Clean Room Design. By the end of this chapter, you will be able to: Introduction. Chapter 5
|
|
|
- Betty Lang
- 9 years ago
- Views:
Transcription
1 Chapter 5 Clean Room Design By the end of this chapter, you will be able to: l Explain the terms positive and negative pressure l Name and describe two categories of air flow in a clean room l List the main design features of a clean room l Explain the different grades of clean rooms Introduction In this chapter we will look at the specific design of a clean room including the walls, ceilings and floors as well as the practical needs of items such as workbenches, storage cupboards and chairs. We will examine how air is filtered to maintain the air quality and how air pressure prevents contamination of the cleanroom when people and equipment move into or out of the clean room. We will also take a brief look at the different types of clean room using particle counts to grade areas. Chapter 5: Clean Room Design 1
2 Aseptic Processing What is a Clean Room? Cleanrooms are usually self-contained facilities with their own dedicated ventilation systems. These control air quality, temperature and humidity. Air is filtered through High Efficiency Particulate Air (HEPA) filters which have a very small pore size. The filters collect and remove small particles, before air enters through the ceiling grilles. Ceiling HEPA filter Dirty air from the surrounding area is prevented from entering the cleanroom by controlling the air pressure in the cleanroom. l Cleanest room at highest pressure l Air flows from the cleanest to dirtiest areas Operation is at positive pressure, so ensures any airflow is pushed outwards from the room and dirty air cannot enter the room by default. The size of the aseptic suite depends on the maximum number of people who might use it at any one time. A fairly large room is more pleasant to work in, and the overall level of microbes in the environment is less affected by local air disturbances or contamination produced by individual workers. Clean Room Design Clean rooms fall into two categories, unidirectional and non-unidirectional. Build up of contaminants in the cleanroom is prevented by the flow of clean air at a rate of a minimum of 20 room air changes per hour. Unidirectional clean rooms normally have vertical airflow. Air flows downwards through HEPA filters located in the ceiling. The air is extracted through perforated flooring or grilles mounted on the walls at floor level. Note: airflow in a unidirectional clean room can also be horizontal. 2 Chapter 5: Clean Room Design
3 Chapter 5 Clean Room Design Non unidirectional clean rooms have air flows from HEPA filters located in various positions and returned through opposite locations. Filters may be distributed at equal intervals throughout the room or grouped over critical areas. The distribution and returns in this instance mean that the air flow may be turbulent in nature. The floors, walls and ceiling should be made of a smooth impervious material to ensure no particle shedding and easy cleaning. They should also be chemically resistant. All joins in the covering materials should be welded to ensure that there is no chance of seepage of cleaning fluids under the covering. Doors should be easy to open and, where necessary, two doors linked together to form an air lock. This prevents a sudden rush of air when a door is opened. All doors should be controlled to prevent unwanted flow of air from one area to another by opening of doors simultaneously. Benches should be made from one complete sheet of laminate because some liquids attack the adhesive at the joints and eventually cause lifting. Where possible made they should be made from stainless steel, Trespa or Conan which are impervious. They are usually wall-mounted to reduce dust collection and facilitate its detection and removal. When storage space is required, cupboards are preferable to drawers because they are easier to clean. Cupboards should be dust proof and smooth inside. Rounded beading may be used to cover dust-retaining angles within storage spaces and between fixed benches and walls. Small units on castors make useful additions to the working surface. Chairs must be adjustable and comfortable and covered with an impervious washable material. Trolleys should be made from stainless steel and be easily cleanable. Switches and sockets should be flush fitting and have plastic fingerplates. There should be no l shelves, window ledges or door frames where dust might settle. l pipes or ductwork. (False ceilings should be fully sealed with lighting recessed). l sinks or drains. Chapter 5: Clean Room Design 3
4 Aseptic Processing Hand washing facilities should be available external to changing rooms. Taps should be elbow or foot operated so that cleaned hands are not used to turn the water off. Soap should be conveniently dispensed from a wall or bench dispenser. Electric hand dryers or high quality paper towels should be used to dry hands. Remember: In summary, there should be: l smooth impervious surfaces l no ledges for dust to gather l surfaces which are easy to clean l transfer systems/airlocks to prevent contamination l no water sources Other aspects of design of the Cleanroom When designing a clean room there are many considerations to make. Here are a few but this is not an exhaustive list of good and bad practice. There should be a separate two-way transfer hatch system for the transfer of goods in and out of the cleanroom, to prevent contamination of environments. Material used in the construction should make cleaning and disinfection easy. For example there should be no joins between walls, floors and ceiling and all surfaces should be smooth and easy to clean. There should be a support room from which materials can be passed into and out of the cleanroom through hatches. Horizontal surfaces can accumulate particles and should be maintained by regular cleaning 4 Chapter 5: Clean Room Design
