Thermostatic Shower Valve 10019CP

Similar documents
Safe Touch TMV3 Thermostatic Shower ST10010CP

Coolflo Safe Touch Shower Mixing Valve ST20015CP

Artisan Thermostatic Bath Shower Mixer

Chill 4 Hole Bath Shower Mixer

Artisan Thermostatic basin mixer. Fitting Instructions & Contents List

Artisan Thermostatic bath shower mixer. Fitting Instructions & Contents List

Design Utility Lever Thermostatic Bath Shower Mixer

STABITHERM INSTALLATION & SERVICE BOOKLET

Thermostatic bar showers. Troubleshooting and maintenance

Colonial Tap Range. Installation Instructions & User Guide. Please keep these instructions for future reference and request of replacement parts

THERMOSTATIC MIXING VALVE TRIM K-T9493, K-T9494

Installation Instructions and User Guide

V10 THERMOSTATIC SHOWER VALVE PRODUCT MANUAL

Installation Instructions S

PHOENIX TAPWARE. Gloss. Shower/Wall Mixer RRP: $ Product Code: Available Finishes: GS780. Chrome MATCH WITH...

INSTALLATION INSTRUCTIONS MK-8704

Liquorice Kitchen Sink Tap

INSTALLATION INSTRUCTIONS BL-8704

Almond Kitchen Sink Tap

Installation Instructions / Warranty

Assembly and instructions

Installation Instructions

Almond Kitchen Sink Tap

Visage. Digital. Exposed with adjustable height head. Visage Digital exposed installation instuctions page 1

AMX300 DirectConnect Mixing Valve Kits

IMPORTANT INFORMATION

Apricot Kitchen Sink Tap

SHOWERS SHOWERS

Close Coupled & Back To Wall WC Saintaryware. Fitting Instructions

GLOSS SOAP DISH PRODUCT CODE: FINISH: GS895 CHROME CONTEMPORARY DESIGN PHOENIX WARRANTY STYLISH PREMIUM CHROME FINISH MATCH WITH...

Zenith Solar thermal 4.5m pump station Installation manual

Cadet Tap Range. Installation Instructions & User Guide. Please keep these instructions for future reference

Visage. Digital. Digital diverter. Installation guide. Visage Digital diverter installation instructions Page 1

Select Radiators Installation Guide

Thermostatic Valve Replacement Cartridge and Rebuild Kit

USER INSTRUCTIONS FOR 10 LITRE PORTABLE DEHUMIDIFIER MODEL NO. DHMD102

ALTO EV. Installation Instructions Thermostatic Bar Shower Valve

Installation Instructions

Installation and User Instructions Unvented Electric Storage Water Heater Models: S10UNV, S15UNV.

AIRE Thermostatic bath shower mixer Installation and operating instructions

Speedflow Undersink Unvented Water Heater. Models SF10K and SF15K. Instruction Manual

Apricot Kitchen Sink Tap

MODEL VG08008 CONTENT PACKING LIST / TOOLS NEEDED PANEL DIMENSIONS FITTINGS / TECHNICAL DATA WALL/CORNER INSTALLATION CARE AND TROUBLE SHOOTING

SF15K SF05KSS, SF10KSS

Important Information

SELECTION, APPLICATION AND MAINTENANCE

CW-4622 INSTALLATION INSTRUCTIONS CB-4622 RISER KIT TO SUIT BLACK LEVER EXPOSED VALVES & BATH/SHOWER VALVES

SHOWER WATER HEATER MODEL BS 35 / 45 / 60 BS 35 E / 45 E / 60 E OPERATION AND INSTALLATION INSTRUCTIONS

AN500T, AN1000, AN1000T, AN1500, AN1500T AN2000, AN2000T

Installation Instructions / Warranty

SUB Universal water baths SBB Boiling baths JB, PB Unstirred water baths

ecomax Instructions for use Wall hung room sealed fan assisted condensing boilers For the user

Installation Instructions / Warranty

Installation and Operating Instructions Installation Instructions for SS EPE-316L Series

