Fire-induced damage in prestressing steels



Similar documents
Fire and Concrete Structures

Introduction. Eurocodes. Specification. Cost

Reliability of Temperature-Dependent Models for Analysis of Reinforced Concrete Members Subjected to Fire

Long term performance of polymers

Numerical Analysis of Independent Wire Strand Core (IWSC) Wire Rope

The ACI 562 Repair Code

Numerical modelling of shear connection between concrete slab and sheeting deck

Damage due to fatigue occurs when loading is markedly varying in time. R decreases with time S T. MSÚ F max

Hardened Concrete. Lecture No. 14

Evaluating. A Case Study

ICS: Strengthening retrofitting of reinforced concrete structures by gluing of fibre reinforced polymeric fabrics (FRP fabrics)

Fire-Damage or Freeze-Thaw of Strengthening Concrete Using Ultra High Performance Concrete

Measuring the Condition of Prestressed Concrete Cylinder Pipe

4 Thermomechanical Analysis (TMA)

North American Stainless

FIRE PERFORMANCE OF STRUCTURAL INSULATED PANEL SYSTEMS

Pragmatic multi-scale and multi-physics analysis of Charles Bridge in Prague

Local buckling of plates made of high strength steel

EDEXCEL NATIONAL CERTIFICATE/DIPLOMA MECHANICAL PRINCIPLES OUTCOME 2 ENGINEERING COMPONENTS TUTORIAL 1 STRUCTURAL MEMBERS

The Suitability of CRA Lined Pipes for Flowlines Susceptible to Lateral Buckling SUT Global Pipeline Buckling Symposium, February 2011

Experimental assessment of concrete damage due to exposure to high temperature and efficacy of the repair system

APE T CFRP Aslan 500

Chapter 5 Bridge Deck Slabs. Bridge Engineering 1

Lecture 14. Chapter 8-1

Field Damage Inspection and Static Load Test Analysis of Jiamusi Highway Prestressed Concrete Bridge in China

Prestressed Concrete Pipe Fitness for Service and Repair

TIE-32: Thermal loads on optical glass

Fire safety in timber buildings

CH 6: Fatigue Failure Resulting from Variable Loading

METHOD OF STATEMENT FOR STATIC LOADING TEST

Testing and appraisal of Lucobit polymer effect as an additive on asphalt mixture performance

STRUSOFT EXAMPLES PRE-STRESS 6.4

REHABILITATION OF THE FIGUEIRA DA FOZ BRIDGE

Appendix H Interscience Communications. Reprinted with permission.

DEVELOPMENT OF A NEW TEST FOR DETERMINATION OF TENSILE STRENGTH OF CONCRETE BLOCKS

Tentative Interim Amendment NFPA 59A. Standard for the Production, Storage, and Handling of Liquefied Natural Gas (LNG) 2016 Edition

Companion Document. EN : Eurocode 2: Design of Concrete Structures Part 1: General rules and rules for buildings

How To Determine The Effect Of Frost Deterioration On Chloride Penetration And Carbonation

Integrated Manhole Ladder System

IMPELLER FATIGUE ASSESSMENT USING AN S-N APPROACH

Stress Strain Relationships

Chapter 2 Basis of design and materials

Safe & Sound Bridge Terminology

INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES. Interpretations of the FTP

PRESTRESSED CONCRETE. Introduction REINFORCED CONCRETE CHAPTER SPRING Reinforced Concrete Design. Fifth Edition. By Dr. Ibrahim.

The BASA Guide to the ISO Classification of Sealants for Building Construction

NON-DESTRUCTIVE METHODS. CE 165: Concrete Materials and Concrete Construction

Robert H. White, Research Wood Scientist, U.S. Forest Products Lab., Madison, WI, USA, Brian Kukay, Associate Professor of General

Elevated Roads for Sri Lanka

The Strength of Concrete

Structural fire design Eurocode Timber structures

AdMaS centre Structure of the centre: Development of Advanced Building Materials Development of Advanced Structures and Technologies

