COOPER POWER SERIES. Edison single-phase vacuum capacitor switch installation and operation instructions. Vacuum Switches MN230007EN

Similar documents
Step 1. Item 6. Item 1

Installation, Operation and Maintenance Instructions Viper -S Solid Dielectric Reclosers Three Phase, Vacuum Recloser.

Medium voltage VCP-W MR2 (integral racking)

Safety Manual BT50(T) Safety relay / Expansion relay

Installation instructions for Series NRX INCOM communications adapter module

Installation Instructions for EHD, EDB, EDS, ED, EDH, EDC, FDB, FD, HFD, FDC, HFDDC Circuit Breakers and Molded Case Switches

Model 1756 Test Lead Kit

Instructions For SF 6 Refill Kit

Seven function digital multimeter

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

Owner s Manual. For Automatic Transfer Switch Amp, Service Entrance/Non-Service Entrance

MCR1900 Media Converter 19-Slot Chassis

Advantium 2 Plus Alarm

Tina 2A/B Adaptor unit

Replacement of 600-Ampere Bushing and 200-Ampere Bushing-Well Adapters

Original instructions Tina 3A/Aps Adaptor unit

12-Volt 10-Amp Regulated Power Supply

Arc Flash Avoidance and its Application to Overhead Traveling Cranes

Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms

Owner s Manual & Safety Instructions

WIRE AND CABLE ENGINEERING GUIDE

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES

Installer s Guide WARNING: 18-GJ11D1-2. Ultraviolet (UV-C) Lamp Kit for 2-5 Ton Air Handlers HAZARDOUS VOLTAGE - DISCONNECT POWER BEFORE SERVICING

, User s Manual

ATS Overhead Table Shelf System INSTRUCTION MANUAL

Smile 11 AS-i Emergency stop with safe AS-i input node

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp and 1250 Amp

Installation. Smart-UPS VT MGE Galaxy Maintenance Bypass Panel kva 400 V

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013

PART 1 - INTRODUCTION...

Machine Safety Switch: SI-LM40 Series Limit Switch Style

The table below lists the symbols used on the Clamp and/or in this manual. Important Information. See manual.

Eaton Generator and Automatic Transfer Switch Generator Start Connection Diagrams

SC Series: MIS Chip Capacitors

Lightning Arresters P KVA P KVA. Description & Installation

DTM04 TANK MONITOR DTM08 TANK MONITOR Dtm12 TANK MONITOR. Installation and Operation Manual

Ceiling Mount Air Handler Manual

Unified requirements for systems with voltages above 1 kv up to 15 kv

1 POLE - 16A 80A Inrush type. (b) Contact configuration A : 1 form A (SPST-NO) C : 1 form C (SPDT) (standard type "K" only)

Insulation Resistance Testing of Low Voltage Cables in the Field

VAQ. Built-in V-series Miniature Basic Switch for Compatibility with Business and Consumer Equipment. Pushbutton Switch (Cylindrical 10.5-dia.

This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules.

Type K current limiting fuse canister Technical information and installation guide

Reliance DuraStar ORDINARY LOCATION INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS

RI-215A Operator s Manual. Part Number: RK Revision 0 Released: 10/3/05

NFC Communication Tray Model: HHX-IT3-Z

UniStream CPU-for-Panel

StorTrends 3400 Hardware Guide for Onsite Support

SBC90. Abrasive Blast Cabinet Assembly & Operating Instructions

INSTRUCTIONS FOR MAGNUM DS TRIP UNIT TESTING USING TEST KIT SYLES 140D481G02R, 140D481G02RR, 140D481G03 AND 140D481G04

TTL to RS232 Adapter User Guide

LESTRONIC DV AUTOMATIC 12 OR 24 VOLT DUAL OUTPUT DUAL MODE BATTERY CHARGER MODEL TYPE 12/24EL40-10ET

Operating Instructions

Elektromotoren und Gerätebau Barleben GmbH

OPERATOR S MANUAL 18 VOLT, 1 HOUR CHARGER

High-Voltage Compact Switchgear 3AP1 DTC for 145 kv and 245 kv

Arc Flash Hazards. Electrical Hazards. Dan Neeser Field Application Engineer Electrical Hazards 2/18/2015. Shock.

