Clean Room Design. By the end of this chapter, you will be able to: Introduction. Chapter 5

Size: px
Start display at page:

Download "Clean Room Design. By the end of this chapter, you will be able to: Introduction. Chapter 5"

Transcription

1 Chapter 5 Clean Room Design By the end of this chapter, you will be able to: l Explain the terms positive and negative pressure l Name and describe two categories of air flow in a clean room l List the main design features of a clean room l Explain the different grades of clean rooms Introduction In this chapter we will look at the specific design of a clean room including the walls, ceilings and floors as well as the practical needs of items such as workbenches, storage cupboards and chairs. We will examine how air is filtered to maintain the air quality and how air pressure prevents contamination of the cleanroom when people and equipment move into or out of the clean room. We will also take a brief look at the different types of clean room using particle counts to grade areas. Chapter 5: Clean Room Design 1

2 Aseptic Processing What is a Clean Room? Cleanrooms are usually self-contained facilities with their own dedicated ventilation systems. These control air quality, temperature and humidity. Air is filtered through High Efficiency Particulate Air (HEPA) filters which have a very small pore size. The filters collect and remove small particles, before air enters through the ceiling grilles. Ceiling HEPA filter Dirty air from the surrounding area is prevented from entering the cleanroom by controlling the air pressure in the cleanroom. l Cleanest room at highest pressure l Air flows from the cleanest to dirtiest areas Operation is at positive pressure, so ensures any airflow is pushed outwards from the room and dirty air cannot enter the room by default. The size of the aseptic suite depends on the maximum number of people who might use it at any one time. A fairly large room is more pleasant to work in, and the overall level of microbes in the environment is less affected by local air disturbances or contamination produced by individual workers. Clean Room Design Clean rooms fall into two categories, unidirectional and non-unidirectional. Build up of contaminants in the cleanroom is prevented by the flow of clean air at a rate of a minimum of 20 room air changes per hour. Unidirectional clean rooms normally have vertical airflow. Air flows downwards through HEPA filters located in the ceiling. The air is extracted through perforated flooring or grilles mounted on the walls at floor level. Note: airflow in a unidirectional clean room can also be horizontal. 2 Chapter 5: Clean Room Design

3 Chapter 5 Clean Room Design Non unidirectional clean rooms have air flows from HEPA filters located in various positions and returned through opposite locations. Filters may be distributed at equal intervals throughout the room or grouped over critical areas. The distribution and returns in this instance mean that the air flow may be turbulent in nature. The floors, walls and ceiling should be made of a smooth impervious material to ensure no particle shedding and easy cleaning. They should also be chemically resistant. All joins in the covering materials should be welded to ensure that there is no chance of seepage of cleaning fluids under the covering. Doors should be easy to open and, where necessary, two doors linked together to form an air lock. This prevents a sudden rush of air when a door is opened. All doors should be controlled to prevent unwanted flow of air from one area to another by opening of doors simultaneously. Benches should be made from one complete sheet of laminate because some liquids attack the adhesive at the joints and eventually cause lifting. Where possible made they should be made from stainless steel, Trespa or Conan which are impervious. They are usually wall-mounted to reduce dust collection and facilitate its detection and removal. When storage space is required, cupboards are preferable to drawers because they are easier to clean. Cupboards should be dust proof and smooth inside. Rounded beading may be used to cover dust-retaining angles within storage spaces and between fixed benches and walls. Small units on castors make useful additions to the working surface. Chairs must be adjustable and comfortable and covered with an impervious washable material. Trolleys should be made from stainless steel and be easily cleanable. Switches and sockets should be flush fitting and have plastic fingerplates. There should be no l shelves, window ledges or door frames where dust might settle. l pipes or ductwork. (False ceilings should be fully sealed with lighting recessed). l sinks or drains. Chapter 5: Clean Room Design 3

4 Aseptic Processing Hand washing facilities should be available external to changing rooms. Taps should be elbow or foot operated so that cleaned hands are not used to turn the water off. Soap should be conveniently dispensed from a wall or bench dispenser. Electric hand dryers or high quality paper towels should be used to dry hands. Remember: In summary, there should be: l smooth impervious surfaces l no ledges for dust to gather l surfaces which are easy to clean l transfer systems/airlocks to prevent contamination l no water sources Other aspects of design of the Cleanroom When designing a clean room there are many considerations to make. Here are a few but this is not an exhaustive list of good and bad practice. There should be a separate two-way transfer hatch system for the transfer of goods in and out of the cleanroom, to prevent contamination of environments. Material used in the construction should make cleaning and disinfection easy. For example there should be no joins between walls, floors and ceiling and all surfaces should be smooth and easy to clean. There should be a support room from which materials can be passed into and out of the cleanroom through hatches. Horizontal surfaces can accumulate particles and should be maintained by regular cleaning 4 Chapter 5: Clean Room Design

5 Chapter 5 Clean Room Design Airlocks should be installed between clean areas and adjoining dirty areas This is a close up of a high quality door and hinge. Glass is easily cleanable and enables safe access/egress. Equipment should not reduce the airflow and should not be placed anywhere it disturbs the airflow. This image shows an alcohol extraction unit situated in the spraying in zones of the preparation area. It works as a vacuum extracting the alcohol fumes. Many of the normal routes out of an aseptic suite can be difficult to access during a fire alarm due to the number of corridors out of the suite. This is an example of a specially constructed fire escape to the outside of the building from an aseptic suite. The outer door is fabricated as a standard fire escape door, however it is sealed behind a sheet of breakable glass. Chapter 5: Clean Room Design 5

6 Aseptic Processing Remember: Here are some other important considerations about the design and use of clean rooms. l The equipment should be arranged to minimise the amount of operator movement while maximising their comfort. l The number of staff in an aseptic processing room should be kept to a minimum. l The flow of personnel should be limited to minimise exit and entry especially in the critical area. l The number of transfers to the critical area of the clean room or isolator should be minimised. l Excessive movement adjacent to the critical area should be restricted. Test Yourself Can you list 10 features to take into consideration when designing/fitting out a cleanroom? Chapter 5: Clean Room Design

