AGING CHARACTERISTICS OF NUCLEAR PLANT RTDS AND PRESSURE TRANSMITTERS



Similar documents
Fundamentals of Mass Flow Control

Practical Application of Industrial Fiber Optic Sensing Systems

UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF NUCLEAR REACTOR REGULATION WASHINGTON, D.C June 1, 2005

Load Cell Troubleshooting

Subminiature Load Cell Model 8417

Environment-Laboratory Ambient Conditions

No. : EX##-OMF0004 OPERATION MANUAL. SI unit EX12#-SMB1

Calibrating DC Shunts: Techniques and Uncertainties

Application Note 142 August New Linear Regulators Solve Old Problems AN142-1

SELECTING PRESSURE TRANSMITTERS TO IMPROVE CENTRIFUGAL COMPRESSOR SAFETY & EFFICIENCY

ELECTRIC HEATER COMPANY Operating and Maintenance Manual For Immersion Heating Elements

The following document contains information on Cypress products.

Nuclear Safety Council Instruction number IS- 23 on in-service inspection at nuclear power plants

4.0 TECHNICAL REFERENCE FOR MONITORING EQUIPMENT AND INSTRUMENTS

SDX Submersible Depth Transmitter User Manual

Basic RTD Measurements. Basics of Resistance Temperature Detectors

SECTION 13. Multipliers. Outline of Multiplier Design Process:

Models SFP33 & SFP32 Pressure Transmitters

ENERGY TRANSFER SYSTEMS AND THEIR DYNAMIC ANALYSIS

Bearing Failure: Causes and Cures

NEW SIX-SEALS CUTTING RING. INTERNATIONAL INDUSTRIAL PATENT Nr of the 10/03/99 FLANKS AND DOES NOT REPLACE THE STANDARD RING CURRENTLY IN USE

THE STRAIN GAGE PRESSURE TRANSDUCER

A discussion of condensate removal systems for clarifier and thickener drives for water and wastewater facilities.

MRF175GU MRF175GV The RF MOSFET Line 200/150W, 500MHz, 28V

16. Industrial Platinum Resistance Thermometers

Improving regulatory practices through the OECD-NEA Stress Corrosion Cracking and Cable Ageing Project (SCAP)

Select the Right Relief Valve - Part 1 Saeid Rahimi

North American Stainless

North American Stainless

LEAD CRYSTAL. User Manual. Valve-regulated lead-crystal batteries Energy storage Cells

High Voltage Power Supplies for Analytical Instrumentation

Temperature Accuracy of Thermistors and RTDs Application Notes

North American Stainless

PRODUCT / APPLICATION INFORMATION

Outages Happen 24/7 So Should Monitoring / SAFEGUARD YOUR HIGH VOLTAGE ASSETS WITH VAISALA ONLINE MONITORING

Selecting Sensors for Safety Instrumented Systems per IEC (ISA )

Flowserve - Edward Valves Quick Closing Isolation Valves -The Equiwedge Alternative

A Practical Overview of Level Measurement Technologies

Solid-State Relays (SSRs) vs Electromechanical Relays (EMRs)

Compliant Terminal Technology Summary Test Report

Best Practices for Reducing Transmitter Life Cycle Costs

Signal Manager Installation and Operation Manual

ATI 2205 ATI Technical Data Sheet. Duplex Stainless Steel GENERAL PROPERTIES. (UNS S31803 and S32205)

Crimp Tooling Where Form Meets Function

UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF NUCLEAR REACTOR REGULATION WASHINGTON, DC June 16, 2011

Government Degree on the Safety of Nuclear Power Plants 717/2013

V K Raina. Reactor Group, BARC

Simulation Technology to Support the Design of Electric Distribution and Control Devices

Solar Powered Wireless Sensors & Instrumentation: Energy Harvesting Technology Reduces Operating Cost at Remote Sites

Technical Info Sheet. Ionic contamination testing in a no-clean soldering process. Scope

