Minimum Standards for a Cross-Connection Control Program



Similar documents
Revised April (May) 2015

FAQ and Device/Usage Chart. What Is a Cross-Connection? What Is Backflow Prevention? What Is Backflow?

CROSS-CONNECTION CONTROL PROGRAM MANUAL

ORDINANCE NO THE CITY COUNCIL OF THE CITY OF NORTH LAS VEGAS, NEVADA, DOES HEREBY ORDAIN AS FOLLOWS:

Cross Connection Control Policy

UTILITIES DEPARTMENT

CHAPTER 26 PLUMBING CODE

WESTFIELD WATER RESOURCES DEPARTMENT

Cross Connection Control and Backflow Prevention Program Guidelines

Metropolitan Domestic Water Improvement District. Backflow Prevention Control Ordinance. Ordinance No

77 ILLINOIS ADMINISTRATIVE CODE, PART 890 (NEW) ILLINOIS PLUMBING CODE (02/04) SUBPART I: WATER SUPPLY AND DISTRIBUTION

City of West Chicago Community Development Department 475 Main Street, West Chicago, IL Phone: (630) x 131 / Fax: (630)

(a) Purpose. The purpose is to safeguard potable water supplies by preventing backflow into public water systems.

CITY OF BAY CITY ORDINANCE NO. 628

Chapter 8 Water and Sewage Systems

Cross-Connection Control. Protecting the potable water supply from contamination.

ALBUQUERQUE BERNALILLO COUNTY WATER UTILITY AUTHORITY CROSS CONNECTION PREVENTION AND CONTROL ORDINANCE

ARTICLE 1141 Cross Connection Control Program

LOS ANGELES UNIFIED SCHOOL DISTRICT INDUSTRIAL WASTEWATER MANAGEMENT PROCEDURES

TUCSON BACKFLOW ORDINANCE ARTICLE V. BACKFLOW PREVENTION AND CROSS-CONNECTION CONTROL*

Equipment Breakdown. The extended property coverage you need for the equipment you rely on.

CHAPTER 17. Sewers and Sewage

HARRIS COUNTY MUNICIPAL UTILITY DISTRICT NO SH 249, Suite 210, Houston, Texas Phone Number (281)

PUBLIC WORKS TECHNICAL BULLETIN July 2001 CROSS-CONNECTION CONTROL AT ARMY INSTALLATIONS

New York State Department of Environmental Conservation 625 Broadway, Albany, NY Environmental Self Audit For Small Businesses

Backflow Bulletin #1

THE CORPORATION OF THE CITY OF COURTENAY BYLAW NO A bylaw to amend Storm Sewer Bylaw No. 1402, 1986

American Safety Insurance Company

The Plumbing Pipeline

6. Principles of effective plumbing systems

15. Design of plumbing systems for industrial and temporary applications

Presented By: Fred J. Sánchez Water Quality Operations Supervisor

Element D Services Plumbing

VEHICLE SERVICE FACILITIES. Best Management Practices

ORDINANCE NO Ordinance No Page 1 of 7. Language to be added is underlined. Language to be deleted is struck through.

A Cross-Connection is a. water system and a nonpotable CROSS-CONNECTION CONTROL BACKFLOW PREVENTION CROSS-CONNECTION CROSS-CONNECTION

Questions and Answers for Local Governments

WHITE PLAINS PLUMBING CODE PART 1. GENERAL REQUIREMENTS

CROSS-CONNECTIONS AND BACKFLOW PREVENTION MANUAL

FREQUENTLY ASKED QUESTIONS

Property Condition Disclosure Statement

POLLUTION PREVENTION FACT SHEET: AUTOMOBILE MAINTENANCE

SERVICE RULES AND REGULATIONS LOUISVILLE WATER COMPANY

B-1 Buildings & Service Maintenance

SERVICE RULES AND REGULATIONS LOUISVILLE WATER COMPANY

DIVISION D ELECTRICITY, GAS, WATER AND WASTE SERVICES

2010 Annual Drinking Water Quality Report Collier County Water Department

Substance Abuse Treatment Facility

Plumbing Installations. A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling

ARTICLE 252. PD 252.

