No. CP-UM-7E DIGITRONIK Digital Indicating Controller SDC User s Manual Thank you for purchasing the DIGITRONIK Digital Indicating Controller SDC. This manual contains information for ensuring correct use of the DIGITRONIK Digital Indicating Controller SDC. It also provides necessary information for installation, maintenance and troubleshooting. This manual should be read by those who design and maintain devices and operator control panels that use the DIGITRONIK Digital Indicating Controller SDC. Be sure to keep this manual nearby for handy reference. Index Chapter NAMES & FUNCTIONS OF PARTS... Chapter 2 STRUCTURE... 2 Chapter MOUNTING... Chapter 4 WIRING... 6 Chapter 5 INITIAL SETTINGS... 9 5- Overall Operation Flow... 5-2 Setup Items... 5- Parameter Settings... 8 5-4 Event Settings... 2 5-5 Setting... 2 Chapter 6 TUNING... 24 6- Selecting the Control Method... 24 6-2 Self-tuning... 24 6- Cautions During Self-tuning... 25 6-4 Auto-tuning... 26 6-5 Control Troubleshooting... 27 Chapter 7 ECIFICATIONS... 28 Chapter 8 ALARM CODES... Chapter 9 MAINTENANCE... SDC Setup Worksheet... 2
RESTRICTIONS ON USE This product has been designed, developed and manufactured for general-purpose application in machinery and equipment. Accordingly, when used in applications outlined below, special care should be taken to implement a fail-safe and/or redundant design concept as well as a periodic maintenance program. Safety devices for plant worker protection Start/stop control devices for transportation and material handling machines Aeronautical/aerospace machines Control devices for nuclear reactors Never use this product in applications where human safety may be put at risk. REQUEST Ensure that this User's Manual is handed over to the user before the product is used. Copying or duplicating this User's Manual in part or in whole is forbidden. The information and specifications in this User's Manual are subject to change without notice. Considerable effort has been made to ensure that this User's Manual is free from inaccuracies and omissions. If you should find any inaccuracies or omissions, please contact Yamatake Corporation. In no event is Yamatake Corporation liable to anyone for any indirect, special or consequential damages as a result of using this product. 995 Yamatake Corporation ALL RIGHTS RESERVED This manual uses the following symbols to ensure safe operation of this controller: WARNING CAUTION Warnings are indicated when mishandling the SDC might result in death or serious injury to the user. Cautions are indicated when mishandling the SDC might result in minor injury to the user, or only physical damage to the SDC. WARNING Note that incorrect wiring of the SDC can damage the SDC and lead to other hazards. Check that the SDC has been correctly wired before turning the power ON. Before wiring, or removing/mounting the SDC, be sure to turn the power OFF. Failure to do so might cause electric shock. Do not touch electrically charged parts such as the power terminals. Doing so might cause electric shock. Do not disassemble the SDC. Doing so might cause electric shock or faulty operation. i
CAUTION Do not operate the keys with a propelling pencil or sharp-tipped object. Doing so might cause faulty operation. In addition to the standard ON/OFF and PID controls, the SDC is also equipped with self-tuning control which does not require setting control constants. Self-tuning control ensures stable control even during changes in values or during disturbances. This is achieved by monitoring and learning the characteristics of the control target to automatically output control constants. This function should be used according to the instructions given in the manual. Use the SDC within the operating ranges recommended in the specifications (temperature, humidity, voltage, vibration, shock, mounting direction, atmosphere, etc.). Failure to do so might cause fire or faulty operation. Do not block ventilation holes. Doing so might cause fire or faulty operation. Wire the SDC properly according to predetermined standards. Also wire the SDC using specified power leads according to recognized installation methods. Failure to do so might cause electric shock, fire or faulty operation. Do not allow lead clippings, chips or water to enter the controller case. Doing so might cause fire or faulty operation. Firmly tighten the terminal screws at the torque listed in the specifications. Insufficient tightening of terminal screws might cause electric shock or fire. Do not use unused terminals on the SDC as relay terminals. Doing so might cause electric shock, fire or faulty operation. We recommend attaching the terminal cover (sold separately) after wiring the SDC. Failure to do so might cause electric shock, fire or faulty operation. Use the relays on the SDC within the service life listed in the specifications. Continued use of the relays after the recommended service life has expired might cause fire or faulty operation. Use Yamatake Corporation's SurgeNon if there is the risk of power surges caused by lightning. Failure to do so might cause fire or faulty operation. ii
SAFETY REQUIREMENTS To reduce risk of electrical shock which could cause personal injury, follow all safety notices in this document. This symbol warns the user of a potential shock hazard where hazardous live voltages may be accessible. * If the controller is used in a manner not specified by Yamatake Corporation, the protection provided by the controller must be impaired. * Do not replace any component (or part) not explicitly specified as replaceable by your supplier. * All wiring must be in accordance with local norms and carried out by authorized and experienced personnel. * A switch in the main power supply is required near the equipment. * Provide delayed type (T) fuses having a rated power supply of 2mA and voltage of 25V for the mains power supply wiring of this AC power supply controller. (IEC 27) EQUIPMENT RATINGS Supply voltage to 24Vac (operating power voltage 85 to 264Vac) Frequency 5/6Hz Power consumption 7VA max. EQUIPMENT CONDITIONS Do not operate the instrument in the presence of flammable liquids or vapors. Operation of any electrical instrument in such an environment constitutes a safety hazard. Temperature: to 5 C Humidity: to 9%RH (condensation not allowed) Vibration: 2m/s 2 ( to 6Hz) Over-voltage category: Category II (IEC664-4-44, IEC6664-) Pollution degree: 2 EQUIPMENT INSTALLATION The controller must be mounted into a panel to limit operator access to the rear terminals. Make sure that the I/O common voltage and the grounding voltage excluding the power voltage are Vrms max., 46.7V (peak) max. and 7Vdc max. APPLICABLE STANDARDS EN6-, EN58-2, EN582-2, EN626 HThe CE supported model is the CT type (panel type) only. iii
Unpacking When unpacking the product, check that you have received all the items that you ordered. Name Catalog No. Q ty Remarks Body See Model Selection Guide on page 2. Installation tool 84464- (CT type only) User s Manual CP-UM-7E This manual Engineering Unit seal The CS type socket is optional. After unpacking, handle the SDC and its accessories taking care to prevent damage or loss of parts. Those using the communications function, should read the DIGITRONIK digital indicating controller User's Manual SDC Communications Function Manual. If an inconsistency is found or the package contents are not in order, immediately contact your dealer. Conventions Used in This Manual The following conventions are used in this manual. Handling Precautions : Handling Precautions indicate items that the user should pay attention to when handling the SDC. Note : Notes indicate useful information that the user might benefit by knowing. Chapter NAMES & FUNCTIONS OF PARTS key Hold this key down for at least second to enable either of the following operations. Run (RUN)/ (READY) Cancelation of event latch state Auto-tuning start/stop No. switching Factory setting is key lock state. Mode LEDs EV: Lights when event is ON. EV2: Lights when event 2 is ON. OT: Lights when the control output is ON. : Lights (or, blinks) when No. to No. is switched. : Lights when READY (control stop) PARA key Switches the display. Hold down for at least seconds to switch modes. Upper display Displays values (current temperature, etc.) or setup items This LED blinks in the self-tuning mode. Lower display Displays values (set temperature, etc.) and other parameter values. This LED blinks in the auto-tuning mode. keys: Used for incrementing numeric values and performing arithmetic shift operations.