SOLAR ELECTRIC MODULE ES-124 & ES-62T Owners Manual and Installation Guide

EE-SPY801/802. Photomicrosensors for detecting wafer-carrier mounting. Wafer-carrier Mounting Photomicrosensors. Ordering Information.

DLP-PU/E Instruction Manual

Single Phase Soft Starter

Series /16 DIN Multi-Mode Bar Graph Display Timer TIMERS PRODUCT HIGHLIGHTS

ABR Brake Rectifier Instruction Manual

CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH

Pressure monitoring equipment for oil-sf 6. bushings, type GOEK

DRM75A 230V 20/100A DIN rail single phase two wire energy meter

Mounting Instructions. Torque Transducer. A en

Instruction Bulletin. MCS025 Sync-Check Module Installation Sheet


WSD130 SOLDERING STATION

How To Use A Power Supply Unit (Upu)

WE-350 Series ¼ Turn Electric Actuator

Owner's/Installation Manual

What are the basic electrical safety issues and remedies in solar photovoltaic installations?

UNIVERSAL LUMBAR INSTALLATION INSTRUCTIONS

DC disconnects for solar photovoltaic installations. Connecting the. power of the sun

Manual. Solar Fountain Mobile Phone Charger

G670 Intermittent Pilot Ignition Controls

USER MANUAL Stand Alone Power Supply PSQ 2909 / PSQ 3909 / PSQ 4909 PSQ 2920 / PSQ 3920 / PSQ 4920

AMPSEAL* Automotive Plug Connector and Header Assembly

Leak Detection System

WARNING: FAILURE TO FOLLOW THESE RULES MAY RESULT IN SERIOUS PERSONAL INJURY CAUTION: INSTALLATION LOCATION:

PLUGS & RECEPTACLES. INNOVATIVE EXPLOSION PROTECTION by R. STAHL

Engineering innovation

ALPHA Meter Installation Information

Detection System Model 500 Series Owner s Manual

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points

Three-phase monitoring relay CM-PFE

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

7 FUNCTION DIGITAL MULTIMETER

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

Owner s Manual & Safety Instructions

User Manual. English. APC Smart-UPS SC. 1000/1500 VA 110/120/230 Vac. 2U Tower/Rack-Mount Uninterruptible Power Supply

Elektromotoren und Gerätebau Barleben GmbH

Pet hair clipper. Model Diagrams within this manual may not be drawn proportionally.

Installation and safety instructions for AC/DC built-in devices

SlimSeal SSL Connector. Now Available in 1 Position. Free Hanging Version

Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves

Packaged Terminal Air Conditioner Wall Sleeve Installation

Transcription:

Vacuum Switches MN230007EN Effective November 2016 Supersedes March 2014 (S230-50-1) COOPER POWER Edison single-phase vacuum capacitor switch installation and operation instructions SERIES

DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information, recommendations, descriptions and safety notations in this document are based on Eaton Corporation s ( Eaton ) experience and judgment and may not cover all contingencies. If further information is required, an Eaton sales office should be consulted. Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser. THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES. In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or other-wise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations and descriptions contained herein. The information contained in this manual is subject to change without notice. i

Contents DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY... I SAFETY FOR LIFE... III SAFETY INFORMATION... III Safety instructions... iii PRODUCT INFORMATION.... 1 Introduction...1 Read this manual first...1 Additional information...1 Acceptance and initial inspection...1 Handling and storage...1 Standards...1 Quality standards................................................................................1 Description of operation...1 RATINGS AND SPECIFICATIONS.... 2 Check switch ratings before installation...2 Ratings...2 INSTALLATION PROCEDURE.... 3 Check-out procedure...3 High-voltage connections...3 Control wiring...3 Three-wire control...3 Wiring diagrams...4 SWITCH OPERATION.... 5 Electrical operation...5 Manual hotstick operation...5 DIMENSIONS.... 6 SERVICE INFORMATION.... 7 Service requirements...7 Frequency of inspection...7 ii

