Series DS-1 Dry-Type Sprinklers 5.6K Horizontal Sidewall Standard and Quick Response, Extended Coverage General Description



Similar documents
Sprinkler Identification Numbers (SINs) Technical Data

Sprinkler Identification Number. Page 1 of 6 MARCH 2014 TFP288. Worldwide Contacts.

Model SW-20 and SW K-factor Extended Coverage Ordinary Hazard Horizontal Sidewall Sprinklers (Standard Response) General Description

Series TY-FRB 5.6 and 8.0 K-factor Extended Coverage Horizontal Sidewall Sprinklers Quick and Standard Response (Light Hazard) General Description

Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General Description

Sprinkler Identification Numbers

Model WS Specific Application Window Sprinklers Horizontal and Pendent Vertical Sidewall 5.6 K-factor General Description

Type EA-1 PROTECTOSPRAY Directional Spray Nozzles, Automatic, Medium Velocity General Description

Series ELO-231B 11.2 K-factor Upright and Pendent Sprinklers. Standard Response, Standard Coverage, General Description

Model F822 thru F834 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description

Type D3 PROTECTOSPRAY Directional Spray Nozzles, Open, Medium Velocity General Description

Series TY-FRL 5.6 and 8.0 K-factor Extended Coverage Horizontal Sidewall Sprinklers Quick & Standard Response (Light Hazard) General Description

Model/Sprinkler Identification Numbers

Series MJC Multiple Jet Controls DN20, DN25, DN40, and DN50, 12 bar BSPT Inlet & Outlets Threads General Description.

Model KFR56 Series Quick Response Standard Spray

ESFR DRY PENDENT SPRINKLER VK502 (K14.0) TECHNICAL DATA

RAPID RESPONSE Model RSV-1 Residential Shut-Off Valve, 1 Inch and 2 Inch (DN25 and DN50) for Dual-Purpose Residential Water Supply General Description

TECHNICAL DATA 2. LISTINGS AND APPROVALS. Spray Nozzle 11. December 20, 2013

Quick response concealed horizontal sidewall sprinkler

esfr pendent sprinkler vk510 (k25.2)

Model F1FR Series Quick Response Glass Bulb Sprinklers

IDENTIFICATION BROCHURE FOR Central RESIDENTIAL WET SPRINKLERS

1-1/2 Inch (DN40) 9 lbs. (4,1 Kg) 8 lbs. (3,6 Kg) Flange Groove* N/A N/A. Flange Flange N/A N/A

Technical Data. Installation

Viking Residential Sprinkler Installation Guide

Installation and Operating Instructions Installation Instructions for SS EPE-316L Series

ASX7-4-IOM-7 J

Your safety and the safety of others are very important.

Model F156 Sprinkler Types. Model F156 Recessed Sprinkler Types. Model F142, F1XLH & F128 Sprinkler Types

IDENTIFICATION BROCHURE FOR Central COMMERCIAL WET SPRINKLERS

5800 Temperature Sensor Cable Assembly

RESIDENTIAL SPRINKLER INSTALLATION GUIDE

TD01211 PIN: NX nd Edition. Water Motor Alarm MODEL: NX010 TECHNICAL DATA

Float and Thermostatic Traps Series H, C and X

Submersion/Insertion Toroidal Sensor

Constantemp Double Wall Low pressure steam-water Heater F-340LDW,F-640LDW, F-940LDW and F-1240LDW

08.08 Vic-Check Valves

Select Radiators Installation Guide

THERMOSTATIC MIXING VALVE TRIM K-T9493, K-T9494

INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected)

TECHNICAL ASSISTANCE TOLL FREE TELEPHONE NUMBER TECHNICAL ASSISTANCE FAX:

Extended Coverage Sprinklers

TABLE 1. Rugged cast aluminum alloy casing,celcon waterways with nichrome parts White (unless stainless steel housing)

Engineering Specifications

NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code

Powers Controls Free Energy Band TH 193 HC Heating/Cooling Room Thermostat

DV-5 Deluge Valve with Remote-Resetting, Pressure-Reducing Trim 4 Inch and 6 Inch (DN100 and DN150) General Description.

