Installation and Operating Instructions. MPPT Solar System Controller ISC3042

Similar documents
Installation and operating instructions. Solar charge controller Solarix MPPT Z Z

12 Volt 30 Amp Digital Solar Charge Controller

LS1024B / LS2024B/ LS3024B. Solar Charge Controller USER MANUAL

EPSOLAR LS0512R / LS0524R. Solar Light Controller INSTRUCTION MANUAL. Please read this manual carefully before using the product!

Tracer-1206RN / 1210RN / 1215RN. Maximum Power Point Tracking Solar Charge Controller INSTRUCTION MANUAL

12 Volt 30 Amp Digital Solar Charge Controller Installation & Operation Manual

Solar Controller / Battery Charger User s Manual

INSTRUCTION MANUAL EPSOLAR. Tracer-2210RN / 2215RN. Maximum Power Point Tracking Solar Charge Controller

Manual. Solar Fountain Mobile Phone Charger

SOLAR POWER - THE NEW WAY TO RV!

400 Amp Rechargeable Jump Start System RAC-HP082

3000W Power Inverter

MANUAL D250S DUAL. Solar panel + Vehicle ground/solar panel

Solar Wind Microhydro Water Pumping Inverters Batteries Professional system design and installation

Instructions: Retain these instructions for future reference SmartChargePro35 RSCPR35-12v, 2 / 8 / 16 / 35A

BlueSolar Pro Remote Panel For BlueSolar PWM-Pro charge controllers 12/24V 5, 10, 20, 30A Article number SCC

MANUAL. * Supply plugs may differ to suit your wall socket. EN 3. Continue to press the MODE-button to combine charging program with charging options.

S10I / S20I / S30I Solar Light Controller USER MANNUAL

TIG INVERTER INSTRUCTION MANUAL

BATTERY CHARGING GUIDELINES FOR 6-VOLT DEEP CYCLE BATTERIES

PHOTOVOLTAIC SYSTEM CONTROLLERS SUNSAVER MODELS INCLUDED IN THIS MANUAL SS-6 / SS-6L SS-10 / SS-10L SS-10-24V / SS-10L-24V SS-20L SS-20L-24V

How To Control A Battery Cell Phone With A Battery Power Control System

MULTI XS 4003 Battery charger

How To Use A Power Supply Unit (Upu)

User s Manual Before using the inverter, you need to read and save the safety instructions.

Charge Regulator SCR 12 Marine

LESTRONIC DV AUTOMATIC 12 OR 24 VOLT DUAL OUTPUT DUAL MODE BATTERY CHARGER MODEL TYPE 12/24EL40-10ET

SOLAR BOOST 2000E 25AMP 12VDC MAXIMUM POWER POINT TRACKING PHOTOVOLTAIC CHARGE CONTROLLER INSTALLATION AND OPERATION MANUAL

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF

USER S MANUAL. MaxPower UPS. Uninterruptible Power System 28-2MAXPO0018

Solar charger controller User s Manual

MULTI XS Battery charger. For lead-acid batteries 1,2-120Ah

User s Manual AURORA 1.2K/2.2K

2 Installation Explanation

EN 3 ABSORPTION, READY TO USE ANALYSE BULK DESULPHATION SOFT START. L: 2000 mm MODE- BUTTON SUPPLY PLUG* SUPPLY

TELEDYNE BATTERY PRODUCTS. INSTRUCTIONS FOR CONTINUED AIRWORTHINESS and COMPONENT MAINTENANCE MANUAL. For

Battery Power Inverters

LITHIUM BALANCE CHARGER

MANUAL EN 3. Continue to press the MODE-button to combine charging program with charging options.

User Manual. Hybrid 1KW-5KW INVERTER / CHARGER. Version: 1.1

BATTERY CHARGER MULTI US 7000

BC-5000 OPERATIONS MANUAL BATTERY CAPACITY TESTER COFKO LLC.

