boiler houses Reducing water use in Guidance Leaflet

Similar documents
Hot water supply, distribution and use

Water Efficiency. Water Management Options. Boilers. for Commercial, Industrial and Institutional Facilities. Boiler Water Impurities

Boiler Blowdown. Boiler Blowdown Benefits. Best Operating Practices for Boiler Blowdown

steam centre of excellence Steam Boiler System Optimization

Saving Boiler Fuel. Figure 1: Boiler System Operation Costs

Overview of Heat Recovery Boiler Systems and Operating Costs Factors Effecting Blowdown Blowdown Heat Recovery The Energy Tank

Safe management of industrial steam and hot water boilers A guide for owners, managers and supervisors of boilers, boiler houses and boiler plant

BOILER EFFICIENCY F7 Energy eco-efficiency opportunities in Queensland Foundries

Some Criteria for Choosing a Steam Boiler for a Microbrewery

Wastewater Reuse. Typical treated wastewater is:

Energy Efficient Operations and Maintenance Strategies for Boilers

Boiler Efficiency. Charles Stark Department of Poultry Science.

Best Practice in Boiler Water Treatment

Steam System Best Practices Condensate System Piping

Best Practices for Textile Mills to Save Money and Reduce Pollution in Bangladesh

GUIDELINES FOR SELECTING RESIN ION EXCHANGE OR REVERSE OSMOSIS FOR FEED WATER DEMINERALISATION

IGEMA BOILER LEVEL & TDS CONTROLS

Energy Saving Fact Sheet Boilers

The Rippleffect: water efficiency for business Cost-effective water saving devices and practices - for industrial sites

BOILER FEED AND CONDENSATE RECOVERY SYSTEMS Extend the life and efficiency of your boiler system

Water Efficiency Self-Assessment Guide from

FLASH TANK ECONOMIZER PRODUCT GUIDE

Recover Heat from Boiler Blowdown Water

Printing and Publishing Energy Savings Guide

BEST PRACTICE GUIDE. Energy Efficiency: Steam, Hot Water and Process Heating Systems

Increasing Natural Gas Boiler Efficiency by Capturing Waste Energy from Flue Gas

Steam Generation Efficiency Module Blowdown Losses Section

PLANT LOCATION AND LAYOUT

Steam System Efficiency. Bill Lumsden Leidos Engineering

Water for Injection (WFI) and Pure Steam Production in a Lean Manufacturing Environment. Larry Zanko Project Manager STERIS Corporation

Resource efficiency in the UK whisky sector

Blowdown vessels Meeting the requirements of HSE PM60

Natural Gas Energy Efficiency Opportunities for Commercial & Industrial Customers. Michael Pace Lead Engineer C & I Efficiency Programs

GUIDANCE FOR DEVELOPMENT OF SPILL AND SLUG PREVENTION CONTROL PLANS AND FACILITIES FOR THE CITY OF ATTLEBORO SEWER USERS

Vaillant s plain English guide to. simple, concise and precise

COOLING WATER MANAGEMENT

Forgotten savings: Heat recovery from surface blowdown

USERS GUIDE. LOGIC Heat 12, 15, 18, 24, 30. For installation guide see reverse of book

USERS GUIDE. LOGIC Combi 24, 30, 35. For installation guide see reverse of book

WISI - ABB Water Industrial Sector Initiative Introducing ABB Water for Process Industry. ABB Group July 29, 2009 Slide 1

Energy Efficiency in Steam Systems

C. starting positive displacement pumps with the discharge valve closed.

GAS HEATING IN COMMERCIAL PREMISES

Energy Efficiency. Bars & RestauRants.

Heating Water by Direct Steam Injection

Troubleshooting Your RO

Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues

INTEGRATED POLLUTION REGULATIONS AT TEXTILE SECTOR

Chapter 2.2: Boilers

Steam Boiler Feedwater Storage Technology

Routine and Emergency Boiler Operation

Guidance Notes For Provision Of Water Expansion For 10 & 15 Litre Unvented Hot Water Heaters

V. ENERGY SAVINGS IN INDUSTRY

Fact Sheet on Steam Sterilizers at Stanford University

Monitoring Water Use

6. Principles of effective plumbing systems

Specific Volume of Liquid (Column 7). The volume per unit of mass in cubic feet per pound.

Energy Efficiency HOSPITALITY.

