Zone Distribution in the Data Center



Similar documents
Corning Cable Systems Optical Cabling Solutions for Brocade

Data Center Design for 40/100G

Migration to 40/100G in the Data Center with OM3 and OM4 Optical Connectivity

The Need for Low-Loss Multifiber Connectivity

Migration Strategy for 40G and 100G Ethernet over Multimode Fiber

ADC s Data Center Optical Distribution Frame: The Data Center s Main Cross-Connect WHITE PAPER

Managing High-Density Fiber in the Data Center: Three Real-World Case Studies

TIA-942 Data Centre Standards Overview WHITE PAPER

Data Center Cabling Design Trends

ADC KRONE s Data Centre Optical Distribution Frame: The Data Centre s Main Cross-Connect WHITE PAPER

Data Center Optimization: Component Choice. Innovative Design. Enabling Infrastructure

Corning Cable Systems Optical Cabling Solutions for Brocade

AMP NETCONNECT Data Center Cabling Solutions

Data Center Topology Guide

The Need for Speed Drives High-Density OM3/OM4 Optical Connectivity in the Data Center

AMP NETCONNECT CABLING SYSTEMS FOR DATA CENTERS & STORAGE AREA NETWORKS (SANS) High-density, High Speed Optical Fiber and Copper Solutions

Obsolete Fiber Technology? Not in my Data Center!

Overcoming OM3 Performance Challenges

Table of Contents. Fiber Trunking 2. Copper Trunking 5. H-Series Enclosures 6. H-Series Mods/Adapter Panels 7. RSD Enclosures 8

ANSI/TIA-942 Telecommunications Infrastructure Standards for Data Centers

Ethernet 301: 40/100GbE Fiber Cabling and Migration Practices

Pretium EDGE HD Solutions

Plug & Play Gigabit Ethernet Media Conversion Module. Application Note

ANSI/TIA-942 Telecommunications Infrastructure Standard for Data Centers

HUBER+SUHNER AG Phil Ward

Data Center Standards Making Progress on Many Fronts. Jonathan Jew J&M Consultants, Inc

How To Make A Data Center More Efficient

The Three Principles of Data Center Infrastructure Design WHITE PAPER

Considerations for choosing top-of-rack in today's fat-tree switch fabric configurations

Dat Da a t Cen t Cen er t St andar St d andar s d R o R undup o BICSI, TIA, CENELEC CENELE, ISO Steve Kepekci, RCDD

InstaPATCH ZERO Solution Guide

Telecommunications Infrastructure Standard for Data Centers Tutorial

The Optical Fiber Ribbon Solution for the 10G to 40/100G Migration

Arista and Leviton Technology in the Data Center

TIA Releases Guidelines for Maintaining Polarity Using Array Connectors

Data Centre Design ready for your future

Living Infrastructure Solution Guide.

White Paper. Optimizing the SAN Fiber Optic Physical Layer in Your Data Center

DATA CENTER NETWORK INFRASTRUCTURE. Cable and Connectivity for the Most Demanding Networks. BerkTekLevitonTechnologies.com

Data Center Network Infrastructure The Smart Choice For Your Data Center

Data Centers. Mapping Cisco Nexus, Catalyst, and MDS Logical Architectures into PANDUIT Physical Layer Infrastructure Solutions

Plug & Play Universal Systems

The migration path from 10G to 40G and beyond for InstaPATCH 360, InstaPATCH Plus and ReadyPATCH installations

Data Center Architecture with Panduit, Intel, and Cisco

InstaPATCH Cu Cabling Solutions for Data Centers

Navigating the Pros and Cons of Structured Cabling vs. Top of Rack in the Data Center

Innovation. Volition Network Solutions. Leading the way in Network Migration through Innovative Connectivity Solutions. 3M Telecommunications

DATA CENTER DESIGN BEST PRACTICES: EFFICIENCIES BEYOND POWER AND COOLING

PANDUIT is a Technology Developer Partner for Storage Networking Hardware. FIBER OPTIC CABLING SYSTEM SOLUTIONS B EYOND T HE G LASS