DMP 331. Industrial Pressure Transmitter for Low Pressure. Stainless Steel Sensor

Cable Discharge Event

SAMPLE CHAPTERS UNESCO EOLSS

BLUE RIBBON CORP. BC001 Birdcage Installation Manual

REGULATORY GUIDE OFFICE OF NUCLEAR REGULATORY RESEARCH. REGULATORY GUIDE 8.4 (Draft was issued as DG-8036, dated April 2010)

جامعة البلقاء التطبيقية

EASIDEW PORTABLE HYGROMETER INSTALLATION, OPERATION AND MAINTENANCE MANUAL

Linear Heat Series. Fiber Optic Linear Heat Detection System. Tunnels & Metros. Conveyer Belts. Parking Lots. Manufacturing Warehouse Facilities

Reliability of Air Moving Fans, and Their Impact on System Reliability. A White Paper from the Experts in Business-Critical Continuity TM

Series 510 Submersible Level Transmitters

A Study of Durability Analysis Methodology for Engine Valve Considering Head Thermal Deformation and Dynamic Behavior

Michael Montgomery Marketing Product Manager Rosemount Inc. Russ Evans Manager of Engineering and Design Rosemount Inc.

IAEA-TECDOC-1402 Management of life cycle and ageing at nuclear power plants: Improved I&C maintenance

Errors Related to Cable Resistance Imbalance in Three Wire RTDs

Assembly and Installation Procedures

DC MOTOR ANALYSIS & TROUBLESHOOTING

Section 3. Sensor to ADC Design Example

The soot and scale problems

Oil and Coolant Circulating Heating System. Model - OCSM

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013

RESULTS OF ICARUS 9 EXPERIMENTS RUN AT IMRA EUROPE

Telemetry system for cathodic protection equipment of underground metal pipelines

Heat Exchanger Thin Film Foul Release Applications Corrosion Resistant Protective Coatings Grit Blast Surface Prep of Tubular Equipment

APPENDIX CC NUCLEAR WASTE STORAGE

TECHNICAL DATASHEET #TD1404AX PWM CONTROLLED SOLENOID DRIVER

1.5A Very L.D.O Voltage Regulator LM29150/29151/29152

Failure Modes, Effects and Diagnostic Analysis

TRANSPORT OF DANGEROUS GOODS

The accelerometer designed and realized so far is intended for an. aerospace application. Detailed testing and analysis needs to be

Interactive Logging with FlukeView Forms

High-ohmic/high-voltage resistors

E. K. A. ADVANCED PHYSICS LABORATORY PHYSICS 3081, 4051 NUCLEAR MAGNETIC RESONANCE

User checks and maintenance of laboratory balances

LM134-LM234-LM334. Three terminal adjustable current sources. Features. Description

ALARMLINE ANALOGUE Linear Heat Detection System

National Building Code of Canada 2010

Waters Corporation. Waters 2690/5 USER & TROUBLESHOOTING GUIDE

SLLP G PRODUCT DATASHEET. RoHS Compliant

Application Note. So You Need to Measure Some Inductors?

Engineering & Testing Services. Hydraulic Fitting Design and Hydro-Mechanical Testing

AC-DC Converter Application Guidelines

GENERAL PROPERTIES //////////////////////////////////////////////////////

Nuclear Power Plant Electrical Power Supply System Requirements

Role of Sockets in IC Product Life Cycle Ila Pal, Ironwood Electronics

Series AMEPR30-AZ up to 2.5A AC-DC / DC-DC LED Driver / Converter

Rosemount 333 HART Tri-Loop

CPCI-3U-AC-300W-R. Rugged 300W AC Input 3U CompactPCI Power Supply. Electrical Specification for: Telkoor Part Number:

Reliability Accuracy Performance

CONTRACT SPECIFICATIONS - SEISMIC ISOLATION BEARINGS

Estimating Weighing Uncertainty From Balance Data Sheet Specifications

Transcription:

