+ - A + B B - V + - NO NC COM + - + - V + - PV PV
Ramp Soak 100 70 50 30 3 5 3 8 5 3 Minute Steam Heating Sensor Cooling Water PID
Hotplate
Specifications Input power supply AC 100 to 240V, 50/60Hz, DC 24V ±10% Display method LCD. Present Value: red, Set Value: green Thermocouple: K, J, T, E, N, R, S, B, L, U, TXK Input sensors Platinum RTD: Pt100, JPt100 Analog input: 0 to 5 V, 0 to 10 V, 0 to 20 ma, 4 to 20 ma, 0 to 50 mv Control modes PID, PID programmable, FUZZY, Self-tuning, manual, ON/OFF Display accuracy 0 or 1 digit to the right of the decimal point Sampling rate Analog input: 0.1s, Thermocouple or platinum RTD: 0.1s Ambient temperature 0 ~ +50 Ambient humidity 35 to 80% RH (non-condensing) Alarm Outputs The DT3 offers 3 alarm outputs, and each alarm output has 18 alarm modes to choose from in the initial setting mode. When the target temperature exceeds or falls below the set point, the alarm output is enabled. SV 0 1 2 3 4 5 6 7 8 9 11 12 13 14 15 16 17 18 19 Alarm function disabled Alarm Mode Deviation upper- and lower-limit: This alarm output operates when PV value is higher than the set value SV + (AL - H) or lower than the set value SV - (AL - L). Deviation upper-limit: This alarm output operates when PV value is higher than the set value SV + (AL - H). Deviation lower-limit: This alarm output operates when PV value is lower than the set value SV - (AL - L). Absolute value upper- and lower-limit: This alarm output operates when PV value is higher than the set value AL-H or lower than the set value AL - L. Absolute value upper-limit: This alarm output operates when PV value is higher than the set value AL - H. Absolute value lower-limit: This alarm output operates when PV value is lower than the set value AL - L. Hysteresis upper-limit alarm output: This alarm output operates if PV value is higher than the set value SV + (AL - H). This alarm output is OFF when PV value is lower than the set value SV + (AL - L). Hysteresis lower-limit alarm output: This alarm output operates if PV value is lower than the set value SV - (AL - H). This alarm output is OFF when PV value is higher than the set value SV - (AL - L). Disconnection Alarm: This alarm output operates if the sensor connection is incorrect or has been disconnected. CT1 Alarm: CT1 is ON if the value of CT1 is lower than the value of AL - L or higher than AL - H. CT2 Alarm: CT2 is ON if the value of CT2 is lower than the value of AL - L or higher than AL - H. When SOAK status (temperature hold) happens to PID program control, alarm output is ON. When RAMP UP status happens to PID program control, alarm output is ON. When RAMP DOWN status happens to PID program control, alarm output is ON. When RUN status happens to PID program control, alarm output is ON. When HOLD status happens to PID program control, alarm output is ON. When STOP status happens to PID program control, alarm output is ON. When END status happens to PID program control, alarm output is ON. Alarm Output Operation ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF SV - (AL - L) SV AL - L AL - L AL - H AL - L AL - L SV SV - (AL - L) SV AL - L SV + (AL - H) SV + (AL - H) AL - H AL - H AL - H AL - H 5