7 Chapter 5 Clean Room Design Environmental Control The highest standard of environmental control will be included in the design of the clean room. Processes should be designed to give optimal personnel and product flow through the unit. We will look at this in more detail later. Aseptic processes in the clean room are designed to minimise the exposure of sterile components to the potential hazards of the manufacturing process. There are a maximum number of particles of different sizes allowed in the clean room at rest and during operation. Grade Particle size at rest Particle count (max particle /m3) Particle size in operation 0.5 µm 5 µm 0.5 µm 5 µm A 3, ,500 1 B 3, ,000 2,000 C 350,000 2,000 3,500,000 20,000 D 3,500,000 20,000 Not defined Not defined The table shows the values for the maximum particle count for different particle sizes within the different grades of clean room (Reference: Orange Guide 2007) Examples of Cleanroom Grade Grade A Laminar air flow cabinets and isolators, i.e. the point of fill. Grade B The aseptic room. Grade C The preparation room inner support room. Grade D Support, filling and isolator rooms. Information: Isolators may be sited in Grade C or D rooms check your local procedures). Chapter 5: Clean Room Design 7

8 Aseptic Processing Alarm Systems Fire and smoke alarms must be fitted in all areas of the facility. Staff must respond to alarms by evacuating the area immediately. An air supply alarm should be fitted which detects if there is a failure in the air supply to the facility. If this is triggered, work must cease immediately. In this simulated image the red lamps would indicate a problem with the cabinets. Work should only restart when the air supply has been reinstated and been running constantly for a minimum period. In the absence of a validation exercise of the cleanup time, this period should be one hour. Here is an example of an alarm panel with lamps showing the working status of the LAFC and Isolator cabinets. The green lamp indicates that the cabinet is running correctly in this image. Malfunctioning and Problems Problems should be reported immediately so that appropriate action can be taken. Anything unusual should be reported even though it may seem trivial, as it could be a precursor to a major fault or incident. You should report any procedural deviations or difficulties. Reports may be filed with the Estates Department at the hospital for any routine work that may need to be done within the cleanroom or supporting areas. Specialist cleanroom companies may be required to carry out more complicated tasks. Air pressure The air pressure in clean rooms is highest in the aseptic filling room ( cleanest ) and drops incrementally to the corridors. The usual practice is to start at 45 Pascals and come down in 10 Pascals increments, with the final differential being at least 15 Pascals. This will depend on the layout of your clean rooms. 8 Chapter 5: Clean Room Design

9 Chapter 5 Clean Room Design Clean Room Suite Layout The following plans are examples of clean room suite layouts for Isolators and LAFC s and show the flow of work and air. Airflow direction Workflow direction Step over Bench Transfer Hatches Isolator Suite Layout Laminar Air Flow Cabinet (LAFC) Suite Layout Isolator EU grade A LAFC EU grade A Clean Room EU Grade D Clean Room EU Grade B 2nd Change Room EU Grade D at rest 2nd Change Room EU Grade B at rest Inner Support Room 1st Change Room Outer Support Room Inner Support Room EU Grade D (clean room) Outer Support Room 1st Change Room EU Grade D at rest Chapter 5: Clean Room Design 9

10 Aseptic Processing Activity Make a sketch plan of your unit and mark on it: l Flow of products l Flow of people l Flow of documents l Air pressures in different parts of the unit. 10 Chapter 5: Clean Room Design

11 Chapter 5 Clean Room Design Questions Q1 What is the maximum allowable number of particles in a Grade A and Grade B clean room at rest and in operation? Complete the table below to show your answers. Grade A At rest In operation Particle size: 0.5 μm 5 μm 0.5 μm 5 μm Max number of particles allowed: Grade B At rest In operation Particle size: 0.5 μm 5 μm 0.5 μm 5 μm Max number of particles allowed: Q2 Why are airlocks installed between clean areas and adjoining less clean areas? (2) Chapter 5: Clean Room Design 11

12 Aseptic Processing Q3 What s the difference between a unidirectional and a non-unidirectional airflow? (6) 12 Chapter 5: Clean Room Design

Cleaning. By the end of this chapter, you will be able to: Introduction. Definitions. Chapter 9

Cleaning. By the end of this chapter, you will be able to: Introduction. Definitions. Chapter 9 Chapter 9 By the end of this chapter, you will be able to: l Define the terms cleaning, decontamination, disinfection l List the factors that affect disinfection l Describe the aims of a cleaning schedule

More information

Cleanroom Solutions Ltd T: 01273 760 060 F: 01273 760 061 E: mail@cleanroom-solutions.co.uk W: www.cleanroom-solutions.co.uk

Cleanroom Solutions Ltd T: 01273 760 060 F: 01273 760 061 E: mail@cleanroom-solutions.co.uk W: www.cleanroom-solutions.co.uk Cleanroom Solutions Ltd T: 01273 760 060 F: 01273 760 061 E: mail@cleanroom-solutions.co.uk W: Introduction Cleanroom Solutions Ltd has a wealth of experience together with a solid track record in the

More information

Environmental Monitoring

Environmental Monitoring Chapter 10 Environmental Monitoring By the end of this chapter, you will be able to: l List the types of environmental testing l Name three types of checks that are carried out to ensure the isolator is

More information

Sample Pharmacy CLEANING AND SANITIZING PROCEDURE P-304.1

Sample Pharmacy CLEANING AND SANITIZING PROCEDURE P-304.1 P-304.1 1.0 Definition and Purpose: To standardize and define the process by which the controlled Cleanroom environments (ISO Class 5, 7, and 8) and the general pharmacy prep area is cleaned, disinfected,

More information

SPECIAL APPLICATIONS

SPECIAL APPLICATIONS Page 1 SPECIAL APPLICATIONS The protection of microelectronics clean rooms using aspirating smoke detection systems requires special consideration. The physical configuration of the room(s) and the direction

