STRATEGIC ENERGY MANAGEMENT PLAN FOR NORFOLK GENERAL HOSPITAL 2014

Similar documents
Joint Strategic Energy Management Plan for Listowel Wingham Hospitals Alliance 2014

STRATEGIC ENERGY MANAGEMENT PLAN. MICs Group of Health Services to Anson General Hospital Bingham Memorial Hospital Lady Minto Hospital

Brant Community Healthcare System STRATEGIC ENERGY MANAGEMENT PLAN (SEMP) FOR

Georgian Bay General Hospital Strategic Energy Management Plan 2014

STRATEGIC ENERGY MANAGEMENT PLAN ENGLEHART AND DISTRICT HOSPITAL

Collingwood General and Marine Hospital STRATEGIC ENERGY MANAGEMENT PLAN (SEMP)

NORTHUMBERLAND HILLS HOSPITAL STRATEGIC ENERGY MANAGEMENT PLAN FOR 2014 TO 2019

THE WEST NIPISSING GENERAL HOSPITAL STRATEGIC ENERGY MANAGEMENT PLAN 2014

ENERGY AUDITS (OR SURVEYS) & ENERGY MANAGEMENT PROGRAMS SECTION B

Electrical infrastructure serving the city of London CITY OF LONDON Corporate Energy Consumption Report

Energy Action Plan 2015

5-Minute Primer for Commercial Building Energy Audits

HVAC System Optimization

10 Strategic Steps to Reducing Your Energy Costs AEE Regional Chapter Meeting February 2, 2005

Cutting Electricity Costs with Electricity Financial Incentives. Gordon Lau Union Gas

Sea Water Heat Pump Project

Energy Efficiency: Integrated Design and HVAC Systems HEALTHCARE - TOP 5 GREEN BUILDING STRATEGIES

Energy Benchmarking Report for Lafayette Elementary School Bound Brook, NJ

AT&T Global Network Client for Windows Product Support Matrix January 29, 2015

Greenhouse Gas Implications of HVAC Upgrades in Multi-Unit Residential Buildings

PDATED: NOV Durham College. Conservation and Demand Management Plan

Business Plan: Energy Conservation

COMPARISON OF FIXED & VARIABLE RATES (25 YEARS) CHARTERED BANK ADMINISTERED INTEREST RATES - PRIME BUSINESS*

COMPARISON OF FIXED & VARIABLE RATES (25 YEARS) CHARTERED BANK ADMINISTERED INTEREST RATES - PRIME BUSINESS*

A Key Component of Environmental Sustainability Efforts and a Source of Substantial Cost Savings for FCGU. Dr. Simeon Komisar

Dallas/Fort Worth International Airport District Energy Plant Upgrades Project Making More with Less Sustainable Communities Conference Dallas, TX

Corporate Energy Management Plan

THE EUROPEAN GREEN BUILDING PROGRAMME. Technical Module on Combined Heat and Power

Continuous Commissioning of the Dallas/Fort Worth International Airport

CITY OF ORILLIA ENERGY MANAGEMENT PLAN

2015 RACE TO ZERO STUDENT DESIGN COMPETITION

Carbon Project Annual Report

Sino-Italian Environment & Energy Building S I E E B

HVAC Costs. Reducing Building. Building owners are caught between two powerful forces the need to lower energy costs. By Stephen J.

Corporate Energy Conservation & Demand Management Plan (CECDMP)

BWH & CEEH 2 - A Model of Strategic Energy Management

Tools for Energy Tracking and Benchmarking. ENERGY STAR Portfolio Manager for Congregations

school energy consumption assessment

Improving comfort and energy efficiency in a nursery school design process S. Ferrari, G. Masera, D. Dell Oro

IMPLEMENTING A STRATEGIC ENERGY MANAGEMENT PLAN FOR HEALTH CARE

Building Performance Optimization Services in the city of Boras, Sweden.