5 Chapter 5 Clean Room Design Airlocks should be installed between clean areas and adjoining dirty areas This is a close up of a high quality door and hinge. Glass is easily cleanable and enables safe access/egress. Equipment should not reduce the airflow and should not be placed anywhere it disturbs the airflow. This image shows an alcohol extraction unit situated in the spraying in zones of the preparation area. It works as a vacuum extracting the alcohol fumes. Many of the normal routes out of an aseptic suite can be difficult to access during a fire alarm due to the number of corridors out of the suite. This is an example of a specially constructed fire escape to the outside of the building from an aseptic suite. The outer door is fabricated as a standard fire escape door, however it is sealed behind a sheet of breakable glass. Chapter 5: Clean Room Design 5
6 Aseptic Processing Remember: Here are some other important considerations about the design and use of clean rooms. l The equipment should be arranged to minimise the amount of operator movement while maximising their comfort. l The number of staff in an aseptic processing room should be kept to a minimum. l The flow of personnel should be limited to minimise exit and entry especially in the critical area. l The number of transfers to the critical area of the clean room or isolator should be minimised. l Excessive movement adjacent to the critical area should be restricted. Test Yourself Can you list 10 features to take into consideration when designing/fitting out a cleanroom? Chapter 5: Clean Room Design
7 Chapter 5 Clean Room Design Environmental Control The highest standard of environmental control will be included in the design of the clean room. Processes should be designed to give optimal personnel and product flow through the unit. We will look at this in more detail later. Aseptic processes in the clean room are designed to minimise the exposure of sterile components to the potential hazards of the manufacturing process. There are a maximum number of particles of different sizes allowed in the clean room at rest and during operation. Grade Particle size at rest Particle count (max particle /m3) Particle size in operation 0.5 µm 5 µm 0.5 µm 5 µm A 3, ,500 1 B 3, ,000 2,000 C 350,000 2,000 3,500,000 20,000 D 3,500,000 20,000 Not defined Not defined The table shows the values for the maximum particle count for different particle sizes within the different grades of clean room (Reference: Orange Guide 2007) Examples of Cleanroom Grade Grade A Laminar air flow cabinets and isolators, i.e. the point of fill. Grade B The aseptic room. Grade C The preparation room inner support room. Grade D Support, filling and isolator rooms. Information: Isolators may be sited in Grade C or D rooms check your local procedures). Chapter 5: Clean Room Design 7
8 Aseptic Processing Alarm Systems Fire and smoke alarms must be fitted in all areas of the facility. Staff must respond to alarms by evacuating the area immediately. An air supply alarm should be fitted which detects if there is a failure in the air supply to the facility. If this is triggered, work must cease immediately. In this simulated image the red lamps would indicate a problem with the cabinets. Work should only restart when the air supply has been reinstated and been running constantly for a minimum period. In the absence of a validation exercise of the cleanup time, this period should be one hour. Here is an example of an alarm panel with lamps showing the working status of the LAFC and Isolator cabinets. The green lamp indicates that the cabinet is running correctly in this image. Malfunctioning and Problems Problems should be reported immediately so that appropriate action can be taken. Anything unusual should be reported even though it may seem trivial, as it could be a precursor to a major fault or incident. You should report any procedural deviations or difficulties. Reports may be filed with the Estates Department at the hospital for any routine work that may need to be done within the cleanroom or supporting areas. Specialist cleanroom companies may be required to carry out more complicated tasks. Air pressure The air pressure in clean rooms is highest in the aseptic filling room ( cleanest ) and drops incrementally to the corridors. The usual practice is to start at 45 Pascals and come down in 10 Pascals increments, with the final differential being at least 15 Pascals. This will depend on the layout of your clean rooms. 8 Chapter 5: Clean Room Design
9 Chapter 5 Clean Room Design Clean Room Suite Layout The following plans are examples of clean room suite layouts for Isolators and LAFC s and show the flow of work and air. Airflow direction Workflow direction Step over Bench Transfer Hatches Isolator Suite Layout Laminar Air Flow Cabinet (LAFC) Suite Layout Isolator EU grade A LAFC EU grade A Clean Room EU Grade D Clean Room EU Grade B 2nd Change Room EU Grade D at rest 2nd Change Room EU Grade B at rest Inner Support Room 1st Change Room Outer Support Room Inner Support Room EU Grade D (clean room) Outer Support Room 1st Change Room EU Grade D at rest Chapter 5: Clean Room Design 9
10 Aseptic Processing Activity Make a sketch plan of your unit and mark on it: l Flow of products l Flow of people l Flow of documents l Air pressures in different parts of the unit. 10 Chapter 5: Clean Room Design
