OPERATING AND MAINTENANCE MANUAL FOR HORIZONTAL IMMERSION HEATED STEAM BOILERS. Technical Control Systems Limited MODELS "HIHS"
|
|
- Helen Phillips
- 7 years ago
- Views:
Transcription
1 OPERATING AND MAINTENANCE MANUAL FOR HORIZONTAL IMMERSION HEATED STEAM BOILERS Technical Control Systems Limited MODELS "HIHS"
2 Technical Control Systems Ltd Treefield Industrial Estate Gildersome, Leeds LS27 7JU Phone Fax Internet -- IMPORTANT -- Always reference the full model number and serial number when calling the factory. WARNING / CAUTION 1. Mains water should be piped to the feed water 'break' tank, and the tank completely filled with water before energizing. 2. Due to the rigors of transportation, all connections should be checked for tightness before boiler is placed in operation. 3. Site pipework from the main valve on the boiler to the steam using equipment must be completed before putting the boiler in operation. 4. KEEP AWAY FROM LIVE ELECTRICAL CIRCUITS. Do not perform any maintenance, make any adjustments, or replace any components inside the control panel with the high voltage power supply turned on. Under certain circumstances, dangerous potentials may exist even when the power supply is off. To avoid casualties, always turn the power supply safety switch to off, before performing any maintenance or adjustment procedure. 5. Generalized instructions and procedures cannot anticipate all situations. For this reason, only qualified installers should perform the installation. A qualified installer is a person who has licensed training and a working knowledge of the applicable codes regulation, tools, equipment, and methods necessary for safe installation of a steam fired water heater. If questions regarding installation arise, check with your local plumbing and electrical inspectors for proper procedures and codes. If you cannot obtain the required information, contact the company. Page 2
3 TABLE OF CONTENTS SECTION TITLE PAGE I GENERAL DESCRIPTION AND CONSTRUCTION 4 II INSTALLATION AND OPERATION 5 III SCHEDULED MAINTENANCE AND SERVICING 9 IV TROUBLESHOOTING 10 Page 3
4 SECTION I - GENERAL DESCRIPTION AND CONSTRUCTION GENERAL DESCRIPTION This book describes a TCS packaged horizontal immersion heated steam boiler (HIHS), which is a stationary, self contained unit. The complete assembly on a standard unit consists of the pressure vessel, immersion heating elements, and a control panel built to IEC Optional equipment may be supplied with your unit. Please consult the product drawing for details specific to your assembly. The unit is factory assembled, insulated, jacketed, primed, painted, piped, tested, and ready for service connections. CONSTRUCTION PRESSURE VESSEL Standard Vessel Construction: The standard pressure vessel is constructed of all welded carbon steel, designed and built in accordance with BS5500 and stamped, certified, and registered with Lloyds. SERVICE CONNECTIONS The boiler is supplied with the following service connections WATER SUPPLY The feed water 'break' tank is situated to the side of the boiler and mains water should be piped to this tank which has B.S.P. connections as sized in the dimension list. An overflow connection is provided on this tank and this must be piped to a safe drainage point. STEAM OUTLET The steam outlet is fitted with a main valve which should be piped to the steam using equipment. STEAM SAFETY VALVE Ensure that the outlet connection of the valve is free from packing material, keep the outlet pipe as short as possible and ensure it is adequately supported, fit outlet pipework of equal or larger size then the valve outlet, direct the outlet pipework to a safe point, where the discharge is visible and there is no risk of injury to persons or damage to equipment if the valve operates, where the outlet pipework is directed upwards an open drain must be provided at it's lowest point. BLOWDOWN CONNECTIONS There are two blowdown valves on the boiler, the main valve at the rear of the boiler, and the water gauge glass blowdown valve. The outlet pipe from each blowdown valve must lead to a blowdown vessel or other safe discharge point OUTER SHELL, INSULATION, AND SUPPORTS The pressure vessel is encapsulated in 2-inches of high-density fiberglass insulation. The protective shell is constructed of galvanised steel and is coated with a durable blue hammertone finish. The entire vessel is supported on heavyduty integrally welded steel supports for sturdy floor mounting. Page 4
5 HEATING ELEMENTS The steam boiler is supplied with high quality factory installed heavy duty "Incoloy" sheathed elements of low watts density (11.6 W/cm²), arranged for multi-stage progressive load control, mounted with B.S.P. threaded ferrules to facilitate easy field replacement. Page 5