SEISMIC RETROFITTING TECHNIQUE USING CARBON FIBERS FOR REINFORCED CONCRETE BUILDINGS

SAFIR A software for modelling. to the fire

Design of Impact Load Testing Machine for COT

A Study of Durability Analysis Methodology for Engine Valve Considering Head Thermal Deformation and Dynamic Behavior

GENERAL PROPERTIES //////////////////////////////////////////////////////

FOAMULAR LT40, 400 and 600 insulations with minimum compressive strengths of

INFLUENCE OF THERMOMECHANICAL TREATMENT ON THE STEEL C45 FATIGUE PROPERTIES

Measurement of Residual Stress in Plastics

Eurocode 5: Design of timber structures

The pretopped double tee is a very common precast,

C. PROCEDURE APPLICATION (FITNET)

DuPont Kapton HN. polyimide film

STRAIN-LIFE (e -N) APPROACH

A Simple Method of Gripping Prestressing Strands for Tension Tests

Force measurement. Forces VECTORIAL ISSUES ACTION ET RÉACTION ISOSTATISM

BOFIRE A FEM-programm for non-linear analysis of structural members under fire conditions

Fatigue and Fracture Testing Solutions

REVISION OF GUIDELINE FOR POST- EARTHQUAKE DAMAGE EVALUATION OF RC BUILDINGS IN JAPAN

ADHESIVE BONDING PERFORMANCE OF GA COATED 590 MPa TENSILE STRENGTH STEELS

Assistant Professor of Civil Engineering, University of Texas at Arlington

Solution for Homework #1

4.1. Fire damaged structures

Technical Notes 3B - Brick Masonry Section Properties May 1993

MECHANICAL CHARACTERIZATION

Draft Table of Contents. Building Code Requirements for Structural Concrete and Commentary ACI

Linear Elastic Cable Model With Creep Proportional to Tension

Nonlinear Analysis of Reinforced Concrete Structures in Design and Structural Assessment

A NEW DESIGN METHOD FOR INDUSTRIAL PORTAL FRAMES IN FIRE

DEFECTS IN SHEET ROOFING THAT IMITATES ROOF TILES AS A RESULT OF THEIR ANCHORAGE

EN DK NA:2007

Modern Codes for Design of Concrete Concrete Structures Presentation Outline

PROPERTIES OF MATERIALS

ATI 2205 ATI Technical Data Sheet. Duplex Stainless Steel GENERAL PROPERTIES. (UNS S31803 and S32205)

A PERFORMANCE TEST STUDY ON CHINESE G4 LEAD RUBBER BEARINGS

1.5 Concrete (Part I)

North American Stainless

Shrinkage and Creep Properties of High-Strength Concrete Up To 120 MPa

THE IMPACT OF YIELD STRENGTH OF THE INTERCONNECTOR ON THE INTERNAL STRESS OF THE SOLAR CELL WITHIN A MODULE

CRITERIA FOR PRELOADED BOLTS

B. INTRODUCTION TO ASSESSMENT PROCEDURES FOR CRACKED COMPONENTS

Structural use of concrete

Precast Concrete Parking Structures

Eurocode 2: Design of concrete structures

Transcription:

Fire-induced damage in prestressing steels By José Miguel Atienza and Manuel Elices Madrid Polytechnic University, Spain Abslracl: After a fire, even If no collapse happens, there Is a possibility of fire-induced damage in the structure. Correct knowledge of residual properties of wires after fire Is of major importance for the assessment of the residual load-bearing capacity of a presfressed structure. This paper studies the non-vlslble fire-induced damages In presfressed wires, Including the reduction of the prestress bads and the strength of steel wires produced by the exposure to high temperatures. Atienza Elices José Miguel Atienza teaches in the materials science department at Madrid Polytechnic University, Spain, where he started as a researcher in 1998. His areas of scientific interest include steel wire forprestressed concrete and biomaterials. He holds a Ph.l>. degree in civil engineering from Madrid Polytechnic. Manuel Elices is full professor of materials science and technology at Madrid Polytechnic and dean of the faculty for materials science and engineering. His professional and research work has been centered mainly on cracking and fracture of materials. 195

