AIRPORT SECURITY FENCING. A. American Society for Testing and Materials (ASTM):

Similar documents
CHAIN-LINK FENCES BID SPECIFICATIONS DESCRIPTION

SECTION CHAIN LINK FENCES AND GATES

Fence SpecCheck Wheatland Tube Company

MERCHANTS METALS SECTION ARMORLINK ALUMINIZED CHAIN LINK FENCE AND GATES 2014!

Standard Specification for Polyvinyl Chloride (PVC) and Other Organic Polymer-Coated Steel Chain-Link Fence Fabric 1

SECTION STORM DRAINAGE SYSTEM

DIVISION 2 - SEWERAGE AND DRAINAGE SECTION STORM DRAIN SYSTEMS PART 1 - GENERAL

SUPPLEMENTAL TECHNICAL SPECIFICATIONS BI-DIRECTIONAL STATIC LOAD TESTING OF DRILLED SHAFTS

PART 1 GENERAL 1.1 SECTION INCLUDES

SECTION GUARDRAILS

HIGH TENSION CABLE BARRIER

SECTION PUBLIC STORM UTILITY DRAINAGE PIPING

SECTION STORM DRAIN SYSTEM

A. Contractor shall furnish, to the Engineer, all materials certifications available from the manufacturer for all required materials.

SECTION PRECAST CONCRETE STRUCTURES

Precast Manhole Sections and Castings. These items shall conform to Section 31, "Storm Drain Installation," of these Standard Provisions.

SECTION PRECAST CONCRETE UTILITY STRUCTURES

SECTION CEMENT-MORTAR LINED AND COATED STEEL PIPE

SECTION 15 AIR RELEASE VALVE ASSEMBLIES General

SECTION REMOVAL OR ABANDONMENT OF EXISTING UTILITIES AND UNDERGROUND STRUCTURES. 1. Trench excavation, backfill, and compaction; Section

SECTION COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here)

SECTION COLD-FORMED METAL DECK FRAMING Elevations Steel Deck Framing by Trex

SECTION PREFORMED METAL STANDING SEAM ROOFING PART 1 - GENERAL 1.1 DESCRIPTION OF WORK

ITEM # OSTERBERG CELL LOAD TESTING OF DRILLED SHAFT

SECTION 1 GENERAL REQUIREMENTS

WILDCAT CANYON ROAD SPECIFICATION NO SLIDE REPAIR BIDDER'S PROPOSAL (continued)

Preformed Metal Roofing and Siding

SECTION PIPE HANGERS AND SUPPORTS

SECTION WINDOW WASHING SYSTEMS

State of Illinois Department Of Transportation CONSTRUCTION INSPECTOR S CHECKLIST FOR STORM SEWERS

TARIFF CODE and updates standard

San Antonio Water System Standard Specifications for Construction ITEM NO. 854 SANITARY SEWER LATERALS

SECTION STORM DRAINAGE STRUCTURES. 1. Trench excavation, backfill, and compaction; Section

TABLE OF CONTENTS. Manhole, Frame, and Cover Installation (includes Drop Manhole) Additional Manhole Depth

TS 813 GROUNDING AND BONDING TTD TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD CONTROLLER CABINET GROUNDING

PTS HELICAL PIERS INSTALLATION SPECIFICATIONS NOTICE

A. The shade structure contractor shall be responsible for the design, engineering, fabrication, and supply of the work specified herein.

SECTION 807 PUMP STATION REHABILITATION

TECHNICAL SPECIFICATION SERIES 8000 PRECAST CONCRETE

SECTION FACILITY STORM DRAINAGE PIPING

GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables

Final inspections are completed by site visit only. Access to fenced yards shall be planned.

INSTRUCTIONS FOR COORDINATION SECTION SOLID SURFACE FABRICATIONS

TECHNICAL SPECIFICATION FOR HIGH TENSION LINE HARDWARE AND ACCESSORIES FOR ACSR PANTHER & WOLF CONDUCTOR

CCU Engineering Specifications. Section PRECAST CONCRETE PRODUCTS

Product Manual CLF-PM0610 (revised January, 2012)

FORM DESIGN. easy to work with, and generally available.

