CIP-003-6 R2 BES Assets Containing Low Impact BCS. Lisa Wood, CISA, CBRA, CBRM Compliance Auditor Cyber Security



Similar documents
Notable Changes to NERC Reliability Standard CIP-005-5

Cyber Security Standards: Version 5 Revisions. Security Reliability Program 2015

Summary of CIP Version 5 Standards

North American Electric Reliability Corporation: Critical Infrastructure Protection, Version 5 (NERC-CIP V5)

Cyber Security Compliance (NERC CIP V5)

Cyber Security Standards Update: Version 5

CIP Cyber Security Security Management Controls

E-Commerce Security Perimeter (ESP) Identification and Access Control Process

Completed. Document Name. NERC CIP Requirements CIP-002 Critical Cyber Asset Identification R1 Critical Asset Identifaction Method

NERC Cyber Security Standards

Implementation Plan for Version 5 CIP Cyber Security Standards

ReliabilityFirst CIP Evidence List CIP-002 through CIP-009 are applicable to RC, BA, IA, TSP, TO, TOP, GO, GOP, LSE, NERC, & RE

CIP v5/v6 Implementation Plan CIP v5 Workshop. Tony Purgar October 2-3, 2014

CIP Cyber Security Configuration Change Management and Vulnerability Assessments

CIP Cyber Security Electronic Security Perimeter(s)

Standard CIP 007 3a Cyber Security Systems Security Management


NERC CIP VERSION 5 COMPLIANCE

Information Shield Solution Matrix for CIP Security Standards

Standard CIP 004 3a Cyber Security Personnel and Training

Standard CIP Cyber Security Security Management Controls

NovaTech NERC CIP Compliance Document and Product Description Updated June 2015

Joe Andrews, MsIA, CISSP-ISSEP, ISSAP, ISSMP, CISA, PSP Sr. Compliance Auditor Cyber Security

Lessons Learned CIP Reliability Standards

CIP Cyber Security Configuration Change Management and Vulnerability Assessments

IRA Risk Factors Update for CIP. Ben Christensen Senior Compliance Risk Analyst, Cyber Security October 14, 2015

NERC CIP Whitepaper How Endian Solutions Can Help With Compliance

Alberta Reliability Standard Cyber Security Personnel & Training CIP-004-AB-5.1

SecFlow Security Appliance Review

Redesigning automation network security

TASK TDSP Web Portal Project Cyber Security Standards Best Practices

Standard CIP Cyber Security Systems Security Management

How to Integrate NERC s Requirements in an Ongoing Automation and Integration Project Framework

CIP Physical Security. Nate Roberts CIP Security Auditor I

John M Shaw Presentation to UTC Region 7 February 19, 2009 jshaw@garrettcom.com

RuggedCom Solutions for

Automating NERC CIP Compliance for EMS. Walter Sikora 2010 EMS Users Conference

The first step in protecting Critical Cyber Assets is identifying them. CIP-002 focuses on this identification process.

152 FERC 61,054 UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION. 18 CFR Part 40. [Docket No. RM ]

Alberta Reliability Standard Cyber Security System Security Management CIP-007-AB-5

NERC CIP Substation Cyber Security Update. John M Shaw Presentation to UTC Region 7 February 19, 2009 jshaw@garrettcom.com

Question Name C 1.1 Do all users and administrators have a unique ID and password? Yes

Alberta Reliability Standard Cyber Security Implementation Plan for Version 5 CIP Security Standards CIP-PLAN-AB-1

Verve Security Center

Securing Modern Substations With an Open Standard Network Security Solution. Kevin Leech Schweitzer Engineering Laboratories, Inc.

Entity Name ( Acronym) NCRnnnnn Risk Assessment Questionnaire

KEY CONSIDERATIONS FOR MIGRATING TO THE VERSION 5 NERC CIP CYBER SECURITY STANDARDS

NERC CIP Tools and Techniques

HANDBOOK 8 NETWORK SECURITY Version 1.0

Olav Mo, Cyber Security Manager Oil, Gas & Chemicals, CASE: Implementation of Cyber Security for Yara Glomfjord

Module 8. Network Security. Version 2 CSE IIT, Kharagpur

SAQ D Compliance. Scott St. Aubin Senior Security Consultant QSA, CISM, CISSP

Voluntary Cybersecurity Initiatives in Critical Infrastructure. Nadya Bartol, CISSP, SGEIT, 2014 Utilities Telecom Council

Critical Controls for Cyber Security.