11 Chapter 5 Clean Room Design Questions Q1 What is the maximum allowable number of particles in a Grade A and Grade B clean room at rest and in operation? Complete the table below to show your answers. Grade A At rest In operation Particle size: 0.5 μm 5 μm 0.5 μm 5 μm Max number of particles allowed: Grade B At rest In operation Particle size: 0.5 μm 5 μm 0.5 μm 5 μm Max number of particles allowed: Q2 Why are airlocks installed between clean areas and adjoining less clean areas? (2) Chapter 5: Clean Room Design 11
12 Aseptic Processing Q3 What s the difference between a unidirectional and a non-unidirectional airflow? (6) 12 Chapter 5: Clean Room Design
Cleaning. By the end of this chapter, you will be able to: Introduction. Definitions. Chapter 9
Chapter 9 By the end of this chapter, you will be able to: l Define the terms cleaning, decontamination, disinfection l List the factors that affect disinfection l Describe the aims of a cleaning schedule
Cleanroom Solutions Ltd T: 01273 760 060 F: 01273 760 061 E: [email protected] W: www.cleanroom-solutions.co.uk
Cleanroom Solutions Ltd T: 01273 760 060 F: 01273 760 061 E: [email protected] W: Introduction Cleanroom Solutions Ltd has a wealth of experience together with a solid track record in the
Environmental Monitoring
Chapter 10 Environmental Monitoring By the end of this chapter, you will be able to: l List the types of environmental testing l Name three types of checks that are carried out to ensure the isolator is
Sample Pharmacy CLEANING AND SANITIZING PROCEDURE P-304.1
P-304.1 1.0 Definition and Purpose: To standardize and define the process by which the controlled Cleanroom environments (ISO Class 5, 7, and 8) and the general pharmacy prep area is cleaned, disinfected,
SPECIAL APPLICATIONS
Page 1 SPECIAL APPLICATIONS The protection of microelectronics clean rooms using aspirating smoke detection systems requires special consideration. The physical configuration of the room(s) and the direction
Laminar Flow Cabinets and Workstations
VERTICAL AND HORIZONTAL HEPA FILTERED SYSTEMS FOR PROCESS OR OPERATOR PROTECTION Laminar Flow Cabinets and Workstations For procedures requiring protection from particulate contamination and for aseptic
International Standard ISO 14644
International Standard ISO 14644 Cleanrooms and associated controlled environments Praphon Angtrakool Food and Drug Administration 1 International Standard : ISO 14644 ISO 14644 consists of the following
Series 18 Pass Thru Air Lock Cleanroom Entry System
OPERATION & MAINTENANCE INSTRUCTIONS FOR Series 18 Pass Thru Air Lock Cleanroom Entry System SOLUTIONS BUILT TO YOUR SPECIFICATIONS 8605 Wyoming Ave. N. Minneapolis MN 55445 fax: 763.425.2004 e-mail: [email protected]
Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,
4658.4500 PLUMBING SYSTEMS; NEW CONSTRUCTION. Subpart 1. Installation. All plumbing systems must be installed and tested according to this chapter and chapter 4715, the Minnesota Plumbing Code. Subp. 2.
USER INSTRUCTIONS FOR 10 LITRE PORTABLE DEHUMIDIFIER MODEL NO. DHMD102
USER INSTRUCTIONS FOR 10 LITRE PORTABLE DEHUMIDIFIER MODEL NO. DHMD102 THANK YOU FOR CHOOSING YOUR NEW DEHUMIDIFIER. BEFORE USING THE UNIT READ THESE INSTRUCTIONS FULLY AND RETAIN THEM FOR FUTURE REFERENCE
WIBObarrier OCS - Open Containment Systems WIBObarrier CCS - Closed Containment Systems
WIBOjekt and WIBObarrier Air Curtain Systems. The perfect protection for person, product and environment. Filling Weighing Sampling Research Safe handling with high potent products / API WIBObarrier OCS
Class II Type B2 Laminar Flow Biological Safety Cabinets at Ordering Criteria for the National Institutes of Health
Background Class II Type B2 Laminar Flow Biological Safety Cabinets at Ordering Criteria for the National Institutes of Health This document provides guidelines for the design and installation of Class
Procedures for the Effective Use of Biological Safety Cabinets
Procedures for the Effective Use of Biological Safety Cabinets APPROVAL DATE BY BIOHAZARDS SUBCOMMITTEE: August 10, 2012 SUPERSEDES: March 1, 2012 This corporate guideline/procedure is intended as a minimum
Laboratory Design & Construction Guidelines
Laboratory Design & Construction Guidelines Department of Environmental Health & Safety EHS-M-35 Page 1 Issue Date: 03/01/10 General Health and Safety The USC Environmental Health and Safety Department
Safety and Health Office WORKPLACE SAFETY CHECKLIST
Location: Date: Inspected by: Safety and Health Office WORKPLACE SAFETY CHECKLIST WORK ENVIRONMENT Ventilation Removal of fumes and dust Temperature and humidity control Noise levels Vibration Lighting
Hazardous Drug. Cleanroom. Standards
Hazardous Drug Cleanroom Standards Module 3 Table of Contents Section A... 1 A.1 International Standards Organization (ISO) Classifications... 1 A.2 Hazardous Drug Cleanroom and Anteroom... 1 A.2.1 Location
Spray Booth Guideline
Department of Development Service 135 North D Street, Perris CA. 92570 Phone: (951) 443-1029 Fax: (951) 943-3293 PURPOSE The intent of this guideline is to provide the information necessary to ensure that
Questions & Answers (Q & A) Regarding Asbestos Treatment with the Fire Suppression and Renovation Project
Questions & Answers (Q & A) Regarding Asbestos Treatment with the Fire Suppression and Renovation Project The Watergate Community is currently in the process with the fire suppression and interior renovations
THE UNIVERSITY OF NEWCASTLE- SCHOOL of BIOMEDICAL SCIENCES
Page: 1 of 7 1. Purpose: 1.1. To describe the procedures to be used when dealing with chemical or microbiological spills. 2. Equipment: 2.1. Spill Kit 2.2. Miscellaneous items as listed 3. Materials: 3.1.
