Technical Specification for Oil insulated Transformers U m < 24 kv up to 1250 kva



Similar documents
PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & Instructions For Installation, Operation & Maintenance

Power transformers. Special transformers Railway

Multi-tap Transformers

S. C. Electric Cooperative s Specification for a Three-Phase, Padmounted URD Transformer (Revised 12/2014)

1ZSE en, Rev. 8. Transformer bushings, type GOE and GOE(2) Technical guide

James M. Pleasants Company

PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS

SECTION DRY-TYPE TRANSFORMERS

1ZSC AAC en, Rev. 7. Resin impregnated paper bushing, oil to air, type GSB Technical guide

Pressure monitoring equipment for oil-sf 6. bushings, type GOEK

System 8. ü ( System 8

DRY TYPE TRANSFORMER

Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER.

Transformer Bushings for GIS

ISORIA. Centered disc butterfly valves with AMRING elastomer liner. 240 PSI: 1½ to PSI : 10 to 24

produces and delivers products worldwide can provide the optimal are dedicated to supplying you with superior advice and global support.

Pallet Jack. OWNER S MANUAL Model MH1230. Important Safety Instructions Assembly Instructions Parts and Hardware Identification

CRN A-F-G-E-HQQE 3x400D 50 HZ

SF 6 Gas Insulated Switchgear Type SDF for 170 kv

Volkswagen Golf > VW Rabbit GTI 2006->

P System Cubicles. Certified for more safety

Givare NC-SRS 280 och 880

CRN5-5 A-FGJ-G-E-HQQE 3x230/400 50HZ

ECOCIAT. Domestic hot water heat recovery unit

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV

Technical data. Danfoss DHP-A

Tyco PremiAir Pneumatic Actuators

LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS

Directory chapter 02 - DIN Power (to 6 A) Types D, E, F, FM, 2F, F9, interface connectors I/U Technical characteristics types D and E

Vario-Series Accessories

HERZ-Thermal Actuators

Technical data UNIBLOCK UBSF

Mini USB and USB 2.0-IP67 Connector System

Instructions for Secondary Unit Substation Transformers KVA, Three Phase

DXPE*J /215 ED. DIRECtIONAL CONtROL VALVE PILOt OPERAtED, WItH OBE AND FEEDBACK. Q max (see performance table) SERIES 30

Ferrostat Speed Sensor Series DSF Explosion Proof Versions EEx

Tasarım ve Baskı: AJANSBRAND A

Transformer oil cooler ALFA A02

Pump Specifications 405 Series Commercial Drain Pump (High-Temp) 2 Solids handling

OUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd

Explosion proof enclosures

3/2-way Solenoid Valve, direct-acting, NC or NO

Operating Instructions Parts List Manual Scissor Lift Pallet Truck

Select Radiators Installation Guide

Modular Systems, PPMV, 2014 UniPack-G Glass Fiber Reinforced Polyester Compact Secondary Substation

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp and 1250 Amp

Cooling system components, removing and installing

Water Pump Replacement

ACL 395 Resistivity Meter

TECHNICAL SPECIFICATION FOR HIGH TENSION LINE HARDWARE AND ACCESSORIES FOR ACSR PANTHER & WOLF CONDUCTOR

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2...

NEW SIX-SEALS CUTTING RING. INTERNATIONAL INDUSTRIAL PATENT Nr of the 10/03/99 FLANKS AND DOES NOT REPLACE THE STANDARD RING CURRENTLY IN USE

Ergo-Pro Single Line Solar Station Installation and Operating Instructions

Fluid Level Gauge Fluid Level Sensor Temperature Switch FSA / FSK / TS

MiCAFIL. 1 RIP Technology. Bushings. Z. Zic 09/2003

SureSite Magnetic Liquid Level Indicator

E4E PILOT OPERATED DIRECTIONAL CONTROL VALVE WITH ELECTRIC PROPORTIONAL CONTROL SERIES 51

BUGGY SETUP GUIDE. Volume GOKARTSUSA GY6 150, CN250. Buggy Setup Guide

This section applies to the design and installation of transformers.

