INDOOR AIR QUALITY ASSESSMENT



Similar documents
INDOOR AIR QUALITY REASSESSMENT. A. J. Sitkowski Elementary School 29 Negus Street Webster, Massachusetts

WATER DAMAGE INVESTIGATION. Massachusetts Department of Public Utilities 1 South Station Boston, Massachusetts

INDOOR AIR QUALITY POST-OCCUPANCY ASSESSMENT. Massachusetts Department of Revenue 100 TradeCenter, Suite 760 Woburn, MA

INDOOR AIR QUALITY ASSESSMENT. Alcott Elementary School 91 Laurel Street Concord, Massachusetts

INDOOR AIR QUALITY REASSESSMENT. Sgt. William H. Carney Memorial Academy 247 Elm Street New Bedford, Massachusetts

INDOOR AIR QUALITY ASSESSMENT INCIDENT RESPONSE. Sgt. William H. Carney Memorial Academy 247 Elm Street New Bedford, Massachusetts

INDOOR AIR QUALITY ASSESSMENT. Dennett Elementary School 80 Crescent Street Plympton, Massachusetts

MOLD ASSESSMENT. Charles A. Bernazzani Elementary School 701 Furnace Brook Parkway Quincy, Massachusetts

INDOOR AIR QUALITY ASSESSMENT. Braintree Rehabilitation Hospital 250 Pond Street Braintree, Massachusetts 02184

INDOOR AIR QUALITY POST-FLOODING ASSESSMENT. Massachusetts Department of Developmental Services 100 Cummings Center Suite 150B Beverly, Massachusetts

WATER DAMAGE INVESTIGATION. Massachusetts Gaming Commission 101 Federal Street Boston, Massachusetts

INDOOR AIR QUALITY ASSESSMENT MOLD INVESTIGATION. Department Of Children and Family 810 Memorial Drive Cambridge, Massachusetts

A Breath of Poor Air: Inspecting Indoor Air Quality in the Classroom Ashley Schopieray

Mould Mould A Basic Guide

Causes of High Relative Humidity Inside Air Conditioned Buildings. Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates

BUILDING ASSESSMENT QUESTIONNAIRE. B. TENANTS Is there more than one tenant in the building? YES

CENTER FOR ENVIRONMENTAL HEALTH Emergency Response/Indoor Air Quality Program

Risk Bulletin. Mold Prevention and Control for Mechanical and HVAC Contractors. XL Group Insurance

Mold/Water Damage Investigation. Weymouth High School One Wildcat Way Weymouth, Massachusetts

KEY ELEMENTS IN PREVENTING AND MITIGATING MOLD CLAIMS

Components HVAC General Standards HVAC Guidelines HVAC System Selection Life Cycle Cost Analysis

HVAC Checklist - Long Form

INDOOR AIR QUALITY ASSESSMENT. Massachusetts State Lottery Commission Building 60 Columbian Street Braintree, Massachusetts

PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE

WATER DAMAGE/MOLD INVESTIGATION. Massachusetts Department of Developmental Services 68 North Main Street Carver, Massachusetts

DESERT RESEARCH INSTITUTE MOLD ASSESSMENT AND REMEDIATEION PROCEDURE

PEOSH. Indoor Air Quality Training for Asthma-Friendly Schools Part I PEOSH Indoor Air Quality Standard Overview. Eric Weren, MSIH

Why Measure Carbon Dioxide Inside Buildings? By Rich Prill, Washington State University Extension Energy Program

ASTHMA REGIONAL COUNCIL

THREE. Heating and Cooling

Mold and Mildew Mold and mildew can be detected by sight, smell and touch.

INDOOR AIR QUALITY INTRODUCTION WHAT ARE THE SYMPTOMS OF SICK BUILDING SYNDROME? WHEN DID POOR INDOOR AIR QUALITY BECOME A PROBLEM?

Radford University. Indoor Air Quality Management Plan

heating 3 & cooling heating and cooling 2010 PulteGroup, Inc. All Rights Reserved.