0 THE 4TH INTERNATIONAL TOPICAL MEETING ON NUCLEAR THERMAL HYDRAULICS, OPERATIONS AND SAFETY April 68,1994, Taipei, Taiwan XA04NO629 AGING CHARACTERISTICS OF NUCLEAR PLANT RTDS AND PRESSURE TRANSMITTERS H. M. Hashemian Analysis and Measurement Services Corporation AMS 91 Cross Park Drive Knoxville, Tennessee 37923 USA Phone: 615) 691-1796 Fax: 615) 691-9344 ABSTRACT time testing and calibration performed once every fuel cycle is adequate for management of aging of the Resistance Temperature Detectors (RTDs) and safety-related RTDs and pressure transmitters in nuclear pressure, level, and flow transmitters provide almost all power plants. the vital signals that are used for the control and safety of nuclear power plants. Therefore, it is crucial to II. AGING CHARACTERISTICS OF RTDs ensure that the performance of these sensors remain acceptable as they age in the process under normal A. Definition of Performance operating conditions. The performance of an RTD is characterized by its Four comprehensive research projects were conducted accuracy and response time. Accuracy is a measure of for the U.S. Nuclear Regulatory Commission (NRC) to how well the RTD may indicate a static temperature and evaluate the effects of normal aging on calibration response time defines how quickly the RTD may detect stability and response time of RTI)s and pressure a temperature change. The accuracy and response transmitters of the types used for safety-related time of RTQs are generally independent. measurements in nuclear power plants. Each project was conducted over a three year period. The projects The deterioration of accuracy is called calibration involved laboratory testing of representative RTDs and drift or calibration shift and the deterioration of pressure transmitters aged in simulated reactor response time is called response time degradation. conditions. The main purpose of these projects was to Accuracy can be restored by recalibration if the RTD is establish the degradation rate of the sensors and use stable, but response time is an intrinsic characteristic the information to determine if the current testing that cannot be altered once the RTD is manufactured. intervals practiced by the nuclear power industry are In the case of thermowell-mounted RTDs, however, adequate for management of aging of the sensors. The response time degradation due to movements of the results have indicated that the current nuclear industry RTD in its thermowell can sometimes be reversed. practice of testing the response time and calibration of the sensors once every fuel cycle is adequate. B. Definition of Aging 1. INTRODUCTION The term "aging" used in this paper refers to decalibration or response time degradation of RTDs This paper presents the key results of four with time in normal environments and under normal experimental research projects conducted for the NRC operating conditions in the primary coolant system of on aging of safety system RTDs and pressure Pressurized Water Reactors (PWRs). transmitters in nuclear power plants. Each project was conducted in two phases; a Phase I feasibility study The definition of aging mentioned above is based followed by a comprehensive research and on the NRC's definition of aging, which is the development effort in Phase 11. The results of these cumulative degradation that occurs with the passage of projects have reports. (1,2,3,4) been published in four NRC time in a component, system, or structure which can, if unchecked, lead to loss of function and impairment of safety." Since the performance of RTDs is tested The overall purpose of these projects has been to periodically, the degradation does not accumulate. determine if the current nuclear practice of response Therefore, the word cumulative was deleted in our 32-C-1

