range (entered in %) Starting point for slip compensation is P334 x P3. Upper threshold is always P % 6. % P335 =... Slip compensation (entered in %). % Dynamically adjusts output frequency of inverter so that motor speed is kept constant independent of motor load. SINAMICS G Operating Instructions (Compact) 23

24 6 Commissioning Issue / Inverter/motor protection P29 =... Inverter overload reaction Selects reaction of inverter to an internal overtemperature Reduce output frequency Trip (F4 / F5) P335 =... Motor cooling (enters the motor cooling system) Self-cooled: Using shaft mounted fan attached to motor Force-cooled: Using separately powered cooling fan P6 =... Motor I 2 t reaction Defines reaction when motor I t reaches warning threshold. 2 Warning, no reaction, no trip Warning, I max reduction, 2 Warning, no I max reduction, trip F P6 =... Motor I 2 t time constant (entered in s) s The time until the thermal limit of a motor is reached, is calculated via the thermal time constant. A higher value increases the time at which the motor thermal limit is reached. The value of P6 is estimated according to the motor data during quick commissioning or is calculated using P34 (Calculating of the motor parameters). When the calculation of motor parameters during quick commission is complete the stored value can be replaced by the value given by the motor manufacturer P64 =... Motor I 2 t warning level (entered in %) Defines the value at which alarm A5 (motor overtemperature) is generated. r27 2 P35 r2 P3 P6 P335 t r34 ( i 2 t ) Trip threshold. P64 Motor i2t temp. reaction P6 P64 Warning threshold F I_max reduction A5. % P64 =... Motor overload factor [%] 5. % Defines motor overload current limit in [%] relative to P35 (rated motor current). Limited to maximum inverter current or to 4 % of rated motor current (P35), whichever is the lower Inverter-specific functions Flying start P2 =... Flying start Starts inverter onto a spinning motor by rapidly changing the output frequency of the inverter until the actual motor speed has been found. Flying start disabled Flying start is always active, start in direction of setpoint 2 Flying start is active if power on, fault, OFF2, start in direction of setpoint 3 Flying start is active if fault, OFF2, start in direction of setpoint 4 Flying start is always active, only in direction of setpoint 5 Flying start is active if power on, fault, OFF2, only in direction of setpoint 6 Flying start is active if fault, OFF2, only in direction of setpoint P22 =... Motor-current: Flying start (entered in %) Defines search current used for flying start.relative to rated motor current (P35) P23 =... Search rate: Flying start (entered in %) % Sets factor by which the output frequency changes during flying start to synchronize with turning motor. % SINAMICS G 24 Operating Instructions (Compact)

25 Issue /4 6 Commissioning Automatic restart P2 =... Automatic restart Configures automatic restart function. Disabled Trip reset after power on 2 Restart after mains blackout 3 Restart after mains brownout or fault 4 Restart after mains brownout 5 Restart after mains blackout and fault 6 Restart after mains brown/blackout or fault Holding brake P25 =... Holding brake enable Enables/disables holding brake function (MHB). MBH disabled MBH enabled NOTE The MHB is controlled via the signal of status word r52 bit 2. This signal can be issued via the digital output DOUT with parameter setting P73=4 for controlling an external brake relay. In firmware version. r52 bit 2 will be set when P26 time has been passed. P26 =... Holding brake release delay (entered in s). s Defines the time interval during which the frequency inverter runs with the min. frequency P8, before ramping up P27 =... Holding time after ramp-down (entered in s). s Defines time for which inverter runs at minimum frequency (P8) after ramping down DC braking & Compound braking P232 =... DC braking current (entered in %) Defines level of DC current in [%] relative to rated motor current (P35). % P233 =... Duration of DC braking (entered in s) s Defines duration for which DC injection braking is to be active following an OFF or OFF3 command. P234 =... DC braking start frequency (entered in Hz) Sets the start frequency for DC braking 65 Hz P236 =... Compound braking current (entered in %) % Defines DC level superimposed on AC waveform after exceeding DC link voltage threshold of compound braking. This value is entered in % relative to rated motor current (P35). P236= Compound braking disabled P236= - 25 Level of DC braking current defined as % of rated motor current P35 SINAMICS G Operating Instructions (Compact) 25

26 6 Commissioning Issue / Vdc controller P24 =... Configuration of Vdc controller Enables / disables Vdc controller. Vdc controller disabled Vdc-max controller enabled NOTE P24 = prevents an overvoltage condition of the DC link (F2) in regenerative operation by extending the ramp down time. SINAMICS G 26 Operating Instructions (Compact)

27 Issue /4 7 Displays and messages 6.3 Series commissioning An existing parameter set can be transferred to a SINAMICS G frequency inverter using STARTER or BOP (see 5.3). Typical applications for series commissioning include:. If several drives are to be commissioned that have the same configuration and same functions. A quick / application commissioning (first commissioning) must be carried-out for the first drive. Its parameter values are then transferred to the other drives. 2. When replacing SINAMICS G frequency inverters. 6.4 Parameter reset to factory setting START P=3 Commissioning parameter 3 Factory setting P97 = END Factory reset disabled Parameter reset The drive inverter carries-out a parameter reset (duration, approx. s) and then automatically exits the reset menu and sets: P97 = : disabled P = : ready 7 Displays and messages 7. LED status display LED Meaning Position LED Off Inverter Off / No supply LED ms On/ ms Off Power On / Ready LED On steadily Inverter Running 5 ms On / 2 ms Off General Warning ms On / ms Off Fault Condition 7.2 Fault messages and Alarm messages Fault Significance Alarms Significance F Overcurrent A5 Current Limit F2 Overvoltage A52 Overvoltage limit F3 Undervoltage A53 Undervoltage Limit F4 Inverter Overtemperature A55 Inverter I 2 t F5 Inverter I 2 t A5 Motor Overtemperature I 2 t F Motor Overtemperature I 2 t A9 Vdc-max controller de-activated F5 Parameter EEPROM Fault A9 Vdc-max controller active F52 Powerstack Fault A92 ADC parameters not set properly F6 Asic Timeout A923 F72 F85 USS setpoint fault External Fault Both JOG Left and JOG Right are requested SINAMICS G Operating Instructions (Compact) 27