SECTION 55 PIPE FOR STORM DRAINS AND CULVERTS (FAA D-701)

STANDARD SPECIFICATIONS FOR PRIVATE BUILDING SEWER LINES IN PUBLIC RIGHT-OF-WAY

3. Contractor shall ensure that all permits are obtained prior to any construction. Contractor shall be responsible for all utility fees.

Display hidden notes to specifier. (Don't know how? Click Here) A. Advanced Upcoiling Security Grilles, power operated.

Section SEWER PIPE INSTALLATION AND TESTING

SECTION SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS

CT-02 CABLE TRAY SYSTEMS

SUBDRAINS AND FOOTING DRAIN COLLECTORS. A. Construct subdrains, subdrain cleanouts and outlets, and footing drain collectors.

SECTION 6 SANITARY SEWER MAIN 6.01 SCOPE

The work of this Section includes furnishing and installing Reinforced Concrete Pressure Pipe as shown on the Drawings and as specified.

TECHNICAL SPECIFICATIONS CONCRETE SIDEWALKS, DRIVEWAYS AND CURB AND GUTTER

CONCRETE SEGMENTAL RETAINING WALL SYSTEM

Wastewater Capital Projects Management Standard Construction Specification

1.02 SYSTEM DESCRIPTION

High Strain Dynamic Load Testing of Drilled Shafts

STANDARD AND SPECIFICATIONS FOR STORM DRAIN INLET PROTECTION

SECTION 36 - CAST-IN-PLACE CONCRETE PIPE (CIPCP) TABLE OF CONTENTS

Section 2100-Trenching and Tunneling

Acceptance Codes APPENDIX - A. Acceptance Criteria

MANUFACTURED HOUSING USED AS DWELLINGS

Section 600 Incidental Construction

SPECIFICATIONS. INTERLOCKING CONCRETE POROUS PAVING UNITS or Permeable Interlocking Concrete Pavers (PICP)

SECTION GROUND WATER STORAGE TANKS

SECTION SANITARY SEWER AND STORM DRAIN SYSTEMS

PROJECT TITLE : 2-STOREY RESIDENCE LOCATION : ALONG DAANG HARI,MOLINO.BACOOR,CAVITE OWNER : CUEVASVILLE REALTY

AIR RELEASE, CLEANOUT, AND SEWER MANHOLES

SECTION STORM DRAINAGE TABLE OF CONTENTS

CONSTRUCTION OF PERIMETER FENCE - COMMERCIAL AND T&D OFFICE COMPOUND, ONVERWAGT

Specifications for Lightning Protection. ASAE Engineering Practice

SWIMMING POOL, SPA, & HOT TUB GUIDELINES

STANDARD SPECIFICATIONS SECTION PRECAST REINFORCED CONCRETE MANHOLES AND MANHOLE BASES. 1. Structure Earthwork: 02200

SPECIFICATIONS FOR PRECAST MODULAR BLOCK RETAINING WALL SYSTEM (revised 11/5/13)

SECTION LS 2530 SANITARY SEWERS. A. General: Submit the following in accordance with The General Conditions.

Specifications. Preformed Metal Wall and Roof Panels. Alcoa Cladding Systems Manufacturing Plant 100 Industrial Boulevard Eastman, Georgia 31023

Mobile Home Pre-Inspection Checklist

SECTION CABLE TRAYS. A. Continuous, rigid, welded steel or stainless steel wire mesh cable management system.

SECTION UNDERGROUND ELECTRIC SERVICE

SECTION PRECAST CONCRETE STRUCTURES

CONCRETE SEGMENTAL RETAINING WALL SYSTEM

SECTION ALUMINUM HANDRAIL AND RAILING SYSTEMS WITH DECORATIVE METAL PANEL INFILLS

Cable Support Solutions

Proposed Minimum Subterranean Termite Treatment Standards

SAMPLE GUIDE SPECIFICATIONS FOR OSTERBERG CELL LOAD TESTING OF DEEP FOUNDATIONS

Section 402. STORM SEWERS

SECTION EARTH MOVING

UNIFIED FACILITIES GUIDE SPECIFICATIONS

SEPTIC SYSTEM CONSTRUCTION REQUIREMENTS ST. MARY S COUNTY HEALTH DEPARTMENT

SECTION PREFORMED METAL STANDING SEAM ROOFING

How to secure your property after a disaster

ENGINEERING SPECIFICATION FIBERGRATE MOLDED GRATING. January 24,

Transcription:

SECTION 02832 AIRPORT SECURITY FENCING PART 1-GENERAL 1.1 SUMMARY A. Section includes: Construct airport security chain-link fence and gate at specified areas and conforming lines, grades, details indicated or established by Engineer. B. Related Sections 1.2 REFERENCES 1. Section 01300 Submittals. 2. Section 01700 Contract Close-out. 3. Section 03300 Cast-in-Place Concrete. A. American Society for Testing and Materials (ASTM): 1. ASTM A90 Weight of Coating on Zinc-Coated (Galvanized) Iron or Steel Articles 2. ASTM A121 Zinc-Coated (Galvanized) Steel Barbed Wire. 3. ASTM A123 Zinc (Hot Dip Galvanized) Coatings on Iron and Steel Products. 4. ASTM A153 Zinc Coating (Hot Dip) on Iron and Steel Hardware. 5. ASTM A392 Zinc-Coated Steel Chain-Link Fence Fabric. 6. ASTM A446 Specification for Steel Sheet, Zinc-Coated (Galvanized) by the Hot-Dip Process, Structural ( Physical) Quality. 7. ASTM A491 Aluminum-Coated Steel Chain-Link Fence Fabric 8. ASTM A569 Steel Carbon (0.15 Maximum, Percent), Hot Rolled Sheet and 1

Strip-Commercial Quality. 9. ASTM A570 Hot-Rolled Carbon Steels, Sheet and Strip Structural Quality. 10. ASTM A585 Aluminum-Coated Steel Barbed Wire. 11. ASTM A824 Metallic-Coated Steel Marcelled Tension Wire for use with Chain Link Fence. 12. ASTM F1043 Strength and Protective Coating on Metal Industrial Chain Link Fence Framework 13. ASTM F1083 Pipe, Steel, Hot-Dipped Zinc-Coated ( Galvanized) Welded, for Fence Structures. 14. ASTM F1345 Zinc-5% Aluminum-Mischmetal Alloy-Coated Steel Chain-Link Fence Fabric. B. Federal Specifications (FS) 1.3 SUBMITTALS 1. FSRR-F-191/3D Fencing, Wire and Post, Metal (Chain-Link Fence Posts, Top Rails and Braces). 2. FSRR-F-191/4 Fencing, Wire and Post, Metal ( Chain-Link Accessories). 3. FAA-F-162 Chain-Link Fences A. General-Comply with requirements of Section 01300. B. Product Data 1. Manufacturer s Catalog Data: a. Complete Fence Assembly b. Complete Gate Assembly c. Gate Hardware and Accessories 2

2. Material Safety Data Sheet C. Shop Drawings 1. Erection/Installation Drawings: a. Complete Fence Assembly b. Complete Gate Assembly c. Gate Hardware and Accessories D. Samples 1. Fabric Fence 2. Line Post 3. End, Corner s Posts 4. Sleeves 5. Top Rail 6. Tension Wire 7. Barbed Wire Supporting Arms 8. Barbed Wire 9. Post Tops 10. Gate Post 11. Gate Hardware and Accessories 12. Wire Ties 13. Post Brace Assembly E. Quality Control Submittals 3

1. Test Reports for fence posts and braces 2. Certificates Manufacturer s Certificates certifying that all materials comply with applicable requirements. 3. Manufacturer s Instructions a. Fence Assembly b. Gate Assembly c. Hardware Assembly d. Accessories F. Contract Close-out Submittals: Comply with Section 01700 1.4 QUALITY ASSURANCE A. Manufacturer s Quality Control And Assumed Manual. B. Engineers may inspect all fence materials at place of manufactures. C. Engineer will inspect installation for compliance with requirements herein. 1.5 PROJECT CONDITIONS A. Take Field measurements prior to preparations of shop drawing and fabrication. B. Coordinate installation with concrete work to insure that all fencing and appurtenances are properly supported to require lines and grades when concrete is placed. 1.6 METHOD OF MEASUREMENT 4