More information

Laminar Flow Cabinets and Workstations

Laminar Flow Cabinets and Workstations VERTICAL AND HORIZONTAL HEPA FILTERED SYSTEMS FOR PROCESS OR OPERATOR PROTECTION Laminar Flow Cabinets and Workstations For procedures requiring protection from particulate contamination and for aseptic

More information

International Standard ISO 14644

International Standard ISO 14644 International Standard ISO 14644 Cleanrooms and associated controlled environments Praphon Angtrakool Food and Drug Administration 1 International Standard : ISO 14644 ISO 14644 consists of the following

More information

Series 18 Pass Thru Air Lock Cleanroom Entry System

Series 18 Pass Thru Air Lock Cleanroom Entry System OPERATION & MAINTENANCE INSTRUCTIONS FOR Series 18 Pass Thru Air Lock Cleanroom Entry System SOLUTIONS BUILT TO YOUR SPECIFICATIONS 8605 Wyoming Ave. N. Minneapolis MN 55445 fax: 763.425.2004 e-mail: sales@cleanairproducts.com

More information

Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,

Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715, 4658.4500 PLUMBING SYSTEMS; NEW CONSTRUCTION. Subpart 1. Installation. All plumbing systems must be installed and tested according to this chapter and chapter 4715, the Minnesota Plumbing Code. Subp. 2.

More information

USER INSTRUCTIONS FOR 10 LITRE PORTABLE DEHUMIDIFIER MODEL NO. DHMD102

USER INSTRUCTIONS FOR 10 LITRE PORTABLE DEHUMIDIFIER MODEL NO. DHMD102 USER INSTRUCTIONS FOR 10 LITRE PORTABLE DEHUMIDIFIER MODEL NO. DHMD102 THANK YOU FOR CHOOSING YOUR NEW DEHUMIDIFIER. BEFORE USING THE UNIT READ THESE INSTRUCTIONS FULLY AND RETAIN THEM FOR FUTURE REFERENCE

More information

WIBObarrier OCS - Open Containment Systems WIBObarrier CCS - Closed Containment Systems

WIBObarrier OCS - Open Containment Systems WIBObarrier CCS - Closed Containment Systems WIBOjekt and WIBObarrier Air Curtain Systems. The perfect protection for person, product and environment. Filling Weighing Sampling Research Safe handling with high potent products / API WIBObarrier OCS

More information

Class II Type B2 Laminar Flow Biological Safety Cabinets at Ordering Criteria for the National Institutes of Health

Class II Type B2 Laminar Flow Biological Safety Cabinets at Ordering Criteria for the National Institutes of Health Background Class II Type B2 Laminar Flow Biological Safety Cabinets at Ordering Criteria for the National Institutes of Health This document provides guidelines for the design and installation of Class

More information

Procedures for the Effective Use of Biological Safety Cabinets

Procedures for the Effective Use of Biological Safety Cabinets Procedures for the Effective Use of Biological Safety Cabinets APPROVAL DATE BY BIOHAZARDS SUBCOMMITTEE: August 10, 2012 SUPERSEDES: March 1, 2012 This corporate guideline/procedure is intended as a minimum

More information

Laboratory Design & Construction Guidelines

Laboratory Design & Construction Guidelines Laboratory Design & Construction Guidelines Department of Environmental Health & Safety EHS-M-35 Page 1 Issue Date: 03/01/10 General Health and Safety The USC Environmental Health and Safety Department

More information

Safety and Health Office WORKPLACE SAFETY CHECKLIST

Safety and Health Office WORKPLACE SAFETY CHECKLIST Location: Date: Inspected by: Safety and Health Office WORKPLACE SAFETY CHECKLIST WORK ENVIRONMENT Ventilation Removal of fumes and dust Temperature and humidity control Noise levels Vibration Lighting

More information

Hazardous Drug. Cleanroom. Standards

Hazardous Drug. Cleanroom. Standards Hazardous Drug Cleanroom Standards Module 3 Table of Contents Section A... 1 A.1 International Standards Organization (ISO) Classifications... 1 A.2 Hazardous Drug Cleanroom and Anteroom... 1 A.2.1 Location

More information

Spray Booth Guideline

Spray Booth Guideline Department of Development Service 135 North D Street, Perris CA. 92570 Phone: (951) 443-1029 Fax: (951) 943-3293 PURPOSE The intent of this guideline is to provide the information necessary to ensure that

More information

Questions & Answers (Q & A) Regarding Asbestos Treatment with the Fire Suppression and Renovation Project

Questions & Answers (Q & A) Regarding Asbestos Treatment with the Fire Suppression and Renovation Project Questions & Answers (Q & A) Regarding Asbestos Treatment with the Fire Suppression and Renovation Project The Watergate Community is currently in the process with the fire suppression and interior renovations

More information

THE UNIVERSITY OF NEWCASTLE- SCHOOL of BIOMEDICAL SCIENCES

THE UNIVERSITY OF NEWCASTLE- SCHOOL of BIOMEDICAL SCIENCES Page: 1 of 7 1. Purpose: 1.1. To describe the procedures to be used when dealing with chemical or microbiological spills. 2. Equipment: 2.1. Spill Kit 2.2. Miscellaneous items as listed 3. Materials: 3.1.