CIP Electronic Security Perimeter (ESP) - Dan Mishra FRCC Compliance Workshop May 09-13, 2011

i-pcgrid Workshop 2015 Cyber Security for Substation Automation The Jagged Line between Utility and Vendors

Alberta Reliability Standard Cyber Security Security Management Controls CIP-003-AB-5

Small Firm Focus: A Practical Approach to Cybersecurity Friday, May 29 9:00 a.m. 10:15 a.m.

Alberta Reliability Standard Cyber Security Physical Security of BES Cyber Systems CIP-006-AB-5

Techno Security's Guide to Securing SCADA

Plans for CIP Compliance

Access Control BUSINESS REQUIREMENTS FOR ACCESS CONTROL

Firewall Audit Techniques. K.S.Narayanan HCL Technologies Limited

1. Cyber Security. White Paper Data Communication in Substation Automation System (SAS) Cyber security in substation communication network

GE Oil & Gas. Cyber Security for NERC CIP Versions 5 & 6 Compliance

The North American Electric Reliability Corporation ( NERC ) hereby submits

Secure SCADA Network Technology and Methods

Security Solutions to Meet NERC-CIP Requirements. Kevin Staggs, Honeywell Process Solutions

Going Critical. How to Design Advanced Security Networks for the Nation s Infrastructure. w w w. G a r r e t t C o m. C o m

WHITE PAPER CYBER SECURITY AND ELECTRIC UTILITY COMMUNICATIONS WHAT NERC/CIP MEANS FOR YOUR MICROWAVE

TOP 10 CHALLENGES. With suggested solutions

Utility Modernization Cyber Security City of Glendale, California

Cyber Security for NERC CIP Version 5 Compliance

NB Appendix CIP NB-1 - Cyber Security Personnel & Training

Consensus Policy Resource Community. Lab Security Policy

Security Policy for External Customers

ENTERPRISE IT SECURITY ARCHITECTURE SECURITY ZONES: NETWORK SECURITY ZONE STANDARDS. Version 2.0

MONITORING AND VULNERABILITY MANAGEMENT PCI COMPLIANCE JUNE 2014

NERC CIP Compliance with Security Professional Services

Best Practices for PCI DSS V3.0 Network Security Compliance

DESIGNATED CONTRACT MARKET OPERATIONAL CAPABILITY TECHNOLOGY QUESTIONNAIRE

LogRhythm and NERC CIP Compliance

Appendix A: Configuring Firewalls for a VPN Server Running Windows Server 2003

REDSEAL NETWORKS SOLUTION BRIEF. Proactive Network Intelligence Solutions For PCI DSS Compliance

Secure Remote Substation Access Interest Group Part 3: Review of Top Challenges, CIPv5 mapping, and looking forward to 2014!

TRIPWIRE NERC SOLUTION SUITE

What is a Firewall? Computer Security. Firewalls. What is a Firewall? What is a Firewall?

Secure Substation Automation for Operations & Maintenance

Supporting our customers with NERC CIP compliance. James McQuiggan, CISSP

Manage Utility IEDs Remotely while Complying with NERC CIP

SCADA Compliance Tools For NERC-CIP. The Right Tools for Bringing Your Organization in Line with the Latest Standards

Secure Remote Substation Access Solutions

Network Security Policy

Critical Infrastructure Security: The Emerging Smart Grid. Cyber Security Lecture 5: Assurance, Evaluation, and Compliance Carl Hauser & Adam Hahn

Secure External Network Communications Lynda L. McGhie Payoff

ForeScout CounterACT and Compliance June 2012 Overview Major Mandates PCI-DSS ISO 27002

A Rackspace White Paper Spring 2010

Reclamation Manual Directives and Standards

AURORA Vulnerability Background

Franchise Data Compromise Trends and Cardholder. December, 2010

Transcription:

CIP-003-6 R2 BES Assets Containing Low Impact BCS Lisa Wood, CISA, CBRA, CBRM Compliance Auditor Cyber Security