definition. Furthermore, we concentrated on the aging that occurs in an 18 month period, the length of a typical PWR fuel cycle and the period of time between periodic response time and cross calibration tests currently performed in nuclear power plants. insulation resistance is normally high compared to that of the sensing element and has a negligible effect on resistance measurement. However, with moisture, the insulation resistance decreases and causes the RTD to indicate a lower temperature than normal. C. Effects of Aging on Performance 2. Effects of Aging on Response Time. Response time degradation results from changes in the Normal aging of RTDs occurs from long-term heat transfer properties of the insulation material. Gaps exposure to any combination of heat, humidity, and cracks which may develop in the insulation vibration, temperature cycling, and mechanical shock. materials from long-term exposure to high temperature, Nuclear radiation can also affect RTID performance, but vibration, and temperature cycling are detrimental to this was not studied to limit the project scope and dynamic performance. If moisture enters the RTID, the concentrate on aging effects that are believed to be response time may decrease at the cost of a calibration more important. Since primary coolant RTIDs are shift. Although improvement in response time with age remote from the reactor ore, they are normally is possible, an RTID whose response time continues to unaffected by nuclear radiation except for gamma decrease with age could be suffering from degradation which may cause degradation in the insulation and of insulation resistance. other RTID materials. Another major cause of response time degradation 1. Effects of Aging on Calibration. A significant in nuclear plant RTDs is changes that can occur in the calibration shift should not occur in an RTID as long as RTID/thermowell interface in thermowell-mounted RTIDs. the sensing element is not stressed or contaminated Experience has shown that air gaps in the after calibration and the insulation material is kept in RTD/thermowell interface play a major role in controlling place and dry. Any new stress, contamination, or the overall response time of the RTID. Changes of as metallurgical changes in the sensing element, or little as a few hundredths of a millimeter in the size of moisture in the insulation material can cause a the air gap caused by vibration, shock, and other calibration shift. mechanical effects during plant operation, installation, handling, or dimensional tolerances will change the Stress results from any combination of heat, response time significantly. vibration, temperature cycling, and mechanical shock. The effect of temperature is the most important. This is D. Aging Test Results because the RTD materials have different thermal expansion coefficients causing the element to The first step in performing the RTD aging project experience stress whenever the temperature changes. was to construct a laboratory with calibration and aging The resistance of the sensing element increases with equipment and to obtain nuclear grade RTDs. The tension stresses and decreases with compression project was started with W-one nuclear grade and stresses. For small temperature variations, the stress seventeen commercial grade RTDs. The commercial reverses itself but for large ones, the effect is not grade RTDs were included for comparison purposes. reversible except by annealing. Chemical Of the fifty-one nuclear grade RTDs, twenty-one were contamination and oxidation of the sensing element dual element providing a total of seventy-two results from long-term exposure to high temperatures. independent RTD elements. These RTDs were used in To avoid oxidation, RTDs may be built with a reducing one or more of the five aging categories: thermal aging, atmosphere in the sheath. However, this leads to vibration aging, humidity aging, thermal cycling, and contamination due to migration of metal ions from the high temperature testing. The project focussed on the sheath to the sensing element at temperatures above effects of aging on RTID calibration more so than RTD 5000C. response time. As such, the results presented here concentrate on the effects of aging on calibration. Metallurgical changes such as grain growth occur at temperatures above 4200C. Cold working (or work Next, a computer-based automatic calibration and hardening) results from vibration and mechanical shock monitoring system and procedure were developed. The and can be eliminated by annealing, which requires RTDs were calibrated and placed in two furnaces at heating the RTD above 4000C. approximately 3200C, the primary coolant temperature in most PWRs. The RTDs were monitored in the The insulation resistance of an RTD decreases as furnaces using a computer scanning system which moisture enters the sheath. The electrical resistance of measured and stored their loop resistance, insulation an RTID is a parallel combination of two resistances: the resistance, open circuit voltage, and lead wire sensing element and the insulation resistance. The resistance. These measurements helped identify and 32-C-2