! SAFETY FOR LIFE Safety for life Eaton s Cooper Power series products meet or exceed all applicable industry standards relating to product safety. We actively promote safe practices in the use and maintenance of our products through our service literature, instructional training programs, and the continuous efforts of all Eaton employees involved in product design, manufacture, marketing, and service. We strongly urge that you always follow all locally approved safety procedures and safety instructions when working around high-voltage lines and equipment, and support our Safety For Life mission.! SAFETY FOR LIFE Safety information The instructions in this manual are not intended as a substitute for proper training or adequate experience in the safe operation of the equipment described. Only competent technicians who are familiar with this equipment should install, operate, and service it. A competent technician has these qualifications: Is thoroughly familiar with these instructions. Is trained in industry-accepted high and low-voltage safe operating practices and procedures. Is trained and authorized to energize, de-energize, clear, and ground power distribution equipment. Is trained in the care and use of protective equipment such as flash clothing, safety glasses, face shield, hard hat, rubber gloves, clampstick, hotstick, etc. Following is important safety information. For safe installation and operation of this equipment, be sure to read and understand all cautions and warnings. Hazard Statement Definitions This manual may contain four types of hazard statements: DANGER Indicates a hazardous situation which, if not avoided, will result in death or serious injury. Indicates a hazardous situation which, if not avoided, could result in death or serious injury. CAUTION Indicates a hazardous situation which, if not avoided, may result in minor or moderate injury. CAUTION Indicates a hazardous situation which, if not avoided, may result in equipment damage only. Safety instructions Following are general caution and warning statements that apply to this equipment. Additional statements, related to specific tasks and procedures, are located throughout the manual. DANGER Hazardous voltage. Contact with hazardous voltage will cause death or severe personal injury. Follow all locally approved safety procedures when working around highand low-voltage lines and equipment. G103.3 Before installing, operating, maintaining, or testing this equipment, carefully read and understand the contents of this manual. Improper operation, handling or maintenance can result in death, severe personal injury, and equipment damage. G101.0 This equipment is not intended to protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply can result in death, severe personal injury and equipment damage. G102.1 Power distribution and transmission equipment must be properly selected for the intended application. It must be installed and serviced by competent personnel who have been trained and understand proper safety procedures. These instructions are written for such personnel and are not a substitute for adequate training and experience in safety procedures. Failure to properly select, install or maintain power distribution and transmission equipment can result in death, severe personal injury, and equipment damage. G122.3 iii

Product information Introduction Service Information MN230007EN provides installation instructions, operation information, and maintenance information for Edison capacitor switches. The information contained in this manual is organized into the following major categories: Safety Information, Product Information, Ratings and Specifications, Installation Procedure, Switch Operation, Dimensions, and Service Information. Refer to the table of contents for page numbers. Description of operation The Edison vacuum capacitor switch is a single-phase, Solenoid-operated vacuum switch. The solid polymer insulation system does not rely on gas, foam, or liquid dielectrics. Highly resistant to ozone, oxygen, moisture, contamination, and ultraviolet light, it is an environmentally safe capacitor switch. The Edison capacitor switch has polymer bushings and is suitable for operation through a temperature range of -40 C to +60 C. Read this manual first Read and understand the contents of this manual and follow all locally approved procedures and safety practices before installing or operating this equipment. Additional information These instructions cannot cover all details or vari ations in the equipment, procedures, or process described nor provide directions for meeting every possible contin gency during installation, operation, or maintenance. When additional information is desired to satisfy a problem not cov ered sufficiently for the user s purpose, please contact your Eaton s Cooper Power series product representative. Acceptance and initial inspection Each capacitor switch is completely assembled, inspected, tested, and adjusted at the factory. It is in good condition when accepted by the carrier for shipment. Upon receipt of a capacitor switch, inspect the capacitor switch thoroughly for damage and loss of parts incurred during shipment. If damage or loss is discovered, file a claim with the carrier immediately. Handling and storage If the capacitor switch is to be stored for an appreciable time before installation, provide a clean, dry storage area. Locate the capacitor switch so as to minimize the possibility of mechanical damage. When transporting or storing the switch, the contacts should be kept in the closed position to avoid damage to the vacuum bottle contacts. Standards Edison capacitor switches are designed and tested in accordance with IEEE Std C37.66-2005 standard. Quality standards ISO 9001 Certified Quality Management System 1