Model RV-1 Pressure Relief Valve 2 to 8 Inch (DN50 to DN200), 250 psi (17,2 bar) Pilot-Operated, Globe and Angle Body Styles General Description

Stainless Steel Single and Dual Circulation Kits

INSTRUCTION MANUAL IM042. Slide Rail Systems - Series A10 INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

Installation Instructions

Viking Residential Sprinkler Installation Guide

LPM-06 CONVERSION KIT

STORED PRESSURE STAINLESS STEEL

foot skylight) is enough to knock a worker off their feet. A 10 mph wind gust on a 5 x 6 skylight develops a wind force of 270 lbs.

Installation Instructions S

SunMor SM-V30 Solar Water Heater Installation Manual

TECHNICAL DATA. Dry 122a. November 12, 2013

INSPECTION, MAINTENANCE AND RECHARGE SERVICE MANUAL P/N 16303

Sprinkler Guards Model C Model D

Toroidal Conductivity Sensor

PREPIPED LIQUID FUEL MANIFOLDS PLPM

TYPE E Main Valve Sizes 3 /8 through 12

ASK THE EXPERT: Burner Troubleshooting Information & Maintenance

MODEL J SERIES CONVERTER

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve

NAVIEN AMERICA INC FITCH AVENUE

USE &CARE GUIDE. Remote Faucet Pump System. See Important Safeguards on page 2

Tyco Fire & Building Products is a leading manufacturer and distributor of water-based fire suppression systems and components, offering one of the

AMPSEAL* Automotive Plug Connector and Header Assembly

Preaction System with DV-5 Deluge Valve Single Interlock, Supervised Wet Pilot Actuation 1-1/2 thru 8 Inch (DN40 thru DN200) General Description

Refrigeration Installation 101

Morrison Bros. Co. General Product Specifications

INSTALLATION & OPERATING INSTRUCTIONS

with installation dynafact boost GAUGE this manual is for use with systems

VdS en. VdS Guidelines for water extinguishing systems. Non-return valves. Requirements and test methods. VdS en : (01)

CARING FOR YOUR WATER HEATER

How To Install An Evaporator Coil

CAST IRON THE BASICS. Heatline - Cast Iron Radiators SMOOTH FLAT FILE TO REMOVE ANY SWARF. ONE TIME. ASSEMBLY. JOINTS SHOULD BE TIGHTENED.

Product Manual. CVS Type 67AFR Filter Regulator. Introduction. Installation. Description

VOYAGER 570G. 744A Sprayer Control

TECHNICAL DATA. 2. LISTINGS AND APPROVALS See Tables 1 & 2.

Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling

HIGH VELOCITY WATER SPRAY NOZZLE

WAVELET WATER QUALITY MONITORING KIT

OWNER S MANUAL FORCE 10 MARINE COMPANY HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) FAX: (604)

3", 4", 6" & 8" Model H Series Alarm Check Valve Installation and Maintenance Guide

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D

Price Book - Section 20 Miscellaneous

ENGINE FUEL FUEL FILTER... FUEL HEATER... INJECTOR... SUPPLY PUMP... COMMON RAIL... FUEL PRESSURE LIMITTER...

Air Eliminators and Combination Air Eliminators Strainers

300 SERIES 331, 332, 333, 344, 356 AND 367 MODELS

All work shall comply with applicable codes and ordinances. Work shall comply with the BOCA National Plumbing Code, latest edition.