POWER TO GET THE JOB DONE

BATTERY BOX INSTALLATION WARNING WARNING CAUTION ATTENTION AVERTISSEMENT ADVERTENCIA PRECAUCIÓN SOLBBOX12V CARTON INVENTORY COMPLETED OVERVIEW

Installation Instructions for Solar Pumps USER MANUAL FOR SPS, SPC, SPSC SPQB, SPGJ SERIES SOLAR PUMPS AND PUMP CONTROLLERS

13 Watt PORTABLE SOLAR POWER KIT

Battery Charger For Nickel Cadmium and Nickel-Metal Hydride Rechargeable Batteries Model PSN Series

ENGLISH INSTRUCTION & INSTALLATION MANUAL DUCTLESS MINI SPLIT AIR CONDITIONING SYSTEMS

MANUAL EN 3 SUPPLY PLUG* MAINS CABLE CTEK COMFORT CONNECT ABSORPTION, READY TO USE ANALYSE FLOAT, FULLY CHARGED PULSE, MAINTENANCE CHARGING

IMPORTANT SAFETY INSTRUCTIONS WARNING READ AND SAVE THESE OPERATING AND SAFETY INSTRUCTIONS BEFORE USING THIS HEATER.

PSC-A5 Solar Charge Controller Manual

VLT Series 300 Watt True Sine Wave Inverter

30W SOLAR CHARGING STATION

Home Solar Kit Owner s Manual. Model: HS

Height w/o Terminals (in)

GV-Boost Manual. 8A Input / W IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS. Solar Charge Controllers with Maximum Power Point Tracking

If you accidentally get battery acid on your skin, flush it with lots of water

White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5

User Manual DONGGUAN SHENGYANG INDUSTRIAL CO., LTD. SY WMVC Smart Grid Tie Microinverter. Dongguan Shengyang Industrial Co., Ltd.

O. Gas boiler. Gaz 6000 W WBN H-E-N/L-S2400. Operating instructions for the end customer (2014/07) en

View Star series. Solar Charge Controller INSTRUCTION MANUAL

DAB+ / FM Tuner Model: TU-201

SOLAR ELECTRIC MODULE ES-124 & ES-62T Owners Manual and Installation Guide

Dear Neuton Owner, This is a helpful hint to guide you in getting the most out of your NEUTON Battery and Charger.

OWNER S MANUAL 2.5/3.0 ACS PANEL (ADVANCED CONTROL SYSTEM) 7725 Lougheed Highway Burnaby, BC V5A 4V8 Canada

User Manual HomeGrid 3000 Solar Generator

Automatik-Lader AL 600 Automatic Charger AL 600 fcr V / for V. Best.-Nr. : / Order No

OUTPUT CABLE CONNECTIONS:

Instruction manual. Electrobloc EBL 100-2

Manual for Fire Suppression & Methane Detection System

Product catalogue. solar charge controller & inverter BEIJING EPSOLAR TECHNOLOGY CO., LTD. Tel: Fax:

Installation and Operating Instructions (for chargers shown below)

SPECIFICATIONS. Recommended Battery sizes (Maintenance) AUTOMOTIVE CCA CCA MARINE MCA MCA DEEP CYCLE 17 55Ah 17 80Ah

Portable Air Conditioner

YSmart Technology Co.,Ltd

1. Connect the charger to the battery. 2. Connect the charger to the wall socket. 3. Press the MODE-button to select charging program.

Home Solar Kit Owner s Manual. Model: HS

AUTOMATIC BEST BATTERY SELECTOR INSTALLATION & OPERATION BBS-1600 BBS-1600E

Mounting instruction Read instructions carefully!

