Application guidelines for selected fluid power components

Size: px
Start display at page:

Download "Application guidelines for selected fluid power components"

Transcription

1 1 July 2010 Application guidelines for selected fluid power components Accumulators Cylinders Hydraulic valves Pneumatic filters, regulators and lubricators Selection of position transducers published by NATIONAL FLUID POWER ASSOCIATION, INC N. Mayfair Road / Milwaukee, WI USA PHONE: / FAX: / nfpa@nfpa.com

2 Copyright 2010 by the NATIONAL FLUID POWER ASSOCIATION Printed in the USA All standards, recommended practices, information reports, and bibliographies (collectively, NFPA Documents ) are advisory only. Use thereof by anyone for any purpose is entirely voluntary and in any event without risk of any nature to the National Fluid Power Association (NFPA), its officers, directors or authors of such work. There is no agreement by or between anyone to adhere to any NFPA Document. In formulating and approving NFPA Documents, NFPA and/or its councils and committees will not investigate or consider citations, references or patents which may or may not apply to such subject matter since prospective users of such NFPA Documents alone are responsible for establishing necessary safeguards in connection with utilization of such matters, including technical data, proprietary rights or patentable materials. The information and data contained in NFPA Documents has been obtained from sources believed to be reliable. However, it should not be assumed that all acceptable or applicable sources of information, procedures, methods or techniques are contained in NFPA Documents, or that additional measures may not be required under certain circumstances or conditions. NFPA Documents and/or policies and procedures are subject to periodic review and may be changed without notice. NFPA Documents are only current as of their publication date. NFPA Documents, after publication, may be revised or withdrawn at any time and current information on all NFPA Documents may be received by calling or writing NFPA. Additionally, the various codes and regulations referenced in NFPA Documents may be amended from time to time and it should not be assumed that the versions referenced therein are the most current versions of such codes and regulations. Please consult the appropriate regulatory authorities for the most up-to-date versions. NFPA Documents imply a consensus of those substantially concerned with their scope and provisions and are intended as a guide to aid the manufacturer, the consumer and the general public. The publication of NFPA Documents does not in any respect preclude anyone, whether they have participated in the development of or approved such NFPA Documents or not, from manufacturing, marketing, purchasing, or using of products, processes or procedures not conforming to the NFPA Documents. NFPA Documents do not constitute or indicate a warranty of any sort, express or implied, including but not limited to a warranty or representation as to quality, merchantability or fitness for a particular use or purpose. Participation by federal agency representative(s) or person(s) affiliated with the industry is not to be interpreted as government or industry endorsement of an NFPA Document(s). NOTICE NFPA Documents do not express or imply any judgment, certification or endorsement of or with respect to, the safety, design or performance of any product, component, or its use. NFPA does not examine, investigate, test, recommend, or certify the design, use or safety of any product or component, even those which may incorporate one or more NFPA Documents. NFPA Documents therefore have no application to and do not express or imply any recommendation, representation or warranty, with respect to the safety, design, use, performance, or functional interchangeability of components or products which incorporate NFPA Documents. This publication may not, in whole or in part, be reproduced, copied or disseminated, entered into or stored in a computer database or retrieval system, or otherwise utilized without the prior written permission of NFPA.

3

4 Application guidelines Table of contents Application guidelines for selected fluid power components Table of contents Accumulators... page 1 Cylinders. page 9 Hydraulic valves page 21 Pneumatic filters, regulators, lubricators. page 31 Selection of position transducers... page 39

5 Application guidelines - Accumulators Application guidelines Accumulators Introduction In fluid power systems, power is transmitted and controlled through a fluid (liquid or gas) under pressure within an enclosed circuit. An accumulator is defined as a device for storing hydrostatic energy and subsequently releasing it to do useful work. The energy can be stored in the form of a compressed spring, lifted weight or compressed gas. By far the compressed gas (which must be an inert gas such as nitrogen) is the most common and is the type discussed in this document. This type is called a hydropneumatic accumulator. This is defined as an accumulator in which compressed gas applies force to the stored liquid. 1 Scope This recommended practice applies to bladder, diaphragm, and piston types of accumulators for their use in fluid power systems for industrial, marine, and mobile applications. 2 Normative references The following normative documents contain provisions which, through reference in this text, constitute provisions of the Application guidelines Accumulators section (pages 1-7) of this NFPA document. For dated references, subsequent amendments to, or revisions of, any of these publications do not apply. However, parties to agreements based on this NFPA document are encouraged to investigate the possibility of applying the most recent editions of the normative documents indicated below. For undated references, the latest edition of the normative document referenced applies. NFPA maintains registers of currently valid NFPA Standards. Standards development organization contact information and links can be found on the NFPA website ( EN 982 (latest edition), Safety of machinery Safety requirements for fluid power systems and their components Hydraulics. ISO 4413 (latest edition), Hydraulic fluid power General rules relating to systems. ISO 5598 (latest edition), Fluid power systems and components Vocabulary. 3 Definitions For the purposes of this recommended practice, the terms and definitions given in ISO 5598 apply. 1

6 Application guidelines - Accumulators 4 Accumulator types The following is a description of commonly used hydropneumatic accumulators. For their official definitions see ISO a) A bladder accumulator is an accumulator in which the liquid and gas are separated by an elastic bag or bladder. b) A diaphragm accumulator is an accumulator in which the liquid and gas are separated by a flexible diaphragm. c) A piston accumulator is an accumulator in which the liquid and gas are separated by a floating piston. d) A nonseparator accumulator is an accumulator in which the compressed gas operates directly on liquid within the pressure chamber. This type of an accumulator is not normally recommended because of safety reasons. Standards such as ISO 4413 state that circuits incorporating accumulators shall vent the accumulator liquid pressure or shall positively isolate the accumulator when the equipment is shut off. 5 General 5.1 A hydropneumatic accumulator works by storing energy in the form of a compressed gas. Normally this is an inert gas such as nitrogen. The accumulator is initially charged with some amount of gas pressure (the actual value of this pressure depends on the application); see Figure 1. At some point in the machine cycle, a pump will typically push hydraulic fluid into the hydraulic fluid side of the accumulator. At this point, the separator (a bladder, diaphragm or piston) will compress the gas to the same pressure as the hydraulic fluid; see Figure 2. Separator Gas precharge As charged Figure 1 Accumulator empty of hydraulic fluid and containing some amount of gas precharge Separator Hydraulic fluid Gas pressure Maximum operating pressure Figure 2 Accumulator charged with hydraulic fluid at maximum system pressure 5.2 When hydraulic fluid flow from the accumulator is required, a valve in the hydraulic system will direct the fluid to the component or components while the expanding gas pushes on the separator, expelling the hydraulic fluid from the accumulator. The pressure of the hydraulic fluid coming from the accumulator will follow the thermodynamic laws as applied to the expanding gas on the other side of the separator. Since the gas volume is not infinite, the hydraulic pressure will drop as an accumulator is discharged; see Figure 3. 2

7 Application guidelines - Accumulators Separator Hydraulic fluid Gas pressure Minimum required system pressure NOTE All of the hydraulic fluid has not been expelled. It is considered a good practice to maintain some fluid in the accumulator at the end of the discharge cycle for longer accumulator life. Figure 3 Accumulator, after it has been discharged and system is at minimum required system pressure 5.3 The general gas law for expansion or compression of a gas is described by the following equation: P 1 V 1 n = P 2 V n 2 where P 1 is the initial pressure; V 1 is the initial volume; P 2 is the final pressure; V 2 is the final volume; n is the polytropic exponent. 5.4 If an accumulator is discharged very slowly (this is seldom the case), the polytropic exponent is the isothermal exponent and is equal to 1.0. However, if the discharge is rapid, this value will be closer to the adiabatic exponent and is greater than 1.0. For nitrogen this factor will vary depending on several operating conditions. Consult your accumulator supplier for specific applications. The gas pressure may also vary when an accumulator is charged based on the rate at which it is charged. Again, consult your accumulator supplier for specific applications. 5.5 On occasions, especially when the operation requires the maximum and minimum operating pressures to be close to each other a large amount of gas volume may be required. An auxiliary gas bottle may be used as shown in Figure 4. 3

8 Application guidelines - Accumulators Auxiliary gas bottle Gas pressure Separator Gas pressure Hydraulic fluid Figure 4 Illustration of an auxiliary gas bottle used with a hydropneumatic accumulator. 5.6 Hydropneumatic accumulators are considered pressure vessels and, as a result, they may be subject to certain laws. Each state in the U.S. as well as each province in Canada has laws concerning pressure vessels. Foreign countries also have laws concerning pressure vessels. 5.7 Several national and international standards cover the application of an accumulator such as ISO 4413 and EN 982. Other industries may have their own standards. 6 Applications 6.1 General Accumulators are used to store or absorb energy. Typical applications are: a) energy storage; b) pulsation dampening; c) compensation for thermal expansion; d) hydraulic shock suppression. 6.2 Energy storage Supplementing pump flow In cases where relatively high actuator velocities are required with dwell time between cycles, it is possible to use an accumulator in conjunction with a pump to make a more efficient system. During the dwell time in the cycle, the pump charges the accumulator. Then when the actuator is activated, both the accumulator and the pump supply fluid under pressure to the actuator Minimum information required for this application: a) maximum hydraulic fluid pressure required at actuator; b) minimum hydraulic fluid pressure required at the actuator; 4