Slide 2 About Me Been with WECC for 5 years 1 ½ years as a Compliance Program Coordinator 2 Years as an Associate Compliance Auditor 1 Year as a Compliance Auditor, Cyber Security Buyer @ OPSGEAR for 1 year Risk Management @ JPMorgan Chase for 7 years

Slide 3 Agenda Day 1 Recap CIP-003-6 R2 Low Impact Update Attachment 1 overview Attachment G (per section) Examples of Evidence (per section) Considerations (per section) Questions

Slide 4 Day 1 Recap Discussed SDT updates to Low Impact (CIP-003-6 R2), and Guidelines and Technical Basis Overview of CIP-002-5.1 Applied IRC to BILL s BES Assets Determined impact rating for each BES Asset Identified which of BILL s BES Assets fell into Low impact rating

Slide 5 https://i.vimeocdn.com/video/520165827_ 295x166.jpg

Slide 6 Low Impact Progress Changes to Requirement language Added Attachment 1 & 2 Developed a tiered approach to implementation timeline of Low Impact Newly defined terms: Low Impact External Routable Connectivity Low Impact BES Cyber System Electronic Access Point

Slide 7 CIP-003-6 R1 Policies R1. Each Responsible Entity shall review and obtain CIP Senior Manager approval at least once every 15 calendar months for one or more documented cyber security policies that collectively address the following topics: 1.2 For its assets identified in CIP-002 containing low impact BES Cyber Systems, if any: 1.2.1. Cyber security awareness; 1.2.2. Physical security controls; 1.2.3. Electronic access controls for Low Impact External Routable Connectivity (LERC) and Dial-up Connectivity; and 1.2.4. Cyber Security Incident response (NERC, 2015, CIP-003-6 Cyber Security, p.5)

Slide 8 CIP-003-6 R2 Language R2. Each Responsible Entity with at least one asset identified in CIP-002 containing low impact BES Cyber Systems shall implement one or more documented cyber security plan(s) for its low impact BES Cyber Systems that include the sections in Attachment 1. [Violation Risk Factor: Lower] [Time Horizon: Operations Planning] Note: An inventory, list, or discrete identification of low impact BES Cyber Systems or their BES Cyber Assets is not required. Lists of authorized users are not required. (NERC, 2015, CIP-003-6 Cyber Security, p.8)

Slide 9 Attachment 1 Added Attachment 1 Required Sections for Cyber Security Plan(s) for Assets Containing Low Impact BES Cyber Systems (LIBCS). Includes the four (4) subject matter areas that were developed in response to FERC s concerns in Order 791 relative to specific controls and objective criteria for Low-impact BCS: Cyber Security Awareness Physical Security Controls Electronic Access Controls Cyber Security Incident Response

Slide 10 Attachment 1 (continued) Provides flexibility on how to apply the required security controls Utilization of High and Medium Impact BCS policies, procedures, and processes for your Low Impact BCS Can develop Cyber Security plans by asset or group of assets

Slide 11 Attachment 2 Added Attachment 2 Examples of Evidence for Cyber Security Plan(s) for Assets Containing Low Impact BES Cyber Systems High level, non-prescriptive Is not all-inclusive

Slide 12 Important Actions/Dates Ballot came back February 2, 2015 Board of Trustees Approval February 12, 2015 Filed with FERC February 13, 2015 Pending Regulatory decision

Slide 13 Tiered Approach to Implementation

Slide 14 Newly Defined Terms Low Impact External Routable Connectivity (LERC) Direct user-initiated interactive access or a direct device-todevice connection to a low impact BES Cyber System(s) from a Cyber Asset outside the asset containing those low impact BES Cyber System(s) via a bi-directional routable protocol connection. Point-to-point communications between intelligent electronic devices that use routable communication protocols for time-sensitive protection or control functions between Transmission station or substation assets containing low impact BES Cyber Systems are excluded from this definition (examples of this communication include, but are not limited to, IEC 61850 GOOSE or vendor proprietary protocols). (NERC, 2015, Definition of Terms, p. 1)

Slide 15 Newly Defined Terms (continued) Low Impact BES Cyber System Electronic Access Point (LEAP) A Cyber Asset interface that controls Low Impact External Routable Connectivity (LERC). The Cyber Asset containing the LEAP may reside at a location external to the asset or assets containing low impact BES Cyber Systems. (NERC, 2015, Definition of Terms, p. 1)

Slide 16 Newly Defined Terms What is the reason for them? To differentiate the obligations and implementations of Low Impact BCS from the High and Medium Impact BCS

Slide 17 Attachment G: Pre-Audit Data Request Provide: (a) a list of BES assets [R1.3] that contain Low Impact BCS, as determined by the application of the CIP-002-5.1 IRC, (b) plan documentation (c) documentation the plans were implemented

Slide 18 Audit Approach Does the entity have a list of BES assets containing low impact BES Cyber Systems? Does the entity have documented Cyber Security Plan(s) for low impact BCS? Did the entity implement the plans and controls in Attachment 1?