WATER DAMAGE/MOLD INVESTIGATION. Massachusetts Department of Transitional Assistance 160 W. Rodney French Blvd New Bedford, Massachusetts

Old Dominion University Mold Management Plan

WHOLE-HOUSE VENTILATION SYSTEMS

IAQ - indoor ventilation Air contaminants Molds Requirements for growth Health effects Mold prevention - moisture EH&S mold checks & removal

Glossary of Heating, Ventilation and Air Conditioning Terms

Building and Grounds Maintenance Checklist

Charles McCammon, Ph.D., CIH

Liabilities of Vented Crawl Spaces And Their Impacts on Indoor Air Quality in Southeastern U.S. Homes

Liabilities of Vented Crawl Spaces, Their Impacts on Indoor Air Quality in Southeastern U.S. Homes and One Intervention Strategy

INDOOR AIR QUALITY ASSESSMENT. Monson Town Offices 29 Thompson Street Monson, Massachusetts

HVAC Systems and Indoor Air Quality. Douglas K. Spratt, M.Sc., P.Eng.

RECOMMENDATIONS FOR ENCLOSED ICE ARENA MANAGEMENT

Before You Start an Energy Efficiency Retrofit The Building Envelope

Glossary of HVAC Terms

Energy Efficiency in Industrial HVAC Systems

THE APPLICATION OF OZONE FOR AIR TREATMENT: CASE STUDY OF A BINGO HALL HVAC SYSTEM

HVAC For Schools How to purchase an HVAC system that meets your school s unique requirements and stays within your budget

Venice Library Humidity Study. for Williams Building Diagnostics, LLC th Street West Bradenton, FL Report April 13, 2015

BUREAU OF ENVIRONMENTAL HEALTH Emergency Response/Indoor Air Quality Program

Mold Basics. Why is mold growing in my home?

Maintenance Matters. Avoiding Exhaust Duct Problems

Arbor Heights Indoor Air Quality Investigation Interim Report

Guidelines for Mold Remediation (Removal)

Pool Dehumidification Basics

Molds and mildew are fungi that grow

Mechanical and Natural Ventilation

DRYER VENTING SPECIFICATIONS DRYER SAFETY

Carson Dorn, Inc. December 18, Patrick Holmes Associate Manager Juneau I, LLC 645 G Street, Suite Anchorage, AK Dear Mr.

AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries

Indoor Air Quality Issues for Hotels

Construction Indoor Air Quality Management Plans for LEED. Matt Gregg, PE, LEED AP

Answers to Your Questions from the Webinar

ASTACEA4 Inspect complex/central air conditioning systems

Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,

Basic Mold Prevention

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) March

IEQ Management Plan. Denver Museum of Nature and Science ECF Addition

How To Prevent And Manage A Flood And Mold

Chignecto-Central Regional School Board. Highland Consolidated Middle School. Indoor Air Quality Issues Mechanical Systems

WATER DAMAGE INVESTIGATION. Massachusetts Department of Children and Families 33 East Merrimack Street Lowell, Massachusetts

WATER DAMAGE FOLLOW-UP INVESTIGATION. Massachusetts Department of Children and Families 33 East Merrimack Street Lowell, Massachusetts

DUCT SYSTEM DESIGN CONSIDERATIONS Part 1

about your house Before You Start Renovating Your Basement Moisture Problems Figure 1 Moisture problems to solve

1932 Lexington Houston, Texas (713) Recommendations for installation of cooling systems

How To Perform A Mold And Indoor Air Quality Assessment

Walkthrough Inspection Checklist

Solving Persistent Moisture Problems and Moisture Damage

bout your HOUSE before you start Renovating Your Basement Moisture Problems

This appendix provides information

INDOOR AIR QUALITY ASSESSMENT. Holbrook Junior/Senior High School 245 South Franklin Street Holbrook, MA 02343

Indoor Environmental Quality Checklist Including Background Information in Comment Section

PROPERTY INSPECTION OR ASSESSMENT OF DAMAGES

IEQ-15 Air Distribution System

Chilled Beam Solutions ADVANCING THE SCIENCE OF AIR DISTRIBUTION. Redefine your comfort zone.