Chapter 2 STRUCTURE Model Selection Guide Basic Model No. Mounting Control Output Input Power Voltage Option Additional Processing Specifications C T Panel mounting (Note ) S Socket mounting D Relay output 6D Voltage pulse output (for SSR drive) T Thermocouple input (K, J, E, T, R, DIN U, DIN L) R RTD (Pt/JPt) L DC voltage input ( to Vdc, to 5Vdc, to 5Vdc) A to 24Vac, 5/6Hz D 24Vdc (no polarity) None 2 event outputs (Note 2) 2 (Note 2) (Note 2) 5 2 event outputs 2 non-insulated external switch inputs current transformer input 2 event outputs 2 insulated external switch inputs current transformer input 2 event outputs RS-485 communications (CPL) current transformer input D No additional processing Provision of Inspection Sheet (Note ) (Note 2) A socket mounted model cannot be combined with 2,, 5 (option). The socket is sold as an option. CE is not covered on socket mounted models. The current transformer is sold as an option. Options Name Current transformer Model No. QN26A (5.8mm hole dia.) QN22A (2mm hole dia.) Socket (CS) 84469- Mounting bracket 84464- Hard cover 8446442- Soft cover 844644- Terminal cover 8446464-2
Chapter MOUNTING External Dimensions CT (panel mounted) 4 Unit: mm 48 Mounting bracket (included) M.5 terminal screw 48 45 6 CS (with socket) 48 4 9.5 M.5 terminal screw 5 26.5 Mounting hole for 2-M4 screw 8 7 6 5 4 48 4 7 9 2 6.5 Socket (sold separately) Model No.: 84469- Panel Cut-out Dimensions +.6 45 - (Nx48-2.5) - + N is the number of mounted units +.6 45 - +.6 45 - Handling Precautions When three or more units are gang-mounted horizontally, the maximum allowable ambient temperature is 45 C.
Chapter MOUNTING Mounting Procedure CAUTION Use the SDC within the operating ranges recommended in the specifications (temperature, humidity, voltage, shock, mounting direction, atmosphere, etc.). Failure to do so might cause fire or faulty operation. Do not block ventilation holes. Doing so might cause fire or faulty operation. Be sure to attach the terminal cover (sold separately) after wiring the SDC. Failure to do so might cause electric shock, fire or faulty operation. Handling Precautions When three or more units are gang-mounted horizontally, the maximum allowable ambient temperature is 45 C. CT Required tools Phillips screwdriver Panel 2 4 Insert the controller into the opening on the front side of the panel. Attach the mounting bracket at the rear side of the panel. Mounting Bracket Press the controller against the mounting bracket to make sure that the bracket claws enter the grooves of the controller. Tighten the top and bottom screws. (When the screws touch the panel, turn the screws another half turn.) Handling Precautions Do not operate the keys with a propelling pencil or sharp tipped object. Be sure to mount this controller on a panel. Cover terminals to prevent electric shock. An optional terminal cover is provided. (model No.: 8446464-) Do not overtighten the screws to prevent deformation of the front panel. CS Mount the socket in the panel using a DIN rail or screws. Socket 2 Wire the socket. Insert the body of the controller into the socket. 4 Insert the clasps at the top and bottom of the socket into the holes of the controller body to firmly secure it to the socket. 4
Chapter MOUNTING Location Do not install the controller in locations where it is: subject to extreme temperature and humidity subject to sulfuric or corrosive gases subject to dust or oil smoke subject to direct sunlight, or splashing by rain or water subject to mechanical vibrations and shock subject to high-voltage lines, welding machines and sources of electric noise less than 5 m from high-voltage ignition devices subject to electromagnetic fields subject to flammable liquids or vapor Removing the SDCT Case The following instructions show how to remove the SDCT body from the case. This has to be carried out only when the controller is to be replaced: 2 4 Required tools Small standard screwdriver Press the claw on the lower left side of the mask bezel with your finger. Insert the screwdriver into the groove between the mask bezel and the controller body. Press the claw while turning the screwdriver. Take hold of the front end of the body as it is forced out of the case and pull it out. Mask bezel Case Handling Precautions Turn the power OFF before carrying out the above procedure. In the case of the socket model (CS), internal components cannot be drawn out. 5
Chapter 4 WIRING Terminal Array and Wiring WARNING Before wiring, or removing/mounting the SDC, be sure to turn the power OFF. Failure to do so might cause electric shock. Do not touch electrically charged parts such as the power terminals. Doing so might cause electric shock. CAUTION Wire the SDC properly according to predetermined standards. Also wire the SDC using specified power leads according to recognized installation methods. Failure to do so might cause electric shock, fire or faulty operation. Do not allow lead clippings, chips or water to enter the controller case. Doing so might cause fire or faulty operation. Firmly tighten the terminal screws at the torque listed in the specifications. Insufficient tightening of terminal screws might cause electric shock or fire. Do not use unused terminals on the SDC as relay terminals. Doing so might cause electric shock, fire or faulty operation. We recommend attaching the terminal cover (sold separately) after wiring the SDC. Failure to do so might cause electric shock, fire or faulty operation. Use the relays on the SDC within the service life listed in the specifications. Continued use of the relays after the recommended service life might cause fire or faulty operation. Use Yamatake Corporation s SurgeNon if there is the risk of power surges caused by lightning. Failure to do might cause fire or faulty operation. Make sure all wiring is correct. Incorrect wiring may damage connected equipment. The controller does not operate until six seconds after the power has been turned ON. Special arrangements must be made when the relay output from the controller is to be used as an interlock signal. When a ground type thermocouple must be used and an external switch input is required, readout error caused by sneak path current may occur. Select the insulated external switch input model (option code ). 6
