1 DESIGO with VISONIK building automation system Answers for infrastructure.

2 DESIGO high energy efficiency and flexibility to protect your investments Making efficient savings without sacrifices with the building automation system DESIGO, you can achieve significant energy savings while at the same time you will benefit from a pleasant room climate and optimum comfort. Especially thanks to features such as centralized, intelligent energy management, highly efficient and innovative energy saving functions, and the effective interaction of all system components and processes. With DESIGO, you also benefit from a kind of flexibility that protects your investments throughout their entire life cycle. Not only can our system be tailored precisely to suit your building and applications, but it can also be easily adapted to changes in your requirements and expanded at any time.

3 Content DESIGO the flexible building automation and control system...5 Highest degree of energy efficiency...5 Protect investment over the entire life-cycle of the building...5 DESIGO System topology with VISONIK...6 Automation level VISONIK...7 BPS process station...7 DESIGO building automation and control with VISONIK...8 Comprehensive functionality uniform operation...8 Data and communication server (DCS)...9 Communication between system levels...10 Data points and parameters...10 System operation...11 Reporting...12 Data logging...12 Reaction programs...13 DESIGO I/O modules...14 Overview of TX-I/O modules...15 DESIGO with VISONIK: Migration as the bridge to the future...16 The path to DESIGO...16 Advantages of DESIGO with VISONIK...17 System functions...17 Management level...17 Automation level...17 System functions...18 Operation and monitoring...18 Trend/History...19 Alarm management...19 Scheduler / Calendar...20 Access rights...21 Communication - Networks...22 Communication standards specially developed for building services technology...22 The management level - DESIGO INSIGHT...23 Taskbar...24 Plant Viewer...25 Time Scheduler...26 Alarm Viewer...27 Alarm Router...28 Trend Viewer...29 Object Viewer...30 Log Viewer...31 Report Viewer / 72

4 Reaction Processor...33 Operation and monitoring with Web technology...33 DESIGO High Availability Solution...35 The DESIGO PX automation level...36 A range of graded operator units...36 Operation at the automation level...37 Freely-programmable automation stations...40 Room automation - DESIGO RX...45 Convenient room automation with DESIGO RX...45 Product range overview: DESIGO RXC...46 Product range overview: DESIGO RXB...47 Product range overview - DESIGO RXL...47 Applications...49 DESIGO OPEN...51 DESIGO INSIGHT OPEN...52 DESIGO SX OPEN...53 DESIGO PX OPEN...54 DESIGO TX OPEN...55 DESIGO tools...55 DESIGO XWORKS plus...56 Programming with D-MAP...57 Proven application solutions...58 DESIGO S The automation level - SIMATIC S7 for industrial applications...59 Communication processor CP BACnet...61 The field level - SIMATIC ET 200 S...61 Local operation and monitoring...61 Energy management...62 Software package for energy efficient building operation...62 Pharma Solution...64 Integrated regulatory compliance for DESIGO INSIGHT...64 InfoCenter...66 GxP compliant monitoring and reporting...66 Data security...66 Reliable data archival...66 Technical solutions for 21 CFR Part System topologies...68 System design for small buildings...68 System design for small to medium-sized buildings...69 System design for medium-sized to large building complexes / 72

5 DESIGO the flexible building automation and control system The DESIGOTM system is a forward-looking family of freely programmable management and automation stations for the full spectrum of building services applications in today's world. With system functions such as alarm management, time scheduling, and trend logging, combined with sophisticated control functions, DESIGO is a highly versatile asset in a building. Innovative Web technology, powerful databases and open communications make DESIGO a financially wise investment in the future. Scalable from small to large projects with the highest degree of energy efficiency, transparency and optimum operations as well as applications for infrastructure and industry. DESIGO is consistent in its support of open communications, making it easy to connect a wide variety of building services equipment on the basis of standard open data interfaces: BACnetTM for the automation level and management level network LonWorks and Konnex (KNX) S-Mode (instabus EIB) to network room automation and decentralized secondary processes M-Bus, Modbus, OPC and other interfaces for universal connection of third-party devices and systems TCP/IP network protocol Highest degree of energy efficiency The tested DESIGO plant applications comply with European standard EN in the highest energy efficiency classes. You can save, for example, up to 30% percent on energy in offices compared to standard systems through the use of proven and predefined energy savings functions. A number of DESIGO room applications are already eu.bac certified. The DESIGO INSIGHT management station uses life-like graphics to portray complex issues in an easy-to-read way. Trend curves are easily evaluated and analyzed on both the PXM20 operator units as well as the management station. Plant operations are simple to optimize in this manner and allow operators to operate the entire building services plants in an energy efficient manner. Protect investment over the entire life-cycle of the building With its flexible range of automation stations, room controllers and operator units, DESIGO is ideally suited to projects of all sizes and for all types of building. A flat system topology permits low-cost entry with small systems which can be extended and expanded as required. Consistent compatibility protects investment over decades and throughout the entire building life-cycle. DESIGO integrates existing automation systems VISONIK seamlessly and carries them forward into the future. Changes in use, system expansion and retrofit projects can all be handled in gradual stages. 5 / 72

6 DESIGO System topology with VISONIK The DESIGO system can be divided into two levels: Management level Automation level The automation level forms the interface to the field level and includes room automation as well. By virtue of distributed intelligence, each of these levels operates both autonomously and in a network. The principal DESIGO system components: DESIGO INSIGHT management station for higher-level operation and monitoring, graphics-based display of the process, automatic alarm distribution and a wide range of different data analysis options. DESIGO PX automation system for control and for operation and monitoring of primary plants. By use of PX-WEB, the automation system can also be operated via a Web client. The VISONIK automation system as homogeneous part of the DESIGO system. DESIGO TX-I/O and PTM I/O modules, which provide the interface to the devices at the field level, the sensors and actuators. DESIGO RX room automation system for control of comfort conditions in individual rooms, and for operation of lighting and blinds. DESIGO OPEN for the integration of a wide variety of plants at all levels of the system. DESIGO Overall system topology with VISONIK One of the key benefits of DESIGO is its scope for gradual expansion, from the smallest systems to large, distributed systems. Scalability is illustrated using example topologies in the appendix. Existing VISONIK process devices are homogeneously integrated into the DESIGO system achieving expanded functionality accordingly. 6 / 72

7 Automation level VISONIK The VISONIK process devices available in DESIGO implements control and monitoring functions in existing building automation and control plants. They can be adapted to any control technical requires on a project-by-project basis. Programming is in a free programming language. All VISONIK process devices work per the principle of distributed intelligence. This guarantees operations of building services plant even when part of the system fails. BPS process station BPS process station BPS process stations is suitable for challenging building automation and control system tasks. The process station and controller work in multitasking mode, i.e. multiple tasks are processed in parallel and in real-time. Application programs are created in COLBAS * programming language. * COLBAS, Control Oriented Language for Building Automation Systems BPS process station most important functions Freely programmable measuring, control and monitoring tasks. Process scheduling functions and applications programs. Local data archiving. Connection for local alarm printer. Communication with: Data and communications server DCS. Process and field devices Operating and output devices. Run manual command entries using a POP Card (Personal Operation Process Card), PC or Palm PDA. Display of process value in the BPS LCD display. 7 / 72

8 DESIGO building automation and control with VISONIK Comprehensive functionality uniform operation DESIGO with VISONIK integrates a number technical discipline for a building with a uniform and cross-electrical and mechanical installation system. Uniform operation from a single operator station allows the operator to operate the building at a high degree of comfort and at low operating costs. Systems with special tasks can be integrated above and beyond the areas heating, ventilation, air conditioning, refrigeration and electrical, such as fire and intruder detection system as well as access control and video systems. Expandable over the long term DESIGO with VISONIK connects process stations and individual room controllers from different system generations. This long-term compatibility includes, for example, the process stations from BPS (PRV2) up to NetBPS, compact stations RWI (AEROGYR) as well as the individual room controller product ranges TEC, DESIGO RX and MONOGYR. Flexibility DESIGO with VISONIK offers a multitudes of possibilities for designing the system, topology as: Integrated system. Regionally distributed system. Remote management system. Linked system. Integration system. Remote management DESIGO in remote management integrates different size buildings in regional and cross-regional systems. Dial-up connections (analog, ISDN) or dedicated lines are used. Full monitoring, operating and optimization is possible. Integrate into the network DESIGO INSIGHT and VISONIK management stations with data and communication server DCS allow for flexible integration into networks. This guarantees a high degree of system security and availability. Validation and certification DESIGO with VISONIK was test per EU-GAMP (Good Automated Manufacturing Practice) and is specially well suited for use in the pharmaceutical industry for the FDA (Food and Drug Administration). 8 / 72

9 Decentralized and distributed intelligence The building automation and control system works according to the principle of distributed intelligence. All levels are autonomous and continues to operate independently when communication or a higher system level fails. Important functions are processed similar to the DDC stations or the room automation controllers. DDC stations exchange data peer-to-peer. Emergency operation of the I/O modules ensure secured intervention at the plant under all circumstances. Data and communication server (DCS) The data and communication server (DCS) serves as the link in DESIGO with VISONIK between the automation level and the management level using DESIGO INSIGHT. DESIGO INSIGHT and VISONIK software can be installed on the same server. Task oriented Its client/server architecture of the DCS supports the system environment with numerous, simultaneous services (multitasking operations). And all management tasks are processed in real time. The most important tasks DCS type PLD 10 / Tower Acquiring, processing, storing process data, and preparing for DESIGO INSIGHT. Monitor process data flow and communications connections to DESIGO INSIGHT at the automation level and to the input/output modules. Run superposed system functions, e.g. peak loads or power restoration program. Distributing alarm and fault messages to receivers such as a printer, fax or mobile services. Scalable and powerful DCS type PLD 10 / Rack DCS can be expanded in a flexible manner from small plants with a few hundred data points up to large buildings with multiple tens of thousands of data points. Easy to maintain Integrated programs for self-diagnostics ease early recognition and trouble shooting of technical faults. Maintenance and renovations as well as expansions are possible without interrupting plant operation. New plants are switched on or others taken from the bus for a period, when improved optimization programs are worked in. 9 / 72

10 Communication between system levels System communications is event oriented per the COV (Change Of Value) principle. Process values in the system are only distributed when actual changes (events) occur. This avoids unnecessary load on the bus and achieve a high-level of performance in large systems as well. Process and system data Data points and their parameters serve in building automation and control tasks as information carriers of process and system data. Data points and parameters In the DESIGO system with VISONIK, data points are optimized to certain applications via their parameters. Parameters characterize the multifaceted properties of the data points, as they contain comprehensive integration functions, for example, for limit value supervision, operating hours count and alarm handling or adjustable operating mode for event processing. The point/parameter model from the system allows the user to intervene into complex functions by activating "parameterization". This simplifies operation and improves the overview, creating the flexibility necessary for efficient operation. The settings are made online. The following example illustrate the impact of point-specific parameters act: Limit value supervision Operating hours count Alarm handling Message delays Measured values and meter values are supervised using set or floating limit values with two limit value pairs available. Limit value violations are distributed as fault messages. The parameters of each switch command point can be set for runtime totalizing. For example, for a three-stage switching commend, the times for each switch stage (OFF/Stage 1 3) are totalized. The alarm handling system can incorporate all data points. Important properties such as limit value, alarm priority, alarm text and output device are configured via the parameters. If an alarm occurs, the time-stamp, cause and frequency of the alarm are stored in parameters. The same applies to the user logon acknowledgement. All events are made available for long-term data storage. Message delays prevent unwanted alarms in the case of briefly occurring, transient states. If the fault persists, the alarm is transmitted after expiry of the delay time. With digital input points, the delay time is started, for example, by a change of state (e.g. from "contact open" to "contact closed"). Messages or process reactions are not initiated until the delay time has elapsed, i.e. when the change of state is stable and unambiguous. In the case of digital output points, the evaluation of the feedback signal can be delayed. 10 / 72

11 Virtual data points Virtual data points (i.e. data points without a direct physical connection to I/O modules) are provided for higher-level applications. Their point-specific parameters can be used, for example, for reliable execution of the following tasks: Buffering of calculated values P, PI and PID control functions with setpoint adjustments Room management, with room groups and zones Plant control with start-up monitoring and safety functions such as frost protection System operation All user inputs are entered online, and processed directly by the system. Operator units The user can operate the system with operator units connected directly to the DCS, operator units connected to the automation stations, and from the DESIGO INSIGHT management station. The system allows combined use of operator units of different generations. Multi-user operation In a DESIGO system with VISONIK, up to four DESIGO INSIGHT management stations can be active concurrently. Further local operator units (e.g. terminals) may be used in addition to the above. In a networked system, multi-user operation can be extended by a further four management stations per system. Web operation DESIGO WEB is a genuine Web solution based on Microsoft IIS (Internet Information Server). The programs for operation of the management system are mapped to ASPs (Active Server Pages) in special interfaces optimized for Microsoft Internet Explorer. Access protection Each user has individual access rights (read and write), protected by password. These cover the following categories: Address range, e.g. ranges based on building or type of plant Graduated read/write access to system functions, parameters and password editing options Expiry date for access rights 11 / 72

12 Logging into the system All login and logout operations of each user are logged and saved in the log database. Reporting Individually compiled reports help the user with diagnostics for the entire DESIGO system. Address ranges, time ranges, parameter names and parameter values can be selected freely. The main report types: Status report Fault report Alarm report Maintenance report Room management report Peak load report for switched loads Automatic reports are activated on the basis of time or date, or in response to a specific event, e.g. as a process reaction in the case of a fault in the plant. Data logging Process values which provide important point information can be logged over long periods of time. This data can be used to review the indoor conditions and plant status, to optimize the process and, in the event of a fault, for help with diagnostics. Data security The logged data is stored securely in the DCS and protected from data loss. The DCS provides various applications for the logging of process and system values. 12 / 72