characterize the failures when they occurred. Once results are summarized in Figure 2 along with the every one or two months, the RTI)s were removed from duration of each test. the furnaces and calibrated to quantify any drift. The thermal aging process was continued for 18 months, equivalent to a typical PWR fuel cycle. Of thirty RTID 0.12- elements tested for thermal aging, two failed, six showed drift in the range of 06 to 3.OOC, but the 0.10- remaining twenty-two drifted less than 0.20C over the entire thermal aging period. The average positive and 3 U8- negative drift of the unfailed RTDs as a function of )CD calibration interval is given in Figure 1. Each calibration 2 C? 0.06- interval corresponds to one to two months. The results :9 show that after an apparent burn-in period which lasted until the fifth calibration or approximately nine months 0.04- into the aging process, the RTDs stabilized in a drift 0;02- band of 0.20C. Note that the results are presented in terms of an average drift band rather than a drift rate because the calibration changes as a function of time 000- THERMAL VIBRATION HUMIDITY HIGH TEMP CYCLING were random and not systematic and therefore, a drift 181vionths 2 Months 2 Months 3 Days 100 Cycles rate could not be calculated. Figure 2 Summary of Aging Test esults for RTDs In addition, a number of RTDs removed from CL4- operating nuclear power plants after 2 to years of 3 0.3. Y) service were tested to determine the drift of naturally a) 02-2C' aged RTDs. The drift results for these RTDs were 0.1 Q - mostly within : 0.211C which is consistent with the Z9 0- laboratory aging test results. _0Z _03- E. Testing Intervals and Replacement Schedules -0.4- The current industry practice for verifying -0.5 i; i it ii io it 12 adequate RTD accuracy and response time is to Calibration Interval perform on-line cross calibration and response time - Positive Drift Negative Drift testing at least once every fuel cycle. In light of the results generated in the aging project discussed here and elsewhere, this practice is reasonable unless there are plant'specific problems requiring more frequent Figure 1. Average Drift of the Test RTDs as a Function testing or the RTDs are suspected of deficiencies in of Time in the Aging Furnace design, fabrication, or installation. For example, in one plant, a small margin between the required response time and the nominal response time of primary coolant The RTDs were then stored at room temperature, RTDs, in addition to a history of response time pressure, and humidity, and periodically tested for shelf- problems due to degradation of a thermal compound life drift. The results showed that the RTDs are not used in the thermowell, required periodic response time immune to degradation during storage. This problem testing to be performed once every one or two months. can be resolved by recalibrating the RTDs shortly before they are installed in the plant. F. Conclusions on Aging of RTDs The aging of the RTDs; was continued to identify The calibration and response time of RTDs are the effects of vibration and mechanical shock, humidity, adversely affected by aging even at normal operating high temperature, and thermal cycling. These effects conditions. However, the aging is manageable by could not be combined and were performed individually periodic tests performed once every fuel cycle. on a group of RTDs at a time. These tests resulted in three more failures, but did not increase the average If an RTD has been in storage for more than two drift of the RTDs beyond that of thermal aging. The years, it should be recalibrated before it is installed in 32-C-3

