UV100A Ultraviolet Air Treatment System

Similar documents
UV100A Ultraviolet Air Treatment System

UV100E Ultraviolet System

WARNING: FAILURE TO FOLLOW THESE RULES MAY RESULT IN SERIOUS PERSONAL INJURY CAUTION: INSTALLATION LOCATION:

Ultraviolet Germicidal Lamps Owner s Manual MODELS 1910 & 1930

Installation Instructions

Installation Guide. VisionPRO. TH8000 Series. Need Help? This manual covers the following models. System Types

Installer s Guide WARNING: 18-GJ11D1-2. Ultraviolet (UV-C) Lamp Kit for 2-5 Ton Air Handlers HAZARDOUS VOLTAGE - DISCONNECT POWER BEFORE SERVICING

T7079A,B Solid State Remote Temperature Controllers

Lamp and Sleeve Replacement

Installation Instructions WARNING: WARNING: WARNING: WARNING: WARNING:

Installation Instructions

Installation Instructions

INFRARED QUARTZ WALL HEATER

FOR THE FOLLOWING MODELS: EE-8075W EE-8075O EE-8075R EE-8075BK

INSTALLATION INSTRUCTIONS for Bifold Doors (JII103)

IMPORTANT SAFETY INSTRUCTIONS WARNING READ AND SAVE THESE OPERATING AND SAFETY INSTRUCTIONS BEFORE USING THIS HEATER.

Packaged Terminal Air Conditioner Wall Sleeve Installation

5800 Temperature Sensor Cable Assembly

Installation Guide. LR-HWLV-HVAC TouchPRO Wireless. System Types

Vertical Display and Storage B SKOPE Gen2: Three Door Chiller

Installation Guide. Programmable Thermostat TH6220D

F50F Duct Mounted Electronic Air Cleaner

FLUORESCENT UV- RING LIGHT OPERATING INSTRUCTION

LED Security Spotlight User Manual

StorTrends 3400 Hardware Guide for Onsite Support

Portable Air Conditioner

THERMOSTATIC MIXING VALVE TRIM K-T9493, K-T9494

Q309A,B; Q335C; Q340A; Q390A Thermocouples and Q313A,B,C,F Thermopile Generators

MICA HEATER INSTRUCTION MANUAL Model No: UHM V 50Hz 2200W

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve

LED 18W/12V SWIMMING POOL LIGHT WITH REMOTE CONTROL INSTALLATION AND OPERATING INSTRUCTIONS

UB1 AIR CONDITIONING UNIT INSTALLATION INSTRUCTIONS

Your safety and the safety of others are very important.

V94 BULK TAPE DEGAUSSER

National- Spencer Inc.

15GAL STEEL OIL DRAIN WITH 110V PUMP

SAFETY & OPERATING INSTRUCTIONS

Solid Core and Split Core Adjustable Current Status Switches CSS-O, CSS-C; CSP-O, CSP-C

AMX300 DirectConnect Mixing Valve Kits

OPERATOR S MANUAL 18 VOLT, 1 HOUR CHARGER

Operator: Save these instructions for future use!

Ultrasonic support removal tank

USER INSTRUCTIONS FOR 10 LITRE PORTABLE DEHUMIDIFIER MODEL NO. DHMD102

IMPORTANT INSTRUCTIONS & OPERATING MANUAL. Houston 50 Inch Electric Wall Mounted Fireplace Black / White

GENUINE PARTS INSTALLATION INSTRUCTIONS

Service Guide. Evaporator Coil Cleaning and Condensate Drain Maintenance Guidelines. ORDER No: UN-SVG001A-EN DATE: October 9, 2007

Cleaning up spilled mercury in the home

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CCS. Voltage rating: 115V~60Hz Power rating : 1400W