13 Event log The event log records events associated with the system and the process: User login and logout Fault and alarm messages/alarm acknowledgement Status messages from the plant Configuration changes carried out by the user System error messages Maintenance messages Different operator units can be used for the display and reporting of messages. Values log Data series from all kinds of data points and parameters (measured values, positioning values, operating hours, etc.) are recorded in the "values log". The data series are logged at regular intervals (ranging from every minute to every 24 hours) and saved after synchronization. The values are stored in the form of hourly or daily mean, minimum and maximum values. The data series can be evaluated and analyzed in reports and trend graphs, using: DESIGO INSIGHT The supplementary packages ADP (Advanced Data Processing) for analysis of the process, and CC (Consumption Control) for energy management Archiving Logged events and process values are easy to transfer from the DESIGO INSIGHT log database to other data storage media. Reaction programs A building automation and control system must be capable of responding to specific events, such as the tripping of a safety thermostat or the receipt of a time or date flag, by influencing the process in a predefined way. The events which trigger a predefined reaction can occur anywhere in the system. The "reactions" therefore affect the system. Often the result from the cause of multiple reactions, that for their part are the causes of additional reaction triggers. 13 / 72

14 DESIGO I/O modules In current VISONIK systems, the proven DESIGO PTM I/O modules are already installed in the control panel. The new TX-I/O module can be connected in parallel to the BPS (PRV2). DESIGO TX-I/O modules, which provide the interface to the devices at the field level, the sensors and actuators. They communicate with connected DESIGO PX modular automation stations and can be interconnected in application-specific configurations. A space-saving, flexible product range of compact TX-I/O modules is available for signalling, measuring, metering, switching and positioning. The I/O module system is DIN compliant in design and optimized for panel mounting and supports decentralized, remote module installations. The TX-I/O modules have LEDs or optional LCD displays with signal and warning display programs to indicate the state of the plant and can be manually or emergency operated depending on the module type. The integrated isolating-terminals facilitate the hardware test carried out during commissioning. The combination of DESIGO TX-I/O modules with proven PTM modules within a plant is also possible without a problem. For the user, the advantages of the DESIGO TX-I/O modules are as follows: Integrated isolating-terminal feature. Integrated manual controls (optional). Integrated diagnostics functions with LED and optional LCD display. Optimized for HVAC actuators and sensors. DIN compliant construction optimized for panel mounting. Self-connecting bus connection for the easiest possible assembly. Lean, flexible product range for optimized logistics. Clear text module labeling. Tool support for configuration, diagnostics and function test. Third-party integration with DESIGO TX OPEN modules for Modbus, M-bus meters and variable speed drives (Siemens SED2). DESIGO TX-I/O modules with integrated isolating terminals and optional manual operation You can integrate third-party integration, for example, pumps (GRUNDFOS, WILO), M-Bus meters, and variable speed drives in an economic manner via I/O modules. Control operating mode Setpoint adjustment Fault and status codes Delivery head Power Speed You can also use the PTM module together with the BPS (PRV2) or with the PXC -U series automation stations. 14 / 72

15 Overview of TX-I/O modules Type TXM1.8D TXM1.16D TXM1.8U TXM1.8U-ML TXM1.8X TXM1.8X-ML TXM1.6R TXM1.6R-M TXM1.8P Total number of inputs/outputs Functionality Local override LCD panel 3 color I/O status LED Green I/O status LED Digital inputs (DI) Status signal (NO/NC). Signal pulse Meter 10 Hz (with contact bounce suppression) Meter 25 Hz (no contact bounce suppression) 1 8 1) n Analog inputs (AI) LG-Ni1000 Pt1000 / Ohm T1 DC V Ohm ma / ma Pt100 4-Wire n Analog outputs (AO) DC V ma 5 8 2) 5 8 2) Digital outputs (DO) Permanent contact on/off. Permanent contact 3- speed 3-point output On/off pulse Pulse Pulse (3-speed) 1) On TXM1.16D, you can implement the meters on inputs 1 through 8 2) Auf TXM1.8X.. outputs ma are implemented on the I/O points 5 through 8 15 / 72

16 DESIGO with VISONIK: Migration as the bridge to the future The philosophy underpinning migration from VISONIK to DESIGO is based on integrated, phased and cost-effective modifications to the building automation and control system. This approach makes it possible to keep the system technology consistently up to date. This, in turn, extends the life of the system, so that the high cost of replacing the entire system at a later date can be avoided. DESIGO covers all the important system functions of an existing VISONIK system, including operation and monitoring, alarm management, time scheduling and data archiving. The operation and display of the VISONIK automation stations may differ in certain respects. The following DESIGO section refers to the DESIGO PX automation stations. The path to DESIGO DESIGO INSIGHT, the common management station DESIGO INSIGHT is the uniform management station for all existing systems supplied by Siemens Building Technology. The management station also provides the basis for the seamless integration of VISONIK into the DESIGO system. In addition to the latest technology, DESIGO INSIGHT offers customers an extended range of system functions, and the facility to connect to the new DESIGO PX automation stations. The common management station, DESIGO INSIGHT, is the foundation stone for the future. System expansion with DESIGO PX The expansion of existing VISONIK systems will be implemented with DESIGO PX. State-of-the-art technology is assured by the use of open communications standards, BACnet, LonWorks or KNX. Multiple operating modes are available: local, centralized, via Ethernet or the web. The wide range of possibilities offered by integration makes way for the connection of other disciplines. 16 / 72

17 Advantages of DESIGO with VISONIK Interaction between the DESIGO and VISONIK automation levels can be depended upon. Compatibility with the TX-I/O modules as of BPS (PRV2) is assured. System functions Web access with browser, via Ethernet or analog, ISDN or null modem. Higher system limits OPC-integrated solution Management level Common management station for all existing systems supplied by Siemens Building Technology. Modern platform based on Microsoft Windows and today's computer standards User log in using Windows authentification. Simple and intuitive operation with fully graphical user interface (2D and 3D). Integration of other disciplines by use of SCADA technology. Operation via a standard Web browser. Communication with the connected automation level via Ethernet or the telephone line. BACnet communications between the management and automation level. Configuration of complex exception schedules (e.g. "every 2nd and 4th Saturday"). Numerous alarm routing options (e.g. SMS, , pager, fax etc.). The amount of information can be freely adapted based on user needs and abilities. Redundant design provides high availability of DESIGO INSIGHT. Automation level Compact modules. PXM20 for operation of automation stations. The module PXA30/40-W supports web access via Web browser. DESIGO RX room controller applications. Use of DESIGO TX-I/O modules in parallel to existing PTM-I/O modules on the same process station BPS (PRV2). 17 / 72

18 System functions Operators of the DESIGO building automation and control system have a versatile range of equipment at their disposal, offering convenient access to the system and the plant. Operation and monitoring Operator station The DESIGO INSIGHT management station is a powerful and user-friendly interface for monitoring of the overall system. Access and alarm management can be modified to the operator s supervisory chain. For example, alarms can be separated based on the user. DESIGO WEB and DESIGO Terminal Service allows access to the management level using Web technology. The PX-WEB software uses Web technology to map all plant and system information from the automation level to a standard Web browser. Room unit The room unit product range. QAX.. offers functionality matched to meet the exact requirements / needs of the user and the appropriate design. Operation in the control panel The user-friendly, graphics-based PXM10 operator unit allows full local operation of the automation stations. The PXM20 network-compatible graphics-based operator unit presents all plant and system information in an easy-to-understand format with a plain-text commentary. PX-WEB can also be used with a touch panel for operation and monitoring of the automation level. Manual operation The DESIGO TX-I/O modules include facilities for manual/emergency operation of plants and for the display of operating states. The PXC36-S compact automation station incorporates slide switches which can be configured for manual operation, or as freely-assignable outputs. DESIGO operating levels 18 / 72

19 Trend/History Fully integrated trend data processing allows effortless evaluation and analysis of realtime (online) data and (offline) historical data. The trend feature facilitates the monitoring and fine-tuning of the plant. In the DESIGO system this feature is implemented in the form of trend log objects, in compliance with BACnet standard. Trend logging options: Continuous logging. Single run. Logging over a specified period. Sampling options: Polling. COV polling (Change of Value). Event-driven polling. Trend graphs can be displayed both on the PXM20 operator unit and on the management station. The management station also allows displays in color and in 2D or 3D. Trend Viewer on the DESIGO INSIGHT management station and on the PXM20 operator unit Online trend features: Real-time display of process data. Based on changes in the value of a data point (COVs) or on periodic sampling by Trend Viewer (times can be configured). Offline trend features: Offline data display no permanent connection required. Longer periods of time (days,months). Data acquisition in the automation system. The data is uploaded to the management level at regular intervals or as needed. Alarm management One of the most important functions of a building automation and control system are the automatic alarms for faults in the building services plants. The management of alarms (generation, display and handling) must be simple, efficient and consistent at all levels of the system. DESIGO uses the BACnet alarm functions, and supports the following three types of alarms with up to 256 alarm priority levels: Basic alarm (for alarms not requiring user interaction). Simple alarms (for alarms requiring acknowledgment). Extended Alarms (alarms requiring acknowledgement and reset). Alarm messages When an alarm occurs, it is automatically detected, registered and transferred to operator units such as PXM20 or PX-WEB, or to the DESIGO INSIGHT management station. Informative alarm messages are also transmitted to remote devices such as mobile phones, fax machines, printers or PCs and Web browsers, via SMS and / 72

20 DESIGO INSIGHT further separates alarms in a customized manner so that each user receives only those alarms corresponding to the area of responsibility. Alarm lists provide a view of all pending and time-stamped alarms at a glance, and permit straightforward processing. Operators are alerted to incoming and pending alarms with pop-up windows and audible and visual signals. Alarm routing Alarms are transferred on the basis of time, priority and/or plant type, using a truly powerful alarm routing system at the management station. This ensures the uninterrupted routing of alarms, irrespective of whether or not there is an operator sitting at the management station. Users are supported in their work by various overview options which help ensure a fast and correct response even in critical alarm situations. Alarm messages on the PXM20 operator unit and on the DESIGO INSIGHT management station Scheduler / Calendar One of the basic functions of a building automation and control system is time control of procedures and processes and ensuring energy efficient operation. Scheduler programs ensure that the heating and lighting are switched off automatically at the end of the workday, that the temperature in the building is reduced at night, and that the plant is not kept running for longer than necessary. They can also be used to switch off the air conditioning in certain rooms during holidays. Saving energy / increasing the service life of plant The ideal scheduler programs help save energy and increase the service life of the plant. This is another area where DESIGO excels with its straightforward and exceptionally user-friendly operation. Time-switching operations in the DESIGO building automation and control system are implemented per the BACnet standard, using the BACnet objects "Schedule" and "Calendar". The function allows for flexible operation of the building. From simple 7-day schedules to recurring exceptions, these powerful functions make programming easy. By use of standard BACnet functions, the BACnet scheduler programs can be operated system-wide from the user-friendly operator units PXM20 and PX-WEB and from the DESIGO INSIGHT management station. 20 / 72

21 Scheduler program on the DESIGO INSIGHT management station and on the PXM20 operator unit For safety reasons, schedules and calendars are stored in the automation station, so that in the event of a network or PC failure, the automation level can continue to operate autonomously. Access rights Freely-definable access rights Access rights can be used to filter information from the plant and system based on the individual requirements of a user. The resident engineer or the service engineers, for example, only have access to this important information. A distinction can also be made between read access and write access. Certain users may be able to read a value but not modify it, while other users may have extended access rights, enabling them both to read and to modify values (edit). Only authorized personnel are granted access to the system via the operator units. When a user enters a user name and password, the system verifies the associated access rights and enables access to the relevant plant. Read and write access rights can be defined in detail, right down to individual information points. The following access classes are supported in the DESIGO system: Internal Extended service Basic service Administration Extended operation Standard operation Basic operation Information flow under control Moreover, the Scopes function allows you to freely adapt the amount of information on the management station to meet the needs and competencies of individual users with regard to building area. Customizing the environment to each user ensures clear areas of responsibility, so simplifying cooperation between the various user groups. 21 / 72

22 Communication - Networks Communication standards specially developed for building services technology BACnet, LonWorks and KNX S mode (EIB) DESIGO Terminal Server DESIGO WEB DESIGO Terminal Server DESIGO WEB BACnet certification Connection of legacy systems Compliant devices can be interconnected at low cost using the BACnet (Building Automation and Control network) open communications protocol. The worldwide BACnet standard was developed specifically for the needs of building services, under the auspices of ASHRAE (the American Society of Heating, Refrigerating and Air- Conditioning Engineers). BACnet networks provide all subscribers with access to all the data and functions of the connected devices. For the exchange of information among its own system components, DESIGO uses three standard protocols, recognized worldwide: BACnet, LonWorks and Konnex (KNX) S-mode (EIB). The BACnet communication protocol is used for the exchange of information between one DESIGO PX automation station and another, and between DESIGO PX and PXM20 BACnet operator units and DESIGO INSIGHT. DESIGO/IP uses LonTalk or PTP (point-to-point, modem or null-modem) as the transport medium. At the room automation, DESIGO RX communicates per LonWorks standard or KNX S-mode (EIB). DESIGO Terminal Server and DESIGO WEB make optimum use of the advantages of modern IT technology for the benefit of building services. Properly selected and used, they have a significant influence on the ability to fine-tune the running of the building and on the comfort and satisfaction of building users. This reduces maintenance and upkeep costs. DESIGO Terminal Server provides all the functions of the management system in the form of terminal services over the network. These services can be accessed simultaneously by different users in independent sessions. In addition to operation and monitoring programs for the day-to-day operation of the plant, engineering tools are also provided, allowing modification and expansion of the system while it is running. This makes the DESIGO Terminal Server the optimum solution for professional building operators who need unrestricted access to building data via their intranet or extranet, from any location. DESIGO WEB is a genuine Web solution based on Microsoft IIS (Internet Information Server). The programs for operation of the management system are mapped to ASPs (Active Server Pages) in special interfaces optimized for Microsoft Internet Explorer. All DESIGO PX BACnet servers were submitted to the BACnet Interest Group Europe (BIG-EU) for compliance testing on the BACnet standard DIN EN ISO and successfully certified. A well-known testing institution conduced the comprehensive testing. DESIGO PX devices comply with the B-BC profile (BACnet Building Controller) and DESIGO INSIGHT largely comply with the B-OWS profile (BACnet Operator Workstation). DESIGO is compatible with the legacy automation systems UNIGYR, VISONIK, INTEGRAL and SIMATIC S7 and allows their seamless integration. Changes in use, system expansion and retrofit projects can all be handled in gradual stages. 22 / 72