Session 2: Hot Water Supply

Fuel Treatment and Conditioning Systems

Delivering exceptional performance and Ecovalue. Ecocent

Prevent Blockages in the Sanitary Sewer System

Boiler NOx Emissions and Energy Efficiency

Combi 24 HE. User s Guide and Important Warranty Information

Ultrasonic support removal tank

12 November 2008 *** I:\CIRC\MEPC\01\642.DOC INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR

HomeServices Terms and Conditions

HOW TO SELECT A LOW VOLUME (L.V ) BOILER

Condensing Economizers Workshop Enbridge Gas, Toronto. MENEX Boiler Plant Heat Recovery Technologies. Prepared by: Jozo Martinovic, M A Sc, P Eng

CITY OF GOLDEN DEPARTMENT OF PUBLIC WORKS, ENVIRONMENTAL SERVICES DIVISION

Examples of pressure systems and equipment are:

Reuse of Alternative Water Sources for Cooling Tower Systems Two Case Studies Using Non-Traditional Water Sources

HS-901(A) BASIC STEAM HEATING SYSTEMS

ecomax Instructions for use Wall hung room sealed fan assisted condensing boilers For the user

ABSTRACT. aspects of potential waste heat recovery systems and the economics of installing them at selected survey factories.

EU F-Gas Regulation Guidance Information Sheet 5: Stationary Air-conditioning and Heat Pumps

Boiler and Steam Efficiency What does it mean?

Best Practice Guide BPGCS007

For installation guide see reverse of book

Design Utility Lever Thermostatic Bath Shower Mixer

Drying of Woody Biomass. Process Engineering / GEA Barr-Rosin

PBX Series Quick Fit Connector Bimetallic Steam Traps

Morco House Riverview Road Beverley HU17 0LD

STEAM HEATING SYSTEM TROUBLESHOOTING GUIDE

I. STEAM GENERATION, BOILER TYPES

A Guide to Trouble-Free Cooling Towers

Overview. Introduction Cooling Tower Basics Principles of Operation Types of Cooling Towers Common Applications Design Considerations

Managing the Risk of Legionnaires Disease in Vehicle Wash Systems

EU F-Gas Regulation Guidance Information Sheet 14: Refrigeration, Air-Conditioning and Heat Pump Contractors

Tracking Water Use to Cut Costs

Tips for burner modulation, air/fuel cross-limiting, excess-air regulation, oxygen trim and total heat control

User's Instructions. Alpha HE CB25/33 and HE SY25

BASIC WATER TREATMENT OF STEAM BOILERS

How To Clean Up A Reactor Water Cleanup

RULE DRY CLEANERS USING SOLVENT OTHER THAN PERCHLOROETHYLENE


Information Technology Solutions

Site Visit Report. MEAT PROCESSING FACILITY COD Reduction. Industrial Assistance Section Assessment Team

Baxi Combi 80e & 105e

What is a successful Steam Trap Management Program?

Transcription:

Guidance Leaflet Reducing water use in boiler houses Significant amounts of water are used in boiler houses to provide hot water and steam and steam-raising boilers require large quantities of make-up water to compensate for uncollected condensate or blowdown water. Adding to the cost of this water is the cost of energy used in boiler houses to heat water, and in ancillary water-treatment processes to improve the quality of the boiler feedwater. Any loss of water (or steam) will incur costs. These include the direct costs (i.e. paying for the water itself) and the hidden costs (i.e. for treatment and the energy used for heating). Quite often, it is the hidden costs that are the most significant. Hidden costs Reducing water use in a boiler house can save more than the direct cost of the water alone. Understanding the full cost of water is important, particularly for steam-raising boilers. Water is frequently pre-treated prior to use, may have conditioning chemicals added and is then heated in the boiler. Each of these steps contributes significantly to the overall cost of the water. Remember that additional costs will also be incurred for disposal of any wastewater to sewer, typically 0.54 2.67/m 3. Typical costs for water UK mains supply 1 0.59-1.75/m 3 Softened water 1.00-2.16/m 3 Demineralised/deionised water 2.53-3.70/m 3 Reverse osmosis (RO) 1.51-3.83/m 3 treatment 2 Hot water (60 C) gas heated 3 2.82-3.98/m 3 Hot water (60 C) electrically 6.48-7.64/m 3 heated 3 Boiler blowdown (100 C) gas 5.09-6.25/m 3 heated 3,4 Condensate gas heated 3,4 3.70-4.86/m 3 Steam gas heated 3 29.71-30.87/tonne 1 UK mains supply based on standard 2010/11 tariffs 2 Note this does not include capital and maintenance costs (e.g. membrane replacement) which can be significant for RO plant 3 Energy costs at 3.6p/kWh for gas and 9.5p/kWh for electricity, using a boiler with 90% efficiency 4 Excludes boiler-water conditioning chemical costs (e.g. oxygen scavenger/corrosion inhibitor/anti-foam) www.wrap.org.uk/rippleffect