ABSTRACT After a fire, even if no collapse happens, there is a possibility of fire-induced damage in the structure. Correct knowledge of residual properties of wires after fire is of major importance for the assessment of the residual load-bearing capacity of a prestressing structure. In tliis work, the non-visible fire-induced damages in prestressing wires have been studied: the reduction of the prestressing loads and the strength of steel wires produced by the exposure to liigh temperatures. 1 INTRODUCTION When fue occurs either in buildings or bridges, depending on the relative severity of the fire, there is a possibility of fire-induced damage, which affects the performance of the structures, even if no collapse happens. The extent of damage depends on the veiy intensity and duration of the fire, as well as the geometry, materials used in construction and load intensity. After fire, the question which then arises unavoidably, is whether the structure should be replaced or whether it is still possible to use it, either as it is or after some partial repairs, hi many cases, the structural members can be restored through repairs. However, before undertaking such repairs an assessment of the load beaiing capacity of the structure has to be carried out, even if it seems that no repairs are needed, since a misjudgement at this point can lead to unsafe situations. The financial aspect of the question is of course an important issue and may, in some cases, lead to the decision of destruction rather than repairing of the remaining structure. However, the essential question that the engineers have to face is whether the structure is still safe. What is the load beaiitig capacity of the structure now? How has it been affected by the fire? Appropriate knowledge of the behavior of construction materials after a fire is of major importance for answering these questions. Much experimental work on the characterization of the mechanical properties of steels at liigh temperatures, aiming at structural fire design, has been done hi the past decades 196

[1-7]. However, less work has been performed in the characterization of the mechanical residual properties after fire. Conect knowledge of such properties is of major importance for the assessment of the residual load-bearing capacity of the structure, hi this work, the behavior of prestressing steel after fire is studied, examining the two main factors which can affect the security of the structures: - The permanent deterioration of the material properties, specially the strength and elastic limit. - The modification in the distribution of actions and loads due to the increase hi the stress relaxation losses of prestressing steels produced by the exposure to high temperatures. Tlris can reduce the prestressing load after fire, with a subsequent reduction in the safety of the structure. 2 AN EXAMPLE OF FIRE DAMAGES IN PRESTRESSING WIRES 2.1- Fire Simulation A prestressing wire has been subjected to afire scenario to simulate the effects of afire on the mechanical behavior of prestressing steel wires when the structure does not collapse. The key feature of the fire relevant to the prestressing steel behavior is the temperature-time curve endured by the material. Given that structural steel has a high thermal conductivity coefficient, when directly exposed to a fire it acquires immediately the the temperature. However, as concrete surrounds steel wires and has low thermal conductivity, its thickness protects steel wires, delaying the values of temperature reached inside the stnictmal elements. Standards provide curves to predict the temperature inside concrete elements during the nominal fires. The time-temperature curve (Fig. La) used in this work represents a realistic and conservative fire scenario, even considering the bearing capacity of the wire is not surpassed. The heating velocity is around 3 C/min representing a typical temperature curve inside concrete elements during the nominal fires. Maximum temperature is reached at the end of the fire, three horn's after the beginning. 197

An additional aspect should be considered to model the effects of fire: temperature produces a dilatation of the structural members which, hi general, could not expand free due to the external constraints. Standards distinguish between "restrained" and "unrestrained" assemblies. The term restrained means that thermal expansion of the specimen is restricted during the fire test. If a fire occurs beneath a portion of a large structure, the heated portion will expand and push against the surrounded unhealed portion. In turn, the unhealed portion exerts compressive forces in the heated portion, altering the seivice load during the fire, hi the case of unrestrained assemblies, the dilatation of the element is free. 0.7 F max 0.5 F r 60 120 TIME, (minutes) 5 days Figure 1. a) Time-temperature curve endured by the steel wire during the fire simulation, b) Evolution of prestressing load dining the fire simulation. 198