23 The management level - DESIGO INSIGHT Applications in DESIGO INSIGHT The clearly structured, modular, object-oriented software of the DESIGO INSIGHT management station is based on the latest standard Windows technology. The functional scope and ease of use of the software reduces operating costs and familiarization time, while at the same time maintaining operational reliability. The DESIGO INSIGHT applications are introduced below: Plant Viewer: Realistic plant graphics allowing fast, targeted monitoring and operation of the system. Time Scheduler: Central programming of all timecontrolled building services functions. Alarm Viewer: Detailed overview of alarms to quickly localize and eliminate errors. Alarm Router: Flexible routing of alarms to printers, fax machines, mobile phones and . Trend Viewer: Comfortable analysis of trend data to optimize operations and increase energy efficiency. Report Viewer: Snapshot queries to meet customers needs and their display in reports. Reports provide information on plant operation analysis as well as evaluation and documentation purposes. Object Viewer: An efficient tool for navigation through the hierarchical tree-structure to all the data points in the system. These points can then be read or manipulated, depending on the access rights of the user concerned. Log Viewer: Alarms, errors and user activities are logged in chronological order, and can be displayed for further evaluation, as needed. Database Audit Viewer: Log unauthorized changes in databases (audit trail) guaranteeing the highest possible data integrity. Reaction Processor: System-wide monitoring of plants and processes based on certain criteria (events). The Reaction Process triggers predefined (re) actions when one (or a combination) of the criteria are met. Allows for centralized time control of plants without scheduler programs / calendar functions. System Configurator: Used to configure the general setup of the DESIGO INSIGHT management station and associated applications. Graphics Builder: Efficient creation of customized plant graphics. Open Drivers such as BACnet, OPC, KNX S-Mode (EIB), LONWORKS: For direct integration of various interfaces into the management station. Online operator tools for existing systems. Plant Viewer 23 / 72

24 Taskbar A taskbar appears after starting DESIGO INSIGHT. It provides fast and direct access to all the user applications, and displays important status information. In the case of several remote plants, it is possible to switch from one plant to another via the taskbar, subject to the appropriate access rights. This ensures clear demarcation lines between the various areas of responsibility. The user's entry into the system is simplified by user-specific start-sequences with preselected programs and plant. The DESIGO INSIGHT taskbar The icons on the taskbar provide access to the main user applications: Connect and disconnect sites Login and logout, restart, lock or shutdown Plant Viewer the graphical interface to the plant Alarm Viewer displays the state of abnormal alarm points Trend Viewer displays graphs containing live data Log Viewer displays all event messages including alarms Database Audit Viewer logs unauthorized changes to databases Object Viewer shows all data points in the system, in list form Scheduler allows the user to modify plant switch times Report Viewer displays reports of momentary values recorded and compiled by the user Reaction Processor allows automatic triggering of cross-system process reactions Alarm Router routes alarms to printers, fax machines, mobile phones and systems Number of current system alarms On-line help Number of connected sites Pending alarms in order of priority DESIGO INSIGHT archive server 24 / 72

25 Background functions in DESIGO INSIGHT: Life Check feature for checking the connection to automation systems. User log on using Windows authentification Windows OS administers password guidelines, such as password expiration and security. Automatic log on to DESIGO INSIGHT when user accounts match. Alarm upload after system start. Check on unauthorized login attempts. The Scopes function provides user customized information views. You can adapt the amount of information available to individual users based on need and competencies. Unwanted information (objects) are hidden for the given applications. For example, only messages are displayed in Alarm Viewer for which the user is responsible. Furthermore, multiple user can work on the same system without access to certain information intended for other users (especially user for remote control units). Security functions in DESIGO INSIGHT: Management station locked by timeout after period without user activity. Time synchronization between management station and automation stations. Verification of hard disk memory capacity and availability of database. High Availability solution through redundant design of the DESIGO INSIGHT server. The primary switches automatically to the standby system in the event of a hardware failure. The management is once again available without loss of data after a minimum interruption. Plant Viewer Process display Plant Viewer displays the areas of a building and the associated plants in graphical form. The user works interactively with these views to monitor and control the data points throughout the building. Values can be modified and alarms can be acknowledged by clicking the corresponding concerned. The Plant Viewer is based on SCADA technology. Numerous windows of different sizes can be displayed simultaneously (overlapping or tiled). Even large graphics, such as floor plans etc. can be accommodated, and the freely definable page size makes them easy to view. Process display Real-time display Measured values, setpoints, operating modes and alarms are displayed on the screen in real-time, and updated continuously. The display form is determined during engineering. Changes are indicated either by the object symbol, e.g. through animation or a change in shape or color, or by the movement of, or a change in the color, shape, or text of the values affected. 25 / 72

26 Other features of Plant Viewer: Genuine multitasking with fully dynamic functioning of all active pages. Object-oriented plant operation and monitoring. Freely definable page sizes for versatile handling of several pages in the same screen. Page selection via dialog box, context menu or hyperlinks. Integrated standard page selection features based on the page naming strategy. Standard functions such as Last/Next/Top etc. Object-oriented navigation between applications. Definition of, and quick access to "Favorites". ToolTips for all dynamic objects, with the option of User, Technical or System Designation. Context-specific information such as text, photos or maintenance information can be added to each dynamic symbol. Black-and-white or color graphics printing Import of Windows 32-bit supported graphics file formats, such as AutoCAD and PXC. User privileges for access to different levels Tools for efficient and error-free engineering. Time Scheduler The Time Scheduler application in DESIGO INSIGHT can be used for central programming of all time-controlled functions in the building services plant, including the individual room control system. Graphics-based operation The facilities for graphics-based operation of the weekly schedules and exception programs, the user can modify and/or optimize scheduler programs at any time and without difficulty. Primary functions: Graphics-based overview and manipulation of all scheduler programs in the system. Easy graphics-based programming of switch times. Programs invoked directly from the plant graphics. Logging of user activities. Direct entry of various operating modes (e.g. Comfort, Standby, Energy Hold-Off). Storage and processing are independent of the management station. Reports printed in different display formats. Calendars operated via the same easy-to-use interface. System Browser view, and overview of daily profiles in the Time Scheduler application 26 / 72

27 Alarm Viewer The Alarm Viewer application displays alarms by type, and provides the user with helpful information as to the type of action required by the system. With its extensive filter and search functions, Alarm Viewer facilitates fast and well-targeted access to the required information. In larger systems with more than one management station, all management stations access the same alarm database. An alarm for any given management station is entered in this database and automatically displayed on all other management stations. Functions in Alarm Viewer: View, acknowledge and reset single or multiple alarms. Display the associated alarm property sheet with detailed data point information. Read associated alarm help text with operating instructions or additional information in text form. Object-based navigation to other applications, such as Plant Viewer and Log Viewer. Alarm Viewer Pop-up windows The pop-up window is an important means of attracting the attention of the user in the event of an alarm. Incoming alarms are displayed in a pop-up window that opens on the Windows desktop and appears in the foreground of all other applications-including third-party applications. If several alarms occur, they are displayed one after the other. An audio file (.wav) can be added to each alarm window defined to further alert the user to the alarm with an audible signal. The appearance of the pop-up window can be varied for each alarm category. From this window, the user can invoke helpful instructions about the required response to the alarm, or jump directly to other applications such as Plant Viewer or Alarm Viewer. Alarm pop-up 27 / 72

28 Alarm Router The Alarm Router application provides highly effective building management. Important messages or events in the building automation and control system are transferred to specific receivers without the need for any user action at the management station. Alarm Router is a background application which starts when DESIGO INSIGHT is started, whether or not a user or site is connected. Alarms and important system events can be transferred via the following media: Printers Faxes Pagers Mobile phones systems Criteria for alarm routing Alarms can be grouped according to various criteria. A routing table defines the conditions under which these alarm groups are routed to the assigned receivers. The alarm messages are routed to alternative receivers in the event of connection problems. The criteria include the following, for example: Time schedules and exceptions (e.g. at night, switch to the printer in the security guard's office). Responsibility for the site (e.g. send a fax to the company responsible for maintaining the system). Urgency of the alarm (e.g. call resident engineer via pager only in the event of high priority alarms). Alarm Router 28 / 72

29 Trend Viewer The Trend Viewer application is used to review current process data in real time (online) and past process data (offline) over a period of time. Trend Viewer is an easyto-handle tool used to optimize plant operation and reduce costs. Trend Viewer tasks: Process values and measured values logged over a period of time. Minimum and maximum values retained in graphs irrespective of time range. Monitoring of current plant conditions. Plant optimization and fine-tuning. Response times appropriate for the support of large trend databases. Up to ten process values can be displayed in 2D and 3D graphs in a single trend view. Both online and offline data can be displayed simultaneously in separate windows, enabling the user to compare past and current situations. Drag Drop Drag & drop in Trend Viewer Trend logging Essentially, trend data can be displayed in three different modes: Online trend logging: Displays real-time process data which is updated whenever a change of value (COV) occurs, or as the result of a time-based scan. Offline trend logging: Displays past process data which has been uploaded to a database at the management level. Archive data: Displays older data which has been moved from the trend database into archive files. The trend views can be saved and retrieved at a later date. Online trend data is continuously logged and stored in the trend database. 29 / 72

30 Object Viewer Object Viewer helps users of the building automation and control system to navigate efficiently through the entire structure; data objects can be easily selected. Object Viewer supports three different hierarchical views: Technical View System View The technical view is the plant-based standard view The system view is a standard associated with the technical designation. hierarchical view, representing User View the topology of the BACnet The user view is based on customer-specific user network, whereby a site contains designations (user addresses). devices and each device contains The address structure and contents are defined as objects. part of the DESIGO PX engineering process. Technical View User View System View Various System Browser views System Browser The left pane of Object Viewer contains the System Browser, which displays a hierarchically structured view of the system (in a tree-structure). The right pane of Object Viewer displays the contents of the currently selected object. Detailed alarm display in Object Viewer 30 / 72

31 Functions in Object Viewer: Fast navigation through the building automation and control system. Quickly locate objects and alarms. Detailed information on the properties of each object. Display of real-time process data. Modification of setpoints and parameters, and manual override of outputs. Jump functions Back / Forward. Modification and definition of object-related text. Function with wildcarding for quick and direct access to certain objects. Object search in other views by changing view in context-menu. Supports read/write access levels. Object Editor: A user-friendly user interface for editing all imported objects. Log Viewer Log Viewer provides users with access to all events that have occurred within the system. Events and user activities are archived in chronological order in the log database and can be viewed whenever required. Event Handler The data logging system is a background service performed by the Event Handler in DESIGO INSIGHT, which continuously logs reported events as follows: Events in Log Viewer: Alarm events from the process level, such as plant alarms and high priority warnings. The alarm is logged when it occurs, and thereafter upon acknowledgment, reset and return to normal. System events from DESIGO INSIGHT management stations and PX automation stations. Examples include communication failures, selection procedures, start-up, shutdown, hard-disk monitoring, battery checks etc. User events for reporting user activities on the management station. These include authorized and unauthorized user log-in procedures and the modification of values, parameters and setpoints etc. Status events from the process level, such as plant ON/OFF etc. The user interface of Log Viewer has the same look and feel as the Alarm Viewer and is based on the same versatile sort and filter functions. Log Viewer 31 / 72

32 Functions in Log Viewer: Query-configurations can be stored and reused. Display of current filter and sorting state. The Log Viewer display is divided into tabs Alarm, System, User and Status events enabling the user to pre-select events of a particular category. Columns can be flexibly rearranged, re-sized or hidden as required. The events logged for a specific object, such as events associated with a given site, automation station or data point, can be located quickly in the left pane (System Browser). Logging of changes in the project configuration. Parameter modification feature includes original parameter value. Logged data is saved and exported on an SQL server. Log and trend data archiving The archiving function serves to remove data from the runtime databases. This is necessary to first create space for new data in cases where storage capacity is normally limited, and second, to store the data in a suitable form for retrieval at a later date. The removed data is archived in a safe location for later retrieval and display if required. Data is archived in DESIGO INSIGHT automatically on the basis of time or quantity of data accumulated, or manually by the user. Report Viewer The Report Viewer allows the user to select existing report templates to manually start momentary value data acquisition. A report is then generated with the values for the plant data defined in the template at the time the data is recorded (snapshot function). Pre-selected reports can even be automatically executed together with the Reaction Processor. The reports displayed on-screen can be printed or stored as PDFs for documentation purposes. An export to CSV file format allows for additional evaluation of recorded data values in other programs (Microsoft Excel, Microsoft Access) Filters Filter criteria for searches may be entered to display only the data the user desires in the reports (address masks wildcards, by plant, data point type, time, date, etc.). Standard report templates The following standard report templates available with DESIGO INSIGHT: Reports to record alarm and fault states (active, unconfirmed, etc.). Reports to record logbook entries (alarm, system and user events). Reports to record plant states (manual override, maintenance requirement, room measured values, actual values, setpoint settings, etc.). Customized report templates The Report Builder tool creates customized templates for customers requiring their own template reports. The report function with standard report templates is included as part of the basic license; the Report Builder, however, requires a separate license. 32 / 72