SUB Universal water baths SBB Boiling baths JB, PB Unstirred water baths

INSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX

OASIS-PLUS 120V READ ALL INSTRUCTIONS BEFORE OPERATING READ ALL INSTRUCTIONS BEFORE OPERATING OZONE IS A POWERFUL OXIDIZER AND MUST BE USED WITH CARE

Wall-Mounting your HP computer. User Guide

REMOTE AUXILIARY AIR CONDITIONING SYSTEM AND AIR DISTRIBUTION

Ceiling Fan Installation Instructions

CORNER FRIDGE REFRIGERATION UNIT INSTALLATION AND OPERATION INSTRUCTIONS

USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR

LED MOTION ACTIVATED FLOOD LIGHT

ROUTER TABLE INSERT ASSEMBLY AND OPERATING INSTRUCTIONS

Owner s Manual Model 5000 Safety, Operating and Maintenance Instructions

Introduction to Use of UV Light For the Control of Air Handler Contamination. What is UVGI or Ultraviolet Light?

Installation Instructions

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MN12CES / MN10CESWW

Installation Instructions READ BEFORE INSTALLING UNIT For SLO3 Air Conditoner (8,000~12,000 BTU)

3/4 PIPE CLAMP WITH STAND

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

Installation and Operation Manual. Digital Remote Meter for Monitoring System Performance. Version: RM-1

Replacement Instructions. Warning: During this procedure, keep small parts away from children.

There are several types of air cleaning devices available, each designed to remove certain types of pollutants.

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013

Installer s Guide 18-AH39D1-13

Replacing the Gateway M320 Keyboard

SCION tc DASH APPLIQUE Preparation

NewAir AC-10000E, AC-10000H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS

Air Conditioner Water Heater - A Product of HotSpot Energy LLC

Cooktop Low-Profile Ventilation Hoods

Dehumidifier Users manual. For Models: DH45S DH65S

Radiant Temperature Sensor TY7321

Installation Instructions S

TOYOTA Tundra BACK-UP CAMERA SYSTEM Preparation

Service manual. Website: CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.

User Guide. Bagless Cylinder White. Get Cleaning... vax.co.uk. Vax Careline: (UK) (ROI) White series

+by RGF A Guardian Air Purification System New Advanced Environmental Air Treatment System

USER MANUAL. Bottom Loading Bottled Water Dispenser SAVE THIS MANUAL FOR FUTURE USE. Model #

Nucleus Freedom BTE Rechargeable Battery (A25) and Nucleus Freedom BTE Recharger

SMD Rework Station TABLE OF CONTENTS

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MF08CESWW. Voltage rating: 115V~60Hz Power rating : 800W

CAUTION RISK OF ELECTRIC SHOCK DO NOT OPEN

Installer Guide smart connect

USER S MANUAL FH052EAV1 FH070EAV1. System Air Conditioner (Cooling and Heating) ENGLISH ESPAÑOL FRANÇAIS ITALIANO PORTUGUÊS DEUTSCH E HNIKA

DESERT RESEARCH INSTITUTE MOLD ASSESSMENT AND REMEDIATEION PROCEDURE

Table of Contents. What to Expect with. Preparation. Tools Needed. Wiring. Hanging the Fan. Blades. Motor Housing.

INSTALLATION AND SERVICE MANUAL

NADCA White Paper on Ultraviolet Lighting Applications in HVAC Systems

Please read this owner s Manual carefully before operating the unit. - Cooling - Heating - Dehumidifying - Fan

Central Air Conditioner

DIMENSION ELECTRIC RANGE

12-Volt 10-Amp Regulated Power Supply

Operating Instructions Bedienungsanleitung Mode d emploi

E-PDD Duct Smoke Detector Installation Sheet

Transcription:

UV100A Ultraviolet Air Treatment System INSTALLATION INSTRUCTIONS APPLICATION When installed in forced air heating and cooling systems, the UV100A Ultraviolet Air Treatment System kills airborne microorganism contaminants in the air passing over it. Individual results depend on how carefully all installation and maintenance requirements are followed and on the actual amount of time the air delivery fan operates. To capture and minimize micro-organism pass-through in residential heating, ventilation and air conditioning (HVAC) systems, combine the Ultraviolet Air Treatment System with a high-efficiency air filtration system that includes an electronic air cleaner. Add a high-efficiency electronic air cleaner to complement the air treatment system and provide added benefit for the homeowner. The UV100A Ultraviolet Air Treatment System is available in three models: a single-lamp, entry level medium-efficiency return air unit; a two-lamp, premium high-efficiency return air unit; and an air conditioner coil irradiation unit. The UV100A1000 single-lamp, entry level unit is mounted in the return air duct of an HVAC system. It has moderateefficiency performance against airborne bacteria in return air applications. The UV100A1018 two-lamp, premium unit is mounted in the return air duct of an HVAC system. It has highefficiency performance against airborne bacteria in return air applications. The UV100A1026 coil irradiation unit is mounted in the supply side air duct or downstream from the air conditioner cooling coils in the HVAC system. The single lamp reduces mold and spores on duct surfaces, coils and drip pans. The Ultraviolet Air Treatment System has a power cord that plugs into a 120 Vac electrical outlet. The units are designed to prevent accidental installer and homeowner contact with the voltage and with the ultraviolet rays in the sealed unit the ultraviolet lamps do not illuminate unless the base is mounted on the HVAC duct. INSTALLATION When Installing this Product 1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition. 2. Check the rating given in the instructions and on the product to make sure the product is suitable for your application. 3. Installer must be a trained, experienced service technician. 4. After installation is complete, check out product operation as provided in these instructions. CAUTION Personal Injury Hazard. Power supply can cause electrical shock. Disconnect power supply before beginning installation. Do not open base unit or lamp knob; there are no user-serviceable components inside. WARNING UV Light Hazard. Harmful to skin and eyes. Can cause temporary or permanent loss of vision. Never look at the lamps while illuminated. Only view illumination by way of the light indicator on the lamp knob. To prevent exposure to ultraviolet light, disconnect power to the ultraviolet air treatment system before servicing any part of the heating/air conditioning system. Do not mount device in location that allows ultraviolet light to be seen after installation. Do not attempt to bypass the duct mount switch. U.S. Registered Trademark Copyright 2000 Honeywell Inc. All Rights Reserved 69-1379- 1

Selecting Mounting Location NOTE: CAUTION Equipment Damage Hazard. Ultraviolet light can cause color shift or structural degradation of plastic HVAC materials. Select mounting location that prevents exposure to plastic flexible duct liner or other plastic components with unknown resistance to ultraviolet light. When the installer is uncertain about whether the drip pan in the installation can tolerate UV exposure, call the Honeywell Customer Assistance Center, 1-800-468-1502, Monday-Friday, 7:00 am to 5:30 pm, Central time. Ask for drip pan testing results. IMPORTANT The Ultraviolet Air Treatment System units operate outside the duct in residential environments exposed to temperatures between 30 and 120 F (-2 and +49 C). The lamp(s) inside the duct operate normally at varying temperatures, depending on the model: Single-lamp entry level units can be exposed to temperatures between 30 and 120 F (-2 and +49 C). Two-lamp premium unit lamps can be exposed to temperatures between 30 and 120 F (-2 and +49 C). Coil irradiation unit lamp can be exposed to temperatures between 30 and 170 F (-2 and +77 C) in moving air and 30 and 120 F (-2 and 49 C) in still air. The Ultraviolet Air Treatment System operates normally when exposed to 95 percent relative humidity, non-condensing. 1. The ultraviolet air treatment system can be mounted in any orientation. 2. Choose a location that is readily accessible for regular inspection and cleaning. 3. Allow clearance in front of the device for removing the lamp assemblies. See Fig. 2 for lamp assembly lengths. 4. Select mounting location that prevents exposure to plastic components with unknown resistance to ultraviolet light. A minimum of three feet is required between the ultraviolet lamps and devices fabricated of plastic, such as humidifiers. 5. Mount the ultraviolet air treatment system to non-lined metal ductwork. Do not mount in a location that permits ultraviolet exposure to plastic flexible duct liner. CAUTION Sharp Edges Hazard. Can cause personal injury. Be careful when inserting ultraviolet device into the sheet metal cutout. Wear protective gloves when working near sheet metal. Mounting in Duct Use the following instructions to mount the air treatment system on the air duct of an HVAC system: 1. Disconnect power to the HVAC system before installing the Ultraviolet Air Treatment System. 2. Determine the location for installation (see Fig. 1): a. The entry level and premium units require an easilyaccessible, flat mounting surface on the metal return air duct of the HVAC system. The coil irradiation unit requires an easily-accessible, flat mounting surface on the metal supply air duct of the HVAC system. The coil irradiation unit must be located so the lamp surrounds the evaporator coil and drip pan with ultraviolet light. b. The duct mounting location must be a minimum of 8 in. wide. See Fig. 2. c. The depth of the duct must accommodate the full length of the ultraviolet lamp for your model as shown in Fig. 2. d. The unit should be located as far away as possible from any rubber or plastic components, such as isolators, in the duct. e. The space adjacent to the mounting location must be large enough to allow for ultraviolet lamp installation and removal. f. A 120 Vac electrical outlet must be within range of the unit to plug in the power cord. 69-1379 1 2