9 Application guidelines - Accumulators c) hydraulic fluid flow rate and volume required by actuator or actuators; d) pump displacement (volumetric); e) dwell time Leakage compensation Hydraulic valves and cylinder pistons may have some internal leakage. In some applications, it may be desirable to make up this leakage by using an accumulator. This is possible as long as there is some dwell time in the machine cycle so that the pump can recharge the accumulator Minimum information required for this application: a) maximum hydraulic fluid pressure required at actuator; b) minimum hydraulic fluid pressure required at the actuator; c) expected leakage volume; d) pump displacement (volumetric); e) dwell time Emergency (auxiliary) power source Certain equipment may require some sort of stored energy to be used in an emergency. In such cases, an accumulator is charged with hydraulic fluid that can be relieved manually or electrically in an emergency Minimum information required for this application: a) maximum hydraulic fluid pressure required; b) minimum hydraulic fluid pressure required at the actuator; c) hydraulic fluid flow rate and volume required by actuator or actuators. 6.3 Pulsation dampening Positive displacement pumps, especially piston type, generate hydraulic flow that may exhibit pressure ripple, which is not always desirable. The exact amount of ripple depends on pump displacement, pressure and number of pumping chambers. Accumulators can be used to smooth out these pressure ripples Minimum information required for this application: a) pump displacement (volumetric); b) number of pumping chambers in pump; c) rotational speed of pump; d) system pressure. 5

10 Application guidelines - Accumulators 6.4 Compensation for thermal expansion Thermal expansion, if not compensated for in a closed loop hydraulic system, can increase pressure beyond acceptable limits. Accumulators absorb the volume increase and return fluid to the line when the temperature falls Minimum information required for this application: a) type of hydraulic fluid; b) fluid conductor material; c) volume of contained fluid; d) normal operating temperature; e) maximum operating temperature; f) normal operating pressure; g) maximum operating pressure. 6.5 Hydraulic shock suppression When valves open and close quickly, they can generate shock waves in a hydraulic system. Both shock and vibration can generate noise and also lead to premature wear and tear on machine components. Accumulators have relatively good damping characteristics over a wide frequency range that effectively reduces shock and vibration Minimum information required for this application: a) flow rate in hydraulic lines; b) specific gravity of hydraulic fluid; c) length and size of hydraulic lines; d) valve closing time; e) operating pressure; f) maximum operating pressure. 7 Ports It is suggested that the port at the hydraulic end of the accumulator be of a type that is sealed by an elastomer rather than an interference fit, such as a pipe thread port. It is also suggested that the port size be sufficiently large for the required fluid flow rate out of the accumulator. 8 Environment Accumulators contain static seals as well as dynamic seals in the separator. These seals, which are available in several compounds, are exposed to the operating condition of the accumulator as well as the hydraulic fluid. Seal selection 6

11 Application guidelines - Accumulators should be done together with the accumulator manufacturer, taking into account the maximum and minimum operating temperature and hydraulic fluid used. 9 Corrosion Accumulators are considered pressure vessels. As a result, corrosion, both internal and external, should be taken into account. Internal corrosion that can be caused by the hydraulic fluid will both weaken the pressure vessel and damage the separator. External corrosion will weaken the pressure vessel. Therefore, the environment to which the accumulator is exposed must be considered. Some codes also require that a corrosion allowance be addressed in the stress calculations related to the pressure vessels. 10 Mountings An accumulator should be securely mounted to a machine frame. The hydraulic plumbing should not be the sole method by which the accumulator is secured to a machine frame. Care should be taken not to squeeze the body of piston accumulators by overtightening U-bolt type brackets. Your accumulator supplier should be consulted for the proper method of securing the accumulator to the machine frame, as well as its orientation. 11 Precharge pressure 11.1 Each specific application shall be accomplished most effectively with a specific value of precharge pressure. The specific value shall be determined by the system operating conditions. Variation from this pressure will cause the system to degrade in performance. Since the precharge pressure is gas pressure in a contained vessel, it will vary as a function of temperature, i.e., if the gas temperature increases, the pressure will increase, and if the gas temperature decreases, the pressure will decrease In a typical hydraulic system, the operating temperature of the accumulator is usually higher than the temperature of the surrounding environment. When checking the precharge pressure, it is important to determine the temperature of the gas. It is easiest to check the pressure when the equipment has been shut down for some time and the gas temperature has stabilized to the temperature of the surrounding environment. Also, shutting down the equipment may remove all hydraulic fluid from the accumulator, which will affect the gas precharge pressure value. Therefore, it is important to know how the precharge pressure in this condition will translate to a gas pressure at operating conditions. The accumulator supplier can help to determine these two values. 12 Maintenance 12.1 An accumulator should be charged only with an inert gas, such as nitrogen Charging of an accumulator or the periodic checking of proper precharge pressure should be done only in accordance with the accumulator manufacturer s instructions and using only components specified by the accumulator manufacturer Any repair to an accumulator shall be done after it has been relieved of liquid and gas precharge pressure and removed from the hydraulic system. The discharging, removal and repair shall be done by a properly trained person following procedures specified by the accumulator manufacturer. 7

12

13 Application guidelines - Cylinders Application guidelines Cylinders Introduction In fluid power systems, power is transmitted and controlled though a fluid under pressure within an enclosed circuit. The application of hydraulic and pneumatic cylinders requires precise communication between manufacturer and user. It is the intent of this recommended practice to provide basic guidance in cylinder applications and to promote communication. Users of this recommended practice are cautioned, however, to review each clause for applicability and to utilize sound engineering judgement 1 Scope This recommended practice will apply to hydraulic and pneumatic fluid power cylinders for their use in hydraulic and pneumatic systems for industrial, marine, and mobile applications. 2 Normative references The following standards contain provisions which, through reference in this text, constitute provisions of the Application guidelines Cylinders section (pages 9-20) of this NFPA document. At the time of publication, the editions indicated were valid. All documents are subject to revision, and parties to agreements based on this NFPA document are encouraged to investigate the possibility of applying the most recent editions of the documents indicated below. NFPA maintains registers of currently valid NFPA standards. NFPA/T3.6.7 R1-1996, Fluid power systems and products Square head industrial cylinders Mounting dimensions. ISO 5598:1985, Fluid power systems and components Vocabulary. 3 Definitions A description of different types of cylinders is given in this document several times. For their official definition as well as definition of other terms see ISO Operation and cylinder concepts Cylinders are used when linear force and motion are required. Cylinders are broken down into two main categories: pneumatic and hydraulic. Pneumatic cylinders can be operated by several types of gases, however, compressed air is by far the most common. Hydraulic cylinders can be operated with a very large range of fluids. By far the most common is petroleum based hydraulic fluid. Fire-resistant fluids are also common, they may be synthetic or water based. 9

14 Application guidelines - Cylinders Cylinders can be broken down into two main components. The pressure containing envelope and the piston and rod assembly. Typically the pressure containing envelope is fixed on the machine and the piston and rod assembly is attached to the machine member on which motion and force need to be applied. In rare occasions the opposite is done. See figure 1. Pressure containing envelope Piston and Rod assembly Motion 4.1 Force. Figure 1 Typical cylinder The amount of force applied to the machine member is the product of the fluid pressure multiplied by the effective area of the piston. Most cylinders contain a single piston rod. Assuming a constant value for the applied pressure, a cylinder would normally exert more force in the push stroke than it will in the retract stroke. The amount by which the retract force is less than the extend force depends on the cross-sectional area taken up by the piston rod. See figure 2. For example, a 100 mm bore (10 cm) cylinder housing a 45 mm (4.5 cm) diameter piston rod operating at 1,000 kilopascals (1,000 kpa) will deliver 7,854 neutons (N) of force in the push direction and 6,264 N in the pull direction. Example: one neuton (N) of force = one pascal (Pa) applied to an area one meter square (M 2 ). N=Pa M 2 Calculation for push stroke surface area = Π 4 D2 bore Calculation for pull stroke surface area = Π 4 (D2 bore - D 2 rod) An area of cm 2 = M 2 In push direction force (N) = 1,000 kpa x M 2 =7,854 neutons In pull direction force (N) = 1,000 kpa x M 2 =6,264 neutons F p ull F p ush 10

15 Application guidelines - Cylinders 10 cm Dia piston 4.5 cm Dia. Piston rod Area = cm 2 Area = cm Velocity Figure 2 Effective areas The velocity at which the piston and rod assembly moves is dependent on the rate at which the fluid is introduced into the cylinder. Normally a cylinder is connected to a directional valve and sometimes flow control valves. In a pneumatic system the maximum speed of the piston and rod assembly is dependent on the rate at which the air can flow through the valving. For a hydraulic cylinder, the maximum piston rod velocity depends on the ability of the hydraulic system to provide the hydraulic fluid to the cylinder. In most applications piston rod velocity is held in the.3 to.9 m/s. However, velocities up to 3 m/s have been achieved. See figure 3. 11

16 Application guidelines - Cylinders Hydraulic circuit Pneumatic circuit Figure 3 Hydraulic and pneumatic circuits 5 Basic construction The following three types of construction are the more commonly used types of cylinders. 5.1 Square head tie rod This is a very common type of cylinder used in industrial applications. Head and cap enclosures are secured by tie rods that run the length of the cylinder. See figure 4. 12

17 Application guidelines - Cylinders Figure 4 Square head tie rod cylinder 5.2 Bolted end These cylinders have flanges that are attached to the barrel. The end caps are attached to these flanges with bolts. See figure Nonbolted end Figure 5 Bolted end This type of cylinder has end caps that are usually retained by welding or with a locking ring. In many cases these are used for mobile applications. Some pneumatic cylinders crimp the tube onto the end caps. See figure 6. Figure 6 Nonbolted end 6 Types of cylinders Double acting, single piston rod cylinders are by far the most common types of hydraulic and pneumatic cylinders used in industry. However, there are other configurations which are used in special situations. 6.1 Double acting By far, most cylinders are considered double acting. That is, when the cylinder is required to extend, pressure is applied to the cap end of the cylinder while pressure is exhausted from the rod end. When the cylinder is required to retract, pressure is applied to the rod end and the cap end is exhausted. See figure 7. 13