More information

EU GMP Annex 1 Update 2008: Airborne Particle Counting

EU GMP Annex 1 Update 2008: Airborne Particle Counting EU GMP Annex 1 Update 2008: Airborne Particle Counting Airborne Particle Counting for Pharmaceutical Facilities: Update 2008, EU GMP Annex 1 Morgan Polen - VP of Applications Technology, Lighthouse Worldwide

More information

Hygiene Standards for all Food Businesses

Hygiene Standards for all Food Businesses Hygiene Standards for all Food Businesses Food hygiene laws are not simply a list of rules. They are intended to let food business operators assess the risks to food safety in their business and apply

More information

APPLICATION FOR FITOUT OR PLAN ASSESSMENT UNDER THE FOOD ACT 2001

APPLICATION FOR FITOUT OR PLAN ASSESSMENT UNDER THE FOOD ACT 2001 Health Protection Service Howard Florey Centenary House, 25 Mulley Street, Holder ACT 2611 Locked Bag 5005, Weston Creek ACT 2611 Phone: (02) 6205 1700 Fax: (02) 6205 1705 Website: www.health.act.gov.au

More information

Environmental Monitoring

Environmental Monitoring Environmental Monitoring Purpose of Environmental Monitoring Critical process within the pharmaceutical and biotechnology industries. Determines the microbial and particulate content of cleanroom air and

More information

Biosafety Program University of Colorado. BSL-1 Audit Checklist

Biosafety Program University of Colorado. BSL-1 Audit Checklist PI first name: PI last name: username: IBC application #: Inspection Date: Lab Location: Department: email: best lab contact lab contact email Inspected by: Time BSL-1 Yes BSL-2 Yes A. Contamination Control

More information

LAMINAR FLOW FOR ALL YOUR NEEDS

LAMINAR FLOW FOR ALL YOUR NEEDS LAMINAR FLOW FOR ALL YOUR NEEDS 2 LAMINAR FLOW FOR ALL YOUR NEEDS EXPLORE TECNIPLAST COMPLETE RANGE OF LAMINAR FLOW SOLUTIONS: OUR CUTTING-EDGE TECNOLOGY IS AT YOUR SERVICE, TO ASSURE TOP ENVIRONMENTAL,

More information

CHILDCARE SETTINGS. Childcare Settings

CHILDCARE SETTINGS. Childcare Settings Childcare Settings This document provides guidelines and recommendations for cleaning childcare settings such as nurseries, crèches and schools in the event of a disease outbreak in the vicinity. Cleaning

More information

PI s Name Date Bldg./Rm# CDC Biosafety Level 3 (BSL-3)

PI s Name Date Bldg./Rm# CDC Biosafety Level 3 (BSL-3) PI s Name Date Bldg./Rm# CDC Biosafety Level 3 (BSL-3) Yes No 1. Is access to the laboratory limited or restricted at the discretion of the laboratory director when experiments are in progress? Yes No

More information

Restaurant & café guide

Restaurant & café guide 'Helping our customers stay in business by reducing risk' NZI Risk Solutions TM About NZI Risk Solutions NZI has extensive experience in providing expert risk management advice to help our commercial customers

More information

Guidelines for Mold Remediation (Removal)

Guidelines for Mold Remediation (Removal) Guidelines for Mold Remediation (Removal) Indoor mold growth, water damage, or musty odors should be addressed quickly. Removing mold growth and correcting the underlying cause of water accumulation can

More information

Risk Assessment: Biosafety Cabinet

Risk Assessment: Biosafety Cabinet Risk Assessment: Biosafety Cabinet Biosafety cabinets (BSCs) serve as primary containment devices for operations involving potential splashes, spills or aerosolization of hazardous biological materials.

More information

ISLE OF MAN FIRE & RESCUE SERVICE FIRE PRECAUTIONS LOGBOOK. Website www.iomfire.com

ISLE OF MAN FIRE & RESCUE SERVICE FIRE PRECAUTIONS LOGBOOK. Website www.iomfire.com ISLE OF MAN FIRE & RESCUE SERVICE FIRE PRECAUTIONS LOGBOOK Website www.iomfire.com ADDRESS OF PREMISES FIRE CERTIFICATE No. (where applicable).. LOCATION OF LOG BOOK. CONTENTS OF LOG BOOK Useful telephone

More information

SOUTH CAROLINA. Downloaded January 2011

SOUTH CAROLINA. Downloaded January 2011 SOUTH CAROLINA Downloaded January 2011 1401. General (II) B. When meals are catered to a facility, such meals shall be obtained from a meal service establishment graded by the Department, pursuant to R.61

More information

LAMINAR FLOW CABINETS

LAMINAR FLOW CABINETS LAMINAR FLOW CABINETS Vertical Laminar Flow Cabinets VLF 550 VLF650 VLF1000 VLF1200 VLF 1500 VLF1800 Monmouth Scientific's brand new range of Vertical laminar Flow (VLF) cabinets is available in six different

More information

Essam E. Khalil khalile1@asme.org

Essam E. Khalil khalile1@asme.org AIR-CONDITIONING SYSTEMS DEVELOPMENTS IN HOSPITALS: COMFORT, AIR QUALITY, AND ENERGY UTILIZATION Essam E. Khalil khalile1@asme.org PROFESSOR OF MECHANICAL ENGINEERING, CAIRO UNIVERSITY, EGYPT Abstract

More information

ASTCCR2 - SQA Unit Code H548 04 Carry out and complete clean-room cleaning operations

ASTCCR2 - SQA Unit Code H548 04 Carry out and complete clean-room cleaning operations Carry out and complete clean-room cleaning Overview 1 Carry out clean-room 2 Remove and store equipment, tools and materials after clean-room 3 Remove and dispose of contaminated material after clean-room

More information

CARE HOMES AND NURSING HOMES

CARE HOMES AND NURSING HOMES Care Homes and Nursing Homes: This document provides guidelines and recommendations for cleaning care homes and nursing homes in the event of a disease outbreak in the vicinity. Cleaning and disinfection

More information

Industrial Ventilation Design Guidebook Chapter 10 LOCAL VENTILATION

Industrial Ventilation Design Guidebook Chapter 10 LOCAL VENTILATION Industrial Ventilation Design Guidebook Chapter 10 LOCAL VENTILATION LARS OLANDER, LORRAINE CONROY, ILPO KULMALA, RICHARD P. GARRISON, MICHAEL ELLENBECKER, BERNHARD BIEGERT, BERNARD FLETCHER, HOWARD D.