A. Quality of Chain-Link fence to be paid for shall be number of linear meter, in place, completed and accepted B. Measurement will be along top of fence from center to center of end posts, excluding length occupied by gate openings. C. Gates will be measured as complete units 1.7 BASIS OF PAYMENT A. Accepted quantities of Chain-Link fence will be paid for at contract unit price per linear meter which price and payment shall be full compensation for furnishing and placing all materials, and for all preparation, erection, and installation of these materials, and for all labor, equipment, tools, and incidentals necessary to complete the work. B. Payment for driveway or walkway gates will be made at a contract unit price for each gate. C. Payment will be: 1. Chain-Link Fence--per linear meter 2. Driveway Gates--per each 3. Walkway Gates--per each D. Cost of removing and disposing of material shall not constitute a pay item and shall be considered incidental to fence construction. E. No extra compensation shall be made for rock excavation F. Installation of ground rods shall no constitute a pay item and shall be considered incidental to fence construction. PART 2-PRODUCTS 2.1 MANUFACTURERS 2.2 MATERIALS A. General: Fence and gate materials shall conform to ASTM Standards requirements 5

herein. B. Fabric 1. Fabric shall be woven with 9-gauge (galvanized steel wire) (polyvinyl chloride (PVC)-coated steel) (aluminum coated steel) (zinc-5% aluminum mischmetal) wire in 50mm mesh and shall meet requirements of ( ).) The fabric shall be woven form (9) gauge aluminum-coated steel wire in 50mm mesh and shall conform to requirements of ASTM A 491 or Galvanized steel fabric shall conform to requirements of ASTM A 392, Class 2 or Zinc-5% aluminum mischmetal alloy coated steel shall conform to requirements of ASTM F1345, Class 2 Metallic-coated fabric shall have clear acrylic coating applied to selvage area after weaving. C. Barbed Wire 1. Comply with ASTM A585 2. Each line of barbed wire shall consist of 2-strand of No. 12-½ gauge aluminum coated wire twisted with 4-point No. 14 gauge barbs spaced 125mm on center. D. Posts, Rails, and Braces 1. Posts, rails, and braces furnished for use in conjunction with zinc-coated, zinc 5% aluminum mischmetal alloy coated, or aluminum-coated steel fabric shall be of zinc-coated steel, zinc/polymer-coated steel, or zinc 5% aluminum mischmetal alloy coated steel framework. Those furnished for use in conjunction with alumumum alloy favric shall be alumunum alloy. 2. Line posts, rails, and braces shall be (galvanized steel pipe) ( zince/polumercoated steel pipe) (vinyl-coated steel) (roll formed) conforming to the requirements of ( ). Galvanized steel pipe shall conform to the requirements of ASTM F 1083. 6

Zinc/polymer-coated steel pipe shall conform to the requirements of ASTM A 569 or ASTM A 446, Grade D. Exterior coating shall be in accordance with ASTM F 1043, Type B or D. Roll-formed sections shall be fabricated from material meeting the requirements of ASTM A 570, Grade 45, and shall be galvanized in accordance with the requirements of ASTM F 1043, Type A, or coated with zinc-5% aluminum mischmetal alloy in accorfance with ASTM F 1043, Type C. C. The dimemsions of the posts, rails and braces shall be in accordance with Tables 1 through VI of Federal Spec. RR-F-191/3D. D. Gates 1. Gates frames shall consist of (galvanized steel pipe) (pplymer-coated steel pipe) ( aluminum alloy pipe) and shall conform to specifications for same material under paragraph D. 2. Fabric shall be of te same type material as used in fence. E. Wire Ties and Tension Wires 2.3 ACCESSORIES 1. Wires ties for use in conjunction with given type of fabric shall be of same material and coating weight indentified with fabric type. 2. Tension wire shall be 7-gauge marcelled steel wire with same coating as fabric type and shall conform to ASTM A 824. 3. All material shall conform to FS-RR-F-191/4. A. Miscellaneous Fittings and Hardware 1. Miscellaneous steel fittings and hardware for use with (zinc-coated) (aluminum-coated) (zinc5% aluminum mishcmetal alloycoated) steel fabric shall be of commercial grade steel or better quality, wrought or cast as appropriate to the article, and sufficient in strength to provide a balanced design when used in conjunction with fabric posts, and wires of the quality specified herein. (All steel fittings and hardware shall be protected with a zinc coating applied in conformance with ASTM A 153.) 7