the plant. The same argument applies to RTDs that 0 Friction in mechanical linkages due to corrosion have been inactive such as those installed in a non- can cause response time degradation and may operating plant for a period of more than two years. also affect the transmitter calibration. The stability of these RTDs may be improved if they are first annealed and then calibrated. 0 Failure of seals: Seals can harden or crack allowing moisture to leak Into the transmitters. The drift of nuclear grade RTDs was found to generally lie in a 0.20C band. A drift band is used 0 Loosening of mechanical components in instead of a drift rate because the drift of RTDs does force-balance transmitters due to pressure not occur in a monotonic fashion to provide a unique fluctuations, surges, and mechanical vibration can value for calibration changes as a function of time. result in calibration and response time problems. Ill. AGING CHARACTERISTICS OF PRESSURE 0 Blockages in capillary tubes and other TRANSMITTERS passageways restricting the flow of fill fluid in oil filled systems. Aging degradation may occur in a pressure transmitter when the material in the transmitter is 2. Aging Effects on Electronics. The electronic exposed to a stress for a period of time. Typical aging components of pressure transmitters include numerous mechanisms that can cause a material's mechanical resistors, capacitors, diodes, and integrated circuits that strength or physical properties to degrade include are used for signal conversion, signal conditioning, and thermal, mechanical, or electrical fatigue, wear, linearization of the transmitter's output. In some corrosion, erosion, embrittlernent, diffusion, chemical transmitters, 0 to 20 resistors are used to maintain the reaction, cracking or fracture, surface contamination, linearity of the transmitter output in addition to resistors etc. These degradations may result from exposure to and capacitors to control the transmitter "zero" and any combination of the following stressors: heat, "span." Almost all of these components are affected by humidity, vibration, radiation, mechanical shock, thermal long-term exposure to temperature, humidity and shock, temperature cycling, pressure cycling, testing, radiation. Any significant change in the value of the electromagnetic interferences, etc. electronic components can cause calibration shifts and A. Effects of Aging on Calibration and in some cases response time changes. Response Time B. Aging Test Results The stresses experienced by nuclear plant The eff ects of normal aging on the performance of pressure transmitters during a long period of normal representative nuclear plant pressure transmitters were plant operation can cause performance degradation in studied in a series of laboratory measurements. The the mechanical and electronic components of the transmitters were first calibrated and response time transmitter and result in steady-state (calibration) and tested, then aged in simulated plant conditions for up dynamic (response time) performance problems. to one year. Following this aging, the calibration and Examples of potential effects of some of the most response time tests were repeated and the results were dominant stressors are discussed below. compared with the original unaged test results to 1. Aging Effects on Mechanical Components. determine if significant changes or failures had Some examples of the mechanical components of occurred due to the aging. The results of the aging pressure transmitters susceptible to aging degradation tests are presented here in terms of aging effects on during normal operation include the following: complete transmitter assemblies. Permanent deformation of sensing elements due The project involved fifty-seven pressure to pressure surges during reactor trips and transmitters representing five manufacturers. The aging maintenance. processes included heat and humidity levels corresponding to normal operating conditions of Failure of the bellows. nuclear power plants, heat and humidity simulating the extremes of normal conditions, normal vibration, Degradation or leakage of fill fluid: The fill fluid pressure cycling, and overpressurization. The aging (usually oil) in pressure transmitters can suffer tests conducted in this project were focused on degradation due to radiation and heat or may leak determining gross malfunctions more so than identifying out. small changes or verifying manufacturer's specifications. The goal was to determine if pressure Degradation of diaphragm due to work hardening. transmitters are resilient enough to justify the testing 32-C-4

frequencies of once every fuel cycle or every 18 to 24 The aging test results are summarized in Table months that are currently practiced by the nuclear in terms of the aging conditions, the aging periods and power industry. percentages of transmitters that were affected, not affected, or failed due to aging. The results in the last Since the project focused on determining gross six columns in Table were averaged as shown in the and unusual transmitter behavior, instead of presenting results section at the bottom of the table. The results the results in terms of numerical changes in zero, span, from the weighted average calculations of Table are and response time of the transmitters, the following shown in Figure 3. qualitative criteria were used to present the results. C. Conclusions on Aging of Pressure For the steady-state results, the transmitter Transmifters instabilities or their deviations from a reference transmitter or a normal value were categorized as The aging test results have shown that the "High", "Medium" and "Low" corresponding calibration and response time of pressure sensing respectively to gross malfunction or failure, systems in nuclear power plants are subject to degraded but acceptable performance, and readily degradation from normal aging, and must therefore be acceptable performance. tested periodically to ensure acceptable performance. The question is how often the transmitters should be For the response time results, the degradations tested or replaced. This question is addressed below. were categorized again as "High", "Medium", and "Low"corresponding respectively to more than 50 Testing Intervals. Typical nuclear industry percent increase in response time, 20 to 50 practices for the management of aging degradation of percent increase, or less than 20 percent pressure sensing systems are as follows: increase. The response times of nuclear plant 0 Calibrate all safety-related transmitters once every pressure transmitters are usually very small 30 to fuel cycle. 300 milliseconds). Therefore, increases of up to 50 percent may correspond to a very small 0 Response time test the transmitters in one or change in actual response time. In addition, the more safety-related channels once every fuel inherent repeatability problems with response time cycle. testing of pressure transmitters usually make it impractical to distinguish differences of less than 0 Blow down or purge the sensing lines as needed 20 percent for those transmitters which have a if there is any reason to believe that blockages are small response time. present. Table Summary of Aging Test Results for Pressure Transmitters Number of Aging Test Results Duration Aging Transmitters Aging Stressor (Month) CondItIons Involved Effect on Calibration Effect on Response Time Not Moderately Not Moderately Affected Affected Failed Affected Affected Failed 1. Normal Heat 6-12 11 O-F, 65% H 23 61% 35% 41/6 87% 4% 9% & Humidity 2. Extremes of 3 150oF, 90% RH 11 73% 18% 9% 64% 27% 9% Normal Heat Humidity 3. Vibration 2 3 mils at 20 Hz 7 0 100% 0 57% 43% 0 4. Pressure Cycling 2 50% of Span: 8 63% 37% 0 100% 0 0 1 OOK to 500K Cycles 5. Overpressurization 0.5 1 000 psi 8 75% 25/6 0 100% 0 0 6. Phase I Results see Reference 3 1 7 59% 2a% 18% 88% 12% 0 I Average Results of All Laboratory Aging Tests Performed In This Project Straight Average 55 40 4 3 Weighted Average 58 35 7 1 84 2 4 32-C-5