hi our case, the length of the specimen remanís constant during the fire. Tliis is a typical case of a restrained assembly, in which the service load would diminish during the heating because of the constrained dilatation. The fire scenario was simulated following the next steps: - The prestressing steel wire (specimen length: 1.2 m) is loaded at 20 C. The initial load has been 70% of the maximum load, the value proposed by Standards for the stressrelaxation tests. The curve load-time is recorded continuously. - Once the majority of the stress relaxation losses have occurred, after five days, the effects of file are simulated using a furnace (size: 0.7 of the specimen length). The fire duration was about three hours. Then the furnace was turned off and left open so that the wire would cool in air. The curve load-time is recorded continuously dining the whole process. - The test continues five more clays at room temperature. Again, the curve load-time is continuously recorded. - After that, conventional tensile test and stress relaxation test at room temperature were performed on the final wire to study the residual properties. 2.2- Fire-induced Damages Figure l.b shows the evolution of the prestiess load before, dining and after fire. It can be observed that during the fire there is a significant reduction of tire beaiing load, as a consequence of the restrained dilatation and the mcrease of stress relaxation at liigh temperatures. When cooling, the part of this lost load due to the constrained dilatation is recovered, but not the stress relaxation losses. Although the wire has successfully supported the fire without any visible damage, the prestressed load after fire has been considerable reduced. Additionally, the results of the conventional tensile and stress relaxation tests at room temperature showed that the residual strength has been affected (20% less than the 199

original value) as well as relaxation (five times larger than the typical for a "low relaxation" wire). hi summary, even the fire has not produced visible damages, tlie strength of the wire and tlie prestiessed load were reduced, with the subsequent reduction of the residual load-bearing capacity of tlie structure. 3 CHARACTERIZATION OF PRESTRESSING STEEL RESIDUAL BEHAVIOR AFTER FIRE - Stress relaxation losses at high temperatures By definition, stress relaxation refers to tlie decrease in stress at a constant deformation. hi prestiessed concrete structures, steel tendons hi tension provide compressive stresses to the concrete. Throughout the life of the structure there should not be an appreciable loss of tension, because a reduction in prestressing loads would affect tlie structural safety. Design codes place limits for keeping the relaxation losses within safe margins. Stress losses are measured according to a standardized test (ASTM E328, ISO15630/3) and tlie figures should be provided by the manufacturer for the acceptance of the steel tendons; those with a figure of stress losses of less than 2.5% of the initial stress after 1000 hours, at room temperature, when stressed at 0.70 of the tensile strength are called "low relaxation" tendons and are those used in prestressing at present [8]. Temperature lias a great influence on tlie stress relaxation; an increment of temperature produces a large increase in stress relaxation losses. During a fire, the wire temperature ulereases and, depending on tlie boundary conditions, initial wire load can decrease due to the restrained dilatation. Since no results under such conditions were found hi tlie literature, a detailed experimental study on the effects of temperature on the stress relaxation losses of the wires was perfonned. Stress relaxation tests at different temperatures and at different initial loads were carried out. The duration of the tests was four hours, longer than tlie duration of the conservative fire scenarios proposed by 200

standards (ECl 2002, EC2 2005). Temperatures studied were: 20, 100, 200, 300, 400, 500 and 600 C. Initial loads considered were: 10-30-50-70-90% of the tensile strength. hi Figui'e 2, the time-stress relaxation losses cuives are depicted as a function of temperature and initial loads. It can be seen that as temperature increases the stress relaxation losses increase significantly, and, consequently, the prestressed compressive loads provided to concrete decreases. Clearly, this is a fact to be considered when assessing the tire-induced damage after cooling. - Residual mechanical behavior at room temperature After a fire, even if no collapse happens and no effects can be visually seen in the structure, damage can be-induced hi the materials due to previous exposure to high temperatures. The term "residual" will be used here to indicate the properties that the prestressed steel exhibits after a complete cycle of heating and cooling. hi our work, to simulate the effects of fire, wires were subjected to a complete cycle of heating and cooling (tour hours), while loaded at 70% of then tensile strength. The effects of fire will depend upon the fire duration and the loading of the wire, in this case testing conditions are a conservative simulation since the duration of the fire is longer than the nominal fires (BS811, ECl, EC2), and the load is the maximum load experimented for the wires hi service. Temperature was raised at a rate of around 20 C/min and the different maximum temperatures studied were the same as the rest of this work: 20,100, 200, 300,400, 500 and 600 C. 201