Chapter 4 WIRING CT Event output 6 Voltage output Relay output 2 + 2 Thermocouple RTD DC voltage input 4 5 + C 4 B 4 5 5 A + 2 4 5 2 4 5 Current transformer input Current transformer 2 6 7 8 9 7 Event 8 Event 2 AC power supply 9 ~ to 24Vac 5/6Hz Non-insulated external switch input RSW2 4 RSW 5 DC power supply 9 24Vdc No polarity Insulated external switch input RSW2 4 RSW 5 2/24Vdc CPL communications + 4 5 SG CS Thermocouple 2 + Voltage output Relay output 5 5 4 4 + RTD DC voltage input C 2 B 2 A + 5 6 7 4 8 9 2 Event output 7 8 Event 9 Event 2 AC power supply ~ to 24Vac 5/6Hz DC power supply 24Vdc No polarity Handling Precautions Check the model number of the controller and terminal numbers on the label on the side of the controller to prevent any wiring errors. Use crimped solderless wire connectors for M.5 screws. I/O signal lines should be routed at least 5cm away from power lines. Also, do not route I/O leads through the same distribution box or ducts. Crimped solderless wire connectors must not contact other connectors. Do not use unused terminals as relay terminals. Two or more SDC series controllers can be connected in parallel by external switch input. The controller can be connected with the Yamatake Corporation SDC2//4 series in parallel by non-insulated external switch inputs. Before connecting in parallel to other equipment, first check the conditions of the other equipment. Non-insulated external switch inputs are non-voltage contact inputs. So, use external switch for small current. Pass a lead wire for carrying the heater current through a current transformer. Use the controller with the heater current within the specification range (allowable current). Otherwise, the controller may be damaged. The controller is designed not to function for six seconds after it is turned ON. This is to allow it to stabilize. The controller then enters the operation mode. However, warm up the controller to satisfy standard accuracy requirements. Warming up takes about minutes. 7
Chapter 4 WIRING Current transformer input cannot be used for -phase motors and phase control. Devices and systems to be connected to this unit must have the basic insulation sufficient to withstand the maximum operating voltage levels of the power supply and input/output parts. Use power supply with reinforced insulation for DC model. How to connect open collector output to external switch inputs In the case of a non-insulated type external switch input SDC 4 5 In the case of an insulated type external switch input SDC 2/24Vdc 4 5 Noise Countermeasures Use power from a single-phase control power supply to reduce noise. Install an insulating transformer when power line noise is excessive and use a line filter. (model number of Yamatake Corporation line filter: 844664-) Use a CR filter to counteract fast-rising noise. (model number of Yamatake Corporation filter: 844665-) Handling Precautions When noise countermeasures have been taken, do not bundle primary and secondary cables together or route them through the same distribution box or ducts. Meanings of Symbols in the Terminal Wiring Label The following table shows the meanings of symbols in the terminal wiring label on the instrument top. Symbol ~ Alternating current Direct current Description Earth (ground) terminal CAUTION, risk of electric shock CAUTION 8
Chapter 5 INITIAL SETTINGS Set up the SDC according to the following procedure: Step Enter the customer settings in the Setup Worksheet referring to the setup items and the parameter items list. See Page Step 2 Set up item settings (in setup mode) Carry out initial setup for basic controller operations. Step Parameter settings (in parameter mode) Carry out control constant setup. 8 Step 4 Event value settings (in operation mode) 2 Step 5 values and start operation (in operation mode) 2 Set up values and start operation. Procedure Enter numeric values with the keys. How to Set up Data PARA C (Note) L O c is displayed in the lower display for about 2 seconds to indicate that an incorrect key or data entry was made. Such entries are ignored. 2 Numeric values blink for about 2 seconds. During blinking, the PARA key cannot be used. C C 4 L O c Blinking stops to indicate that the data has been set. C 9
Chapter 5 INITIAL SETTINGS 5- Overall Operation Flow Power ON S d C This value is displayed for 6 seconds. The controller enters the Operation mode when power is turned ON. Hold down the PARA key for three seconds to change modes, and use this key to move setup items between modes. No key operation for minute or more. No key operation for minute or more. Hold down the PARA key for second. Operation mode / value normal display mode Hold down the PARA key for seconds. 2 Parameter mode C T R L Hold down the PARA key for seconds. Setup mode C PARA key PARA key PARA key e l O S P C 2 PARA key PARA key PARA key e 2 h PARA key Items that are shaded are not displayed depending on the setup or installed options. Operation Mode Display Order : Basic display state S P - : No. value S P - : No. value S P - 2 : No. 2 value S P - : No. value O v T : Manipulated variable C T : Current value (CT) T : Remaining timer time T 2 : Remaining timer 2 time e L O : Event (E ) Lower limit E H I : Event Upper limit E 2 L O : Event 2 (E 2) Lower limit E 2 H I : Event 2 Upper limit C Y C L PARA key 5 d L Y PARA key Parameter Mode Settings and Display Order C T R L : Control method A T : Auto-tuning S P : No. value S P : No. value S P 2 : No. 2 value S P : No. value P : Proportional band I : Reset time D : Rate time O L : Output limit low O H : Output limit high R E : Manual reset value S B : Self-tuning startup width D I F F : Differential gap C Y C L : Time-proportional cycle P B I A : bias value H Y S I : Event hysteresis D L Y I : Event ON delay time H Y S 2 : Event 2 hysteresis D L Y 2 : Event 2 ON delay time F I L T : filter C 2 PARA key Setup Mode Settings and Display Order C : Key lock C 2 : Temperature unit C : Direct/reverse operation C 4 : Input range C 5 : Decimal point position C 6 : range lower limit C 7 : range upper limit C 9 : Lower limit C : Upper limit C : Preset output value C 2 : Operation mode display C : Number of s used C 4 : Event type C 5 : Event 2 type C 6 : Event operation when READY C 7 : External switch input type C 8 : External switch input 2 type C 2 : READY key settings C 2 2 : Communications address C 2 : Communications conditions C 2 4 : Cold junction compensation C 2 5 : Selection of time-proportional control operation
Chapter 5 INITIAL SETTINGS 5-2 Setup Items Procedure Entering the setup mode This section describes how to set the controller to the Operation mode after it is first mounted in instruments. Before this controller is first used, the input range, event operation type and other operating conditions matched to the desired instrument application must be set. This is referred to as setup. If this controller is already mounted in instruments and the setup is already completed, proceed to the next chapter. The following shows the initial settings in basic controller operation: Power ON The initial screen is displayed for about 6 seconds. S d C Example: Change the input range from "K to 4 C" to "J to 8 C". Operation mode 2 The operation mode is displayed. Hold down the PARA key for seconds to advance to the parameter mode. 2 Current value Current value Parameter mode Hold down the PARA key for seconds to advance to the setup mode. C t R L Setup mode 4 The setup mode is displayed. C 5 Press the the selection. PARA key to scroll C 4 C 4 (input range) Item setting value (default : K to 4 C) To return to the operation mode Operation mode 6 Press the, and keys to set the numeric value. 7 Hold down the PARA key for seconds or wait minute. C 4 5 2 Change to 5. The value blinks for 2 seconds before it is fixed. (5: J to 8 C) Current value (in the operation mode) Current value Handling Precautions The alarm code and blinking to indicate self-tuning or auto-tuning in progress are not displayed while moving to the setup mode.