Unified requirements for systems with voltages above 1 kv up to 15 kv

SPECIFICATIONS FOR 220KV CAPACITOR VOLTAGE TRANSFORMER. The equipment is required for 220KV system. The system data is given as under:

Toroidal Conductivity Sensor

V47 Series Temperature Actuated Modulating Water Valves

CAS 36 Ring Main Unit

Operators manual Basic water heater

OLI. Oil level indicator

SECTION SUBSTATION TRANSFORMERS

VOYAGER 570G. 744A Sprayer Control

High-Voltage Compact Switchgear 3AP1 DTC for 145 kv and 245 kv

Rating when used as a weight carrying hitch without spring bars:

Catalog May Cable Accessories < 1 kv

WE-350 Series ¼ Turn Electric Actuator

Takfan Machinery and Mould Co Ltd. Plug in Bushing. LV Monoblock. RMU Bushing. 4 Way CT Terminal.

RAY-MAX Integrated Solar Power Strip

Technical Specification for 12kV Padmounted Distribution Substations (Rectangular Type)

INSTALLATION AND OPERATING INSTRUCTIONS For Model GL1 Gate Locks

Step 1. Item 6. Item 1

CAST IRON THE BASICS. Heatline - Cast Iron Radiators SMOOTH FLAT FILE TO REMOVE ANY SWARF. ONE TIME. ASSEMBLY. JOINTS SHOULD BE TIGHTENED.

R.C.C.B. s two-pole LEXIC

Maintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / SC / SC / 1250SC / 1600SC / 1800SC / 2000SC

Technical Information Requirement for MV transformers and transformer for internal power supplies for SUNNY CENTRAL

TYPE TEST CERTIFICATE OF SHORT-CIRCUIT PERFORMANCE. A three-phase outdoor oil-immersed distribution transformer

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application

Medium Voltage Electrical Distribution

DF-DT (G) MEDIUM VOLTAGE SWITCHGEAR THE MODULAR CONCEPT. User Manual. SGC - SwitchGear Company nv - Moorstraat 24 - B-9850 Nevele - Belgium

Volkswagen Jetta, Golf, GTI 1999, Liter VR6 2V Engine Mechanical, Engine Code(s): AFP 17 Engine-Lubrication (Page GR-17)

QPM3 Low pressure pump for circulation of oil in hydraulic and lubricating systems


Fire Hydrant Troubleshooting

61W - Wafer style resilient seated butterfly valve 61L - Lugged style resilient seated butterfly valve

Instructions Manual. Electromagnetic sensor Series FLOMID FX. instrumentation for fluids. R-MI-FlomidFX Rev.: 0 English version

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Self-operated Pressure Regulators Universal Pressure Reducing Valve Type 41-23

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points

Electric Rotary Actuator - On/Off or programmable control actuator

14.5GHZ 2.2KW CW GENERATOR. GKP 22KP 14.5GHz WR62 3x400V

Assisted lift operated 2/2-way solenoid valves Type EV250B

Installation Guide of Sunrise Solartech PV Modules. Term Contents. Purpose of this guide. General. Safety precaution for installing a solar

F-Series Camera Mounting Accessories

Transcription:

to 1250 kva Page 1/10 Technical Specification for Oil insulated Transformers U m < 24 kv up to 1250 kva This technical specification is valid for the business unit E.ON Sweden of the market unit E.ON Nordic. With this specification, technical determinations were made beyond existing publications. Contact of the working committee: Nobelvägen 66 S-205 09 Malmö/Sweden Stefan Andersson phone +46 - (0)705 24 41 17 fax +46 - (0) 40 24 40 33 stefan.andersson@eon.se

to 1250 kva Page 2/10 1 Scope 2 Electrical data 2.1 Rated output 2.2 Maximum voltage 2.3 Rated voltage 2.4 Switchgear 2.5 Coupling type 2.6 Short-curcuit impedance 2.7 Losses and noise levels 2.8 Insulation and insulations testing 3 Design requirements 3.1 Type of oil system and degree of sealing 3.2 Terminals and tapping marking 3.3 Terminals 3.4 Signs 3.5 Corrosion protection 3.6 Lifting equipment, transport and fastening devices 3.7 Monitoring devices 4 Dimensions 4.1 Transport wheels 4.2 External dimensions 5 Fittings 6 Tender information, documentation 6.1 Tender 6.2 Documentation