GSA Green Initiatives. NEBB Annual Conference October 22, 2011

Case Studies: Infrared Heating in Industrial Applications

Rules of Thumb Energy Efficiency in Buildings

Level 1 Energy Audit Report. For: Gladstone Regional Council

HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY

ENERGY AUDITS FOR EXISTING BUILDINGS: It s like (nearly) free money! FSi consulting engineers

Analysis One Code Desc. Transaction Amount. Fiscal Period

Energy Audits. Who needs one? Why it is needed? So many choices. Which one is right for my home? My business? My community?

EnerSmart Programs. enercase. Performance Contracting. contracting. Tired of. chasing capital for infrastructure upgrades?

Energy Audits. Good energy management begins with an energy audit

Driving Action through. Title Style. Moderated by: Sarah Zaleski U.S. DOE

Using Performance Contracting and Incentives to Accelerate Energy Efficiency Projects

Measurement & Verification Plan

Building Energy Efficiency Opportunity Report

University Health Network. Energy Management Plan 2014 to Energy & Environment. University Health Network

Energy Audits and Retro-commissioning Background Report

Codes and High Performance Hot Water Systems. Gary Klein Affiliated International Management, LLC

OPTIMAL POLYGEN COOLING CONCEPT FOR ST. OLAVS HOSPITAL IN TRONDHEIM, NORWAY

Reducing the Impact of Energy Costs on Business

HIGH LEVEL BUSINESS CASE FOR AN EEMS SYSTEM

Industrial Green Building Retrofit 101 Opportunities and Challenges. Light Industrial Green Building Retrofits. Why Green Retrofit?

Implementing Sustainable Practices in Environmental Management Systems: the Cultural Change Game

TOWN OF CALEDON. Corporate Energy Management Plan

Energy Benchmarking Report for Lakeside Middle School. Millville, NJ

Continuous Energy Management at UC San Diego. Anna Levitt, P.E. Assistant Energy Manager June 13, 2013

Oakland County Executive Department of Facilities Management. Energy Management Procedures October 5, 2009

Engineering Department. Public Works Division. August 14th, 2014

Case 2:08-cv ABC-E Document 1-4 Filed 04/15/2008 Page 1 of 138. Exhibit 8

Performance Contracting

PENNSYLVANIA GREEN ENERGY LOAN FUND

B O A R D M E E T I N G N a s h v i l l e, T e n n e s s e e November 6, 2014

Energy Conservation and Demand Management Plan. Township of Wellesley: Developed by Wendy Smith, Administrative Assistant Fire/Recreation

Comprehensive Resource Management

The Role of Building Maintenance in Energy Efficiency and Building Operations

Electricity Supply. Monthly Energy Output by Fuel Type (MWh)

Massey Hall Energy and Water Audit. Prepared for: The Corporation of Massey Hall and Roy Thomson Hall. April

Corporate Energy Conservation and Demand Management Plan Engineering Department. Public Works Division

Example of a diesel fuel hedge using recent historical prices

Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers

Energy Conservation and Demand Management Plan Municipality of Oliver Paipoonge 2011 to 2018

City of Cornwall Social Housing Division Top 10 Energy & Water Saving Tips. in Multi-Unit Residential Buildings

For. The Conservation Bureau Ontario Power Authority

Township of T Tay Energy Conservation and Demand Management Plan July 1, 2014 to June 30, 2019

Commercial Building Energy Initiative Tenant Business Case

Energy Savings from Business Energy Feedback

Connecticut Housing Finance Authority. Construction Guidelines: Energy Conservation 2014

Top 5 Trends in Data Center Energy Efficiency

City of Timmins Corporate Energy Conservation & Demand Management Plan (CECDMP) 2014 to Prepared by:

BOMA BESt Assessment Overview

Every Student I Every Day I Every Possibility

COUNTY OF PETERBOROUGH - ENERGY MANAGEMENT PLAN TEMPLATE

Identify Ways to Save with Energy Audits

Reducing the Impact of Energy Costs on Business

The main steam enters the building in the basement mechanical room; this is where the condensate line also leaves the building.