18 Application guidelines - Cylinders Fluid flow Fluid flow Fluid flow Fluid flow Thrust Thrust Figure 7 Double acting 6.2 Single acting In these types of cylinders pressure is applied only to one side of the piston, and some other force is used to move the piston and rod assembly in the opposite direction. In some cases it may be gravity; however, in most cases this is accomplished by a spring. Springs can be mounted on either side of the piston. However, most commonly a spring is mounted on the rod end of the piston and is used to retract the cylinder. Springs can be mounted in either hydraulic or pneumatic cylinders. Normally the mechanical force provided by a spring is rather small in comparison to the potential force which a hydraulic cylinder can apply. Therefore, most single acting cylinders tend to be pneumatic. See figure 8. Fluid flow Spring 6.3 Double rod Figure 8 Single acting Double rod cylinders can be used so that the applied load to the machine member is the same in both directions. Sometimes a smaller rod is used on one end to trip limit switches. See figure Ram cylinders Figure 9 Double rod end The rod and piston are the same diameter. This type of cylinder is usually single acting, with an external force used to retact the cylinder. A typical application is a lift in a service station. See figure

19 Application guidelines - Cylinders 6.5 Telescopic cylinders Figure 10 Ram Telescopic cylinders utilize multiple sections to achieve long strokes when short collapsed lengths are required. This type of configuration is sometimes used in cylinders for dump trucks or lift trucks. These are usually single acting. The net force is a function of the smallest section. See figure Tandem cylinders Figure 11 Telescopic Tandem cylinders consist of two pistons attached to a common piston rod. These cylinders are used in situations where space requirements are very tight and the combined areas of two pistons can be applied to one piston rod. These are used to increase force. In some cases such as a press, a tandem cylinder is constructed of a large press cylinder with a small cylinder attached to the back. This configuration is used where the smaller bore cylinder is pressurized to rapidly advance the larger cylinder. See figure Duplex cylinders Figure 12 Tandem Duplex cylinders consist of multiple piston and rod assemblies which are not connected to each other. This configuration is often used where more than two distinct stopping points are required. See figure 13. or 6.8 Rodless cylinders Figure 13 Duplex These cylinders are typically used when limited space prohibits the use of a cylinder with a piston rod. 15

20 Application guidelines - Cylinders Direct coupled The carriage and piston are directly connected. See figure 14. Carriage Piston Figure 14 Direct coupled Magnetically coupled The carriage is and piston are magnetically coupled. See figure 15. Carriage Piston Cable connected Figure 15 Magnetically coupled The carriage is connected to the piston by a cable or flexible band. See figure 16. Carriage Motion Cable/band Fluid flow Piston Fluid flow Figure 16 Cable connected 16

21 Application guidelines - Cylinders 7 Mounting 7.1 Fixed and pivot The pressure containing envelope is normally mounted to the machine. This is normally done with one of two types of mounting configurations. A fixed type mounting or a pivot type mounting. If the machine member moves in a straight line type motion, a fixed mount can be used. If the machine member is required to move in an arc a pivot mounting must be used. See figure 17. Fixed mount Pivot mount 7.2 Types Figure 17 Fixed and pivot mounts Fixed mounts are available in many configurations. Typical mountings may be front or rear flange mountings, tie rod extended mounts, or foot mounts. Pivot mounts can be head, cap or center trunnions, or a rear cap pivot mount. For a more complete list of the mounts, consult the manufacturer or NFPA/T See figure 18 for some examples. Figure 18 Typical mounts 17

22 Application guidelines - Cylinders 7.3 Mounting enhancements Selection of any mounting style depends primarily upon the operating specifications of the application. Cylinder mounting directly affects the maximum operating pressure at which the cylinder may be used. Whether the cylinder is used in thrust (push) or tension (pull), its stroke length, piston rod diameter and method of connection to the load must be considered when selecting a mounting style. Fixed mountings that absorb the force on the centerline of the cylinder are considered the best for straight line force transfer. The symmetrical mountings allow the thrust or tension forces to be distributed uniformly within the mounting framework. Flange mounts are considered the best mounting styles within this category. Front flange mounts are ideally suited when the piston rod is in tension (pull), while cap flanges are recommended for thrust (push) applications. Fixed noncenterline mountings do not absorb forces on their centerline. The offset thrust introduces bending stresses and additional loads on the mounting bolts. This is especially true in short stroke applications. This type should be very well aligned for maximum service life. Use of shear pins or keys should be considered when these cylinders are subjected to high pressures or shock loads. These mountings are among the easiest to use for mounting and replacement ease. If the path of the load is curved or misalignment is a problem, a pivoted centerline mounting should be used. These mounts offer compensation for non-linear travel in only one plane. Pivot mounts require a pivot type rod attachment. Threaded rod end attachments should be torqued tightly against a threaded shoulder to minimize bending and reduce fatigue stresses. 8 Design considerations 8.1 Column strength Piston rod column failure (buckling) can occur if the rod diameter is not sized to match the stroke and load. The manufacturer should be consulted for application assistance. Reference figure 19 for an example of piston rod column failure. 8.2 Bearing load Figure 19 Piston rod column failure Cylinders are normally intended to push and pull without excessive side load. If a side load exists, the manufacturer should be consulted. Usually bearing load can be reduced with the addition of a stop tube. The use of a stop tube increases the distance between the piston bearing and piston rod bearing. See figure 20. Piston bearing Stop tube Piston rod bearing Figure 20 Stop tube 18

23 Application guidelines - Cylinders 8.3 Cushions The purpose of a cushion is to decelerate the piston and rod assembly as it nears the end of stroke, preventing excessive mechanical stresses. Cushions may be of either a fixed or adjustable design. Both designs function by providing a bypass passage to remove the pressurized fluid trapped between the piston and the cylinder head when the cushion sleeve has entered the cushion bore. Varying the orifice opening with an adjustable cushion screw allows the user to select the best cushion rate for the system. A check valve in the cushion assembly allows for the free flow of fluid back to the piston face for quick acceleration when the rod is withdrawn. Heavy loads may also require an external device to stop the motion. Cushions are available on either or both ends of the cylinder. Consult manufacturer for the conditions under which cushions should be used. See figure 21. Fluid flow Piston rod motion Figure 21 Cushions 8.4 Eccentric Loads A very important general consideration is to keep the cylinder thrust as close as possible to the centerline of the piston rod and free from misalignment or side thrust. Off-center thrust or side loads can substantially reduce the service life expected from the rod bearing and seals. Off-center thrust and side loading can be caused by cylinder deflection under load, machine frame deflection, rod bending or sagging, as well as by poor design of the machine. See figure 22. Piston rod centerline Applied load Figure 22 Eccentric Loads 9 Compatibility The temperature and fluid type must be considered in any application to ensure proper seal effectiveness and life. The manufacturer should be consulted for assistance. 10 Corrosion Surfaces of either hydraulic or pneumatic cylinders can be corroded by water or other substances. Although paint may be suitable protection against corrosion for most indoor industrial uses, the cylinder specifier should be aware of corrosion potential in the operating environment. The material content and surface preparation of the piston rod must be considered in any application where a corrosive environment exists. Consult the cylinder manufacturer for corrosion protection recommendations. 19

24 Application guidelines - Cylinders 11 Maintenance Cylinder maintenance primarily involves replacing seals and/or bearings. Consult the manufacturer for maintenance guidelines Visual inspection Degradation of cylinder thrust or erratic motion can indicate seal leakage. Prior to disassembly, visual inspection can be performed on the rod seal and tube end seals. This is accomplished by inspecting these locations for either oil or escaping air depending on whether the cylinder is hydraulic or pneumatic. Inspection of the piston seals and bearing require disassembly Disassembly Prior to performing any maintenance that requires the disassembly of the cylinder, the pressure within the cylinder must be zero. The machine manufacturer should be consulted for any lock-out requirements. Follow the cylinder manufacture s recommended disassembly and reassembly procedures, paying particular attention to prescribed fastener torque values and internal springs. While the cylinder is disassembled, inspect all components for evidence of unusual wear. Signs of internal corrosion may indicate the presence of water or lack of lubrication. Signs of contamination may indicate improper filtration. Proper preventative maintenance will extend seal and bearing life. Wear can be caused by misalignment of the cylinder and load, or other problems that should be remedied before the cylinder is returned to service Preventative maintenance. Preventative maintenance such as hydraulic oil filtration and compressed air filtration/drying will extend cylinder service intervals. 20

25 Application guidelines - Hydraulic valves Application guidelines Hydraulic valves Introduction In hydraulic fluid power systems, power is transmitted and controlled through a liquid under pressure within an enclosed circuit. The application of hydraulic valves requires precise communication between manufacturer and user. It is the intent of this recommended practice to provide basic guidance in valve application and to promote communication. Users of this recommended practice are cautioned, however, to review each section for applicability and to utilize sound engineering judgment. 1 Scope 1.1 This recommended practice is applicable to hydraulic valves used in industrial, marine and mobile equipment. 1.2 This recommended practice provides basic guidance for the selection, installation, operation, and maintenance of hydraulic valves. 2 Normative references The following normative documents contain provisions which, through reference in this text, constitute provisions of the Application guidelines -- Hydraulic valves section (pages 21-29) of this document. For dated references, subsequent amendments to, or revisions of, any of these publications do not apply. However, parties to agreements based on this NFPA document are encouraged to investigate the possibility of applying the most recent editions of the normative documents indicated below. For undated references, the latest edition of the normative document referenced applies. NFPA maintains registers of currently valid NFPA Standards. Standards development organization contact information and links can be found on the NFPA website ( NFPA/T2.6.1 R (R2005), Fluid power components Method for verifying the fatigue and establishing the burst pressure ratings of the pressure containing envelope of a metal fluid power component NFPA/T (latest edition), Hydraulic fluid power systems Methods for preventing external leakage. NFPA/T3.5.1 (latest edition), Hydraulic fluid power Valves Mounting surfaces. NFPA/T (latest edition), Hydraulic fluid power Directional control valves Method for determining the metering characteristics. NFPA/T (latest edition), Hydraulic fluid power Valves Method for determining the internal leakage characteristics. NFPA/T (latest edition), Hydraulic fluid power Flow control valves Method for measuring and reporting regulating characteristics. NFPA/T R (R2005), Hydraulic valve Pressure rating supplement to NFPA/T2.6.1 R Method for verifying the fatigue and burst pressure ratings of the pressure containing envelope of a metal fluid power hydraulic valve 21