Installer s Guide 18-AH39D1-13

Powers Controls TH 192 S Single Temperature Room Thermostat

AMX300 DirectConnect Mixing Valve Kits

BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS

DC REFRIGERATORS 12/24 VOLTS INSTALLATION AND OWNER S MANUAL

Transcription:

Worldwide Contacts www.tyco-fire.com Series DS-1 Dry-Type Sprinklers 5.6K Horizontal Sidewall Standard and Quick Response, Extended Coverage General Description TYCO Series DS-1 Dry-Type Sprinklers, 5.6 K-factor Horizontal Sidewall, Standard (5 mm Bulb) and Quick Response (3 mm Bulb) and Extended Coverage, are decorative glass bulb automatic sprinklers typically used where the sprinklers and/or a portion of the connecting piping may be exposed to freezing temperatures; for example, horizontal piping extensions through a wall to protect an unheated area of a building. Series DS-1 Dry-Type Sprinklers are designed for extended coverage use in light hazard occupancies. NOTICE Series DS-1 Dry-Type Sprinklers described herein must be installed and maintained in compliance with this document, as well as with the applicable standards of the National Fire Protection Association (NFPA), in addition to the standards of any other authorities having jurisdiction. Failure to do so may impair the performance of these devices. The owner is responsible for maintaining their fire protection system and devices in proper operating condition. Contact the installing contractor or product manufacturer with any questions. Series DS-1 Dry-Type Sprinklers must only be installed in fittings that meet the requirements of the Design Criteria section. IMPORTANT Always refer to Technical Data Sheet TFP700 for the INSTALLER WARNING that provides cautions with respect to handling and installation of sprinkler systems and components. Improper handling and installation can permanently damage a sprinkler system or its components and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Sprinkler Identification Numbers (SINs) TY3338 3 mm Bulb Type TY3358 5 mm Bulb Type Technical Data Approvals UL and C-UL Listed NYC Approved under MEA 352-01-E Refer to Table A. Maximum Working Pressure 175 psi (12,1 bar) Inlet Thread Connections 1 inch NPT or ISO 7-R 1 Discharge Coefficient K=5.6 gpm/psi 1/2 (80,6 lpm/bar 1/2 ) Temperature Ratings Refer to Table A. Finishes Sprinkler: Natural Brass, Chrome Plated, or Signal White Escutcheon: Signal White, Chrome Plated, or Brass Plated Physical Characteristics Inlet....Copper Plug...Copper Yoke...Stainless Steel Casing...Galvanized Carbon Steel Insert... Bronze Bulb Seat...Stainless Steel Bulb...Glass Compression Screw........ Bronze Deflector.... Bronze Frame... Bronze Guide Tube...Stainless Steel Water Tube...Stainless Steel Spring....Stainless Steel Gasketed Spring Plate Seal...Beryllium Nickel w/teflon Escutcheon...Carbon Steel Operation When TYCO Series DS-1 Dry-Type Sprinklers are in service, water is prevented from entering the assembly by the Plug and Gasketed Spring Plate Seal (Ref. Figure 1) in the Inlet of the sprinkler. The glass bulb contains a fluid that expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb, and the Bulb Seat is released. The compressed Spring is then able to expand and push the Water Tube as well as the Guide Tube outward. This action simultaneously pulls inward on the Yoke, withdrawing the Plug and Gasketed Spring Plate Seal from the Inlet allowing the sprinkler to activate and flow water. Page 1 of 8 SEPTEMBER 201 TFP520

