15 April 2015 Nuclear Regulation Authority, Japan. 1. Overview



Similar documents
Overview of the Multi-nuclide Removal Equipment (ALPS) at Fukushima Daiichi Nuclear Power Station. March 29, 2013 Tokyo Electric Power Company

February 19, Senior Fellow, Nuclear Energy Systems & Services Division Power Systems Company

Status of Contaminated Water Treatment and Tritium at Fukushima Daiichi Nuclear Power Station

Roadmap towards Restoration from the Accident at Fukushima Daiichi Nuclear Power Station, TEPCO. Progress Status

Unit 4. Storage and handling. Fuel debris removal. Scenario development & technology consideration. Design and manufacturing of devices/ equipment

Engineered Media for Removal of Fission Products from Aqueous Streams Abigail Holmquist, UOP - A Honeywell Company

The integrity evaluation of the reactor building at unit4 in the Fukushima Daiichi nuclear power station

July 30, 2012 Nuclear Emergency Response Headquarters Government-TEPCO Med-and-long Term Response Council

Start of introducing ICP MS method for analyzing water samples for Strontium. November 27, 2014 Tokyo Electric Power Company

May 23, 2011 Tokyo Electric Power Company

FILLING AND PURGING THE SYSTEM

Chemical Decontamination and Fluid Handling Services

Damage of Fukushima Nuclear Accident and a new compensation scheme

How To Clean Up A Reactor Water Cleanup

Office for Nuclear Regulation

Decommissioning situation of Nuclear Power Plant in Japan

Results of Airborne Monitoring by the Ministry of Education, Culture, Sports, Science and Technology and the U.S. Department of Energy

Activities of Nuclear Damage Compensation & Decommissioning Facilitation Corporation (NDF) Yasuharu Igarashi

Azeri, Chirag & Gunashli Full Field Development Phase 3 Environmental & Socio-economic Impact Assessment. A10.1 Introduction...

Condensing Boiler Efficiency

How Ground/Water Source Heat Pumps Work

Volkswagen B3 Passat General-Engine 4 CYL. 19 Engine - Cooling System (Page GR-19)

Cooling system components, removing and installing

Application Note. ipix A Gamma imager to support various applications

MAINTENANCE INSTRUCTIONS. Thermia Robust heat pump

APPENDIX G Materials Storage and Handling Guidelines

Environmental Remediation Examples and Remediation Strategic Planning

History of the SPCC Rule

DIRECTIVE 055: STORAGE REQUIREMENTS FOR THE UPSTREAM PETROLEUM INDUSTRY. August 2012

STP 3 & Liquid Waste Management System Design Basis

SPILL PREVENTION, CONTROL AND COUNTERMEASURE PLAN

HEATING OF DOMESTIC OUTDOOR SWIMMING POOLS

Stenner Pump Chlorinator Installation & Start Up Guide

Heat Pumps for Swimming Pools

DIRECTIVE 055: STORAGE REQUIREMENTS FOR THE UPSTREAM PETROLEUM INDUSTRY

HVAC: Cool Thermal Storage

COMMISSIONING OF HVAC SYSTEMS

A cure for water damage in real estate

Standard Hydraulic Piping Flushing Procedure

Inspections Standard Operating Procedure 5 Aboveground Storage Tanks

CHAPTER PETROLEUM CONTACT WATER

Fukushima Accident: Radioactive Releases and Potential Dose Consequences

UltraTech International, Inc. Canadian Secondary Containment Requirements

Nuclear Safety Council Instruction number IS- 23 on in-service inspection at nuclear power plants

Boiling Water Reactor Systems

INNOVATIVE SOLUTION OF DOMESTIC HEATING SPLIT TYPE SPLIT DHW INTEGRATED TYPE MONOBLOC TYPE

AMERICAN NUCLEAR INSURERS. Potential for Unmonitored and Unplanned Off-Site Releases of Radioactive Material

Government Degree on the Safety of Nuclear Power Plants 717/2013

How To Use A Water Source Heat Pump

IV. Occurrence and Progress of Accidents in Fukushima Nuclear Power Stations and Other Facilities

Arctic King Fuel Tanks meet the Environment Canada TECHNICAL REQUIREMENTS FOR COLLAPSIBLE FABRIC STORAGE TANKS (BLADDERS) - December 17, 2009

A discussion of condensate removal systems for clarifier and thickener drives for water and wastewater facilities.

Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,

Loviisa 3 unique possibility for large scale CHP generation and CO 2 reductions. Nici Bergroth, Fortum Oyj FORS-seminar

APPROVED. PXP 2009 Tank Leak Detection and Containment at Inglewood Oil Field. Baldwin Hills CSD Conditions L.18. and E.29.e.