26 Application guidelines - Hydraulic valves IEEE/ASTM SI 10 (latest edition), Standard for Use of the International System of Units (SI): The Modern Metric System. ISO 1000 (latest edition), SI units and recommendations for the use of their multiples and of certain other units. ISO (latest edition), Fluid power systems and components Graphic symbols and circuit diagrams Part 1: Graphic symbols for conventional use and data processing applications (second edition) ISO (latest edition), Fluid power systems and components Graphic symbols and circuit diagrams Part 2: Circuit diagrams ISO 4401 (latest edition), Hydraulic fluid power Four-port directional control valves Mounting surfaces. ISO 4406 (latest edition), Hydraulic fluid power Fluids Method for coding level of contamination by solid particles. ISO 5598 (latest edition), Fluid power systems and components Vocabulary. ISO (latest edition), Connections for hydraulic fluid power and general use Ports and stud ends with ISO 261 metric threads and O-ring sealing Part 1: Port with truncated housing for O-ring seal (second edition) ISO (latest edition), Connections for hydraulic fluid power and general use Ports and stud ends with ISO 261 threads and O-ring sealing Part 2: Dimensions, design, test methods and requirements for heavy-duty (S series) stud ends (second edition) ISO (latest edition), Connections for hydraluic fluid power and general use Ports and stud ends with ISO 261 threads and O-ring sealing Part 3: Dimensions, design, test methods and requirements for light-duty (L series) stud ends (second edition) ISO (latest edition), Hydraulic fluid power Flange connectors with split or one-piece flange clamps and metric or inch screws Part 1: Flange connectors for use at pressures of 3,5 MPa (35 bar) to 35 MPa (350 bar), DN 13 to DN 127 ISO (latest edition), Hydraulic fluid power Flange connectors with split or one-piece flange clamps and metric or inch screws Part 2: Flange connectors for use at pressures of 35 MPa (350 bar) to 40 MPa (400 bar), DN 13 to DN 51 ISO 7368 (latest edition), Hydraulic fluid power Two-port slip-in cartridge valves Cavities. ISO (latest edition), Hydraulic fluid power Electrically modulated hydraulic control valves Part 1: Test methods for four-way directional flow control valves. ISO (latest edition), Connections for general use and fluid power Ports and stud ends with ISO 725 threads and O-ring sealing Part 1: Ports with O-ring seal in truncated housing ISO (latest edition), Connections for general use and fluid power Ports and stud ends with ISO 725 threads and O-ring sealing Part 2: Heavy-duty (S series) stud ends ISO (latest edition), Connections for general use and fluid power Ports and stud ends with ISO 725 threads and O-ring sealing Part 3: Light-duty (L series) stud ends SAE J518 (latest edition), Hydraulic flanged tube, pipe, and hose connections, 4 bolt split flange type. SAE J1783 (latest edition), Selection of hydraulic directional control valves for marine vehicle applications. 22

27 Application guidelines - Hydraulic valves 3 Terms and definitions For the purposes of this NFPA document, the terms and definitions given in ISO 5598 apply. 4 General 4.1 Valve classifications Hydraulic valves can be classified into four general categories based on their function. These categories are described in through Valve assemblies or subassemblies comprise components from more than one valve category, such as a directional valve incorporating an internal pressure control valve. See ISO and ISO for hydraulic valve graphic symbols and their use in circuit diagrams Directional control valves Directional control valves connect or isolate one or more flow paths. They are commonly used to control speed and direction of a hydraulic actuator. They may range from a simple two-port check valve to a multiple-port directional valve. Application guidelines for these valves are contained in clause Pressure control valves Pressure control valves are commonly used to limit or control pressure excursions of the pump or of portions of the hydraulic circuit. They may range from direct-acting relief valves to pilot-operated counterbalance valves. Application guidelines for these valves are contained in clause Flow control valves Flow control valves are used to limit or control flow with the circuit or portions of the circuit. They may range from a simple fixed orifice to a pressure- and temperature-compensated flow control valve. Application guidelines for these valves are contained in clause Load holding valves Load holding valves are used to prevent drift of a loaded actuator and to prevent uncontrolled movement of an actuator due to overrunning loads. Application guidelines for these devices are contained in clause Fluids Hydraulic fluids may range from petroleum oils to synthetics, fire resistant fluids and biodegradable fluids. Select a fluid that is appropriate for the system and machine type and environment. Fluid types and equipment manufacturer s recommendations may vary widely among mobile, industrial, and marine systems. Ensure that valves, including seals and electrical wiring, are compatible with the system fluid. 4.3 Fluid conditioning Fluid filtration requirements depend upon several factors, including the type of system and components, the severity of the application, the operating environment, and the level and frequency of maintenance. Filtration should be provided to maintain the system fluid within the cleanliness level recommended by the valve manufacturer and system designer. The system design and installation should minimize entrained air and other contaminants, such as water. The fluid temperature and water content should be maintained at levels consistent with the fluid and component manufacturer s recommendations. Acceptable fluid temperature ranges will differ among mobile, industrial, and marine systems. 23

28 Application guidelines - Hydraulic valves 4.4 Ports Valve ports should be of the O-ring sealed straight thread type conforming to ISO or ISO , or of the flange type conforming to ISO , ISO or SAE J518. Ports with pipe threads should not be used because of the potential for external leakage. See also NFPA/T for additional information on port types and their characteristics. 4.5 Mounting Valves are available in many different construction and mounting configurations, including: a) independently mounted, of monoblock, sectional, or combination block construction b) subplate or manifold mounted, in accordance with ISO 4401, NFPA/T3.5.1, or custom interface design c) cartridge design and installation, of the screw-in type in accordance with ISO 7789 or NFPA/T3.5.50, or of other custom design. d) cartridge design and installation, of the slip-in type in accordance with ISO 7368, or of other custom design e) actuator installed or direct mounted The function or at rest mode of some valves may be influenced by the mounting direction. Consult the manufacturer for recommendations regarding preferred mounting. 4.6 Location In most cases, valves should be mounted as close to the actuators as practical. Valves should also be installed so that they are accessible for maintenance and removal. In the case of manual valves, ease of actuation shall be taken into account. 4.7 Pressure rating and reliability Valve selection should take into account the maximum pressure excursions in the system, the operating duty cycle, and the expected service life. The potential for overloads, external mechanical loads, and other abnormal conditions should be considered. Fatigue rating of the pressure containing envelope(s) of valves should be in accordance with NFPA/T2.6.1 and NFPA/T Repair and maintenance Specific instructions for maintenance and repair should be contained in the equipment manual(s) and/or on equipment decals. If a repair involves disassembly of a valve or its hydraulic connections, care shall be taken to ensure that the cleanliness levels recommended in 4.3 are maintained before the valve is returned to service. Replacement fluid shall be of the proper type and shall meet the cleanliness requirements of Other application considerations Other system and application characteristics that may affect the performance or reliability of valves include: a) excessive vibration or shock, particularly if valves are cantilever mounted or if the system could be unstable under certain conditions; b) intermittent temperature extremes, such as cold startup conditions or temporary overheating; c) exposure to unusual or extreme environments, such as water spray or immersion, corrosive chemicals, fine dust, abrasive materials, etc. See SAE J1783 for marine application guidance; d) hazardous locations that may require explosion-proof or intrinsically safe devices. 24

29 Application guidelines - Hydraulic valves 5 Directional control valve application guidelines 5.1 Check (non-return) valves Unpiloted two-port check (non-return) valves are one of the simplest forms of directional control valves, blocking flow in one direction and allowing essentially free flow or flow at a prescribed pressure in the opposite direction. The check valve shall be sized to provide an acceptable pressure drop at maximum flow and shall be designed to provide acceptable internal leakage control in the blocking condition. Check valves normally are spring-biased to assist in rapid closing, stability, and leakage control. The spring bias adds to the pressure drop in the open condition. Three-port check valves, also known as shuttle valves, are utilized to connect the higher or lower pressure of two lines to a third connection. Pilot-to-open and pilot-to-close check valves are also available for situations in which the check valve must respond to an external pilot pressure. See clause 8 for a more detailed discussion of load holding valves. 5.2 Directional control valves Directional control valves may be actuated mechanically, hydraulically, pneumatically or electrically. Electrical actuation can be on/off or proportional. In the case of hydraulically, pneumatically or electrically piloted valves, the pilot system shall be designed to provide satisfactory response and acceptable characteristics in the event of failure. Directional control valves are normally spring-centered but may also contain mechanical detents, electromagnetic detents or other devices. Valves shall be sized to provide acceptable pressure drops at maximum flow rates, recognizing that individual ports may have different flow rates. If the internal leakage characteristics of the directional control valve are such that actuator creep is a concern, the use of pilot-operated check valves or other blocking valves should be considered Two-port valves Two-port spool, poppet, gate, or other mechanical valves are used to connect or disconnect two-ports. They differ from check valves in that they are typically bidirectional when open. Internal leakage characteristics may differ from check valves, depending upon the design Three-port valves Three-way valves provide a means to connect and disconnect three ports. A typical application of a two-position, threeport valve is to bypass pump flow to tank in one position and to connect pump flow to an actuator in the other Four-port valves Four-port valves provide a means to connect and disconnect four ports. A two-position, four-port valve can be used to control an actuator in forward and reverse directions by connecting opposite actuator ports to pump flow or to tank. Intermediate or transition characteristics of the valve may have a significant impact on pump and actuator pressures and metering, and should be selected based on the requirements of the application. Four-port valves are often applied in a three-position configuration, with the third (center) position providing a neutral condition for the pump and a holding or freewheeling condition for the actuator. A holding or blocked actuator port, center position is normally used with cylinders in order to maintain a load in position. The valve shall have internal leakage characteristics that result in acceptable drift rates for the loaded cylinder. A freewheeling, or vented-to-reservoir actuator port, center position is normally used with motors in order to allow the motor to coast to a stop after pump inlet flow is disconnected, avoiding large pressure spikes. With regard to the pump, the three-position valve can be open center, in which the pump flow is bypassed to the reservoir, or closed center, in which the pump flow path is blocked. An open center valve is normally used with a fixed displacement pump, and a closed center valve is typically selected for use with a variable displacement pump or a fixed displacement pump with an integral unloading device. Closed center valves may also be load sensing, controlling a pressure and flow compensated pump s displacement by means of a sensing line downstream of the valve s metering element. Special four-position options are also available with four-port valves. A relatively common fourth position option with cylinders is float, in which both sides of the cylinder are connected to the reservoir (unlike the center, or holding, position in which both ports are blocked). Regeneration, in which the supply side of the cylinder is connected to both the pump and the return (rod) side of the cylinder, is another option. This provides faster cylinder speed, but at the expense of available force, since the pressure is effectively only acting on the rod area of the cylinder. 25