Chapter 5 INITIAL SETTINGS Function Prompt C C 2 C C 4 C 5 C 6 C 7 C 9 C C 2 List of setup items Factory Function Selections and Setting Range Remarks Setting Key lock Temperature unit Control output direction Input type and range Decimal point position range lower limit range upper limit lower limit upper limit Manipulated variable when READY mode or Alarm occur : Key lock not engaged : Key lock engaged for items other than value, set selection, event value, key and AT 2: Key lock engaged for items other than value, set selection and key : Key lock engaged for all items : C : F : Reverse operation (heat control) : Direct operation (cooling control) Thermocouple input range : K to 2 C to 22 F 2: K to 6 C to F : K to 4 C to 7 F 4: K -2 to +4 C - to +7 F 5: J to 8 C to 5 F 6: J -2 to +4 C - to +7 F 7: E to 6 C to F 8: T -2 to +4 C - to +7 F 9: DIN U -2 to +4 C - to +7 F : DIN L to 8 C to 5 F : R to 6 C to F 2: S to 6 C to F RTD input range 2: Pt -2 to +5 C - to +7 F 22: Pt to 2 C to F 2: Pt. to 2. C. to. F 24: JPt -2 to +5 C - to +7 F 25: JPt to 2 C to F 26: JPt. to 2. C. to. F 27: Pt -5 to + C -5 to +5 F 28: Pt -5. to +. C -5. to+5. F 29: JPt -5 to + C -5 to +5 F : JPt -5. to +. C -5. to+5. F DC voltage input range 42: to 5Vdc 4: to 5Vdc 44: to Vdc : Decimal point not displayed (XXXX) : Decimal point No. display (XXX.X) 2: Decimal point No.2 display (XX.XX) : Decimal point No. display (X.XXX) -999 to +9999-999 to +9999 Setting range : range lower limit to upper limit Setting range : lower limit to range upper limit Setting range : to % (no decimal point) 22 4 Range Min. Range Max. Key lock can be canceled anytime Displayed on DC voltage input models only Displayed on DC voltage input models only Displayed on DC voltage input models only (Applied alarm code A L, 2,, 7, 9 8)
Chapter 5 INITIAL SETTINGS Function Prompt C 2 C Operation mode Number of s used and display method C 4 Event operation type C 5 Event 2 operation type C 6 C 7 C 8 C 2 Function C 2 st digit 2nd digit rd digit 4th digit Event operation in READY mode External switch input operation type External switch input 2 operation type key setting Selections and Setting Range Factory Setting Remarks st digit : Displays both and values : Displays value only 2: Displays value only 2nd digit : Does not display manipulated variable : Displays manipulated variable rd digit : Displays event settings or heater current value : Does not display event settings or heater current value 2: Does not display heater current only 4th digit : Displays time remaining of event timers/ Displays heater current and event setting with a resolution of A : Does not display time remaining of event timers/ Displays heater current and event setting with a resolution of A 2: Displays time remaining of event timers/ Displays heater current and event setting with a resolution of.a : Does not display time remaining of event timers/ Displays heater current and event setting with a resolution of.a See page 4. See page 5. See page 5. : Operation continued in READY mode : Event output OFF in READY mode Description :No operation :Switches between No. and No. 2:Switches between RUN and READY :Event timer operation 4:Event 2 timer operation 5:Event latch canceled 6:Event 2 latch canceled 7:Auto-tuning starts/ stops Operation when OFF No. RUN Timer reset Timer reset Latch enabled Latch enabled Stopped Operation when ON No. READY Timer activated Timer activated Latch canceled Latch canceled Started : Disabled : Switches between RUN and READY 2: Event latch canceled : Auto-tuning start/stop 4: value switching (two to four values) Valid when the st digit of the number of sets C is or more. Displayed on event output model Displayed on event output model Displayed on event output model Displayed on external switch input model. All operation types are alternated. Do not set the same operation type No. to external inputs and 2. (excluding : switching) When ( switching) is set for both C7 and C8, the four values can be switched. key cannot be operated when same functions as external switch input have been set.
Chapter 5 INITIAL SETTINGS Function Prompt C 2 2 Factory Function Selections and Setting Range Remarks Setting Communications address to 27 Displayed on communications model only Communications disabled when set to C 2 Communications conditions : 96bps, 8bits, even parity, stop bit : 96bps, 8bits, no parity, 2 stop bit 2: 48bps, 8bits, even parity, stop bits : 48bps, 8bits, no parity, 2 stop bits Displayed on communications model only C 2 4 Cold junction compensation : Yes : No Thermocouple input model only C 2 5 Selection of time-proportional control operation : Priority given to controllability : Priority given to life of control target (only ON/OFF operation within the timeproportional cycle) If a large fluctuation of the manipulated variable occurs during the time-proportional cycle when this item is set to, control follows this fluctuation. For this reason, control may be turned ON and OFF several times within the cycle. C (number of s used and display method) Setting st digit: Number of s used This digit sets the number of values that are used. Setting Number of s Used 2 2 4 C st digit 2nd digit rd digit 4th digit 2nd digit: Display/change method Setting No. Display in Operation Mode Change of Value during Selection (in Operation mode) Display of Front Panel LED () *See Lighting Pattern Table. OFF Disabled Pattern ON Disabled Pattern 2 OFF Enabled Pattern ON Enabled Pattern 4 OFF Disabled Pattern 2 5 ON Disabled Pattern 2 6 OFF Enabled Pattern 2 7 ON Enabled Pattern 2 No. display in Operation mode This setting selects whether or not to display the No. ( to ) in the Operation mode. Change of value during selection This setting selects whether or not to enable changing of the currently selected VP value. 4 Display of front panel LED () This setting is for distinguishing which value is currently selected by the lit/blinking state of the front panel LED ().