6 SECTION II INSTALLATION AND OPERATION WARNING / CAUTION The voltage of the mains and control system is high enough to endanger life, when the equipment is opened for inspection and testing, it will sometimes expose live parts. Work on live equipment is only to be undertaken by qualified personnel who are fully aware of the risks involved and who have taken precautions to avoid direct contact with dangerous voltages. So far as is possible low voltage equipment must be entirely disconnected and isolated from the system before any repairs or maintenance is commenced, and tests made to prove that the relevant equipment is completely dead. Positive safeguards should be employed to prevent the circuit from being inadvertently energised whilst work is in progress and a DANGER warning notice should always be displayed in the vicinity of exposed live connections. If the unit is painted or insulated on site, care should be taken not to paint or insulate over any nameplates. These plates should be accessible and legible at all times to inspectors, and information from the TCS rating plate must be used when ordering parts from the factory. BOILER SITING 1. Adequate space should be provided for removal of heating elements and in front of the control panel for electrical connections to be made safely. 2. Unit should be sited on a firm and level base to permit proper drainage. PIPING INSTALLATION Piping to the unit should be sized to meet the design conditions, as dictated by good engineering practices. CAUTION: No valve of any type should be installed in the safety valve pipework. ELECTRICAL CONNECTIONS Terminate the main supply cable on the control panel main isolator. Ensure that a full screw check for tightness is carried out before switch on, connections for main cables between both fuses and contactors, contactors and elements can become loose during transport and if so will overheat. It is also essential to remove shrouds from fuse carriers and check clamp connections to copper bars. These are tightened by means of an Alen Key or screw connection. Page 6
7 FILLING THE BOILER Begin with all water valves closed. Open the steam valve. Open cold water supply valve(if fitted), and fill tank with cold water. Open valve between the tank and the pump. Ensure all stage selector switches are in off position. Close main isolator and turn panel live on/off switch to on position. The extra low water level warning lamp(red) will illuminate and the feed pump should automatically start and run until water level in boiler reaches the correct level. While ever the pump is running, the pump running indicator light should be illuminated(green). If the water level in the feed tank does not drop then the pump requires bleeding. Loosen the bolt adjacent to the pump outlet until all the air is vented. CAUTION: During the initial filling of the pressure vessel the pump may deliver more water than can be replaced by the cold water feed. Do not operate pump without the tank being filled with water as damage to the pump could result. STARTUP Carry out the following procedure on the initial start up of the boiler and on every subsequent occasion when re-starting the boiler after a shutdown. 1. Open the steam valve. 2. Open all the valves in the water line to the top up tank and feed pump. 3. Open the water gauge valves. 4. Close the boiler and water gauge glass blowdown valves. 5. Switch on main power isolator. 6. Switch on the boiler control circuit and load stage switches. 7. The panel indicator lights will come on showing that the controls have been energised and the water feed pump will start and continue operating until the water in the boiler has reached the correct level. 8. Once the water in the boiler has reached the correct level the elements will automatically be energised and the load stage contactors will be heard to click in progressively. The steam pressure control will control the on-off cycle of the elements once the boiler is operating. The low water relay will immediately shut off the power to the elements should the water in the boiler drop to an unsafe level and will only re-energise the elements when the water has regained a safe level in the boiler. A red indication light is provided to give warning of this condition. The element thermostat will shut off the power to the elements should the temperature of the elements rise above the permitted level. when this happens the red light on the front of the boiler will light up. The boiler cannot be restarted until the thermostat has been manually reset. Page 7