LECTURE 28 to 29 ACCUMULATORS FREQUENTLY ASKED QUESTIONS

LECTURE 28 to 29 ACCUMULATORS FREQUENTLY ASKED QUESTIONS LECTURE 28 to 29 ACCUMULATORS FREQUENTLY ASKED QUESTIONS 1. Define an accumulator and explain its function A hydraulic accumulator is a device that stores the potential energy of an incompressible fluid

More information

Unit 24: Applications of Pneumatics and Hydraulics

Unit 24: Applications of Pneumatics and Hydraulics Unit 24: Applications of Pneumatics and Hydraulics Unit code: J/601/1496 QCF level: 4 Credit value: 15 OUTCOME 2 TUTORIAL 2 HYDRAULIC AND PNEUMATIC CYLINDERS The material needed for outcome 2 is very extensive

More information

Example. Fluid Power. Circuits

Example. Fluid Power. Circuits Example Fluid Power Circuits To Enhance Symbol Reading Skills To Work On Circuit Reading Skills With Answers HI LO Pump Circuit 18 A1 B1 17 16 15 13 Set 14 2,000 PSI PG2 Set 500 PSI 12 11 7 8 10 PG1 9

More information

WHAT YOU DON T KNOW ABOUT ACCUMULATORS CAN KILL YOU!

WHAT YOU DON T KNOW ABOUT ACCUMULATORS CAN KILL YOU! WHAT YOU DON T KNOW ABOUT ACCUMULATORS CAN KILL YOU! Atlanta (Monroe) GA 770-267-3787 gpm@gpmhydraulic.com www.gpmhydraulic.com What You Don t Know About Hydraulic Accumulators Can Kill You TABLE OF CONTENTS

More information

APPLIED PNEUMATICS AND HYDRAULICS H TUTORIAL HYDRAULIC AND PNEUMATIC CYLINDERS. This work covers part of outcome 2 of the standard Edexcel module.

APPLIED PNEUMATICS AND HYDRAULICS H TUTORIAL HYDRAULIC AND PNEUMATIC CYLINDERS. This work covers part of outcome 2 of the standard Edexcel module. APPLIED PNEUMATICS AND HYDRAULICS H TUTORIAL HYDRAULIC AND PNEUMATIC CYLINDERS This work covers part of outcome 2 of the standard Edexcel module. The material needed for outcome 2 is very extensive so

More information

COUNTERBALANCE VALVES

COUNTERBALANCE VALVES COUNTERBALANCE VALVES Introduction They are modulating valves which allow free flow into the actuator and then block the reverse flow until they feel a pilot pressure inversely proportional to the load

More information

Material taken from Fluid Power Circuits and Controls, John S. Cundiff, 2001

Material taken from Fluid Power Circuits and Controls, John S. Cundiff, 2001 Pressure Control Chapter 3 Material taken from Fluid Power Circuits and Controls, John S. Cundiff, 2001 Introduction Pressure control is a key element in the design of any circuit. Used correctly, it can

More information

SIMPLIFIED VALVE CIRCUIT GUIDE

SIMPLIFIED VALVE CIRCUIT GUIDE SIMPLIFIED CIRCUIT GUIDE A GUIDE TO UNDERSTANDG PNEUMATIC DIRECTIONAL CONTROL S SOLENOID NO. 0 OUT 0 FLOW CONTROL METERED- FREE FLOW 0 0 OUT CYLDER TENDED Z-00 Compressed Air Valves Directional control

More information

PART 2 FORKLIFT HYDRAULIC SYSTEM

PART 2 FORKLIFT HYDRAULIC SYSTEM PART 2 FORKLIFT HYDRAULIC SYSTEM Chapter 1 Description and Operation Component Locations & Circuit Layouts 1 Hydraulic Pump 11 Control Valve 14 Valve Section Oil Flows 15 Anti-Cavitation Valve 22 Velocity

More information

FIXED DISPLACEMENT HYDRAULIC VANE PUMPS BQ SERIES

FIXED DISPLACEMENT HYDRAULIC VANE PUMPS BQ SERIES BQ FIXED DISPLACEMENT HYDRAULIC VANE PUMPS BQ SERIES Versatility, power, compactness and low running costs are the main characteristics of B&C vane pumps. All the components subject to wear are contained

More information

The Secret of Hydraulic Schematics. BTPHydraulics www.iranfluidpower.com

The Secret of Hydraulic Schematics. BTPHydraulics www.iranfluidpower.com The Secret of Hydraulic Schematics BTPHydraulics www.iranfluidpower.com www.iranfluidpower.com Table of Contents The Secret to Reading and Interpreting Hydraulic Schematics... 1 Hydraulic System Schematics...

More information

FIXED DISPLACEMENT HYDRAULIC VANE PUMPS BQ SERIES

FIXED DISPLACEMENT HYDRAULIC VANE PUMPS BQ SERIES BQ FIXED DISPLACEMENT HYDRAULIC VANE PUMPS BQ SERIES Versatility, power, compactness and low running costs are the main characteristics of B&C vane pumps. All the components subject to wear are contained

More information

FIXED DISPLACEMENT HYDRAULIC VANE PUMPS BQ SERIES

FIXED DISPLACEMENT HYDRAULIC VANE PUMPS BQ SERIES BQ FIXED DISPLACEMENT HYDRAULIC VANE PUMPS BQ SERIES Versatility, power, compactness and low running costs are the main characteristics of B&C vane pumps. All the components subject to wear are contained

More information

Quiz On Information Learned From Chapter 1

Quiz On Information Learned From Chapter 1 Quiz On Information Learned From Chapter 1 1. Most hydraulic circuits are designed by: A. mechanical engineers. B. fluid power engineers. C. fluid power distributor salesmen. 2. Atmospheric pressure at

More information

Hydraulic control unit series 0086-372-01

Hydraulic control unit series 0086-372-01 Technical Product Information No. 1290 EN Hydraulic control unit series 0086-372-01 Contents Page About this Technical Product Information (TPI) 2 The ORTLINGHAUS numbering system 2 About the product 3

More information

Unit 24: Applications of Pneumatics and Hydraulics

Unit 24: Applications of Pneumatics and Hydraulics Unit 24: Applications of Pneumatics and Hydraulics Unit code: J/601/1496 QCF level: 4 Credit value: 15 OUTCOME 2 TUTORIAL 4 DIRECTIONAL CONTROL VALVES The material needed for outcome 2 is very extensive

More information

Basic Symbols. Lines. Circular. Square. Diamond. Miscellaneous Symbols. -continuous line - flow line. -dashed line - pilot, drain

Basic Symbols. Lines. Circular. Square. Diamond. Miscellaneous Symbols. -continuous line - flow line. -dashed line - pilot, drain Airline Hydraulic's Main Page Basic Symbols Lines continuous line flow line dashed line pilot, drain envelope long and short dashes around two or more component symbols. Circular Square Diamond large circle

More information

Chapter 7 Hydraulic System Troubleshooting

Chapter 7 Hydraulic System Troubleshooting Chapter 7 Hydraulic System Troubleshooting General The following troubleshooting information is provided as a general guide to identify, locate and correct problems that may be experienced with the hydraulic

More information

Schematic Symbols Chart (Design Hydraulic and Pneumatic circits)

Schematic Symbols Chart (Design Hydraulic and Pneumatic circits) Page 1 of 6 (Home) Symbols / Visit us on: Fluid Power, Automation and Motion Control for all Industries About Us Products Services Catalogs Place an Order Training & Information Contact Us Employee Access

More information

SERIES ASM NEOPRENE/EPMD FLANGED SINGLE SPHERE CONNECTOR CONNECTORS. Pressures to 225 PSIG (15.51 barg) Temperatures to 230ºF (110ºC)

SERIES ASM NEOPRENE/EPMD FLANGED SINGLE SPHERE CONNECTOR CONNECTORS. Pressures to 225 PSIG (15.51 barg) Temperatures to 230ºF (110ºC) APPLICATIONS Process Industry Weak Acids Alkalies Compressed Air Pulp & Paper MODELS ASM - Flanged Connection OPTIONS Control Rods Oil & Gas Water & Waste Pump suction & discharge Sea water Chemical lines

More information

Hydraulic Troubleshooting PRESENTED BY

Hydraulic Troubleshooting PRESENTED BY Hydraulic Troubleshooting PRESENTED BY NORMAN KRONOWITZ Introduction Welcome to the CMA/Flodyne/Hydradyne s Hydraulic Troubleshooting presentation. We will introduce many aspects of troubleshooting hydraulic

More information

TECHNICAL BULLETIN. Meritor WABCO Cab Leveling Valves and Chassis Leveling Valves. How the Cab Leveling and Chassis Leveling Valves Work