Slide 19 Examples of Evidence Spreadsheet or list of BES assets containing Low Impact BCS Cyber Security Plan(s) documentation Evidence of implementation of the Cyber Security Plan(s) and associated controls

Slide 20 Attachment 1 Section 1. Cyber Security Awareness

Slide 21 Attachment 1 - Section 1 1. Cyber Security Awareness: Each Responsible Entity shall reinforce, at least once every 15 calendar months, cyber security practices, (which may include associated physical security practices).

Slide 22 Attachment G: Pre-Audit Data Request Section 1 Cyber Security Awareness Provide plan documentation including policies, programs, and processes. Provide documentation that the reinforcement of cyber security practices occurred at least once every 15 calendar months.

Slide 23 Audit Approach Did the entity document the cyber security practices? Do the practices cover the protection of Low Impact BES Cyber Systems (logical or physical)? What is the entity s process for reinforcing the documented cyber security practices? Did the entity follow the documented processes for reinforcing the cyber security practices once every 15 months?

Slide 24 Examples of Evidence Cyber Security Awareness Plan Documentation Evidence of reinforcement Direct Communications Emails Memos Computer-based training What else?

Slide 25 Examples of Evidence Evidence of reinforcement (continued) Indirect Communications Posters Intranet Brochures Company Newsletters Coffee mugs Management Support and Reinforcement Presentations w/ agenda and topics

Slide 26 Cyber Security Awareness Considerations Five do s for a Security Awareness program: 1. Ensure executive support and management buyin 2. Make it fun 3. Include posters, newsletters, email tips, and reminders 4. Focus on changing behaviors 5. Solicit end-user ideas

Slide 27 Security Awareness Resources SANS Securing the Human Resources http://www.securingthehuman.org/resources/pl anning Planning Measuring results Posters

Slide 28 Attachment 1 Section 2. Physical Security Controls

Speaker Intro: Darren T. Nielsen, CPP, PSP, PCI, CISA, CBRM, CBRA, 25 years Physical Security Experience Marine Corps Veteran (PRP) Retired Law Enforcement Officer 8 years Critical Infrastructure Protection Program ASIS Utilities Security Council - Chair ASIS Physical Security Council Degrees: M.Ad. (Leadership Emphasis) w/distinction- Northern Arizona University BA- Police Science- Ottawa University (Summa Cum Laude)

30 OVERVIEW Known Unknown Suggestions

Slide 31 Audit Approach-Low Impact shall control physical access, based on need as determined by the responsible entity Need should be a business justification based on a risk determination Risk = Threat x Vulnerability x Consequence

Slide 32 Section 2 - Audit Approach Risk = Threat x Vulnerability x Consequence Threat Who or what could damage the facility or asset(s)? Vulnerability How easily could that damage be carried out? Consequence How bad would the damage be in the larger picture? W E S T E R N E L E C T R I C I T Y C O O R D I N A T I N G C O U N C I L

Slide 33 Attachment G: CIP-003-7 R2 Evidence Section 2 Physical Security Controls Provide (a) documentation of the selected controls, (b) an explanation and rationale for the selected controls, and (c) documented policies, procedures, and processes for controlling physical access, specific to those controls. Provide documentation that the selected controls were implemented to control access to the asset, if any, or the location of the BES Cyber System within the asset; and the Cyber Asset containing LEAP, if any.

Slide 34 Section 2 - Audit Approach What are the controls the entity selected and why? The why is where the entity should explain how they determined the need for the selected controls ( based on need as determined by the Responsible Entity ) Do the policies, procedures, and processes address the selected controls? Did the entity implement the controls?