8 SHUTDOWN Turn panel live selector switch to the off position. Open each blowdown valve for a few seconds to clear away accumulated sediment. Where untreated feed water is used, increased sediment inside the boiler should be removed by blowing down for a longer period. Page 8
9 SECTION III - SCHEDULED MAINTENANCE AND SERVICING WARNING / CAUTION Before performing any maintenance procedure, make certain boiler water supply and electrical power supply is OFF and cannot accidentally be turned on. WEEKLY INSPECTION 1. Make sure that the pipe from the safety valve outlet is not damaged and that it continues to a safe blow-off point. 2. With the boiler under pressure, lift test lever on safety valve and let steam discharge for a second or two. This proves the free operation of the safety valve. 3. Check the low water cut-out relay is operating correctly as follows: With the boiler switched on, but with little or no steam pressure, open the boiler blowdown valve allowing the water in the boiler to drop below the safe working level, at which point the elements should de-energise and an audible click heard as the contactors 'drop out'. The red warning light situated on the facia panel should indicate a low water condition. THREE MONTHLY 1. Check the elements for continuity and insulation. 2. Inspect the boiler for leaks and replace gaskets as necessary. 3. Clean the water gauge sight glass. If any leakage is evident renew the gasket. 4. Remove the strainer situated in the feedwater line between the tank and pump and clean thoroughly before replacing. 5. Remove copper pipework to pressure switch and pressure gauge and flush with water to clean out sediment. 6. Check the free operation of the anti-vac valve by removing the protective cap and depressing the plunger. NOTE: This check should only be done with the boiler shut-down and no pressure in the vessel. ANNUALLY 1. Drain and flush the feedwater tank. Clean any filters in the tank, in the feedwater line or the feedwater pump. 2. Remove the elements and clean off any scale build-up. 3. Inspect boiler shell for scale and lime and clean out. 4. Remove and clean the three water electrodes, taking care not to crack the porcelain. After replacement check the operation of the low water cut-off relay and of the water feed pump. 5. Check all control panel connections for tightness. 6. Check contactors for free action and clean contacts. Page 9
10 SECTION IV TROUBLESHOOTING (See separate component O&M for additional details.) Symptom Probable Cause Corrective Action / Remedy Gradual loss of heating capacity Gauge glass not showing correct level Element failure Blockage in pipe or gauge cock. Renew faulty elements Remove gauge cock and clean cock and pipe Pump overfills boiler Level probe failure Check connections and replace probe if necessary Boiler not filling with water or hot water returning to tank Check valve faulty Remove check valve and clean valve seat, or renew check valve. * Red symptom indicates that equipment should be shut down immediately and cause of malfunction corrected before unit is re-started or serious damage may result. Page 10
OPERATING AND MAINTENANCE MANUAL FOR COMMERCIAL ELECTRIC WATER HEATER ELECTRIC HEATER COMPANY BASE MODEL SE
OPERATING AND MAINTENANCE MANUAL FOR COMMERCIAL ELECTRIC WATER HEATER ELECTRIC HEATER COMPANY BASE MODEL SE HUBBELL ELECTRIC HEATER COMPANY P.O. BOX 288 STRATFORD, CT 06615 PHONE: (203) 378-2659 FAX: (203)
More informationOil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
More informationElectric Water Heater
Electric Water Heater Operation and Installation Manual (LIMITED WARRANTY AND TANK REPLACEMENT POLICY) The following information should be noted at time of installation and retained for future reference.
More informationMaxi Pressurisation Units (Maxi, Maxi Plus & HP)
Maxi Pressurisation Units (Maxi, Maxi Plus & HP) Installation and Maintenance Instructions Contents 1 Dimensions 3 1.1 Installation 4 1.1 Mains/boosted cold water inlet 4 1.2 Connection to the system 5
More informationCARING FOR YOUR WATER HEATER
http://waterheatertimer.org/troubleshoot-rheem-tankless-water-heater.html Water Heater Inspections CARING FOR YOUR WATER HEATER Venting System (Direct Vent Only) The venting system should be inspected
More informationPBX Series Quick Fit Connector Bimetallic Steam Traps
6262100/6 IM-P626-01 ST Issue 6 PBX Series Quick Fit Connector Bimetallic Steam Traps Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Commissioning
More informationInstallation and User Instructions Unvented Electric Storage Water Heater Models: S10UNV, S15UNV.