Top of Rack: An Analysis of a Cabling Architecture in the Data Center

Enterprise Networks EMEA. Core Products FOR DATA CENTRES

A Comparison of Total Costs of Ownership of 10 Gigabit Network Deployments in the Data Center

DATA CENTRES POWERED BY EXCEL

Secure/Keyed LC System Solutions Overview

The ABC of Direct Attach Cables

Network Design. Yiannos Mylonas

THE IMPACT OF CURRENT TRENDS ON THE DATA CENTER COMMUNICATIONS CABLING INFRASTRUCTURE

Data Center. Pre-terminated. Patch Panel System. Cabling Systems Simplified. Patch Panels. 10G + Gigabit. Patch Cords. Plug & Play Installation

High density Fiber Optic connections in the Data Center. Phil Ward Datacenter Product Market Manager. HUBER+SUHNER AG

How To Determine Data Center Reliability

Infrastructure for the next three generations

24 fiber MPOptimate Configuration and Ordering Guide

Network Monitoring - Fibre TAP Modules

40GBASE-T Advantages and Use Cases

Patch Cords for Data Center Applications

Maintaining Proper Polarity for Modular Pre-terminated Fiber Systems. Rudolph A. Montgelas Fiber Optic Senior Product Manager Ortronics/Legrand

Automating Infrastructure A connectivity perspective for BICSI SEA meeting, November 2011

SIEMON Data Center Solutions.

Upgrading Path to High Speed Fiber Optic Networks

Data Centre Issues supported in TIA-942 : "Telecommunications Infrastructure for Data Centre s"

Physical Infrastructure trends and evolving certification requirements for Datacenters Ravi Doddavaram

Data Center Network Topologies

Fiber in the Data Center

MPO. Fast Fibre Solution for Data Centres

Sustaining the Cloud with a Faster, Greener and Uptime-Optimized Data Center

Is it recommended that specifiers and installers read this guide carefully and ensure that all directions are fully and clearly understood.

Arista 40G Cabling and Transceivers: Q&A

Cable Assemblies. Features and Benefits

Design Guide. SYSTIMAX InstaPATCH 360 Traffic Access Point (TAP) Solution.

Security & Surveillance Cabling Systems

Enterprise Networks EMEA. Core Products FOR DATA CENTRES

Data Center Market Trends

How To Write An Infrastructural Standard For Data Center Infrastructure

Fabrics SDN and Big Data. What this means to your white space

10GBASE T for Broad 10_Gigabit Adoption in the Data Center

Faster Method for Connecting Customers in the Colocation Data Center

Gigabit Passive Optical Networks

Structured and Point to Point Network Cabling for Industrial Automation

Juniper Networks QFabric: Scaling for the Modern Data Center

Polymer Coated Fiber Cable (PCF)

Data Centre & Enterprise Solutions. RapidNet

10G and Beyond in the Data Center with OM3 Fiber

Data Centre Cabling. 20 August 2015 Stefan Naude RCDD The SIEMON Company

Optimizing Infrastructure Support For Storage Area Networks

Transcription:

Zone Distribution in the Data Center By Jennifer Cline, RCDD As data centers face the continued need to expand and grow, the fundamental concerns and needs remain constant. Key concerns of the data cabling infrastructure in the data center must provide reliability, scalability, manageability and flexibility in order to meet the ever-changing requirements of the data center network. Data Center Needs To ensure essential reliable performance, data center cabling infrastructures must provide stability and enable 24 hours x seven days per week uptime. Uptime requirements are segmented by the tier level implemented in the data center, ranging from Tier 1 to Tier 4, as page 14 September 2008 www.cablingbusiness.com defined by the Uptime Institute. Tier 4 data centers have uptime requirements of 99.995 percent, less than one halfhour per year. Cabling infrastructures must also support data center growth, both in the actual addition of system electronics, whether servers, storage or switch ports, as well as providing for a migration path for increasing of data rates. As technology evolves and standards are completed to define data rates such as 40 and 100 Gigabit Ethernet, as well as Fiber Channel data rates of 16 Gigabits per second (G/bs), 32 G/bs and beyond, the cabling infrastructures installed today must provide scalability to accommodate the need for more bandwidth in support of future applications. In addition to reliability and scalability, the management of the infrastructure is also crucial. Infrastructure design, cabling solutions and deployment are areas where flexibility and manageability go hand-in-hand. With a constant in data centers being change, the cabling infrastructure must be modular to accommodate changing requirements. With the technology and system equipment upgrades on the horizon, the infrastructure deployed today must be flexible in order to easily adapt and accommodate the changes that will be required. While the infrastructure is designed and