More information

Fire Alarm system Installation Guide

Fire Alarm system Installation Guide Fire Alarm system Installation Guide Fire Alarm System Categories Systems designed for Protection of Property only, fall into two classifications P1 or P2. but a manual system is also needed, then this

More information

LONDON BOROUGH OF BROMLEY STANDARDS FOR HOUSES IN MULTIPLE OCCUPATION (HMO) INTRODUCTION

LONDON BOROUGH OF BROMLEY STANDARDS FOR HOUSES IN MULTIPLE OCCUPATION (HMO) INTRODUCTION LONDON BOROUGH OF BROMLEY STANDARDS FOR HOUSES IN MULTIPLE OCCUPATION (HMO) INTRODUCTION 1. Minimum Standards: This document sets out the minimum standards required in HMOs located within the London Borough

More information

Chemical Fume Hoods. Environmental Health and Safety 974-5084

Chemical Fume Hoods. Environmental Health and Safety 974-5084 Chemical Fume Hoods Environmental Health and Safety 974-5084 Regulatory References Prudent Practices in the Laboratory 2011 (National Research Council of The National Academies): Laboratory chemical hoods

More information

FlowFAST V. Vertical Laminar Airflow Cabinets PROTECTION, SAFETY, RELIABILITY. AND MORE.

FlowFAST V. Vertical Laminar Airflow Cabinets PROTECTION, SAFETY, RELIABILITY. AND MORE. Vertical Laminar Airflow Cabinets PROTECTION, SAFETY, RELIABILITY. AND MORE. Vertical Laminar Flow Cabinets BEYOND MINIMUM SAFETY REQUIREMENT Cabinets are ISO Class 3 vertical laminar flow cabinets which

More information

Air Shower Biosafety Changing Station with Pass-Through Box Pass-Through Box Automatic atomizer for no-contact hand disinfection

Air Shower Biosafety Changing Station with Pass-Through Box Pass-Through Box Automatic atomizer for no-contact hand disinfection Air Shower Biosafety Changing Station with Pass-Through Box Pass-Through Box Automatic atomizer for no-contact hand disinfection A wide range of products to meet the needs of transferring animals, operators,

More information

Florida s Cottage Food Industry and Beyond

Florida s Cottage Food Industry and Beyond Florida s Cottage Food Industry and Beyond The 2012 Educational Program Committee is pleased to share conference educational materials with you under the condition that they are used without alteration

More information

Construction Indoor Air Quality Management Plans for LEED. Matt Gregg, PE, LEED AP

Construction Indoor Air Quality Management Plans for LEED. Matt Gregg, PE, LEED AP Construction Indoor Air Quality Management Plans for LEED Matt Gregg, PE, LEED AP Agenda What is a Construction IAQ Management Plan? What are the LEED Requirements? What is the Mechanical Contractor s

More information

Checklist for a Physical Containment Level 2 (PC2) Laboratory Facility

Checklist for a Physical Containment Level 2 (PC2) Laboratory Facility Checklist for a Physical Containment Level 2 (PC2) Laboratory Facility (The Gene Technology Regulator s Guidelines for Certification of Facilities/Physical Containment Requirements applies) Facility Name:.

More information

PANDA SPRAY BOOTH FILTER INFORMATION

PANDA SPRAY BOOTH FILTER INFORMATION PANDA SPRAY BOOTH FILTER INFORMATION Our Spray Booth has been designed to reduce the risk of potential hazardous situations occurring. You must adhere to the specifications chart listed below when replacing

More information

Centre for Healthcare Related Infection Surveillance and Prevention & Tuberculosis Control

Centre for Healthcare Related Infection Surveillance and Prevention & Tuberculosis Control GUIDELINE Storage Design for Sterile and Non-Sterile Stock for New and Refurbished Healthcare Facilities TABLE OF CONTENTS GLOSSARY OF ACRONYMS, ABBREVIATIONS AND TERMS & DEFINITIONS... 2 1.0 INTRODUCTION...

More information

CLEANROOMS IN PHARMACEUTICAL PRODUCTION

CLEANROOMS IN PHARMACEUTICAL PRODUCTION Mikhail Kitain CLEANROOMS IN PHARMACEUTICAL PRODUCTION Bachelor s thesis Building Services March 2010 DESCRIPTION Date of the bachelor's thesis 14.03.2010 Author(s) Mikhail Kitain Degree programme and

More information

CORNER FRIDGE REFRIGERATION UNIT INSTALLATION AND OPERATION INSTRUCTIONS

CORNER FRIDGE REFRIGERATION UNIT INSTALLATION AND OPERATION INSTRUCTIONS CORNER FRIDGE REFRIGERATION UNIT INSTALLATION AND OPERATION INSTRUCTIONS D E F Y I N G C O N V E N T I O N Congratulations on your new Corner Fridge Your new corner fridge may have different functions

More information

A GUIDE TO AVA FOOD FACTORY GRADING SYSTEM

A GUIDE TO AVA FOOD FACTORY GRADING SYSTEM A GUIDE TO AVA FOOD FACTORY GRADING SYSTEM Introduction The main objective of the Food Factory Grading System is to ensure that the food manufacturers observe good manufacturing practices so as to produce

More information

Spetec. Laminar Flow Box. Portable Clean Room Technology

Spetec. Laminar Flow Box. Portable Clean Room Technology Spetec Laminar Flow Box Portable Clean Room Technology 1 Fundamentals Portable Clean Room Technology Laminar Flow The basis for the development of the clean room technology was first established in the

More information

CONTAMINATION CONTROL IN HOSPITALS. Isabelle Pautrel Ingénieur Clean Concept Patriarche & Co i.pautrel@patriarche.fr

CONTAMINATION CONTROL IN HOSPITALS. Isabelle Pautrel Ingénieur Clean Concept Patriarche & Co i.pautrel@patriarche.fr CONTAMINATION CONTROL IN HOSPITALS Isabelle Pautrel Ingénieur Clean Concept Patriarche & Co i.pautrel@patriarche.fr 1 P&CO 120 person Agency Savoie 94 person Paris 15 person Lyon 9 person Montréal 2 person

More information

Workspace and storage furnishings

Workspace and storage furnishings LISTA Compact Workspace and storage furnishings Test and inspection workstations With its modular test and inspection workstations, LISTA offers optimised solutions for modern quality assurance practices.