Energy Conservation for Colleges and Universities

Federal Buildings Initiative Audit Standards Guidelines

Corporate Energy Management Plan

Town of Whitby Corporate Energy Management Plan

Applying ICT and IoT to Multifamily Buildings. U.S. Department of Energy Buildings Interoperability Vision Meeting March 12, 2015 Jeff Hendler, ETS

Transcription:

STRATEGIC ENERGY MANAGEMENT PLAN FOR NORFOLK GENERAL HOSPITAL 2014 1

TABLE OF CONTENTS Introduction Energy Management Vision Guiding Principles for Energy Management Business Case for Strategic Energy Management Business Proposition Energy Management Goals and Objectives Goal: Obtain Organizational Approval of SEMP and Commitment of Resources Goal: Implement Financial Practices and Decision Making Processes; Establish Funding Resources Goal: Implement Strategic Energy Management Practices Purchasing/Procurement Procedures and Specifications Enhanced Design & Construction Practices Enhanced Facility Operating Practices Cost-Effective Facility Upgrades Active Commodity Management Goal: Monitoring, Track, & Improve Performance Timeline and Responsibilities for Plan Adoption and Implementation Baseline Energy and Water Use Energy Use Breakdown Energy Savings Opportunity Report Executive Summary 2

INTRODUCTION The overall purpose of Norfolk General Hospital s energy management plan and policies is to promote good stewardship of our environment and community resources. In keeping with our core values of Efficiency and Financial Responsibility, Norfolk General Hospital s energy management program will ultimately result in reduced operating costs and enable the Hospital to provide compassionate service to a greater number of persons in the community. Utility and energy related costs are a significant part of overall operating costs Utility costs in the 2011/12 fiscal year were $964,570.00. The Hospital s Energy Use Index (EUI) was 61.9 ekwh/ft2/yr Facility related O&M costs are $1,420,000 annually Facility capital project costs are projected at $2.5 million over 5 years With energy management an integral part of business decisions, Norfolk General Hospital can expect the following: 3 % reduction in energy use, with an overall reduction of 10 % in utility use and costs $140,000.00 plus in savings annually to the bottom line (1.4 million plus over 10 years), in addition to the existing annually achieved savings of $400,000 since 1992. Energy investments will get a 10% internal rate of return (IRR) Recent activity associated with managing these costs include the following: A recently completed Opportunity Assessment through the Healthcare Energy Leaders Ontario program. (Executive Summary attached) OHA Hospital Scorecard Survey participation & benchmarking report. saveonenergy application for new lighting incentives Interior lighting retrofits such as T5 lighting in Mechanical areas and LED s lighting retrofits in entrances. Reports on past activities in the area of energy and water conservation can be viewed through the following links: http://www.csaregistries.ca/challenge/cha_entity_e.cfm?no=3161 To further strengthen and obtain full value from energy management activities, a strategic approach will be taken: the organization will fully integrate energy management into its business decision-making, policies, and operating procedures. Active management of energy related costs and risks in this manner will provide a significant economic return to the organization and will support other key organizational objectives. 3

Energy Management Vision Norfolk General Hospital s mission statement is to relieve illness and suffering, and help people live healthier lives. Therefore, we consider our facilities a primary source of giving care and an integral part of the healing environment. Key to this equation is the ability to use our facilities efficiently and effectively. This results in Norfolk General Hospital being able to direct more resources toward patient care and the relief of illness and suffering. Not only that, but by reducing our environmental footprint, we are also doing our part to create a healthier environme nt. Something that is essential to the people we serve and that which helps them to lead healthier lives. So Norfolk General Hospital s energy management vision is to eliminate energy waste, wherever possible, through infrastructure improvement, through policy and process changes, and through the embracing of best practice and technology changes. 4