Mobile Data Power Model: MDP-25

Solar Home System. User Manual. AEH-SHS01-10W2L Solar Home System 2 Lamps

AUTO CHARGE 3 STEP AUTOMATIC BATTERY CHARGER

User Manual THR840DUK Digital Thermostat

Carefree Sealed Lead Acid (SLA) MSDS

ST Series POWER SUPPLIES USER INSTRUCTIONS

Drayton Digistat +2RF/+3RF

Installation/Operator Manual For use with WFCO ULTRA III Power Center Model WF-8712P and WF-8725P

2/8/12 AMP Smart Charger OWNER S MANUAL

TruPower-Portable-500W. Solar Starter kit

MAKING MODERN LIVING POSSIBLE. UniLynx Indoor User Manual. ULX 1800i ULX 3000i ULX 3600i ULX 5400i SOLAR INVERTERS

Instructions: Part I. Charge the Power Bank. Method 1. Charge the Power Bank via Computer USB Terminal.

T4X BAT TERY CHARGER. Before reading, unfold the page containing the illustrations and familiarise yourself with all functions of the device.

LEAD CRYSTAL. User Manual. Valve-regulated lead-crystal batteries Energy storage Cells

Manual Ranging MultiMeter

Installation and Operation Guide for PD4100 Series Power Control Centers

Installation Instructions for Alarm Module Kit A043F059

BARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell

CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN

TROUBLESHOOTING GUIDE

Instruction manual for Firstline FCS12000CH

Transcription:

Installation and Operating Instructions MPPT Solar System Controller ISC3042

ABOUT THIS MANUAL These operating instructions come with the product and should be kept with it as a reference to all user s of the product. Read these operating instructions carefully before use, Keep them over the entire life of the product, And pass then on to any future owner or user of this product. This manual describes the installation, function, operation and maintenance of the solar system controller ISC3042. These operating instructions are intended for end customers. A technical expert must be consulted in cases of uncertainty. SAFETY 1. The solar controller may only be used in PV systems for charging Lead-Acid type batteries. This includes: SLA, VRLA, Lead-Calcium, AGM and GEL. Note; User s should always refer to battery manufacturer/supplier s recommended values for battery charging settings and float voltage setting. 2. No energy source other than a solar panel (PV) may be connected to the solar charge controller. 3. Do not connect any defective or damaged measuring equipment. 4. Follow the general and national safety and accident prevention regulation. 5. Never alter or remove the factory plates and identification labels. 6. Keep children away from PV & Battery systems. 7. Never open the device. (No user serviceable parts inside) 8. One set solar module can connect with one controller only. 9. Never touch bare cables. OTHER RISKS Danger of fire and explosion Do not use the solar charge controller in dusty environments, in the vicinity of solvents or where inflammable gases and vapors can occur. No open fires, flames or sparks in the vicinity of the batteries. Ensure that the room is adequately ventilated. Check the charging process regularly. Follow the charging instructions of the battery manufacturer. Battery acid Acid splashes on skin or clothing should be immediately treated with soap suds and rinsed with plenty of water. If acid splashes into the eyes, immediately rinse with plenty of water. Seek medical advice. 2

Function The solar system controller is designed to: Monitor the state of charge of the battery; Control the charging process, Control the connection/disconnection of loads, Make sure solar system works at max possible power. Features Charging Voltage is user programmable. Load Terminal switches Positive side. Manual load switch with automatic re-start. Night-Light Functions Set the two timer schedule programmable for street light application Performs the MPPT algorithm to harvest the maximum power available from the solar panel. Caution Users should seek advice if any of the following situations occur: The solar charge controller does not appear to function at all. The solar charge controller or connected cables are visibly damaged. Emission of smoke or fluid penetration. When parts are loose. In the event of such an occurrence, If possible and safe to do so immediately disconnect the solar charge controller from the solar panels and battery and insulate cable conductors. -------------------------------------------------------------- MPPT means "Maximum Power Point Tracking". This refers to the type of advanced electronic circuits used to harvest Maximum Power from your solar panel(s). The Maximum Power Point of PV systems can vary depending on the prevalent conditions, such as the temperature and solar irradiation levels. This controller establishes and Tracks the most efficient operating point of the solar panel enabling it to deliver the maximum available power to the battery. Operating the controller The display shows a variety of system data by symbols and digits. Four buttons control all settings and display windows. 1. Display and operation LCD display for controller information and messages. Page down button Manual load switch, or confirmation button in program mode (Enter button) Page up button Button for switching display windows or calling up the settings (Menu button) 3

