Technical Brief. 3M Commercial HVAC Filters. Commercial HVAC Filter Efficiency Reporting Value. Abstract. Introduction
|
|
- Meghan Goodman
- 8 years ago
- Views:
Transcription
1 3M Commercial HVAC Filters Technical Brief Commercial HVAC Filter Efficiency Reporting Value Abstract The effi ciency of fi lters utilized in the HVAC industry is characterized by the Minimum Effi ciency Reporting Value (MERV), as defi ned in the ASHRAE standard. When originally adopted in 1999, it was recognized by the standard committee that the MERV value did not predict the full drop in effi ciency of electret media in actual use in many HVAC environments. ASHRAE has adopted an improved method that more accurately predicts the drop in effi ciency of electret media in commercial and industrial environments. This improved fi lter conditioning protocol is included in as Appendix J, having a designation of MERV-A. 3M Commercial HVAC Filters A13 and A11 are specifi cally designed to provide predictable particle capture effi ciency per Appendix J. To help provide the maximum energy savings potential, 3M s innovative HVAC fi lters utilize a composite media that contains a highly engineered, proprietary electrostatically charged (electret) polypropylene microfi ber layer. 3M has successfully developed products that retain a signifi cant electret component at the effi ciency minimum determined by Appendix J. 3M s fi ltration media consists of an optimized balance of electret and mechanical fi ltration components resulting in a low pressure drop, high particle loading fi lter that is robust in commercial and industrial HVAC environments. Introduction HVAC air fi lters are critical to the effi cient operation of the air handling system of any building. They provide additional protection for the equipment within the air handling system 1 and provide an important component to an Indoor Air Quality management program. 2,3 Higher particle reduction effi ciency results in cleaner air moving through the building s air handling system. Importantly, HVAC fi lters may also contribute substantially to the energy required to move air within a building as a result of the pressure drop across the fi lter, or a bank of multiple fi lters. 4,5 The pressure drop of the fi lter increases over time as it loads with environmental debris, hence, the energy utilization correspondingly increases over time. The total energy required to move air through a fi lter is directly related to the average pressure drop over the fi lter life. The greater the ability of a fi lter to load without substantial increase in pressure drop, the greater the possible energy savings. The choice of a fi lter is in large part based upon these three fundamental attributes: effi ciency, initial pressure drop, and filter loading. 3M s design approach for the 3M Commercial HVAC brand fi lters is based on ensuring that the particle capture effi ciency meets the most stringent requirement set forth by the leading industry standard test method. This test method is rigorously defi ned by ASHRAE 52.2 (2007): Method of Testing General Ventilation Air-Cleaning Devices for Reduction Effi ciency by Particle Size (Appendix J). Filters rated by this test protocol are designated with a MERV-A reporting value (Minimum Effi ciency Reporting Value, where A designates that the testing was done per Appendix J of the standard). 3M Commercial HVAC fi lters are highly engineered to provide the optimum balance of these properties for commercial and industrial air handling systems. To provide the most value for the building owner and operator, 3M Commercial HVAC fi lters are precisely designed to minimize the total energy utilization at each effi ciency level. Energy utilization is minimized by designing a product with very low initial pressure drop and low rate of pressure drop increase as it loads in-use. This is accomplished by control and optimization of every component of the product from media to pleat structure to frame design. This requires an iterative process of media and fi lter development, design and performance testing.
2 3M s innovative fi ltration media is a composite containing a highly engineered, proprietary electrostatically charged (electret) polypropylene microfi ber layer. Each layer in this composite contributes to a fi lter having a unique balance of mechanical and electrostatic fi ltration mechanisms. Importantly, the composite media is designed to help ensure a long life from both a pressure drop and minimum effi ciency perspective. 3M s unique fi ltration media is based on advanced materials and processes that result in a stable, long life electret. By truly optimizing media structure and media charge, 3M is able to provide a fi lter that is robust in HVAC environments as validated by the challenging conditioning protocol defi ned in ASHRAE Appendix J. In-Use Particle Capture Efficiency It is well known that electrostatically charged media (electret media) provides the potential basis for a fi lter having very low initial pressure drop compared to fi lters utilizing uncharged media of the same fi lter design and effi ciency. 6 Electret media is composed of fi bers containing a bipolar distribution of positive and negative charges, yet being charge neutral overall (see following illustration) 7. Fiber with line dipole charge It is also well known that the effi ciency of electret based fi lters, including 3M s, will reduce over time to some extent in HVAC and other environments. 8,9 It is important to note that this in-use effi ciency reduction is not a result of the electret charge stability itself. The charge level on 3M s media remains essentially unchanged for years when stored in temperature and humidity conditions found in the most extreme HVAC environments. Instead, the in-use effi ciency reduction is a direct result of the initial loading of the media with particulates in the environment. This effect is an inevitable consequence of the fact that airborne particles in the environment carry a bipolar charge distribution. When a charged particle is drawn to media having an opposite charge, the effect is to shield or neutralize that charge to subsequent airborne particles. At the same time, as particles are captured the effective media fi ber area is increasing, thereby, increasing the mechanical capture effi ciency. The balance in electret and mechanical effi ciency mechanisms and how they vary over time is shown generically in the following graph. Example Particle Capture Efficiencey (%) Minimum Efficiency Electret Component at Minimum Electret Mechanical Total Time In-Use 2