CHAPTER 4 VENTILATION

bout your house before you start Renovating Your Basement Moisture Problems

Attached is a link to student educational curriculum on plug load that provides additional information and an example of how to estimate plug load:

Mold Response and Remediation Plan

Replacement of Heating, Ventilation, Air Conditioning (HVAC) Units In Apartments Located at 641 Fifth Avenue. Photo Essay

MOLD RESPONSE AND REMEDIATION PLAN

Indoor Air Quality FILL YOUR HOME WITH AIR THAT IS AS CLEAN AS IT IS COMFORTABLE. READ ONLY

Controlling Condensation On CWP Insulation BY ED LIGHT, MEMBER ASHRAE; JAMES BAILEY, P.E., MEMBER ASHRAE; AND ROGER GAY

Water Management & Damage Prevention:

Envirotest Research Inc NE 200 th St. Suite 100 Shoreline, WA Fax:

Managing Heat Stress in Poultry

Wellesley College Mold Management Program March 2009

Transcription:

INDOOR AIR QUALITY ASSESSMENT Massachusetts Criminal Justice Training Council at the Boylston Town Offices Building 221 Main Street Boylston, Massachusetts Prepared by: Massachusetts Department of Public Health Bureau of Environmental Health Assessment August, 2000

Background/Introduction At the request of a parent, an indoor air quality assessment was done at the Boylston Elementary School at the Boylston Town Offices Building, 221 Main Street, Boylston, Massachusetts. This assessment was conducted by the Massachusetts Department of Public Health (MDPH), Bureau of Environmental Health Assessment (BEHA). On March 14, 2000, Michael Feeney, Chief of Emergency Response/Indoor Air Quality (ER/IAQ), BEHA made a visit to this school, to conduct an indoor air quality assessment. Mr. Feeney was accompanied in part by Dennis Costello, Boylston Board of Health and Charles McCarthy, Principal of the Boylston Elementary School. The Boylston Town Offices Building is a two-story steel frame structure built in 1973 on the campus of the Sheppard Knapp School. After the private school ceased operation, the building was used as office space by Digital Equipment Corporation (DEC). DEC appears to have modified the second floor rooms and cafeteria area. The Town of Boylston obtained the building after DEC ceased operation in the mid-1990s and was converted to space for town offices. As part of a current renovation project, students from the Boylston Elementary School were temporarily moved into the first floor and two rooms on the second floor. Once the planned renovations are complete, students will be moved from this building and the space occupied by the school revert back to town office space. The second floor is the Massachusetts Criminal Justice Training Council (MCJTC), which rents this space from the Town of Boylston and uses the five rooms as offices and a training center for police officers and cadets. Alterations were made to the heating ventilation and air-conditioning (HVAC) system by DEC in the space occupied by the MCJTC that do not exist in other areas in the building. For this reason, the conditions in each area will be described in separate reports. The focus of this report is the MCJTC. The 2

space currently occupied by the Boylston Elementary School is the subject of a separate report. The section occupied by the school consists of classrooms, a gymnasium and a kitchen/cafeteria. Windows in the school section of the building are openable. The HVAC system is capable of providing both heat and chilled air. A chiller connected to the HVAC system is located at the rear of the building. The section occupied by the MJCTC consists of three large meeting rooms and two offices. It was reported that the classrooms on the second floor would be reoccupied by the MCJTC once Boylston Elementary School students move from the building. Windows in the MCJTC section of the building are openable. The HVAC system is capable of providing both heated and chilled air. A chiller connected to the HVAC system is located at the rear of the building. Methods Air tests for carbon dioxide were taken with the Telaire, Carbon Dioxide Monitor and tests for temperature and relative humidity were taken with the Mannix, TH Pen PTH8708 Thermo-Hygrometer. Results The school has a police officer and cadet population of approximately 70 and a staff of approximately 5-7. Tests were taken under normal operating conditions. Test results appear in Table 1. Discussion Ventilation 3

It can be seen from the tables that carbon dioxide levels were elevated above 800 parts per million (ppm) in two of five areas surveyed, which is indicative of a ventilation problem in these areas. Fresh air is supplied by a mechanical unit ventilator (univent) system (see Figure 1). Univents were not operating during the assessment. Of note was classroom 1BTO201, which had a carbon dioxide level over 2,000 ppm, indicating little air exchange in this room. To function as designed, univents and univent returns must remain free of obstructions. Importantly, these units must be activated and allowed to operate while rooms are occupied. It appears that additional fan coil units (FCUs) were retrofitted into the heating pipes in the large meeting rooms on the second floor (see Picture 1). These FCUs were not part of the original HVAC system, but were believed installed during the DEC occupancy of the building. Each of these FCUs appears to be equipped to provide both heat and air conditioning. The FCUs do not supply fresh air, but rather only heat or cool recirculated air. With the exception of restrooms, no mechanical exhaust ventilation system exists in this building. Second floor rooms have a passive non-mechanical exhaust vent located over windows (see Picture 2). In order to function, this ventilation system relies on positive pressure created by the univent to force air out of the passive vent. As the univent operates, air pressure increases as additional fresh air is introduced into the classroom (called positive pressure). As positive pressure increases, air is forced out of the room through wall and door spaces. The passive vent is designed to allow for slow release of air from classrooms by increasing positive pressure created by the univent. The design of these exhaust vents requires that classroom hallway doors remain closed as much as practical in order to maintain positive pressure. With hallway doors open, classroom air would be forced into hallways. In addition, several of these passive vents were examined and were noted to be 4