Page 2 of 8 PLUG WITH GASKETED SPRING PLATE SEAL YOKE INLET BAND CASING INSERT FRAME 3 or 5 mm BULB DEFLECTOR INLET 1" NPT SPRING WATER TUBE GUIDE TUBE BULB SEAT VENT HOLE COMPRESSION SCREW FIGURE 1 EXTENDED COVERAGE HORIZONTAL SIDEWALL ASSEMBLY ORDER LENGTHS: 2-3/" to 8" (69,9 to 1219,2 mm) IN 1/" (6, mm) INCREMENTS FACE OF SPRINKLER FITTING 1-3/" DIA. (,5 mm) 2-3/8" ± 1/8" (60,3 ± 3,2 mm) FACE OF MOUNTING SURFACE 3" DIA. (76,2 mm) SPRINKLER FITTING (REFER TO DESIGN CRITERIA SECTION) CENTERLINE OF WATERWAY 7/16" (11,1 mm) Design Criteria FIGURE 2 EXTENDED COVERAGE HORIZONTAL SIDEWALL WITH STANDARD ESCUTCHEON TY3338 (3 MM BULB) AND TY3358 (5 MM BULB) TYCO Series DS-1 Dry-Type Sprinklers are intended for use in fire sprinkler systems designed in accordance with the standard installation rules recognized by the applicable Listing or Approval agency; for example, UL Listing is based on NFPA 13 requirements. Sprinkler Fittings Install 1 inch NPT Series DS-1 Dry-Type Sprinklers in the 1 inch NPT outlet or run of the following fittings: malleable or ductile iron threaded tee fittings that meet the dimensional requirements of ANSI B16.3 (Class 150) cast iron threaded tee fittings that meet the dimensional requirements of ANSI B16. (Class 125) Do not install Series DS-1 Dry-Type Sprinklers into elbow fittings. The Inlet of the sprinkler can contact the interior of the elbow. The unused outlet of the threaded tee is plugged as shown in Figure 5. You can also install Series DS-1 Dry-Type Sprinklers in the outlet. The configuration shown in Figure 6 is only applicable for wet pipe systems where the sprinkler fitting and waterfilled pipe above the sprinkler fitting are not subject to freezing and where the length of the Dry-Type Sprinkler has the minimum exposure length depicted in Figure 6. Refer to the Exposure Length section. For wet pipe system installations of 1 inch NPT Series DS-1 Dry-Type Sprinklers connected to CPVC piping, use only the following TYCO CPVC fittings: 1 x 1 NPT Female Adapter (P/N 8015) 1 x 1 x 1 NPT Sprinkler Head Adapter Tee (P/N 8029) For dry pipe system installations, use only the side outlet of maximum 2-1/2 inch reducing tee when locating Series DS-1 Dry-Type Sprinklers directly below the branch line. Otherwise, use the configuration shown in Figure to assure complete water drainage from above Series DS-1 Dry-Type Sprinklers and the branch line. Failure to do so may result in pipe freezing and water damage. NOTICE Do not install Series DS-1 Dry-Type Sprinklers into any other type fitting without first consulting the Technical Services Department. Failure to use the appropriate fitting may result in one of the following: failure of the sprinkler to operate properly due to formation of ice over the Inlet Plug or binding of the Inlet Plug insufficient engagement of the Inlet pipe threads with consequent leakage Drainage In accordance with the minimum requirements of the National Fire Protection Association for dry pipe sprinkler systems, branch, cross, and feed-main piping connected to Dry Sprinklers and subject to freezing temperatures must be pitched for proper drainage.