3 There are many factors which impact the specifi c transient effi ciency and pressure drop behaviors. Primary among these factors is the precise chemical and mechanical structure of the fi ltration media, including the media polymer and charge additive chemistry, the media formation process, the average fi ber and size distribution, and the electret charging process. In addition, the fi lter design will impact this behavior since media face air velocity and particle loading rate are important. The environmental conditions are equally important in determining this transient particle capture behavior including particle charge, average particle size and size distribution, air fl ow velocity and humidity. These factors are all dependent on a given location and air handling system. The most important of these environmental factors is the particle size distribution challenging the fi lter. Small particles have a much greater impact on the shielding effects of the electret, particularly when considering the build-up of mechanical effi ciency. It is clear that electret fi lters can be designed to maintain an important level of charge at the point that the total effi ciency is at its minimum. However, to do so in the widest range of environments requires a highly engineered product from media to fi lter, designed specifi cally for HVAC environments. ASHRAE : Method of Testing General Ventilation Air-Cleaning Devices for Reduction Efficiency by Particle Size The performance of a fi lter, particularly an electret fi lter, is dependent on many factors, related to both design and environment. The in-use effi ciency performance for an electret will vary from that in which there is little reduction in the effective charge prior to the mechanical effi ciency increase to that in which the electret reduction is more signifi cant. The challenge is to effectively quantify the minimum in-use performance in a laboratory protocol knowing that performance will be better in many environments. The American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) has developed such an HVAC fi lter test standard, to provide a robust basis to compare fi lters by predicting a uniform level of known performance under operating conditions with reasonable certainty. When this protocol is used a Minimum Effi ciency Reporting Value is used to characterize the fractional effi ciency from 0.3 to 10 microns and is referred to as MERV. When originally adopted in 1999 the organization clearly recognized that the initial conditioning step of the dust-loading procedure described in this standard may affect the effi ciency of the fi lter but not as much as would be observed in actual service. Therefore, the minimum effi ciency observed during testing may be higher than that achieved during actual use. To address this important shortcoming in the standard an improved fi lter conditioning protocol was adopted that more nearly represents the minimum effi ciency points in actual real-world use. This improved protocol is the result of extensive laboratory and fi eld work completed over numerous years by a number of research groups and technical experts. This optional conditioning protocol is included in Standard as Appendix J. When the test in Appendix J is used, the minimum effi ciency reporting value is referred to as MERV-A. Extensive discussion of the difference between the conditioning protocol outlined in the body of the standard and that in Appendix J is provided in ASHRAE RP The fundamental difference is the size distribution and quantity of challenge particles. In the standard conditioning, the challenge dust is 72% ISO test dust (ISO fi ne), 23% powdered carbon, and 5% milled cotton linters by weight. 12 The powdered carbon (e.g., average particle size of 100 microns) and cotton linters (e.g., 4 mm screen) particle sizes are large, compared to the ISO fi ne dust. The median particle size of ISO fi ne dust is around 7 microns by volume. The median size of the particle challenge specifi ed in Appendix J is around 350 nm by volume and 35 nm by number. 3
4 ASHARE Appendix J conditioning protocol was not inherently developed to fully discharge an electret fi lter. As discussed in the ASHRAE RP-1190, it is possible to completely discharge the electret media by various means including an isopropanol dip, as in the European EN 779 standard, or exposing the fi lter to ionizing radiation such an x-ray source. 13 However, instead of adopting one of these conventional approaches, the small particle challenge protocol in Appendix J was chosen. To ensure that electrostatic mechanisms have the potential to contribute to the total effi ciency at the conditioned minimum, a maximum exposure time has been set when either (a) the effi ciency shows no more than two percentage point drop in two or more adjacent particle size ranges relative to the minimum effi ciencies ranges measured or (b) the cumulative exposure of the fi lter reaches a value estimated to be the maximum encountered in a year. Particle size effi ciency measurements are performed similarly for both conditioning protocols in that the fractional effi ciency (i.e., the capture effi ciency in 12 channels from 0.3 microns to 10 microns) is measured following a number, or sequence, of defi ned conditioning and loading intervals. A Composite Minimum Effi ciency (CME) curve is derived from the minimum effi ciency measured at any interval in each particle size channel. From this composite minimum, a MERV level is determined from a lookup table published in the standard. For the standard conditioning with ASHRAE dust the fi rst step includes a dust loading of 30g or an increase of 0.04 in. of water pressure drop across the fi lter, whichever comes fi rst. Subsequently, the increments are determined by dust-loading steps that achieve an airfl ow resistance increase of one-quarter, one-half, and three quarters of the difference between the beginning and the maximum recommended airfl ow resistance. A CME is derived and converted into a MERV value. Dust holding capacity (DHC) and mass arrestance effi ciency are also measured during this procedure. The conditioning sequence for the Appendix J protocol is much more intensive. It consists of a series of steps of exposing the fi lter to the small particle potassium chloride challenge. The conditioning sequence is concluded based on the above criteria. This is then followed by the dust loading sequence used in the standard protocol. Again, a CME is derived and converted into, in this case, a MERV-A value, along with a DHC-A. A fi nal important note is that complete discharging was found in all electret fi lters evaluated in the development of the Appendix J protocol. However, the report discusses the potential for future long life electrets. 3M has developed such a desired long life electret fi lter based on numerous innovative advances in media chemistry and structure, as well as fi lter design. 3M Commercial HVAC Filter Performance The 3M Commercial HVAC products have been designed specifi cally for building air handling environments where predictable particle capture effi ciency, low pressure drop and potential energy savings are paramount. Low fi lter pressure drop is attained through an innovative combination of fi lter materials and processes, resulting in a highly charged stable electret media. The rate of pressure drop rise during use is minimized through a composite, lofty media ensuring that particles are captured through the depth of the media, delaying, if not preventing, face loading. These two media performance attributes are maintained in the fi nal product by optimized fi lter design and precision production. 3M Commercial HVAC Filters MERV-A13 and MERV-A11 are based on advancements in blown microfi ber (BMF) media and product design. The product performance of these 3M Commercial HVAC Filter products is provided in the following table. 3M Commercial HVAC Filter Mini-Pleat Product Comparison Testing per ASHRAE MERV-A Reporting Value Air Flow Resistance Air Flow 492 fpm ( Water) Dust Holding Capacity (grams to 1.4 Water) A A