33 Create and query reports via Web With the appropriate access rights, a DESIGO WEB client PC user may select existing report templates on the DESIGO INSIGHT computer via the Web Report Viewer and start momentary value recording. The generated report is displayed in DESIGO WEB and can be saved or printed as a PDF file and downloaded from the Web Server to the client computer. Reaction Processor The Reaction Processor is an event program capable of system-wide monitoring of plants and processes for the occurrence of certain criteria (events) such as time, date, changes of values or exceeding limit values. The Reaction Process triggers preconfigured (re) actions when one (or a combination) of the criteria are met. The user can define the entries in the Reaction Processor. Global time scheduler with calendar function DESIGO INSIGHT has a global time scheduler with calendar functions on the system management level to execute reactions at predefined times of the day (time schedule) or on certain days (calendar / date). You can even control plants and devices on the automation level accordingly without time and calendar functions! Primary application for the Reaction Processor Reaction Processor automates a user's routine work. The Reaction Processor includes a global scheduler / calendar program at the management level for plants integrated at the automation level without a timeswitch. Automated control and switching of plants based on events occurring and monitored during operation. Automated start up and routing of reports. Operation and monitoring with Web technology DESIGO WEB and DESIGO Terminal Server make optimum use of the advantages of modern IT technology for the benefit of building services. Properly selected and used, they have a significant influence on the ability to fine-tune the running of the building and on the comfort and satisfaction of building users. They distribute building information to the person who needs it, and in the exact location where it is needed. In addition to flexibility of operation, both solutions contribute substantially to a reduction in the day-to-day costs of modifications, expansion, maintenance and data backup. Both solutions are based on software standards and are therefore compatible with today's IT security strategies (firewalls, Virtual Private Networks (VPN) etc.). DESIGO Terminal Server DESIGO Terminal Server provides all the functions of the management system in the form of terminal services over the network. These services can be accessed simultaneously by different users in independent sessions. In addition to the operation 33 / 72

34 and monitoring programs for day-to-day operation of the plant, engineering tools are also provided, allowing modification and expansion of the system while it is running. This makes the DESIGO Terminal Server the optimum solution for professional property managers who need unrestricted access to building data via their intranet or extranet, from any location. All the user requires is a simple, standard networkcompatible terminal device such as a PC, Net PC or Web pad with a Microsoft operating system, without other installed software components (Thin Client). Safety is a top priority: Remote access from client devices is via Microsoft Remote Desktop Web Connection with the highly encrypted Remote Desktop Protocol (RDP) 5.0 which uses RSA Security's RC4 cipher with the option of 40, 56 or 128-bit encryption. DESIGO Terminal Server is based on the Windows Server operating system with the Terminal Server component, and runs on standard server hardware. The hardware and software specification depends on how intensively it is used, with the number of users requiring simultaneous access being a decisive factor. DESIGO WEB DESIGO WEB is a genuine Web solution based on Microsoft IIS (Internet Information Server). The programs for operation of the management system are mapped to ASPs (Active Server Pages) in special interfaces optimized for Microsoft Internet Explorer. Functions in DESIGO WEB: Operation of graphics (Plant Viewer). Operation of data points (Object Viewer). Alarms and log (Alarm Viewer, Log Viewer). Trend data (Trend Viewer). Time schedules (Scheduler). Report Viewer. This makes DESIGO WEB the optimum solution for those responsible for technical services (such as the house engineer, building operator or security staff) who track the day-to-day operation of the building and need easy access to all the key functions. In addition, it makes new options available, enabling selected building data and user access to be allocated relevantly to tenants and users of the building (e.g. room operation, time schedules and display of room conditions). WEB Plant Viewer 34 / 72

35 DESIGO High Availability Solution The DESIGO High Availability solution (HA) guarantees higher reliability, availability and data security for DESIGO INSIGHT and InfoCenter, in particular for plants with increased security requirements such as Pharma production facilities, high-tech industry, airports, data centers, etc. The DESIGO HA solution is based on standard IT components and consists of 2 or more physical servers together with ESX server virtualization software by VMware. The High Availability solution includes the following functionality: Continuously monitors all physical servers in a pool and restarts the DESIGO INSIGHT server on the backup server without human intervention in the event of a hardware fault. Monitors the operating system, automatically restarts the service when a malfunction occurs. Monitors the DESIGO INSIGHT service; the service restarts automatically when an error occurs. Recognizes server hardware faults thanks to mutual heartbeat functionality. Immediate restart of virtual machines without human intervention to an other physical server within the server pool. Informs specialist in the event of a fault. VMware Infrastructure Manager (VIM) for server administration. DESIGO High Availability solution 35 / 72

36 The DESIGO PX automation level The most striking features of DESIGO PX are the consistent openness of the system and the scalability of the system with its freely programmable automation stations and operator units. DESIGO PX reliably meets all expectations associated with the control and monitoring of building services. With its modular system design, DESIGO PX can be ideally adapted to specific requirements and needs, making cost-effective DDC technology a possibility even in smaller HVAC systems. Whether for new buildings or modernization projects, investment costs are limited to the system components that are actually needed. This innovative system strategy allows phased expansion of DESIGO PX into a building automation and control system as and when required. A range of graded operator units Room users and building operators benefit from a comprehensive range of operator units which can be used for targeted modification of room conditions or of the whole plant. Operator units The touch panel ensures convenient operation and display of complex building services plant. DESIGO touch panel operation Maximum flexibility, and optimum assistance for users of the technology. Easy to add new operator controls and functions. Versatile guidance of users in the event of alarms. The right operator unit in the right place: Monitor and operate via PX-WEB: In the event of faults in the plant, DESIGO PX transmits SMS messages and allows remote diagnostics via Web client. For the house engineer: With optimized operator units, it is easy to check the functioning of the building services plant or to take account of changes in occupancy by modifying the comprehensive time schedules. For building users: Room units optimized for building occupants can be used for simple and direct local operation of the plant. So, for example, the room temperature in a meeting room can be adapted to individual requirements, simply and without fuss. 36 / 72

37 Operation at the automation level PXM20 network operator units The PXM20 and PXM20-E network-compatible operator units allows full operation of all DESIGO PX automation stations connected to a BACnet network. As a BACnet client, the PXM20/20-E automatically reads the data from the DESIGO PX automation stations. It is therefore always up to date and can be replaced while the system is in operation. The operator unit has a high-resolution illuminated display for graphics and text, keys for operation, and a common alarm indicator with an audible signal. The operator unit can be mounted remotely for compact and modular automation stations in the control panel door. The clearly arranged function buttons and fast access buttons ensure correct operation, even by inexperienced users. PXM20 operator unit Time scheduler Alarm overview Online trend Graphics-based display of the heating curve PXM20 / PXM20-E operator functions Alarm monitoring with acknowledgement and visual and audible alarm indication. Data point display and operation of all measured values, setpoints, plant states, operating states and parameters. Graphics-based display and operation of time schedules, exception calendar, online-trend and heating curve. User-friendly guidance through the plant functions. Favorites, configurable overview of main values in the plant. Multilevel access protection. Type summary PXM20 PXM20-E Operator unit for the automation level. Communication via LonTalk. Operator unit for the automation level. Communication via IP. 37 / 72

38 PXM10 plant operator terminal The PXM10 operator terminal allows full local operation of an automation station. The unit incorporates user-friendly "single-button" operation and a high-quality display panel. PXM10 can be mounted remotely for compact and modular automation stations in the control panel door. PXM10 operator unit Display of setpoints and actual values Alarm display Time scheduler PXM10 operator functions Display of measured values, setpoints, plant states and operating modes. Setpoint adjustment where required. Visual alarm display. Alarm display with scope for acknowledgement. Graphics-based display of time schedule. QAX room units Up to five, bus-capable QAX room units can be connected to the automation station PPS bus allowing the room user to modify comfort values to meet individual needs. QAX30.1 QAX31.1 QAX32.1 QAX33.1 QAX34.1 QAX84.1/PPS2 2) Function overview QAX30.1 QAX90.11) QAX31.1 QAX32.1 QAX33.1 QAX34.1 QAX91.11 ) QAX34.33) Room temperature sensor Setpoint correction Operating mode switch Fan speed switch LCD display for room temperature, setpoint adjustment and operating mode 1) wireless room units 2) Flush mounted room 3) One device per PXC QAX84.1/ PPS22) Additional information available at: Room unit: Key to individual comfort 38 / 72

39 PX-WEB Web operation With its integrated Internet technology, the embedded Web server allows full plant option of the automation station using standard Web browsers. The Web server is integrated into the modular automation station PXC100/200-E.D using the option module PXA40-W.. as well as PXC..-U using the module PXA30-W PXC100/200.E-D with plugged-in option module PXA40-W.. Operate and monitor via Web client (e.g. touch panel) Main functions of PX-WEB: Operation via Web browser or mobile clients (mobile phone, PocketPC or PDA). Simple plug-and-play functions; no engineering needed. User-friendly guidance through the plant functions. Full access to all measured values, setpoints, plant and operating states, and parameters. Comprehensive data point operation and setpoint entry using clear text. Alarm management via SMS (to specified telephone number) or by . Operation of time schedules, exception calendar and heating curve graphs. Reading of trend data, with the facility to export data to Microsoft Excel for evaluation purposes. Collation of main values via Favorites. Support of multiple level access protection. Additional graphics-based display of plant easy to create and modify. Modem and Ethernet version available. Plant operation Alarm overview PX-WEB type summary PXC100/200-E.D + PX40-W1 or PXC -U + PX30-W1 PXC100/200-E.D + PX40-W0 / W2 or PXC -U + PXA30-W0 / -W2 Access with Web server via IP, alarms via SMS and , generic Web functions/operation on all connected DESIGO PX automation stations of a BACnet network. Access with Web server via IP, alarms via SMS and , graphical Web functions/operation on all connected automation stations (for PXA..-W0) or on all DESIGO PX automation stations of a BACnet network (for PXA..-W2). 39 / 72

40 Freely-programmable automation stations DESIGO PX offers maximum flexibility with freely-programmable automation stations to optimally control and monitor building services plants. Comprehensive system functions such as alarms, time scheduling and trend data storage cover all the requirements associated with the operation of a building. The distributed automation stations, available in two categories, operate autonomously. BACnet communications for maximum openness DESIGO PX is based on industry standards designed not only for the present but also for future communications technologies. BACnet/LonTalk or IP are not mere buzzwords to us. On the contrary, they emphasize the openness of our systems and our use of the latest communications technology for maximum overall efficiency. Our consistent and coordinated use of standard technologies also ensures straightforward and costeffective integration of third-party systems and components. Freely-programmable automation stations 40 / 72

41 Automation stations - Compact series The mounting technique and the fixed configuration of integrated I/Os in the compact series automation stations make them ideal for control of small and distributed plant. The I/Os in these automation stations can be adapted to various types of signal. The automation stations are installed in the control panel. The operator units are connected to BACnet, PPS bus or HMI connection. Automation station PXC22-E.D Plant size I/O: UI DI AO DO BACnet/LonTalk PXC12.D PXC22.D PXC236.D PXC36-S PXC52 BACnet/LonTalk modem connection PXC12-T.D PXC22-T.D PXC36-T.D PXC10-TL BACnet/IP PXC12-E.D PXC22-E.D PXC36-E.D Input and output options UI DI AO DO Universal inputs, which can be connected to passive (LG-Ni 1000) and active (DC 0 10 V) sensor elements, or to binary volt-free contacts, for signaling functions. For PXC D, a meter at 20 Hz available as an option. Binary inputs for signaling functions. For PXC10TL, PXC36-S and PXC52, meter functions also available as an option (max. 4 meters per PXC at 20 Hz). Analog outputs for the connection of V actuators or for binary control. Via the program structure, analog outputs can also be programmed as binary switch functions and connected to 24 V/20 ma loads. AC 230 V / 2A relay outputs for binary control. Up to 5 QAX3 room units can be connected to all compact series automation stations. The PXC36-S automation station also incorporates a manual switch and further LED indicators. The manual controls, with switch positions "Auto/Stop/Manual" or "Auto/0/1/2", can be used for direct switch control of actuators or freely configured in software for other purposes. Further, the PXC10-TL automation station is optimized for wall mounting and has a built-in 230 V supply, and a freely-programmable LED button. The PXC -T.D automation stations for direct modem connection allow for remote management and alarming using DESIGO INSIGHT. 41 / 72