Page 3 of 8 WRENCH FLAT WRENCH RECESS PUSH WRENCH IN TO ENSURE ENGAGEMENT WITH SPRINKLER WRENCH FLATS FIGURE 3 W-TYPE 7 SPRINKLER WRENCH TO DRY SYSTEM DSB-2 INTENDED FOR FREEZER STRUCTURES AREA SUBJECT TO FREEZING FIGURE SPRINKLER FITTING UNHEATED AREA RUN OUTLET PLUGGED DSB-2 INTENDED FOR FREEZER STRUCTURES 1 INCH NPT TEE (SEE DESIGN CRITERIA SECTION) TO DRY SYSTEM AREA SUBJECT TO FREEZING FIGURE 5 SPRINKLER FITTING UNHEATED AREA EXPOSURE LENGTH (SEE DESIGN CRITERIA SECTION) FACE OF SPRINKLER FITTING DSB-2 INTENDED FOR FREEZER STRUCTURES HEATED AREA FIGURE 6 EXPOSURE LENGTH 1-3/" DIA. (,5 mm) CLEARANCE HOLE ADHESIVE DSB-2 BOOT STRAP TIES (ENDS ON OPPOSING SIDES OF BOOT) INSULATED FREEZER STRUCTURE DS-1 SHOWN WITH STANDARD ESCUTCHEON FIGURE 7 MODEL DSB-2 DRY SPRINKLER BOOT WITH DRY-TYPE SPRINKLER Exposure Length When using Dry Sprinklers in wet pipe sprinkler systems to protect areas subject to freezing temperatures, use Table C to determine a sprinkler s appropriate exposed barrel length to prevent water from freezing in the connecting pipes due to conduction. The exposed barrel length measurement must be taken from the face of the sprinkler fitting to the surface of the structure or insulation that is exposed to the heated area. Refer to Figure 6 for an example. For protected area temperatures between those given above, the minimum recommended length from the face of the fitting to the outside of the protected area may be determined by interpolating between the indicated values. Clearance Space In accordance with Section 8..9.2 of the 2010 edition of NFPA 13, when connecting an area subject to freezing and an area containing a wet pipe sprinkler system, the clearance space around the sprinkler barrel of Dry-Type Sprinklers must be sealed. Due to temperature differences between two areas, the potential for the formation of condensation in the sprinkler and subsequent ice build-up is increased. If this condensation is not controlled, ice build-up can occur that might damage the dry-type sprinkler and/or prevent proper operation in a fire situation. Use of the Model DSB-2 Dry Sprinkler Boot, described in Technical Data Sheet TFP591 and shown in Figure 7, can provide the recommended seal.

Page of 8 Temperature Rating Bulb Color Code TY3338 Horizontal Sidewall with Standard Escutcheon (3 mm Bulb Type) TY3358 Horizontal Sidewall with Standard Escutcheon (5 mm Bulb Type) (Ref. Figure 2) SPRINKLER FINISH Natural Brass Chrome Plated Signal White 135 F (57 C) Orange 155 F (68 C) Red 1, 2, 3 Notes: 1. Listed by Underwriters Laboratories, Inc. (maximum order length of 8 inches). 2. Listed by Underwriters Laboratories for use in Canada (maximum order length of 8 inches). 3. Approved by the City of New York under MEA 352-01-E. TABLE A SERIES DS-1 EXTENDED COVERAGE HORIZONTAL SIDEWALL DRY-TYPE SPRINKLERS LABORATORY LISTINGS AND APPROVALS Application Coverage 1 W x L, Ft. x Ft. (m x m) Minimum Flow, gpm (lpm) Minimum Pressure, psi (bar) Temperature Rating Top of Deflector-to-Ceiling Distance 2, Inches (mm) TY3338 Horizontal Sidewall (3 mm Bulb Type) For Quick Response, Light Hazard Extended Coverage per NFPA 13 TY3358 Horizontal Sidewall (5 mm Bulb Type) For Standard Response, Light Hazard Extended Coverage per NFPA 13 16 x 16 (,9 x,9) 16 x 18 (,9 x 5,5) 16 x 20 (,9 x 6,1) 18 x 16 (5,5 x,9) 16 x 16 (,9 x,9) 16 x 18 (,9 x 5,5) 16 x 20 (,9 x 6,1) 18 x 16 (5,5 x,9) 26 (98) 29 (110) 32 (121) 29 (110) 26 (98) 29 (110) 32 (121) 29 (110) 21.6 (1,9) 26.8 (1,85) 32.7 (2,25) 26.8 (1,85) 21.6 (1,9) 26.8 (1,85) 32.7 (2,25) 26.8 (1,85) 135 F and 155 F (57 C and 68 C) to 12 (100 to 300) Notes: 1. The minimum allowable spacing between sprinklers to prevent cold soldering is 1 feet (,3 m). 2. To meet the deflector-to-ceiling distance of to 12 inches (100 to 300 mm), the centerline of the sprinkler waterway must be -7/16 to 12-7/16 inches below the ceiling. TABLE B SERIES DS-1 EXTENDED COVERAGE HORIZONTAL SIDEWALL DRY-TYPE SPRINKLERS UL AND C-UL INSTALLATION CRITERIA