5 The graph on the following page shows the impact of the two ASHRAE conditioning protocols when applied to the 3M Commercial HVAC MERV-A13 fi lters. In addition, the effi ciency of a clean and x-ray discharged fi lter is included for reference. The curves are the average over a number of fi lters that have been tested using 3M s ASHRAE 52.2 standard test duct combined with results obtained by an external independent test organization. The fractional effi ciencies have been averaged as defi ned in 52.2 and characterized as a reporting value in the subsequent table. The fractional effi ciency of a clean fi lter is shown as the dotted blue line. This is the effi ciency that is measured on a new fi lter. This also represents the general effi ciency characteristics that should be measured on start-up in a facility. The dashed red line shows the effi ciency upon standard conditioning with ASHRAE test dust. As anticipated the effi ciency is reduced with the resulting effi ciency reporting value of MERV-14. The average initial pressure drop for the A13 fi lter is 0.39 of water and the maximum recommended pressure for the 3M Commercial HVAC Mini-Pleat fi lter line is 1.4 of water. In all fi lters tested, the minimum effi ciency was found to be at the second loading interval or ¼ of the total dust load, or after 0.64 of water. The effi ciency drop is most pronounced for the smaller particles in the E1 range. This result is anticipated as the electrostatic force is relatively greater for small particles. The effi ciency following conditioning per the Appendix J protocol is shown as the dashed green line. The effi ciency reduction more signifi cantly impacts both the E1 and E2 ranges. The average effi ciency drops for these two ranges are 28% and 8%, respectively. The conditioning time to achieve the minimum was between 7 and 13 hours. The general transient characteristic of the effi ciency reduction was that E3 attained its minimum then began to increase fi rst while E1 and E2 continued to decline. This continued until E2 attained its minimum then began to increase while E1 continued to decrease, until its minimum was attained. The last curve shown on the graph is that for an x-ray discharged clean fi lter. This shows the effi ciency in the complete absence of the electrostatic charge attribute of the media. This protocol for discharging a fi lter is not part of the 52.2 standard. Nonetheless, this is a valuable technique in quantifying the contribution to fi lter performance provided by the electrostatic charge on the media. The drop in E2 effi ciency from a clean fi lter to discharged fi lter is 17%, while that from an Appendix J conditioned to discharged fi lter is 9%. In other words, the electret charge contributes 9% to the total E2 effi ciency at the conditioned minimum. This is an important 9% from a potential energy savings standpoint. The pressure drop of a media is the result of the mechanical structure of the fi bers in the media. It is this same mechanical structure which is responsible for the mechanical only component of the particle fi ltration. It is possible to increase the mechanical fi ltration effi ciency while maintaining pressure drop but only at the expense of dust holding capacity. These three characteristics are inter-related in a fairly complex fashion. Nonetheless, a fi lter having a mechanical only E2 effi ciency of 90% would have a substantially higher initial pressure drop, and/or substantially lower dust holding capacity, than one having 81%. The minimum E2 and E3 effi ciency requirements for a MERV-A13 fi lter is 90%. There is no requirement for the E1 effi ciency range in reporting values less than MERV-A14. As can be seen in the table below, the 3M Commercial HVAC Filter MERV-A13 has been designed for a low pressure drop while meeting these minimum effi ciency requirements following conditioning per Appendix J. 5
6 100 3M TM Commercial HVAC Filter MERV-A13 Fractional Efficiency per ASHRAE at 492 fpm KCI Efficiency (%) Clean Filter Standard Conditioning Conditioning per Appendix J Clean Filter Following X-Ray Discharge 0 0 E1 E2 E Particle Size (microns) 3M Commercial HVAC Filter A13 Average Efficiencies per ASHRAE 492 fpm Particle Size Range (micron) Clean Filter Standard Filter Conditioning Conditioning per Appendix J X-Ray Discharged E1: % 84 64% 53% E2: % 97 90% 81% E3: % % 98% MERV-14 MERV-A13 For comparison, the same performance characteristics are shown below for the 3M Commercial HVAC Filter MERV-A11 below. The general behavior is very similar to that for the A13 except that the magnitude of effi ciency drop upon conditioning is more signifi cant. The E3 effi ciency drops by 3% upon conditioning per Appendix J and 13% for a completely discharged fi lter, whereas E2 drops by 23% and 40%, respectively. The electret component remaining at the conditioned minimum is 17% for E2 and 10% for E M TM Commercial HVAC Filter MERV-A11 Fractional Efficiency per ASHRAE at 492 fpm KCI Efficiency (%) Clean Filter Standard Conditioning Conditioning per Appendix J Clean Filter Following X-Ray Discharge 0 0 E1 E2 E Particle Size (microns) From this detailed data analysis it is clear that 3M has developed a long life electret fi lter as validated by the rigorous conditioning protocol defi ned in ASHRAE Appendix J. 3M Commercial HVAC Filter A11 Average Efficiencies per ASHRAE 492 fpm Particle Size Range (micron) Clean Filter Standard Filter Conditioning Conditioning per Appendix J X-Ray Discharged E1: % 67% 33% 20% E2: % 97% 68% 51% E3: % 98% 94% 84% MERV-13 MERV-A11 6