28 SINAMICS G Operating Instructions (Compact) Information about SINAMICS G is also available from: Regional Contacts Please get in touch with your contact for Technical Support in your Region for questions about services, prices and conditions of Technical Support. Central Technical Support The competent consulting service for technical issues with a broad range of requirements-based services around our products and systems. Europe / Africa Tel: +49 () Fax: +49 () adsupport@siemens.com America Tel: Fax: simatic.hotline@sea.siemens.com Asia / Pacific Tel: Fax: adsupport.asia@siemens.com Online Service & Support The comprehensive information system available round the clock via the Internet, ranging from Product Support and Service & Support services to the Support Tools in the Shop. Internet Home Address Customers can access technical and general information at: Siemens AG Automation & Drives Standard Drives Postfach 3269, D 95 Erlangen Germany Siemens AG 24 Subject to change without prior notice Issue /4

SINAMICS BOP-2. Basic Operator Panel 2. Operating Instructions March 2010 SINAMICS

SINAMICS BOP-2. Basic Operator Panel 2. Operating Instructions March 2010 SINAMICS SINAMICS BOP-2 Basic Operator Panel 2 Operating Instructions March 2010 SINAMICS Safety notes 1 Overview 2 SINAMICS SINAMICS Operating Instructions Installation 3 Monitoring 4 Control 5 Diagnostics 6

More information

AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5

AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5 AMFA-27 AMFA-29 Operator s Manual & Installation Instructions Rev. 2.5 Date: 17 July, 2010 Permanently-connected, utility Interactive, single-phase, inverters Model AMFA-27 WIND TURBINE INVERTER (240 VAC

More information

ΑΣΚΗΣΗ 8 η L 1 L 2 L 3. «Σταθεροποίηση των στροφών Ασύγχρονων Τριφασικών κινητήρων με μεταβολή της συχνότητας της τάσης τροφοδοσίας»

ΑΣΚΗΣΗ 8 η L 1 L 2 L 3. «Σταθεροποίηση των στροφών Ασύγχρονων Τριφασικών κινητήρων με μεταβολή της συχνότητας της τάσης τροφοδοσίας» ΑΣΚΗΣΗ 8 η «Σταθεροποίηση των στροφών Ασύγχρονων Τριφασικών κινητήρων με μεταβολή της συχνότητας της τάσης τροφοδοσίας» Χρησιμοποιούμενα Όργανα Ασύγχρονος Τριφασικός Κινητήρας Φορτίο (Ηλεκτρομαγνητική

More information

SED2 Variable Frequency Drives. Operation & Maintenance Manual

SED2 Variable Frequency Drives. Operation & Maintenance Manual SED2 Variable Frequency Drives Operation & Maintenance Manual SED2 VFD Operation & Maintenance Manual SED2 Variable Frequency Drives Operation & Maintenance Manual 125-3202 Rev. EA, November, 2006 SED2

More information

NX Series Inverters. HVAC Pocket Programming Guide

NX Series Inverters. HVAC Pocket Programming Guide NX Series Inverters HVAC Pocket Programming Guide HVAC Pocket Programming Guide HVAC Pocket Programming Guide / Contents This guide provides a single reference document for the user of NXL HVAC (product

More information

VLT 6000 HVAC. Contents

VLT 6000 HVAC. Contents Contents Introduction Safety...3 Safety Guidelines...3 Warnings Against Unintended Start...3 Introduction...4 About this manual...4 Assumptions...4 References...4 Trademarks...5 Programming the VLT 6000

More information

Siemens AG 2011 SINAMICS V60. The perfect solution for basic servo applications. Brochure May 2011 SINAMICS. Answers for industry.

Siemens AG 2011 SINAMICS V60. The perfect solution for basic servo applications. Brochure May 2011 SINAMICS. Answers for industry. The perfect solution for basic servo applications Brochure May 2011 SINAMICS Answers for industry. with 1FL5 servomotors The solution for basic servo applications There is a requirement to automate motion

More information

A1000 Cheat Sheet (Open Loop Vector)

A1000 Cheat Sheet (Open Loop Vector) A1000 Cheat Sheet (Open Loop Vector) The following procedure is a supplement to supplied with this equipment and will guide the user in properly wiring the A1000 and. It will also show the user how to

More information

MICROMASTER 420. User Documentation 6SE6400-5BA00-0BP0

MICROMASTER 420. User Documentation 6SE6400-5BA00-0BP0 MICROMASTER 40 Parameter List Issue04/0 User Documentation 6SE6400-5BA00-0BP0 Getting Started Guide Is for quick commissioning with SDP and BOP. Operating Instructions Gives information about features

More information

Permissible ambient temperature Operation Storage, transport

Permissible ambient temperature Operation Storage, transport The Sitras PRO combined DC protective unit and controller is used in the power supply for DC railways in mass transit and main-line systems up 3,000 V DC. It protects DC switch gear and contact line systems

More information

SINAMICS G120. Control Units CU240E CU240S CU240S DP CU240S DP-F CU240S PN CU240S PN-F. Operating Instructions 03/2009 SINAMICS. Answers for industry.