More information

PUBLIC RESTROOMS, DESIGN INTENT

PUBLIC RESTROOMS, DESIGN INTENT PUBLIC RESTROOMS, DESIGN INTENT 1.01 STRUCTURAL A. Where feasible, metal stud partitions will be constructed on a 6 high concrete curb. 1.02 MECHANICAL A. Restrooms will have a minimum of 15 air changes

More information

Public Works Department Sewer Backup No-Fault Assistance

Public Works Department Sewer Backup No-Fault Assistance Public Works Department Sewer Backup No-Fault Assistance Spanish Fork City and its employees will help to alleviate some of the problems created by this unfortunate backup. City employees are working hard

More information

STARTING A NEW FOOD BUSINESS? GUIDELINES FOR OPENING A CLASS 3 FOOD BUSINESS

STARTING A NEW FOOD BUSINESS? GUIDELINES FOR OPENING A CLASS 3 FOOD BUSINESS STARTING A NEW FOOD BUSINESS? GUIDELINES FOR OPENING A CLASS 3 FOOD BUSINESS Updated: July 2010 Contents Procedure for opening a new Food Business... 2 Basic Records... 3 Summary - Construction and Fitout

More information

Article 11 Laundry and Dry Cleaning

Article 11 Laundry and Dry Cleaning Article 11 Laundry and Dry Cleaning 41101. General Provisions. 41102. Construction Permit. 41103. Sanitary Permit. 41104. Materials and Construction of Physical Facilities. 41105. Sanitary Facilities Plumbing.

More information

ENVIRONMENTAL HEALTH PROFESSIONAL PRACTICE VOL II CHAPTER III. HOUSES IN MULTIPLE OCCUPATION Space Standards

ENVIRONMENTAL HEALTH PROFESSIONAL PRACTICE VOL II CHAPTER III. HOUSES IN MULTIPLE OCCUPATION Space Standards ENVIRONMENTAL HEALTH PROFESSIONAL PRACTICE VOL II CHAPTER III HOUSES IN MULTIPLE OCCUPATION Space Standards ADOPTED HOUSING STANDARDS:CATEGORY F HOUSES Houses within this category would be of a low priority

More information

Department: Manager: Safety Coordinator: Date:

Department: Manager: Safety Coordinator: Date: SAFETY and staff, regardless of hiring status or job position 1 1. Can staff name their department safety coordinator? 2. Is the Department Safety Binder current? 3. Do slip/trip hazards exist? 4. How

More information

HEPA-filtered Negative Air Machines and their Role in Creating Airborne Infection Isolation Rooms with the ECU AnteRoom. Frequently Asked Questions

HEPA-filtered Negative Air Machines and their Role in Creating Airborne Infection Isolation Rooms with the ECU AnteRoom. Frequently Asked Questions HEPA-filtered Negative Air Machines and their Role in Creating Airborne Infection Isolation Rooms with the ECU AnteRoom Frequently Asked Questions What is a negative air machine and why do I need one?

More information

Market Food Stalls Information Package

Market Food Stalls Information Package Market Food Stalls Information Package Health Services Last review April 2007 Modified July 2010 T:\HEALTH\1 INFORMATION MANAGEMENT\GUIDELINES\~Approvals\AP Traders - Food Market Stalls.doc REQUIREMENTS

More information

Asbestos in the Workplace: A Guide to Removal of Friable Asbestos Containing Material

Asbestos in the Workplace: A Guide to Removal of Friable Asbestos Containing Material Asbestos in the Workplace: A Guide to Removal of Friable Asbestos Containing Material Revised November 21, 2013 Application Code of Practice Where asbestos is present or believed to be present in a workplace

More information

Infection Control Risk Assessment : the Infection Preventionist s Role in Construction

Infection Control Risk Assessment : the Infection Preventionist s Role in Construction Infection Control Risk Assessment : the Infection Preventionist s Role in Construction Key Concepts Use of ICRA is an important element in an infection prevention program Should be an integral part of

More information

ASBESTOS AWARENESS IN THE WORKPLACE. This easy-to-use Leader s Guide is provided to assist in conducting a successful presentation.

ASBESTOS AWARENESS IN THE WORKPLACE. This easy-to-use Leader s Guide is provided to assist in conducting a successful presentation. ASBESTOS AWARENESS IN THE WORKPLACE This easy-to-use Leader s Guide is provided to assist in conducting a successful presentation. Featured are: INTRODUCTION: A brief description of the program and the

More information

GUIDELINE FOR THE DESIGN, CONSTRUCTION AND RECONSTRUCTION OF A FOOD HANDLING ESTABLISHMENT

GUIDELINE FOR THE DESIGN, CONSTRUCTION AND RECONSTRUCTION OF A FOOD HANDLING ESTABLISHMENT GUIDELINE FOR THE DESIGN, CONSTRUCTION AND RECONSTRUCTION OF A FOOD HANDLING ESTABLISHMENT This guideline provides general information to anyone proposing to construct a new food handling establishment,

More information

SPACE TYPE: LABORATORY (WET) FOR CHEMISTRY AND BIOLOGY

SPACE TYPE: LABORATORY (WET) FOR CHEMISTRY AND BIOLOGY SPACE TYPE: LABORATORY (WET) FOR CHEMISTRY AND BIOLOGY Construction Criteria The unit costs for (Wet) space types are based on the construction quality and design features in the following table. This

More information

Infection Control in the Dental Practice through Proper Sterilization

Infection Control in the Dental Practice through Proper Sterilization Midmark Corporation 60 Vista Drive P.O. Box 286 Versailles, Ohio 45380-0286 937-526-3662 midmark.com Infection Control in the Dental Practice through Proper Sterilization In today's world, the need for

More information

Restaurant and Café Risk Management Guide. Don t Risk It!