2. Display window Change the display windows with the Menu button; (e.g. for 12V battery) 1. The default window will show like below, battery voltage/capacity volume of the battery. 2. Press menu button once to check charging current. 3. Press menu button again to display the load current. 4. When the charging current or output current is less than 0.5Amp, the LCD will always show Min A. When there is no current, it will show 0 Amp. CHARGING CURRENT (<0.5A) OUTPUT CURRENT (<0.5A) 4

5. If solar module cannot provide current or the current is less than 1Amp for 5 minutes, the controller will switch to Night mode and display in the lower right hand corner. 6. When the unit is in the default display mode, Pressing the enter button will turn the load ON or OFF manually. The arrow/lamp symbol will be displayed when the load terminal is ON. 3. How to set the system time. 1. At default display mode, press menu button 3 times to show controller s system time to you. In this mode, press enter button once, the hours will flash, you can adjust the figure via Pageup / Pagedown button, press enter button one more time to confirm the setup for Hour and switch to Minute setup mode, you can adjust the figure of minute via Page up/page down button, once it s done, press enter button to save. 2. Charging Voltage Check & Program Press menu button 4 times. Window will switch to show BULK voltage setting. To change this setting; Press enter button once, you can program charge voltage via Pageup/Pagedown button: 12V Battery (13.8V-14.8V); 24V Battery (27.6V-29.6V) Press enter or menu button to save setting. 3. Press menu button 5 times. Window will switch to show FLOAT voltage setting. To change this setting; Press enter button once; you can program Float voltage via Pageup/Pagedown button: 12V Battery (13.0V-14.2V); 24V Battery (26.0V-28.4V) Press enter or menu button to save setting. 4. You can set the FLOAT Voltage to automatically adjust (trim) voltage, based on the ambient temperature: In the FLOAT setup interface press enter button once; use the Pagedown button until LCD displays OFF. Float voltage will vary accordingly to the ambient temperatures stated below: 12V System: 0 C. (14.2-14.4v), 0 C - 20 C (13.8-14.4v), 20 C (13.5-14.4v) 24V System: 0 C. (28.4-28.8v), 0 C - 20 C (27.8-28.8v), 20 C (26.9-28.8v) 5

4. Night-Light Function (NLF) setup. Press menu button 6 times. Window will switch to NLF setup interface. Press enter button once, through Pageup/Pagedown buttons, choose ON and then confirm by enter button. After NLF on, press menu button, window switch to Timer1 setup interface. Press enter button once, you can adjust the Hour (1-12hours) via Pageup/Pagedown buttons, and then confirm it by pressing enter. Timer1 hours stands for the time the load terminal will be switched ON. Press menu button again, window switch to Timer2 setup interface. Press enter button once, you can adjust the Hour (1-12hours) via Page up/page down buttons, and then confirm it by pressing "enter. Timer2 hours stands for the time the load will be OFF after Timer1 hours have finished. NOTE: When the Timer2 hours are finished, the load will turn ON again until dawn. (See Diagram below) If you want the load to stay OFF for the remainder of the night, make sure Timer2 hours are sufficient to reach dawn. The ISC3042 recognizes day and night based on the solar array voltage NLF (Night mode) will start when the PV Input Voltage falls below 10 Volts.. Standard Controller Mode = NLF set to OFF, (See Item # 9.1 Page 7) 6