Chapter 5 INITIAL SETTINGS Front Panel LED () Lighting Pattern Pattern Pattern 2 No. Selected Out Out No. Selected Lit Lit No.2 Selected Blinks twice Lit No. Selected Blinks times Lit C4 and C5 settings Digit settings: Enable/Disable C4 and C5 Settings 4th digit rd digit 2nd digit st digit Controller alarm : No : Yes : No : Standby 2: Latch : Standby and latch 4: Non 5: Standby at changing : Direct : Reverse : No : upper limit alarm 2: lower limit alarm : upper and lower limit alarms 4: Deviation upper limit alarm E or E Low (E2) (E2 High) -999 to +9999-999 to +9999-999 to +9999 (E2 High) -999 to +9999 Event Settings E High (E2 High) E Low to 9999 (E2 Low) Enable/Disable Related Settings Hysteresis ON delay 5: Deviation lower limit alarm -999 to +9999 6: Deviation upper and lower limit alarms to 9999 to 9999 7: Heater line break/ overcurrent alarm -999 to E High (A) (E2 High) E Low to 9999 (A) (E2 Low) 8: Control device short-circuit alarm -999 to +9999 (A) (See note) 9: Timer to 9999 (s.) x x (Note) When the event operation type is set to timer, set digits 2, and 4 to. When the controller fault alarm (4th digit) is set, the controller fault alarm operates directly at all times. 5
Chapter 5 INITIAL SETTINGS Event operation type setting, direct/reverse operation 2nd Digit st Digit Event Description Remarks No upper limit alarm 2 lower limit alarm upper and lower limit alarms 4 Deviation upper limit alarm 5 Deviation lower limit alarm ON OFF ON OFF ON OFF ON OFF ON OFF HyS E HyS ELo HyS +E HyS E HyS EHl HyS +E See note 6 Deviation upper and lower limit alarms ON OFF HyS ELo HyS EHl 7 Heater line break/ overcurrent alarm ON OFF ELo HyS HyS EHl Current See note 2 8 Control device short-circuit alarm ON OFF HyS E Current See note 2 9 Timer External contact input ON OFF RSW Event operation ON OFF E Time Time Note Note 2 Set a negative value as the lower deviation limit (E). If a positive value is set, a temperature higher than the value will be used as the operating point. Example: Enter - to set an operating point of - C Heater line break/overcurrent and control device short-circuit alarm. Models with a current transformer input detect heater line breaks, overcurrent conditions and control device short-circuit alarms by input from the current transformer. Heater line break/overcurrent alarm (operation type: 7) Heater line break: This alarm is activated when the current at control output ON is lower than the event setting (Ex Low). Set Ex High to 9999 to disable the overcurrent alarm. Overcurrent: This alarm is activated when the current is higher than the event setting (Ex High) when the control output is ON. Set Ex Low to 999 to disable the heater line break alarm. Control device short-circuit alarm (operation type: 8) This alarm is activated when the current is higher than the event setting (Ex) when control output is OFF. Note The current display ( C t ) in the operation mode indicates the current value when the control output is ON. This displayed current value is not updated when control output is OFF and for ms after control output changes to ON. Detection of the current value is not updated for ms after the current output state changes. 6
Chapter 5 INITIAL SETTINGS The following shows an example of how to set the event setting during detection of a line break. Calculate the event setting using the heater current value at control output ON (monitor the displayed CT value) and heater current value at control output OFF (cannot be measured on the product) according to the following equation: Event setting = {(heater current value at control output ON) + (heater current value at control output OFF)}/2 2 Direct/reverse setting (C4 and C5 2nd digit setting) The direct/reverse setting is used to reverse (invert an ON/OFF relationship) the operation of the event set on the st digit. (: Direct, : Reverse) Handling Precautions Direct operation of the upper limit alarm and deviation upper limit alarm is the same as the reverse limit of lower limit alarm and deviation lower limit alarm operation. Example: Event operation type setting (st digit): ( upper and lower limits) Direct/reverse operation setting (2nd digit): (reverse) ON OFF ExLo HyS When using the, deviation upper/lower limit and heater line break/overcurrent and control device short-circuit alarm, set HYS so that the OFF point is not lost. HyS ExHI (bad example) ExLo ON OFF HyS HyS ExHI (correct setting) ON OFF ExLo HyS HyS ExHI When using the heater line break/overcurrent and control short-circuit alarm, set the area to A or more. Additional function settings (C4 and C5 rd digit setting) Standby and latch operations can be added as additional functions to an event operation type set on the st digit. Settings : No : Standby 2: Latch : Standby and Latch 4: Non 5: Standby at changing Note Standby The standby function prevents an event from turning ON, even when the ON condition of that event is satisfied at controller power ON or when the READY mode changes to the RUN mode. Event output is activated when an ON condition is satisfied after an OFF condition has been satisfied. The standby state occurs at power ON when the value is the shaded area. Latch Once event output is ON, the latch function holds an event in the ON state even when an OFF condition is satisfied. Follow the procedure below to reset the latch state. 7
Chapter 5 INITIAL SETTINGS.Set Latch Cancel to the external switch input to turn the external switch ON. 2.Reset the additional event setting function (by setting the rd digit on C4 and C5 to )..Turn the power OFF and back ON again. 4.Set Latch Cancel to the key, and hold down the key for at least one second. Handling Precautions Latch Cancel by the key is enabled for both events and 2. External switch input is valid individually for events and 2. 4 Controller alarm setting (C4 and C5 4th digit setting) This function turns ON an event when a controller alarm code (AL, AL2, AL, AL7, AL97 and AL98) is generated regardless of the direct/reverse setting of the operation mode. OR logic can be set on the st digit of the event operation type. Setting: : Disable : Enable 5- Parameter Settings Control parameter settings are shown below. Procedure Power ON This initial screen is displayed for about 6 seconds. S d C Example: Change the control method from "ON/OFF control" to "selftuning". Operation mode 2 The operation mode is displayed. Hold down the PARA key for seconds to advance to the parameter mode. 2 Current value Current value Parameter mode The parameter mode is displayed. C t R L C T R L is displayed is displayed (default: ON/OFF operation) 4 5 Use the, and keys to enter numeric values. To set other items, press the PARA key to display the item and enter numeric values as described in Step 4 above. C t R L Change to ( : self-tuning) The digit that is changed blinks for about 2 seconds. Blinking stops when the value is fixed. 8 Operation mode 6 Hold down the PARA key for seconds twice or wait minute. 2 Current value (in the operation mode) Current value