RS-485 Communication DT3 supports baudrate 2,400 to 38,400 bps, MODBUS ASCII/RTU protocol, function code 03H and reads maximum 8 words from the register. Address 1000H 1001H 1002H 1003H 1005H 1006H 1007H 1008H 1009H 100AH 100BH 1012H 1013H 1016H 102AH 102BH 102CH 102DH 103BH 103CH Present value (PV) Set value (SV) Upper limit of temp. range Lower limit of temp. range Control mode Heating/ Cooling control st 1 Heating/ Cooling control cycle nd 2 Heating/ Cooling control cycle Proportional band (PB) Ti value Td value Read/write Output 1 volume Read/write Output 2 volume Regulated temp. value Read/write LED status Read/write key status Panel lockup status CT value AT setting Content Control RUN/STOP setting Measuring unit: 0.1 scale. The following values read mean error occurs. 8002H: Temperature not yet acquired 8003H: Not connected to sensor 8004H: Incorrect sensor Measuring unit: 0.1 scale Cannot exceed the default value Cannot fall below the default value 0: PID, 1: ON/OFF, 2: Manual, 3: FUZZY 0: Heating/ Heating, 1: Cooling/ Heating, 2: Heating/ Cooling, 3: Cooling/ Cooling 0.1 ~ 99 sec. 0.1 ~ 99 sec. 0.1 ~ 999.9 0 ~ 9999 0 ~ 9999 Unit: 0.1%, only valid in manual control mode Unit: 0.1%, only valid in manual control mode -99.9 ~ +99.9, Unit: 0.1 b0: ALM3, b1: ALM2, b2: F, b3: C, b4: ALM1, b5: OUT2, b6: OUT1, b7:at b0: Set, b1: Select, b2: Up, b3: Down, 0: it 0: Normal, 1: Fully locked, 11: SV adjustable Unit: 0.1A 0: OFF(default), 1: ON Definition 0: STOP, 1: RUN (default), 2: END (program), 3: HOLD (program) 6
Parameters Operation Regulation Mode SET for less than 3 sec. SET Operation Mode SET for more than 3 sec. SET Initial Setting Mode Regulation Mode Operation Mode Initial Setting Mode Auto-tuning (when CTRL set in PID or FUZZY and in RUN mode) Self-tuning switch (set when in PID control and the TUNE parameter = ST) Select the nth (n = 0 ~ 5) PID. When n = 6, PID is autoselected. Set up PID control offset Set up start step (when in programmable control) Set up FUZZY gain value Set up the position of decimal point Set up FUZZY Deadband Lock the keys Adjust Output 1 hysteresis (when in ON/OFF control) Use to set up target temperature Control loop RUN or STOP Set up start pattern (when in PID programmable control and ) Set up upper limit of Alarm 1 Set up input type Set up temperature unit (not displayed when in analog input) Set up upper temperature limit Set up lower temperature limit Select control modes Select SV control modes Set up waiting temperature (when in programmable control) Adjust Output 2 hysteresis (when in ON/OFF control) Control cycle for Output 1 (except in ON/OFF control) Control cycle for Output 2 (except in ON/OFF control) Ratio of Output 1 against Output 2 when in dual output control (set when in PID and dual output control) Set up deadband (when in dual output) Set up lower limit of Alarm 1 Set up upper limit of Alarm 2 Set up lower limit of Alarm 2 Set up upper limit of Alarm 3 Set up lower limit of Alarm 3 Set up waiting time (when in programmable control) Set up start slope (when in programmable control) Select pattern to be edited Select AT or ST Select heating, cooling or dual output heating and cooling Set up input filter factor Record highest temperature of Alarm 1 Set up input filter range Record lowest temperature of Alarm 1 Adjust input compensation Record highest temperature of Alarm 2 Adjust input gain Record lowest temperature of Alarm 2 Set up rising slope (when CRTS = SLOP) Record highest temperature of Alarm 3 Set up reverse alarm output Set up Remote type Set up Alarm 1 mode Set up Alarm 1 options Set up Alarm 1 delay Adjust upper limit compensation for analog Output 1* Record lowest temperature of Alarm 3 Select auxiliary function 7