Ratings and specifications Check switch ratings before installation The Edison capacitor switch must be applied within its specified ratings. Check data plate ratings and compare with the system characteristics at the point of application prior to installation. Table 1 list the ratings and specifications for the Edison capacitor switch. Ratings All ratings meet or exceed values in IEEE Std C37.66-2005 standard for a distribution-class switch, where applicable. Table 1. Ratings and specifications Voltage class Switch type Rated maximum voltage, 50/60 Hz 15 kv ECS15-95 ECS15-125 Ungrounded capacitor banks, L-L (kv) 15.6 25 25 kv ECS25-125 Solidly grounded capacitor banks, L-L (kv) 27 38 Impulse withstand voltage Open contact kv (BIL) 95 95 125 125 Line to ground (kv BIL) 95 125 125 150 Withstand voltage, 60 Hz Power Frequency Dry Withstand (kv) 60 60 70 Power Frequency Wet Withstand (kv) 50 50 60 Continuous current 50/60 Hz (A) 200 200 Capacitive switching current 50/60 Hz (A) 200 200 Fault making peak current (A) 15,000 15,000 Symmetrical fault making current (A) 6,000 6,000 Withstand peak current (A) 15,000 15,000 Short-time symmetrical withstand current (A) 4,500 4,500 High frequency transient making peak current (A) 9,000/12,000* 9,000 Rated transient inrush frequency (Hz) 6,000 6,000 Creepage distance Terminal to terminal (mm) 440 600 813 813 Terminal to ground (mm) 498 610 610 813 Operating voltage range, 50/60 Hz 110/120 Vac (V) 75-130 75-130 115/125 Vdc (V) 70-130 70-130 240 Vac (V) 150-260 150-260 Nominal control current 110/120 Vac for 100 msec (A) 9 9 115/125 Vdc for 100 msec (A) 9 9 240 Vac for 100 msec (A) 6 6 Weight (lb/kg) 32/14 33/15 33/15 34/16 Operating temperature range -40 C to +60 C -40 C to +60 C Mechanical operations 50,000 50,000 ECS25-150 * The 15.6 kv rated Edison Capacitor Switch is available with an optional High Frequency Transient Making Peak Current of 12 ka. Contact factory for additional information. NNote: The durability of the Edison capacitor switch was demonstrated by completing a minimum of 50,000 mechanical operations after performing the Mechanical Life Test in accordance with IEEE Std C37.66-2005 standard. 2

Installation procedure CAUTION Personal injury. Sheds on epoxy encapsulation have sharp edges. Wear protective gloves when handling the unit. Failure to do so can result in cuts and abrasions. Check-out procedure 1. Check data plate. Make sure that ratings on the data plate are correct for the planned installation. 2. Visually inspect the switch. Visually inspect the switch for any damage to bushing sheds, terminals, tank, of trip handle. 3. Install the switch. Follow locally approved installation procedures. Mounting hardware is available for pole mounting as an accessory. T258.1 Control wiring Connections to the actuating mechanism are made through the standard five-pin (or optional six-pin) receptacle at the bottom of the switch. Mating plugs for the receptacle may be ordered separately. Maximum cable and wire sizes accommodated by the plugs are indicated in Table 2. Table 2. Control wiring specifications Accessory plug Cable range Number of pins O.D. 5 11 14 mm (0.437 0.562 in.) 12 6 13 16 mm (0.500 0.625 in.) 16 Max. wire size AWG Pin orientation diagrams for the accessory receptacles are shown in Figure 1. KEY High-voltage connections 1. Ground the switch. Make the ground connection to the ground connector located on the switch bracket of the switch. D E A E F A 2. Make line connections. Connect the primary leads to the switch terminals. The universal clamp-type terminals accommodate AWG No. 8 solid through 2/0 stranded conductor. 3. Recommended torque levels for line and load terminal hardware is 20-22 ft-lbs (27.1-29.8 N-m) not to exceed 30 ft-lbs (40.7 N-m). Hazardous voltage. Solidly ground all equipment. Failure to comply can result in death, severe personal injury, and equipment damage. T223.2 This equipment is not intended to protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply can result in death, severe personal injury and equipment damage. G102.1 C B 5-pin Receptacle Figure 1. Receptacle pin orientation Three-wire control D C B 6-pin Receptacle Remote control of the Edison capacitor switch is supplied by a single-pole, double-throw switch (three-wire control) supplied by the customer. Any manual switch, relay contact, time switch, voltage-, current- or photo-electric-controlled switch, or similar device can be used, provided the control circuit is energized for a minimum of 100 ms (at -40 C) for each operation. A connection diagram for a standard three-wire control is shown in Figure 2. 3