SINAMICS G120. Control Units CU240E CU240S CU240S DP CU240S DP-F CU240S PN CU240S PN-F. Operating Instructions 03/2009 SINAMICS. Answers for industry. SINAMICS G120 Control Units CU240E CU240S CU240S DP CU240S DP-F CU240S PN CU240S PN-F Operating Instructions 03/2009 SINAMICS Answers for industry. Introduction 1 Description 2 SINAMICS SINAMICS G120

More information

Number 1 in efficiency

Number 1 in efficiency PowerXL DE1 Variable Speed Starter www.eaton.eu/de1 Number 1 in efficiency The easiest way of variable motor speed NEW Variation DE11 The new device category! The PowerXL DE1 Variable Speed Starter Why

More information

GPD 506/P5 Start-up Procedure and Checklist

GPD 506/P5 Start-up Procedure and Checklist GPD 506/P5 Start-up Procedure and Checklist Preparation for GPD506/P5 Drive Start-Up...2 HVAC Start-Up Procedure for GPD 506/P5 WITH Bypass Option:...4 HVAC Start-Up Procedure for GPD 506/P5 WITHOUT Bypass

More information

SINAMICS drives SINAMICS DCM. DC converters from 6 kw to 2500 kw for variable-speed direct-current drives. Load-balanced control application

SINAMICS drives SINAMICS DCM. DC converters from 6 kw to 2500 kw for variable-speed direct-current drives. Load-balanced control application SINAMICS DCM DC converters from 6 kw to 2500 kw for variable-speed direct-current drives Edition 01-12/2010 SINAMICS drives SINAMICS DCM Compact User Manual Legal information Warning notice system This

More information

ABB i-bus EIB Logic Module LM/S 1.1

ABB i-bus EIB Logic Module LM/S 1.1 Product Manual ABB i-bus EIB Logic Module LM/S 1.1 Intelligent Installation System Contents page 1 General... 3 1.1 About this manual... 3 1.2 Product and functional overview... 3 2 Device technology...

More information

Automation System TROVIS 6400 TROVIS 6493 Compact Controller

Automation System TROVIS 6400 TROVIS 6493 Compact Controller Automation System TROVIS 6400 TROVIS 6493 Compact Controller For panel mounting (front frame 48 x 96 mm/1.89 x 3.78 inch) Application Digital controller to automate industrial and process plants for general

More information

Technical Manual. FAN COIL CONTROLLER COOLING or HEATING ANALOG or PWM Art. 119914 631001A

Technical Manual. FAN COIL CONTROLLER COOLING or HEATING ANALOG or PWM Art. 119914 631001A COOLING or HEATING ANALOG or PWM Art. 119914 631001A TOTAL AUTOMATION GENERAL TRADING CO. LLC SUITE NO.506, LE SOLARIUM OFFICE TOWER, SILICON OASIS, DUBAI. UAE. Tel. +971 4 392 6860, Fax. +971 4 392 6850

More information

CAT AVR V2.3. Instruction Manual. Voltage regulator for generators. March 2008

CAT AVR V2.3. Instruction Manual. Voltage regulator for generators. March 2008 CAT AVR V2.3 Voltage regulator for generators March 2008 Instruction Manual Warnings WARNING The system should not be installed, operated, serviced or modified except by qualified personnel who understand

More information

SJ200 Series Inverter Quick Reference Guide

SJ200 Series Inverter Quick Reference Guide SJ2 Series Inverter Quick Reference Guide Single-phase Input 2V Class Three-phase Input 2V Class Three-phase Input 4V Class Hitachi Industrial Equipment Systems Co., Ltd. Manual No. NB6501XA March 24 Caution:

More information

32VFD Variable Frequency Drives for Centrifugal Chillers

32VFD Variable Frequency Drives for Centrifugal Chillers 32VFD 32VFD Variable Frequency Drives for Centrifugal Chillers ENERGY-SAVING CONTROL FOR CENTRIFUGAL CHILLERS Reduce energy consumption in your existing centrifugal chiller Your chiller was specified to

More information

Getting Started - SINAMICS Startdrive. Startdrive. SINAMICS Getting Started - SINAMICS Startdrive. Introduction 1

Getting Started - SINAMICS Startdrive. Startdrive. SINAMICS Getting Started - SINAMICS Startdrive. Introduction 1 Introduction 1 Connecting the drive unit to the PC 2 Startdrive SINAMICS Getting Started - SINAMICS Startdrive Getting Started Creating a project 3 Going online and incorporating devices 4 Commissioning

More information

Siemens Standard Drives. Application Handbook

Siemens Standard Drives. Application Handbook Siemens Standard Drives Application Handbook Martin Brown Siemens Standard Drives Congleton December 1997 1. Introduction....4 1.1 What is a Variable Speed Drive?...4 1.2 The Variable Frequency Inverter...7

More information

Install the DeviceNet Module using the following procedure:

