Pipe through Embankment Dams

Similar documents
STRUCTURES Excavation and backfill for structures should conform to the topic EXCAVATION AND BACKFILL.

Nebraska Department of Roads Drainage and Erosion Control Manual December 2011 Appendix C: Pipe Material Policy Page C-1 PIPE MATERIAL POLICY

State of Illinois Department Of Transportation CONSTRUCTION INSPECTOR S CHECKLIST FOR STORM SEWERS

TECHNICAL NOTE Culvert Sliplining and Lining of Casings with HPPipe

DIVISION 2 - SEWERAGE AND DRAINAGE SECTION STORM DRAIN SYSTEMS PART 1 - GENERAL

Stormwater/Wetland Pond Construction Inspection Checklist

Emergency Spillways (Sediment basins)

FY11 Sanitary Sewer Main Rehab and Point Repair Bid Tabulation

SECTION 724 PIPE CULVERTS

Section 2100-Trenching and Tunneling

SEDIMENT/STORMWATER MANAGEMENT BASIN CONSTRUCTION CHECKLIST

Specifications for Residential Property Owners Connection to New Public Sewer

SECTION STORM DRAINAGE TABLE OF CONTENTS

Minimum Design Criteria for the permitting of Gravity Sewers

Small Dam Repair The Stone Lake Dam Story. Joe Barron, P.E. SynTerra formerly the Fletcher Group, Inc. 148 River St. Suite 220 Greenville, S.C.

PART 6 - STANDARD DESIGN AND CALCULATION FORMS 6.1 SANITARY SEWER DATA SHEET

Lecture 24 Flumes & Channel Transitions. I. General Characteristics of Flumes. Flumes are often used:

SECTION PUBLIC STORM UTILITY DRAINAGE PIPING

STORM DRAINS CHAPTER 7

Section 2 Specification 2.18 Concrete and/or Corrugated Steel Storm Sewer TABLE OF CONTENTS

RECENT FAILURES OF LARGE CORRUGATED METAL PIPE SPILLWAYS

STORMWATER MANAGEMENT CHECKLIST

DIVISION 4300 STORM DRAINAGE

Indiana State Department of Health Construction Guidelines for Gravity and Flood-Dose Trench Onsite Systems

CHAPTER 14 SECTION 1

Section 402. STORM SEWERS

CLEANING, INSPECTION, AND TESTING OF SEWERS

SERVICE LINE EXTENSION AND SERVICE LINE CONNECTION CONDENSED SANITARY SEWER SYSTEM INSTALLATION SPECIFICATIONS

FY08 SEWER POINT REPAIRS BID TABULATION

A perforated conduit such as pipe, tubing or tile installed beneath the ground to intercept and convey ground water. or structures.

SECTION 7- STORM SEWER

PUBLIC WORKS DESIGN, SPECIFICATIONS & PROCEDURES MANUAL LINEAR INFRASTRUCTURE

STANDARD SPECIFICATIONS & CONSTRUCTION DETAILS MANUAL SECTION 5 - STORM DRAINAGE Design

CHAPTER 8 CIVIL DESIGN

Wastewater Collection System Supplemental Design Standards for Capital Improvement Program Projects

The Evolution of Watertight Storm Drainage Systems John M. Kurdziel, P.E. (Member)

SECTION 6A STORM DRAIN DESIGN Mar S E C T I O N 6A STORM DRAIN - DESIGN

BEST PRACTICE GUIDELINES FOR CULVERT LINER SELECTION

CHAPTER 9 CULVERTS TABLE OF CONTENTS. CDOT Drainage Design Manual

SECTION 9.02 BUILDING SUBSURFACE DRAINS (PERIMETER, ETC.)

SPECIFICATIONS FOR PRECAST MODULAR BLOCK RETAINING WALL SYSTEM (revised 11/5/13)

SEPTIC SYSTEM CONSTRUCTION REQUIREMENTS ST. MARY S COUNTY HEALTH DEPARTMENT

NATURAL RESOURCES CONSERVATION SERVICE CONSERVATION PRACTICE STANDARD SUBSURFACE DRAIN. (Ft.) CODE 606

550 PIPE CULVERTS, SEWERS AND DRAINS

ICOLD POSITION PAPER ON DAM SAFETY AND EARTHQUAKES

Chapter 9 Remedial Measures

Local Road Assessment and Improvement Drainage Manual

SIENA STONE GRAVITY RETAINING WALL INSTALLATION SPECIFICATIONS. Prepared by Risi Stone Systems Used by permission.