Art.S001-S002 SOLAR MODULE WITH DELIVERY AND RETURN CONNECTIONS

This instruction is valid for all ACD pump models shown on page 2

THE BOILING WATER DISPENSER INSTALLATION & OPERATING INSTRUCTIONS

User's Instructions. Alpha HE CB25/33 and HE SY25

Troubleshoot resources for homeowner

Shower and Floor Gullies Channel Drain and Tile Drain SECTION

Stainless Steel Single and Dual Circulation Kits

San josé OWNER S MANUAL

SELECTION, APPLICATION & MAINTENANCE

Please also see 10 golden rules for correct Saniflo installation on

ACE. PIVOT AND BI-FOLD DOOR Installation and User Guide. These instructions must be left with the user W2-D

Wetroom Panel (Concealed Fix)

Baxi Combi 80e & 105e

FLUSHOMETER - TANK SYSTEM

Getting the best from your urn

NewAir AC-10100E / AC-10100H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS

OWNER S MANUAL. FOOTWORKS tm Faucet Controller. Foot Operated Faucet Control Valves for Commercial Sinks

REDRING POWERSTREAM-ECO UNVENTED INSTANTANEOUS WATER HEATER. Installation and User Guide

INSTALLATION MANUAL MODEL RP-100

Shower Handbook (Also covers 650 chrome variant)

WALLACE MAXIPUMP 3000, 5000, 6000 and HYDROJET 30P, 30C AND HJ400 INSTALLATION AND MAINTENANCE INSTRUCTIONS

COASTLINE QUADRANT ENCLOSURE. Installation / Maintenance Instructions Rev

BASYS INSTALLATION INSTRUCTIONS FOR ELECTRONIC CAPACITANCE SENSING LAVATORY FAUCETS EFX-3XX Pedestal, Sensor Activated Lavatory Faucets

Installation guide Nordic mixer taps. Before installing read this guide first

FAUCET SPECIFICATIONS. Vessel Bathroom Faucet Model VG03023 MODEL VG03023

PLUMBING CARE AND REPAIR

Constantemp Double Wall Low pressure steam-water Heater F-340LDW,F-640LDW, F-940LDW and F-1240LDW

OPERATIONS AND MAINTENANCE INFORMATION FOR: THE CANPLAS BACKWATER VALVE THE CHEMTROL BALL SHUT OFF VALVE SUMP PUMPS AND WASTEWATER EJECTOR PUMPS

Model 2128 AIR COMPRESSOR PUMP Operating Instructions

Mira Extra Bath and Thermostatic Shower Control

Support Cleaning Apparatus. Operation, Cleaning, & Safety Manual

OPL BASIC. Dosing System for Professional Laundry machines. Contents

NÜVE SANAYİ MALZEMELERİ İMALAT VE TİCARET A.Ş. OT 020 BENCH TOP STEAM STERILIZER USER S MANUAL

orlando OWNER S MANUAL

Fleck Service Manual INSTALLATION AND START-UP PROCEDURE TABLE OF CONTENTS JOB SPECIFICATION SHEET

123 Industrial Loop Road Paynesville, MN Phone: MASTER MANUFACTURING MASTER GARDNER

Duo-tec Combi HE A Range. User s Operating Instructions & Important Warranty Information. Gas Fired Wall Mounted Condensing Combination Boiler

OWNER S MANUAL FORCE 10 MARINE COMPANY HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) FAX: (604)

3. SEISCO PARTS & SERVICE REMOVAL AND REPAIR GUIDE

Version: 1.0 TWO HANDLES INWALL WATERFALL FAUCET INSTALL GUIDE

TECHNICAL INSTRUCTIONS REPAIR KITS Hydroguard Series 420 Thermostatic Valve All Models (1 9)

Volkswagen B3 Passat General-Engine 4 CYL. 19 Engine - Cooling System (Page GR-19)

Instruction Manual. Alfa Laval SB Membrane Sample Valve ESE02963-EN

PBX Series Quick Fit Connector Bimetallic Steam Traps

Elson Coral E. Open Vented Thermal Store providing mains pressure hot water heated by electricity. Installation, Servicing and User's Instructions