Install the DeviceNet Module using the following procedure: Installation INSTALLATION INSTRUCTIONS: MCD DEVICENET MODULE Order Code: 175G9002 1. Installation Install the DeviceNet Module using the following procedure: 1. Remove control power and mains supply from

More information

Frequency Converter Fv

Frequency Converter Fv 2 Bosch Rexroth AG Electric Drives and Controls Documentation Brake chopper with up to 30 kw continuous braking power Easy to operate and service (detachable fan, LCD operating panel with copy function)

More information

ABB i-bus KNX Fan Coil Controller FC/S 1.1

ABB i-bus KNX Fan Coil Controller FC/S 1.1 Product manual ABB i-bus KNX Fan Coil Controller FC/S 1.1 Intelligent Installation Systems Contents Page 1 Introduction... 2 2 Device technology... 3 3 Application and planning 3.1 Heating, ventilation

More information

3753 en - 04.2004/b VE/B - VE/RG Va V riable speed drives

3753 en - 04.2004/b VE/B - VE/RG Va V riable speed drives 3753 en 04.2004/b Variable speed drives LEROYSOMER's drives provide SPEED VARIATION for a DC motor, SIMPLY and ECONOMICALLY from a singlephase power supply. CMStype technology is used. These products conform

More information

Installation manual. Generator Paralleling Controller GPC multi-line 2 4189340225C

Installation manual. Generator Paralleling Controller GPC multi-line 2 4189340225C Installation manual Generator Paralleling Controller GPC multi-line 2 Software ver. 1.3X Compact system in one unit - dynamic synchronisation - load sharing - generator protection DEIF A/S 3-phase AC RMS

More information

Thyristor-controlled power supplies and battery chargers

Thyristor-controlled power supplies and battery chargers Thyristor-controlled power supplies and battery chargers Input voltage: 115 / 230 VAC, single phase, 50 / 60 Hz or 208 / 400 / 480 VAC, three phases, 50 / 60 Hz Output voltage: 12 / 24 / 48 / 60 / 72 /

More information

HITACHI INVERTER SJ/L100/300 SERIES PID CONTROL USERS GUIDE

HITACHI INVERTER SJ/L100/300 SERIES PID CONTROL USERS GUIDE HITACHI INVERTER SJ/L1/3 SERIES PID CONTROL USERS GUIDE After reading this manual, keep it for future reference Hitachi America, Ltd. HAL1PID CONTENTS 1. OVERVIEW 3 2. PID CONTROL ON SJ1/L1 INVERTERS 3

More information

Analog Servo Drive 25A8

Analog Servo Drive 25A8 Description Power Range NOTE: This product has been replaced by the AxCent family of servo drives. Please visit our website at www.a-m-c.com or contact us for replacement model information and retrofit

More information

Operating Manual for the Electronic Built-in Interval Timer. Micro II (Countdown Timer)

Operating Manual for the Electronic Built-in Interval Timer. Micro II (Countdown Timer) Operating Manual for the Electronic Built-in Interval Timer Micro II (Countdown Timer) Note: This document has been designed for our OEM customers. They can use it as supporting material when creating

More information

MINI MCR-SL-R-UI(-SP)

MINI MCR-SL-R-UI(-SP) Resistance/potiposition transducer INTERFACE Data Sheet 0807_en_05 Description PHOENIX CONTACT - 0/008 Features The slim MINI MCR-SL-R-UI... potiposition transducer has a width of only 6. mm and converts

More information

Brake module AX5021. Documentation. Please read this document carefully before installing and commissioning the brake module!

Brake module AX5021. Documentation. Please read this document carefully before installing and commissioning the brake module! Documentation Brake module AX5021 Please read this document carefully before installing and commissioning the brake module! Version : 1.2 : 2012.03.05 Date Article-no. : TDmlAX-5021-0000-0200 Page 2/8

More information

Specifying a Variable Frequency Drive s

Specifying a Variable Frequency Drive s Specifying a Variable Frequency Drive s Put on by Bruce Reeves and Jeremy Gonzales Dykman Electrical Covering the Western US For all of your VFD and Soft Start and Motor Needs How To Specify a Variable

More information

MC Series Drives. Flexible, simple, rugged, robust! Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.actechdrives.com - Email: info@actechdrives.

MC Series Drives. Flexible, simple, rugged, robust! Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.actechdrives.com - Email: info@actechdrives. Drives Flexible, simple, rugged, robust! Our promise Commitment to Price Leadership Price leadership is serious business. It takes continuous life cycle management to make price leadership a sustainable

More information

FlexPak 3000 Digital DC Drive Software Reference Manual Version 4.3

FlexPak 3000 Digital DC Drive Software Reference Manual Version 4.3 FlexPak 3000 Digital DC Drive Software Reference Manual Version 4.3 Instruction Manual D2-3405-2 The information in this manual is subject to change without notice. Throughout this manual, the following

More information

Operational Overview and Controls Guide. Two or Three Pump IronHeart Lite with Variable Frequency Drives

Operational Overview and Controls Guide. Two or Three Pump IronHeart Lite with Variable Frequency Drives DOCUMENT: ECSEQ6-0 EFFECTIVE: 09/23/10 SUPERSEDES: Operational Overview and Controls Guide Two or Three Pump IronHeart Lite with Variable Frequency Drives 6700 Best Friend Road. Norcross, GA 30071. (770)

More information

Easy to connect - Easy to configure Easy to install

Easy to connect - Easy to configure Easy to install SIMPLE TO USE... CG Drive- SK is an easy drive - easy to connect, easy to configure and easy to install. Easy to connect - All connectors are generously sized and clearly labeled. Easy to configure - The