Regulation Mode Operation Mode Initial Setting Mode Adjust lower limit compensation for analog Output 1* Adjust upper limit compensation for analog Output 2* Adjust lower limit compensation for analog Output 2* Adjust upper limit compensation for Retransmission* Adjust lower limit compensation for Retransmission* Adjust Remote gain Adjust Remote compensation Set up EVENT1 function Set up EVENT2 function Display and adjust Output 1 volume Display and adjust Output 2 volume Set up upper limit percentage for Output 1 Set up lower limit percentage for Output 1 Set up upper limit percentage for Output 2 Set up lower limit percentage for Output 2 CT1 CT2 Display current measured at Display current measured at Enable/disable communication write-in Select ASCII or RTU format Set up communication address Set up baudrate Set up data length Set up stop bit Set up parity bit Set up EVENT3 function to return to auto-tuning to return to set up target temperature to return to set up input type *1 scale = 1μA; 1 scale = 1mV PID mode: Any of the 6 PID groups can be selected. When n = 6, the program will automatically select the PID group that is the closest to the target temperature. Select the nth PID (n = 0 ~ 5) Set up the 0 PID temperature value Set up the 0 th proportional band value th Set up the 0 Ti value th Set up the 5 PID temperature value Set up the 5 th proportional band value th Set up the 5 Ti value th th Set up the 0 Td value th Set up the 5 Td value th 0 ~ 5 PID Set up the 0 PID integral deviation th to return to PID deviation Set up the 5 PID integral deviation th to return to PID deviation Patterns and steps: Edit in parameter. Take editing pattern 0 for example: Select the pattern number to be edited Select number to select OFF Exit pattern and step editing and switch to to continue the setup process Edit temperature for Step 0 Select actual number of steps when the program is executing Edit time for Step 0 (time unit: hr, min) Set up Step 0 ~ 15 in order Edit temperature for Step 15 Edit time for Step 15 to set up actual step numbers Set up additional cycles (0 ~ 99) for the pattern execution Set up link pattern. OFF refers to the program end. to return to select the pattern number to be edited 8
Parameters Operation Regulation Mode SET for less than 3 sec. SET Operation Mode SET for more than 3 sec. SET Initial Setting Mode Regulation Mode Operation Mode Initial Setting Mode Auto - tuning ( when in PID control and RUN mode ) Use temperature to set up target Set up input type Set proportion band Control loop RUN or STOP Set up temperature unit Set integration time Set up the position of decimal point Set up upper temperature limit Set derivative time Lock the keys Set up lower temperature limit Set up PID control offset Set up upper limit of Alarm 1 Select control modes Adjust Output 1 hysteresis (when in ON / OFF control) Set up lower limit of Alarm 1 Select heating, cooling or dual output heating and cooling Adjust Output 2 hysteresis (when in ON / OFF control) OUT1 HEAT: Heating control cycle for Output 1 (when Ctrl = PID/FUZZY/MANUAL) Set up upper limit of Alarm 2 Set up Alarm 1 mode Set up lower limit of Alarm 2 Set up Alarm 1 options *3 OUT1 COOL: Cooling control cycle for Output 1 (when Ctrl = PID/FUZZY/MANUAL) OUT2 HEAT: Heating control cycle for Output 2 (when Ctrl = PID/FUZZY/MANUAL) OUT2 COOL: Cooling control cycle for Output 2 (when Ctrl = PID/FUZZY/MANUAL) Ratio of Output 1 against Output 2 when in dual output control (set when in PID control) Set up deadband Set up input filter factor Set up input filter range Adjust input compensation *1 Adjust input gain *1 Adjust upper limit compensation for analog Output 1 *2 Display and adjust Output 1 volume Display and adjust Output 2 volume Set up upper limit percentage for Output 1 Set up lower limit percentage for Output 1 Set up upper limit percentage for Output 2 Set up lower limit percentage for Output 2 Set up Alarm 1 delay *4 Set up Alarm 2 mode Set up Alarm 2 options *3 Set up Alarm 2 delay *4 Adjust lower limit compensation for analog Output 1 *2 to return to auto-tuning to return to set up target temperature to return to set up input type 11