Folding Bath Screen Instruction Manual

Transcription:

Thermostatic Shower Valve 10019CP Installation and Maintenance Instructions In this procedure document we have endeavoured to make the information as accurate as possible. We cannot accept any responsibility should it be found that in any respect the information is inaccurate or incomplete or becomes so as a result of further developments or otherwise. Intatec Ltd Airfield Industrial Estate Hixon Staffordshire ST18 0PF Tel: 01889 272 180 Fax: 01889 272 181 email: sales@intatec.co.uk web: www.intatec.co.uk

Introduction This installation guide has been produced for the 10019CP thermostatic shower with concealed supply pipes and covers the installation, operation and maintenance. Please read the enclose instructions before commencing installation. WE RECOMMEND THAT THE INSTALLATION OF ANY INTA PRODUCT IS CARRIED OUT BY AN APPROVED INSTALLER. Please read the enclosed instructions before commencing the installation of this product please note; The installation must be carried out strictly in accordance with the Water Supply (Water Fittings) Regulations 1999 and any local water authority regulations. If in any doubt, we recommend that you should contact either your local water authority, the secretary of the Water Regulations Committee at the WRc on Tel: 01495 248454 or The Institute of Plumbing on Tel: 01708 472791. Please check that all the components are in the box, before commencing installation. Technical Specification This thermostatic shower valve is suitable for use on all common types of plumbing system including gravity supplies, fully pumped, modulating combination boilers, unvented water heaters and unbalanced supplies i.e. cold mains & tank fed hot. They are not suitable for non-modulating combination boilers. Designated Pressure Max. Static Pressure Temperature Stability HP 10 bar ± 2 C Inlet Temperature Range 55 C to 65 C: Hot Supply 25 C: Cold Supply BS EN 1111 Working Pressure Ranges 0.5 to 5.0 High Pressure Min Temp Differential (Mix to Hot) for fail-safe 10 C Max. Pressure Inlet Differential 5:1 Preset Temperature 38 C Preparation for Installation Ensure all the parts are present before commencing the installation of any Inta product. Before commencing the installation ensure the site conditions are suitable. The hot and cold supply pipes can be concealed behind a stud wall or embedded into the a solid wall. When installing, care must be taken not to damage / affect the finish of this product. Service valves must be installed in both the hot and cold water supply pipes, in order to isolate the shower valve should servicing be required in the future. Flush the water supply pipes thoroughly prior to installation. Do not allow debris, PTFE or any metal particles enter the shower valve. Turn off the water supply. 1

Installation Instructions Stud Wall 34 Installation with the supply pipes concealed behind a stud wall. Cut 2 holes 24 to 26mm in diameter at 45mm centres in the plaster board or wall plate. Finish tiling the wall cutting 2 holes 24mm to 26mm in the tiles. Insert the shower valve through the two holes and secure with the 2 back nuts, do not over tighten. Connect the hot supply to the lower inlet and the cold to the upper. A swivel to copper connector or an olive and compression nut are 2 typical fittings for making the connections. Connect the flexible hose of the shower kit to the mixed water outlet and secure the rail to the wall. Turn on the water supplies and check joints for leakage. Solid Wall Installation with the supply pipes embedded into a solid wall. Cut a channel into the wall for the supply pipes allowing sufficient depth to position the concealing plates to as shown on the finished tiled surface. Connect the supply pipes to the valve and turn of the water supplies and check for leakage from any joints. Turn off the water supplies. Unscrew the two socket set screws and carefully remove the body and concealing plates. Fill the channel and finish tiling the wall. Seal the holes between inlets and tiles with silicone sealer. Refit the concealing plates and push firmly to the wall surface. Carefully refit the valve and re-tighten the socket set screws. Connect the flexible hose of the shower kit to the mixed water outlet and secure the rail to the wall. Turn on the water supplies and check for correct operation. 132 12 Allen key hexagon G½ 33 50 Mixed water outlet 10 Concealing plate Ø36 4.5 7 45.5 Cold inlet Hot inlet 45 Ctr Plaster board and tiled wall Olive and comp. nut Swivel connector G½ G½ 2