5. Timer1 and Timer2 setup. To change Timer settings you must first make sure that NLF is set to OFF 9.1. Check that NLF (Night light function) is set to OFF by pressing the menu (page) button 6 times from the main default screen. Window will switch to NLF setup interface. Press the enter button once, through Pageup/Pagedown buttons, choose OFF and then confirm by enter button. 9.2 From the main default screen press the menu button 7 times, Timer1 screen will appear. 9.3 Press the enter button once. Then adjust Hour via Pageup/Pagedown buttons. Press the enter button to confirm the hour setting and switch to Minute adjustment. Use Pageup/Pagedown buttons to adjust Minute. Press enter button to confirm minute setting. Now using Pageup/Pagedown buttons; choose ON or OFF or ON/OFF and then confirm by enter button. ON stands for the time when you want to turn the load on. OFF stands for the time when you want to turn the load off. ON/OFF means the Timer is disabled. 9.4 From the main default screen press the menu button 8 times, Timer2 screen will appear. Follow step 9.3 operation as per above. Timer1 and Timer2 setup should now be complete; you can confirm these settings by using the menu key to scroll through to Timer1 and Timer2 screens FEATURES 1. PWM Charge control - Depending on the actual battery level, various charging procedures, float charging and boost charging are automatically performed. 2. Deep discharging protection - If the battery falls below a specified voltage (11.0V/22V), the load output is disconnected preventing excessive discharge of the battery. Once the voltage increases to 12.0V/24V the load will be automatically re-connected. The set points of the deep discharging protection are predefined and cannot be reset. 3. Two timers can be set to turn the loads on and off automatically. 4. Temperature Compensation ISC3042 has an internal ambient temperature sensor that compensates during the float mode. This functions only when float voltage setup is set to OFF (See item no. 4 page 5) 5. MPPT function - Implementing the latest MPPT technology the controller is able to harness the panels maximum available output at all times. 6. 5V USB output provides 5Vdc/ 500mA power supplier 7

INSTALLATION Install the controller in a ventilated area away from flammable materials and gases. The surface should be solid, even, dry and nonflammable. The battery to controller cable should be as short as possible (1-2mtrs is ideal) and be of a suitable diameter to minimize voltage loss. Do not assemble outdoor, the unit should be installed in the way to be protected against humidity, dripping, rainwater as well as direct and indirect heat (sunlight). To ensure the air circulation for cooling an area of 15cm on each side of the unit must be kept free. The LCD display should be protected against UV rays (e.g. sunlight). Long time exposure to UV rays can permanently discolor the LCD. The solar charge controller may only be connected to the local loads and the battery by trained personnel and in accordance with any applicable regulations. Follow the installation and operating instructions for all components of the PV system. Ensure that no cables are damaged. Ensure that polarity of Solar panel/battery/load is correct and use only insulated tools. WARNING ISC3042 can work with input voltage up to 65 V DC maximum; when installing at this voltage, particularly with regard to module open circuit voltage (Voc), the entire solar energy system must be installed with protection class II. Cover solar modules during installation and use only insulated tools. GROUNDING Grounding ISC3042 is not technically required when installing a stand alone solar system. However, if required, Common grounding of the negative Battery and Load control output is OK (for negative earth electrical systems such as a caravan or motor-home). Note: ISC3042 can ground the negative only, and PV array Output should NOT be grounded. CONNECTING / DIS-CONECTING SYSTEM SEQUENCE Connect the wires in the sequence from 1 to 6 according the above diagram; when Disconnect the wires in the REVERSE sequence from 6 to 1 according the above diagram. Use with 12V or 24V battery bank, (controller will detect voltage of battery automatically). Never exceed the nominal ratings (see below technical data for reference). Suggested cable length, 10m solar panel connection cable/2m battery connection cable/5m load connection cable. 8