EU GMP Annex 1 Update 2008: Airborne Particle Counting
EU GMP Annex 1 Update 2008: Airborne Particle Counting Airborne Particle Counting for Pharmaceutical Facilities: Update 2008, EU GMP Annex 1 Morgan Polen - VP of Applications Technology, Lighthouse Worldwide
Hygiene Standards for all Food Businesses
Hygiene Standards for all Food Businesses Food hygiene laws are not simply a list of rules. They are intended to let food business operators assess the risks to food safety in their business and apply
APPLICATION FOR FITOUT OR PLAN ASSESSMENT UNDER THE FOOD ACT 2001
Health Protection Service Howard Florey Centenary House, 25 Mulley Street, Holder ACT 2611 Locked Bag 5005, Weston Creek ACT 2611 Phone: (02) 6205 1700 Fax: (02) 6205 1705 Website: www.health.act.gov.au
Environmental Monitoring
Environmental Monitoring Purpose of Environmental Monitoring Critical process within the pharmaceutical and biotechnology industries. Determines the microbial and particulate content of cleanroom air and
Biosafety Program University of Colorado. BSL-1 Audit Checklist
PI first name: PI last name: username: IBC application #: Inspection Date: Lab Location: Department: email: best lab contact lab contact email Inspected by: Time BSL-1 Yes BSL-2 Yes A. Contamination Control
LAMINAR FLOW FOR ALL YOUR NEEDS
LAMINAR FLOW FOR ALL YOUR NEEDS 2 LAMINAR FLOW FOR ALL YOUR NEEDS EXPLORE TECNIPLAST COMPLETE RANGE OF LAMINAR FLOW SOLUTIONS: OUR CUTTING-EDGE TECNOLOGY IS AT YOUR SERVICE, TO ASSURE TOP ENVIRONMENTAL,
CHILDCARE SETTINGS. Childcare Settings
Childcare Settings This document provides guidelines and recommendations for cleaning childcare settings such as nurseries, crèches and schools in the event of a disease outbreak in the vicinity. Cleaning
PI s Name Date Bldg./Rm# CDC Biosafety Level 3 (BSL-3)
PI s Name Date Bldg./Rm# CDC Biosafety Level 3 (BSL-3) Yes No 1. Is access to the laboratory limited or restricted at the discretion of the laboratory director when experiments are in progress? Yes No
Restaurant & café guide
'Helping our customers stay in business by reducing risk' NZI Risk Solutions TM About NZI Risk Solutions NZI has extensive experience in providing expert risk management advice to help our commercial customers
Guidelines for Mold Remediation (Removal)
Guidelines for Mold Remediation (Removal) Indoor mold growth, water damage, or musty odors should be addressed quickly. Removing mold growth and correcting the underlying cause of water accumulation can
Risk Assessment: Biosafety Cabinet
Risk Assessment: Biosafety Cabinet Biosafety cabinets (BSCs) serve as primary containment devices for operations involving potential splashes, spills or aerosolization of hazardous biological materials.