More information

Electronic overload relay EF19 and EF45

Electronic overload relay EF19 and EF45 Data sheet Electronic overload relay EF19 and EF45 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays. Motor

More information

ACS800. Master/Follower Application Guide Supplement to Firmware Manual for ACS800 Standard Application Program

ACS800. Master/Follower Application Guide Supplement to Firmware Manual for ACS800 Standard Application Program ACS800 Master/Follower Application Guide Supplement to Firmware Manual for ACS800 Standard Application Program Master/Follower Application Guide Supplement to Firmware Manual ACS800 Standard Application

More information

Product Manual. ABB i-bus KNX. Universal Dim Actuator, MDRC UD/S 2.300.2. Intelligent Installation Systems ABB

Product Manual. ABB i-bus KNX. Universal Dim Actuator, MDRC UD/S 2.300.2. Intelligent Installation Systems ABB Product Manual ABB i-bus KNX Universal Dim Actuator, MDRC UD/S 2.300.2 Intelligent Installation Systems ABB UD/S 2.300.2 Universal Dim Actuator, MDRC This manual describes the function of the Universal

More information

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller Overview/Modes of Operation Bulletin 150 Smart Motor Controller The SMC-3 is a compact, simple to use, solid-state motor controller designed to operate 3-phase motors. It features a built-in overload relay

More information

Installation and User Guide

Installation and User Guide Installation and User Guide 458-UNI8 8-Channel Universal Dimmer Module Introduction The 458/UNI8 is an 8-channel universal, digital transistor, dimmer module. Each channel s mode can be selected for either

More information

CB15/CB155. PROFIBUS Module

CB15/CB155. PROFIBUS Module CB15/CB155 PROFIBUS Module Contents Warning and Caution Notes 1. OVERVIEW 1.1 Description and Features 1.2 Application on a PROFIBUS Link 2. INSTALLATION 2.1 Installing the Module 2.1.1 CB15 Installation

More information

Supplement to the Operating Instructions for SIMOREG DC-MASTER Series 6RA70. for Software Release 3.2. Version 13 Order no.

Supplement to the Operating Instructions for SIMOREG DC-MASTER Series 6RA70. for Software Release 3.2. Version 13 Order no. s Supplement to the Operating Instructions for SIOREG DC-ASTER Series 6RA7 Version 3 Order no. 6RX7-AD76 for Software Release 3. C983-A756-A4--768 8. Converter software version: As this document went to

More information

Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592. * see variants. Applications.

Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592. * see variants. Applications. Safety Technique SAFEMASTER Emergency Stop Module BG 5924, IP 5924 Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592 BG 5924 IP 5924 Product Description

More information

Modular I/O System Analog and Digital Interface Modules

Modular I/O System Analog and Digital Interface Modules OPERATING INSTRUCTIONS Modular I/O System Analog and Digital Interface Modules Installation Operation Maintenance Document Information Document ID Title: Operating Instructions Modular I/O System Part

More information

... Electronic Softstarter...

... Electronic Softstarter... . CT-START Electronic Softstarter. 6 A. to 900. A......... CT START CT-START is a multi-function electronic system with a microcontroller and thyristors, designed for use with all 3-phase squirrel cage

More information

TURBOtech srl. SED-635 Digital Excitation System. Industrial Electronics Sector FEATURES

TURBOtech srl. SED-635 Digital Excitation System. Industrial Electronics Sector FEATURES SED-635 Digital Excitation System SED-635 is a complete excitation system capable of adapting to control synchronous generators of any size. The integration of the TOUCH SCREEN operator interface and a

More information

FAQ about Drive Technology

FAQ about Drive Technology FAQ about Drive Technology Technology CPU FAQ Operation of SINAMICS S120 (Firmware V2.2) with the Technology CPU (S7 Technology V2.0 SP1) SINAMICS S120 at Technology CPU Entry ID: 21767896 Table of Contents

More information

Application Note AN-SERV-006

Application Note AN-SERV-006 THIS INFORMATION PROVIDED BY AUTOMATIONDIRECT.COM TECHNICAL SUPPORT IS SUPPLIED "AS IS", WITHOUT ANY GUARANTEE OF ANY KIND. These documents are provided by our technical support department to assist others.

More information

Addendum to the Operating Instructions

Addendum to the Operating Instructions Drive Technology \ Drive Automation \ System Integration \ Services Addendum to the Operating Instructions MOVIMOT with AS-Interface and AC Motor DT/DV Unit Replacement MOVIMOT MM..C -> MM..D with MLK3A

More information

Electronic overload relay EF65, EF96 and EF146

Electronic overload relay EF65, EF96 and EF146 Data sheet Electronic overload relay EF65, EF96 and EF146 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays.

More information

SX460. Generator Automatic Voltage Regulator Operation Manual

SX460. Generator Automatic Voltage Regulator Operation Manual SX460 Generator Automatic Voltage Regulator Operation Manual Self Excited Automatic Voltage Regulator Compatible with Newage SX460* * Use for reference purpose only and not a genuine Newage product. 1.