Chapter 5 INITIAL SETTINGS List of parameters Function Prompt Function Selections and Setting Range Factory Setting Remarks C T R L Control method : ON/OFF control : Self-tuning 2: Control by PID fixed values A T Auto-tuning : Stop : Start Displayed when C T R L (control method) is set to or 2. Normally, setting is not required when C T R L (control method) is set to (self-tuning). S P S P No. value No. value Same as normal value or limit value range (.) (.) Displayed when st digit of C is "" to "" S P 2 S P No.2 value No. value (.) (.) Displayed when st digit of C is "2" or "" Displayed when st digit of C is "" P Proportional band. to 999.9% 5. I Reset time to 6 s 2 D Rate time to 2 s O L O H Output limit low Output limit high % to Output limit high Output limit low to % Displayed when C T R L = or 2 R E Manual reset value to % 5 S B Self-tuning startup width/correction width setting Thermocouple/RTD input: to 5 (or. to 5.) C/ F 2 (or 2.) C/ F DC voltage input. to.% (%F.S.).5% (%F.S.) D I F F Differential gap to 25 ( or. to 25.) 5 (.5) C T R L = C Y C L Time-proportional cycle 5 to 2 s (relay output) to 2 s (voltage output) Displayed when C T R L = or 2 P B I A bias value -999 to +9999 (or -99.9 to +999.9) (.) H Y S D L Y H Y S 2 Event hysteresis Event ON delay time Event 2 hysteresis to 9999 (or. to 999.9) to 9999 s to 9999 (or. to 999.9) 5 (.5) 5 (.5) Displayed on event output model and when value of st digit of event type setting (C 4 or C 5) is to 8 D L Y 2 Event 2 ON delay time to 9999 s F I L T filter. to 2. s. 9
Chapter 5 INITIAL SETTINGS Self-tuning Startup Width Setting Any deviation width (S b) for startup can be set as a startup condition of self-tuning. Startup width (S b) is set in the parameter settings. Setting the startup width to disables (self-tuning is started only when the value changes) self-tuning by deviation. The startup width (S b) is set to in the following applications: - In the case of interference control targets (e.g. instruments that are easily influenced by changes in the temperature of adjacent (up, down, left, right) zones - In the case of control targets where disturbance is generated intermittently (e.g. packaging equipment) value value Startup width (sb) Self-tuning startup Note Event ON delay An event operation whose condition (exceeding an upper temperature limit, for example) has been satisfied is not activated until a set time has elapsed. Event setting Event output ON delay time Time ON OFF 2
Chapter 5 INITIAL SETTINGS 5-4 Event Settings (only with option installed) Procedure Power ON The initial screen is displayed for about 6 seconds. S d C Example: Set E in operation mode. Operation mode 2 The operation mode is displayed. 2 Current value Current value Press the PARA key several times to scroll the selection. E E (event setting) is displayed. 4 Use the, and keys to enter numeric values. 5 Hold down the PARA key until the and values are displayed. Set event 2 by the same procedure. E 5 2 The digits that are changed blink for about 2 seconds. Blinking stops when the value is stored. Current value Current value 5-5 Setting Procedure The following shows how to set an value. Power ON The initial screen is displayed for about 6 seconds. S d C Example: Change the value in the basic display state in the operation mode. Operation mode 2 The operation mode is displayed. 2 Current value Current value Use the, and keys to enter numeric values. 2 2 Change the value. The digits that are changed blink for about 2 seconds. Blinking stops when the value is stored. 4 Hold down the PARA key until the and values are displayed. 2 2 Current value Current value 2
Chapter 5 INITIAL SETTINGS List of Operation modes Function Prompt Upper display: Lower display: S P - S P - S P - 2 S P - O V T C T T T 2 E (E L O) E H I E 2 (E 2 L O) E 2 H I Function Normal display mode No. and value displayed Manipulated variable displayed Current (Ct) displayed Timer event remaining time displayed Timer event 2 remaining time displayed Event (lower limit) setting Event (upper limit) setting Event 2 (lower limit) setting Event 2 (upper limit) setting Selections and Setting Range : upper and lower limit Settings can be made in the C 9 to C range Not settable Not settable Not settable Not settable Depends on event operation type See pages to 2 for details Depends on event 2 operation type See pages to 2 for details Factory Setting Remarks Upper display (): Displays C 2 = XXX, XXX2 Lower display (): Displays C 2 = XXX, XXX No. switched by keys. (See note ) Displays C 2 = XX X ON/OFF control:. is displayed at OFF. is displayed at ON PID control: Values in. to. (%) range displayed C 2 = XXX is displayed on CT model Measurement range: to 55 A Event operable range: to 5 A Lights when control output is ms or more (See note 2). Displays C 2 = XXX (See note ) Displays C 2 = XXX (See note ) Displays C 2 = XXX Displays settings C 2 = to 9 E : Sets either upper or lower limit. Displayed at event E L O, E H I: Displayed at events requiring upper/lower limit setting (Note ) (Note 2) (Note ) This value cannot be changed when switching by external switch input is selected. This value blinks when control output is OFF or ON at ms or less. During blinking, the displayed CT value cannot be changed. This value is displayed by timer events set in the event and by the operation type of the external switch input set to the timer start setting. As long as timer operation continues, the time elapsed after the occurrence of the event is displayed within the range to -999 seconds. 22
Chapter 5 INITIAL SETTINGS How to Switch the Value Up to four values can be switched by the following three methods: By No. 2 By the key By external switch input By No. If the value of the 2nd digit of setup item C is set to an odd-number (,, 5, 7), pressing the PARA key in the operation mode displays the Nos. S P - through to S P - on the upper display. S p _ Upper display: No. Lower display: value Pressing the, keys in this state changes the No. in the upper display, and switches the value. The No. is not displayed if the value of the 2nd digit of setup item C is set to an even-number (, 2, 4, 6). 2 By the key If the value of setup item C 2 is set to 4, the value can be switched by the key. Holding down the key for at least two seconds switches the No. S P S P S P 2 S P S P and so forth. By external switch input (optional function) If the values of both setup items C 7 and C 8 are set to ( switching), the four values can be switched according to the ON/OFF states of the two external switch inputs. External External Selected Switch Input Switch Input 2 Set OFF OFF No. Set 2 ON OFF No. Set OFF ON No.2 Set 4 ON ON No. 2
Chapter 6 TUNING 6- Selecting the Control Method The SDC is provided with three types of control method. Select the desired method according to the C t R l (control method) setup in parameter items.. ON/OFF control. Self-tuning : This control method automatically changes control constants when is changed, or disturbance occurs. 2. Control by PID fixed values : Control follows fixed PID values set by auto-tuning or manual operation. 6-2 Self-tuning The controller can be self-tuned by setting the control method to self-tuning ( C t R l = ). Tuning is automatically started and control constants are changed by the following operation or when a change in state occurs in this state. Start by change Start conditions: Initial start (*) 2nd start onwards change of ±%FS (*2) or more change of ±5%FS or more * Initial start refers to initial tuning after the C t R l setting is set to. *2 FS (full-scale) refers to the width between the upper and lower temperatures set by range code (setup item C4). Example: ±%FS when the range is -2 to +4 C becomes: 6 ( C) x (%) = 6 ( C) 2 Start by generation of deviation Startup conditions: When the difference between and is sb or more * sb: Self-tuning startup width. This is set in the parameter items. Start by power ON or mode change from READY to RUN Start conditions: When the power is turned ON with the difference between and at ±sb or more, or the mode is changed from READY to RUN Self-tuning display The lower right LED after the st digit in the upper display blinks when the self-tuning function is ON. The LED goes out when learning ends and control constants are stored. 2 25 LED 24