7 1 Air-Conditioning and Refrigeration Technology Institute, Report:ARTI-21CR/ US Green Building Council (USGBC) LEED v.3 ( 3 EPA Indoor Environments Division ( 4 Avery, R.H., Air Filtration: Resistances, Energy and Service Life, Heating, Piping, Air-Conditioning,. December Also sited in NAFA Guide to Air Filtration. NAFA Certifi cation Committee, t. Washington, DC: NAFA, See for example, Energy Consumption Characteristics of Commercial Building HVAC Systems Volume II: Thermal Distribution, Auxiliary Equipment, and Ventilation ( nal_report. pdf). 6, 7 ASHRAE Report: Investigation of Mechanism and Operating Environments that Impact the Filtration Effi ciency of Charged Air Filtration Media, 1189-TRP. 8 See for example, L.I. Johnson, et. al, Effi ciency of Degraded Electret Filters: Part I and Part II, Journal of the International Society for Respiratory Protection, Vol. 20 (2003), pg ; A. Wang and KC Hofacre, Assessment of Advanced Building Air Filtration Systems, EPA/600/R-08/032 (2008), 9 Raynor, P.C. and Chae, S.J., The Long-Term Performance of Electrically Charged Filters in a Ventilation System, Journal of Occupational and Environmental Hygiene, 1: ANSI/ASHRAE Standard , Method of Testing General Ventilation Air-Cleaning Devices for Reduction Effi ciency by Particle Size. 11 Hanley, J.T. and Owen, M.K., Develop a New Loading Dust and Dust Loading Procedures for he ASHRAE Filter Test Standards 52.1 and 52.2 Final Report, ASHRAE Project No PR, August See for example commercially available ASHRAE Test Dust from Powder Technology Inc., Ewing Avenue South, Burnsville, MN ( 13 3M s preferred method for discharging the charge on an electret fi lter is x-ray exposure. Rousseau, A.D., et. al., Effects of Ionizing Radiation on the Performance of Advanced Electret Filter Media, presented at the 7th International Symposium on Protection Against Chemical and Biological Warfare Agents, Stockholm, Sweden, June (2001). 7
8 IMPORTANT NOTICE: The information in this literature is based on tests 3M Purifi cation Inc. believes are reliable. It is not and should not be relied on as a product or technical specifi cation. We do not guarantee the accuracy of this information. You are responsible for determining whether products described in this literature are fi t for a particular purpose and suitable for your application. Because there are many factors within your knowledge and control that might affect the use and performance of these products, you must evaluate these products to determine whether they are fi t for a particular purpose, are suitable for your application, and meet your performance expectations. 3M PURIFI- CATION INC. IS NOT LIABLE FOR ANY LOSS OR DAMAGES, WHETHER DIRECT, INDIRECT, SPECIAL, INCIDENTAL, OR CONSEQUENTIAL ARISING OUT OF THE USE OF OR INABILITY TO USE ANY OF THESE PRODUCTS. CAUTION: USED FILTERS MAY CONTAIN CONTAMINANTS FROM OPERATION OF THE HVAC SYSTEM. FOR PROPER HANDLYING OF USED FILTERS, CONSULT APPLICABLE HEALTH AND SAFETY STANDARDS OR CONTACT AN INDUSTRIAL HYGIENIST. TO REDUCE RISK OF ILLNESS OR INJURY, ALWAYS USE APPROPRIATE RESPIRATORY PROTECTION AND PROTECTIVE CLOTHING WHEN REMOVING OR HANDLING USED FILTERS. DISPOSE OF USED FILTERS ONLY IN ACCORDANCE WITH FEDERAL, STATE AND LOCAL LAWS AND REGULATIONS. IMPORTANT USE RESTRICTIONS: DO NOT EXPOSE THIS FILTER DIRECTLY TO UV RADIATION FROM A UV PURIFICATION SYSTEM. EXCESSIVE UV EXPOSURE MAY LEAD TO A REDUCTION IN THE MECHANICAL INTEGRITY AND PERFORMANCE OF THE FILTER. THIS FILTER MUST NOT BE USED FOR THE FOLLOWING UNATHORIZED USES: A) ASBESTOS, LEAD OR MOLD REMEDIATION; B) BIOTERRORISM PROTECTION; C) APPLICATIONS IN BUILDING THAT REQUIRE OR ARE UNDERGOING AIR HANDLING SYSTEM REMEDIATION OF HAZARDOUS SUBSTANCES; OR D) PROTECTIVE ENVIRONMENTS PER AIA GUIDELINES. LIMITED WARRANTY: 3M Purifi cation Inc. warrants that these products will be free of defects in material and manufacture when shipped. This is the exclusive remedy for any defects in these products. This warranty does not apply to damage or defects resulting from improper use, storage or maintenance of these products. LIMITATION OF LIABILITY: User must determine whether these products are fi t for a particular purpose, suitable for user s application and meet user s performance expectations. 3M Purifi cation Inc. IS NOT LIABLE FOR ANY LOSS OR DAMAGE, WHETHER DIRECT, INDIRECT, SPECIAL, INCIDENTAL OR CONSEQUENTIAL, ARISING OUT OF THE SALE, USE OF, OR INABILITY TO USE ANY OF THESE PRODUCTS REGARDLESS OF LEGAL THEORY. Your Local Distributor: 3M Purification Inc. 400 Research Parkway Meriden, CT U.S.A. (800) (651) cation.com/airfi lters 3M is a trademark of 3M Company. LEED is a trademark of the U.S. Green Building Council M Company. All rights reserved. Please recycle. Printed in U.S.A REV 0214
3M Purification Inc. 3M Air Management Products for Your Commercial HVAC Needs. Create. Air. Confidence
3M Purification Inc. 3M Air Management s for Your Commercial HVAC Needs Create an Air of Confidence Pursuing Innovation 3M Company has long encouraged employees to pursue ideas and concepts that might,
More informationTotal Cost of Ownership Tool from 3M
Commercial HVAC Filters Total Cost of Ownership Tool from 3M Restricted budgets challenge facility owners and operators to seek solutions that help save energy and reduce operating costs, while maintaining
More informationA. Air-Conditioning and Refrigeration Institute: 1. ARI 850 - Commercial and Industrial Air Filter Equipment.
SECTION 23 40 00 - HVAC AIR CLEANING DEVICES PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Activated carbon filters. 2. Extended surface rigid air filter with synthetic media. 3. Disposable panel
More informationRobert McCabe Director, Health Care Solutions HTS Chicago. Improved Air Quality and Energy Efficiency through Air Handler Filtration System Upgrade
Robert McCabe Director, Health Care Solutions HTS Chicago Improved Air Quality and Energy Efficiency through Air Handler Filtration System Upgrade Biography Robert McCabe has been involved in commercial
More informationQuick wins for energy savings in buildings
Quick wins for energy savings in buildings Choosing low energy air filters for both optimized energy performance and indoor air quality Executive Summary HVAC systems heat, cool and clean the air within
More informationG U I D E L CERTIFICATION EDUCATION TRAINING. Procurement Guideline. National Air Filtration Association Recommended Practice
G U National Air Filtration Association Recommended Practice I D E L I N E Procurement Guideline TRAINING EDUCATION CERTIFICATION HVAC Air Filter Purchasing Specification Guideline 1.0 Purpose To provide
More informationOwner s Manual Model 5000 Safety, Operating and Maintenance Instructions
Electronic Air Cleaner 90-1147 Owner s Manual Model 5000 Safety, Operating and Maintenance Instructions READ AND SAVE THIS MANUAL WARNING 120 Volts may cause serious injury from electrical shock. Disconnect
More informationCamfil Farr Technical Services Bulletin
Camfil Farr Technical Services Bulletin ASHRAE Testing for HVAC Air Filtration A Review of Standards 52.1-1992 & 52.2-1999 The American Society of Heating, Refrigeration, and Air Conditioning Engineers
More informationHow to Choose An Air Filter For Your Boat
How to Choose An Air Filter For Your Boat That Will Reduce Diesel Fumes, Smoke and Odors L-2395 Rev. 1-07-06 Air Filtration Fundamentals Air filters are devices that capture dust and other contaminants
More informationANSI/ASHRAE 52.2-2007
The Updated Air Filter Standard ANSI/ASHRAE 52.2-2007 Koch Filter Corporation...Durable. Reliable. Versatile. Bulletin No. K-ASH52.2-09 In recent years, the air filter industry has changed important portions
More informationThere are several types of air cleaning devices available, each designed to remove certain types of pollutants.