ISLE OF MAN FIRE & RESCUE SERVICE FIRE PRECAUTIONS LOGBOOK. Website www.iomfire.com
ISLE OF MAN FIRE & RESCUE SERVICE FIRE PRECAUTIONS LOGBOOK Website www.iomfire.com ADDRESS OF PREMISES FIRE CERTIFICATE No. (where applicable).. LOCATION OF LOG BOOK. CONTENTS OF LOG BOOK Useful telephone
SOUTH CAROLINA. Downloaded January 2011
SOUTH CAROLINA Downloaded January 2011 1401. General (II) B. When meals are catered to a facility, such meals shall be obtained from a meal service establishment graded by the Department, pursuant to R.61
LAMINAR FLOW CABINETS
LAMINAR FLOW CABINETS Vertical Laminar Flow Cabinets VLF 550 VLF650 VLF1000 VLF1200 VLF 1500 VLF1800 Monmouth Scientific's brand new range of Vertical laminar Flow (VLF) cabinets is available in six different
Essam E. Khalil [email protected]
AIR-CONDITIONING SYSTEMS DEVELOPMENTS IN HOSPITALS: COMFORT, AIR QUALITY, AND ENERGY UTILIZATION Essam E. Khalil [email protected] PROFESSOR OF MECHANICAL ENGINEERING, CAIRO UNIVERSITY, EGYPT Abstract
ASTCCR2 - SQA Unit Code H548 04 Carry out and complete clean-room cleaning operations
Carry out and complete clean-room cleaning Overview 1 Carry out clean-room 2 Remove and store equipment, tools and materials after clean-room 3 Remove and dispose of contaminated material after clean-room
CARE HOMES AND NURSING HOMES
Care Homes and Nursing Homes: This document provides guidelines and recommendations for cleaning care homes and nursing homes in the event of a disease outbreak in the vicinity. Cleaning and disinfection
Industrial Ventilation Design Guidebook Chapter 10 LOCAL VENTILATION
Industrial Ventilation Design Guidebook Chapter 10 LOCAL VENTILATION LARS OLANDER, LORRAINE CONROY, ILPO KULMALA, RICHARD P. GARRISON, MICHAEL ELLENBECKER, BERNHARD BIEGERT, BERNARD FLETCHER, HOWARD D.
Fire Alarm system Installation Guide
Fire Alarm system Installation Guide Fire Alarm System Categories Systems designed for Protection of Property only, fall into two classifications P1 or P2. but a manual system is also needed, then this
LONDON BOROUGH OF BROMLEY STANDARDS FOR HOUSES IN MULTIPLE OCCUPATION (HMO) INTRODUCTION
LONDON BOROUGH OF BROMLEY STANDARDS FOR HOUSES IN MULTIPLE OCCUPATION (HMO) INTRODUCTION 1. Minimum Standards: This document sets out the minimum standards required in HMOs located within the London Borough
Chemical Fume Hoods. Environmental Health and Safety 974-5084
Chemical Fume Hoods Environmental Health and Safety 974-5084 Regulatory References Prudent Practices in the Laboratory 2011 (National Research Council of The National Academies): Laboratory chemical hoods
FlowFAST V. Vertical Laminar Airflow Cabinets PROTECTION, SAFETY, RELIABILITY. AND MORE.
Vertical Laminar Airflow Cabinets PROTECTION, SAFETY, RELIABILITY. AND MORE. Vertical Laminar Flow Cabinets BEYOND MINIMUM SAFETY REQUIREMENT Cabinets are ISO Class 3 vertical laminar flow cabinets which
Air Shower Biosafety Changing Station with Pass-Through Box Pass-Through Box Automatic atomizer for no-contact hand disinfection
Air Shower Biosafety Changing Station with Pass-Through Box Pass-Through Box Automatic atomizer for no-contact hand disinfection A wide range of products to meet the needs of transferring animals, operators,
Florida s Cottage Food Industry and Beyond
Florida s Cottage Food Industry and Beyond The 2012 Educational Program Committee is pleased to share conference educational materials with you under the condition that they are used without alteration
Construction Indoor Air Quality Management Plans for LEED. Matt Gregg, PE, LEED AP
Construction Indoor Air Quality Management Plans for LEED Matt Gregg, PE, LEED AP Agenda What is a Construction IAQ Management Plan? What are the LEED Requirements? What is the Mechanical Contractor s
Checklist for a Physical Containment Level 2 (PC2) Laboratory Facility
Checklist for a Physical Containment Level 2 (PC2) Laboratory Facility (The Gene Technology Regulator s Guidelines for Certification of Facilities/Physical Containment Requirements applies) Facility Name:.
PANDA SPRAY BOOTH FILTER INFORMATION
PANDA SPRAY BOOTH FILTER INFORMATION Our Spray Booth has been designed to reduce the risk of potential hazardous situations occurring. You must adhere to the specifications chart listed below when replacing
Centre for Healthcare Related Infection Surveillance and Prevention & Tuberculosis Control
GUIDELINE Storage Design for Sterile and Non-Sterile Stock for New and Refurbished Healthcare Facilities TABLE OF CONTENTS GLOSSARY OF ACRONYMS, ABBREVIATIONS AND TERMS & DEFINITIONS... 2 1.0 INTRODUCTION...