Chapter 6 TUNING Startup method Procedure Check that the control device (heater, etc.) is ON and in an operating state. 2 Hold down the PARA key for seconds to advance to the parameter mode. Parameter mode The parameter mode is displayed. C t R L C T R L is displayed. is displayed. (default: ON/OFF operation) 4 Use the, and keys to enter numeric values. C t R L The C T R L value changes from to. Operation mode 5 Hold down the PARA key for seconds twice to advance to the operation mode. 2 6 Use the, and key to set the value to the desired temperature. Self-tuning is automatically started for value disturbances and changes whenever necessary. 5 2 Self-tuning starts (LED starts blinking) simultaneously with value input. When reaches the value, tuning stops and the LED goes out to indicate that self-tuning has stopped. Stop method Change C t R l from to 2. This fixes the PID values. PID values can also be changed by key entry. 6- Cautions During Self-tuning Observe the following when using the self-tuning function: Turn heaters or other control devices ON before turning the controller ON. To turn a control device OFF, set the controller to the READY mode. When turning a control device back ON again, set the controller to the RUN mode. When the power is turned OFF during self-tuning while the LED blinks, the control constants used during tuning are not stored in controller memory. If any of the above mistakes have been made, unsuitable control constants are stored to memory, which may result in unexpected control. If this happens, follow the procedure below to reset the controller. 25
Chapter 6 TUNING Handling Precautions Use auto-tuning. For details on how to use auto-tuning, see 6-4 Auto-tuning. Reset the PID values, and resume self-tuning. Set parameter item C t R l (control method) to 2. 2 Reset the PID values to the factory settings (P = 5., I = 2, d = ). Set C t R l to, and resume self-tuning. In the Case of Interference Control Targets Control targets may be located to the left or right (above or below), and response may slow down as a result of mutual tuning being adversely affected by respective changes in temperature. If this happens, either use control by fixed PID values (C t R l = 2), or set parameter item (S b) to. In the Case of Control Targets Where Disturbance Is Generated Intermittently Tuning results are sometimes adversely influenced when tuning control targets where intermittent temperature drops occur (e.g. during sealing on packaging machines). If this happens, either use control by fixed PID values (C t R l = 2), or set parameter item (S b) to. 6-4 Auto-tuning 26 Procedure Use the auto-tuning function in the following instances: To automatically calculate PID constants by control by fixed PID value (C t R l = 2) When startup is slow in self-tuning control When response startup is slow in self-tuning control The auto-tuning function can be used in either of self-tuning control (C t R l = ) or control by fixed PID values (C t R l = 2). 2 Hold the PARA key down for at least seconds in the RUN mode and with the value set to enter the parameter setup mode. Press the PARA key with C t R l set to or 2. A t (auto-tuning) is displayed. Set. If is already set, set to then back to. Auto-tuning can also be stopped by using the external switch input function. To forcibly cancel auto-tuning midway, either set A t to, or set the controller to the READY mode. Auto-tuning indication 2 25 LED The lower right LED after the st digit in the lower display blinks when the auto-tuning function is ON. The LED goes out when tuning ends.
Chapter 6 TUNING Handling Precautions Auto-tuning does not function normally unless the control target is connected. The auto-tuning time from start to finish varies according to the control target. When auto-tuning is executed, control is suspended, and to % output is repeated several times. If this hinders operation, manually set the PID values. Sometimes suitable PID values cannot be obtained according to the control target. If this happens, manually set the PID values. The following describes auto-tuning operation: Operation when the difference between and values is % FS or more and > Temperature - 2 At startup, operation stabilizes at a temperature of about ( - )/2 The temperature rises again and reaches. Auto-tuning ends when stability is achieved. 2 Operation when the difference between and values is % FS or less and < Cycling is repeated around the value. Auto-tuning ends when stability is achieved. Temperature Time Time 6-5 Control Troubleshooting Phenomenon Slow startup time Slow response value fluctuates Tuning does not end. value fluctuates with a 2 C or more error between and value. Tuning does not end. value is stable but does not end. Large overshoot Control signals repeatedly turn ON and OFF more than necessary. 2 2 2 4 2 4 5 2 4 2 4 5 Remedy Execute auto-tuning. Set C T R L to 2, reset PID values to factory settings, and set C T R L to to execute self-tuning. Reduce the value of timeproportional cycle ( C y C L ). Set the value of filter (parameter item) to. to 2.. Operation ends though it takes a long time. The slower the response of the control target, the longer tuning takes. 27
Chapter 7 ECIFICATIONS Category Item Specifications Inputs Indicators and Settings Control Outputs Additional Functions Input type Sampling cycle bias Set points Setting indication range Indication accuracy Temperature unit switching Model number Output Control action Output rating Differential gap Output direct/reverse switching Event Current transformer input No. of points Type Additional functions Differential gap Life Min. switching specifications No. of points Display range Guaranteed operating range Accuracy Recommended operating conditions Thermocouple: K, J, E, T, R, DIN U, DIN L RTD: Pt, JPt DC voltage: to 5 V, to 5 V, to V 5ms -999 to +9999 or -99.9 to +999.9 or 2 to 4 Input range display: See page 2 for details ±.5%FS ± digit Negative thermocouple area: ±%FS ± digit C/ F switchable D Relay contacts ON/OFF, time-proportional Contact type: ST Contact rating: 25Vac, A, Vdc, A Life: Min., operations (resistive load) Min. switching specification: 5V, ma 6D Voltage pulse (for SSR drive) ON/OFF, time-proportional Voltage (open): 22.5Vdc ±5% Internal resistance: Ω ±5% Leakage current (OFF): µa max. to 9999 or. to 999.9 Switchable 2, ST contacts, common shared Contact rating: 25Vac A, Vdc A (resistive load) upper limit alarm, lower limit alarm, upper/lower limit alarms, deviation upper limit alarm, deviation lower limit alarm, deviation upper/ lower limit alarms, heater line break/overcurrent, control device shortcircuit, timer Standby, latch, ON delay, controller alarm to 9999 or. to 999.9 Min., operations (resistive load) 5V, ma AC to 55A AC to 5A ±A Measuring Current No. Current Thru Lines CT Value Display (ave.) Allowable Input Current AC to 5A 9 to 45A Max. AC A AC 5 to 2A 2 to 46A Max. AC 5A AC 9 to 5A 9 to 5A Max. AC A External switch input No. of points Function Non-insulated type 2 switching, RUN/READY switching, event latch state cancel, timer event start/stop, auto-tuning start/stop Dry contact or open-collector Allowable ON contact resistance: Max. 25Ω Allowable OFF contact resistance: Min. kω Allowable ON residual voltage: Max..V Terminal current voltage (open): 5Vdc Terminal current (ON): Approx. 4mA 28