Guiding Principles for Strategic Energy Management Norfolk General Hospital s energy management plan will be guided by these principles: Taking A Strategic Approach: While Norfolk General Hospital actively manages energy and utility costs by implementing opportunities as they are identified, by acting strategically, the Hospital can significantly improve its energy-related performance. Internalizing energy and utility management into our organization s every-day decision-making, policies, and operating procedures will help assure substantial and long-lasting reductions in energy use throughout Norfolk General Hospital. Supporting Mission-Critical Goals: Strategic energy management will directly support Norfolk General Hospital s mission-critical goals of caring for the environment and the community. It will also help the Hospital to optimize the healing and working environment; improve the hospital s financial bottom line by reducing unnecessary energy and utility costs; and optimize the capacity of existing energy systems to meet current and expanding operational needs. The impacts of Norfolk General Hospital s energy management efforts on those goals will be tracked and reported wherever possible. Pursuing Long-Term Change to Core Business Practices: The core of a strategic approach is the consistent incorporation of energy and utility management into our organization s core practices and decision making, such as the strategic planning and budgeting processes. Change in energy-related business practice will cover all applications of energy management new construction and major renovations, existing facility operations and upgrades, and economic analysis and procurement practices. Fostering Organizational Commitment and Involvement: Executive and organizational commitment and involvement is critical to successful strategic energy management. Upper management at Norfolk General Hospital will work with facility managers and other key staff to ensure that adequate organizational support and resources are provided to maximize the benefits of energy and utility management. Energy and utility management will be integrated into the strategic planning and capital budgeting processes. Obtaining Solid Economic Returns: Energy management investments will yield solid economic returns that meet Norfolk General Hospital s expectations on Internal Rate of Return and Return on Investment. Norfolk General Hospital will apply consistent financial analysis methods that consider life-cycle costs that reduce total cost of facility ownership and operation. Using Available Resources and Assistance: Norfolk General Hospital will use national, regional, and local sources of strategic, technical, and financial assistance to help achieve our energy management goals. These include programs through local distribution companies, the Ontario Power Authority, ENERGYSTAR, saveonenergy, the Canadian Coalition for Green Health Care, The Canadian Healthcare Engineering Society, and EnerCan. 5

The Business Case for Strategic Energy Management Below are the central business arguments for Norfolk General Hospital s pursuit of strategic energy management. Section VI then presents the business proposition the results of analysis of the energy efficiency opportunities and their associated costs and internal rate of return. Strengthened Community Leadership and Environmental Stewardship Energy management is a visible, public commitment to the community and environment. Through aggressive energy management, Norfolk General Hospital can provide leadership in promoting sustainable communities, efficient business practices, and environmental stewardship. This is an excellent opportunity to provide leadership and reduce costs at the same time. Enhanced Healing and Working Environment In existing facilities, efficient operating practices improve patient as well as employee comfort with more stable air temperature, better indoor air quality, and lighting. By way of an example, recent research has found that daylight eases surgical pain and contributes to substantial savings in pharmaceutical costs. Improved Financial Health and Operating Cost Reduction Strategic energy management presents a highly leveraged opportunity to reduce operating costs and positively impact Norfolk General Hospital s bottom line. Dollars of operating cost savings directly improve the operating margin. Further, investments in energy projects typically have a lower risk of performance over time relative to other investments and savings from energy projects are easier to forecast reliably than savings or revenue increases expected from more variable types of investment. Optimization of Capacity to Meet Current and Expanding Operational Needs Energy efficiency optimizes overall equipment/system operation so that system capacity can be reclaimed for current and expanding operational needs. This free capacity can eliminate the need to add major new infrastructure is far less expensive. 6

Business Proposition If energy management considerations are integral to relevant business practices, policies, procedures, and decision-making processes, Norfolk General Hospital s energy and utility related costs can be reduced by an additional 10% over a 5year period. Based on 2013 utility rates, this will result in $140,000 thousand in annual value to the bottom line, or a total $700,000 thousand over a 5-year period. Integration of energy management into organizational decision making and business practices will continue to produce value annually for a much longer period of time. To support the achievement of these financial benefits, Norfolk General Hospital will invest in energy-related capital and operating improvements, meeting an Internal Rate of Return (IRR) that is acceptable to its Board of Directors and Executive Officers. 7