Please Note: EPA neither certifies nor recommends particular brands of home air cleaning devices. While some home air cleaning devices may be useful in some circumstances, EPA makes no broad endorsement
More informationCUNO TM Series NB Bags for Liquid Filtration
CUNO TM Series NB Bags for Liquid Filtration Customers have relied on CUNO to provide quality filtration solutions for the most demanding applications. Leveraging 3M innovation, CUNO has applied this expertise
More informationDATA CENTERS. Protect Your Best in Class Technology With Ours CLEAN AIR SOLUTIONS
DATA CENTERS Protect Your Best in Class Technology With Ours CLEAN AIR SOLUTIONS COSTLY FAN ENERGY REDUCED BY CAMFIL PREMIUM PRODUCTS = COST SAVINGS Power Usage Effectiveness (PUE) is an important metric
More informationHIH-4000 Series Humidity Sensors
HIH-4000 Series Humidity Sensors DESCRIPTION The HIH-4000 Series Humidity Sensors are designed specifically for high volume OEM (Original Equipment Manufacturer) users. Direct input to a controller or
More informationControlling Condensation On CWP Insulation BY ED LIGHT, MEMBER ASHRAE; JAMES BAILEY, P.E., MEMBER ASHRAE; AND ROGER GAY
This article was published in ASHRAE Journal, Decemeber 2014. Copyright 2014 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without
More informationIEQ-15 Air Distribution System
AIM OF CREDIT To encourage and recognise the design and maintenance of air distribution systems that minimise the risk of particulate and microbial contamination to the internal air supply. CREDIT CRITERIA
More informationWARNING: FAILURE TO FOLLOW THESE RULES MAY RESULT IN SERIOUS PERSONAL INJURY CAUTION: INSTALLATION LOCATION:
Revision Level: 01 Revision Date: 07/07/2011 Please read all instructions carefully to help ensure a correct and SAFE installation of your Second Wind Ultraviolet Germicidal Air Purifier. Failure to do
More informationSpecification. Indoor Air Quality Management
GREENGUARD Environmental Institute 2211 Newmarket Parkway, Suite 110 Marietta, GA 30067 1.800.427.9681 Specification Indoor Air Quality Management This Master Specification section is intended for use
More informationElectrostatic or Electronic: Know the Facts By Robert P. Scaringe, P.E., Ph.D., ---President of Mainstream Engineering
Electrostatic or Electronic: Know the Facts By Robert P. Scaringe, P.E., Ph.D., ---President of Mainstream Engineering HVAC system air filter upgrades are one way contractors can simultaneously increase
More informationAsbestos in the Workplace: A Guide to Removal of Friable Asbestos Containing Material
Asbestos in the Workplace: A Guide to Removal of Friable Asbestos Containing Material Revised November 21, 2013 Application Code of Practice Where asbestos is present or believed to be present in a workplace
More informationLaminar Flow Cabinets
Laminar Flow Cabinets The World s Most Practical Selection of Benchtop Laminar Flow Cabinets. 24 36 48 Simple, Effective Protection for Samples and Work Processes, Uncompromised Performance, Economical
More informationASHRAE ADDENDA. Method of Testing General Ventilation Air-Cleaning Devices for Removal Efficiency by Particle Size
ANSI/ASHRAE Addendum b to ANSI/ASHRAE Standard 52.2-2007 ASHRAE ADDENDA 2008 SUPPLEMENT Method of Testing General Ventilation Air-Cleaning Devices for Removal Efficiency by Particle Size Approved by the
More informationSCIENCE. SERVICE. SOLUTIONS. ROOF GARDEN. CCW Green Roof Systems By Columbia Green Technologies. 800.527.7092 www.carlisleccw.com
SCIENCE. SERVICE. SOLUTIONS. ROOF GARDEN CCW Green Roof Systems By Columbia Green Technologies 800.527.7092 www.carlisleccw.com ROOF GARDEN CCW Green Roof Systems By Columbia Green Technologies Carlisle
More informationMC² Market & Competitive Convergence Air Filters: New Facilities, New Standard
MC² Market & Competitive Convergence Air Filters: New Facilities, New Standard Advances in testing procedures, coupled with greater pressure for better IAQ, leads to a new standard By Ron Wilkinson, P.E.
More informationDouble Coated Urethane Foam Tapes
3 Double Coated Urethane Foam Tapes 4004 4008 4016 4026 4032 4052 4056 4085 Technical Data April, 2009 Product Description 3M Double Coated Urethane Foam Tapes are conformable foams that offer high shear
More informationDEEPSEALSM SERVICE SOLUTIONS
DEEP WATER CHEMICAL SOLUTIONS DEEPSEALSM SERVICE SOLUTIONS (DEEP SEA ENGINEERING ASSURANCE LEADERSHIP) Solving challenges. Deepwater Solutions from Multi-Chem ABOUT HALLIBURTON Founded in 1919, Halliburton
More informationUser s Guide. Oreck Air Purifier with HEPA Filtration. Important! Read this manual carefully, and keep for future reference.
User s Guide Oreck Air Purifier with HEPA Filtration Important! Read this manual carefully, and keep for future reference. Enjoy Congratulations on your purchase of the Oreck Air Purifier with HEPA Filtration.
More informationWhitepaper Cross-Contamination
Whitepaper Cross-Contamination Protection in HVAC I N D U S T R Y I N S I G H T S Norman A. Goldschmidt September 30, 2011 Principal, Engineering www.geieng.com I N D U S T R Y I N S I G H T S Genesis
More informationLEED GOLD CERTIFIED OFFICE DESIGN AND CONSTRUCTION
LEED GOLD CERTIFIED OFFICE DESIGN AND CONSTRUCTION Setting a Precedent for Sustainable Interior Commercial Design FLEXIBLE INNOVATIVE CREATIVE R E S P O N S I B L E We transformed our lower Manhattan office
More informationASTHMA REGIONAL COUNCIL
ASTHMA REGIONAL COUNCIL WHAT S THAT SMELL? Simple Steps to Tackle School Air Problems ARC is a coalition of governmental and community agencies dedicated to addressing the environmental contributors to
More informationINDOOR AIR QUALITY ASSESSMENT MOLD INVESTIGATION. Department Of Children and Family 810 Memorial Drive Cambridge, Massachusetts
INDOOR AIR QUALITY ASSESSMENT MOLD INVESTIGATION Department Of Children and Family 810 Memorial Drive Cambridge, Massachusetts Prepared by: Massachusetts Department of Public Health Bureau of Environmental
More information3 Thermal Transfer Acrylate Label Material 3921
3 Thermal Transfer Acrylate Label Material Technical Data April, 2008 Product Description 3M Thermal Transfer Acrylate Label Material consists of a non-topcoated acrylate facestock designed for thermal
More informationDevelopment of Performance Data for Common Building Air Cleaning Devices FINAL REPORT
United States Environmental Protection Agency SC EN E EPA/600/R-08/013 December 2008 www.epa.gov/ord Development of Performance Data for Common Building Air Cleaning Devices FINAL REPORT Office of Research
More informationOur Environmental Protection Plan RECYCLING CAPABILITIES AND ENVIRONMENTAL ACCOMPLISHMENTS
Our Environmental Protection Plan RECYCLING CAPABILITIES AND ENVIRONMENTAL ACCOMPLISHMENTS WHO WE ARE Since day one, East Penn has made safe recycling an everyday practice. East Penn opened its doors as
More informationOil Analysis. It is important that the sampling be done in the following manner: 1.