SECTION LS 2530 SANITARY SEWERS. A. General: Submit the following in accordance with The General Conditions.

SECTION 55 PIPE FOR STORM DRAINS AND CULVERTS (FAA D-701)

GEOTECHNICAL DESIGN MANUAL

City of Shelbyville Site Inspection Checklist

SECTION STORM DRAIN SYSTEM

AIR RELEASE, CLEANOUT, AND SEWER MANHOLES

June 2007 CHAPTER 7 - CULVERTS 7.0 CHAPTER 7 - CULVERTS 7.1 GENERAL

SECTION 5 - STORM DRAINS

Chapter 9 Storm Sewers

900 SEWERAGE WORK ITEM PIPE SEWERS COMPLETE IN PLACE

Chapter 5: Drainage, Ditches, and Culverts

SECTION 200: STORM SEWER CONSTRUCTION STANDARDS

Appendix B.1. NRCS-MD Code No. 378 Pond Standards/Specifications

SECTION G SEWERS (STORM, SANITARY AND FDC)

SECTION GRAVITY SANITARY SEWERS

REHABILITATION OF FAILED CORRUGATED METAL PIPE SPILLWAYS PRESENTED AT JUNE 1996 REGIONAL CONFERENCE MID-ATLANTIC COUNCIL FOR SAFE DAMS

OAR52 A-1 (September, 1981)

CHAPTER 17: STORM SEWER STANDARDS Introduction Administration Standards 17.1

CHAPTER 11 STORM DRAINAGE

Liner system design for tailings impoundments and heap leach pads

DESCRIPTION OF STORMWATER STRUCTURAL CONTROLS IN MS4 PERMITS

CHAPTER 5. Storm Sewer

Construction Site Inspection Checklist for OHC By making use of some simple Best Management Practices (BMPs) a construction site operator can

SECTION STORM DRAINAGE STRUCTURES. 1. Trench excavation, backfill, and compaction; Section

Foundation Water Problems. An Overview and Discussion of some Causes and Cures for Water Infiltration into Basements and Foundation Structures

Index. protection. excavated drop inlet protection (Temporary) Block and gravel inlet Protection (Temporary)

Failing Culverts Structural Problems & Economic Considerations

STANDARD SPECIFICATIONS FOR STORM SEWER CONSTRUCTION CITY OF PLYMOUTH, MINNESOTA

SANITARY GRAVITY SEWER LINE TESTING. B. Section CCTV Inspection of Gravity Sewer Lines

Technical Specifications For Sewing Enveilment Plans

Access chambers and maintenance shafts. Issue 1

Precast Manhole Sections and Castings. These items shall conform to Section 31, "Storm Drain Installation," of these Standard Provisions.

City of West Linn Public Works Standard Construction Specifications. Table of Contents

Riprap-lined Swale (RS)

WET/DAMP BASEMENTS ANSWER: BASEMENT WALLS AND FLOORS CAN BECOME WET BY A LEAK, CAPILLARY SUCTION OR CONDENSATION.

ENVIRONMENTAL CODE OF PRACTICE FOR CONCRETE BATCH PLANT & ROCK WASHING OPERATIONS

CONSTANT HEAD AND FALLING HEAD PERMEABILITY TEST

Section 600 Incidental Construction

Waste Collection Systems

8-11 Structural Analysis and Fill Height Tables Pipe Cover Shallow Cover Installation Fill Height Tables...

NCMA TEK CONCRETE MASONRY FOUNDATION WALL DETAILS. TEK 5-3A Details (2003)

SPECIFICATION FOR PIPE SUBSOIL DRAIN CONSTRUCTION

STANDARD SPECIFICATIONS SECTION PRECAST REINFORCED CONCRETE MANHOLES AND MANHOLE BASES. 1. Structure Earthwork: 02200

Basement Moisture Problems

City of Lubbock Public Works Engineering Design Standards and Specifications

TECHNICAL NOTE Lining of Casings with SaniTite HP Pipe

Investigation of Foundation Failure. Step 1 - Data Collection. Investigation Steps

PERMEABILITY TEST. To determine the coefficient of permeability of a soil using constant head method.