TECHNICAL BULLETIN. Meritor WABCO Cab Leveling Valves and Chassis Leveling Valves. How the Cab Leveling and Chassis Leveling Valves Work Revised 02-00 TECHNICAL BULLETIN Meritor WABCO Cab Leveling Valves and Chassis Leveling Valves This technical bulletin covers both cab and chassis leveling valves manufactured by Meritor WABCO. While the

More information

HYDRAULIC CIRCUIT DESIGN AND ANALYSIS

HYDRAULIC CIRCUIT DESIGN AND ANALYSIS HYDRAULIC CIRCUI DESIGN AND ANALYSIS A Hydraulic circuit is a group of components such as pumps, actuators, and control valves so arranged that they will perform a useful task. When analyzing or designing

More information

Maxi-Stamper. 200 to 1,000 Tons STAMPING OUT DOWNTIME

Maxi-Stamper. 200 to 1,000 Tons STAMPING OUT DOWNTIME TM Maxi-Stamper 200 to 1,000 Tons STAMPING OUT DOWNTIME Standard Features Steel Fabricated Construction Drive Capacity Rated 1/2 Above Bottom of Stroke Self-Diagnostic Solid State Controller Moveable Operator

More information

SIMPLIFIED VALVE CIRCUIT GUIDE

SIMPLIFIED VALVE CIRCUIT GUIDE NA-09 FLOW CONTROL METERED- FREE FLOW UT OUT CYLDER TENDED SOLENOID NO. A Guide to Understanding Pneumatic Directional Control Valves SIMPLIFIED CIRCUIT GUIDE 0 0 0 0 Compressed Air Valves Directional

More information

Steering unit. Table of contents. Features RE 11872/05.06. Type LAGL. Frame sizes 500 to 1000 Component series 1X Maximum flow 80 l/min

Steering unit. Table of contents. Features RE 11872/05.06. Type LAGL. Frame sizes 500 to 1000 Component series 1X Maximum flow 80 l/min Steering unit RE 11872/05.06 /10 Type LAGL Frame sizes 500 to 1000 Component series 1X Maximum flow 80 l/min H7375 Table of contents Contents Page Features 1 Ordering code 2 Function, section 3 Device

More information

Oil and Coolant Circulating Heating System. Model - OCSM

Oil and Coolant Circulating Heating System. Model - OCSM Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine

More information

Rexroth Hydraulic Pump A10VO Series User Manual

Rexroth Hydraulic Pump A10VO Series User Manual Rexroth Hydraulic Pump A10VO Series User Manual Rexroth Hydraulic pump A10VO Series User Manual Revised 5/1/2009 Page 1 of 12 Functional Purpose This pump is preferred over a fixed displacement (gear)

More information

Piston Accumulators. SK Series. Accumulator Catalog. Piston Types. Description. Sealing Systems. End Cap. O-ring. Sealing System. Piston.

Piston Accumulators. SK Series. Accumulator Catalog. Piston Types. Description. Sealing Systems. End Cap. O-ring. Sealing System. Piston. SK Series Piston Types TYPE 2 pplication: Low-friction design for higher piston speeds, slow movements without stick-slip effect and high number of actuations (millions). ctual cycles achieved will vary

More information

OPERATING and MAINTENANCE MANUAL SERIES 2700A CONTROL VALVE CONTENTS. INTRODUCTION...1 Scope...1 Description...1 Valve Identification...

OPERATING and MAINTENANCE MANUAL SERIES 2700A CONTROL VALVE CONTENTS. INTRODUCTION...1 Scope...1 Description...1 Valve Identification... OPERATING and MAINTENANCE MANUAL SERIES 2700A CONTROL VALVE CONTENTS INTRODUCTION...1 Scope...1 Description...1 Valve Identification...2 1.0 VALVE INSTALLATION...2 2.0 VALVE MAINTENANCE...3 Actuator Disassembly...3

More information

Why and How we Use Capacity Control

Why and How we Use Capacity Control Why and How we Use Capacity Control On refrigeration and air conditioning applications where the load may vary over a wide range, due to lighting, occupancy, product loading, ambient weather variations,

More information

Basic Hydraulics and Pneumatics

Basic Hydraulics and Pneumatics Basic Hydraulics and Pneumatics Module 1: Introduction to Pneumatics PREPARED BY IAT Curriculum Unit March 2011 Institute of Applied Technology, 2011 ATM 1122 Basic Hydraulics and Pneumatics Module 1:

More information

Introduction to Pneumatics and Pneumatic Circuit Problems for FPEF Trainer

Introduction to Pneumatics and Pneumatic Circuit Problems for FPEF Trainer and Pneumatic Circuit Problems for FPEF Trainer John R. Groot President FPEF John Nagohosian FPEF Educational Coordinator John Prisciandaro Birmingham Covington School Birmingham, Michigan Dan Butchko

More information

Subminiature Load Cell Model 8417

Subminiature Load Cell Model 8417 w Technical Product Information Subminiature Load Cell 1. Introduction... 2 2. Preparing for use... 2 2.1 Unpacking... 2 2.2 Using the instrument for the first time... 2 2.3 Grounding and potential connection...

More information

SECTION G2: CABLE PROCESSOR MODULE MAINTENANCE

SECTION G2: CABLE PROCESSOR MODULE MAINTENANCE SECTION G2: CABLE PROCESSOR MODULE MAINTENANCE Cable Processor Module overview WARNING! When tipping the Cable Processor Module back, (after removing the toggle arm pin), use extreme caution not to drop

More information

Unit 24: Applications of Pneumatics and Hydraulics

Unit 24: Applications of Pneumatics and Hydraulics Unit 24: Applications of Pneumatics and Hydraulics Unit code: J/601/1496 QCF level: 4 Credit value: 15 OUTCOME 2 TUTORIAL 3 HYDRAULIC AND PNEUMATIC MOTORS The material needed for outcome 2 is very extensive

More information

PVH131/141 Variable Displacement Piston Pump - 11 Design

PVH131/141 Variable Displacement Piston Pump - 11 Design Service Data Vickers Piston Pumps PVH131/141 Variable Displacement Piston Pump - 11 Design Revised 05/01/97 M-2209-S Maximum Adjustable Stop S Option 913341 Locknut Torque 25-50 N.m. (18-37 lb. ft.) Torque

More information

Model F822 thru F834 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description

Model F822 thru F834 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description Worldwide Contacts www.tyco-fire.com Model F thru F3 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description The Mulsifyre Nozzles are open (nonautomatic) nozzles and they are designed

More information

Volkswagen Jetta, Golf, GTI 1999, 2000 2.8 Liter VR6 2V Engine Mechanical, Engine Code(s): AFP 17 Engine-Lubrication (Page GR-17)

Volkswagen Jetta, Golf, GTI 1999, 2000 2.8 Liter VR6 2V Engine Mechanical, Engine Code(s): AFP 17 Engine-Lubrication (Page GR-17) 17 Engine-Lubrication (Page GR-17) Lubrication system components, removing and installing Oil filter housing, disassembling and assembling Oil pan, removing and installing Oil pressure and oil pressure

More information

Industrial Process Pump Safety Manual IMPORTANT SAFETY NOTICE

Industrial Process Pump Safety Manual IMPORTANT SAFETY NOTICE Industrial Process Pump Safety Manual IMPORTANT SAFETY NOTICE To: Our Valued Customers User safety is a major focus in the design of our products. Following the precautions outlined in this manual will

More information

IMPORTANT SAFETY NOTICE

IMPORTANT SAFETY NOTICE IMPORTANT SAFETY NOTICE To: Our Valued Customers User safety is a major focus in the design of our products. Following the precautions outlined in this manual will minimize your risk of injury. ITT Goulds

More information

Automatic Back-Flushing Filter AutoFilt RF9.

Automatic Back-Flushing Filter AutoFilt RF9. Automatic Back-Flushing Filter AutoFilt RF9. AutoFilt RF9 Clearing the Way. The Challenge: In response to the Tier III standard which will come into effect in 2016, the International Maritime Organization

More information

Installation and Operating Instructions Installation Instructions for SS EPE-316L Series

Installation and Operating Instructions Installation Instructions for SS EPE-316L Series INSTR3010 0406 Installation and Operating Instructions Installation Instructions for SS EPE-316L Series Congratulations on your purchase of this Aqua-Pure high flow, single housing filtration system. This

More information

NFPA31FuelOilPiping 1 Revised 3-1-11

NFPA31FuelOilPiping 1 Revised 3-1-11 NFPA 31 Fuel Oil Piping, Installation and Testing Chapter 8 Fuel Piping Systems and Components 8.1 Scope. This chapter shall apply to piping systems and their components used to transfer fuel oil from

More information

Class 5 to 7 Truck and Bus Hydraulic Brake System

Class 5 to 7 Truck and Bus Hydraulic Brake System Class 5 to 7 Truck and Bus Hydraulic Brake System Diagnostic Guide 1st Edition * 5+0 Important Service tes The information in this publication was current at the time of printing. The information presented

More information

Series 30000 Hose Reels

Series 30000 Hose Reels Operating Instructions and Parts List for Series 30000 Hose Reels - MANUAL DRIVEN - - POWER DRIVEN - SAFETY PRECAUTIONS Personal injury and/or equipment damage may result if proper safety precautions are

More information

Unit 24: Applications of Pneumatics and Hydraulics

Unit 24: Applications of Pneumatics and Hydraulics Unit 24: Applications of Pneumatics and Hydraulics Unit code: J/601/1496 QCF level: 4 Credit value: 15 OUTCOME 2 TUTORIAL 1 HYDRAULIC PUMPS The material needed for outcome 2 is very extensive so there

More information

Volkswagen Jetta, Golf, GTI 1999, 2000 Brake System 47 Brakes - Hydraulic Components (Page GR-47)

Volkswagen Jetta, Golf, GTI 1999, 2000 Brake System 47 Brakes - Hydraulic Components (Page GR-47) 47 Brakes - Hydraulic Components (Page GR-47) FS III front brake calipers, servicing Front brake caliper piston, removing and installing FN 3 front brake calipers, servicing Front caliper piston, removing