Restaurant and Café Risk Management Guide. Don t Risk It! property & liability Restaurant and Café Risk Management Guide Don t Risk It! About Lumley Insurance Lumley Insurance has extensive experience in restaurant insurance and risk management. This experience

More information

BENCH TECH 150. IVD In vitro diagnostic-medical device. General information Type of instrument: Bench chemical hood. Technical datasheet BenchTech150

BENCH TECH 150. IVD In vitro diagnostic-medical device. General information Type of instrument: Bench chemical hood. Technical datasheet BenchTech150 IVD In vitro diagnostic-medical device CND code: W0202059016 - CIVAB code: BENCH TECH 150 General information Type of instrument: Bench chemical hood. Model: Bench Tech 150. Code: 50-150-201 Description:

More information

School of Engineering University of Glasgow

School of Engineering University of Glasgow School of Engineering University of Glasgow Electronics Workshops Rankine Building 319A (2 Technicians) 510 (1 Technician) 712A (4 Technicians, 1 Modern Apprentice) James Watt South 619 (2 Technicians)

More information

- 2 - IMPORTANT SAFETY REMINDERS

- 2 - IMPORTANT SAFETY REMINDERS USER MANUAL IMPORTANT SAFETY REMINDERS This appliance should only be used for domestic cleaning, as described in this user guide. Please ensure that this guide is fully understood before operating the

More information

Recommendations for the Safe Use of Handling of Cytotoxic Drugs

Recommendations for the Safe Use of Handling of Cytotoxic Drugs Recommendations for the Safe Use of Handling of Cytotoxic Drugs Introduction Cytotoxic drugs are toxic compounds and are known to have carcinogenic, mutagenic and/or teratogenic potential. With direct

More information

Clean Water: Supply side potable water, not wastewater. Gray Water/Sewage: Wastewater originating from a drain (sink, toilet, urinal).

Clean Water: Supply side potable water, not wastewater. Gray Water/Sewage: Wastewater originating from a drain (sink, toilet, urinal). Procedures for Emergency Responses to Flooding and Building Water Intrusion PURPOSE: To establish uniform, sanitary, and systematic procedures for responding to flooding and water intrusion emergencies.

More information

The following standard practices, safety equipment, and facility requirements apply to BSL-1:

The following standard practices, safety equipment, and facility requirements apply to BSL-1: Section IV Laboratory Biosafety Level Criteria The essential elements of the four biosafety levels for activities involving infectious microorganisms and laboratory animals are summarized in Table 1 of

More information

Owner Cleaning and Maintenance Checklist

Owner Cleaning and Maintenance Checklist Owner Cleaning and Maintenance Checklist Whether in between rentals or on a yearly basis, it is important to keep your holiday home in great condition, which is why we have created this list to make it

More information

Spetec. Clean room. technology. Laminar flow box Clean room workbench CleanBoy Clean room cell Service, certification

Spetec. Clean room. technology. Laminar flow box Clean room workbench CleanBoy Clean room cell Service, certification Spetec Clean room technology Laminar flow box Clean room workbench CleanBoy Clean room cell Service, certification 1 Product overview PBS, FMS, and FBS series device families feature a modular design,

More information

MOHD NASRUL MOHAMAD NOOR

MOHD NASRUL MOHAMAD NOOR QUALITY ASSURANCE IN ASEPTIC WHO Collaborating Centre For Regulatory Control of Pharmaceuticals DISPENSING : MAINTENANCE OF CLEAN ROOM & EQUIPMENT Member of Pharmaceutical Inspection Cooperation Scheme

More information

Environmental Monitoring of Clean Rooms

Environmental Monitoring of Clean Rooms Environmental Monitoring of Raul Duarte President DDK Scientific, Corp. Copyright DDK Scientific, Corp. 2008, 2009, DDK Scientific, Corp. Proprietary A manufacturing facility for pharmaceutical products

More information

GMP ANNEX 1 REVISION 2008, INTERPRETATION OF MOST IMPORTANT CHANGES FOR THE MANUFACTURE OF STERILE MEDICINAL PRODUCTS

GMP ANNEX 1 REVISION 2008, INTERPRETATION OF MOST IMPORTANT CHANGES FOR THE MANUFACTURE OF STERILE MEDICINAL PRODUCTS PHARMACEUTICAL INSPECTION CONVENTION PHARMACEUTICAL INSPECTION CO-OPERATION SCHEME PI 032-2 8 January 2010 RECOMMENDATION GMP ANNEX 1 REVISION 2008, INTERPRETATION OF MOST IMPORTANT CHANGES FOR THE MANUFACTURE

More information

Biosafety Level 2 (BSL-2) Safety Guidelines

Biosafety Level 2 (BSL-2) Safety Guidelines BLS-4 Biosafety Level 2 (BSL-2) Safety Guidelines BSL-3 BSL-2 BSL-1 BSL-2 builds upon BSL-1. If you work in a lab that is designated a BSL-2, the microbes used pose moderate hazards to laboratory staff

More information

Current as of 11/10/08 1 of 1

Current as of 11/10/08 1 of 1 BEST PRACTICES STANDARDS FOR SCHOOLS UNDER CONSTRUCTION OR BEING PLANNED FOR CONSTRUCTION I. Site Layout A. School buildings shall be provided with a securable perimeter. A securable perimeter means that

More information

USP <797> Cleanroom Design and Environmental Monitoring. Andrew King, USP <797> Specialist CETA Member RCCP-SC

USP <797> Cleanroom Design and Environmental Monitoring. Andrew King, USP <797> Specialist CETA Member RCCP-SC USP Cleanroom Design and Environmental Monitoring Andrew King, USP Specialist CETA Member RCCP-SC Objectives The objectives of this presentation: To summarize basic cleanroom concepts and how

More information

Cleanroom. For. Sterile Manufacturing Facilities

Cleanroom. For. Sterile Manufacturing Facilities Cleanroom For Sterile Manufacturing Facilities Praphon Angtrakool Food and Drug Administration 1 WHO TRS No. 823 Annex 1, 1992 (1) General 17.1 The production of sterile preparations should be carried