Radioactive Waste Storage Facility and Tank System Design Criteria Standards

APPENDIX C. Accident Cleanup

Chemical Feed System Operation and Design Considerations

Compliance Guidance for Motor Vehicle Waste Disposal Wells in Oregon September 2015

IAEA INTERNATIONAL FACT FINDING EXPERT MISSION OF THE NUCLEAR ACCIDENT FOLLOWING THE GREAT EAST JAPAN EARTHQUAKE AND TSUNAMI

Volkswagen Golf > VW Rabbit GTI 2006->

Current state of plant Functioning as a peak and emergency centre. Statistics Accumulated operating hours:

Improper storage of fuel on construction sites will increase the risk of water pollution that may occur as a result of leaks or spills.

IAEA Action Plan on Nuclear Safety 1

DESIGN CHALLENGES AND OPERATIONAL EXPERIENCE OF A MEGA MED SEAWATER DESALINATION PLANT IN TIANJIN

Air Conditioner Water Heater - A Product of HotSpot Energy LLC

8. Heat pumps, heat pipes, cold thermal energy storage

Reclamation Plants, Separation Facilities & Stationary Treatment Facilities

Managing Floor Drains and Flammable Traps

PREVENTING GROUNDWATER POLLUTION: SECONDARY CONTAINMENT

Hazardous Waste Accumulation, Storage, & Labeling

Cooling system components, servicing

Standard Operating Procedures for Flood Preparation and Response

Stormwater BMPs: Secondary Containment and Spill Control. September 2012

Rutgers Environmental Health and Safety

Three Mile Island Unit 2 Overview and Management Issues

MBJ Environmental Programmes

Element D Services Plumbing

GEOTHERMAL HEATING AND COOLING INTRODUCTION

Fukushima & Three Mile Island Reactor Accidents: Recovery, Cleanup, Lessons, & Future

GUIDE FOR THE PREPARATION OF RADIOACTIVE MATERIAL APPLICATIONS FOR WELL LOGGING OPERATIONS IN KENTUCKY

The Fukushima Nuclear Disaster

Radioactive waste managment in Estonia past, present and future

Cooling system components, removing and installing

Nuclear power plant systems, structures and components and their safety classification. 1 General 3. 2 Safety classes 3. 3 Classification criteria 3

Draft IAEA Action Plan on Nuclear Safety

11. COOLING SYSTEM 11-0 COOLING SYSTEM BET & WIN 50

[LAST UPDATED March 25, 2015]

Transcription:

Evaluation of the report of the Tokyo Electric Power Company regarding the leakage from the double strainer differential manometer for the water transfer pipes of the desalination system at Fukushima Daiichi Nuclear Power Station 1. Overview 15 April 2015 Nuclear Regulation Authority, Japan Around 11:05 on 6 February 2014, the double strainer differential manometer of the water transfer pipe connected to the reactor water-injection equipment (hereinafter, referred to as the differential manometer ) was found to be leaking RO-treated water. 1 RO-treated water that had leaked from the differential manometer spilled out of the drain water receiver of the mount installed in the lower part of the double strainer and permeated the soil. Tokyo Electric Power Company (hereinafter, referred to as TEPCO ) confirmed that there was no indication that the leaked water had flowed outside the wall of sandbags placed around the mount, and there was no trace of water flow in the side ditch near the location of the leakage. In the same day, the Nuclear Regulation Authority (hereinafter, referred to as NRA ) received the report regarding accidents and failures based on the Article 62-3 of the Act on Regulation of Nuclear Source Material, Nuclear Fuel Material and Reactors from TEPCO. Subsequently, the NRA received the report regarding causes and countermeasures of the aforementioned event (the final report) from TEPCO as of 30 June 2014 (partially corrected on 31 October 2014) and the NRA reviewed the contents and summarized the evaluation result. Report from TEPCO http://www.nsr.go.jp/activity/bousai/trouble/20141031-4.html 1 Desalinated water that has been treated by reverse osmosis wastewater treatment equipment and is used for nuclear reactor water injection (refer to Figures 1 and 2). 2. Overview of the report submitted by TEPCO (1) Environmental impact assessment (expansion of contaminated water) The amount of RO-treated water that leaked from the differential manometer was approximately 600 L based on the changes in flowmeter readings. According to the