to 1250 kva Page 3/10 1. Scope This requirement specification relates to oil-insulated distribution transformers in accordance with SS 427 02 01-1. Standards The transformer shall comply with the requirements of SS 427 02 01-1.This requirement specification is a supplement, which in connection with each part of the standard notes specific items that will result in changes, additions or that require further explanation. Should the information provided in this requirement specification deviate from SS 427 02 01, the information in the specification will apply. In addition to the list of standards provided in SS 427 02 01-1, reference is made in the requirement specification to the following standards: SS-EN 60296 Fluids for electro technical applications-unused mineral insulating oils for transformers and switchgear. SS-EN 50180 Bushings above 1 kv up to 36 kv and from 250 A to 3,15 ka for liquid filled transformers. SS-EN 50386 Bushings up to 1 kv and from 250 A to 5 ka, for liquid filled transformers. SS-EN 60076-1 Power transformers part 1 : General SS-EN 60076-10 Power transformers - Determination of sound levels. IEC 60076-7 Power transformers-part 7: Loading guide for oil-immersed power transformers. SS ENISO 1461 Inorganic surface layer Galvanizing Guidelines and requirements SFS 2646 Truncated lighting pulse test method (Finnish standard) BSK 99 Steel structures DIN 42554 Thermometer pocket 2 Electrical data 2.1 Rated output The rated power values are: 50-100-200-315-500-630-800-1000-1250 kva Continuous operation, overloadable according to IEC 60076-7 2.2 Maximum voltage The maximum voltage values for equipment are: a) For high-voltage winding: 7.2-12-24 kv.

to 1250 kva Page 4/10 2.3 Rated voltage a) For high-voltage winding: Rated voltage Ur, shall be in accordance with values given in Table I. Table I Um (kv) 7.2 12 24 Ur (kv) 6.35 11 22 b) For low-voltage winding: Rated voltage shall be 420 V. 2.4 Volt switching. 2.4.1 Tap changer for off-voltage switching The tap changer shall have a switching area of ±2x2.5%. The external parts of the switchgear shall be made from corrosion- and UV-resistant material. The switchgear shall have an efficient position lock and shall be constructed so that maneuverability is not impaired by oxidation or bimetallic corrosion. In his tender, the supplier shall designate the make and type of switchgear with which the transformer is equipped. 2.4.2 Changing voltage It shall be possible to conduct a voltage change with the switchgear above the closing cover. In regard to the construction of the switchgear, the same requirements apply as in point 2.4.1. 2.5 Coupling type The transformer shall be designed with a Dyn 11 type of coupler 2.6 Short-circuit impedance For 50-630 kva: 4% For more than 630 kva 6% 2.7 Losses and noise levels No load-losses and load losses values are calculated based on optimal cost effectiveness and cost per kilowatt. Without positive tolerance Noise level shall not exceed 54 db(a). Measurements shall be made in accordance with IEC 60076-10. 2.8 Insulation and insulation testing 2.8.1 Insulation level The transformer shall be designed with an insulation level in accordance with table 2 in IEC 60076-3, with the exception of the test voltage on the low-voltage side, which shall be 5 kv during alternating current tests.

to 1250 kva Page 5/10 2.8.2 Routine tests Routine tests on all transformers shall be conducted in accordance with IEC 60076-1, clause 10. 2.8.3 Type tests The purchaser has the right to demand new type tests on each new delivery. The following two type tests shall be performed on all transformer sizes: 1. Temperature-rise test in accordance with IEC 60076-2 2. Insulation test, with short impulse, in accordance with IEC 60076-3 2.8.4 Special tests Truncated lighting pulse All transformer sizes 200 kva shall be type tested with three truncated lighting pulses. The pulse wave should be negative and have a linear front slope of at least 2000 kv/μs. The test is conducted on a three-phase basis three times on each phase. Truncation is achieved through a spark-gap switch furnished by the purchaser. The air-gap for 11kV shall be 42 mm and 82 mm for 22 kv. The test shall be carried out according to the Finnish standard SFS 2646. A representative of the purchaser shall have the right to be present during the delivery test. The date and time of the test and the test program shall be advised no later than 14 days prior to the delivery test. 3 Design requirements 3.1 Type of oil system and degree of sealing These requirement specifications relate only to hermetically sealed transformers. The delivery shall include the required transformer oil, type Nytro 10X. This should be naphthabased and furnished with a minimum concentration of 0.3 percent by weight of oxidation inhibitor, type ditertiary-butyl-para-cresol (DBPC). If another type, for example a paraffin-based oil is intended, this must be reported, both in the documentation and through notification on the rating plate of the transformer. The dielectric strength of the oil shall be at least 55 kv. The oil shall meet other requirements in accordance with SS-EN 60296. The supplier shall provide a written guarantee that the transformer oil does not contain PCB. The PCB content must be below the limit of detectabillity. If on delivery an oil sample from the transformer contains PCB, the purchaser has the right to reject the transformer. The supplier is then liable to repay any payments already made and to recompense the purchaser for other expenses incurred. The transformer shall be capable of accepting a maximum top oil temperature of +115 C. The transformer tank shall be tested for leaks with a penetrant fluid. The tank must be designed for a minimum rupturing pressure of 0,6 bar. The difference between operating pressure at nominal power and rupturing pressure must Be at least 0,3 bar.