More information

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original A motor starter is a combination of devices to allow an induction motor to start, run and stop according

More information

TABLE OF CONTENTS. Fig. 1 EV Pictorial Wiring Diagram 5. Section 2 Inverter Option Modules 6

TABLE OF CONTENTS. Fig. 1 EV Pictorial Wiring Diagram 5. Section 2 Inverter Option Modules 6 TABLE OF CONTENTS Introduction.. 3 Section 1 Safety Precautions.. 3 1.1 Preface.. 3 1.2 Receiving and Inspection... 3 1.3 Installation and Pre-operation 4 1.4 During Power ON. 4 Fig. 1 EV Pictorial Wiring

More information

is then retained absolutely without interruption.

is then retained absolutely without interruption. Page 1 of 11 DC UPS uninterruptible power supplies - DC UPS module 15 A Compact design, only 50 mm wide Absolutely interruption-free buffering of power failures through immediate electronic connection

More information

with Electronic Assistant

with Electronic Assistant TECHNICAL DATASHEET #TDAX100200 BLDC Motor Drive Drives a 12V, 24V or 48V BLDC motor Bidirectional, up to 25A Smooth speed control using Hall Sensors CAN (SAE J1939) with Electronic Assistant Features:

More information

Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description

Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description Type: EASY719 DC RC Article.: 274119 Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC Description 12 digital inputs (4 inputs available as analog inputs) 6 relay outputs LCD display

More information

Disturbance Recoder SPCR 8C27. Product Guide

Disturbance Recoder SPCR 8C27. Product Guide Issued: April 1999 Status: Updated Version: C/26.04.2006 Data subject to change without notice Features Versatile digital disturbance recorder module for recording various phenomena in the electric power

More information

Sinamics G120. Multimedia Training Package. www.siemens.com/sinamics-g120

Sinamics G120. Multimedia Training Package. www.siemens.com/sinamics-g120 Sinamics G0 Multimedia Training Package www.siemens.com/sinamics-g0 Required System Configuration CD-ROM Processor with min. GHz (dual core recommended) 04 MB RAM Graphics card (min. 56 MB memory recommended)

More information

1 Application Description... 3. 1.1 Objective... 3 1.2 Goals... 3

1 Application Description... 3. 1.1 Objective... 3 1.2 Goals... 3 Contents Moxa Technical Support Team support@moxa.com 1 Application Description... 3 1.1 Objective... 3 1.2 Goals... 3 2 System Topology... 3 3 Hardware and Software Requirements... 4 4 Configuration...

More information

MEMOBUS/Modbus Communications

MEMOBUS/Modbus Communications 2 2.1 MEMOBUS/MODBUS CONFIGURATION............260 2.2 COMMUNICATION SPECIFICATIONS..............261 2.3 COMMUNICATION TERMINAL RESISTANCE........262 2.4 CONNECTING A PLC...........................263 2.5

More information

Bulletin 150 SMC Flex Smart Motor Controller Specifications

Bulletin 150 SMC Flex Smart Motor Controller Specifications Specifications Specifications Standard Features Optional Features Installation Setup Communications Power Wiring Control Wiring Keypad Software Starting and Stopping Modes Protection and Diagnostics Metering

More information

Operational Overview and Controls Guide

Operational Overview and Controls Guide DOCUMENT: ECSEQ2-1 EFFECTIVE: 02/14/07 SUPERSEDES: 02/26/03 Operational Overview and Controls Guide Standard Two or Three Pump Type VFD Booster Controls 6700 Best Friend Road. Norcross, GA 30071. (770)

More information

Application/Connection Examples

Application/Connection Examples This Quick Start Guide is designed to familiarize the user with the connection and configuration of the DTS-305 DIN rail mounted single / 3 phase power & energy meter with RS-485 or TCP communications.

More information

SERIAL INTERFACE. Series SSW-03 and 04

SERIAL INTERFACE. Series SSW-03 and 04 SERIAL INTERFACE Series SSW-03 and 04 SERIAL COMMUNICATION MANUAL SSW-03 and 04 CODE 0899.4457 E/2 MANUAL OF THE SERIAL COMMUNICATION SSW-03 and 04 Series: SSW-03 and 04 Software: Version 4.XX 0899.4657

More information

Whale 3. User Manual and Installation Guide. DC Servo drive. Contents. 1. Safety, policy and warranty. 1.1. Safety notes. 1.2. Policy. 1.3. Warranty.

Whale 3. User Manual and Installation Guide. DC Servo drive. Contents. 1. Safety, policy and warranty. 1.1. Safety notes. 1.2. Policy. 1.3. Warranty. Whale 3 DC Servo drive User Manual and Installation Guide Contents 1. Safety, policy and warranty. 1.1. Safety notes. 1.2. Policy. 1.3. Warranty. 2. Electric specifications. 2.1.Operation ranges. 3. Connections

More information

Softstarters. Type PSTX Fieldbus communication, Built-in Modbus RTU. 1SFC132089M0201 April 2015 1SFC132089M0201 1

Softstarters. Type PSTX Fieldbus communication, Built-in Modbus RTU. 1SFC132089M0201 April 2015 1SFC132089M0201 1 Softstarters Type PSTX Fieldbus communication, Built-in Modbus RTU 1SFC132089M0201 April 2015 1SFC132089M0201 1 1 Modbus RTU The Modbus protocol is a fieldbus protocol that provides full control and status

More information

1115 4G SERIES GOVERNOR. 4-20 ma ANALOGUE DIGITAL SPEED SETTING

1115 4G SERIES GOVERNOR. 4-20 ma ANALOGUE DIGITAL SPEED SETTING 1115 4G SERIES GOVERNOR with 4-20 ma ANALOGUE & DIGITAL SPEED SETTING PO Box 28, 9300AA Roden, The Netherlands Tel: +31 505019888 Fax: +31 505013618 E-mail: regulateurs@regulateurs-europa.com 1115 4G