Operation The red button on the temperature control knob locks the mixed water temperature to 38 C, press the button to release the knob to increase the or lower the water temperature. Turning the flow control knob anti-clockwise turns on the water and regulates the amount flowing. Components Retaining screw Cover Temperature control knob Thermostatic cartridge Non return valve Sealing washer Cover Retaining screw Control knob Flow control valve Filter Connection piece Flow Control Valve Replacement Isolate both the hot and cold water supplies Remove the cover and unscrew the control knob retaining screw and remove the flow control knob. Using a suitable spanner unscrew the flow control valve. Replace with a new valve or replace the disk washer as required and assemble in the reverse order. Cartridge Replacement Isolate both the hot and cold water supplies. Remove the cover and unscrew the control knob retaining screw and remove the temperature control knob. Carefully pull the cartridge out of the body If any of the O ring seals or the thermostatic element is blocked or damaged they must be replaced. Using neutral silicon grease re-lubricate the internal moving components of the valve. Re-assemble in the reverse order. The valve must then be re-commissioned following the procedure detailed. 3

Filter Cleaning and Non Return Valve Removal Isolate both the hot and cold water supplies and disconnect the shower riser from the body. Unscrew the 2 socket set screws and carefully pull the body from the inlets. Carefully pull out the non return valves, flush out any debris and check for correct operation. Remove the filters and flush thoroughly, remove any debris collected in front of the filter from the inlets. Replace non return valves and filters if damaged with new. Re-assemble in the reverse order turn on both supplies and check joints for leakage. Aftercare Inta thermostatic shower valves have a high quality finish and should be treated with care. An occasional wipe with a mild washing-up liquid on a soft damp cloth followed by a thorough rinsing is all that is required. Do not use an abrasive or chemical household cleaner as this may cause damage. Additional Information for Holiday Homes Drain Down Procedure 1. Isolate both the hot and cold water supplies to the mixer and for extended periods including the cold water isolating valve from the mains supply. 2. To drain the thermostatic mixer: Remove the shower hose from the mixer or lay the shower head and hose in the shower tray to drain off any trapped water. Turn the bottom water flow control valve fully open. Turn the control knob of the top thermostatic valve fully clockwise to drain cold water, until water stops flowing. Push in the red temperature set button on the thermostatic control knob and turn the control knob fully anti-clockwise to drain the hot water side until water stops flowing. Note: If after draining down, the thermostatic mixing valve is to be left for a long period in cold or freezing conditions, leave the bottom flow control valve open and line up the ridge on the thermostatic control knob with the letter H etched on the tap body. This will leave the hot and cold sides of the mixer partially open to help prevent frost damage. Guarantee This product is guaranteed in line with the individual Holiday Homes manufacturers warranty period. Providing that the product has been installed in accordance with these instructions, the guarantee covers any manufacturing defect or finish. As gold and special effect finishes are softer than chrome plate special care must be taken when cleaning, see Aftercare. The guarantee does not cover: Direct or indirect damage caused by the mixer. Damage caused by faulty installation or maintenance. Damage caused by improper use of the mixer. Damage caused by using unsuitable cleaning products - see Aftercare. 4