CLEANROOMS IN PHARMACEUTICAL PRODUCTION
Mikhail Kitain CLEANROOMS IN PHARMACEUTICAL PRODUCTION Bachelor s thesis Building Services March 2010 DESCRIPTION Date of the bachelor's thesis 14.03.2010 Author(s) Mikhail Kitain Degree programme and
CORNER FRIDGE REFRIGERATION UNIT INSTALLATION AND OPERATION INSTRUCTIONS
CORNER FRIDGE REFRIGERATION UNIT INSTALLATION AND OPERATION INSTRUCTIONS D E F Y I N G C O N V E N T I O N Congratulations on your new Corner Fridge Your new corner fridge may have different functions
A GUIDE TO AVA FOOD FACTORY GRADING SYSTEM
A GUIDE TO AVA FOOD FACTORY GRADING SYSTEM Introduction The main objective of the Food Factory Grading System is to ensure that the food manufacturers observe good manufacturing practices so as to produce
Spetec. Laminar Flow Box. Portable Clean Room Technology
Spetec Laminar Flow Box Portable Clean Room Technology 1 Fundamentals Portable Clean Room Technology Laminar Flow The basis for the development of the clean room technology was first established in the
CONTAMINATION CONTROL IN HOSPITALS. Isabelle Pautrel Ingénieur Clean Concept Patriarche & Co [email protected]
CONTAMINATION CONTROL IN HOSPITALS Isabelle Pautrel Ingénieur Clean Concept Patriarche & Co [email protected] 1 P&CO 120 person Agency Savoie 94 person Paris 15 person Lyon 9 person Montréal 2 person
Workspace and storage furnishings
LISTA Compact Workspace and storage furnishings Test and inspection workstations With its modular test and inspection workstations, LISTA offers optimised solutions for modern quality assurance practices.
PUBLIC RESTROOMS, DESIGN INTENT
PUBLIC RESTROOMS, DESIGN INTENT 1.01 STRUCTURAL A. Where feasible, metal stud partitions will be constructed on a 6 high concrete curb. 1.02 MECHANICAL A. Restrooms will have a minimum of 15 air changes
STARTING A NEW FOOD BUSINESS? GUIDELINES FOR OPENING A CLASS 3 FOOD BUSINESS
STARTING A NEW FOOD BUSINESS? GUIDELINES FOR OPENING A CLASS 3 FOOD BUSINESS Updated: July 2010 Contents Procedure for opening a new Food Business... 2 Basic Records... 3 Summary - Construction and Fitout
Article 11 Laundry and Dry Cleaning
Article 11 Laundry and Dry Cleaning 41101. General Provisions. 41102. Construction Permit. 41103. Sanitary Permit. 41104. Materials and Construction of Physical Facilities. 41105. Sanitary Facilities Plumbing.
ENVIRONMENTAL HEALTH PROFESSIONAL PRACTICE VOL II CHAPTER III. HOUSES IN MULTIPLE OCCUPATION Space Standards
ENVIRONMENTAL HEALTH PROFESSIONAL PRACTICE VOL II CHAPTER III HOUSES IN MULTIPLE OCCUPATION Space Standards ADOPTED HOUSING STANDARDS:CATEGORY F HOUSES Houses within this category would be of a low priority
Department: Manager: Safety Coordinator: Date:
SAFETY and staff, regardless of hiring status or job position 1 1. Can staff name their department safety coordinator? 2. Is the Department Safety Binder current? 3. Do slip/trip hazards exist? 4. How
HEPA-filtered Negative Air Machines and their Role in Creating Airborne Infection Isolation Rooms with the ECU AnteRoom. Frequently Asked Questions
HEPA-filtered Negative Air Machines and their Role in Creating Airborne Infection Isolation Rooms with the ECU AnteRoom Frequently Asked Questions What is a negative air machine and why do I need one?
Asbestos in the Workplace: A Guide to Removal of Friable Asbestos Containing Material
Asbestos in the Workplace: A Guide to Removal of Friable Asbestos Containing Material Revised November 21, 2013 Application Code of Practice Where asbestos is present or believed to be present in a workplace
Infection Control Risk Assessment : the Infection Preventionist s Role in Construction
Infection Control Risk Assessment : the Infection Preventionist s Role in Construction Key Concepts Use of ICRA is an important element in an infection prevention program Should be an integral part of
ASBESTOS AWARENESS IN THE WORKPLACE. This easy-to-use Leader s Guide is provided to assist in conducting a successful presentation.