Wiring diagrams Schematic diagrams of switch actuators wired for two- and three-wire controls are shown in Figure 2. Accessories are shown with dashed lines. These diagrams apply only for alternating current (ac) control voltage. For direct current (dc) control voltage please contact your Eaton s Cooper Power series product representative. Figure 2. Typical connection diagrams (switch shown in OPEN position) 4

Switch operation Electrical operation The switch may be opened and closed electrically by applying rated control voltage to the proper terminals of the actuator receptacle. Refer to the Installation Procedure section of this manual for electrical connections and operating time. Contact position indication The yellow operating handle is also used as a contact position indicator. The switch is closed when the operating handle is in the up position and is open when the operating handle is in the down position. See Figures 3 and 4. Manual hotstick operation Hazardous voltage. This device is not a substitute for a visible disconnect. Follow all locally approved safety practices. Failure to follow proper safety practices can result in contact with high voltage, which will cause death or severe personal injury. G112.1 The switch may be manually opened by using a hotstick to operate the yellow manual operating handle under the sleet hood as shown in Figures 3 and 4. Hazardous voltage. Do not rely on the open position of the yellow operating handle; it does not ensure that the line has been de-energized. Always establish a visible disconnect. Failure to follow proper safety practices can result in contact with high voltage, which will cause death or severe personal injury. G116.0 Figure 3. Contact position indicator (switch shown in closed position). To open the switch contacts, insert the hotstick tip into the hotstick guide of the manual operating handle and pull downward to the OPEN position. See Figure 3. Control power is required to close the switch. Figure 4. Contact position indicator (switch shown in open position). 5

Dimensions Dimensions A B C 95/95 kv BIL 27.78 (706) 25.89 (659) 17.69 (449) 95/125 kv BIL 27.78 (706) 25.89 (659) 17.69 (449) 125/125 kv BIL 30.54 (776) 28.81 (732) 17.69 (449) 125/150 kv BIL 32.54 (827) 30.81 (783) 19.69 (500) NNote: All dimensions are inches (mm). Dimensions shown are approximate. Creepage 95/95 kv BIL 95/125 kv BIL 125/125 kv BIL 125/150 kv BIL Terminal to Terminal 17.3 (440) 23.6 (600) 32.0 (813) 32.0 (813) Terminal to Ground 19.6 (498) 24.0 (610) 24.0 (610) 32.0 (813) Figure 5. Dimensions of Edison capacitor switch 6

Service information Service requirements The mechanical durability of the Edison capacitor switch was demonstrated by completing a minimum of 50,000 operations after performing the Mechanical Life Test in accordance with IEEE Std C37.66-2005 standard. The switch requires no routine maintenance; however, the switch should be inspected on a regular basis to check for physical damage and to verify operation. Frequency of inspection Because these switches are applied under widely varying operation and climatic conditions, maintenance intervals are best determined by the user based upon actual operating experience. Hazardous voltage. The switchgear (apparatus and control) and high-voltage transformer must be in a test cage or similar protected area to prevent accidental contact with the high-voltage parts. Solidly ground all equipment. Failure to comply can result in death, severe personal injury, and equipment damage. T221.5 CAUTION Radiation. At voltages up to the specified test voltages, the radiation emitted by the vacuum interrupter is negligible. However, above these voltages, radiation injurious to personnel can be emitted. See Service Information S280-90-1, Vacuum Interrupter Withstand Test Voltage Ratings Information for further information. G109.2 7

! SAFETY FOR LIFE Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com Eaton s Power Systems Division 2300 Badger Drive Waukesha, WI 53188 United States Eaton.com/cooperpowerseries 2016 Eaton All Rights Reserved Printed in USA Publication No. MN230007EN Rev 4 November 2016 (Replaces S230501 Rev 3) Eaton is a registered trademark. All trademarks are property of their respective owners. For Eaton s Cooper Power series Edison single-phase vacuum capacitor switch product information, call 1-877-277-4636 or visit: Eaton.com/cooperpowerseries