02 Reducing water use in boiler houses 1. Determine the true cost of the water used in your boiler house by taking the cost of treatment and heating into consideration. Remember to account for steam and condensate. 2. Estimate any water and/or steam losses. Use the cost data on the front page to calculate the cost of these losses. Understanding where water is used Many businesses do not know how much water is used by their boiler(s), how much water is lost at the water treatment plant or, in the case of steam boilers, how much condensate is collected and returned. Monitoring the quantity of water used in each step of the process enables the water efficiency of the boiler house to be assessed. In multi-boiler installations, it can also allow the efficiencies of each boiler to be monitored. Suggested meter locations, together with potential water efficiency improvements in a typical steam boiler system, are shown in Figure 1. In this example, the installed meters would allow the following calculations: Figure 1: Potential areas for water efficiency improvements in a typical steam-boiler installation 2. See if water treatment can be improved Water treatment 5. Routinely look for steam leaks and assess losses (include steam traps) Steam losses Thermal demand Flue gas Incoming cold water M1 Softening Condensate recovery 1. Review where water meters are installed M1 M2 M3 Dealkalisation or demineralisation Reverse osmosis M2 Treated water (make-up water) Feedwater tank (hotwell) 4. Assess and improve condensate recovery Feedwater tank (hotwell) overflow Steam Economiser Regeneration liquors or reject water to drain Key Feedwater Pre-heated feedwater M3 Cold water Boiler blowdown Warm water Hot water Steam 3. Review boiler blowdown operation M1 Meter location Feedwater pump

Reducing water use in boiler houses 03 M1 - M2 = M3 - M2 = water used (loss 6 ) at water treatment plant condensate recovery return volume 7 Installing meters is an easy and effective way to measure water usage at each step in the process. They are inexpensive to install - for example, a simple 30 mm water meter with a pulsed output costs around 75 to 95, excluding fitting. There are often many pipes in a boiler house and, unless they are easy to follow, it can be difficult to understand what flows where, which makes water management more difficult. Labelling pipework, ideally showing contents and direction of flow, can make this much easier and may be particularly useful in an emergency (see Figure 2). Figure 2: Well-labelled pipework (courtesy of Lyreco) softening, to change the chemical composition of some of the dissolved salts and reduce scaling; partial removal of TDS and alkalinity (known as dealkalisation); and demineralisation or reverse osmosis (RO) to remove the majority of TDS. These processes will use ion-exchange beds which will require periodic regeneration. Regeneration processes use water and chemical reagents, and generate effluent, all of which incur costs. Regenerating exchange beds daily, or on a similar time-dependent basis, irrespective of the amount of water that has been treated, can lead to more frequent regeneration than is necessary. Using automated systems based on the volume of water treated or a measured value (such as conductivity breakthrough) can be much more efficient and minimises the number of regenerations required. If a membrane treatment process, such as RO, is used, a permeate stream and a concentrate (or reject water) stream is produced. The permeate is essentially pure water and will be used to supply the boiler feed. The reject water can typically account for 30% of the incoming flow and, even though it will have high salt concentrations, it is still likely to be suitable for recovery and re-use elsewhere on site. An RO membrane treatment plant is shown in Figure 3. Figure 3: RO membrane treatment plant (courtesy of G s Fresh Beetroot) 1. Review where water meters are installed in your boiler house. If necessary, install more meters to monitor water usage effectively. 2. Label pipework to indicate its contents and direction of flow. Treatment of boiler feedwater In hard-water areas, many hot-water boilers have softeners installed on the water supply to help prevent scale building up. The performance of most steam-raising boilers is improved if the feedwater has a low concentration of total dissolved solids (TDS). Lower TDS means the boiler will be less prone to foaming and less blowdown will be required. Most steam-raising boiler installations need some form of feedwater pre-treatment and common processes include: 1. If softeners, dealkalisation or demineralisation plants are used on site, check whether the frequency of the regeneration cycles can be reduced. 2. If the site uses a reverse osmosis membrane treatment plant, assess the potential for re-use of the reject water stream elsewhere on site. 3. Check whether you can improve treatment to reduce the TDS in the feedwater for a steamraising boiler. This will reduce blowdown requirements (refer to page 4). 6 Such as discharges to drain 7 Excluding allowance for boiler blowdown