IMPORTANT The following information is required when the thermostatic shower valve is used in a TMV2 Applications under the requirements of BS EN 1111: 1999 Sanitary tapware Thermostatic Mixing Valve (PN 10) General Technical Specification Supply Conditions The supply conditions to the Thermostatic Mixing Shower Valve must comply with the following; Conditions High Pressure Maximum Static Pressure bar 10 Flow Pressure, Hot & Cold bar 0.5 to 5 Hot Supply Temperature C 55 to 65 Cold Supply Temperature C 25 C Note: Valves operating outside these conditions cannot be guaranteed by the Scheme to operate as type 2 valves. The valves designation of use, HP if tested against BS EN 1111. For valves designated for use HP only, if a water supply is fed by gravity then the supply pressures should be verified to ensure the conditions of use are appropriate for the valve. Introduction The thermostatic shower valve has been specifically designed and manufactured to meet the requirements of BS EN 1111:1999 and TMV2 Type Scheme. The valve has been independently tested and approved as a TYPE 2 valve under the BuildCert TMV2 scheme by the NSF-WRc Limited/Buildcert Limited.. Application The thermostatic mixing shower valve has been independently tested by WRc and certified as meeting the requirements of the BS EN 1111:1999 under the TMV2 Scheme as being suitable for use on the following designations. Recommended Outlet Temperatures The BuildCert TMV scheme recommends the following set maximum mixed water out let temperatures for use in all premises: Code Application Recommended Hot Water Temperature HP-S Shower 41 C The mixed water temperature must never exceed 43 C. The maximum mixed water temperature can be 2 C above the recommended maximum set outlet temperature. 5

Recommended Outlet Temperatures Note: 43 C is the maximum mixed water temperature from the shower. The maximum temperature takes account of the allowable tolerances inherent in thermostatic shower valves and temperature losses. Installation It is not a safe bathing Temperature for adults or children. The British Burns Association recommends 37 to 37.5 C as a comfortable bathing temperature for children. In premises covered by the Care Standard Act 2000, the maximum mixed water outlet temperature is 43 C. Important: - The following instructions must be read prior to the installation of the thermostatic shower valve. The installer of the thermostatic shower valve must comply with the requirements of the Water supply (Water Fittings) Regulations 1999 and also be aware of their responsibility and duty of care to ensure that all aspects of the installation comply with the regulations. It has been brought to our attention that flushing water systems using certain chemicals may wholly or partially remove the lubricant from the internal workings of the valve, which may adversely affect its performance. We recommend that following flushing the system with chemicals; valves are checked for correct operation. 1. It is essential that before installing any thermostatic shower valve to ensure that the supply conditions of the system to which the valve is intended to be fitted are checked to confirm compliance with the parameters as quoted within the technical specification and conditions on which the approval is granted i.e. verify supply temperatures, supply pressures, risk assessment. 2. Consideration must be made for the possibility of multiple / simultaneous demands being made on the supply system whilst the thermostatic shower valve is in use, all practical precautions must be made to ensure that the valve is not affected. Failure to make provision within the pipe sizing etc. will affect the performance of the shower valve. 3. The supply to which the thermostatic shower valve is to be installed must be thoroughly flushed and cleaned to remove any debris, which may have accumulated during the installation. Failure to remove any debris will affect the performance and the manufacturer s warranty of the product. In areas that are subject to aggressive water, provision must be made to treat the supplies prior to the supplies entering the shower valve. 4. The thermostatic shower valve has been designed for vertical installation and surface mounting. 5. The thermostatic shower valve will be installed in such a position that maintenance of its components, associated valves and the commissioning and testing of the shower valve can be undertaken. 6. The hot and cold water supplies must be connected to the valve strictly in accordance with the indications on the body of the valve i.e. hot water supply to the hot port of the valve. 7. In a situation where one or both of the water supplies are excessive, it is recommended to fit a Pressure Reducing Valve to reduce the pressure(s) to within the limits as quoted previously. 8. Any thermostatic shower valve must be fitted with a back flow prevention device, such as check valves to prevent the cross contamination of supplies. The thermostatic shower valve is supplied complete with integral insert check valves and strainers. 6