Slide 35 Section 2 Audit Approach (cont.) Do the selected controls address the Asset or the location of the LIBCS? Does the entity have any LEAPs and do they have controls in place to control physical access to the LEAP?

Slide 36 Components of Physical Security Access Control Perimeter or barrier Access Points Doors Windows Ducts Locks and/or Security Guard Monitoring Alert or alarm when the barrier has been crossed Human observation Direct Video Alarm system Logging Who crossed the barrier? When did they cross it?

Slide 37 Examples of Evidence Documentation of security controls including rationale for selecting those controls May include: Physical security plan/program Site-specific plans List of controls for each LIBCS Evidence of security control implementation Photographs Direct Observation Access Logs Diagrams/Facility Maps

Slide 38 Attachment 1 Section 3. Electronic Access Controls

Morgan King, CISSP-ISSAP, CISA Slide 39 Senior Compliance Auditor, Cyber Security

Requirement R2, Attachment 1, Section 3 Electronic Access Controls Slide 40 Establishment of boundary protections From devices external to the asset containing the low impact BES Cyber Systems Control communication either into the asset containing low impact BES Cyber System(s) At the low impact BES Cyber System itself Reduce the risks associated with uncontrolled communication using routable protocols or Dial-up Connectivity February 5, 2015

Slide 41 Attachment 1 Section 3 3. Electronic Access Controls: Each Responsible Entity shall : 3.1 For LERC, if any, implement a LEAP to permit only necessary inbound and outbound bi-directional routable protocol access; and 3.2 Implement authentication of all Dial-up Connectivity, if any, that provides access to low impact BES Cyber Systems, per Cyber Asset capability. February 5, 2015

Requirement R2, Attachment 1, Section 3 Guidelines and Technical Basis electronic access control used in the general sense, i.e., to control access, and not in the specific technical sense requiring authentication, authorization, and auditing. Slide 42 February 5, 2015

Low Impact External Routable Connectivity (LERC) Slide 43 Direct user-initiated interactive access or a direct device-to- device connection to a low impact BES Cyber System(s) from a Cyber Asset outside the asset containing those low impact BES Cyber System(s) via a bi-directional routable protocol connection. Point-topoint communications between intelligent electronic devices that use routable communication protocols for time- sensitive protection or control functions between Transmission station or substation assets containing low impact BES Cyber Systems are excluded from this definition (examples of this communication include, but are not limited to, IEC 61850 GOOSE or vendor proprietary protocols). February 5, 2015

Slide 44 LERC and ERC LERC Direct user initiated interactive access or a direct device to device connection to a low impact BES Cyber System(s) from a Cyber Asset outside the asset containing those low impact BES Cyber System(s) via a bi directional routable protocol connection ERC The ability to access a BES Cyber System from a Cyber Asset that is outside of its associated Electronic Security Perimeter via a bi-directional routable protocol connection February 5, 2015

Slide 45 Determining LERC Direct user-initiated LERC exists if a person is sitting at another device outside of the asset containing the low impact BES Cyber System Person can connect to logon, configure, read, or interact, etc Device-to-device Devices outside of the asset containing the low impact BES Cyber System sending or receiving bi-directional routable communication from or to the low impact BES Cyber System February 5, 2015

Slide 46 IEC 61850 Complex protocol that has many uses both intra and inter substation communications Exemption language in the LERC definition is specifically crafted for those time sensitive messages does not exclude Control Center communication but rather excludes the communication between the intelligent electronic devices themselves GOOSE messages are only Layer 2 61850-aware RTU, using a Layer 3 routed protocol to a concentrator-like device communication would not be exempted from the CIP Standards February 5, 2015

Slide 47 Attachment G: CIP-003-7 R2 Evidence Section 3 Electronic Access Controls For all Low Impact BES Assets containing LERC and/or Dial-up Connectivity, provide documentation of the controls designed to protect LIBCS using LERC and/or Dial-up Connectivity: For any LERC, configuration files of its associated LEAP(s). Documented controls and/or configuration files to authenticate all Dial-up Connectivity. Confirmation that the controls been implemented February 5, 2015

Slide 48 Guidelines and Technical Basis How does WECC consider G&TB for approach Used for just that guideline and basis Does not address every possible iteration to consider Audit to language of the requirement February 5, 2015