ELECTRONIC AIR CLEANER UV100A ULTRAVIOLET AIR TREATMENT SYSTEM CONDENSER COOLING AIR CONDITIONED AIR TO ROOM PREMIUM AND ENTRY UNIT LOCATION COIL IRRADIATION UNIT LOCATION RETURN AIR CONDENSATE DRAIN HEAT EXCHANGER REMOTE CONDENSER SECTION (HIGH SIDE) REFRIGERANT PIPING FURNACE HIGH EFFICIENCY AIR CLEANER M13529 Fig. 1. Selecting mounting location for Ultraviolet Air Treatment System. 3 69-1379 1

UV100A1026 3-1/2 (89) 1 (25) 7 (178) 2-1/4 (57) 4 (102) 17-3/8 (441) 3-1/2 (89) 4-1/2 (114) 7 (178) M13517 3-1/2 (89) UV100A1000 1 (25) 7 (178) 2-1/4 (57) 4 (102) 7-7/16 (188) 3-1/2 (89) 4-1/2 (114) 7 (178) M13518 5 (127) 3-1/2 (89) UV100A1018 8-1/2 (216) 3-1/4 (83) 2-3/16 (56) 3-1/2 (89) 5 (127) 4 (102) 14-7/8 (379) 7 (178) 10 (254) M13519 Fig. 2. Ultraviolet Air Treatment System dimensions in in. (mm). 69-1379 1 4

3. Place the appropriate template for your model on the duct surface, centering the lamp hole(s) on the duct. See Fig. 3 (below and next page) for the template for your model. ALIGN EITHER OF THESE LINES AS CLOSE AS POSSIBLE TO DUCT CENTER LINE CENTER OF 2 IN. (51 MM) HOLE FOR LAMP 1/8 IN. (3 MM) PILOT HOLES FOR MOUNTING SCREWS INSTALLATION TEMPLATE FOR UV100A1000 AND UV100A1026 M13520 Fig. 3. Ultraviolet Air Treatment System templates. 4. Mark the location on the duct for the 2 in. diameter lamp hole(s) and the unit mounting-screw pilot holes. 5. Use a 2 in. hole saw to cut the lamp hole(s) in the duct. Remove any burrs. 6. Use a 1/8 in. drill to provide pilot holes for the mounting screws. 7. Be sure the duct surface is flat after all holes are drilled. 8. Position the entire base unit on the duct. Be sure the lamp holes in the duct align with those in the unit to allow lamp insertion. 9. Install the unit into the duct using the three (or two, depending on the model) no.10, 2 in. Phillips head sheet metal mounting screws provided. (There is a spare screw provided for the three-screw model.) 10. Tighten the screws to 12 to 14 in.-lb so the space between the case and duct is sealed. 5 69-1379 1