42 Automation stations - modular series PXC..D The modular series PXC..D automation stations with its free I/O configuration and DIN compliant construction are optimized for panel assembly. It primarily controls and monitors larger items of plant. The flexible TX-I/O modular product range for signaling, measuring, metering, switching and positioning can be seamlessly connect to the automation station. The I/O modules with local manual controls on the module housing provide the plant operator with simple manual operation of the plant directly in the control panel. This local manual control is automatically transmitted as a remote/local signal to the automation station and associated operator units. In an emergency, they operate independently of the automation station, providing stand-alone emergency operation. PXC100/200..D modular automation station with connected TX-IO modules Automation station overview Connection of TX I/O modules via island bus up to 200 data points More than 200 data points BACnet/LonTalk PXC100.D PXC200.D BACnet/IP PXC100-E.D PXC200-E.D The LonWorks system controller for this series allows you to connect LonWorks devices such as DESIGO RXC room controllers and third-party devices. Overview of system controllers LonWorks PXC00.D PXC00-E.D System controller with BACnet/LonTalk communication. System controller with BACnet/IP communication. The PXC..D modular series is supplemented with option and expansion modules. Plug-in option module PXA40- for automation stations Side-connection expansion module PXX-L.. for system controller The option module for automation stations assume additional functions such as PX- WEB or remote management together with DESIGO INSIGHT. 42 / 72

43 Option modules for automation stations PXC100.D / PXC200.D PXA40-T Option module for remote management. Option module overview for automation stations PXC100-E.D / PXC200-E.D PXA40-T PXA40-W0 PXA40-W1 PXA40-W2 Option module for remote management. PX-WEB option module for IP, remote management, SMS, 1) and alarming with graphics-based Web functions 1) for the automation station fitted with the module. PX-WEB option module for IP, remote management, SMS 1) and alarming with graphics-based Web functions 1) for all automation stations connected to a BACnet network. PX-WEB option module for IP, remote management, SMS 1) and alarming with graphics-based Web functions 1) for all automation stations connected to a BACnet network. 1) One communication type only: Either DESIGO INSIGHT PTP or WEB PPP The expansion module allows connection of LonWorks devices such as DESIGO RXC room controllers and third-party devices to the system controller LonWorks. Expansion module overview for system controller LonWorks PXC00.D/PXC00-E.D PXX-L11 Expansion module for up to 60 LONWORKS devices / RXC room controllers. PXX-L12 Expansion module for up to 120 LONWORKS devices / RXC room controllers. The system controller supplements room automation with the functions cluster, scheduler program, trend function, alarm management and mapping data points on both BACnet/IP and BACnet/LonTalk. Automation stations PXC..-U modular series The automation stations for the PXC..-U modular series with its free I/O configuration is suitable for expanding existing plants and as PX OPEN system controller for connecting room automation (RXB, RXL) as well as integrating third-party devices. A range of extension modules supplies various additional functions such as PX-WEB or remote management. PXC...-U modular automation stations Extension module PXA30- Automation station overview PXC64-U Modular automation station to connect TX-I/O modules and/or PTM I/O via P-bus with up to 200 data points. PXC128-U For more than 200 data points. 43 / 72

44 Automation station interfaces PPS2 BACnet/LonTalk BACnet/IP P bus Tool/HMI For the connection of up to 5 QAX3 room units to PXC64/128-U. For BACnet communications between automation stations via LonTalk. For BACnet communication via IP between automation stations via extension module PXA30-N/W Connection for I/O modules to PXC64/128-U. Operator unit or DESIGO XWORKS plus connection. PX OPEN system controller overview PXC00-U PXA30-K11 PXA30-RS PXA30-RS1 PXA30-RS2 System Controller Extension modules Integrate DESIGO RXB or RXL room Controllers as well as KNX S-mode third-party devices Integrate M-bus, Modbus, SCL with 100 DPs with 400 DPs with 1000 DPs (M-bus, Modus 2000.) Overview of extension modules for automation stations and system controllers PXA30-T PXA30-N Extension module for remote management. Extension module for BACnet/IP. PXA30-NT Extension module for BACnet/IP and remote management. PXA30-W0 PX-WEB extension module 2) for IP, remote management, SMS, 1) and alarming with graphics-based Web functions 1) for the automation station fitted with the module. PXA30-W1 PX-WEB extension module 2) for IP, remote management, SMS 1) and alarming with graphics-based Web functions 1) for all automation stations connected to a BACnet network. PXA30-W2 PX-WEB extension module 2) for IP, remote management, SMS 1) and alarming with graphics-based Web functions 1) for all automation stations connected to a BACnet network. 1) One communication type only: Either DESIGO INSIGHT PTP or WEB PPP 2) One type of BACnet communications: Either via IP or LonTalk 44 / 72

45 Room automation - DESIGO RX Convenient room automation with DESIGO RX DESIGO RX is a modern, flexible range of room controllers and room units suitable for both stand-alone operation and for communication over a network. Our room controllers control and monitor thermal comfort conditions in rooms and self-contained zones while ensuring maximum energy efficiency. They have indicated outstanding values during the eu.bac certification of our RXC, RXB and RXL devices. The DESIGO RX range comprises compact and modular controllers, easy-to-operate room units and controllers in room-style housings. Easy control of HVAC, lighting and blinds The modular design of DESIGO RXC combines lighting and blinds with the HVAC control system. With a single room unit, users can control all the room functions to individual requirements. The right solution for every network The DESIGO RXB and DESIGO RXC families of controllers represent a lasting investment in the future. The DESIGO RXC room controller communicates with the standardized LonWorks protocol and the DESIGO RXB room controller with KNX S- mode (EIB). The use of these communication standards allows the DESIGO RX to be combined with other third-party devices. This ensures that room automation can be easily expanded or can be adapted for change of use. The RXL family completes the range with an economical room solution for DESIGO. These room controllers use a proprietary DESIGO bus for communication. Seamless integration of DESIGO RX into the DESIGO building automation and control system makes available the additional functions of building management. Integrated operation of HVAC, lighting and blinds with DESIGO RXC 45 / 72

46 Product range overview: DESIGO RXC The DESIGO RXC hardware DESIGO RXC is a comprehensive range of room controllers for HVAC automation, extension modules for lighting and blinds, and a graded range of tailor-made room units. * RXC32.1 not available in Germany (RC-DE) DESIGO RXC software Each room controller carries downloadable application software (referred to as the "application") with optimum control programs for the corresponding room or area. Siemens maintains a comprehensive library of reliable, fieldproven applications for HVAC and electrical applications. 46 / 72

47 Product range overview: DESIGO RXB DESIGO RXB hardware The DESIGO RXB devices are certified by the Konnex Association and are processed with the ETS engineering and commissioning tool. The range consists of compact controllers, controllers in a room-style housing and room units for HVAC operation. DESIGO RXB software Each DESIGO RXB room controller is loaded with HVAC application software which includes one or more applications. The desired application can be enabled during commissioning. The controllers in the RXB10.1 room housing are our cost-effective solution for HVAC control. They cover radiator and chilled ceiling applications and simple VAV systems. Our compact RXB21.1 and RXB22.1 room controllers are optimized for fan coil applications. The RXB24.1 room controller is designed for radiator and chilled ceiling applications. They can be installed directly in the fan coil unit, in control panels or on ducting. They also communicate with the Synco 700 control system. Product range overview - DESIGO RXL DESIGO RXL is a range of economical room solutions. Data communication operates on a proprietary DESIGO bus which provides the transition to BACnet. Additional functions include time scheduling, trend, heating/cooling demand, central control of setpoints and numerous other features. Commissioning and parameterization is carried out directly on the controller using the Synco Tool ACS or the QAX34.3 room operator unit. Network connection is not required. The Service LED shows the operational status of the room controller at all times. 47 / 72

48 The DESIGO RXL hardware The range consists of compact controllers and QAX3, QAX8, QAX9 room units for HVAC operation. The compact RXL21.1 and RXL22.1 room controllers are load with comprehensive standard applications for fan coils. The required application is enabled in the commissioning phase. DESIGO RXL software Each DESIGO RXL room controller is loaded with HVAC application software which include one or more applications. The desired application can be enabled during commissioning. Our compact RXL21.1 and RXL22.1 room controllers are optimized for fan coil applications. The RXL24.1 room controller is designed for radiator and chilled ceiling applications. They can be installed directly in the fan coil unit, in control panels or on ducting. They also communicate with the Synco 700 control system. Room unit: The key to individual comfort The DESIGO QAX.. room units cover a wide spectrum of possible operating scenarios. The range includes units which measure the room temperature and allow setpoint adjustment, operating mode selection or fan-speed control and an LCD display. The QAX9.. room units are wireless devices. Design and ergonomic operation are optimized. The QAX84.1/PPS2 room unit is based on the device QAX34.1 (software and LCD are identical) and are installed flush mounted as a variant. As a consequence, you can combine the device with third-party switching programs. The QAX5 integrated room unit works with LonWorks combines the operation of HVAC, lighting and blinds in a single device. The keypad can be configured with the combination of buttons and switches best suited to the application. 48 / 72

49 Applications The field-proven applications make DESIGO RX highly versatile. An extensive range of standard applications is available for fan-coil units, VAV, radiators and chilled ceilings. The control parameters are matched to the relevant room at the commissioning stage. Stand-alone room automation operation The room automation system performs its control tasks and communicates autonomously over the LonWorks bus or KNX S-mode bus (EIB). Further, with DESIGO RXL, a range of communicating room controllers with a proprietary DESIGO bus is now available. Integration into the building management system DESIGO RX topology 49 / 72

50 Integration into the automation and control level Freely programmable automation stations with a LonWorks or KNX interface connect the DESIGO RX room automation system into the building automation and control system, at the same time making other functions available. Conversion of LonMark or KNX objects into BACnet objects. Interface to BACnet for networks with RXL room controllers. Concentration and simple operation of room data. Grouping for optimization across rooms. System functions and optimizer software such as time schedules, trends, alarm generation etc. Coordination with the primary plant. Safety functions, e.g. in the event of storm warnings. Integration into the management level Automation level ensures that all data and functions of the room automation system can also be viewed and operated at the management level. The control and operation of the RX devices with DESIGO INSIGHT opens the way to a range of additional functions including the following: Operation and monitoring of rooms via plant graphics. Logging and archiving of trend data. Individual time schedules. Central control and override of setpoints, operating modes, lighting, blinds etc. 50 / 72

51 DESIGO OPEN DESIGO OPEN is a consistent and open communication. Simple technical connection of the widest possible range of building technical systems based on open and standardized data interfaces. DESIGO OPEN offers a portfolio of solutions for simple and cost-effective integration of third-party systems and devices. These quality solutions have the following outstanding project-specific and user-specific features: Features Management functions across system boundaries. Uniform user-interface. Full integration of third-party systems into the building automation and control system. Use of recognized standard communication protocols and powerful standard integration platforms. Expansion and replacement of individual components at any time. Optimum cost/benefit ratio for operation and maintenance. Technical support throughout the entire project cycle for long-term investment protection. DESIGO OPEN provide optimum integration of third-party system at each level, depending on the required process interaction and data point amount. DESIGO OPEN topology 51 / 72

52 DESIGO INSIGHT OPEN SCADA technology INSIGHT OPEN is a modern integration platform for direct connection to the management level which uses vendor-neutral visualization systems based on SCADA technology. SCADA (Supervisory Control and Data Acquisition) systems are software products from the field of industrial automation, and can be used to connect various automation systems using a variety of device drivers. SCADA technology is ideal for connecting stand-alone third-party systems or open automation and field buses, where the emphasis is on operation and monitoring and reliable cross-disciplinary interconnection is not required. Vertical connections are implemented with communication cards or system-specific interfaces plugged directly into a management system PC. INSIGHT OPEN makes use of the technological potential of Citect, a leading SCADA system supplied by CiTechnologies Pty. Ltd., Australia. INSIGHT OPEN is an adjunct to the DESIGO INSIGHT management station and provides the following functions for the integrated third-party system or device: Functions in INSIGHT OPEN Graphical operation of the plant and the process. Alarm display and operation. Dynamic trend curves and long-term data storage. Topological data point operation in Object Viewer. Log book and message archiving. Alarm routing to message receivers. Access protection. INSIGHT OPEN runs on Windows XP or Windows Vista on networks. INSIGHT OPEN provides an OPC client (OLE for process control) for the connection of third-party systems. This supports the specifications of Data Access Version 1.0a and Version 2.0. As a consequence, INSIGHT OPEN is an integral component of the process control system and subject to the same high expectations in respect of reliability and minimum downtime. The process values transferred from third-party systems to the DESIGO INSIGHT management station are mapped as SCADA process variables, or "variable tags". Special tags are used for alarm and trend variables: Alarm tag, alarm process variable. Trend tag, trend process variable. Unlike the data points in the building automation and control system, the process variables (tags) each contain one item of information only. Alarms and trend logs are SCADA objects which are generated by and calculated in the I/O server. Vendor-neutral protocols BACnet. LonWorks. KNX S-mode (EIB). Vendor-specific protocols, e.g. SIPORT NT (access control). AlgoRex (fire detection system). 52 / 72

53 DESIGO SX OPEN SX OPEN is an innovative integration platform used to connect OPC-based third-party systems to an open BACnet network. DESIGO SX OPEN forms a powerful bridge between OPC, and BACnet by replicating an OPC client in OPC, and a BACnet server on BACnet. The functions extend far beyond the simple mapping and transfer of OPC items to BACnet. For example, the freely programmable level of SX OPEN, at which functions can be interconnected, allows the following: Direct mapping of OPC items to BACnet objects, for display and operation by BACnet clients. Grouping of OPC items to create standard integrated BACnet objects. Event-driven transfer of alarms in the BACnet network. Trend server with its own data maintenance for trendlog objects. Peer-to-peer communication with other BACnet servers. SX OPEN is especially suitable for the integration of OPC-based third-party systems where there is a need to interconnect functions locally (peer-to-peer communication). It fully compensates for the disadvantages of simple SCADA technology. The modular software package can be run on standard PC systems with Windows operating systems. Industrial control-panel PCs with no rotating parts (e.g. Siemens micro box) offer reliability, easy maintenance and minimal down time. Features BACnet server to ANSI/ASHRAE with BACnet/IP. Supported data objects: Analog Input and Output, Binary Input and Output, Analog and Binary Value, Multistate Input, Output and Value, Device, Notification Class. Read and write access in accordance with BACnet rules of priority. OPC Client Data Access 2.05a. Vendor-neutral protocols OPC server with data access for: - LonWorks - KNX S-mode (EIB) - M-bus - Modbus - PROFIBUS Vendor-specific protocols, e.g. OPC server with data access for third-party systems.(e.g. fire detection, intruder detection, access control, CCTV, industrial PLCs, other). 53 / 72