backdrafting cold air into classrooms. Previous experience indicates that these types of systems tend to backdraft cold air during winter months. Without a mechanical system, these vents may not function to provide exhaust ventilation and be a source of cold air during winter months. In order to have these vents operate as designed, doors and windows must remain closed in classrooms equipped with these vents. With the absence of active mechanical exhaust ventilation, pollutants generated during building occupancy will tend to linger in classrooms. Degrading the ability of the HVAC system to create positive pressure in the MCJTC classrooms are the existence of passive vents in the base of hallway doors (see Picture 3). Since air can readily flow through these vents even with classroom hallway doors closed, the HVAC system will have a difficult time building up positive pressure to expel air through the passive exhaust vents above windows. To maximize air exchange, the BEHA recommends that both supply and exhaust ventilation operate continuously during periods of school occupancy. In order to have proper ventilation with a mechanical supply and exhaust system, the systems must be balanced to provide an adequate amount of fresh air to the interior of a room while removing stale air from the room. The date of the last servicing and balancing was not available at the time of the assessment. The Massachusetts Building Code requires a minimum ventilation rate of 15 cubic feet per minute (cfm) per occupant of fresh outside air or have openable windows in each room (SBBRS, 1997; BOCA, 1993). The ventilation must be on at all times that the room is occupied. Providing adequate fresh air ventilation with open windows and maintaining the temperature in the comfort range during the cold weather season is impractical. Mechanical ventilation is usually required to provide adequate fresh air ventilation. Carbon dioxide is not a problem in and of itself. As carbon dioxide levels rise, it 5

indicates that the ventilating system is malfunctioning or the design occupancy of the room is being exceeded. When this occurs a buildup of common indoor air pollutants can occur, leading to discomfort or health complaints. The Occupational Safety and Health Administration (OSHA) standard for carbon dioxide is 5,000 parts per million parts of air (ppm). Workers may be exposed to this level for 40 hours/week based on a time weighted average (OSHA, 1997). The Department of Public Health uses a guideline of 800 ppm for publicly occupied buildings. A guideline of 600 ppm or less is preferred in schools due to the fact that the majority of occupants are young and considered to be a more sensitive population in the evaluation of environmental health status. Inadequate ventilation and/or elevated temperatures are major causes of complaints such as respiratory, eye, nose and throat irritation, lethargy and headaches. Temperature readings ranged from 73 0 F to 77 0 F, which was within BEHA s recommended comfort guidelines. The BEHA recommends that indoor air temperatures be maintained in a range of 70 0 F to 78 0 F in order to provide for the comfort of building occupants. In many cases concerning indoor air quality, fluctuations of temperature in occupied spaces are typically experienced, even in a building with an adequate fresh air supply. The relative humidity in this building was below the BEHA recommended comfort range in all areas sampled. Relative humidity measurements ranged from 11 to 20 percent. The BEHA recommends that indoor air relative humidity is comfortable in a range of 40 to 60 percent. Relative humidity levels in the building would be expected to drop during the winter months due to heating. The sensation of dryness and irritation is common in a low relative humidity environment. Low relative humidity is a very common problem during the heating season in the northeast part of the United States. 6

Microbial/Moisture Concerns Of note is the univent design. Instead of installing univents as a complete metal case, it appears that the internal workings of a univent were encased in specially built wooden cabinets (see Picture 4). Within these cabinets are pipes clad with fiberglass insulation (see Picture 5). Since these univents can provide chilled air during warm months, moist air introduced into these wooden cabinets can result in the wetting of the insulation paper. It appears that mold may have colonized the insulation paper (see Picture 6). This colonization may be a source of spores and other mold-related particulates, which can be aerosolized by the univent. Other sources of mold colonization of pipe insulation exist in the gymnasium (see Picture 7). Leaks from the heating system resulted in active mold growth on the exterior of the insulation. Each univent is equipped with drip pans to collect and drain condensation from cooling coils. The manufacturer of these univents provided a styrofoam liner to protect the drip pans from water damage. These styrofoam liners have never been replaced since the installation of the univents (see Picture 8). The accumulation of debris in these drip pans can serve as growth media for mold. 7