Page 5 of 8 Ambient Temperature Exposed to Discharge End of Sprinkler 0 F ( C) 30 F (-1 C) 20 F (-7 C) 10 F (-12 C) 0 F (-18 C) -10 F (-23 C) -20 F (-29 C) -30 F (-3 C) -0 F (-0 C) -50 F (-6 C) -60 F (-51 C) 0 F ( C) Temperatures for Heated Area 1 50 F (10 C) Minimum Exposed Barrel Length 2, Inches (mm) 60 F (16 C) 0 0 0 0 0 0 (100) 8 (200) 12 (305) 1 (355) 1 (355) 16 (05) 18 (55) 20 (510) 20 (510) 0 0 1 (25) 3 (75) (100) 6 (150) 8 (200) 8 (200) 10 (255) 10 (255) Notes: 1. For protected area temperatures that occur between values listed above, use the next cooler temperature. 2. These lengths are inclusive of wind velocities up to 30 mph (18,6 kph). TABLE C EXPOSED SPRINKLER BARRELS IN WET PIPE SYSTEMS MINIMUM RECOMMENDED LENGTHS 0 0 1 (25) 3 (75) (100) (100) 6 (150) 6 (150)

Page 6 of 8 Installation TYCO Series DS-1 Dry-Type Sprinklers must be installed in accordance with this section. General Instructions Series DS-1 Dry-Type Sprinklers must only be installed in fittings that meet the requirements of the Design Criteria section. Refer to the Design Criteria section for other important requirements regarding piping design and sealing of the clearance space around the Sprinkler Casing. Do not install any bulb type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprinkler held horizontally, a small air bubble should be present. The diameter of the air bubble is approximately 1/16 inch (1,6 mm). A leak-tight 1 inch NPT sprinkler joint should be obtained by applying a minimum-to-maximum torque of 20 to 30 ft.-lbs. (26,8 to 0,2 Nm). Higher levels of torque may distort the sprinkler Inlet with consequent leakage or impairment of the sprinkler. Do not attempt to compensate for insufficient adjustment in an escutcheon plate by under or overtightening the sprinkler. Re-adjust the position of the sprinkler fitting to suit. Step 1. Install horizontal sidewall sprinklers in the horizontal position with their centerline of waterway perpendicular to the back wall and parallel to the ceiling. The word TOP on the Deflector is to face towards the ceiling. Step 2. With a non-hardening pipethread sealant such as TEFLON tape applied to the Inlet threads, handtighten the sprinkler into the sprinkler fitting. Step 3. Wrench-tighten the sprinkler using either: a pipe wrench on the Inlet Band or the Casing (Ref. Figure 1) the W-Type 7 Sprinkler Wrench on the Wrench Flat (Ref. Figure 3) Apply the Wrench Recess of the W-Type 7 Sprinkler Wrench to the Wrench Flat. Note: If sprinkler removal becomes necessary, remove the sprinkler using the same wrenching method noted above. Sprinkler removal is easier when a non-hardening sealant was used and torque guidelines were followed. After removal, inspect the sprinkler for damage. Step. After installing the ceiling or wall and applying a ceiling finish, slide on the outer piece of the escutcheon until it comes in contact with the ceiling or wall. Do not lift the ceiling panel out of its normal position. Care and Maintenance TYCO Series DS-1 Dry-Type Sprinklers must be maintained and serviced in accordance with this section. Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, obtain permission to shut down the affected fire protection systems from the proper authorities and notify all personnel who may be affected by this action. Absence of the outer piece of an escutcheon, which is used to cover a clearance hole, may delay the time to sprinkler operation in a fire situation. A Vent Hole is provided in the Bulb Seat (Figure 1) to indicate if the Dry Sprinkler is remaining dry. Evidence of leakage from the Vent Hole is an indication that there may be seepage past the Inlet seal and that the sprinkler needs to be removed for determining the cause of leakage (e.g., an improper installation or an ice plug). The fire protection system control valve must be closed and the system drained before removing the sprinkler. Sprinklers which are found to be leaking or exhibiting visible signs of corrosion must be replaced. Automatic sprinklers must never be painted, plated, coated, or otherwise altered after leaving the factory. Modified sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush. Care must be exercised to avoid damage to the sprinklers before, during, and after installation. Sprinklers damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced. Also, replace any sprinkler that has a cracked bulb or that has lost liquid from its bulb. (Ref. Installation Section.) If a sprinkler must be removed, do not reinstall it or a replacement without reinstalling the Cover Plate Assembly. If a Cover Plate Assembly becomes dislodged during service, replace it immediately. The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the National Fire Protection Association (e.g., NFPA 25), in addition to the standards of any other authorities having jurisdiction. Contact the installing contractor or product manufacturer with any questions. Automatic sprinkler systems are recommended to be inspected, tested, and maintained by a qualified Inspection Service in accordance with local requirements and/or national codes.