54 DESIGO PX OPEN The native BACnet automation station PX OPEN is a multifunctional integration platform used to connect third-party automation stations and open field-bus networks to the BACnet network. PX LON for the connection of LonWorks devices and networks and the DESIGO RXC room automation system. PX Modbus, PX M-bus and PX SCL (Structured Control Language) to connect Modbus, M-bus or simple ASCII protocols for RS232 or RS485 (free SCL programming). PX KNX to connect KNX S-mode (EIB) devices and networks, DESIGO RXB and RXL room automation as well as Synco 700. The data points of the third-party are mapped to input/output functions in BACnet and are then available as fully communicating data points for further processing and further connection, e.g. for: Alarm handling and prioritization. Override control, priority control and commands for central operation. Grouping, Time schedules, Trend logging PX OPEN integrates up to 2000 items of information per device. The bi-directional exchange of data is event-driven, i.e. the systems only exchange information if the data point changes. Peer-to-peer communication can be implemented without difficulty in the BACnet network The PX OPEN integration stations are positioned in a flexible configuration in the BACnet network and can be operated via the local LCD operator units. "Simple" protocols based on ASCII strings can be connected directly to PX OPEN by use of SCL in conjunction with a freely programmable RS232 or RS485 port. Vendor-neutral protocols Vendor-specific protocols, e.g. BACnet LonWorks KNX S-mode (EIB) M-bus Modbus Hotel management: Fidelio. Siemens AlgoRex (fire detection system). PX LON PX LON connects LonWorks networks to DESIGO and maps LonWorks network variables to BACnet data points. Main functions of PX LON Compression of DESIGO RXC room controller data and third-party devices. Maps DESIGO RXC applications to BACnet for operation and monitoring (grouped as HVAC, lighting and blind control functions). Higher-level control and optimization functions, such as room and zone-based groups, time control, and system functions such as changeover, summer/winter compensation etc. Alarm handling, device monitoring. Trend storage. 54 / 72

55 PX LON maps RXC applications in such a way as to produce a room view. This enables the rooms to be grouped together, for shared occupancy programs, or for shared commands for the control of lighting or blinds, for example. PX M-bus PX M-bus connects the M-bus consumption meters to the DESIGO system and maps meter readings and device-related meter information to BACnet data points. Main functions of PX M-bus Consumption data acquisition and remote monitoring of a maximum of 250 consumption and heat meters or up to 2,000 BACnet I/O objects. Compresses data from consumption and heat meters at the automation level. Alarm handling, device monitoring. Trend storage to record meter readings. PX Modbus PX Modbus connects Modbus devices or networks supporting the Modbus protocol as specified by Modicon to the DESIGO system and maps their data points to BACnet data points. PX Modbus is particularly suitable for integrating industrial controls or chillers and linking them to the automation process. PX KNX PX KNX connects KNX S-mode (EIB) networks to DESIGO and maps KNX S-mode (EIB) group addresses to BACnet data points. Main functions of PX KNX Compression of data from the DESIGO RXB room controllers and other KNX data points at the automation level. Mapping of DESIGO RXB and RXL as well as SIEMENS Synco 700 and other KNX S- mode (EIB) applications to BACnet for operation and monitoring (grouped as HVAC, lighting and blind control functions). Higher-level control and optimization functions, such as room and zone-based groups, time control, and system functions such as changeover, summer/winter compensation etc. Alarm handling, device monitoring. Trend storage. DESIGO TX OPEN A few, decentralized, distributed third-party devices can be connected quickly and cost effectively via DESIGO TX OPEN and processed in the automation system. The microprocessor-based OPEN modules connect selected third-party devices via RS232 or RS485 to the decentralized I/O bus of the automation station. Various module types can be used depending on the communications protocol. Manufacturer-specific protocols Modbus. M-bus meters. Variable speed drive: Siemens SED2. Pumps: Grundfos, Wilo. 55 / 72

56 DESIGO tools Professional software tools and a wide range of proven application blocks are available for engineering and processing the automation stations. DESIGO XWORKS plus The engineering tool DESIGO XWORKS plus offers user-friendly software tool that are easy to use and geared to technical processing of customer projects. They include planning, configuration, commissioning and final adjustment of the automation station with the associated program. A variety of report functions are available for documentation purposes. Thanks to its intuitive design of DESIGO XWORKS plus, makes it easy to begin working with the time without time-consuming training. Various processes are consistently supported depending on whether you are working with standardized DESIGO application libraries or setup the program using data points. Flexible programming Moreover, DESIGO XWORKS plus provides tools that flexibly program, together with the DESIGO application library, individual solutions as well as parameterization and commissioning. The CFC Editor is used as a basis for this work. Data exchange is continuous for distributed work on various user groups within the project. Data only needs to be entered once and is always consistent. Functions for project management are available such as creating and archiving projects as well as check in/out of project data for commissioning. As a comprehensive engineering tool, DESIGO XWORKS plus also establishes network topology, integrates third-party systems up to the planning of room automation systems. At the same time DESIGO XWORKS plus supports the interaction with standard room automation LNS tools as well. 56 / 72

57 Programming with D-MAP The D-MAP programming language (DESIGO Modular Application Programming) for DESIGO PX ensures efficient programming and parameter setting for building services plant. D-MAP is optimized for building services applications. The control strategies required for and best suited to efficient operation are implemented using graphicsbased data flow programming. Efficient engineering with blocks and compounds The project-specific HVAC applications are configured, programmed, commissioned and maintained using the CFC Editor. The CFC Editor is a graphics editor based on block and data flow techniques. Predefined and tested application programs are assembled to create compound structures (referred to simply as compounds ), and these are then made available in the libraries. Creating the CFC chart with the CFC Editor DMAP programming features The basic elements of D-MAP programming are blocks and "compounds" (compound functional units). These are stored in libraries. To create a D-MAP program, the blocks and compounds for the required functions are put together in the CFC Editor. This process involves creating instances (of blocks) or copies (of compounds) from the libraries The flow of data between blocks is programmed by interconnecting the "pins" (inputs and outputs) of various blocks 57 / 72

58 Proven application solutions The broad range of DESIGO application libraries cover individual customers needs with building automation and control applications in a comprehensive manner. All available solutions contain images of actual plant, aggregates and components in a structure which can be used equally for design engineering, control, operation and monitoring and display. You can lower operating costs in a sustainable way using energy optimizing DESIGO applications saving energy resources and lowering CO2 emission in the process. Energy efficiency Safety and quality Comfort Operation and monitoring Flexibility Standardized, tested functions meet European standard EN15232 : 2007 Energy Efficiency in buildings Influence of Building Automation and Control and Building Management in the highest classes. Using the existing energy efficiency applications, you not only sustainably save the environment, but also lower building operating costs through the entire life cycle of the building. The application reflect decades of Siemens experience. Many of software applications were developed and extensively tested in real plants to maximize the safety and quality of the solutions. The application portfolio guarantees a high degree of protection for your investment All applications are created with a focus on maximizing the user s comfort. With their sophisticated control strategies and concepts, the applications offer a optimum balance between comfort and energy use. All applications are subject to a transparent operating concept to keep training costs to a minimum. The ease of operation is applied throughout the entire DESIGO system and is provided to the customer when compiling the plants. We always pay special attention to ease of operation should operator interventions be required on the DESIGO INSIGHT management station or on the panel using the PXM10 / PXM20. Thanks to its consistent operating concept, operators are able to quickly initiate the proper measure; even during hectic situations. DESIGO applications map real plants and are clearly structured. Multiple components form an aggregate with multiple aggregates forms a complete plant. Changes to the structures can be undertaken in a flexible manner during a project's engineering phase. DESIGO applications thus fit into the overall expandable modular system, ensuring long-term cost-effectiveness. Energy efficiency Safety and quality Comfort Flexibility Operation and monitoring 58 / 72

Desigo PX Automation system for HVAC and building services

Desigo PX Automation system for HVAC and building services Desigo PX Automation system for HVAC and building services System overview Version 5 Building Technologies Desigo PX Automation system for HVAC and building services Version 5 System overview CM110756en_05

More information

Desigo PX Automation system for HVAC and building services

Desigo PX Automation system for HVAC and building services Desigo PX Automation system for HVAC and building services System overview Version 5.1_SP and later Building Technologies Desigo PX Automation system for HVAC and building services Version 5.1_SP and later

More information

Desigo building automation flexible and energy-efficient

Desigo building automation flexible and energy-efficient Desigo building automation flexible and energy-efficient The intelligent system for all building types, sizes and all applications Answers for infrastructure. Desigo high energy efficiency and flexibility

More information

MM8000 safety and security with smart danger management. A scalable and flexible management station for any requirement. Answers for infrastructure.

MM8000 safety and security with smart danger management. A scalable and flexible management station for any requirement. Answers for infrastructure. MM8000 safety and security with smart danger management A scalable and flexible management station for any requirement Answers for infrastructure. Sophisticated technology for comprehensive safety Safety

More information

It s all open from here.

It s all open from here. It s all open from here. Never let technology impose limits on your future. That thinking drove the design of Honeywell EXCEL 5000 OPEN systems the most flexible and open communication platform for building

More information

DCS Data and communication server

DCS Data and communication server 8 58 PLD.TOWER PLD.RACK VISONIK DCS Data and communication server PLD.TOWER PLD.RACK Data and communication servers (DCS) are used as management stations in building automation and control (BAC). With

More information

Efficient remote access to machines and plants with SIMATIC

Efficient remote access to machines and plants with SIMATIC Efficient remote access to machines and plants with SIMATIC Telecontrol and teleservice solutions modular, flexible and secure SIMATIC NET siemens.com/industrial-remote-access Industrial remote access

More information

Guest Room Controls & Monitoring System. Integrated Solution for Hotels Southern Countries. www.lonix.com

Guest Room Controls & Monitoring System. Integrated Solution for Hotels Southern Countries. www.lonix.com Guest Room Controls & Monitoring System Integrated Solution for Hotels Southern Countries www.lonix.com GUEST ROOM CONTROLS & MONITORING SYSTEM INDEX 1 GENERAL... 3 1.1 SYSTEM INTEGRATION... 3 1.2 USER

More information

Integrated Building Management and Security System. Building Automation & Security. www.coba-group.com

Integrated Building Management and Security System. Building Automation & Security. www.coba-group.com Integrated Building Management and Security System Building Automation & Security www.coba-group.com INTEGRATED BUILDING MANAGEMENT AND SECURITY SYSTEM INDEX 1 GENERAL... 3 1.1 SYSTEM INTEGRATION... 3

More information

Automation stations modular model

Automation stations modular model s 9 221 PXC64-U DESIGO PX Automation stations modular model PXC-U Freely programmable modular automation stations for HVAC and building services Native BACnet automation station with communication via

More information

MM8000 highest safety and security with intelligent danger management

MM8000 highest safety and security with intelligent danger management MM8000 highest safety and security with intelligent danger management A scalable and flexible management station for any requirement Answers for infrastructure. Sophisticated technology for comprehensive

More information

Ovation Operator Workstation for Microsoft Windows Operating System Data Sheet

Ovation Operator Workstation for Microsoft Windows Operating System Data Sheet Ovation Operator Workstation for Microsoft Windows Operating System Features Delivers full multi-tasking operation Accesses up to 200,000 dynamic points Secure standard operating desktop environment Intuitive

More information

OPENweb. Efficient controlling at the highest level.

OPENweb. Efficient controlling at the highest level. OPENweb Efficient controlling at the highest level. OPENweb. Secure, networked, powerful. OPENweb at a glance. You would like to have your building service facilities reliably monitored and efficiently

More information

APPLICATION NOTE. The DMP Software Family DMP COMPUTER SOFTWARE PROGRAMS

APPLICATION NOTE. The DMP Software Family DMP COMPUTER SOFTWARE PROGRAMS APPLICATION NOTE Contents The DMP Software Family... 1 Stand-Alone Link Software... 1 Add-on Modules for Link Software... 1 System Link End-User Panel Management Software... 2 Simple Registration and Activation...

More information

AutoLog ControlMan. Remote Monitoring & Controlling Service

AutoLog ControlMan. Remote Monitoring & Controlling Service AutoLog 1 AutoLog ControlMan Remote Monitoring & Controlling Service Web browser based HMI / SCADA interface Server is hosted by Internet server hosting company Control units communicate wirelessly via

More information

Insight Advanced Workstation

Insight Advanced Workstation Technical Specification Sheet Document No. 149-333P25 October 29, 2015 Insight Advanced Workstation Figure 1. Insight Advanced Main Menu. The Insight Advanced Workstation transforms a personal computer

More information

Chapter-5 Introduction to Building Automation System (BAS)

Chapter-5 Introduction to Building Automation System (BAS) Chapter-5 Introduction to Building Automation System (BAS) Chapter-5 Introduction to Building Automation System (BAS) ၅.၁ Introduction Building Automation System(BAS) sub system equipment service monitor

More information

Declaration of Conformity 21 CFR Part 11 SIMATIC WinCC flexible 2007

Declaration of Conformity 21 CFR Part 11 SIMATIC WinCC flexible 2007 Declaration of Conformity 21 CFR Part 11 SIMATIC WinCC flexible 2007 SIEMENS AG Industry Sector Industry Automation D-76181 Karlsruhe, Federal Republic of Germany E-mail: pharma.aud@siemens.com Fax: +49

More information

Integrated Building Management and Security System. Building Automation & Security. www.lonix.com

Integrated Building Management and Security System. Building Automation & Security. www.lonix.com Integrated Building Management and Security System Building Automation & Security www.lonix.com INTEGRATED BUILDING MANAGEMENT AND SECURITY SYSTEM INDEX 1 GENERAL... 3 1.1 GREEN BUILDING REQUIREMENTS...