installed in a way that easily accommodates change, it must also be easy to manage. When moves, adds or changes are required, it is essential to be able to make these adjustments with minimal downtime. Designing the Cabling Infrastructure When designing a data center to meet the aforementioned needs, best practices should be followed. ANSI/EIA/TIA- 942 Telecommunications Infrastructure Standard for Data Centers addresses recommended design practices for all areas of the data center, including pathways and spaces and the cabling infrastructure. The standard defines the following spaces and cabling for typical enterprise, or reduced, data center topologies. An additional topology is also defined in TIA-942, where the horizontal distribution area is included as a separate space, rather than collapsed back to the main distribution area. Utilizing a structured cabling architec- Reduced Data Center Topology Access Providers Offices, Ops. Main Distribution Area Center, Support (Routers, Backbone Rooms LAN/SAN Switches, PBX, M13 Muxes) Zone Dist Area Horizontal Computer Room Cabling Equip Dist Area (Rack/Cabinet) Equip Dist Area (Rack/Cabinet) ture to provide connectivity as defined by but it is also one that is incorporated into TIA-942 facilitates a flexible, manageable many data centers operating today. TIAinfrastructure. An important component 942 defines the space used to implement in the recommended topology is zone zone distribution as the zone distribution distribution. Zone distribution is not only a area (ZDA). The ZDA acts as a consolidation design topology recommended in TIA-942, point for high-fiber-count cabling from

Installation the main distribution area (MDA) or horizontal distribution area (HDA) to regional areas or zones within the data center. Incorporating this architecture into one s data center cabling design allows for a one-time installation of the backbone cabling and provides flexibility to accommodate frequent reconfigurations at the zone required for moves, adds and changes. To implement ZDA, one should identify zones throughout the data center and locate points of distribution within these zones. A common implementation of zone distribution includes the connectivity between the main distribution area and the server rows in the data center. High fiber-count cabling is installed from the MDA to each ZDA within the server rows, and low fiber-count cabling is then distributed from the ZDA to the server racks or cabinets in the equipment distribution areas (EDAs) within the zone. Zone distribution can also be implemented within data center topologies with horizontal distribution areas (HDA). When an HDA is used, high fiber-count cabling is deployed from the HDA (rather than the MDA) to each ZDA. In addition to being a topology included in TIA-942 guidelines, the ZDA also provides many benefits when incorporated in the data center cabling infrastructure.