Installation 9. The fitting of isolation valves is required as close as is practicable to the water supply inlets of the thermostatic shower valve. 10. The fitting of strainers is recommended as close as is practicable to the water supply inlets of the thermostatic shower valve. 11. It is essential that the fail safe thermostatic shower valve should not be installed in situations where there is a possibility of the valve being deprived of water or where demands for water are greater than the actual stored supplies. 12. To ensure that the performance levels of the thermostatic shower valve are maintained (in the event of cold water failure), the temperature of the hot water supply at the point of entry to the thermostatic shower valve must be a minimum of 10 C above the commissioned mixed water discharge temperature. 13. The fail-safe thermostatic shower valve must not be subject to any extreme temperature variations either during the installation or under normal operating conditions. Commissioning Important: - The following instructions must be read and understood prior to commissioning the thermostatic shower valve. If under any circumstances there are aspects to the installation / system which do not comply with the specification laid down, the valve MUST NOT be put into operation until the system / installation complies with the specification. However if all these conditions are met, proceed to set the temperature as follows; 1. Ensure that the system is thoroughly cleaned and free from any debris prior to commissioning the thermostatic shower valve. 2. Commissioning the temperatures must be carried out using a suitably calibrated thermometer preferably a digital thermometer. The sensing part of the thermometer probe must be fully submerged in the water when testing. 3. The valve must be commissioned taking into consideration any fluctuations, which may occur within the system due to simultaneous demands. It is advisable that any outlets which are connected to the same supply as the shower valve are open during setting of the mixed water temperature. It is advisable to ensure that the water temperatures are established before any attempt to commission. 4. Once the supply temperatures are stable and the normal operating conditions are established, the shower valve can be commissioned. The following sequence should be followed when commissioning the valve; 4.1 The first step in commissioning a thermostatic shower valve is to check the following: The designation of the thermostatic shower valve matches the application The supply pressures are within the valve s operating range. The supply temperatures are within the valve s operating range. Isolating valves (and Y strainers preferred) are provided. 4.2 If all these conditions are met, proceed to set the temperature as stipulated in the manufacturer s installation instructions. 7

Commissioning 4.3 Measure and record the temperature of the hot and cold water supplies at the connection to the valve. 4.4 Measure and record the temperature of the water discharging from the valve. 4.5 Isolate the cold water supply to the valve and monitor the mixed water temperature. 4.6 Measure and record the maximum mixed water temperature and the final temperature. The final temperature found during the test should not exceed the values quoted. 4.7 Record all the equipment used during the commissioning. 4.8 The mixed water temperature at the terminal fitting must never exceed 2 C above the set temperature. 5. If the mixed water temperature exceeds the recommended temperature of 41 C by 2 C or does not reach 41 C the shower valve can be adjusted as follows: 5.1 With stable supply conditions remove the temperature control knob. 5.2 Rotate the temperature control knob by one spline clockwise to increase the temperature and one spline anticlockwise to reduce it. 5.3 Measure the water discharging from the shower. 5.4 Repeat 5.2 until the desired temperature is stabilised and record the temperature. 5.5 Repeat 4.4 and 4.5 5.6 Secure the temperature control knob with the retaining screw and re-fit the cover. 6. The above information must be recorded and updated on every occasion when any work is carried out on the valve. In Service Testing It is a requirement that all TMV2 approved valves shall be verified against the original set temperature results once a year. When commissioning / testing is due the following performance checks shall be carried out. 1. Measure the mixed water temperature at the outlet. 2. Carry out the cold water supply isolation test by isolating the cold water supply to the shower, wait for five seconds if water is still flowing check that the temperature is below 43 C. 3. If there is no significant change to the set outlet temperature (±2 C or less from the original settings) and the fail-safe shut off is functioning, then the valve is working correctly and no further service work is required. 8

In Service Testing Notes: If there is a residual flow during the commissioning or the annual verification (cold water supply isolation test), then this is acceptable providing the temperature of the water seeping from the valve is no more than 2 C above the designated maximum mixed water outlet temperature setting of the valve. Temperature readings should be taken at the normal flow rate after allowing for the system to stabilise. The sensing part of the thermometer probe must be fully submerged in the water that is to be tested. Any thermostatic shower that has been adjusted or serviced must be re-commissioned and re-tested in accordance with the manufacturers instructions. Please leave this Manual for the User To active your product warranty please visit www.intatec.co.uk and click on Product Registration Intatec Ltd Airfield Industrial Estate Hixon Staffordshire ST18 0PF E & O.E Tel: 01889 272 180 Fax: 01889 272 181 email: sales@intatec.co.uk web: www.intatec.co.uk Intatec Ltd. 2014 30-06-14