analysis results, the radioactivity concentration was estimated to be approximately 9.3 10 4 Bq/L for total beta and approximately 3.8 10 5 Bq/L for tritium. Based on these results, the amount of radioactivity of the leaked water was calculated to be approximately 5.6 10 7 Bq for total beta and the amount of radioactivity including tritium was calculated to be approximately 2.8 10 8 Bq. Regarding the radiation dose on the ground surface before and after excavation and collection of soil, the effective dose due to gamma rays dropped from 0.18 msv/h to 0.016 msv/h, and the equivalent dose to the skin due to beta rays dropped from 0.07 msv/h to 0.00 msv/h. Although some of the leaked water permeated the soil, it did not flow outside the wall of sandbags placed around the leakage location. TEPCO therefore concluded that this event caused no ocean contamination that raises any concerns about effects on health or the environment. Also, recovery of the soil that leaked water permeated has been completed. (2) Investigation of the leakage situation Before the event occurred, low-temperature conditions persisted inside the lagging material of the differential manometer due to the low outside air temperature (around 6 C) from around 22:00 on 5 February 2014 to around 4:00 on 6 February 2014. Because of this, the RO-treated water inside the differential manometer exposed to outdoor air via the body froze and increased in volume, which led to deformation of the bonnet flange and loosening of the bonnet flange bolts. It is assumed that the bonnet flange thus lost its sealing function and leakage occurred from the seal portion when the frozen RO-treated water melted. Moreover, due to the fact that other instruments having operating temperature ranges similar to that of the relevant instrument (operating temperature range: 5 to 40 C, however, the fluid should not be allowed to freeze) had been used successfully outdoors at Fukushima Daiichi Nuclear Power Station, it was considered sufficient to attach lagging material as a freeze-proofing measure when choosing such an instrument. (3) Countermeasures (i) Anti-freezing countermeasures The entire double strainer, including the differential manometer, was covered with an acrylic cover, and two fan heater units were placed under the cover. As a countermeasure against leakage outside the system, a concrete dike was installed around the double strainer. For instruments installed outdoors or in locations

where it is difficult to isolate them from outdoor air and which contain fluids that may freeze, it was decided to install heaters to prevent freezing or draining of water inside instrument main units and instrumentation piping in the future, and these countermeasures were described in the Flow chart for the implementation of anti-freezing countermeasures. A total of 38 instruments (all installed in the stagnant water storage facilities for Units 5 and 6) are subject to the countermeasures based on said flow, and implementation of countermeasures has been completed for 8 of these. Installation of freeze prevention heaters is scheduled to be completed before the onset of winter in FY2014 for the 30 instruments for which countermeasures have not yet been implemented. (ii) Establishment of the Flow chart for the implementation of anti-freezing countermeasures as a manual The Flow chart for the implementation of anti-freezing countermeasures will be included among the Anti-freezing countermeasures operation guidelines scheduled to be established in November 2014 as lower-tier documents in the Basic Manual for Decommissioning and Basic Manual for Maintenance Management. 3. NRA s evaluation with regard to the report submitted by TEPCO and future response (1) Environmental impact (expansion of contaminated water) Based on the fact that the leaked RO-treated water (radioactivity concentration: approx. 9.3 10 4 Bq/L for total beta, approx. 3.8 10 5 Bq/L for tritium) remained within the sandbag wall placed around the leakage location and no contaminated water was observed flowing outside the sandbag wall, so based on the facts above, the NRA evaluates that there has been no contamination of the ocean that raises any concern about influence to health and the environment. (2) Exposure radiation dose An evaluation of the effective dose due to gamma rays and the equivalent dose to the skin due to beta rays for workers who patrolled the area where the differential manometer was installed showed no significant differences between the values before and after discovery of the leakage. The NRA therefore concludes that there has been no exposure leading to concern (refer to Table 1).

(3) Countermeasures TEPCO determined the assumed cause from the obtained information and formulated anti-freezing countermeasures based on this cause. The NRA has evaluated them as follows, countermeasures summarized by TEPCO shall be checked about its implementation situation at an appropriate timing by safety inspection, etc. (i) Anti-freezing countermeasures Based on the Flow chart for the implementation of anti-freezing countermeasures, it was decided to install freeze prevention heaters and drain the water inside the main units and piping of instruments for which countermeasures were deemed necessary, and these countermeasures were described in the flow chart. The report stated that installation of freeze prevention heaters was scheduled to be implemented before the winter of FY2014 for the 30 instruments for which countermeasures had not yet been implemented among those subject to the Freeze prevention countermeasures implementation flow (38 instruments in total; all are installed in the stagnant water storage facilities for Units 5 and 6). The NRA has confirmed in a meeting with TEPCO that implementation of the countermeasures was completed on 28 November 2014. TEPCO has analyzed the causes of the leakage and taken its measures responding to them appropriately, the NRA thus considers them reasonable. (ii) Establishment of the Flow chart for the implementation of anti-freezing countermeasures as a manual The report stated that the Flow chart for the implementation of anti-freezing countermeasures would be included in the Anti-freezing countermeasures operation guidelines scheduled to be established in November 2014 as lower tier documents in the Decommissioning Basic Manual and Maintenance Management Basic Manual. The NRA has confirmed in a meeting with TEPCO that the guidelines were established on 27 November 2014 and came into force on 1 December 2014. The relevant guideline states: For instruments installed outdoors or in locations where it is difficult to isolate them from outdoor air and which contain fluids that