Installation and User Instructions Unvented Electric Storage Water Heater Models: S10UNV, S15UNV. MULTIPOINT Please read and understand these instructions before starting work. Please leave this leaflet
More informationSpeedflow Undersink Unvented Water Heater. Models SF10K and SF15K. Instruction Manual
Speedflow Undersink Unvented Water Heater Models SF10K and SF15K Instruction Manual Version 2.0 May 2009 Hyco SpeedFLOW UnVENTED WATER HEATER Models SF10K (10 Litres) and SF15K (15 Litres) 1. Introduction
More informationCDS TROUBLESHOOTING SECTION I. VACUUM. 1.0. Weak vacuum at wand. Gauge reads normal (10hg to 14hg)
CDS TROUBLESHOOTING SECTION I. VACUUM 1.0. Weak vacuum at wand. Gauge reads normal (10hg to 14hg) 1.1. Clogged hoses or wand tube. Disconnect hoses and carefully check for an obstruction. 1.2. Excessive
More informationwith MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions.
B Installation & Maintenance Instructions MM-414 Series 150E and 157E Low Water Cut-Off/Pump Controllers For Steam Boilers and Other Level Control Applications A Typical Applications: Primary or secondary
More informationFactory owners must ensure the boiler is:
Factory owners must ensure the boiler is: * Registered with the Boilers and Pressure Vessels Division, Labour Department * Examined by an appointed examiner and has a valid certificate of fitness * Supervised
More informationFloat and Thermostatic Traps Series H, C and X
Hoffman Specialty Installation & Maintenance Instructions HS-(E) and Thermostatic Traps Series H, C and X Series C & NPT Series C NPT Series X NPT Series C NPT Series H Ratings Maximum Max. Operating NPT
More informationINSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS FOR EXHEAT INDUSTRIAL IMMERSION HEATERS (INCLUDING FLAMEPROOF)
INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS FOR EXHEAT INDUSTRIAL IMMERSION HEATERS (INCLUDING FLAMEPROOF) Please read these instructions thoroughly before installation and ensure they are passed
More informationSF15K SF05KSS, SF10KSS
Product Instruction Manual Speedflow SF05K, SF10K & SF15K SF05KSS, SF10KSS & SF15KSS Undersink unvented water heater V15.6/6 Version 3.2 Jan 2015 Thank you for purchasing a Hyco Speedflow unvented water
More informationBlowdown vessels Meeting the requirements of HSE PM60
Blowdown vessels Meeting the requirements of HSE PM60 BDV60 blowdown vessels complete range of equipment for the safe disposal of boiler blowdown Boiler blowdown Steam boilers must be blown down to remove
More informationSERVICE MANUAL RESIDENTIAL ELECTRIC AND LIGHT DUTY COMMERCIAL ELECTRIC WATER HEATERS. Troubleshooting Guide and Instructions for Service
RESIDENTIAL ELECTRIC AND LIGHT DUTY COMMERCIAL ELECTRIC WATER HEATERS SERVICE MANUAL Troubleshooting Guide and Instructions for Service (To be performed ONLY by qualified service providers) Models Covered
More informationINDIRECT WATER HEATER. Installation and Operating Instruction Manual
INDIRECT WATER HEATER Installation and Operating Instruction Manual Maximum supply temperature to heat exchanger must not exceed 180 F (82 C). Safety Warning: Indirect water heaters are heat-producing
More informationIndirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS
Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS Contents Page Ratings and Specifications..................... 2 Installation Requirements......................
More informationFLASH TANK ECONOMIZER PRODUCT GUIDE
FLASH TANK ECONOMIZER PRODUCT GUIDE Overview A flash tank is used to recover blowdown energy in the form of flash steam and blowdown. This can only be used with a deaerator or some other pressurized device.