9D pressure, level, and flow transmitters experience some drift, less than percent actually drift out of tolerance requiring a new calibration. t4) With this information, it is reasonable to conclude that the current calibration 611 interval of once every fuel cycle is adequate for the management of the effects of aging on calibration of pressure transmitters. 16 30- Response Time Testing Intervals, According to the results presented in Table 1, aging produced less - CL degradation in the response times of pressure transmilifters than in their alibrations. The response 0- ra times of 84 percent of the transmitters tested in this study were unaffected by aging. Of the remaining 16 Calibration Changes percent that suffered response time degradation, only 90- about 4 percent failed from a response time standpoint Furthermore, the search of the LER and NPRDS.E - databases showed only a few cases of response time degradation except for the oil loss problem in some C(0 60- models of Rosemount transmitters. The results of the survey of the nuclear power industry indicated that 0 response time problems are not prevalent and pressure 30 transmitters are only rarely replaced due to response time failures. Based on this information, response time 2 4) a. testing intervals of once every fuel cycle are adequate, 0 IV. REFERENCES le erate W Response Time Changes 1 Hashernian, H.M., et al., "Degradation of Nuclear Plant Temperature Sensors," NRC Report Number Figure 3 Overall Results of Aging Effects on NUREG/CR-4928, U.S. Nuclear Regulatory Pressure Transmitter Calibration Commission, Washington, D.C. (June 1987). and Response Time Discussions of whether or not the above practices 2. Hashemlan, H.M., et al., "Aging of Nuclgar Plant Resistance Temperature Detectors," NRC Report are adequate for aging management of pressure Number NUREG/CR-5560, U.S. Nuclear transmitters are provided below. Regulatory Commission, Washington, D.C. (June Transmitter Calibration Intervals. The calibrations 1990). of about 60 percent of the transmitters investigated in 3. Hashemian, H.M., et. al., "Effect of Aging on various aspects of the project reported herein were Response Time of Nuclear Plant Pressure found to be unaffected by normal aging. Of the Sensors," NFIC Report Number NUREG/CR-5383, remaining 40 percent, about percent drifted out of U.S. Nuclear Regulatory Commission, Washington, tolerance and the rest were only moderately aff ected by D.C. (June 1989). the aging tests meaning that their calibrations were still acceptable. Other aging data included searches of the 4. Hashemian, H.M., et. al., "Long Term PeE[ormance, LER and NPRDS databases which showed about to and Aging Characteristics of Nuclear Plant 3 percent calibration failures in a typical fuel cycle of Pressure Transmitters," NRC Report Number two years, and a survey of the nuclear industry which NUREG/CR-5851, U.S. Nuclear Regulatory showed that although up to about 20 percent of Commission, Washington, D.C. (March 1993), 32-C-6