DIRECTIONAL DRILLING

Chapter 3 CULVERTS. Description. Importance to Maintenance & Water Quality. Culvert Profile

Lecture 22 Example Culvert Design Much of the following is based on the USBR technical publication Design of Small Canal Structures (1978)

Outlet stabilization structure

Transcription:

Introduction Many different pipe materials have been used as overflow conduits through embankment dams. As aging dams are rebuilt and new dams are constructed, corrugated HDPE pipe is becoming an increasingly popular choice due to its light weight, joint performance, and structural performance. Corrugated HDPE pipe is suitable for use in many low hazard embankment dam applications, however, as with any pipe material, it is necessary to ensure the dam, overflow structure, and pipe-soil envelope is properly designed and installed for the specific project conditions. Embankment dams, regardless of their size create a significant hazard potential due to the tremendous amount of stored energy in the water they retain. Embankment Dam Failure Modes The majority of embankment dam failures are generally the result of inadequate design, poor construction methods, deteriorated pipe, or significant environmental occurrence. Regardless of the cause of failure, the effects can be devastating. It is extremely important to ensure the design criteria and the construction of an embankment dam is properly established to reduce this failure risk. This document will review common failure modes and associated preventative measures. There are many potential failure modes for embankment dams and while some common modes will be reviewed in this document, it is impossible to provide an exhaustive review. This technical note focuses on failure modes related to the conduit section of a dam. There are two primary methods of outlet works; pressurized outlet works (Figure 1) and nonpressurized outlet works (Figure 2). Figure 1. Pressurized Outlet Works Figure 2. Non-Pressurized Outlet Works Pressurized outlet works is not an acceptable application for corrugated HDPE pipe because the conduit is typically subjected to constant pressure. These applications typically require specialized pipe material or cast in-place conduit and are engineered specifically for the application. Non-pressurized control methods, however, may be suitable applications for corrugated HDPE pipe, depending on the specific project conditions. While many of the failure modes listed in this document can occur to either of the outlet works methods described above, it is important to note that the pressurized control method is generally much more sensitive to inadequate design, product selection, and construction methods. Page 1 of 8

Most embankment dam failures result from piping erosion which is a term commonly used to define the erosion processes through soil. This document focuses on failures associated with piping erosion through embankment dams. The first of these failure modes illustrates a hydraulic fracture through an embankment dam occurring above the conduit. Hydraulic Fracture above Conduit Hydraulic fractures generally occur in embankment dams due to low stress concentrations in the soil of the dam. When a hydraulic fracture occurs above the conduit it is typically the result of poor dam construction, excessive deflection in the pipe (poor backfill compaction around the pipe), differential settlement within the embankment, poor soils, or excessive water levels. Figure 3 illustrates a hydraulic fracture occurring in the embankment dam. Figure 3. Step 1 - Onset of hydraulic fracture The hydraulic fracture eventually extends through the embankment dam due to low stress concentrations in the soil combined with a high enough water level in the reservoir. The progression of this failure mode is illustrated in Figures 3 6 as the hydraulic fracture continues through the embankment to cause internal erosion and eventually failure of the conduit and dam. Figure 4. Step 2 - Hydraulic fracture propagation Page 2 of 8

Figure 5. Step 3 - Onset of internal erosion Figure 6. Step 4 - Complete internal erosion Hydraulic Fractures beneath Conduit While Figures 3-6 represent hydraulic fractures and ultimate internal erosion above the conduit, hydraulic fractures are not limited to occurring above the conduit. Hydraulic fractures can also occur beneath the conduit as a result of the inadequate or excessive compaction in the haunch area of the conduit. The compaction level of the backfill in the haunch area of a pipe is the most critical area to ensure the pipe has adequate structural support. This can also be the most difficult portion of the backfill envelope to compact if proper compaction methods and equipment are not used. This area of concern is amplified in embankment dam applications due to the hydraulic forces present. While lack of compaction in this area causes low stress concentration areas, excessive compaction causes low stress concentration areas in the bedding directly beneath the pipe invert. The compactive efforts and compaction levels are determined by the type of backfill material, moisture content of the backfill material, the pipe material, and overall embankment dam height. Figures 7 11 illustrate hydraulic fracture failures in the area beneath the pipe. Page 3 of 8

Figure 7. Hydraulic Fracture due to poor backfill compaction Figure 8. Hydraulic Fracture due to excessive backfill compaction Figure 9. Step 1 - Hydraulic Fracture propagation causes voids in bedding Page 4 of 8