More information

VLT Series 3500 Adjustable Frequency Drive Instruction Manual

VLT Series 3500 Adjustable Frequency Drive Instruction Manual Adjustable Frequency Drive Instruction Manual VLT Series 3500 Instruction Manual 175R5237 - Document Version 5.00 This manual applies to all VLT Series 3502-3800 Adjustable Frequency Drives with software

More information

Variable Speed AC Motor Drives SM-Basic Installation and Operation Manual

Variable Speed AC Motor Drives SM-Basic Installation and Operation Manual ELECTRIC MOTORS, GEARMOTORS AND DRIVES Variable Speed AC Motor Drives SM-Basic Installation and Operation Manual We, EC Declaration of Conformity In accordance with EN45014:1998 Leeson Electric Corporation

More information

APPENDIX. SureSERVO QUICK START GUIDE. In This Appendix... Quick Start for SureServo Drives...A 2. Tuning Quick Start for SureServo Drives...

APPENDIX. SureSERVO QUICK START GUIDE. In This Appendix... Quick Start for SureServo Drives...A 2. Tuning Quick Start for SureServo Drives... SureSERVO QUICK START GUIDE APPENDIX BA In This Appendix... Quick Start for SureServo Drives.............A 2 Spin the Motor......................................A 2 Position Mode Quick Start (Pt & Pr)......................A

More information

Drayton Digistat +2RF/+3RF

Drayton Digistat +2RF/+3RF /+3RF Programmable Room Thermostat Wireless Model: RF700/22090 Model: RF701/22092 Power Supply: Battery - Thermostat Mains - Digistat SCR Invensys Controls Europe Customer Service Tel: 0845 130 5522 Customer

More information

WINDOW's Programming Software USER MANUAL

WINDOW's Programming Software USER MANUAL www.danahermotion.com High frequency inverter ACO5000 by ACOMEL WINDOW's Programming Software USER MANUAL DANAHER MOTION S.A. La Pierreire 2, CH-1029 Villars-Ste-Croix Telephone +41 21 631 33 33, Telefax

More information

VLT AutomationDrive for Marine winch applications

VLT AutomationDrive for Marine winch applications MAKING MODERN LIVING POSSIBLE VLT APPLICATION NOTE VLT AutomationDrive for Marine winch applications This Application note is meant to be a guideline for using Danfoss VLT AutomationDrive in winch applications.

More information

SECTION 26 29 23 VARIABLE FREQUENCY DRIVES

SECTION 26 29 23 VARIABLE FREQUENCY DRIVES SECTION 26 29 23 VARIABLE FREQUENCY DRIVES PART 1 GENERAL 1.01 SCOPE A. Furnish and install individual freestanding variable frequency AC drives (VFD) as shown on the Drawings and specified herein. 1.02

More information

SED2 Variable Frequency Drives Startup, Operation, and Maintenance Manual

SED2 Variable Frequency Drives Startup, Operation, and Maintenance Manual SED2 Variable Frequency Drives Startup, Operation, and Maintenance Manual Item Number 125-3201, Rev. CA SED2 Variable Frequency Drives Startup, Operation, and Maintenance Manual NOTICE The information

More information

Process modules Digital input PMI for 24 V DC inputs for 120 V AC inputs

Process modules Digital input PMI for 24 V DC inputs for 120 V AC inputs E031026 000823 Process modules Digital input PMI for inputs for 120 V AC inputs PMI Input E4, E5, GND L- PMI 120 V AC Input E4, E5, Common C E6, E7, GND L- E6, E7, Common C LEDs for the inputs operation

More information

MONITORING RELAYS. w VOLTAGE MONITORING RELAY UR5U1011. w SCHRACK-INFO. w TECHNICAL DATA

MONITORING RELAYS. w VOLTAGE MONITORING RELAY UR5U1011. w SCHRACK-INFO. w TECHNICAL DATA w VOLTAGE MONITORING RELAY UR5U1011 w SCHRACK-INFO AC/DC voltage monitoring in 1-phase mains Undervoltage monitoring 1 change over contact Width 17.5 mm Installation design w TECHNICAL DATA 502 1. Functions

More information

EXTERNAL DIMENSIONS AND PARTS

EXTERNAL DIMENSIONS AND PARTS FX2N-4DA SPECIAL FUNCTION BLOCK USER S GUIDE JY992D65901A This manual contains text, diagrams and explanations which will guide the reader in the correct installation and operation of the FX2N-4DA special

More information

EFC 3600. Frequency converters

EFC 3600. Frequency converters 2 Bosch Rexroth AG Electric Drives and Controls Documentation Compact and complete: space saving side-by-side assembly, plug-in I/O terminals, with brake chopper and mains filter for ultra-simple installation

More information

ABB Drives. User s Manual HTL Encoder Interface FEN-31

ABB Drives. User s Manual HTL Encoder Interface FEN-31 ABB Drives User s Manual HTL Encoder Interface FEN-31 HTL Encoder Interface FEN-31 User s Manual 3AUA0000031044 Rev B EN EFFECTIVE: 2010-04-06 2010 ABB Oy. All Rights Reserved. 5 Safety instructions

More information

SIMATIC. ET 200S distributed I/O 2AO I ST analog electronic module (6ES7135-4GB01-0AB0) Preface. Properties 1. Parameters 2.