to 1250 kva Page 6/10 If a hermetically sealed transformer is equipped with a pressure switch, the switch must have an opening pressure that is 10% higher than the maximum pressure in the tank at a top-oil temperature of +115 C. An aperture for oil refilling purposes shall be provided in the transformer closing cover, with a threaded connection of at least M 20. A drain valve with a threaded connection and a protective cover shall be available on all sizes of transformers. The drain valve shall be placed on the bottom of the transformer tank on the operations side. The operations side is the short side on the right, viewed from the high-voltage side. DIN 42551. Both the refilling aperture and the drain valve shall be sealed. 3.2 Terminal and tapping markings The terminal and tapping markings shall be in accordance with IEC 60616. From left to right, viewed from the high-voltage side: A-B-C for high voltage and n-a-b-c low-voltage terminals. The terminals shall be marked with resistant metal plates. The texts shall be embossed or stamped on the metal plates. The plates shall be attached with metal fasteners to the transformer. Signs attached by glue are not permitted. These requirements also apply to signs for marking the position of such operating units as tap changers and voltage regulators. 3.3 Terminals Bushing shall be carried out in accordance with SS-EN 50386 on the low-voltage side and SS-EN 50180 on the high-voltage side, with open bushing as standard. Plug-in type bushings shall be shown as options in the tender for 500 kva transformers. Exterior live parts shall be constructed in copper or copper alloy. It shall be possible to replace the exterior porcelain insulator without the requirement of lifting the transformer out of its tank. Transformers with a rated output of 315 kva shall be delivered with three nuts and two plain washers for each connecting bolt. Spring washers are not permitted. The correct tightening torque for the nuts to the connecting bolts shall be stated on the transformer. Transformers with a rated output of 500 kva shall be designed to include the possibility of connecting cables with cable clips on the low-voltage side. The cable clips are fastened with one bolt per cable clip. Cable clip types E08 251 00 and E08 251 03. The number of cables with cable clips to be connected to each phase and natural is shown in table III. The LV contact flange shall then be adapted accordingly. Table III Rated output (kva) Phase (number x area in Cu mm 2 ) 500 2 x 300 2 x 300 630-1000 2 x 400 2 x 400 1250 3 x 400 2 x 400 Zero (number x area in Cu mm 2 )

to 1250 kva Page 7/10 Screws, nuts and washers for the contact flange shall be of the same material as the flange, or of stainless steel of ISO-class F1 or A2. Spring washers are not permitted. The correct tightening torque for each screw joint shall be stated on the transformer. Cable connection clips for the protective earthing/grounding of the transformer shall be fitted with caps. Transformers with a rated output of 315 kva shall be fitted with a connection clip for the protective earthing/grounding of the closing cover. 3.4 Signs Rating sign displaying information in accordance with SS-EN 60076-1. Rating signs and inventory signs shall be placed on aluminum mounting plates. The plates shall be mounted on the transformer by the supplier and must be capable of being moved from the transformer s operating side. The attachments for the plates shall be of stainless steel, of ISO-class F1 or A2. On transformers with reconnectable windings for different voltage systems, the adjustable indicating device beside the rating sign shall be constructed of durable material and easily adjustable. 3.5 Corrosion protection Transformers with a rated output of 200 kva shall be galvanized in accordance with the requirements of SS EN ISO 1461, at least class A. For transformers with a rated output of 315 kva painting or galvanizing is acceptable. However, it shall be possible to request that the 315 kva is delivered galvanized. In the event of painting, the transformer tank shall be painted using a method and quality that will protect the tank against corrosion in a class A environment. Approved methods are described in table 8:72 in BSK 94. Separate cooling radiators and smaller parts, such as consoles and so forth, shall be surface coated using the same methods as for the transformer tank. Fasteners mounted on galvanized or painted parts shall be of stainless steel in accordance with ISO F1 or A2 requirements. 3.6 Lifting equipment, transport, fastening devices The transformer shall be equipped with lifting devices enabling the complete transformer plus oil and mounted bushings. Lifting devices shall also exist to lift the core and windings out of the tank. The transformer 315 kva shall have a flat bottom. The transformer 315 kva shall be able to mounted both on the ground and at a pole according to EBR specification. Total weight, including oil, for the transformer 200 kva may not exceed 1,100 kg. The transformer 500 kva shall have lift lugs to accommodate lifting straps. To facilitate our inventory control each transformer with a rated output of 315 kva shall be delivered on a cargo pallet designed for handling by a forklift truck.