More information

floater imports DF169 ECO AIR COOLER EVAPORATIVE AIR COOLER WITH IONIZER USER S MANUAL

floater imports DF169 ECO AIR COOLER EVAPORATIVE AIR COOLER WITH IONIZER USER S MANUAL floater imports DF169 ECO AIR COOLER EVAPORATIVE AIR COOLER WITH IONIZER USER S MANUAL WHAT IS AN ECO AIR COOLER? The ECO AIR COOLER uses evaporative cooling to provide an airflow that is cooler than the

More information

Your responsibilities if you have an automatic fire alarm. A handy guide for owners and responsible persons

Your responsibilities if you have an automatic fire alarm. A handy guide for owners and responsible persons Your responsibilities if you have an automatic fire alarm A handy guide for owners and responsible persons Kent Fire and Rescue Service Contents Your responsibilities if you have an automatic fire alarm

More information

ASTACEA4 Inspect complex/central air conditioning systems

ASTACEA4 Inspect complex/central air conditioning systems Overview This Unit covers the competences required to inspect complex/central air conditioning systems as defined by the CIBSE TM 44 Figure 1.1: Summary of system types and their component parts. The air

More information

Biological Safety Program

Biological Safety Program Risk Management & Safety Main Office, Wyoming Hall Phone: (307) 766-3277 Fax: (307)766-6116 Regulated Materials Management Center Phone: (307)766-3696 Fax: (307)766-3699 Web: www.uwyo.edu/ehs Email: UWEHS@uwyo.edu

More information

TEMPLE UNIVERSITY ENVIRONMENTAL HEALTH AND RADIATION SAFETY

TEMPLE UNIVERSITY ENVIRONMENTAL HEALTH AND RADIATION SAFETY Page 1 of 7 ISSUED: 5/00 REVISED: 08/06 1. Potential Releases of Radioactive Materials to Unrestricted Areas The Environmental Health and Safety Department (EHRS) must be notified immediately if an emergency

More information

Biosafety Level 2 Criteria

Biosafety Level 2 Criteria Biosafety Level 2 Criteria Biosafety in Microbiological and Biomedical Laboratories (BMBL) 5th Edition Biosafety Level 2 (BSL-2): Biosafety Level 2 builds upon BSL-1. BSL-2 is suitable for work involving

More information

BUILDING DYNAMICS, LLC

BUILDING DYNAMICS, LLC BUILDING DYNAMICS, LLC www.building-dynamics.com INDUSTRIAL HYGIENE 1216 Ashton Road Ashton, MD 20861 240.899.6926 (mobile) elight@building-dynamics.com HVAC ENGINEERING 703.963.0824 (mobile) jbailey@building-dynamics.com

More information

Decommissioning and clearance of laboratories

Decommissioning and clearance of laboratories Health and Safety Services Safety Note 65 Decommissioning and clearance of laboratories This Safety Note provides guidance to Schools on the decommissioning and clearance of laboratories prior to handing

More information

Fume Hood Questions and Answers

Fume Hood Questions and Answers Fume Hood Questions and Answers 1. When should I use a fume hood? Use a chemical fume hood anytime your work involves: Chemicals with a National Fire Protection Association (NFPA) Health rating of 3 or

More information

Laboratory Biosafety Level 3 Criteria

Laboratory Biosafety Level 3 Criteria Laboratory Biosafety Level 3 Criteria Biosafety in Microbiological and Biomedical Laboratories (BMBL) 5th Edition Section IV Biosafety Level 3 (BSL-3): Biosafety Level 3 is applicable to clinical, diagnostic,

More information

North Carolina State University Emergency Facilities Closure Checklist- Part I

North Carolina State University Emergency Facilities Closure Checklist- Part I North Carolina State University Emergency Facilities Closure Checklist- Part I Unplanned or spontaneous events often disrupt daily operations on campus. In the event that an incident may interrupt your

More information

EudraLex. The Rules Governing Medicinal Products in the European Union Volume 4

EudraLex. The Rules Governing Medicinal Products in the European Union Volume 4 Ref. Ares(2015)283695-23/01/2015 PT CHAPTER 5 PRODUCTION EUROPEAN COMMISSION HEALTH AND CONSUMERS DIRECTORATE-GENERAL Health systems and products Medicinal products quality, safety and efficacy EudraLex

More information

CLASSIFICATION OF CLEANROOMS

CLASSIFICATION OF CLEANROOMS CLASSIFICATION OF CLEANROOMS Cleanrooms are classified by the cleanliness of their air. The method most easily understood and most universally applied is the one suggested in the earlier versions (A to

More information

JANUARY 2013 GUIDANCE NOTES ON HEATING, VENTILATION AND AIR- CONDITIONING (HVAC) SYSTEMS FOR MANUFACTURERS OF ORAL SOLID DOSAGE FORMS

JANUARY 2013 GUIDANCE NOTES ON HEATING, VENTILATION AND AIR- CONDITIONING (HVAC) SYSTEMS FOR MANUFACTURERS OF ORAL SOLID DOSAGE FORMS JANUARY 2013 GUIDANCE NOTES ON HEATING, VENTILATION AND AIR- CONDITIONING (HVAC) SYSTEMS FOR MANUFACTURERS OF ORAL SOLID DOSAGE FORMS Introduction Heating, Ventilation and Air-Conditioning (HVAC) plays

More information

Everything you want to know about USP 797

Everything you want to know about USP 797 Everything you want to know about USP 797 Dr. Linda D. Lee Director of Operations Waste Management Healthcare Solutions September. 22, 2009 Goals High level understanding of USP 797 Who does it apply too

More information

Spetec Laminar Flow Systems. Operating Instructions

Spetec Laminar Flow Systems. Operating Instructions Spetec Laminar Flow Systems Operating Instructions 1 Spetec Laminar Flow Systems Operating Instructions Thank you for your trust in the Spetec clean room systems! Your chosen system is ideally suited for

More information

TYPICAL FIRE SAFETY INSPECTION VIOLATIONS

TYPICAL FIRE SAFETY INSPECTION VIOLATIONS TYPICAL FIRE SAFETY INSPECTION VIOLATIONS The following is a list of typical violations often found by inspectors and a generic solution. You can use this list to improve the safety of your facility, to

More information