Figure 10. Step 2 - Internal Erosion occurring through void Figure 11. Step 3 - Complete internal erosion through bedding Figures 3 11 illustrate common occurrences of hydraulic fracture and internal erosion initiating through the face of an embankment dam above and below the conduit. These failure modes and illustrations are not meant to be an exhaustive listing of all potential failure modes. Hydraulic fractures may occur at any point throughout an embankment dam wherever there are low stress concentrations in the soil. While the above descriptions show internal erosion occurring as a result of hydraulic fractures, internal erosion may also occur from leaking pipe joints. Joint leakage may result from improper assembly, inadequate pipe joint performance, excessive operating pressures, improper installation, or poor dam construction methods. These concerns reinforce the need to review the hazard level of an embankment dam prior to product selection. The hazard level of an embankment dam is a function of the volume of the body of water it restrains, the height of the dam, the potential damage of downstream property, the diameter of the outlet pipe, etc. While there is not a definitive hazard rating system, these criteria along with the overall design of the dam should be carefully reviewed prior to the selection of a pipe material. The following information is provided to help determine applications which are suitable for corrugated HDPE pipe. Application Guidance Figures 1 and 2 identify the two most common outlet works for an embankment dam. Pressurized outlet works is not an acceptable application for corrugated HDPE pipe as the pipe is under constant pressure. In order for corrugated HDPE pipe to be used in a dam, the water level must be controlled so that the pipe does not operate under pressure. Page 5 of 8

Acceptable embankment dam configurations are detailed in Figures 12 15. In addition to the figures, the following general guidelines should be referenced when determining the suitability of corrugated HDPE pipe in a dam application. Maximum Water level over top of pipe - 5 feet Maximum embankment dam height over top of pipe - 10 feet Required Joint Performance Watertight Maximum allowable pipe diameter 24 Maximum allowable riser diameter 24 Maximum length of conduit through dam 60 Vertical pond riser shall not be corrugated HDPE pipe Figure 12. Horizontal Gravity Flow Outlet Conditionally Acceptable Application Figure 13. Sloped Gravity Flow Outlet Conditionally Acceptable Application Figures 12 and 13 represent similar gravity flow outlet systems; Figure 12 represents a horizontal outlet, whereas Figure 13 is a sloped outlet drain. Both outlet designs function similarly as the water elevation is controlled by the elevation of the inlet side of the culvert. These types of applications are the least common methods of control due to Page 6 of 8

their operational limitations. These are acceptable applications for corrugated HDPE, provided the system meets the criteria established above. A more common method of pond level control is the use of a riser structure with a horizontal pipe through the embankment dam. These types of applications are more sensitive to design and installation inadequacies and generally require more care. The following figures illustrate the two main configurations of a pond riser application. Figure 14. Vertical Riser Located in Dam Conditionally Acceptable Application Figure 15. Vertical Riser Located in Pond Unacceptable Application While Figures 14 and 15 represent similar applications with the use of a vertical pond riser, they are significantly different in their associated risk. Figure 14 is an acceptable application for corrugated watertight HDPE pipe provided that the riser is not corrugated HDPE pipe. Also, it is very important to encase the pipe to riser connection in concrete to ensure the connection is adequately sealed and supported. The design engineer shall specify the riser material based on the specific project conditions. Figure 15 represents an application which is unsuitable for corrugated HDPE pipe. Corrugated HDPE pipe shall not be installed into the pond or beneath the pond where it is subjected to constant pressure. It is also very important for the riser structure to be installed in the embankment to reduce damage resulting from wind, frost heave, wave action, constant pressure, etc. Page 7 of 8

Summary While it is often overlooked, pipe through embankment dams involve design, construction, and operation concerns which can easily translate into problems. It is important that embankment dams and the associated outlet control devices and conduits be properly designed by a qualified engineering professional to ensure trouble free operation regardless of the size of the dam, method of outlet control, or pipe material used. As with any pipe material, corrugated HDPE pipe is not appropriate for every application but it certainly may be used in certain embankment dam applications where the design, construction, and installation is properly performed. References The following reference was used extensively in the creation of this technical note both for the technical content and illustrations: Federal Emergency Management Agency. Technical Manual: Conduits through Embankment Dams, September 2005 Page 8 of 8