Slide 49 Section 3 - Audit Approach Is there LERC and/or Dial-up Connectivity? For any LERC, is there an established LEAP? If so, does that LEAP only permit necessary inbound and outbound access Are there controls to authenticate all Dial-up Connectivity? Have the controls been implemented? February 5, 2015

Examples of Evidence Slide 50 Implementing LEAP Configuration files and other documentation showing that inbound and outbound connections for any LEAP(s) are confined to only those the Responsible Entity deems necessary: Restricted IP addresses, ports, or services The entity s rationale for the necessary connections Documentation of Dial-up Connectivity authentication: Dial-out only to a preprogrammed number to deliver data, Dial-back modems, Modems that must be remotely controlled by the control center or control room, and/or Configuration files of dial-up access controls Asset capability exception must be well documented February 5, 2015

Reference Models Diagram 1 Host-based firewall Diagram 2 Security device Diagram 3 Location X security device Diagram 4 IP/Serial converter, directly addressable Diagram 6 No direct access, layer 7 break or authentication, no LERC Diagram 5 No bi-directional routable communication, no LERC Diagram 7 Mixed impact Cyber Asset w/ LEAP and EAP *Responsible Entities may have additional configurations not identified below. February 5, 2015

Slide 52 Guidance Diagram 1 February 5, 2015

Slide 53 Host-Based LEAP /etc/sysconfig/ipchains http://www.wiley.com/legacy/compbooks/negus/rhbf2/ipchains.html February 5, 2015

Slide 54 Guidance Diagram 2 (NERC, 2014, CIP-003-7: Cyber Security, p. 34) February 5, 2015

Slide 55 Diagram 2 LEAP February 5, 2015

Slide 56 Guidance Diagram 4 (NERC, 2014, CIP-003-7: Cyber Security, p. 36) February 5, 2015

Slide 57 Guidance Diagram 3 (NERC, 2014, CIP-003-7: Cyber Security, p. 35) February 5, 2015

Slide 58 Guidance Diagram 6 (NERC, 2014, CIP-003-7: Cyber Security, p. 38) February 5, 2015

Slide 59 Additional Considerations Regarding Reference Model - 3, would the topology shown remain valid if both Low Impact BES Assets were connected through a layer 2 switch before connecting to the LEAP shown at Location X and a cyber asset was added at each location that functioned as a authentication break as shown in Reference Model 6? February 5, 2015

Slide 60 Additional Considerations February 5, 2015

Slide 61 Additional Considerations February 5, 2015

Slide 62 Additional Considerations MAC filtering switch(config-if)# switchport port-security mac-address 0011.D9D0.00BE Private VLANs An entity should not consider utilizing layer 2 switch controls to segment mixed BCS Impact ratings Use of site-to-site tunnels http://www.cisco.com/c/en/us/support/docs/switches/catalyst-6000-series-switches/10601-90.html February 5, 2015

Slide 63 Guidance Diagram 5 February 5, 2015

Slide 64 Guidance Diagram 7 (NERC, 2014, CIP-003-7: Cyber Security, p. 39) February 5, 2015

Slide 65 http://memegenerator.net/instance/58876 870

Slide 66 Attachment 1 Section 4. Cyber Security Incident Response

Slide 67 Attachment 1 Section 4 Section 4 Cyber Security Incident Response Have one or more Cyber Security Incident response plan(s), either by asset or group of assets, which shall include: 4.1 Identification, classification, and response to Cyber Security Incidents; 4.2 Determination of whether an identified Cyber Security Incident is a Reportable Cyber Security Incident and subsequent notification to the Electricity Sector Information Sharing and Analysis Center (ES-ISAC), unless prohibited by law; 4.3 Identification of the roles and responsibilities for Cyber Security Incident response by groups or individuals;

Slide 68 Attachment 1 Section 4 (cont.) 4.4 Incident handling for Cyber Security Incidents; 4.5 Testing the Cyber Security Incident response plan(s) at least once every 36 calendar months by: (1) responding to an actual Reportable Cyber Security Incident; (2) using a drill or tabletop exercise of a Reportable Cyber Security Incident; or (3) using an operational exercise of a Reportable Cyber Security Incident; and 4.6 Updating the Cyber Security Incident response plan(s), if needed, within 180 calendar days after completion of a Cyber Security Incident response plan(s) test or actual Reportable Cyber Security Incident.