More information

DeltaV Remote Client. DeltaV Remote Client. Introduction. DeltaV Product Data Sheet. Remote engineering and operator consoles

DeltaV Remote Client. DeltaV Remote Client. Introduction. DeltaV Product Data Sheet. Remote engineering and operator consoles January 2013 Page 1 DeltaV Remote Client Remote engineering and operator consoles View Multiple DeltaV Systems from a single workstation Remote Operator Station over low speed and dial up communications

More information

How To Use Safety System Software (S3)

How To Use Safety System Software (S3) SPECIFICATION DATA Safety System Software (S3) APPLICATION Safety System Software (S 3 ) is a robust, full featured configuration, diagnostic, programming and real-time monitoring package for integrators

More information

SAUTER novapro Open: B-AWS. BACnet Advanced Workstation

SAUTER novapro Open: B-AWS. BACnet Advanced Workstation SAUTER novapro Open: B-AWS BACnet Advanced Workstation SAUTER novapro Open: A SCADA system that provides all needs for any type of building. Open for public buildings Secure for FDA and GAMP Flexible for

More information

A Real Time, Object Oriented Fieldbus Management System

A Real Time, Object Oriented Fieldbus Management System A Real Time, Object Oriented Fieldbus Management System Mr. Ole Cramer Nielsen Managing Director PROCES-DATA Supervisor International P-NET User Organisation Navervej 8 8600 Silkeborg Denmark pd@post4.tele.dk

More information

IBMS Specification. Specification & Design Guideline for Integrated Intelligent Building Management System. Lonix Ltd. www.lonix.

IBMS Specification. Specification & Design Guideline for Integrated Intelligent Building Management System. Lonix Ltd. www.lonix. 1 (23) IBMS Specification Specification & Design Guideline for Integrated Intelligent Building Management System Lonix Ltd www.lonix.com 2 (23) Specification for Integrated Intelligent Building Management

More information

Software INTERACT. MachineLogic. The Shortest Distance Between Man and Machine

Software INTERACT. MachineLogic. The Shortest Distance Between Man and Machine Software INTERACT MachineLogic The Shortest Distance Between Man and Machine Fully IntegrateYour HMI and PC-Based Control With MachineShop Project Management MachineShop s Project Management is a simple,

More information

TAC Vista Family TAC Xenta 700 Everything You Need to Monitor and Control Your Building

TAC Vista Family TAC Xenta 700 Everything You Need to Monitor and Control Your Building TAC Vista Family TAC Xenta 700 Everything You Need to Monitor and Control Your Building Retail: an application example for small-size solutions The TAC Xenta 700 is a complete Building Management System.

More information

Building Technologies

Building Technologies Building Technologies : simple and secure danger management. Integration increases security! The increasing danger potential for people and assets makes the need for better protection increasingly more

More information

SIMATIC PDM software. Siemens FI 01 2001 7/1

SIMATIC PDM software. Siemens FI 01 2001 7/1 software 7 Application...7/2 Graphical user interface...7/2 Communication...7/3 Diagnostics...7/4 Technical data...7/5 Ordering data...7/5 Siemens FI 01 2001 7/1 Application, graphical user interface Application

More information

Communication Capabilities via a Touch Screen or a Web Browser Further Expand Air-Conditioning Control Possibilities.

Communication Capabilities via a Touch Screen or a Web Browser Further Expand Air-Conditioning Control Possibilities. Communication Capabilities via a Touch Screen or a Web Browser Further Expand Air-Conditioning Control Possibilities. More Freedom to Administrators Connectable up to 128 Indoor Unit Groups (256 indoor

More information

Compliance Response Edition 07/2009. SIMATIC WinCC V7.0 Compliance Response Electronic Records / Electronic Signatures. simatic wincc DOKUMENTATION

Compliance Response Edition 07/2009. SIMATIC WinCC V7.0 Compliance Response Electronic Records / Electronic Signatures. simatic wincc DOKUMENTATION Compliance Response Edition 07/2009 SIMATIC WinCC V7.0 Compliance Response Electronic Records / Electronic Signatures simatic wincc DOKUMENTATION Compliance Response Electronic Records / Electronic Signatures

More information

FOXBORO. I/A Series SOFTWARE Product Specifications. I/A Series Intelligent SCADA SCADA Platform PSS 21S-2M1 B3 OVERVIEW

FOXBORO. I/A Series SOFTWARE Product Specifications. I/A Series Intelligent SCADA SCADA Platform PSS 21S-2M1 B3 OVERVIEW I/A Series SOFTWARE Product Specifications Logo I/A Series Intelligent SCADA SCADA Platform PSS 21S-2M1 B3 The I/A Series Intelligent SCADA Platform takes the traditional SCADA Master Station to a new

More information

Compact Monitoring Technology your environmental monitoring solution

Compact Monitoring Technology your environmental monitoring solution Compact Monitoring Technology your environmental monitoring solution Monitor your GxP environmental parameters and cut your validation costs. Solutions for Life Science and Hospitals www.siemens.com/cmt

More information

Supporting ANY PRODUCT employing

Supporting ANY PRODUCT employing Supporting ANY PRODUCT employing -BackNet -LonWorks -ModBus - XML -SNMP -OPC WEB controllers (JACE-Java Application Control Engine) - Provides server and internet power at the building level - Open & legacy

More information

Safety Integrated. SIMATIC Safety Matrix. The Management Tool for all Phases of the Safety Lifecycle. Brochure September 2010. Answers for industry.

Safety Integrated. SIMATIC Safety Matrix. The Management Tool for all Phases of the Safety Lifecycle. Brochure September 2010. Answers for industry. SIMATIC Safety Matrix The Management Tool for all Phases of the Safety Lifecycle Brochure September 2010 Safety Integrated Answers for industry. Functional safety and Safety Lifecycle Management Hazard

More information

Getting Started with Endurance FTvirtual Server

Getting Started with Endurance FTvirtual Server Getting Started with Endurance FTvirtual Server Marathon Technologies Corporation Fault and Disaster Tolerant Solutions for Windows Environments Release 6.1.1 June 2005 NOTICE Marathon Technologies Corporation

More information

ControlMaestro and. BACnet integrated solution

ControlMaestro and. BACnet integrated solution ControlMaestro and BACnet integrated solution The Automation Software Platform designed to deliver first class solutions to the Build Automation market using its intimate knowledge of Building protocols.

More information

NEW. EVEN MORE data acquisition and test stand automation

NEW. EVEN MORE data acquisition and test stand automation NEW EVEN MORE data acquisition and test stand automation the new class of data The plug&play complete package User benefits Expert Series is the latest generation of data acquisition Complete hardware

More information

DANGER indicates that death or severe personal injury will result if proper precautions are not taken.

DANGER indicates that death or severe personal injury will result if proper precautions are not taken. Multi-User Systems 1 ArchiveServer 2 SIMATIC HMI WinCC V7.0 SP1 File Server 3 WinCC ServiceMode 4 Redundant Systems 5 System Manual Print of the Online Help 11/2008 Legal information Warning notice system

More information

SAUTER EY-modulo 5. The complete building management solution

SAUTER EY-modulo 5. The complete building management solution SAUTER EY-modulo 5 The complete building management solution SAUTER high-end technology for the highest standards in fully integrated building management. The best of the best. In a single system. Integrated,

More information

DeltaV Web Server. DeltaV Web Server. Introduction. DeltaV Product Data Sheet. Gives you a secure view of your process from your desktop PC

DeltaV Web Server. DeltaV Web Server. Introduction. DeltaV Product Data Sheet. Gives you a secure view of your process from your desktop PC January 2013 Page 1 DeltaV Web Server Use the to view your process anywhere on the planet. Gives you a secure view of your process from your desktop PC Offers more information and scalable architecture

More information

Symphony Plus S+ Engineering: Composer Harmony

Symphony Plus S+ Engineering: Composer Harmony Symphony Plus S+ Engineering: Composer Harmony Symphony Plus S+ Engineering: Composer Harmony Symphony TM Plus includes a comprehensive suite of engineering tools. S+ Engineering s Composer tools provide

More information

StruxureWareTM for Buildings

StruxureWareTM for Buildings StruxureWareTM for Buildings Next generation intelligent Building Management System (ibms) Product Catalogue Make the most of your energy Plan for the future while protecting your past investments. 03

More information

Presentation: May 15 th 2013 Location: Saskatoon Speaker: Robert Picard. Airport Expertise. Holistic Approach to IT Solutions Automation Intelligence

Presentation: May 15 th 2013 Location: Saskatoon Speaker: Robert Picard. Airport Expertise. Holistic Approach to IT Solutions Automation Intelligence Presentation: May 15 th 2013 Location: Saskatoon Speaker: Robert Picard Airport Expertise Holistic Approach to IT Solutions Automation Intelligence Agenda Automation Intelligence (AI) Concept Responding

More information

ProfessionalPLUS Station Software Suite

ProfessionalPLUS Station Software Suite January 2013 Page 1 All you need to configure, control, and diagnose your plant is available on the ProfessionalPLUS Station Global database, architected for flexibility and scalability Powerful, graphical

More information

Technical Information POWER PLANT CONTROLLER

Technical Information POWER PLANT CONTROLLER Technical Information POWER PLANT CONTROLLER Content The Power Plant Controller offers intelligent and flexible solutions for the control of all PV power plants in the megawatt range. It is suitable for

More information

Passion for Innovation

Passion for Innovation Passion for Innovation A Complete Solution Hardware All the Alveo servers are designed and optimized to manage the home automation system. They arebuilt for continuous operation with fanless processing

More information

DESIGO PX PXM10 operator unit User's guide Version 2.3. Siemens Building Technologies Building Automation

DESIGO PX PXM10 operator unit User's guide Version 2.3. Siemens Building Technologies Building Automation s DESIGO PX PXM10 operator unit User's guide Version 2.3 CM110397en 31.08.2004 Siemens Building Technologies Building Automation 2/34 Building Automation 31.08.2004 Contents 1 About this manual... 5 1.1

More information

Newron Efficient building management

Newron Efficient building management Newron Efficient building management Everything from one source. And one head. Because today efficient buildings are intelligently networked. The suitable solutions for this can now be found by architects,

More information

YZP 480...495: SAUTER Vision Center

YZP 480...495: SAUTER Vision Center YZP 480...495: SAUTER Vision Center SAUTER Vision Center 3.0 - latest-generation modular building management software for energy-efficient buildings The SAUTER Vision Center (SVC) is a web-based building

More information

Engineering and service software For KNX and LPB plants

Engineering and service software For KNX and LPB plants 5 649 Engineering and service software For KNX and LPB plants As of V9.00 ACS790 The engineering and service software ACS790 is for KNX and LPB plants equipped with the appropriate bus devices. The software

More information

Tracer Summit Web Server

Tracer Summit Web Server Tracer Summit Web Server Web-based access for the Tracer Summit building automation system March 2003 BAS-PRC014-EN Introduction The Tracer Summit Web Server provides the ability to operate a Tracer Summit

More information

General System Architecture

General System Architecture Overview Centracs is an Intelligent Transportation System (ITS) application that provides a centralized integrated platform for traffic signal system control, Closed-Circuit TV (CCTV) monitoring and control,

More information

SYMMETRY PRODUCT OVERVIEW

SYMMETRY PRODUCT OVERVIEW ACCESS CONTROL The Symmetry Security Management Systems provides powerful integrated solutions for organizations requiring Access Control and Integrated Security. Solutions are available for organizations

More information

Semaphore T BOX Applications in Data Center Facilities

Semaphore T BOX Applications in Data Center Facilities Semaphore T BOX Applications in Data Center Facilities Introduction Data centers must reliably provide 24/7/365 operation. For automation and monitoring of the facility, use of a rugged, reliable RTU is

More information

Daily Operations TRACER SUMMIT

Daily Operations TRACER SUMMIT Daily Operations TRACER SUMMIT Version 17 BMTX-SVU01B-EN Daily Operations Tracer Summit Version 17 Tracer Summit Version 17 BMTX-SVU01B-EN June 2006 BMTX-SVU01B-EN Tracer Summit Daily Operations This

More information

SIMATIC. SIMATIC Logon. User management and electronic signatures. Hardware and Software Requirements. Scope of delivery 3.