Oil Analysis Introduction Oil analysis was originally used by the military and the railroad as a preventative maintenance program. It has expanded today to the fi eld of study called Tribology. Oil analysis
More informationEssam E. Khalil khalile1@asme.org
AIR-CONDITIONING SYSTEMS DEVELOPMENTS IN HOSPITALS: COMFORT, AIR QUALITY, AND ENERGY UTILIZATION Essam E. Khalil khalile1@asme.org PROFESSOR OF MECHANICAL ENGINEERING, CAIRO UNIVERSITY, EGYPT Abstract
More informationSafety Data Sheet SOMAmer Reagent
SECTION 1: Identification Safety Data Sheet SOMAmer Reagent 1.1 Product identifier Product name SOMAmer Reagent (aptamer) 1.2 Supplier s details Name Address Email SomaLogic, Inc. 2945 Wilderness Place
More informationGuidelines for Mold Remediation (Removal)
Guidelines for Mold Remediation (Removal) Indoor mold growth, water damage, or musty odors should be addressed quickly. Removing mold growth and correcting the underlying cause of water accumulation can
More informationClimate Comfort and HVAC on Passenger Rolling Stock
Standard Climate Comfort and HVAC on Passenger Rolling Stock Important Warning This document is one of a set of standards developed solely and specifically for use on the rail network owned or managed
More informationImproving Indoor Air Quality on a Tight Budget
Improving Indoor Air Quality on a Tight Budget The HVAC system serving our shelter was outdated, extremely inefficient, and constantly malfunctioning, so it was time for new equipment. I researched information
More informationWhat is LEED? Why pursue LEED accreditation? How does LEED accomplish these goals? Sustainable sites Water efficiency Energy and Atmosphere
Green AAON for What is LEED? Sustainability and green have recently become terms used within the building industry (and others) to refer to a construction project that has low environmental impact, or
More informationScotchgard Multi-Layer Protective Film 1004
Scotchgard Multi-Layer Protective Film 1004 3 Technical Bulletin September, 2008 Scotchgard Multi-Layer Protective Film 1004 Application Kit (3M Part No. 70-0710-4666-1) includes: (clockwise) Heavy Duty
More informationIs This Combustible Dust?
1 of 5 8/6/2012 1:16 PM Is This Combustible Dust? Thursday, 19 July 2012 Dust explosions and fires are serious hazards in the process industries that have lead to loss of life, injury to plant personnel
More informationKEY ELEMENTS IN PREVENTING AND MITIGATING MOLD CLAIMS
KEY ELEMENTS IN PREVENTING AND MITIGATING MOLD CLAIMS By Jerome E. Spear, CSP, CIH Effective January 1, 2005, consultants who prepare mold management plans for buildings located in Texas must be licensed
More informationAir Filtration for. Indoor Firing Ranges
Air Filtration for Indoor Firing Ranges References, credits Lead Exposure at an Indoor Firing Range - NIOSH Lead Exposure & Design Considerations for Indoor Firing RAnges - NIOSH Standards - 29 CFR - OSHA
More informationG u i d e l. Schools CERTIFICATION EDUCATION TRAINING. Recommended Practice
G u i d e l i n e s Schools Recommended Practice TRAINING EDUCATION CERTIFICATION Publication Information Why NAFA Guidelines? The National Air Filtration Association (NAFA) provides Best Practice Guidelines
More informationUSAGE AND PUBLIC REPORTING GUIDELINES FOR THE GREEN GRID S INFRASTRUCTURE METRICS (PUE/DCIE)
WHITE PAPER #22 USAGE AND PUBLIC REPORTING GUIDELINES FOR THE GREEN GRID S INFRASTRUCTURE METRICS (PUE/DCIE) EDITORS: JON HAAS, INTEL JAMIE FROEDGE, EMERSON NETWORK POWER CONTRIBUTORS: JOHN PFLUEGER, DELL
More informationAsbestos Awareness Training
Asbestos Awareness Training Environmental Health & Safety Iowa State University January 1996 1 PREFACE This Asbestos Awareness Training Handout has been prepared by staff members of the Environmental Health
More informationToward Better Buildings. Resources for Managing IAQ during Construction
Toward Better Buildings Resources for Managing IAQ during Construction 26 BY DONALD WEEKES, WANE A. BAKER, AND JACK SPRINGSTON EEPA estimates that, on a yearly basis, many Americans spend an average of
More informationevo + HIGH-WALL DUCTLESS AIR CONDITIONING & HEATING SYSTEM OWNER S MANUAL Models: GWH09AB-D3DNA2D GWH18AC-D3DNA2D GWH24AC-D3DNA2D
evo + HIGH-WALL DUCTLESS AIR CONDITIONING & HEATING SYSTEM OWNER S MANUAL Models: GWC09AB-D3DNA2D GWC12AB-D3DNA2D GWC18AC-D3DNA2D GWC24AC-D3DNA2D GWH09AB-D3DNA2D GWH12AB-D3DNA2D GWH18AC-D3DNA2D GWH24AC-D3DNA2D
More informationFederation of European Heating, Ventilation and Air-conditioning Associations
Federation of European Heating, Ventilation and Air-conditioning Associations Address: Rue Washington 40 1050 Brussels Belgium www.rehva.eu info@rehva.eu Tel: +32 2 514 11 71 Fax: +32 2 512 90 62 Use of
More informationHow To Use The Visifault Visual Fault Locator
VisiFault Visual Fault Locator Instruction Sheet The VisiFault Visual Fault Locator (VFL) is a visible light source that helps you trace optical fibers, check fiber continuity, and find faults such as
More informationUV100A Ultraviolet Air Treatment System
UV100A Ultraviolet Air Treatment System INSTALLATION INSTRUCTIONS APPLICATION When installed in forced air heating and cooling systems, the UV100A Ultraviolet Air Treatment System kills airborne microorganism
More informationLenntech ZETA PLUS CP & SP SERIES GRADE CHOICE. Pharmaceutical Applications
Lenntech info@lenntech.com Tel. +31-15-610-900 www.lenntech.com Fax. +31-15-616-89 ZETA PLUS CP & SP SERIES Zeta Plus CP & SP pharmaceutical grade depth fi lter media is made from inorganic fi lter aids,
More informationSC Series: MIS Chip Capacitors
DATA SHEET SC Series: MIS Chip Capacitors Applications Systems requiring DC blocking or RF bypassing Fixed capacitance tuning element in filters, oscillators, and matching networks Features Readily available
More information3. Asbestos Abatement Course 1. Introduction and Background to Asbestos Abatement. 4. Health Effects and Medical Surveillance
St. Louis Brownfields Worker Training Program St. Louis Community College Harrison Education Center and St. Louis University Environmental Education & Training 1. Introduction to Environmental Technologies
More informationFILTRATION SOLUTIONS PhARmAceUTIcAL manufacturing FILTRATION SPecIALISTS
FILTRATION SOLUTIONS Pharmaceutical Manufacturing filtration specialists Delivering quality filtration products As one of Europe s leading manufacturers of process filters, Amazon Filters is able to offer
More informationIndoor Air Quality Issues for Hotels
Indoor Air Quality Issues for Hotels Chai chen Chao DEA 670 Spring, 2000 Thermal Control Relative Humidity Winter Temperature Summer Temperature 30% 68.5 F - 76.0 F 74.0 F - 80.0 F 40% 68.5 F - 75.5 F
More informationThe Impact of Fouling on the Performance of Filter- Evaporator Combinations
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2004 The Impact of Fouling on the Performance of Filter- Evaporator Combinations