* Alarm 1 is automatically switched to output control 2 when selecting dual output mode * Set up upper / lower limit percentage for output 1 / 2 volume : set output permission ranges. E.g. upper and lower limit percentage are respectively set as 90 and 20, output volume will be limited to 20% ~ 90%. *1. Offset Present value : Use and. Present value = measured value x (1 + /1.000) +. *2. 1 scale = 1μA *3. Set up alarm standby : set corresponding Y value as xxxy (Y = 0 : normal / Y = 1 : standby) Set up reverse alarm output : set corresponding Y value as xxyx (Y = 0 : forward / Y = 1 : backward) Set up Hold output : set corresponding Y value as xyxx (Y = 0 : normal / Y = 1 : Hold) *4. Set up alarm delay : The alarm operates after reaching alarm delay time (recalculating time if discontinuity occurs in the process) Temperature Sensors and Temperature Range Input sensors Display Temperature Range Input sensors Display Temperature Range Platinum RTD: Pt100-200 ~ 850 C Thermocouple E 0 ~ 600 C Platinum RTD: JPt100-100 ~ 400 C Thermocouple T -200 ~ 400 C Copper resistance: Cu50-50 ~ 150 C Thermocouple J -100 ~ 850 C RTD Ni120-80~300 C Thermocouple K -200 ~ 1,300 C Thermocouple B 100 ~ 1,800 C Thermocouple L -200 ~ 850 C Thermocouple S 0 ~ 1,700 C Thermocouple U -200 ~ 500 C Thermocouple R 0 ~ 1,700 C Thermocouple Txk -200 ~ 800 C Thermocouple N -200 ~ 1,300 C Panel Sizes Terminal Wiring Diagram Models Sizes (W H) 4848 45mm 45mm 4896 44.5mm 91.5mm 7272 68mm 68mm 1 2 3 4 5 6 L AC 100~240V 50/60 Hz 5VA N 3A 250 Vac COM ALM1 RTD + + OUT Tc - - 7 8 9 10 11 12 12
Dimensions 4824 4896 44.75 mm 44.0 mm 24.0 mm 21.85 mm 48.0 mm 3.4 mm 99.8 mm 95.7 mm 98.2 mm 91.0 mm SET 48.0 mm 12.8 mm 79.2 mm 4848 7272 48.0 mm 48.0 mm 9.5 mm 80.0 mm 44.75 mm 72.0 mm 74.0 mm 67.80 mm 72.0 mm 13.80 mm 79.20 mm 21
9648 9696 91.0 SET 48.0 44.0 96.0 mm 98.0 mm 90.8 mm UGV DTA9648 96.0 12.3 79.2 96.0 mm 15.8 mm 79.2 mm DTC DTE.900 22
Industrial Automation Headquarters Delta Electronics, Inc. Taoyuan Technology Center 18 Xinglong Road, Taoyuan District, Taoyuan City 33068, Taiwan (R.O.C.) TEL: 886-3-362-6301 / FAX: 886-3-371-6301 Asia Delta Electronics (Jiangsu) Ltd. Wujiang Plant 3 1688 Jiangxing East Road, Wujiang Economic Development Zone Wujiang City, Jiang Su Province, P.R.C. 215200 TEL: 86-512-6340-3008 / FAX: 86-769-6340-7290 Delta Greentech (China) Co., Ltd. 238 Min-Xia Road, Pudong District, ShangHai, P.R.C. 201209 TEL: 86-21-58635678 / FAX: 86-21-58630003 Delta Electronics (Japan), Inc. Tokyo Office 2-1-14 Minato-ku Shibadaimon, Tokyo 105-0012, Japan TEL: 81-3-5733-1111 / FAX: 81-3-5733-1211 Delta Electronics (Korea), Inc. 1511, Byucksan Digital Valley 6-cha, Gasan-dong, Geumcheon-gu, Seoul, Korea, 153-704 TEL: 82-2-515-5303 / FAX: 82-2-515-5302 Delta Electronics Int l (S) Pte Ltd. 4 Kaki Bukit Ave 1, #05-05, Singapore 417939 TEL: 65-6747-5155 / FAX: 65-6744-9228 Delta Electronics (India) Pvt. Ltd. Plot No 43 Sector 35, HSIIDC Gurgaon, PIN 122001, Haryana, India TEL : 91-124-4874900 / FAX : 91-124-4874945 Americas Delta Products Corporation (USA) Raleigh Office P.O. Box 12173,5101 Davis Drive, Research Triangle Park, NC 27709, U.S.A. TEL: 1-919-767-3800 / FAX: 1-919-767-8080 Delta Greentech (Brasil) S.A. Sao Paulo Office Rua Itapeva, 26-3 andar Edificio Itapeva One-Bela Vista 01332-000-São Paulo-SP-Brazil TEL: 55 11 3568-3855 / FAX: 55 11 3568-3865 Europe Deltronics (The Netherlands) B.V. Eindhoven Office De Witbogt 20, 5652 AG Eindhoven, The Netherlands TEL: 31-40-2592850 / FAX: 31-40-2592851 *We reserve the right to change the information in this catalogue without prior notice. DELTA_IA-SS_DT_C_EN_20150204