M13521 1/8 IN. (3 MM) PILOT HOLES FOR MOUNTING SCREWS 1/8 IN. (3 MM) PILOT HOLES FOR MOUNTING SCREWS CENTERS OF 2 IN. (51 MM) HOLES FOR LAMP ALIGN EITHER OF THESE LINES AS CLOSE AS POSSIBLE TO DUCT CENTER LINE INSTALLATION TEMPLATE FOR UV100A1018 69-1379 1 6

CAUTION Breakable Glass Hazard. Can cause personal injury. Be careful when inserting lamps(s) into lamp base. Wear protective gloves when handling lamp(s). MERCURY NOTICE This device contains mercury in the sealed ultraviolet lamp(s). Do not place your used lamp(s) in the trash. Dispose of properly. Broken Lamp Cleanup. Do not use a household vacuum. Sweep debris (phosphor/glass) into a plastic bag and dispose of properly. Contact your local waste management authority for instructions regarding recycling and the proper disposal of old lamp(s). For questions, call Honeywell Customer Response Center at 1-800-468-1502. 11. Insert the lamp into the base unit with the lamp light indicator at the eleven o clock position (left of the raised button on the unit cover). Do not touch the lamp surface with your hands. 12. Continue lightly pushing in on the lamp while rotating it slowly counterclockwise. This should cause the lamp to drop into the bottom of the lamp well. 13. Rotate the lamp clockwise until it snaps into place with the lamp indicator light aligned with the raised button on the unit cover. WARNING UV Light Hazard. Harmful to skin and eyes. Can cause temporary or permanent loss of vision. Never look at the lamps while illuminated. Only view illumination by way of the light indicator located on the lamp knob. To prevent exposure to ultraviolet light, disconnect power to the ultraviolet air treatment system before servicing any part of the heating/air conditioning system. 14. Plug the cord into the nearby 120 Vac electrical outlet. 15. Reconnect the power to the HVAC system. 16. Choose a location on the adjacent HVAC equipment for the HVAC maintenance label included in the air treatment system packing box. Choose a location that a future installer can easily see during any future HVAC maintenance or repair. 17. Adhere the HVAC maintenance label to the HVAC equipment (selected in step 16) such as the furnace, air cleaner or humidifier. CHECKOUT The installer should verify that the ultraviolet lamp(s) are operating only by viewing the lamp indicator on the lamp knob. Do not attempt to look directly into the duct to see the illuminated ultraviolet lamps. The installer should orient the homeowner to the unit by showing them the blue glow of the lamp indicator and discussing how to determine when the unit is functioning properly without looking directly into the duct to see the illuminated ultraviolet lamps. The installer should also emphasize the hot surface and electrical shock safety warnings. The installer should leave the Owner s Guide with the homeowner and review the lamp cleaning and lamp replacement procedures. A Lamp Cleaning Schedule is included in the Owner s Guide to help the homeowner set up and track a regular cleaning schedule. TROUBLESHOOTING AND SERVICE The Ultraviolet Air Treatment System has no field-serviceable parts. Lamp cleaning is recommended as routine maintenance four times a year or every three months (quarterly). Annual lamp replacement is required. See the Owner s Guide for detailed procedural information. 7 69-1379 1

Home and Building Control Home and Building Control Honeywell Honeywell Limited-Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley, MN 55422 Scarborough, Ontario M1V 4Z9 Printed in U.S.A. on recycled 69-1379 1 G.H. Rev. 7-00 paper containing at least 10% www.honeywell.com post-consumer paper fibers.