may freeze, install heaters to prevent freezing and drain the water inside such instrument main units and instrumentation piping in the future. TEPCO has analyzed the causes of the leakage and taken its measures responding to them appropriately, the NRA thus considers them reasonable.

Category Highly radioactive water/waste Treated water (saltwater) Treated water (concentrated saltwater) Treated water (storage tank) Sr treated water (storage tank) Polynuclear species removal system, etc. (incl. other purification systems) Treated water (freshwater) Treated water from polynuclear species removal system, etc. Freshwater Filtrate water tank Concentrated liquid waste (storage tank) Evaporative concentration equipment Treated water (concentrated saltwater) (receiving tank) Desalination system (RO type) Treated water (freshwater) (receiving tank) Reactor building Injection water tank (CST) (buffer tank) Evaporative concentration equipment-treated water Desalination system-treated water Liquid waste supply tank Turbine building Radioactive waste treatment facilities (high temp. incinerator bldg.) Pressure vessel Location of leakage Condenser Radioactive waste treatment facilities (process main building) Treatment system (cesium adsorption apparatus) (secondary cesium absorption apparatus) (decontamination system) Containment Waste From Figure 1 Overview of the processing route for accumulated highly radioactive water (extracted from the Secretariat of the NRA s document for a meeting with TEPCO) Reactor water-injection equipment Solid line: Circulation loop using the condensate storage tank as the water source Dotted line: Circulation loop using the upland buffer tank as the water source Buffer tank Secondary cesium absorption apparatus (SARRY) Location of leakage Stagnant water transfer system Common suppression pool water surge tank (SPT) Reactor waterinjection pump Water treatment system Desalination system (RO) RO-treated water temporary storage tank Treated water transfer pump Figure 2 Approximate position of the leakage (extracted from the Secretariat of the NRA s document for a meeting with TEPCO)

External appearance of the affected differential manometer Note: No traces of damage (scratches, deterioration, etc.) on its exterior (Top) Low pressure side Diaphragm bellows High pressure side Overview of the affected differential manometer The portion shaded orange (low pressure side) and the portion shaded blue (high pressure side) are filled with water, and the diaphragm bellows expands or contracts due to each portion's water pressure, causing the differential manometer to output a value. Condition of the bonnet flange (top) Note: The flange is slightly swollen and the O-ring is projecting out of the flange. Reading of the affected differential manometer when leakage occurred Note: The indicator is off the scale. Figure 3 Overview of the differential manometer (extracted from the TEPCO report)

Table 1 Radiation exposure dose evaluation results (extracted from the Secretariat of the NRA s document for a meeting with TEPCO) Differences in workers' exposure doses Effective dose (gamma rays) Annual dose limit: 50 msv Avg. dose per a single entry [msv] Max. dose per a single entry [msv] Equivalent radiation dose (skin, beta rays) Annual dose limit: 500 msv Avg. dose per a single entry [msv] Max. dose per a single entry [msv] Patrols of the area where the differential manometer is installed (including patrols that also include other areas) Before finding leakage (30 Jan. 5 Feb.) On the day the leakage was found (6 Feb.) After finding leakage (7 13 Feb.) 0.07 0.21 0.15 1.2 0.04 0.11 0.02 0.1 0.04 0.19 0.01 0.1 Table 2 Content and completion time of countermeasures (extracted from the Secretariat of the NRA s document for a meeting with TEPCO) Category Countermeasure Date completed Anti-freezing countermeasures Establishment of the Flow chart for the implementation of anti-freezing countermeasures as a manual Replacement of the affected differential manometer with a new product 9 April 2014 Installation of an overall cover (acrylic) and fan heaters (2 units) 17 June 2014 Replacement of the sandbag wall placed around the double strainer differential manometer with a concrete dike Installation of freeze prevention heaters and draining of the water inside instruments for Units 5 and 6 (30 locations) Revision of the Flow chart for the implementation of anti-freezing countermeasures Formulation of the Flow chart for the implementation of anti-freezing countermeasures 23 June 2014 28 November 2014 4 September 2014 27 November 2014