Energy Management Goals The following outlines some of the energy management goals that will be adopted by Norfolk General Hospital. They include, but are not limited to, the following: SEMP Approval, Resources to Implement Implement Financial Practices and Decision Making Processes; Establish Funding Resources Implement Strategic Energy Management Practices Purchasing/Procurement Procedures and Specifications Enhanced Design & Construction Practices Enhanced Facility Operating Practices Cost-Effective Facility Upgrades Active Commodity Management Monitoring, Track, & Improve Performance Goal: SEMP Approval, Resources to Implement Executive approval process adjustments and resource allocations to support initiatives. Support from key staff (financial management, purchasing/procurement, construction, building operations, etc.). Creation of mechanisms/processes to make resources available. Clarification and communication of staff roles and responsibilities, performance goals, and energy management reporting. Goal: Implement Financial Practices and Decision Making Processes Money spent to achieve energy efficiency is viewed as an investment, not a cost. Financial decision makers consistently use life cycle cost analysis (LCCA) on all new construction, major renovations, and equipment replacements over lowest cost Internal rate of return (IRR) as pre-approved by the Hospital Board and Administration. Train staff on Life Cycle Cost Analysis (LCCA) and financial requirements and decision making process. Decisions about energy management investments will be part of Norfolk General Hospital s high-level, long range process of budgeting for capital and operations. Goal: Establish Purchasing Specifications for Energy Efficient Equipment and Services Establish and consistently use purchasing specifications that minimize life-cycle costs for energy efficient equipment and services. Establish efficiency specifications for standard equipment routinely replaced (e.g. lights, motors, and unitary HVAC equipment). 8

Establish efficiency guidelines that apply LCCA for custom equipment purchases (e.g. chillers). Establish efficiency standards for design and construction, and for building operations and maintenance services. Goal: Implement Enhanced Design & Construction (D&C) Practices Implement improved new construction practices in all capital projects that specify early team collaboration and integrated design (ID). Integrated design required for funding. RFPs, contract terms & conditions, & fee structures will support ID. Apply LCCA and financial hurdle rates described above to design decisions. Apply established purchasing procedures and specifications. Include incentives and tax credits wherever available. Educate all owner s project managers or construction managers and contractors on integrated design and their respective roles in master planning pre-design, design, construction, testing, commissioning, and monitoring. Set and meet clear energy performance targets for new build projects; measure and improve over time. Establish baseline for measuring performance goals (e.g. code, or national reference standards like ASHRAE 90.1). Set targets. Measure performance and improve over time. Specify commissioning as a standard procedure. Retain the services of an independent third-party commissioning agent. 100 percent of fundamental building systems and elements will be designed, installed, and calibrated to operate as designed. Design team, commissioning agent, and building operators will work closely throughout the design process and occupancy to ensure good transition. Goal: Improve Building Operating Performance Equipment tune-up and improved operations and maintenance (O&M) will achieve the following results while supporting patient care, and facility comfort and safety. Achieve reductions in utility related operating costs for existing facilities by an average of 10% over 5 years and continue to improve by 1% per year for 5 years thereafter. Reduce the system-wide EUI from 61.9 ekwh/ft2/yr to 56.0ekWh/ft2/yr by 2019. The EUI will be adjusted for variances in patient days and IT intensity. Reduce energy consumption by 120,000 kwh per year. Improve ENERGYSTAR rating. Goal: Implement Cost-Effective Facility Upgrades Implement equipment and system upgrades where justified by life-cycle cost analysis. Expand use of qualified service providers as needed. Develop standard RFP documents, contract terms, and reporting standards. 9

Goal: Actively Manage Energy & Utility Commodities Minimize utility costs and exposure to market risks. Utility costs include natural gas, electricity, water, and sewer. Participate in the energy/utility regulatory process. Goal: Monitor, Track, and Reward Progress Track progress on Strategic Energy Master Plan Track energy reductions monthly and report annually. Reward staff for successes. 10