More informationCooling Systems. Table of Contents
Cooling Systems Table of Contents Sub-Headings Safety 2 s 2 Cautions 2 Notes 2 Introduction 2 General Specifications 2 ISB Engine 2 ISC Engine 2 Caterpillar 3126 Engine 2 Types of Coolant 3 ISB Engine
More information5.23.22 STEAM AND CONDENSATE PIPING AND PUMPS DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL. 1.01 Purpose:
PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is
More information! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-217(I) Series 150S and 157S (Snap Switch, All Models except 157S-RB-P)
Series 150S and 157S (Snap Switch, All Models except 157S-RB-P) Low Water Cut-Off/Pump Controllers For Steam Boilers and Other Level Control Applications McDonnell & Miller Installation & Maintenance Instructions
More informationBERMAD Fire Protection
Model: 400E-2M BERMAD Electrically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Safety First BERMAD believes that the safety of personnel working with and around
More informationUse & Care Manual. Electric Tankless Water Heaters. With Installation Instructions for the Installer AP15447 (10/10)
Use & Care Manual With Installation Instructions for the Installer Electric Tankless Water Heaters The purpose of this manual is twofold: one, to provide the installer with the basic directions and recommendations
More informationSTAINLESS STEEL TANK TABLE OF CONTENTS TROUBLESHOOTING... 1 TESTING WATER TEMPERATURE... 3 TANK & JACKET ASSEMBLY... 4.
TABLE OF CONTENTS STAINLESS TROUBLESHOOTING... 1 TESTING WATER TEMPERATURE... 3 & JACKET ASSEMBLY... 4 SST Section 052506 1 Troubleshooting performed by untrained personnel could result in electrical
More informationHeat Pump Water Heater IOM Manual
Heat Pump Water Heater IOM Manual Installation Operation & Maintenance This manual is intended as an aid to qualified service personnel for proper installation, operation and maintenance of the heat pump
More informationSeaward Products OWNER S MANUAL WATER HEATERS. Serial Number:
Seaward Products WATER HEATERS OWNER S MANUAL Serial Number: IMPORTANT SAFETY INSTRUCTIONS WARNING When using electrical appliances, basic safety precautions to reduce the risk of fire, electrical shock,
More informationCommercial Electric Water Heaters 9kW 900kW Input Models
INSTALLATION AND SERVICE MANUAL Commercial Electric Water Heaters 9kW 900kW Input Models CHP-I&S-01 Installation and service must be performed by Qualified Service Personnel Only. WARRANTY Factory warranty
More informationMax primary circuit temperature 90ºC Max primary circuit temp. 90ºC Max secondary circuit temperature 45ºC Max secondary circuit temp.
EGLISH 1 Product description exchanger equipped with an electronic control unit and circulation pump for the primary circuit. All Aqua-Mex variants can be ordered with an interior coil of either titanium
More information11. COOLING SYSTEM 11-0 COOLING SYSTEM BET & WIN 50
11 COOLING SYSTEM SERVICE INFORMATION------------------------------------------------ 11-1 TROUBLESHOOTING----------------------------------------------------- 11-1 RADIATOR ------------------------------------------------------------------
More informationInstallation and Operating Instruction Manual
Electric Mini Tank Water Heaters CMT-1.3 CMT-2.5 CMT-4.0 CMT-ST70 Tempering valve Optionally available Installation and Operating Instruction Manual Table of Contents Important Safety Instructions 3 General
More informationModel: 400E-2M. Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset. Installation Operation Maintenance. Application Engineering
Model: 400E-2M Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Application Engineering BERMAD 1. Safety First BERMAD believes that the safety
More informationModel 800 Residential Steam Humidifier Owner s Manual. Includes Safety & Operating Instructions and Warranty Information
Steam Humidifier Model 800 Residential Steam Humidifier Owner s Manual Includes Safety & Operating Instructions and Warranty Information READ AND SAVE THESE INSTRUCTIONS TABLE OF CONTENTS Safety Cautions...