Slide 69 Attachment G: CIP-003-7 R2 Evidence Section 4 Cyber Security Incident Response Provide documentation the Cyber Security Incident Response plan includes the following: Procedures for identifying, classifying, and response to Cyber Security Incidents Procedure for determining whether an incident is reportable and for notification to the Electricity Sector Information Sharing and Analysis Center (ES-ISAC). Procedures for identifying the roles and responsibilities for Cyber Security Incident response by groups or individuals.

Slide 70 Attachment G: CIP-003-7 R2 Evidence Procedures for handling Cyber Security Incidents Procedures for testing the Cyber Security Incident response plan at least once every 36 calendar months. Procedures for updating the Cyber Security Incident response plan(s), if needed, within 180 calendar days after an Incident response plan(s) test or an actual incident. Provide documentation the Cyber Security Incident response plan was implemented

Slide 71 Section 4 - Audit Approach Does the entity have a Cyber Security Incident Response plan and does it include the six (6) parts (4.1-4.6)? Is there evidence of the performance of testing? Was the plan updated within 180 calendar days after a test or incident? Did the entity have a reportable incident and can they demonstrate they followed the documented procedures?

Slide 72 Examples of Evidence Plan documentation including policies, procedures, or process documents with specific information that includes the six (6) parts 4.1 4.6. Documentation of testing of the plan Documentation of any updates made to the plan

Cyber Security Incident Response Considerations Slide 73 Was the procedure followed? Was the incident response appropriate? Were the appropriate parties informed in a timely manner? Have changes been made to prevent a new or similar incident? What lessons have been learned form this incident?

Slide 74 Attachment G: Disclaimer Disclaimer The attachment G document specific to Low Impact assets is still in progress and may change to some degree, but these basic sets of evidence will be expected in the initial evidence package as of today.

Slide 75 Low Impact Lessons Learned None documented at this time As we get closer to April 1, 2017, NERC may provide lessons-learned that specifically address Low Impact BCS and the four (4) subject areas.

Slide 76 Mixed Impact Approach Section Section 1. Cyber Security Awareness Section 2. Physical Security Controls Section 3. Electronic Access Controls Section 4. Cyber Security Incident Response Approach Utilize the CIP-004-6 R1, Security Awareness Program Consider how to demonstrate compliance Utilize CIP-006-6 R1 Part 1.1, Physical Security Plan to define physical controls Utilize CIP-005-5 R1, Part 1.2 identified Electronic Access Point Utilize CIP-008-5 R1-R3 Relevant to Low impact Address the differences, specifically, testing (4.5) and updating the plan (4.6)

Slide 77 Low Only Impact Approach Use Attachment 1 as a starting point Add in the details of the plans and what controls you have in place Can be one document or four individual documents WICF is working on a Low Impact Cyber Security Plan

Slide 78 Low Impact BCS Audits What can you expect from an audit engagement perspective? Depends on the risk associated with the Low Impact assets and LIBCS A lot of new entities developing these programs WECC to provide more focused outreach? Implementation Study for Low Impact Assets?

Slide 79 Low Impact Applicable Requirements CIP-002-5.1 R1 R2 Part 1.1 Part 1.2 Part 1.3 Part 2.1 Part 2.2 CIP-003-6 R1 R2 R3 R4 Part 1.2 R1.2.1 R1.2.2 R1.2.3 R1.2.4

Slide 80 References NERC. (2015 January 23) CIP-003-6 Cyber Security Security Management Controls, draft. Retrieved from:http://www.nerc.com/pa/stand/prjct2014xxcrtclinfraprtctnvr5rvns/cip-003-7_clean.pdf NERC. (2015 January 23) Definitions of Terms used in Standards. Retrieved from: http://www.nerc.com/pa/stand/prjct2014xxcrtclinfraprtctnvr5rvns/definitions_of_003_ter ms_used_in_standard_clean.pdf NERC. (2015 January 23) Implementation Plan, Project 2014-02 CIP Version 5 Revisions. Retrieved from: http://www.nerc.com/pa/stand/prjct2014xxcrtclinfraprtctnvr5rvns/cip_implementation_pl an_clean.pdf

Slide 81 Lisa Wood, CISA, CBRM, CBRA Compliance Auditor, Cyber Security lwood@wecc.biz Desk: 801-819-7601 Cell: 801-300-0225