Baseline Energy Use The baseline energy profile has been selected using the most recent full fiscal year with available utility data, which is 2012. This baseline was used to calibrate energy end -use estimates and as the reference case for calculating energy savings. Exhibit 1 presents the baseline energy use and costs; Exhibits 3, 4, and 5 present the data in graphic format. Key Observations: A review of the baseline energy cost profile reveals that: The total annual utility costs for the site in 2012 were $1,028,543. Electricity represents the largest cost at 51% of total cost, natural gas costs were 21% of total cost, and water costs were 29% of total cost. The annual electrical consumption is 4,626 MWh, and the annual gas consumption is 10,346 emwh, resulting in a total site energy intensity of 61.9 ekwh/ft 2 /yr. This places the Norfolk General Hospital 15% above the average of 53.7 ekwh/ft 2 /yr based on an average of similar facilities in Ontario 1. The natural gas consumption is the reason that the overall site energy intensity is higher t han the benchmark. Natural gas use is 24% higher than the average. The water use intensity is 445 L/ft 2, approximately twice as high as the average 2. 1 Based on audits of 8 hospitals and long term care facilities in Ontario, 2009 to 2011. 2 Based on audits of 7 hospitals and long term care facilities in Ontario, 2009 to 2011. 11

Exhibit 1 Baseline Energy Consumption 2012 Usage Electricity Natural Gas Water Total Intensity GHG Emissions Usage Intensity GHG Emissions Usage Intensity Usage Intensity GHG Emissions [kwh] [kwh/ft 2 ] [teco 2 ] m 3 [ekwh/ft 2 ] [teco 2 ] [m 3 ] [L/ft 2 ] [ekwh] [ekwh/ft 2 ] [teco 2 ] Jan 358,152 1.5 75.2 140,647 6.0 267.7 6,532 27.0 1,812,440 7.5 342.9 Feb 336,074 1.4 70.6 128,582 5.5 244.7 7,931 32.8 1,665,611 6.9 315.3 Mar 356,080 1.5 74.8 100,755 4.3 191.7 8,606 35.6 1,397,886 5.8 266.5 Apr 353,560 1.5 74.2 89,354 3.8 170.0 7,687 31.8 1,277,480 5.3 244.3 May 370,000 1.5 77.7 51,209 2.2 97.4 7,700 31.8 899,496 3.7 175.1 Jun 460,282 1.9 96.7 48,775 2.1 92.8 10,208 42.2 964,616 4.0 189.5 Jul 500,737 2.1 105.2 43,368 1.9 82.5 11,838 48.9 949,166 3.9 187.7 Aug 472,534 2.0 99.2 43,234 1.8 82.3 11,520 47.6 919,572 3.8 181.5 Sep 396,096 1.6 83.2 42,940 1.8 81.7 10,484 43.3 840,097 3.5 164.9 Oct 338,927 1.4 71.2 77,346 3.3 147.2 10,181 42.1 1,138,689 4.7 218.4 Nov 331,873 1.4 69.7 113,316 4.8 215.6 7,452 30.8 1,503,561 6.2 285.3 Dec 351,564 1.5 73.8 121,089 5.2 230.4 7,426 30.7 1,603,624 6.6 304.3 Total 4,625,879 19.1 971.4 1,000,615 42.8 1,904.2 107,565 444.5 14,972,238 61.9 2,875.6 12

Exhibit 2 shows the monthly electricity use profile. The majority of the electricity consumption is baseload, with a summer peak due to cooling, and a smaller winter extra that is the result of increased pumping energy associated with the heating system. Exhibit 2 Baseline Electricity Use Profile Exhibit 3 shows the monthly natural gas use profile. Approximately half of the gas is being used for the baseload, and there is a predictable winter increase that corresponds well with the heating demand. Exhibit 3 Baseline Natural Gas Use Profile Norfolk General Hospital Strategic Energy Management Plan Page 13 of 17

Exhibit 4 shows the monthly water use profile. The majority of the water consumption is baseload, but there is an increase in the summer due to cooling loads. Exhibit 4 Baseline Water Use Profile Norfolk General Hospital Strategic Energy Management Plan Page 14 of 17