An alternative method of deploying connectivity to EDAs is to homerun cabling from the MDA or HDA to each rack or cabinet. When compared to this method, the use of zone distribution reduces pathway congestion and limits data center disruption between the main distribution area and end equipment cabinets, eases implementation of moves, adds and changes and enables a modular solution for a pay-asyou-grow approach to cabling the data center. Solutions for Zone Distribution For data centers utilizing a zone distribution architecture, common product solutions from the zone distribution area to the equipment distribution area racks or cabinets, include extender trunks, harnesses or multiple patch cords for connectivity to the end equipment, such as servers or storage devices. An alternative to using these products between the ZDA and EDA racks or cabinets is the integrated trunk module (ITM). A solution ideal for the zone distribution application, the ITM includes a pre-terminated, 12-fiber MTP trunk assembly inside of an LC or SC breakout module. Each ITM includes a trunk cable of 40 feet or 80 feet in length and yields six ports with SC duplex or LC duplex adapters for interconnecting into electronics, such as servers. The ITM has a sliding tray, which rotates to one side and is designed for easy access for deployment of the pre-terminated MTP trunk cable. The ITM provides a value-add preterminated, modular solution for addressing dynamic cabling requirements, making data center design and installation easier. In data centers employing the zone distribution architecture within server rows, the ITM is placed within a rack or cabinet in the server row EDA. The trunk cable within the ITM is terminated with a pinned MTP connector and is installed from the rack or cabinet to the ZDA, where the pinned connector is mated to the trunk from the main distribution area. The remaining excess cable can be stored within the sliding tray of the ITM for simple slack management. LC or SC jumpers interconnect from the ITM into the electronics within each rack or cabinet. Implementation of Zone Distribution with an ITM With a pre-terminated solution, whether a homerun architecture or zone distribution, a common challenge includes planning and distance measurement for cable assembly lengths, as well as slack management of any length overage within the channel. The ITM offers a unique solution to this challenge by incorporating a means to store the trunk cable within the module itself. By providing a means to store slack easily, the time required to measure channel lengths and plan the cabling within a zone is eliminated. Providing the maximum deployed length within a zone is less than 40 feet or 80 feet, the ITM can be used, and any spare length for shorter channels is stored within the module. With slack management integrated into the ITM, slack is virtually eliminated from the channel. With alternative solutions for zone distribution, such as the extender trunk, a custom component is required for each location requiring connectivity due to the different length requirements from the ZDA to each rack. An ITM solution offers a single component that can be installed at each rack or cabinet with the appropriate length of trunk deployed, eliminating many separate, custom components and simplifying materials management onsite and during installation. An additional consideration in deployment of cabling infrastructures within the data center is channel insertion loss. With current data rates deployed, and the need to provide a migration path for accommodating future data rates and insertion loss budgets, channel insertion loss must be addressed. At first glance, when compared to a homerun solution, zone distribution appears to require additional loss due to the connection point, or mating, at the zone. With previous solutions available for zone distribution, this is true. However, with the ITM, an MTP-mated pair is eliminated from the channel, and zone distribution can be implemented with the same channel insertion loss as a typical homerun solution between the MDA and EDA with a patch panel at each end of the channel. Implementing zone distribution into the data center cabling infrastructure can addi- page 18 September 2008 www.cablingbusiness.com

The ITM Eliminates one mated pair in the channel link ZDA EDA (Cabinet) MDA MM Link Loss = 1.5 db + fiber loss (db) tionally reduce the time required for cabling cally reduced, thereby reducing the time installation. When evaluating, based on required for installation. For example, in a per foot of cable sheath installed, the total data center with multiple server rows of 12 footage of cable to be installed is dramati- cabinets each where 24-fiber connectivity Circle Reader Card #123 page 20 September 2008 www.cablingbusiness.com is required to each cabinet, the estimated time and labor savings are shown as a function of distance. Utilizing the ITM offers significant advantages over a homerun topology, as well as compared to alternative solutions available for zone distribution implementations. Use of the integrated trunk module in zone distribution applications: Eliminates the need for cable length planning; Eliminates slack with integrated slack management into the module; Reduces material management complexity by eliminating the need for multiple custom components; Eliminates one MTP-mated pair from the channel, lowering installed channel insertion loss; and, Reduces installation time and simplifies moves, adds or changes. The integrated trunk module is available in 40-foot lengths, and with compatibility in 1U rack-mountable hardware; the solution is optimized for zone distribution architectures in the data center. With a capacity for three integrated trunk modules, a 1U rack-mountable solution provides up to 36-fiber connectivity per rack; with a 4U rack-mountable solution, capacity is increased to a maximum of 144 fibers. Additionally, 80-foot length solutions are available for use in 4U rack-mountable housings where longer distance capabilities are required. With reduced channel insertion loss, integrated slack management, simplified materials management and reduced time of deployment, zone distribution with integrated trunk modules is the ideal approach for data center design and deployment. Jennifer Cline, RCDD, is the private networks market manager of data centers for Corning Cable Systems in Hickory, NC. In this role, one of her main responsibilities is the commercial leadership for data center applications. Jennifer joined CCS Research and Development in 1999 specializing in product development of flame retardant cables.