Barbed wire support arms shall withstand load 113kg applied vertically to outermost end of arm. B. Concrete: Comply with Section 03300 C. Marking 1. Concrete shall be of a commerial grade with minimum 28day compressive strength of 17250 Kpa. 1. Each roll of fabric shall carry tag showing kind of base metal (steel, aluminum alloy number), kind of coating, gauge of wire, lenght of fencing in roll, and name of manufacturer. Part 3 - EXECUTION 3.1 General A. Fencing installation shall not begin before final grading has been completed and finished elevations have been established, unless otherwise approved. 3.2 PREPARATION A. Surface Preparation 3.3 INSTALLATION 1. All Trees, brush, stumps, logs, and other debris which would interfere with proper construction of fence in required location shall be removed a minimum width of 61 cm on each side of fence centerline before starting fencing operations. A. General 1. Fence shall generally follow contour of ground. 2. Grading shall be preformed where necessary to provide neat appeareance. B. Installing Posts 1. All posts shall be set in concrete at required dimension and depth and at spacing indicated. 8

2. Posts should be spaced not more than 3 m apart and should be set minimum of 90 cm, posts should be set accordingly. Posts holes shall be in proper alignment so that there is minimum of 75 mm of concrete on all sides of posts. 3. Concrete shall be thoroughly compacted aroud posts by tamping or vibrating and shall have smooth finish slightly higher than ground and sloped to drain away from posts. 4. All Posts shall be set plumb ans to require grade and alignment. 5. No materials shall be installed on posts, nor shall posts be distrubed in any manner within 7 days after individual post footing is complete. 6. Should rock be encountered at depth less than planned footing depth, hole 50mm larger than greatest dimension of posts shall be drilled to depth of 300mm. 7. After posts are set, remainder of drilled hole shall be filled with grout, composed of one part Portland cement and two parts mortar sand. 8. Any remaining space above rock shall be filled with concrete in the manner described above. 9. In lieu of drilling, rock may be excavated to required footing depth. C. Installing Top Rails 1. Top Rail shall be continnuous and shall pass through post tops. 2. Coupling used to join top rail lengths shall allow for expansion. D. Installing Braces 1. Install horizontal brace rails, with diagonal truss rods and turnbuckles at all terminal posts. E. Installing Fabric 1. Wire fabric shall be firmly attached to posts and braced in manner shown 9

on plans. 2. All wire shall be stretched taut and shall be installed to required elevations. F. Tolerances 1. Posts Shall be straight and plumb within vertical tolerance of 7mm after fabric has been stretched. 2. Bottom of fence fabric shall be no less than 25 mm or no more than 100mm from ground surface. 3. Fencing and gates shall be true to line wigh no more than 13 mm deviation from established enterline between line posts. 4. Vertical clearance between strands of barbed wire shal be less than 150 mm. 5. At locations of small natural swales or drainage ditches and where it is not pratical to have fence conform to general contour of ground surface, longer posts may be used and multiple strands of barbed wire stretched thereon to span opening below fence. 6. Openings below fence shall be spanned with barbed wire fastened to stakes. 7. Defects shall be repaired as directed. G. Interface with Others 1. General a. Electrical grounds shall be constructed where power line passes over fence or indicated locations on plans b. Ground shall be installed directly below point of crossing or at 150 m intervals. 2. Installing Electrical Grounds a. Ground shall be accomplished with copper clad rod 8 feet (240 cm) 10

long and minimum of 15 mm in diameter driven vertically until top is 150 mm below ground surface. b. No. 6 solid copper conductor shall be clamped to rod and fence in such manner that each element of fence is grounded. 11