ASBESTOS AWARENESS IN THE WORKPLACE This easy-to-use Leader s Guide is provided to assist in conducting a successful presentation. Featured are: INTRODUCTION: A brief description of the program and the
GUIDELINE FOR THE DESIGN, CONSTRUCTION AND RECONSTRUCTION OF A FOOD HANDLING ESTABLISHMENT
GUIDELINE FOR THE DESIGN, CONSTRUCTION AND RECONSTRUCTION OF A FOOD HANDLING ESTABLISHMENT This guideline provides general information to anyone proposing to construct a new food handling establishment,
SPACE TYPE: LABORATORY (WET) FOR CHEMISTRY AND BIOLOGY
SPACE TYPE: LABORATORY (WET) FOR CHEMISTRY AND BIOLOGY Construction Criteria The unit costs for (Wet) space types are based on the construction quality and design features in the following table. This
Infection Control in the Dental Practice through Proper Sterilization
Midmark Corporation 60 Vista Drive P.O. Box 286 Versailles, Ohio 45380-0286 937-526-3662 midmark.com Infection Control in the Dental Practice through Proper Sterilization In today's world, the need for
Restaurant and Café Risk Management Guide. Don t Risk It!
property & liability Restaurant and Café Risk Management Guide Don t Risk It! About Lumley Insurance Lumley Insurance has extensive experience in restaurant insurance and risk management. This experience
BENCH TECH 150. IVD In vitro diagnostic-medical device. General information Type of instrument: Bench chemical hood. Technical datasheet BenchTech150
IVD In vitro diagnostic-medical device CND code: W0202059016 - CIVAB code: BENCH TECH 150 General information Type of instrument: Bench chemical hood. Model: Bench Tech 150. Code: 50-150-201 Description:
School of Engineering University of Glasgow
School of Engineering University of Glasgow Electronics Workshops Rankine Building 319A (2 Technicians) 510 (1 Technician) 712A (4 Technicians, 1 Modern Apprentice) James Watt South 619 (2 Technicians)
- 2 - IMPORTANT SAFETY REMINDERS
USER MANUAL IMPORTANT SAFETY REMINDERS This appliance should only be used for domestic cleaning, as described in this user guide. Please ensure that this guide is fully understood before operating the
Recommendations for the Safe Use of Handling of Cytotoxic Drugs
Recommendations for the Safe Use of Handling of Cytotoxic Drugs Introduction Cytotoxic drugs are toxic compounds and are known to have carcinogenic, mutagenic and/or teratogenic potential. With direct
Clean Water: Supply side potable water, not wastewater. Gray Water/Sewage: Wastewater originating from a drain (sink, toilet, urinal).
Procedures for Emergency Responses to Flooding and Building Water Intrusion PURPOSE: To establish uniform, sanitary, and systematic procedures for responding to flooding and water intrusion emergencies.
The following standard practices, safety equipment, and facility requirements apply to BSL-1:
Section IV Laboratory Biosafety Level Criteria The essential elements of the four biosafety levels for activities involving infectious microorganisms and laboratory animals are summarized in Table 1 of
Owner Cleaning and Maintenance Checklist
Owner Cleaning and Maintenance Checklist Whether in between rentals or on a yearly basis, it is important to keep your holiday home in great condition, which is why we have created this list to make it
Spetec. Clean room. technology. Laminar flow box Clean room workbench CleanBoy Clean room cell Service, certification
Spetec Clean room technology Laminar flow box Clean room workbench CleanBoy Clean room cell Service, certification 1 Product overview PBS, FMS, and FBS series device families feature a modular design,
MOHD NASRUL MOHAMAD NOOR
QUALITY ASSURANCE IN ASEPTIC WHO Collaborating Centre For Regulatory Control of Pharmaceuticals DISPENSING : MAINTENANCE OF CLEAN ROOM & EQUIPMENT Member of Pharmaceutical Inspection Cooperation Scheme
Environmental Monitoring of Clean Rooms
Environmental Monitoring of Raul Duarte President DDK Scientific, Corp. Copyright DDK Scientific, Corp. 2008, 2009, DDK Scientific, Corp. Proprietary A manufacturing facility for pharmaceutical products
GMP ANNEX 1 REVISION 2008, INTERPRETATION OF MOST IMPORTANT CHANGES FOR THE MANUFACTURE OF STERILE MEDICINAL PRODUCTS
PHARMACEUTICAL INSPECTION CONVENTION PHARMACEUTICAL INSPECTION CO-OPERATION SCHEME PI 032-2 8 January 2010 RECOMMENDATION GMP ANNEX 1 REVISION 2008, INTERPRETATION OF MOST IMPORTANT CHANGES FOR THE MANUFACTURE
Biosafety Level 2 (BSL-2) Safety Guidelines
BLS-4 Biosafety Level 2 (BSL-2) Safety Guidelines BSL-3 BSL-2 BSL-1 BSL-2 builds upon BSL-1. If you work in a lab that is designated a BSL-2, the microbes used pose moderate hazards to laboratory staff
Current as of 11/10/08 1 of 1
BEST PRACTICES STANDARDS FOR SCHOOLS UNDER CONSTRUCTION OR BEING PLANNED FOR CONSTRUCTION I. Site Layout A. School buildings shall be provided with a securable perimeter. A securable perimeter means that