GUIDANCE FOR DEVELOPMENT OF SPILL AND SLUG PREVENTION CONTROL PLANS AND FACILITIES FOR THE CITY OF ATTLEBORO SEWER USERS

NYC Department of Education Building Condition Assessment Survey BROADWAY EDUCATION CAMPUS - MANHATTAN, 26 BROADWAY, MANHATTAN, NY, 10004

Standard terms and conditions

CIPHI s 75 th Annual conference Safe Drinking Water Course Cross Connection Control and Backflow Prevention

GUIDANCE DOCUMENT FOR SIZING AND INSTALLATION OF GREASE TRAPS AND INTERCEPTORS

Work Practice: Wastewater Collection System Maintenance Plan Potential Safety Hazards


WHOLESALE/RETAIL PETROLEUM SIC CODES TO NAICS CODES For more detail information go to:

Sample Exam Questions and Recommended References for ABC s Backflow Prevention Assembly Tester Exam

CITY OF CARROLLTON. Business Name:

TCEQ Requirements. Effective Cross-Connection: Why & How. Plumbing Ordinance. Plumbing Ordinance. Plumbing Ordinance. Plumbing Ordinance

Presented by: Jeremy Harris, E.I. Department of Health & Hospitals/ Office of Public Health Engineering Services

CITY OF LAWNDALE Commercial/District Use Table

REQUIREMENTS FOR NEW 2 & LARGER WATER SERVICE from DES MOINES WATER WORKS

WESLEY BRIAN HUTTON KNOXVILLE, TENNESSEE LICENSED MASTER PLUMBER. Dear: Human Resources

TITLE: EXAMPLES OF RETAIL SALES AND NUMBER: ES.A.10.3 SERVICE ESTABLISHMENTS SEE ALSO: ES.A.10.1 ES.A.10.2 CHAPTER: RCW (3) ISSUED: 1/2/2002

TEXAS STATE BOARD OF PLUMBING EXAMINERS EXAMINATION AND REGISTRATION Endorsement Training Programs

Title 15 - Mississippi Department of Health Part 20: Bureau of Public Water Supply Subpart 72: Public Water Supply

CLARIFICATION OF REGULATORY REQUIREMENTS FOR POINT-OF-USE PROTECTION CONTAMINATION BY BACKFLOW

The Town of Lakeshore Basement Flooding Information to Residents

Plumbing Code in Commercial Kitchens

The Plumbing Pipeline

This Food Safety Plan was developed in New York as an example for growers. Each grower must develop their own plan which fits their operation.

GRU Purchasing Material Group Codes

No Environmentally Sensitive NAICS Codes. Environmentally Sensitive NAICS Codes. No Further Investigation 9

Commercial Automobile Insurance Manual

APPLICATION FOR NEW CONSTRUCTION

When Should Examination Preparation Begin?

How To Get A Stormwater Discharge Permit In A City Of Scottsdale

ATTACHMENT 3: SPECIFICATION FOR SEWER CLEANING

FIRE SUPPRESSION INSTALLATION CITY OF HARRISONBURG, VIRGINIA

ARLINGTON COUNTY CODE. Chapter 18 PLUMBING AND GAS CODES

ORDINANCE NO. 3 OF 2009

Identifying Your Hazardous Waste

CITY OF UKIAH, CA BUSINESS LICENSE FEE INFORMATION

PBX Series Quick Fit Connector Bimetallic Steam Traps

Plumbing Apprenticeship Program Curriculum

WHITE OAK BEND MUD Jones Rd, Suite 120, Houston, Texas Phone Number (281)

EMERGENCY RESPONSE PLAN

INCENTIVE PAY SCHEDULES

CROSS-CONNECTION CONTROL MANUAL

City of Clare Grease and Sand Interceptor Policy

Transcription:

Minimum Standards for a Cross-Connection Control Program Arkansas Department of Health Bureau of Environmental Health Services Division of Engineering 4815 West Markham Street Little Rock, Arkansas 72205 (501) 661-2623 Revised December 1997 msfacccp Arkansas Department of Health