to 1250 kva Page 8/10 The transformer s production number shall be provided on any transport packaging material. 3.7 Monitoring devices It shall be possible to equip hermetically sealed transformers with a rated output of 315 kva s with pressure switches containing a release contact. Transformers with a rated output of 315 kva shall be equipped with a thermometer pocket for a signal thermometer in accordance with DIN 42554. An extra thermometer shall be provided, diagonally positioned, on transformers with a rated output of 500 kva. It shall also be possible to equip transformers with a rated output of 200 kva with a thermometer pocket. Those thermometer pockets that are not used shall be plugged or covered over. The thermometer shall have been produced by Kihlströms or a similar supplier and shall have potential-free signal and release contacts. 4 Dimensions 4.1 Transport wheels Transformers with a rated output of 500 kva shall on request be delivered with smooth and reversible wheels for transporting lengthways and sideways. a) The center distance shall be 850 mm in both directions. 4.2 External dimensions The external dimensions of the transformers, including wheels and bushings shall not exceed the values in table IV. Table IV Rated output (kva) Length (mm) Breadth (mm) 50-100 1100 700 1400 200 1100 800 1400 315 1300 900 1500 500 1400 950 1600 630 1500 1000 1800 800 1600 1100 1800 1000 1900 1100 1800 1250 1900 1100 1800 Height (mm) 5 Fittings The transformers shall be provided with fittings in accordance with table V. Table V Fittings Rated output kva

to 1250 kva Page 9/10 50 100 200 315 500 630 800 1000 1250 Rating signs, Tap changer, earth X clip, lifting equipment X X X X X X X X Galvanized tank X X X O flat tank bottom X X X X Adjustable, smooth transport O O O O O wheels Lugs for tow lines O O O O O Fastener equipment for pole X X X O attachment Contact flange for cable clips X X X X X Plug-in type bushings O O O O O Bottom valve connect no. 20 X X X X X X X X X DN22 Thermometer pocket X X X X X X Extra thermometer pocket X X X X X Thermometer O O X X X Pressure switch O O O O X= standard O= delivery on request

to 1250 kva Page 10/10 6 Tender information, documentation 6.1 Tender The tender shall contain the following information Key electrical data Name of company that will manufacture the transformers Type of coupler Short-circuit impedance No-load current No-load and charge losses Materials in windings Terminals/tapping points, bushings( type, earth/ground current, leakage path, materials in connections) Weight (total weight, oil weight) Construction drawings, preferably on diskette in CAD format Painting specifications or directions for the transformer tank Costs of tests in addition to routine tests Deviations from requirement specifications Written guarantee that the transformer noise level does not exceed 54 db(a) Written guarantee that the transformer oil does not contain PCB Assembly instructions and maintenance instructions, with specified maintenance times Type designation of fittings and manufacturers Opportunities for dismantling and recovery/recycling of materials. 6.2 Documentation When delivered, each transformer shall be accompanied by one copy of assembly instructions and maintenance instructions in Swedish for the transformer and its fittings. These documents shall be packed so that they remain unharmed through, for example, external damage during transit or as a result of weather conditions. The assembly instructions and maintenance instructions for the transformer and fittings shall also be available in electronic-form, i.e. on a diskette or CD. They must be written in Word or Excel format. The illustrations shall be in JPEG or GIF format. The reports from routine test on the transformer in question, connection diagrams and final documentation for each delivery must be in the possession of the purchaser before any payments can be made. The text reports for all the transformers included in a delivery shall be compiled in a single document and sent to the purchaser. Construction drawings and diagrams shall also be delivered on diskettes or CDs in CAD format.