Other Concerns Other conditions that can potentially affect indoor air quality were noted during the assessment. Wasp nests were found in the interior of the passive exhaust vents on the first floor. It is possible that wasps are in the passive vents in second floor classrooms as well. It is recommended that they be removed as soon as possible in a manner as to not introduce insects or chemical agents into the school via the ventilation system. Conclusions/Recommendations In view of the findings at the time of the visit, the following recommendations are made to further improve indoor air quality: 1. Operate univents while classrooms are occupied. 2. Seal passive vents in hallway doors. 3. Examine the feasibility of providing mechanical exhaust ventilation for high occupancy meeting rooms to remove heat and moisture from these areas. 4. Service the louvers of the exhaust vents. Remove wasp nests from vents if present. 5. Examine the feasibility of replacing drip pans in univents. 6. Replace water damaged pipe insulation. 7. For buildings in New England, periods of low relative humidity during the winter are often unavoidable. Therefore, scrupulous cleaning practices should be adopted to minimize common indoor air contaminants whose irritant effects can be enhanced when relative humidity is low. An increase in filter efficiency in the HVAC system may also be advisable. Drinking water during the day can help ease some symptoms associated with a dry environment (throat and sinus irritations). 8. Remove wasp s nest from interior of passive first floor vent in a manner as to not introduce insects or chemical agents into the building via the ventilation system. 8

9

References BOCA. 1993. The BOCA National Mechanical Code-1993. 8 th ed. Building Officials & Code Administrators International, Inc., Country Club Hills, IL. M-308.1 OSHA. 1997. Limits for Air Contaminants. Occupational Safety and Health Administration. Code of Federal Regulations. 29 C.F.R 1910.1000 Table Z-1-A. SBBRS. 1997. Mechanical Ventilation. State Board of Building Regulations and Standards. Code of Massachusetts Regulations. 780 CMR 1209.0 10

Figure 1 Unit Ventilator (Univent) Mixed Air Air Diffuser Outdoors Indoors Fan Heating/Cooling Coil Air Mixing Plenum Filter Outdoor Air Return Air Air Flow Control Louvers Air Flow = Fresh Air/Return Air = Mixed Air 11

Picture 1 Original System Retrofitted Fan Coil Unit Fan Coil Unit Retrofitted into Original Heating System

Picture 2 Interior Exhaust Vent Grille Outdoor Exhaust Vent Grille Passive Exhaust Ventilation System in Second Floor Rooms

Picture 3 Passive Vent in Hallway Door MCJTC Classroom

Picture 4 Univent in Wooden Casing

Picture 5 Insulated pipes in Wooden Univent Cabinet, Note Stains/Possible Mold Growth

Picture 6 Paper of Pipe Insulation, Note Possible Mold Colonies

Picture 7 Rust Possible Mold Colonization of Insulation, Note Rusted Exposed Pipe That Indicates Possible Condensation Production

Picture 8 Drip Pans in Univent with Accumulated Debris

TABLE 1 Indoor Air Test Results Massachusetts Criminal Justice Training Council at the Boylston Town Offices Building Boylston, MA March 14, 2000 Remarks Carbon Temp. Relative Occupants Windows Ventilation Remarks Dioxide F Humidity in Room Openable Intake Exhaust *ppm % Outside 367 43 36 (Background) Academy Director s 654 73 12 3 yes yes yes supply off Office 1BTO207 1625 74 19 19 yes yes yes supply off 1BTO201 2000+ 77 20 44 yes yes yes supply off, window open, ceiling fans Sgt. Rufo s Office 715 73 11 1 yes yes yes photocopier odor Comfort Guidelines Carbon Dioxide - < 600 ppm = preferred 600-800 ppm = acceptable > 800 ppm = indicative of ventilation problems Temperature - 70-78 F Relative Humidity - 40-60% * ppm = parts per million parts of air CT = water-damaged ceiling tiles