Division of Engineering Minimum Standards for a Cross-Connection Control Program (Revised December, 1997) I. Statement of Purpose These Minimum Standards for a Cross-Connection Control Program are intended to describe a program by which the water in the public water system facilities is protected from contamination by backflow, via either backpressure or backsiphonage. It is not intended to require a water utility to implement an isolation type cross-connection control program. In general, the program described in these minimum standards is a containment type program. Containment programs do not necessarily insure that the facility being served is in full and complete compliance with the requirements of the Arkansas State Plumbing Code regarding cross-connections. Containment type programs do not generally protect users of water within the facility from cross-connections which occur within the facility plumbing. Internal facility plumbing is under the jurisdiction of the Arkansas State Plumbing Code, as well as any local plumbing codes. II. Definitions A. Facility with Backflow Potential - Any commercial or industrial facility 1 where: 1. There is an auxiliary water supply which is connected to the potable water piping; or 2. There is piping for conveying liquids other than potable water, where that piping is under pressure and is installed in proximity to potable water piping; or 3. There is intricate plumbing which makes it impractical to ascertain whether or not cross-connections exist; or 4. There are cross-connections or potential cross-connections. 1 Please note that these minimum standards apply to a program which covers commercial and industrial facilities only. The Rules and Regulations Pertaining to Public Water Systems do not require that the program address residential facilities at this time. Page two

B. Facility with High Hazard Backflow Potential - Any facility where the substance which could backflow is hazardous to human health. C. Facility with Medium Hazard Backflow Potential - Any facility where the substance which could backflow is objectionable, but does not pose an unreasonable risk to health. D. Facility with Low Hazard Backflow Potential - Any facility where the substance which could backflow is objectionable, but does not pose an unreasonable risk to health, and there is no possibility of backpressure in the downstream piping system. III. Program To be an acceptable cross-connection program, as required by Section VII.E, of the Rules and Regulations Pertaining to Public Water Systems, the program must accomplish the following: A. The water system or parent organization shall have an ordinance, by-law, regulation or other enabling authority for implementing the cross-connection control program. B. All commercial and industrial facilities classified as High Hazard shall be separated from the public water system by a reduced pressure principle backflow prevention assembly (RP) 2 or an air gap approved 3 by the cross-connection control program. The RP assembly or air gap may be located on the service line on the utility side of the meter, on the service line on the customer side of the meter or within the plumbing system. If the program allows the RP assembly or air gap to be located within the plumbing system, annual inspections (surveys) are required to insure that additional high hazard fixtures have not been installed 2 Special consideration may be given when retrofitting existing facilities when the installation of an RP would result in residual pressures less than 15 psi. 3 All devices must meet the requirements specified in the Arkansas State Plumbing Code. Page three

within the plumbing system, upstream of the backflow prevention assembly. C. All commercial and industrial facilities classified as Medium Hazard shall be separated from the water system by a double check valve backflow prevention assembly (DC) approved by the cross-connection program, installed as specified above and shall be inspected (surveyed) every three years, to insure that no high hazard fixtures have been installed within the plumbing system. D. All commercial and industrial facilities classified as Low Hazard shall be inspected (surveyed) every five years, to insure that no medium hazard or high hazard fixtures have been installed within the plumbing system. If such fixtures are found, the facility shall be reclassified to Medium Hazard or High Hazard, as appropriate. E. The issuance of a building permit to any commercial or industrial establishment shall cause the facility to be inspected following the completion of work, unless the facility is already separated from the water system by an air gap or RP assembly. F. For new or expanded fire protection systems 4, fire protection lines shall be separated from the public water system by a double check valve assembly (DC), unless the system utilizes antifreeze or other chemicals within the fire protection lines. In such cases, an RP type backflow prevention assembly or an air gap, approved by the cross-connection control program is required. 4 Special consideration may be given when retrofitting existing facilities when the installation of an RP would result in residual pressures less than that necessary to meet fire protection standards. (See separate Policy for Cross-Connection Control on Fire Protection Systems.) Page four

G. Service lines (including fire service lines) for multi-use developments, where the ultimate hazard is unknown, shall be hydraulically designed to allow for the future installation of RP assemblies, without reducing fire protection ratings. H. All backflow prevention assemblies required under the previous paragraphs shall be tested initially and annually thereafter, as required by Chapter 10 of the Arkansas State Plumbing Code. The water system or its parent organization may choose to do the testing, or require the water user or owner of the backflow prevention assembly to have the testing done. I. Backflow prevention assemblies found to be functioning improperly shall be properly repaired by the water user 5 or owner of the assembly, or the water system shall discontinue service to the facility as required by Section XVI.A of the Rules and Regulations Pertaining to Public Water Systems. IV. Records The water system shall maintain records which include the following: A. A master list of all commercial and industrial establishments connected to the water system. B. Name, address and telephone number of the Responsible Managing Employee of the water system s cross-connection control program. 5 Backflow prevention assemblies located on the customer s side of the meter may be repaired only by a licensed plumber certified as a Repair Technician in accordance with the Arkansas State Plumbing Code. On the utility side of the meter, repairs must be made only by a certified Repair Technician but he does not necessarily have to have a plumber s license. Page five C. For each commercial and industrial establishment:

1. name and address of establishment. 2. date establishment was inspected (surveyed). 3. hazard level determination. 4. backflow prevention method used (air gap, RP, DC or other). 5. date RP or DC was initially tested and test results for the initial test and subsequent annual tests. 6. identification data on each RP or DC 6 including, make, model, serial number and installation location. IV. Non-Limitation of Liability Implementation of a program satisfying these minimum standards should not be presumed to release any city, town or water district or association from complying with the appropriate sections of the Arkansas State Plumbing Law concerning plumbing code enforcement, inspection or cross-connection control. 6 Normally, for a containment type configuration only one RP or DC would be necessary to separate the establishment s plumbing system from the public water system. However, if an isolation type configuration is utilized, then it will become necessary to keep records on all RP and DC backflow prevention assemblies within the plumbing system. Page A-1 Appendix High Hazard Facilities Revised December 1997

This list is provided as a guide to cross-connection control administrators. By no means does this list include all possible High Hazard facilities. The list is provided to aid the cross-connection control surveyor or inspector in making a determination of the types of establishments which under normal circumstances would tentatively meet the definition of a High Hazard facility. The ADH always recommends an inspection of an existing facility to confirm the hazard level before requiring a backflow preventer. Under special circumstances, specific facilities covered by the catagories listed below might qualify as Medium or Low Hazard facilities. For new construction, the facilities listed below should have a RP type backflow prevention assembly designed into the water service line. Agricultural watering station Air craft plants and airfields used by crop dusters Asphalt plants Automobile and truck dealers (using power wash and steam cleaning equipment) Auto radiator repair shop Autopsy facilities Auxiliary water supplies Baking facility Beverage bottling plants Bath house Battery manufacturer or processor Blood banks Bottled water manufacturer Breweries Buildings with water booster pumps, trap primers or sewer ejectors Canneries Car washes Cemetary Chemical, biological or radiological research facilities Chemical or plating plants Chiropractor s offices Cleaners (processing plant) Cold storage plants Commercial laundries Concrete mixing plants Concrete products manufacturer Crime laboratories Dairies and milk distributors Dental clinics Dockside facilities Doctor s (medical) offices Farms handling or diluting pesticides, herbicides or insecticides (commercial) Film processing facilities Food processing plants Funeral home Golf courses Government facilities Gravel processing plant Hazardous waste processing or storage facilities Page A-2 High Hazard Facilities (continued) Health clubs and fitness centers Hog farms Hospitals Incineration facilities

Industrial plants Irrigation systems Laboratories (chemical, biological or radiological) Laundries (commercial, excluding laundrymats) Livestock facilities (where held for sale or slaughter;i.e, cattle, swine, poultry, emus, ostriches) Lumber processor Manufacturing plants using water solutions of toxic chemicals Manufacturing plants using pressurized process water Marinas Medical, dental, health or veterinary clinics Metal plating, etching, passivation or pickling plants Mining operations Morgues Mortuaries Munitions production plant Multi-storied buildings (over four floors) Nursery, shrubbery or garden centers Nursing or convalescent homes Oil or gas production, storage, transmission facilities Packing houses Paper mill Pesticide processors or applicators Plants handling radioactive materials Power plants Pressure vessel repair, testing and maintenance facilities Propane or other LPG handling facility Radioactive material plants and handling facilities Railroad yards Restricted facilities (inspection by water utility personnel not allowed) Rubber manufacturing plants Sand or gravel plants Sanitariums Schools with chemical or biological laboratories (includes high schools and colleges) Sewage treatment plants and sewage grinding and pumping stations Slaughter houses Sod farms Steel manufacturing facility Swimming pools (commercial) Tank cleaning facilities Tanneries Tattoo parlour Taxidermist Wastewater treatment facilities Waterfront facilities Water treatment plants Veterinary clinics Zoos (including safari parks, petting zoos, alligator farms, etc.)