More information

ACADEMIC TEXTBOOK FLUID POWER CONTROL SYSTEMS. The lecture: 15 hours. Kielce University of Technology Faculty of Mechatronics and Machine Design

ACADEMIC TEXTBOOK FLUID POWER CONTROL SYSTEMS. The lecture: 15 hours. Kielce University of Technology Faculty of Mechatronics and Machine Design ACADEMIC TEXTBOOK FLUID POWER CONTROL SYSTEMS The lecture: 15 hours Kielce University of Technology Faculty of Mechatronics and Machine Design Author: Ryszard Dindorf Kielce, 2011/2012 1. Fluid power basic

More information

The Axial Flow Valve. Class 300/600. sales@elster-instromet.co.uk www.elster-instromet.com SERIES

The Axial Flow Valve. Class 300/600. sales@elster-instromet.co.uk www.elster-instromet.com SERIES The Axial Flow Valve SERIES Class 300/600 sales@elster-instromet.co.uk www.elster-instromet.com THE AXIAL FLOW VALVE - SERIES 300/600 A UNIQUE REGULATOR What is the Axial Flow Valve? The Axial Flow Valve

More information

MONO BLOCK DIRECTIONAL CONTROL VALVE TS1120TSLB

MONO BLOCK DIRECTIONAL CONTROL VALVE TS1120TSLB MONO BLOCK DIRECTIONAL CONTROL VALVE TS112TSLB TS TS212TSTSJB P T TS312TSDTSTKJ TS112TSJB FEATURES: O RG PORTS to eliminate leakage. POWER BEYOND CAPABILITY to fit your multi valve circuits. BUILT ANTI-DROP

More information

GS-General Service Control Valves

GS-General Service Control Valves GS-General Service Control Valves GS-General Service Valves The GS-General Service Valves continue Copes-Vulcan s tradition of designing and manufacturing control valves that provide both exceptional service

More information

SE-100-1, SE-200-1, SE-500-1, and SE-1000-1 AIR CHAMP PRODUCTS. User Manual SE BRAKE MODELS: (i) MTY (81) 83 54 10 18 ventas@industrialmagza.

SE-100-1, SE-200-1, SE-500-1, and SE-1000-1 AIR CHAMP PRODUCTS. User Manual SE BRAKE MODELS: (i) MTY (81) 83 54 10 18 ventas@industrialmagza. AIR CHAMP PRODUCTS User Manual SE BRAKE MODELS: SE-00-, SE-200-, SE-500-, and SE-000- (i) FORM NO. L-20084-E-040 In accordance with Nexen s established policy of constant product improvement, the specifications

More information

Flow divider (flow distributor), type TQ

Flow divider (flow distributor), type TQ Flow divider (flow distributor), type TQ Pressure p max = 0 bar Flow Q CN max = 00 lpm Share ratio = :. General Task Flow dividers type TQ are self-regulating valves, which largely irrespective of the

More information

Tech. Services: (800) 477-8326 Fax: (800) 765-8326 Order Entry: (800) 541-1418 Fax: (800) 288-7031 Internet Address: http://www.powerteam.

Tech. Services: (800) 477-8326 Fax: (800) 765-8326 Order Entry: (800) 541-1418 Fax: (800) 288-7031 Internet Address: http://www.powerteam. ORIGINAL INSTRUCTIONS Form No.102842 5 SPX Hydraulic Technologies 5885 11th Street Rockford, IL 61109-3699 USA Tech. Services: (800) 477-8326 Fax: (800) 765-8326 Order Entry: (800) 541-1418 Fax: (800)

More information

SELECTION, APPLICATION AND MAINTENANCE

SELECTION, APPLICATION AND MAINTENANCE DIESEL PROTECTION SYSTEMS D-Series Engine Automatic Overspeed Shut Down Valves (Spindle Types with Air Pressure and Manual Shut Down Options) SELECTION, APPLICATION AND MAINTENANCE Valve Numbers D92-AP

More information

V47 Series Temperature Actuated Modulating Water Valves

V47 Series Temperature Actuated Modulating Water Valves V47 Series Temperature Actuated Modulating Water Valves Master Catalog 125 Valves, Miscellaneous (Other Than Gas) Section V Product Bulletin V47 Issue Date 0286 Application The V47 modulating valves regulate

More information

Pump ED 101. Positive Displacement Pumps. Part I Reciprocating Pumps

Pump ED 101. Positive Displacement Pumps. Part I Reciprocating Pumps Pump ED 101 Positive Displacement Pumps Part I Reciprocating Pumps Joe Evans, Ph.D http://www.pumped101.com There are many pump designs that fall into the positive displacement category but, for the most

More information

HYDRAULIC LIFT TABLE CART 2200-LB.

HYDRAULIC LIFT TABLE CART 2200-LB. HYDRAULIC LIFT TABLE CART 2200-LB. OWNER S MANUAL WARNING: Read carefully and understand all MACHINE ADJUSTMENT AND OPERATION INSTRUCTIONS before operating. Failure to follow the safety rules and other

More information

Document Title Press Maintenance Checklist used in performing routine maintenance on punch presses

Document Title Press Maintenance Checklist used in performing routine maintenance on punch presses Document Title Press Maintenance Checklist used in performing routine maintenance on punch presses Press Maintenance Check List Daily (before each shift) Point of operation guards and devices Other equipment

More information

Signature and ISX CM870 Fuel System

Signature and ISX CM870 Fuel System Signature and ISX CM870 Fuel System Cummins Ontario Training Center HPI-TP Fuel System Heavy Duty High Pressure Injection - Time Pressure Fuel System The fuel system developed for the Signature and ISX

More information

Hydraulic Trouble Shooting

Hydraulic Trouble Shooting Hydraulic Trouble Shooting Hydraulic systems can be very simple, such as a hand pump pumping up a small hydraulic jack, or very complex, with several pumps, complex valving, accumulators, and many cylinders

More information

Pressure Relief and Regulating Valves

Pressure Relief and Regulating Valves Pressure Relief and Regulating Valves With blocked center directional valves and variable displacement pumps, or open center directional valves and fixed displacement pumps where fast response, low leakage

More information

Trouble Shooting. Pump

Trouble Shooting. Pump Trouble Shooting Pump Trouble Possible Cause Remedy Oil leaking in the area of water pump crankshaft Worn crankshaft seal, bad bearing, grooved shaft, or failure of retainer o-ring. Excessive play on crankshaft

More information

Standard Hydraulic Piping Flushing Procedure

Standard Hydraulic Piping Flushing Procedure Page 1 of 6 1.0 Scope This procedure covers the minimum technical requirements for cleaning and flushing of Hydraulic and Piping, and related accessories. 2.0 Introduction In hydraulic fluid power systems,

More information

System Saver 318 Air Compressor for Mack E-Tech and ASET Engines

System Saver 318 Air Compressor for Mack E-Tech and ASET Engines Maintenance Manual 31 System Saver 318 Air Compressor for Mack E-Tech and ASET Engines Revised 08-05 NON-THROUGH DRIVE THROUGH DRIVE Service Notes About This Manual This manual provides service and repair

More information

Table of Contents. Overview 1. Pump Disassembly 2. Control Disassembly / Reassembly 7. Pump Reassembly 13. Adjustment Procedures DR Control 19

Table of Contents. Overview 1. Pump Disassembly 2. Control Disassembly / Reassembly 7. Pump Reassembly 13. Adjustment Procedures DR Control 19 Table of Contents Overview 1 Pump Disassembly 2 Control Disassembly / Reassembly 7 Pump Reassembly 13 Adjustment Procedures DR Control 19 Adjustment Procedures DRG Control 20 Adjustment Procedures DFR

More information

AWWA Butterfly Valve Operation and Maintenance Manual Series 511A & 510A 20 and Smaller

AWWA Butterfly Valve Operation and Maintenance Manual Series 511A & 510A 20 and Smaller January 2013 AWWA Butterfly Valve Operation and Maintenance Manual Series 511A & 510A 20 and Smaller Milliken Valve Company 190 Brodhead Avenue, Suite 100 Bethlehem, PA 18017 Phone: (610) 861-8803 Fax:

More information

Engineering & Testing Services. Hydraulic Fitting Design and Hydro-Mechanical Testing

Engineering & Testing Services. Hydraulic Fitting Design and Hydro-Mechanical Testing Engineering & Testing Services Hydraulic Fitting Design and Hydro-Mechanical Testing Aerofit, Inc. APT Laboratory 1425 South Acacia Avenue Fullerton, CA 92831 Main: 714-521-5060 Fax: 714-535-9862 Our Company

More information

TYPE E Main Valve Sizes 3 /8 through 12

TYPE E Main Valve Sizes 3 /8 through 12 SD 3001F PRINTED IN U.S.A. SD 3001F/0707 A B TYPE E MAIN VALVE C D E TYPE E Main Valve Sizes 3 /8 through 12 The Spence Type E Main Valve is of normally closed, single seat design featuring packless construction,

More information

SureSite Magnetic Liquid Level Indicator

SureSite Magnetic Liquid Level Indicator SureSite Magnetic Liquid Level Indicator Instruction Bulletin No. 177664-1 (Rev. E) Section 1: Weldments Thank you for purchasing the GEMS SureSite Magnetic Level Indicator. Please read this document prior

More information

3. X-REAS (Relative Absorber System)

3. X-REAS (Relative Absorber System) CH-57 3. X-REAS (Relative Absorber System) General The oil passages of the front and rear shock absorbers of the X-REAS are connected diagonally, with a center control absorber interposed. This ensures

More information

Hydraulic Accumulators Introduction. Page Accumulator Selection Guide. Design Features and Construction. Charging Valve.