Energy End Use Breakdown Energy end-use estimates were calculated using spreadsheet-based tools in conjunction with a review of utility profiles. Specific energy uses that may overlap several categories are explained in their respective sections. Electricity Exhibit 5 illustrates the electrical energy end-use distribution. The following end uses shown below were identified to have an electrical impact. Exhibit 5 Electricity End-Use Breakdow n Space Cooling 11% Lighting 11% Plug Loads/Misc. 21% HVAC Fans & Pumps 57% Observations on Electrical End-Use Breakdown: HVAC Fans & Pumps: 57% The energy consumption for HVAC equipment is higher than expected, but still reasonable given that the heating system is hydronic. Plug Loads/Miscellaneous: 21% Plug loads include IT equipment. The energy consumption is within the expected range. Space Cooling: 11% The cooling energy consumption is within the expected range. Lighting: 11% Norfolk General Hospital Strategic Energy Management Plan Page 15 of 17

The lighting energy consumption has been based on the lighting fixture count provided by the Norfolk General Hospital. The lighting power density of the facility based on this count is approximately half of what would be expected in a facility of this type. Consequently, the lightin g energy consumption is probably twice as high, but this will need to be confirmed by a detailed lighting audit. Natural Gas Exhibit 6 illustrates the natural gas energy end-use distribution. The following end uses shown below were identified to impact natural gas use. Exhibit 6 Natural Gas End-Use Breakdow n Space Heating 49% DHW & Process 51% Observations on Natural Gas End-Use Breakdown: Domestic Hot Water & Process: 51% Process loads include steam consumption for humidification, sterilization, and cooking. The amount of energy used for the baseload DHW and steam supply is much higher than expected. Outside of the heating season, the overall efficiency of the boiler plant is likely very low. Space Heating: 49% The energy consumption for space heating is within the expected range. Norfolk General Hospital Strategic Energy Management Plan Page 16 of 17

Energy Savings Opportunity Report Executive Summary The Ontario Power Authority retained ICF Marbek to conduct an opportunity assessment of hospitals throughout Ontario as part of the Commercial and Institutional Host Organizations program. This report pertains to the Norfolk General Hospital, a full service hospital and long term care facility located in Simcoe, Ontario. The objective of the assessment is to identify and assess potential energy retrofit opportunities including lighting, HVAC and building envelope as well as water, renewable energy, and other innovative measures. The results of this report will provide the Norfolk General Hospital with the basis for planning and implementing energy and water reduction improvements in their facility. The results of the assessment indicate that there is a potential for the implementation of cost effective energy and water reduction measures in the areas of lighting, HVAC equipment, and water fixtures. The total cost savings for the immediate implementation measures is estimated to result in a simple payback of 2.5 years, and the resulting GHG emissions reductions are 567.3 tonnes of eco 2 per year. The total savings represent an 11% reduction in electricity and a 24% decrease in natural gas consumption. The implementation of these measures would decrease the energy intensity from the present baseline. The combined heat and power measure would generate 3,162 MWh of electricity annua lly, equivalent to 68% of the baseline electricity consumption. The measure would lead to a net annual increase of 663,745 m 3 of natural gas and a net increase of 599 tonnes of eco 2 per year. It is estimated that the proposed measures would be eligible for incentives from the OPA s saveonenergy program, and would contribute 410 kw and 3,669 MWh of savings towards the OPA s DSM targets. Note that the savings potential is based on the preliminary opportunity assessment. A more accurate estimate of the savings will be available once the detailed assessments of the measures have been completed. Energy Reduction Measure Potential Incentives Incentive Stream [kw] [kwh] [$] Lighting Retrofit ERII Prescriptive 22.8 84,721 $7,618 Pump Retrofit ERII Custom 7.1 62,116 $6,212 HVAC Recommissioning ERII Custom 0.0 360,000 $36,000 Combined Heat & Power PSUI 380.0 3,162,360 $456,146 Total 409.9 3,669,197 $505,976 Norfolk General Hospital Strategic Energy Management Plan Page 17 of 17