Page 7 of 8 P/N * 60 XXX X XXX 350 351 950 951 EC Sidewall 3 mm Bulb (1 NPT), 135 F (57 C) EC Sidewall 3 mm Bulb (1 NPT), 155 F (68 C) EC Sidewall 5 mm Bulb (1 NPT), 135 F (57 C) EC Sidewall 5 mm Bulb (1 NPT), 155 F (68 C) SIN TY3338 TY3338 TY3358 TY3358 0 1 2 9 SPRINKLER FINISH CHROME PLATED NATURAL BRASS NATURAL BRASS SIGNAL WHITE (RAL9003) CHROME PLATED ESCUTCHEON FINISH SIGNAL WHITE (RAL9003) SIGNAL WHITE (RAL9003) BRASS PLATED SIGNAL WHITE (RAL9003) CHROME PLATED ORDER LENGTH** 055 5.50 082 8.25 180 18.00 187 18.75 372 37.25 80 8.00 Notes: * Use Prefix I for ISO 7-R 1 Connection (e.g., I-60-351-1-180). ** Dry-Type Sprinklers are furnished based upon Order Length as measured per Figure 2. After the measurement is taken, round it to the nearest 1/ inch increment. TABLE D SERIES DS-1 STANDARD AND QUICK RESPONSE, STANDARD COVERAGE, DRY-TYPE SPRINKLERS PART NUMBER SELECTION Limited Warranty For warranty terms and conditions, visit www.tyco-fire.com. Ordering Procedure Contact your local distributor for availability. When placing an order, indicate the full product name, including description and Part Number (P/N). Dry Sprinklers When ordering 5.6 K-factor Series DS-1 Horizontal Sidewall, Standard or Quick Response, Extended Coverage Dry-Type Sprinklers, specify the following information: SIN: TY3338 Quick Response TY3358 Standard Response Bulb Size (3 or 5 mm) Order Length: Dry-Type Sprinklers are furnished based upon Order Length as measured from the face of the wall to the face of the sprinkler fitting (Ref. Figure 2). After the measurement is taken, round it to the nearest 1/ inch increment. Inlet Connections: 1 inch NPT or ISO 7-R 1 Temperature Rating Sprinkler Finish Standard Escutcheon and Finish Part Number from Table D Sprinkler Wrench Specify W-Type 7 Sprinkler Wrench, P/N 56-850--001 Sprinkler Boot Specify Model DSB-2 Dry Sprinkler Boot, P/N 63-000-0-002 This Part Number includes one (1) Boot, two (2) Strap Ties, and 1/3 oz. of Adhesive (a sufficient quantity for installing one boot).

Page 8 of 8 GLOBAL HEADQUARTERS 100 Pennbrook Parkway, Lansdale, PA 196 Telephone +1-215-362-0700 Copyright 201 Tyco Fire Products, LP. All rights reserved. TEFLON is trademark of The DuPont Corporation