TECHNICAL INFORMATION Max. Input Current Max. Input Open Circuit Voltage (Voc) 30A dc 65Vdc Max. Load Current Adjustable Charge Voltage(Bulk) Adjustable Charge Voltage(Float) 30Adc 13.8-14.8V / 27.6V-29.6V 13.0-14.2V / 26.0V-28.4V Low Voltage Disconnect 11.0 / 22.0V dc ±2% Auto Reconnect Voltage 12.0 / 24.0V dc ±2% Output Voltage Typical Idle Consumption Operating temperature 12/24V dc <50mA dc -20 C/+50 C Remark: ISC3042 is suitable for 12V or 24V system, you can use a 24V solar panel to charge a 12V battery, but 12V solar panel cannot be used to charge a 24V battery. Charging Curve Bulk Absorption Float Bulk: This is the first stage (Constant Current) where the battery is in a low charge state. During this stage the controller delivers all of the available solar power to the Battery system. Absorption: In this stage (Constant Voltage) the controller charges at a constant voltage as the amount of current required to charge the battery is decreasing. The constant voltage regulation prevents overheating and excessive battery out-gassing; this stage will end when the battery charge current reduces to below 3 Amps OR after 3 hours of entering absorption mode. Float (Maintenance): After the battery is fully charged, the controller reduces to a lower Constant Voltage setting to maintain the Battery (also called trickle charge). Protection functions Overcharge protection Deep discharge protection Battery under-voltage protection Solar panel reverse current protection The following installation faults do not destroy the controller. After correcting fault, the device will continue to operate correctly: Overcharge protection Deep discharge protection Reverse polarity protection of load, panel and battery Automatic electronic fuse Short circuit protection of load and panel Over voltage protection at panel input Open circuit protection without battery Reverse current protection at night Overload protection Battery over voltage shutdown 9

MAINTENANCE The controller is maintenance-free. We strong suggest that all components of the PV system must be checked at least annually, Ensure adequate ventilation of the cooling element Check the cable strain relief Check that all cable connections are secure Tighten screws if necessary Terminal corrosion ERROR MESSAGES Caution! Please do not open the controller or attempt to replace components when troubleshooting. Improper maintenance can be hazardous to the user and the system. If the controller detects errors or unauthorized operating states, it shows error codes on the display. Error codes can generally be differentiated, whether there is a temporary malfunction, e.g. regulator overload or a more serious system error that can be remedied by appropriate external measures. Since not all errors can be simultaneously displayed, the error with the highest error number (priority) is displayed. If several errors are present, the second error code is displayed after remedying the more significant error. The following meaning is assigned to the different error codes: 1. Meaning: Battery reverse polarity warning Remedy: Reconnect battery correctly. 2. Meaning: Battery Voltage (Too high or too low) Remedy: Check battery voltage it might be too low or too high, possible recharge battery manually. If battery can t be recharged, Replace battery & re-check. 10

3. Meaning: Module current too high. Remedy: Reduce the input current (module power) to <30Amps. 4. Meaning: Over current at the load output. Remedy: 1) Reduce load current to <30Amps.. 2) If reducing load current does not work; Press Enter button. If LCD shows E4 with NO load connected or, LCD shows current as 0.00A. WITH a load of more than 50Watts running, Then follow the Reset Procedure as follows; 3) Reset: Dis-connect the unit by removing all connections in Reverse sequence from 6 to 1 (see Page 8), then follow the reset procedure: i. While holding down the Menu button, re-connect the Battery terminals to the unit. ii. Release the Menu button, this will prompt the LCD to show FFFF iii. First connect the PV then the Load terminals NOTE: Always connect the Negative first, then the Positive for all connections 5. Meaning: Meaning not enough sunlight to charge the battery. 11

The Leading Edge in Solar Technology Waste electrical products should not be disposed of with household waste Please recycle where facilities exist Check with your local authority or retailer for recycling advice : Specifications are subject to change without prior notice Copyright reserved by ProVista Technology Limited Instruction manual Ver. 2.1 12