04 Reducing water use in boiler houses Boiler blowdown (steam boilers) Periodic discharges of water from a steam boiler will be required to prevent the TDS from building up in the boiler water, even if pre-treated water is used. Typically, values of TDS in boiler water should be no higher than about 2,500 3,500 mg/litre, although this will depend on specific operating conditions, such as pressure. Boiler blowdown can be controlled manually, by timer or automatically. Automatic methods are usually based on conductivity measurement, which is proportional to TDS concentration. Using an automatically controlled system is recommended because a small volume of water is blowndown more frequently and, overall, this minimises the total amount of water discharged. The amount of boiler blowdown required can be estimated using the TDS concentration of the feedwater and the maximum TDS concentration required in the boiler water. For example, in a boiler where the maximum TDS concentration required is 3,000 mg/litre and the treated (softened) feedwater has a TDS concentration of 250 mg/litre (assuming that the additional TDS burden from the returned condensate is small), the amount of boiler blowdown required, as a percentage of total boiler volume, can be estimated using the formula below. Amount of blowdown required (%) = TDS of feedwater (mg/litre) Maximum increase in x 100 concentration of TDS (mg/litre) 250 = x 100 3,000-250 = 9.1% of boiler feedwater If water treatment can be improved to reduce the TDS of the feedwater, the amount of blowdown required to maintain the maximum TDS in the boiler water will be reduced. This can save significant quantities of water and energy. Boiler blowdown water is very hot and is often under pressure. When boiler blowdown is discharged, flash steam is usually emitted, which is generated as the boiler blowdown is depressurised. On larger installations, it may be worth recovering the water and heat from the flash steam for use in the boiler. This can be done by condensing the steam (using cold feedwater) and returning the flash steam condensate and warmed feedwater back to the feedwater tank (hotwell). Any remaining blowdown will have to be disposed of but, under trade effluent consents, there are usually conditions for the temperature of the discharge. Typically, the upper limit is about 43 C. Instead of discharging hot blowdown water to drain, it is possible to use heat exchangers to recover the heat to pre-heat boiler feedwater. 1. Check if the boiler blowdown water volume, or the frequency of blowdown, can be reduced by improving water treatment. 2. Investigate whether boiler blowdown can be automated. 3. Check whether the flash steam from the boiler blowdown can be recovered. 4. Check how blowdown is being cooled to meet discharge requirements. Condensate recovery and feedwater tanks (hotwells) Wherever steam is used, condensate will form as the steam cools, either in the distribution system or at the point of use, resulting in the formation of hot condensate. This condensate has a high value in terms of water and energy. Preventing condensation of steam by ensuring good insulation (lagging) of steam lines and vessels will reduce condensate production. Well-maintained steam traps can remove condensate from the system without significant loss of steam. Provided the collected condensate is kept clean, it can be returned to the feedwater tank (hotwell) to help reduce water and energy use. Discharging condensate to drain is expensive and will also cause an increase in effluent temperature. Because the feedwater tank (hotwell) needs to store the collected condensate, it is important to ensure it has sufficient working volume during its period of maximum

Reducing water use in boiler houses 05 generation (check the tank volume between the level at which the cold feedwater starts and the bottom of the overflow). Any overflow to drain from the feedwater tank is a waste of water and energy, and should be investigated. Condensate recovery can reduce the: cost of water pre-treatment; use of oxygen scavenging chemicals (dissolved gas concentration decreases with an increase in water temperature); and frequency of blowdown (condensate typically has a low concentration of TDS). contains about six times as much energy as water at 100 C, and is very expensive to produce at around 29.71-30.87/tonne. Hence, even a small steam leak has a significant cost attached. Fortunately, steam leaks are visible and audible, so can be identified relatively easily. Most common leaks are from faulty valves (packed glands), and pipework flanges and joints (see Figure 4). Another way that steam leaks occur is through sticking steam traps, which can either result in a continuous escape of steam, or a blockage which will collect condensate. Steam traps, valves and pipework should be routinely checked and corrective action taken if found to be defective. 1. Minimise the amount of condensate formed by lagging the distribution system. Figure 4: Steam leaks from faulty valves on unlagged steam lines 2. Determine your condensate return rate and check if more condensate can be collected and re-used. Unnecessary uses, losses and leaks Any overuse of hot water will waste not just the water, but also the associated hidden costs. Remember, hot water (60 C) can cost between 2.82-7.64/m 3. Common losses of hot water occur through dripping taps and automatic taps not turning off quickly enough. Hot water supplies are often misused (e.g. for vehicle washing). Producing steam is an energy intensive process, with more than 80% of the energy used for the latent heat of vaporisation of water to steam. This means that steam 1. Check the hot water distribution system and ensure there are no leaks or unnecessary usage. 2. Carry out steam leakage surveys on a routine basis to identify and repair leaks. 3. Repair or replace faulty steam traps promptly. Waste & Resources Action Programme October 2010 The Old Academy 21 Horse Fair Banbury, Oxon OX16 0AH Tel: 01295 819 900 Fax: 01295 819 911 E-mail: info@wrap.org.uk Resource Efficiency helpline 0808 100 2040 www.wrap.org.uk/rippleffect