More informationOVERVIEW OF STANDARD 7E & STANDARD 20
Standard for Thermal Transport Packaging Used in Parcel Delivery System Shipment 7E 2 010 ISTA 7E Usage Modes VERSION DATE OCTOBER 2010 Initial Release ISTA, Distributing Confidence, Worldwide ISTA 7-Series
More information3M Scotchcast Electrical Resin 251 Two-Part, Oven-Curing, Class F, Rigid, Filled, Epoxy Liquid Resin
3M Scotchcast Electrical Resin 251 Two-Part, Oven-Curing, Class F, Rigid, Filled, Epoxy Liquid Resin Data Sheet April 2013 Description 3M Scotchcast Electrical Resin 251 is a medium viscosity, rigid, Class
More informationPEOSH. Indoor Air Quality Training for Asthma-Friendly Schools Part I PEOSH Indoor Air Quality Standard Overview. Eric Weren, MSIH
PEOSH Indoor Air Quality Training for Asthma-Friendly Schools Part I PEOSH Indoor Air Quality Standard Overview Eric Weren, MSIH Public Employees Occupational Safety and Health Unit IAQ Asthma-Friendly
More informationTAMPA ELECTRIC COMPANY ENERGY SUPPLY ASBESTOS AWARENESS PROGRAM
ASBESTOS AWARENESS PROGRAM TABLE OF CONTENTS TITLE PAGE # PURPOSE / INTRODUCTION 1 RESPONSIBILITY 2 EMPLOYEE TRAINING AND DOCUMENTATION 2-4 MEDICAL SURVEILLANCE 4 UNPLANNED DISTRUBANCE OF ASBESTOS CONTAINING
More informationIEQ Management Plan. Denver Museum of Nature and Science ECF Addition
IEQ Management Plan GH Phipps Construction Companies 5995 Greenwood Plaza Blvd., Suite 100 Greenwood Village, Colorado 80111-4710 303.571.5377 PHONE www.ghphipps.com Denver Museum of Nature and Science
More informationRegulatory Compliance Needs Process Management
White Paper Regulatory Compliance Needs Process Management A Pathfinder Technology Solutions Whitepaper October 22, 2004-1 - Introduction All businesses need to comply with government regulations, regardless
More informationCHAPTER 4 VENTILATION
CHAPTER 4 VENTILATION SECTION 401 GENERAL 401.1 Scope. This chapter, in conjunction with the building code, shall govern the ventilation of spaces within a building intended to be occupied. Mechanical
More informationCamfil. Technical Services Bulletin Tools for Schools Filtration for Improved Indoor Air Quality
Camfil Technical Services Bulletin Tools for Schools Filtration for Improved Indoor Air Quality Most non-practitioners notice the HVAC system when it is too hot, or too cold, or in other ways not working
More informationMaterial Safety Data Sheet
1 MSDS1223 Material Safety Data Sheet MSDS1223 06-MAR-2003 "ELVACITE" 2042A ACRYLIC RESIN CHEMICAL PRODUCT/COMPANY IDENTIFICATION "ELVACITE" IS A REGISTERED TRADEMARK OF LUCITE INTERNATIONAL INC. Material
More information3 Scotch-Seal TM. Tamper Proof Sealant 1252. Technical Data Issue No. 5
3 Scotch-Seal TM Technical Data Issue No. 5 Advantages 3M Scotch-Seal is a one-part, fast drying, antitamper sealer. Self-extinguishing. It can be applied over adjustable or removable parts to indicate
More informationATTACHMENT E. FORM B: DEFENDANT INTERROGATORIES: To be answered by all defendant and
FORM B: DEFENDANT INTERROGATORIES: To be answered by all defendant and third party defendant miners, manufacturers, suppliers and installers of asbestos or asbestos containing products in all cases except
More informationNADCA GENERAL SPECIFICATIONS FOR THE CLEANING OF COMMERCIAL HEATING, VENTILATING AND AIR CONDITIONING SYSTEMS
NADCA GENERAL SPECIFICATIONS FOR THE CLEANING OF COMMERCIAL HEATING, VENTILATING AND AIR CONDITIONING SYSTEMS National Air Duct Cleaners Association 1518 K Street, N.W. Suite 503 Washington, DC 20005 (202)
More informationPERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE
PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE APPLICATION NOTE TI-138 TSI s IAQ-CALC TM Indoor Air Quality Meter and TH-CALC TM Thermohygrometer calculate Percent Outdoor Air (%OA). In order to take
More information3M Ionic Liquid Antistat FC-4400
Technical Data September 14 3M Ionic Liquid Antistat FC-40 Introduction 3M Ionic Liquid Antistat FC-40 is a high purity antistatic additive compatible with a variety of high performance polymer systems,
More informationMATERIAL SAFETY DATA SHEET
MATERIAL SAFETY DATA SHEET 1. PRODUCT IDENTIFICATION 1.1 Product Name: Cyanogen Bromide Fibrinogen Fragments 1.2 Product REF: 459 1.3 Configuration: One (1) vial, 5.0 mg, lyophilized 1.4 Use of Product:
More informationEVAPCO ENGINEERING. Commercial HVAC. District Energy. Industrial Process. Industrial Refrigeration. Power
Since its founding in 1976, EVAPCO, Incorporated has become an industry leader in the engineering and manufacturing of quality heat transfer products around the world. EVAPCO s mission is to provide first
More informationVentilation Standard For Health Care Facilities
The following article was published in ASHRAE Journal, October 2008. Copyright 2008 American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. It is presented for educational purposes
More informationASBESTOS MANAGEMENT PROGRAM
ASBESTOS MANAGEMENT PROGRAM Prepared By: Triumvirate Environmental Program Approval Developed: August 2011 Updated: June 2015 Associate Vice President of Public Safety & Administrative Services Date Associate
More informationINSURANCE AND POLLUTION PREVENTION
INSURANCE AND POLLUTION PREVENTION Publication #99-439 Environmental Insurance What is environmental insurance and what does it insure against? Environmental insurance insures against potential damages
More information3M Dual Lock Reclosable Fastener
3 Dual Lock Reclosable Fasteners SJ3550CF (Type 250) SJ3551CF(Type 400) SJ3552CF(Type 170) Dual Lock Reclosable Fastener Black with a clear acrylic adhesive Product Information February, 2007 Product Description
More informationInventory of Performance Monitoring Tools for Subsurface Monitoring of Radionuclide Contamination
Inventory of Performance Monitoring Tools for Subsurface Monitoring of Radionuclide Contamination H. Keith Moo-Young, Professor, Villanova University Ronald Wilhelm, Senior Scientist, U.S. EPA, Office
More informationCauses and Prevention of Symptom Complaints in Office Buildings: Distilling the Experience of Indoor Environment Quality Investigators
Causes and Prevention of Symptom Complaints in Office Buildings: Distilling the Experience of Indoor Environment Quality Investigators Mark J. Mendell, Richard C. Diamond, William J. Fisk Environmental
More informationGet The Mold Out: Mold Clean-Up Guidance for Residences. Introduction
Connec cut Department of Public Health Environmental & Occupa onal Health Assessment Program Environmental Health Sec on 410 Capitol Avenue, MS # 11EOH, PO Box 340308 Har ord, CT 06134-0308 Telephone:
More informationAerosol Fire Suppression. Your Choice for Special Hazard Fire Protection
Aerosol Fire Suppression Your Choice for Special Hazard Fire Protection Traditional Special Hazard Fire Protection Centers Around Two Technologies Water deluge and chemical agent fixed systems protect
More informationRiMatrix S Make easy.