SIMATIC. SIMATIC Logon. User management and electronic signatures. Hardware and Software Requirements. Scope of delivery 3. SIMATIC SIMATIC SIMATIC User management and electronic signatures 1 Hardware and Software Requirements 2 Scope of delivery 3 Installation 4 5 Configuration Manual 08/2008 A5E00496669-05 Legal information

More information

SYMMETRY. DATASHEET ACCESS CONTROL Product Overview

SYMMETRY. DATASHEET ACCESS CONTROL Product Overview DATASHEET ACCESS CONTROL Product Overview SYMMETRY The AMAG Technology range of Security Management Systems provides powerful integrated solutions for organizations requiring Access Control and Integrated

More information

Reliable Security Solutions

Reliable Security Solutions Reliable Security Solutions Challenger10 The proven solution for access control, intrusion detection and video integration. An integrated security solution for your most challenging environments The Tecom

More information

Computer Creep System

Computer Creep System WinCCS II Computer Creep System The Advanced, Versatile, Fully- Automated System for Operating All of Your Creep Test Frames Increased Productivity and Accuracy Through Automation: WinCCS II, the New Creep

More information

CenterMind G+ Smart and Proactive Environment Monitoring

CenterMind G+ Smart and Proactive Environment Monitoring CenterMind G+ Smart and Proactive Environment Monitoring Smart and Proactive Environment Monitoring real-time visibility into the state of your computer room or data center environment, 24/7 RiT CenterMind

More information

Enterprise Facility Management Software

Enterprise Facility Management Software Enterprise Facility Management Software How your environment can benefit from enteliweb systems Scheduling Event scheduling in enteliweb allows occupancy to be associated with specific date ranges or recurrences.

More information

Next Generation. Surveillance Solutions. Cware. The Advanced Video Management & NVR Platform

Next Generation. Surveillance Solutions. Cware. The Advanced Video Management & NVR Platform Next Generation Surveillance Solutions Cware The Advanced Video Management & NVR Platform Advanced Open Management Benefit from the most effective CCTV management platform Cware is an advanced video management

More information

SIMATIC IT Historian. Increase your efficiency. SIMATIC IT Historian. Answers for industry.

SIMATIC IT Historian. Increase your efficiency. SIMATIC IT Historian. Answers for industry. SIMATIC IT Historian Increase your efficiency SIMATIC IT Historian Answers for industry. SIMATIC IT Historian: Clear Information at every level Supporting Decisions and Monitoring Efficiency Today s business

More information

SICAM PAS - the Key to Success Power Automation compliant with IEC 61850 - and your existing system

SICAM PAS - the Key to Success Power Automation compliant with IEC 61850 - and your existing system SICAM PAS - the Key to Success Power Automation compliant with IEC 61850 - and your existing system Power Transmission & Distribution SICAM PAS - Power Automation Up-To-Date Siemens Power Transmission

More information

Communication Interface Units. CIU Prime & CIU Plus

Communication Interface Units. CIU Prime & CIU Plus Communication Interface Units CIU Prime & CIU Plus The Tank Gauging People COMMUNICATION INTERFACE UNITS Tank inventory information in liquid storage terminal and refinery automation is increasingly critical

More information

Kevin Kochirka, ABB Turbine Automation, June 29, 2016. Flexible turbine control retrofits Webinar

Kevin Kochirka, ABB Turbine Automation, June 29, 2016. Flexible turbine control retrofits Webinar Kevin Kochirka, ABB Turbine Automation, June 29, 2016 Flexible turbine control retrofits Webinar Welcome Speaker introduction Kevin Kochirka Sr. Applications Engineer with ABB Inc. Kevin.Kochirka@us.abb.com

More information

Answers for infrastructure. HVAC control with Synco simple and energy-efficient

Answers for infrastructure. HVAC control with Synco simple and energy-efficient Answers for infrastructure. HVAC control with Synco simple and energy-efficient Synco for enhanced comfort and energy efficiency Buildings place different requirements on HVAC control systems depending

More information

3 Easy Steps to Get Started

3 Easy Steps to Get Started Quick Start Guide Contents 1. What is icafe Manager?... 4 1.1. Server... 4 1.2. Client Terminal... 4 2. Downloading, Registering & Activating Cafe Code... 5 2.1. Downloading icafe Manager:... 5 2.2. Registering

More information

Eelectron srl, Via Magenta 77/22, I-20017 Rho (MI), Italia +39 02.9316681 +39 02.93507688 info@eelectron.com www.eelectron.

Eelectron srl, Via Magenta 77/22, I-20017 Rho (MI), Italia +39 02.9316681 +39 02.93507688 info@eelectron.com www.eelectron. 1/48 Contents Introduction Main Description ehotel Advanced ehotel Professional ehotel Standard ehotel Client Installation Program installation Task Description etask etask Description eprog eprog Description

More information

Quareo ICM Server Software

Quareo ICM Server Software The Quareo Infrastructure Configuration Manager (ICM) is a server software application designed to document and administer both passive and active network connectivity infrastructure. ICM enables management

More information

G120P variable speed drive boost efficiency, cut costs

G120P variable speed drive boost efficiency, cut costs G120P variable speed drive boost efficiency, cut costs Intelligent, versatile controlling for fans and pumps in HVAC plants. Easy to use and easy on the environment. www.siemens.com/g120p How do you spell

More information

HELPING BUILDINGS THINK

HELPING BUILDINGS THINK DATASHEET PORTFOLIO Product Helping buildings think. We offer a wide range of products and services for our clients. This documentation provides a list of products that we can offer. Deliverables Products

More information

Functional Specification Document

Functional Specification Document Functional Specification Document Access Control Technology Unit C1 South City Business Centre Tallaght Dublin 24 Ireland Ph: + 353 (0) 1 4662570 Web: www.accesscontrol.ie Index Introduction 1.1 Hardware

More information

R&S AFQ100A, R&S AFQ100B I/Q Modulation Generator Supplement

R&S AFQ100A, R&S AFQ100B I/Q Modulation Generator Supplement I/Q Modulation Generator Supplement The following description relates to the Operating Manuals, version 03 of R&S AFQ100A, and version 01 of R&S AFQ100B. It encloses the following topics: LXI features,

More information

Visualization SIMATIC. Visualization. Present sample project. HMI configuration. Insert HMI device from libraries 3. Configuring HMI connection 4

Visualization SIMATIC. Visualization. Present sample project. HMI configuration. Insert HMI device from libraries 3. Configuring HMI connection 4 Present sample project 1 HMI configuration 2 SIMATIC Getting Started Insert HMI device from libraries 3 Configuring HMI connection 4 Configuring system diagnostics 5 Simulating an HMI device 6 05/2014

More information

Utility Communications FOXMAN-UN Network Management System for ABB Communication Equipment

Utility Communications FOXMAN-UN Network Management System for ABB Communication Equipment Utility Communications FOXMAN-UN Network Management System for ABB Communication Equipment A reliable & flexible communication network lies at the heart of successful electrical grid operations. A comprehensive

More information

Why Can t We Be Friends?

Why Can t We Be Friends? Why Can t We Be Friends? Monitoring the Server Room by Introducing Modbus to SNMP Stanley Liu Product Manager, Data Acquisition & Control Division Overview IA devices are very useful for monitoring server

More information

SCADA Questions and Answers

SCADA Questions and Answers SCADA Questions and Answers By Dr. Jay Park SCADA System Evaluation Questions Revision 4, October 1, 2007 Table of Contents SCADA System Evaluation Questions... 1 Revision 4, October 1, 2007... 1 Architecture...

More information

Alarm Systems. Peace of Mind. Agri-Alert alarms have been protecting swine operations across the world since 1997. automated production systems

Alarm Systems. Peace of Mind. Agri-Alert alarms have been protecting swine operations across the world since 1997. automated production systems Alarm Systems Agri-Alert alarms have been protecting swine operations across the world since 1997. Peace of Mind The Agri-Alert alarm system constantly monitors your operation and quickly notifies you

More information

SECTION 16911 WEB-BASED POWER MONITORING COMMUNICATIONS SYSTEM

SECTION 16911 WEB-BASED POWER MONITORING COMMUNICATIONS SYSTEM WEB-BASED POWER MONITORING COMMUNICATIONS SYSTEM PART 1 GENERAL 01 02 03 04 SCOPE This section describes the metering, communications, and visualization requirements for a modular, scalable Web-based Power

More information

Watchdog Monitor user guide

Watchdog Monitor user guide General The Watchdog AW-4, in short AW-4, can be controlled and monitored by a centralized monitor server. This server is located in a large Dutch server centre with high speed connections, directly connected

More information

Optical Network Management System. Remote Testing, Network Monitoring, and Service Provisioning Solution for High-Quality Network Performance

Optical Network Management System. Remote Testing, Network Monitoring, and Service Provisioning Solution for High-Quality Network Performance Optical Network Management System Remote Testing, Network Monitoring, and Service Provisioning Solution for High-Quality Network Performance JDSU Enabling Broadband and Optical Innovation Improving the

More information

Licenses of savic-net for Integrated Building Management System for FDA Title 21 CFR Part 11 Compliance

Licenses of savic-net for Integrated Building Management System for FDA Title 21 CFR Part 11 Compliance Specifications Licenses of savic-net for Integrated Building Management System for FDA Title CFR Part Compliance General The savic-net for Integrated Building Management System (hereinafter referred to

More information

testo Saveris 21CFR Part 11 Software Instruction manual

testo Saveris 21CFR Part 11 Software Instruction manual testo Saveris 21CFR Part 11 Software Instruction manual 2 1 Contents 1 Contents 1 Contents... 3 2 Specifications... 4 2.1. Intended purpose... 4 2.2. 21 CFR Part 11 and terminology used... 5 3 First steps...

More information

Emerson Smart Firewall

Emerson Smart Firewall DeltaV TM Distributed Control System Product Data Sheet Emerson Smart Firewall The Emerson Smart Firewall protects the DeltaV system with an easy to use perimeter defense solution. Purpose built for easy

More information

ProficyTM. HMI/SCADA - ifix I MPLEMENTING S ECURITY

ProficyTM. HMI/SCADA - ifix I MPLEMENTING S ECURITY ProficyTM HMI/SCADA - ifix I MPLEMENTING S ECURITY Version 4.0 December 2005 All rights reserved. No part of this publication may be reproduced in any form or by any electronic or mechanical means, including

More information

Industrial HiVision Software

Industrial HiVision Software Industrial HiVision Software The Essential Management Tool For All Stages of Your Network Life Cycle Network visibility equals high availability. Industrial HiVision is a state-of-the-art software package

More information

Comprehensive Solutions for Data Centers. Rely on Siemens for maximum uptime, reliability, and efficiency. www.usa.siemens.

Comprehensive Solutions for Data Centers. Rely on Siemens for maximum uptime, reliability, and efficiency. www.usa.siemens. Comprehensive Solutions for Data Centers Rely on Siemens for maximum uptime, reliability, and efficiency. www.usa.siemens.com/datacenters Siemens can meet the demands of your mission critical facility.

More information

NEC Express5800 Series NEC ESMPRO AlertManager User's Guide

NEC Express5800 Series NEC ESMPRO AlertManager User's Guide NEC Express5800 Series NEC ESMPRO AlertManager User's Guide 7-2006 ONL-4152aN-COMMON-128-99-0606 PROPRIETARY NOTICE AND LIABILITY DISCLAIMER The information disclosed in this document, including all designs

More information

PowerLogic ION Enterprise 5.6

PowerLogic ION Enterprise 5.6 PowerLogic ION Enterprise 5.6 Power Management Software User Guide April 2007 Notices This section describes the symbols used in this guide. Danger This alerts you to things that may cause serious injury

More information

IP Based Control for Mechanical and Electrical Systems in an Enterprise Environment

IP Based Control for Mechanical and Electrical Systems in an Enterprise Environment White Paper IP Based Control for Mechanical and Electrical Systems in an Enterprise Environment Joe Noworatzky Vice President, Engineering Johnson Controls, Inc. Introduction Facility managers of the future

More information

IP-Based Communications Solutions

IP-Based Communications Solutions IP-Based Communications Solutions IP-Based Communications Solutions Effective Communications Facility-Wide and Campus-Wide Leverage your network and lower your system costs Scalable, cost-effective and

More information

Andover Continuum Remote Communication Configuration Guide

Andover Continuum Remote Communication Configuration Guide Andover Continuum Remote Communication Configuration Guide 2010, Schneider Electric All Rights Reserved No part of this publication may be reproduced, read or stored in a retrieval system, or transmitted,

More information

VM600 CMS Software. VM600 Series Software for Condition Monitoring System (CMS) FEATURES DESCRIPTION

VM600 CMS Software. VM600 Series Software for Condition Monitoring System (CMS) FEATURES DESCRIPTION VM600 Series Software for Condition Monitoring System (CMS) FEATURES Configuration and operation of VM600 hardware (CMC16 and IOC16T cards) Automatic data acquisition and storage Limit exceedance checking

More information

SPPA-T3000 Control System The Benchmark in Controls

SPPA-T3000 Control System The Benchmark in Controls Instrumentation, Controls & Electrical SPPA-T3000 Control System The Benchmark in Controls Siemens Power & Process Automation Answers for energy. The benchmark for Distributed Control Systems Developed

More information

Real Time Monitor. A Real-Time Windows Operator Interface. DDE Compliant. (for remote data display)

Real Time Monitor. A Real-Time Windows Operator Interface. DDE Compliant. (for remote data display) Real Time Monitor A Real-Time Windows Operator Interface DDE Compliant (for remote data display) TABLE OF CONTENTS 1. INTRODUCTION...1 1.1 INSTALLATION...2 1.2 FIRST START UP - DDE CONFIGURE...2 1.3 AUTO-STARTUP...2

More information

Managing Relion IEDs Protection and control IED manager PCM600

Managing Relion IEDs Protection and control IED manager PCM600 Managing Relion IEDs Protection and control IED manager PCM600 Efficient management of Relion protection and control IEDs The protection and control IED manager PCM600 tool provides versatile functionalities

More information

CPUs - CPU 315-2 PN/DP

CPUs - CPU 315-2 PN/DP Overview The CPU with a medium program memory and quantity framework High processing performance in binary and floating-point arithmetic Used as a central controller on production lines with central and