Hydraulic Accumulators Introduction. Page Accumulator Selection Guide. Design Features and Construction. Charging Valve. Design Features and Construction Piston Accumulators Parker piston accumulators consist of a cylindrical body, sealed by a gas cap and charging valve at the gas end, and by a hydraulic cap at the hydraulic

More information

HYDRAULIC ACCUMULATOR. Energy buffering applications APPLICATIONS OSP 035. Applications with short term high quantity oil requirements

HYDRAULIC ACCUMULATOR. Energy buffering applications APPLICATIONS OSP 035. Applications with short term high quantity oil requirements HYDRAULIC ACCUMULATOR APPLICATIONS OSP 035 Energy buffering applications Energy saving - the capacity of buffering energy is one of the main features of OLAER hydraulic accumulators. Hydraulic installations

More information

81000 Series Aluminum Gate Valve Installation and Repair Manual

81000 Series Aluminum Gate Valve Installation and Repair Manual High Vacuum Valves Leader in Quality and Value 81000 Series Aluminum Gate Valve Installation and Repair Manual Dear Customer, Thank you for choosing HVA as your vacuum valve supplier. Your valve will give

More information

Mechanical Installation

Mechanical Installation Page -1-1. INTRODUCTION AND PURPOSE 1.1. This specification covers the installation, testing and precommissioning of mechanical equipment. Work is to be performed in conjunction with the manufacturer s

More information

Introduction to Process Control Actuators

Introduction to Process Control Actuators 1 Introduction to Process Control Actuators Actuators are the final elements in a control system. They receive a low power command signal and energy input to amplify the command signal as appropriate to

More information

*Rated to 207 Bar/3000 PSI with Aluminum Body. Catalog HY15-3501/US SERIES CAVITY DESCRIPTION FLOW PRESSURE PAGE NO.

*Rated to 207 Bar/3000 PSI with Aluminum Body. Catalog HY15-3501/US SERIES CAVITY DESCRIPTION FLOW PRESSURE PAGE NO. Bodies & Contents SERIES CAVITY DESCRIPTION FLOW PRESSURE PAGE NO. /GPM BAR/PSI STANDARD CHECKS D1A6... 2U... Valve Insert, Ball Type...145/38... 42/6... 5 D1B125... 2C... Valve Insert, Ball Type... 5/132...

More information

MASTER CYLINDER. Section 2. Master Cylinder. Tandem Master Cylinder. Master Cylinder

MASTER CYLINDER. Section 2. Master Cylinder. Tandem Master Cylinder. Master Cylinder MASTER CYLINDER Master Cylinder The master cylinder converts the motion of the brake pedal into hydraulic pressure. It consists of the reservoir tank, which contains the brake fluid; and the piston and

More information

hance the application of specific components, such as pumps, motors, accumulators, filters, and airline lubricators.

hance the application of specific components, such as pumps, motors, accumulators, filters, and airline lubricators. Basic circuits Using schematic symbols as building blocks, you can construct a functional diagram showing piping arragnements and operation of any hydraulic or pneumatic circuit. hance the application

More information

ISO/VDMA Actuators. Engineering GREAT Solutions

ISO/VDMA Actuators. Engineering GREAT Solutions ISO/VDMA Actuators Engineering GREAT Solutions 02 ISO/VDMA Actuators Contents 03 Introduction 04 ISO/VDMA Actuators 06 The ISO/VDMA Range 08 Industrial Options 10 Cleanline Options 12 IVAC innovation to

More information

Cane Creek Double Barrel Instructions

Cane Creek Double Barrel Instructions Cane Creek Double Barrel Instructions Congratulations on your purchase of the Cane Creek Double Barrel (CCDB) rear shock. Developed in partnership with Öhlins Racing, the Double Barrel brings revolutionary

More information

Bearing Failure: Causes and Cures

Bearing Failure: Causes and Cures Bearing Failure: Causes and Cures bearing.ppt Page 1 Excessive loads usually cause premature fatigue. Tight fits, brinelling and improper preloading can also bring about early fatigue failure. The solution

More information

Static Electricity. A Health and Safety Guideline for Your Workplace. What Are Some Sources of Static Electricity? What is Static Electricity?

Static Electricity. A Health and Safety Guideline for Your Workplace. What Are Some Sources of Static Electricity? What is Static Electricity? A Health and Safety Guideline for Your Workplace What is static electricity? What causes it? How is it hazardous? And, most importantly, how can it be controlled? All of these questions will be answered

More information

Direct Operated Regulator for 6.0 MPa (Relieving Type) How to Order. Body size 30 40

Direct Operated Regulator for 6.0 MPa (Relieving Type) How to Order. Body size 30 40 Direct Operated Regulator for (Relieving Type) Series Service life: 0 million cycles Using NSF-H-certified grease on the guide ring (sliding) part. Improved durability under a high environment with a polyurethane

More information

Cartridge Valves. Solenoid Valves. Vickers. Screw-in Cartridge Valves. Maximum Pressure 210 bar (3000 psi) Maximum Flow 227 l/min (60 USgpm)

Cartridge Valves. Solenoid Valves. Vickers. Screw-in Cartridge Valves. Maximum Pressure 210 bar (3000 psi) Maximum Flow 227 l/min (60 USgpm) Vickers Cartridge Valves Solenoid Valves Screw-in Cartridge Valves Maximum Pressure bar ( psi) Maximum Flow 7 l/min (6 USgpm) Rev /99 77 Introduction For over seventy years, Vickers has provided its customers

More information

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable

More information

Unit: mm(in) Item Standard value Service limit Axle shaft run out - 0.2(0.008)

Unit: mm(in) Item Standard value Service limit Axle shaft run out - 0.2(0.008) Rear Wheel/Brake/Suspension 13. Rear Wheel/Brake/Suspension Service Information 13-1 Troubleshooting 13-2 Rear Wheel 13-3 Rear Cushion 13-4 Rear Swing Arm 13-7 Service Information General Safety If the

More information

Presented by Rory S. McLaren. SAFE by DESIGN

Presented by Rory S. McLaren. SAFE by DESIGN Presented by Rory S. McLaren Copyright 2013 1 Hydraulic safety doesn t just happen, it has to be pursued! Safety MUST be the nucleus of hydraulic system design. The responsibility of safe design must be

More information

MP-4V Heavy Duty Riveter / 39048

MP-4V Heavy Duty Riveter / 39048 MP-4V Heavy Duty Riveter / 39048 This newly designed heavy-duty air/hydraulic riveter is ergonomically designed with the professional in mind. The light weight 3.7 lbs. well balanced MP-4V includes a Vacuum

More information

Round Housing with Side Ports

Round Housing with Side Ports Power Steering Steering Control Unit (SCU) Parts and Repair Information 5 Series Steering Control Units 001 Square Housing with Side Ports Round Housing with Side Ports T E L RP Round Housing with End

More information

ENGINEERING SPECIFICATIONS FOR CO2 EXTINGUISHING AGENT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS

ENGINEERING SPECIFICATIONS FOR CO2 EXTINGUISHING AGENT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS ENGINEERING SPECIFICATIONS FOR CO2 EXTINGUISHING AGENT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS SECTION 1 GENERAL SPECIFICATIONS I. SCOPE This specification outlines the requirements for a pre-engineered

More information

STORAGE, INSTALLATION AND MAINTENANCE PROCEDURES

STORAGE, INSTALLATION AND MAINTENANCE PROCEDURES GATE VALVE O.S. & Y 1.0 Periodic Inspections 1.1 The valve stem packing should be inspected at least monthly. If the stem packing shows signs of leakage, simply tighten the adjusting nuts to compress the

More information

DIESEL FUEL CONDITIONING

DIESEL FUEL CONDITIONING COD FILTRATION DIESEL FUEL CONDITIONING REMOVE WATER & PARTICLES TO EXTEND FUEL INJECTOR LIFE & INCREASE COMBUSTION ENGINE FUEL EFFICIENCY Remove free water to saturation point with high single pass efficiency

More information

Series PVP Variable Volume Piston Pumps

Series PVP Variable Volume Piston Pumps Series PVP Variable Volume Piston Pumps Catalog HY28-2662-CD/US Revised June, 212 hpm12-1.p65, lw, jk 1 Notes Series PVP hpm12-1.p65, lw, jk 2 Introduction Series PVP Series Sizes 6-14 Phased Out For Reference

More information

WILROY. Operation. Optional Diaphragm Rupture Detection HYDRAULICALLY ACTUATED DIAPHRAGM PUMP

WILROY. Operation. Optional Diaphragm Rupture Detection HYDRAULICALLY ACTUATED DIAPHRAGM PUMP WILROY ATEX Approved HYDRAULICALLY ACTUATED DIAPHRAGM PUMP Williams and Milton Roy have combined technologies to design a pump blending the proven mroy hydraulic by-pass diaphragm design with the Williams

More information

26 3213.13 Diesel Engine Driven Generators Page 1 of 6

26 3213.13 Diesel Engine Driven Generators Page 1 of 6 Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at

More information

Hydraulic Flow Control Valves

Hydraulic Flow Control Valves Webtec Products Limited Hydraulic Flow Control Valves Quality Hydraulic Components from the Webtec Range CONTENTS DESCRIPTION PAGE No. ILFC Series Fixed Flow Pressure Compensated Control Valve 1 VFC Series

More information

DiscPlus DX195 and DX225 Air Disc Brakes

DiscPlus DX195 and DX225 Air Disc Brakes Revised 11-04 Technical Bulletin Revised 1 Technical 11-04 Bulletin DiscPlus DX195 and DX225 Air Disc Brakes Inspection, Installation and Diagnostics Air Disc Brake Inspection Intervals and Procedures

More information

Vehicle Fire Protection. An Ownerʼs Manual for ANSUL Fire Suppression/Detection Systems

Vehicle Fire Protection. An Ownerʼs Manual for ANSUL Fire Suppression/Detection Systems Vehicle Fire Protection An Ownerʼs Manual for ANSUL Fire Suppression/Detection Systems 002792 Off-road vehicles do have fires Statistics show that off-road vehicles burn with alarming frequency. These

More information