Chapter 7 ECIFICATIONS Category Item Specifications Additional Functions General Specifications External switch input Insulated type Memory backup Rated power supply voltage Power consumption Insulation resistance Dielectric strength Rush current (power ON) Mask material/color Case material/color Standard conditions Operating conditions Shipping and storage conditions Mass Terminal screw tightening torque Wet contact or open-collector Input voltage range: to 26.4Vdc Allowable ON voltage: V min. Allowable OFF voltage:.v max. Input impedance: Approx. 22Ω Terminal current (ON): Approx. 5mA (when 2Vdc is applied) Approx. ma (when 24Vdc is applied) Non-volatile semiconductor memory AC model: to 24Vac, 5/6Hz DC model: 24Vdc (no polarity) AC model: 7VA Max. (under operating conditions) DC model: 7W Max. (under operating conditions) Across power terminal and secondary terminals: 5Vdc, 2MΩ or more AC model: Across power terminal and case: 5Vac for minute (See note) DC model: Across power terminal and case: 5Vac for minute AC model: Max. A DC model: Max. 2A ABS plastic/dark gray (equivalent to Munsell 5Y.5/) PC plastic/light gray (equivalent to Munsell 2.5Y7.5/) Ambient temperature: 2±2 C Ambient humidity: 6±5%RH Power voltage: AC model: 5Vac±%, 5/6Hz±Hz DC model: 24Vdc±5% Vibration resistance: m/s 2 Shock resistance: m/s 2 Mounting angle: Reference plane ± Ambient temperature: to 5 C ( to 45 C when or more units are gang-mounted horizontally) Ambient humidity: Power voltage: to 9%RH (no condensation allowed) AC model: 85 to 264Vac, 5/6Hz±2Hz DC model: 2.6 to 26.4Vdc Vibration resistance: to 2m/s 2 ( to 6Hz, 2 hours in each X, Y, Z direction) Shock resistance: to m/s 2 Mounting angle: Reference plane ± Altitude: Max. 2 mm Ambient temperature: -2 to +7 C Ambient humidity: to 95%RH (no condensation allowed) 2g max. (including installation bracket on panel mounted type) g max. (including socket on socket type).78 to.98n m (Note) The primary side and secondary side capacities are joined inside the controller. For this reason, when performing the withstand voltage test for the panel and controller s power supply, disconnect the wiring of grounded secondary side terminals and input terminals from those terminals. In some cases, the grounding / non-grounding type thermocouples and resistance bulb sensors are not guaranteed for the withstand voltage between the protecting tube and the inner sensor. Because of this, there will be a possible cause of failure if such a withstand voltage test is performed as it is. I/O isolation The following table shows mutual isolation between I/O items. Items surrounded by solid lines are insulated from other signals. Items in dashed lines are not insulated: Power supply Digital circuit Control output input External switch input External switch input 2 * Current transformer input Event output Event output 2 * Insulated external switch inputs (option code ) are insulated from other signals. 29
Chapter 8 ALARM CODES When an error occurs, the following alarm codes are displayed in the upper display: Alarm code Error Cause Countermeasure A L A L 2 A L A L 7 Abnormal input (see Note) Abnormal input (see Note) CJ failure Abnormal input (see Note) Abnormal A/D conversion Sensor line break, incorrect wiring, incorrect range code setting Sensor line break, incorrect wiring, incorrect range code setting Terminal temperature compensation unit failure (thermocouple) Sensor line break, incorrect wiring (RTD) Defective A/D converter Check wiring or reset range code. Check wiring or reset range code. Replace unit. Check wiring. Replace unit. A L 9 7 Abnormal parameter Power turned OFF during fixing of data Data corrupted due to noise Reset data. A L 9 8 Abnormal adjustment data Data corrupted due to noise Replace unit. An alarm code other than A L 9 7 causes the manipulated variable (control output value) to be set to % (OFF). Instrument operations other than manipulated variable are unaffected. The A L 9 7 alarm code does not affect instrument operation. (Note) Display and operation when thermocouple input line break occurs Abnormal State Indication Alarm Code Sensor line break Upscaled A L Display and operation when break occurs in resistance temperature detector input Abnormal State Indication Alarm Code Resistor line break A L Upscaled or downscaled Break in line A or A L 2, A L Break in line B Downscaled A L 2, A L Break in line C A L, A L Upscaled or downscaled Break in 2 lines or more or A L 2, A L B short-circuited Downscaled A L 2 C short-circuited Downscaled A L 2 Display and operation when break occurs in DC voltage input Abnormal State Indication Alarm Code Line break Upscaled A L
Chapter 9 Cleaning MAINTENANCE Wipe off dirt on the controller using a soft, dry cloth. Parts Replacement Only authorized personnel are allowed to replace parts. Fuse Replacement (AC model only) Use only specified standard fuses when replacing fuses on the AC power supply wiring. Standard Cutoff Speed Rated Voltage Rated Current IEC27 Delayed operation type 25V 2mA
SDC Setup Work Sheet Model No. C Person in charge Drawn Up Operation mode settings Display Item Default Customer settings Memo S P value S P - set selection E (E L O) Event (lower limit) setting E H I Event upper limit setting E 2 (E 2 L O) Event 2 (lower limit) setting E 2 H I Event 2 upper limit setting See page 22 for information on operation settings. Parameter mode settings Display Item Default Customer settings Memo C T R L Control method A T Auto-tuning S P No. value S P No. value S P 2 No.2 value S P No. value P Proportional band 5. % I Reset time 2 s d Rate time s O L Output limit low % O H Output limit high % R E Manual reset 5 % S B Self-tuning startup width % Thermocouple, RTD 2 C/ F DC voltage.5 %FS D I F F Differential gap 5 (.5) C Y C L Time-proportional cycle s P B I A bias (.) H Y S Event hysteresis 5 (.5) D L Y Event ON delay time s H Y S 2 Event 2 hysteresis 5 (.5) D L Y 2 Event 2 ON delay time s F I L T filter. s See page 9 for information on parameter settings. 2
Setup mode items Display Item Default Customer settings Memo C Key lock C 2 Temperature unit C Control output direction C 4 Input range : thermocouple input : RTD input 22 : DC voltage input 4 C 5 Decimal point position C 6 range lower limit (DC voltage input) C 7 range upper limit (DC voltage input) C 9 lower limit Range Min. C upper limit Range Max. C Manipulated variable when READY mode or Alarm occur C 2 Operation mode C Number of s used C 4 Event operation type C 5 Event 2 operation type C 6 Event operation in READY mode C 7 External switch input operation type C 8 External switch input 2 operation type C 2 key setting C 2 2 Communications address C 2 Communications conditions C 2 4 Cold junction compensation C 2 5 Selection of time-proportional control operation See pages 2 to 4 for information on setup items.
Specifications are subject to change without notice. Advanced Automation Company Totate International Building 2-2-9 Shibuya Shibuya-ku Tokyo 5-86 Japan URL: http://www.yamatake.com This has been printed on recycled paper. (2) Printed in Japan. st Edition: Issued in Nov., 995 2th Edition: Issued in July, 24(B)