SIMATIC. ET 200S distributed I/O 2AO I ST analog electronic module (6ES7135-4GB01-0AB0) Preface. Properties 1. Parameters 2. SIMATIC ET 200S distributed I/O SIMATIC ET 200S distributed I/O 2AO I ST analog electronic module (6ES7135-4GB01-0AB0) Manual Preface Properties 1 Parameters 2 Diagnostics 3 Analog value representation

More information

Generator Differential Relay Electrical Apparatus

Generator Differential Relay Electrical Apparatus Generator Differential Relay Electrical Apparatus MD3G Rotating Machine Differential Relay 150-3 The MD3G Rotating Machine Differential Relay is a member of Cooper Power Systems Edison line of microprocessor

More information

Application Unit, MDRC AB/S 1.1, GH Q631 0030 R0111

Application Unit, MDRC AB/S 1.1, GH Q631 0030 R0111 , GH Q631 0030 R0111 SK 0010 B 98 The application unit is a DIN rail mounted device for insertion in the distribution board. The connection to the EIB is established via a bus connecting terminal at the

More information

ABB i-bus EIB / KNX Analogue Input AE/S 4.2

ABB i-bus EIB / KNX Analogue Input AE/S 4.2 Product Manual ABB i-bus EIB / KNX Analogue Input AE/S 4.2 Intelligent Installation Systems This manual describes the functionality of Analogue Input AE/S 4.2. Subject to changes and errors excepted. Exclusion

More information

Talon and Talon SR User Manual

Talon and Talon SR User Manual Talon and Talon SR User Manual Brushed DC motor controller Version 1.3 Cross the Road Electronics, LLC www.crosstheroadelectronics.com Cross The Road Electronics, LLC Page 1 4/2/2013 Device Overview Clear,

More information

ABB general machinery drives. User s manual ACS355 drives

ABB general machinery drives. User s manual ACS355 drives ABB general machinery drives User s manual ACS355 drives List of related manuals Drive manuals and guides Code (English) ACS355 user s manual 3AUA0000066143 1) ACS355 drives with IP66/67 / UL Type 4x enclosure

More information

Safety technique. Emergency stop module BO 5988 safemaster

Safety technique. Emergency stop module BO 5988 safemaster Safety technique Emergency stop module BO 5988 safemaster 0221562 Function diagram Pushbutton on Mains or emergencystop () K1 According to EC Directive for machines 98/37/EG According to IEC/E 60204-1

More information

Siemens AG 2009 MICROMASTER. The universal frequency inverter for drive technology. Brochure April 2008 MICROMASTER. www.siemens.

Siemens AG 2009 MICROMASTER. The universal frequency inverter for drive technology. Brochure April 2008 MICROMASTER. www.siemens. The universal frequency inverter for drive technology Brochure April 2008 www.siemens.com/micromaster The universal frequency inverter for drive technology Application: Everywhere in the manufacturing

More information

DC Motor control Reversing

DC Motor control Reversing January 2013 DC Motor control Reversing and a "Rotor" which is the rotating part. Basically there are three types of DC Motor available: - Brushed Motor - Brushless Motor - Stepper Motor DC motors Electrical

More information

Switch Actuator, 8-fold, 10 A, MDRC AT/S 8.10.1, GH Q631 0075 R0111

Switch Actuator, 8-fold, 10 A, MDRC AT/S 8.10.1, GH Q631 0075 R0111 , GH Q631 0075 R0111 The 8-fold switch actuator is a DIN rail mounted device for insertion in the distribution board. It is connected to the EIB via a bus terminal. In the event of bus voltage failure,

More information

Ordering Part Numbers:

Ordering Part Numbers: TECHNICAL DATASHEET #TDAX021500 HYDRAULIC FAN CONTROLLER Application Platform 3 erature Sensors 4 Digital Command Interfaces 1 PWM Input and 1 Analog Input 1 Proportional or ON/OFF Current Output RS232

More information

Voltage Regulator SPAU 341 C. Product Guide

Voltage Regulator SPAU 341 C. Product Guide Issued: July 1998 Status: Updated Version: D/25.04.2006 Data subject to change without notice Features Comprehensive voltage regulation for power transformers with on-load tapchangers in distribution substations

More information

Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit 541 0811

Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit 541 0811 Instruction Sheet 1-2003 Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit 541 0811 PURPOSE OF KIT A CCM-T is used to monitor and control an automatic transfer switch. The

More information

MC1000 Series Installation and Operation Manual

MC1000 Series Installation and Operation Manual MC1000 Series Installation and Operation Manual NOTE! The manual covers software version M108314 and above. Refer to parameter 63 for the software version of the drive you are working with. If you are

More information

05.2007 Parameter list

05.2007 Parameter list 05.2007 Parameter list Parameter list Overview Range of parameter r000 r00 - P050 Function Operating display General visualization parameters P05- r059 Access authorization levels r060 - r065 P067 - P079

More information

Multi-Range Programmable DC Power Supplies 9115 Series

Multi-Range Programmable DC Power Supplies 9115 Series Data Sheet Multi-Range Programmable DC Power Supplies 1200 W / 3000 W Multi-Range DC Power Supplies Features & Benefits Any model can replace several supplies on your bench or in your rack. Unlike conventional

More information

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Manuel d installation Installation manual Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Index 1 Introduction 24 2 Conditions of use 24 3 LCD Panel 25 4 Installation 28 5 UPS communicator

More information