USP <797> Cleanroom Design and Environmental Monitoring. Andrew King, USP <797> Specialist CETA Member RCCP-SC
USP Cleanroom Design and Environmental Monitoring Andrew King, USP Specialist CETA Member RCCP-SC Objectives The objectives of this presentation: To summarize basic cleanroom concepts and how
Cleanroom. For. Sterile Manufacturing Facilities
Cleanroom For Sterile Manufacturing Facilities Praphon Angtrakool Food and Drug Administration 1 WHO TRS No. 823 Annex 1, 1992 (1) General 17.1 The production of sterile preparations should be carried
floater imports DF169 ECO AIR COOLER EVAPORATIVE AIR COOLER WITH IONIZER USER S MANUAL
floater imports DF169 ECO AIR COOLER EVAPORATIVE AIR COOLER WITH IONIZER USER S MANUAL WHAT IS AN ECO AIR COOLER? The ECO AIR COOLER uses evaporative cooling to provide an airflow that is cooler than the
Your responsibilities if you have an automatic fire alarm. A handy guide for owners and responsible persons
Your responsibilities if you have an automatic fire alarm A handy guide for owners and responsible persons Kent Fire and Rescue Service Contents Your responsibilities if you have an automatic fire alarm
ASTACEA4 Inspect complex/central air conditioning systems
Overview This Unit covers the competences required to inspect complex/central air conditioning systems as defined by the CIBSE TM 44 Figure 1.1: Summary of system types and their component parts. The air
Biological Safety Program
Risk Management & Safety Main Office, Wyoming Hall Phone: (307) 766-3277 Fax: (307)766-6116 Regulated Materials Management Center Phone: (307)766-3696 Fax: (307)766-3699 Web: www.uwyo.edu/ehs Email: [email protected]
TEMPLE UNIVERSITY ENVIRONMENTAL HEALTH AND RADIATION SAFETY
Page 1 of 7 ISSUED: 5/00 REVISED: 08/06 1. Potential Releases of Radioactive Materials to Unrestricted Areas The Environmental Health and Safety Department (EHRS) must be notified immediately if an emergency
Biosafety Level 2 Criteria
Biosafety Level 2 Criteria Biosafety in Microbiological and Biomedical Laboratories (BMBL) 5th Edition Biosafety Level 2 (BSL-2): Biosafety Level 2 builds upon BSL-1. BSL-2 is suitable for work involving
Decommissioning and clearance of laboratories
Health and Safety Services Safety Note 65 Decommissioning and clearance of laboratories This Safety Note provides guidance to Schools on the decommissioning and clearance of laboratories prior to handing
Fume Hood Questions and Answers
Fume Hood Questions and Answers 1. When should I use a fume hood? Use a chemical fume hood anytime your work involves: Chemicals with a National Fire Protection Association (NFPA) Health rating of 3 or
Laboratory Biosafety Level 3 Criteria
Laboratory Biosafety Level 3 Criteria Biosafety in Microbiological and Biomedical Laboratories (BMBL) 5th Edition Section IV Biosafety Level 3 (BSL-3): Biosafety Level 3 is applicable to clinical, diagnostic,
North Carolina State University Emergency Facilities Closure Checklist- Part I
North Carolina State University Emergency Facilities Closure Checklist- Part I Unplanned or spontaneous events often disrupt daily operations on campus. In the event that an incident may interrupt your
EudraLex. The Rules Governing Medicinal Products in the European Union Volume 4
Ref. Ares(2015)283695-23/01/2015 PT CHAPTER 5 PRODUCTION EUROPEAN COMMISSION HEALTH AND CONSUMERS DIRECTORATE-GENERAL Health systems and products Medicinal products quality, safety and efficacy EudraLex
CLASSIFICATION OF CLEANROOMS
CLASSIFICATION OF CLEANROOMS Cleanrooms are classified by the cleanliness of their air. The method most easily understood and most universally applied is the one suggested in the earlier versions (A to
JANUARY 2013 GUIDANCE NOTES ON HEATING, VENTILATION AND AIR- CONDITIONING (HVAC) SYSTEMS FOR MANUFACTURERS OF ORAL SOLID DOSAGE FORMS
JANUARY 2013 GUIDANCE NOTES ON HEATING, VENTILATION AND AIR- CONDITIONING (HVAC) SYSTEMS FOR MANUFACTURERS OF ORAL SOLID DOSAGE FORMS Introduction Heating, Ventilation and Air-Conditioning (HVAC) plays
Everything you want to know about USP 797
Everything you want to know about USP 797 Dr. Linda D. Lee Director of Operations Waste Management Healthcare Solutions September. 22, 2009 Goals High level understanding of USP 797 Who does it apply too
Spetec Laminar Flow Systems. Operating Instructions
Spetec Laminar Flow Systems Operating Instructions 1 Spetec Laminar Flow Systems Operating Instructions Thank you for your trust in the Spetec clean room systems! Your chosen system is ideally suited for
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS The following is a list of typical violations often found by inspectors and a generic solution. You can use this list to improve the safety of your facility, to