020 020 UJ 015 fo }5 005 "% 0.5 10 15 20 25 30 35 TME.(HCURS) Figure 2. Stress-relaxation losses as a function of temperature, for different initial stresses. The relative values are given as stress loss/strength 202

After cooling, tensile tests and stress relaxation tests at room temperature were performed to obtain the residual mechanical propeities of tlie wires. Table 1 shows tlie variation of tlie tensile strength, tlie yield stress and tlie stress relaxation losses after 250 hours for the different maximum temperatures reached during tlie lire simulations. The reference values of the original wires (control samples without thermal treatment) at room temperature have also been included. Tlie values of the residual tensile strength for the tested prestressing steel remain approximately constant up to temperatures around 300 C. If tlie wire suffers higher temperatures during lire, the residual strength, the elastic limit and the stress relaxation behavior are affected. Table 1, strength). Residual mechaiiicul properties after a fire (duration: 4 hours, loaded at 70% maximum Max. Temp Yield Stress Strength Str. Relax C c) (MPa) (MPa) ( /cinit. load) 20 (R oom) 1770 1950 2,2% 100 1765 1947 2.2 % 200 1770 1940 2.4 % 300 1752 1926 2.5 % 400 1590 1755 6.2 % 500 1380 1521 13.2 % 600 887 1014 Breaks 203

4 SUMMARY Fire safety should consider not only tlie performance of tlie structure during the fire but also tlie behavior of tlie stmctuie after cooling. Even if a fire does not give rise to apparent damage in the prestressed structure, mechanical properties of materials as well as load distribution can be affected. After fire, a verification of residual load-beating capacity is necessary to determine if the stmctuie can be maintained in use. The extent of damage in prestressing steels depends on the intensity and duration of tlie fire, tlie temperatures reached in tlie wires, as well as tlie load intensity they bear during a fire. hi this work, we have tried to attract attention to the possible non-visible fire-induced damages produced in prestressing steels after fire: - Reduction of the prestressing loads due to the increment in tlie stress relaxation losses during the exposure to high temperatures. - Damage of the mechanical properties of steel wires produced by the exposure to high temperatures: residual strength and stress relaxation behavior at room temperature depend on the maximum temperature reached hi tlie wire during fire. ACKNOWLEDGEMENTS Tlie authors gratefully acknowledge the support of tlie Ministerio de Fomento in Spain, by means of the "Durability of prestressed concrete tendons" grant. They are also indebted to Mr. Luis del Pozo, from Emesa Trefilerías, and Mr. Mariano Qrtez for their liigmy beneficial comments and help with the material and the tests. REFERENCES [1] Harmathy, T.Z. & Staiizak, W.W. 1970. Elevated temperature tensile and creep properties of some structural and prestressing steel. Fire Test Performance, ASTM STP 464. American Society for Testing and Materials 186-208. [2] British Standards Institution BS8110: Part 2, 1985. Stmctiiral use of concrete, Code of practise for special circumstances. BSI, London. 204

[3] CEB (Comité Euro-International du Betón) 1991. Fire design of concrete stmchires. Bulletin 208, Comité Euro-International du Betón (CEB),Laussane, Switzerland [4] Cristofano, A.H. & Martin, L.D. 1989. Design for fire resistance of precast prestressed concrete. Second Edition, Prestressed Concrete Institute PCI. [5] ECi 2002. Eurocode 1: Basis of design and actions on structures, Part 2.2: Actions on structures exposed to fire, EN 1991-1-2:2002. November 2002. [6] EC2 2005. Eurocode 2: Design of concrete stmchires - Part 1-2: General rules - Stnicfural Fire Design EN 1992-1-2: 2002. February 2005. [7] fib 2007 (Federation Internationale du Beton) Working Party 4.3-1. Fire design of concrete stmchires -materials, structures and modelling. State of art report, fib Bulletin 38. [8] Atienza, J.M. & Elices, M. 2007. Role of residual stresses in the stress relaxation of prestressed concrete wires. Journal of Materials in Civil Engineering, 19(8), 703-7. 205