RiMatrix S Make easy. 2 RiMatrix S Rittal The System. The whole is more than the sum of its parts. The same is true of Rittal The System. With this in mind, we have bundled our innovative enclosure, power
More informationSENTRY AIR SYSTEMS, INC. PHARMACEUTICAL COMPOUNDING CONTAINMENT SYSTEMS SIMPLE SOLUTIONS FOR CLEANER AIR. www.sentryair.com 1.800.799.
SENTRY AIR SYSTEMS, INC. PHARMACEUTICAL COMPOUNDING CONTAINMENT SYSTEMS SIMPLE SOLUTIONS FOR CLEANER AIR 1.800.799.4609 www.sentryair.com Pharmaceutical Compounding Safety Solutions Sentry Air Systems
More informationBest Practices for Handling Nanomaterials in Laboratories
Best Practices for Handling Nanomaterials in Laboratories Much of the toxicology of nanomaterials is currently uncertain or unknown. Some nanosized particles are more toxic than their respective micron
More informationPVC ROOFING SYSTEMS BUILDING SOLUTIONS A SINGLE SOURCE FOR SINGLE-PLY ROOFING
V E R S I C O R O O F I N G S Y S T E M S PVC ROOFING SYSTEMS BUILDING SOLUTIONS A SINGLE SOURCE FOR SINGLE-PLY ROOFING Versico, PO Box 1289, Carlisle, PA 17013 Tel: 800.992.7663 Fax: 717.960.4036 Web:
More informationENGINEERING SPECIFICATION. Engineering Specification SAPPHIRE 42 Bar
Engineering Specification SAPPHIRE 42 Bar PART 1 GENERAL 1.1 DESCRIPTION OF WORK This specification outlines the requirements for a "Total Flood" SAPPHIRE Clean Agent Fire Suppression System. The work
More informationSAFETY DATA SHEET EVO-STIK PLUMBERS MAIT
Revision Date November 2012 Revision 9 1 / 5 SAFETY DATA SHEET According to Regulation (EC) No 1907/2006 SECTION 1: IDENTIFICATION OF THE SUBSTANCE/MIXTURE AND OF THE COMPANY/UNDERTAKING 1.1. Product identifier
More informationCLA4607-085LF: Surface Mount Limiter Diode
DATA SHEET CLA4607-085LF: Surface Mount Limiter Diode Applications Low-loss, high-power limiters Receiver protectors Anode (Pin 1) Anode (Pin 3) Features Low thermal resistance: 55 C/W Typical threshold
More information3 Destructible Vinyl Label Material 7613T / 7930T
3 Destructible Vinyl Label Material Technical Data September, 2010 Product Description 3M Destructible Vinyl Label Materials 7613T and 7930T are consistent, smooth, topcoated films designed to exhibit
More informationStaff shall ensure that airflow is not obstructed by the blocking of ventilators with posters, furniture, books, or other obstacles.
1 Environmental Safety AR 3514 The Superintendent may designate and train one or more employees to oversee and coordinate the district's environmental safety program(s). The responsibilities of the coordinator(s)
More informationMineral Insulated Cable A cable for today and tomorrow!
Mineral Insulated Cable A cable for today and tomorrow! Bill Davis Technical and Business Development Director If MIC had never been introduced, the industry would be actively pursuing the development
More informationFiltration and Air-Cleaning Systems to Protect Building Environments from Airborne Chemical, Biological, or Radiological Attacks
Guidance for Filtration and Air-Cleaning Systems to Protect Building Environments from Airborne Chemical, Biological, or Radiological Attacks Department of Health and Human Services Centers for Disease
More informationMEASURING THE EFFICACY OF MOLD REMEDIATION ON CONTAMINATED DUCTWORK
MEASURING THE EFFICACY OF MOLD REMEDIATION ON CONTAMINATED DUCTWORK JD Krause 1,2* and YY Hammad 1 1 College of Public Health, University of South Florida, Tampa, FL, USA 2 Indoor Air Solutions, Tampa,
More informationAPPENDIX B. EPA s Investigating, Evaluating, and Remediating Moisture and Mold Problems (see EPA website for complete details)
APPENDIX B. EPA s Investigating, Evaluating, and Remediating Moisture and Mold Problems (see EPA website for complete details) Table 1: Water Damage - Cleanup and Mold Prevention Table 1 presents strategies
More informationHow To Clean A Data Center
DATA CENTER MAINTENANCE IT OPERATIONS Why, What & When To Clean The Data Center Author: Bill Montgomery Date: November 2010 Introduction: The service of data center cleaning has been a major focus of late
More informationIWU PHYSICAL PLANT SAFETY PROGRAM. Toxic and Hazardous Substances, Title 29 Code of Federal Regulations (CFR) Part 1910.1001, Subpart Z Asbestos
STANDARDS Toxic and Hazardous Substances, Title 29 Code of Federal Regulations (CFR) Part 1910.1001, Subpart Z Asbestos 1. INTRODUCTION IWU has a responsibility to provide a safe environment for students,
More informationIndustrial Adhesives and Tapes Division 3M Center Building 225-3S-06 St. Paul, MN 55144-1000 1-800-362-3550 www.3m.com/vhb
Limited Product Warranty: 3M warrants for 24 months from the date of manufacture, 3M VHB tapes will be free of defects in material and manufacture. 3M MAKES NO OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING
More informationRev. No. 0 January 5, 2009
ENERGY & ENVIRONMENTAL ENERGY ISSUES COMMITTEE 415 Main Building Telephone (574) 631-6666 Notre Dame, Indiana Facsimile (574) 631-5883 46556 USA Energy Conservation Plan For HVAC Systems Rev. No. 0 January
More information