More informationConsortiwm Awdurdodau Lleol Cymru Consortium Local Authorities Wales
Consortiwm Awdurdodau Lleol Cymru Consortium Local Authorities Wales SPECIFICATION FOR BOILER SERVICING MAINTENANCE Maintenance Module 11 March 2012 issue This document has been compiled by the Engineering
More informationASME Packaged Indirect Fired Water Heater
Utilizes Or HTHW To Heat Domestic Water, Semi-Instantaneous or Storage Type Model BW Features Reliable Only high grade materials used in construction to ensure long operating life Hydrastone cement lining
More informationA.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps
A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps Troubleshooting Submersible Pumps Fuse overload or circuit breaker trips when motor is started 1. Incorrect line voltage. Check the line
More informationINSTALLATION, OPERATION, MAINTENANCE AND PARTS MANUAL 'J' SERIES - GAS FIRED STEAM BOILERS (6J - 60J)
INSTALLATION, OPERATION, MAINTENANCE AND PARTS MANUAL 'J' SERIES - GAS FIRED STEAM BOILERS (6J - 60J) This Manual must be available to the boiler operator at all times. JGAS-E-10 2008 In case of Emergency
More informationSHOWER WATER HEATER MODEL BS 35 / 45 / 60 BS 35 E / 45 E / 60 E OPERATION AND INSTALLATION INSTRUCTIONS
SHOWER WATER HEATER MODEL BS 35 / 45 / 60 BS 35 E / 45 E / 60 E OPERATION AND INSTALLATION INSTRUCTIONS 2 This water heater must be installed (water and electrical installation), commissioned and serviced
More informationService Guide 12/27/03 TESTING, SERVICE & REPAIR GUIDE (For SH Space Heating Models & RA Water Heating Models)
TESTING, SERVICE & REPAIR GUIDE (For SH Space Heating Models & RA Water Heating Models) WARNING - HIGH VOLTAGE AC electrical circuits are connected to this heater. Do not attempt any service work on the
More informationOWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608
Electric Water Heater OWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608 If your water Heater is Damaged or you have questions
More informationINSTALLATION & MAINTENANCE MANUAL TURBOPOWER GAS, OIL & GAS/OIL WATER HEATER
INSTALLATION & MAINTENANCE MANUAL TURBOPOWER GAS, OIL & GAS/OIL WATER HEATER Installation and service must be performed by a qualified service installer, service agency or the gas supplier. Oil Gas/Oil
More informationBradlee Boilers Ltd. Instruction Manual for starting up Bradlee Hire Boiler from Cold
Bradlee Boilers Ltd Instruction Manual for starting up Bradlee Hire Boiler from Cold To be read in conjunction with Bradlee Boiler guide to Commissioning Boilers Document Ref: HM001 1. Ensure that all
More informationOperators manual Basic water heater
Operators manual Basic water heater Isotemp Basic water heater has been designed and produced to ensure that your water heater will give long and trouble free operation for many years. It is important,
More informationTHE BOILING WATER DISPENSER INSTALLATION & OPERATING INSTRUCTIONS
THE BOILING WATER DISPENSER INSTALLATION & OPERATING INSTRUCTIONS Applied Energy Products Limited, Morley Way, Peterborough, PE2 9JJ, UK Telephone: +44 (0) 844 372 7761 / Fax: +44 (0) 84 372 7762 Website:
More informationHeating, Ventilation, Air Conditioning and Refrigeration (HVACR)
Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety
More informationFLUORESCENT UV- RING LIGHT OPERATING INSTRUCTION
FLUORESCENT UV- RING LIGHT OPERATING INSTRUCTION Caution! UV-radiation of this device is in the range of UV-A (320-400 nm). Direct exposure to eyes shall therefore be avoided. UV protection glasses shall
More informationCTV-1500 Cooling Tower Vacuum Operating & Maintenance Manual
CTV-1500 Cooling Tower Vacuum Operating & Maintenance Manual Goodway Technologies Corporation 420 West Avenue Stamford, CT 06902-6384 (203)359-4708 Sales: 1-800-333-7467 Customer Service: 1-800-370-2855
More informationTrouble Shooting. Pump
Trouble Shooting Pump Trouble Possible Cause Remedy Oil leaking in the area of water pump crankshaft Worn crankshaft seal, bad bearing, grooved shaft, or failure of retainer o-ring. Excessive play on crankshaft
More informationCOMMERCIAL ELECTRIC WATER HEATER INSTALLATION & OPERATING INSTRUCTION MANUAL
COMMERCIAL ELECTRIC WATER HEATER La A version Spanish espanola language de version estas of instrucciones these instructions se puede is available obtener al by escribirle contacting a la the fábrica company
More informationMini Tank. Electric Mini Tank Water Heaters WM-1.0 WM-2.5 WM-4.0 WM-6.0. Installation and Operating Instruction Manual
Mini Tank Electric Mini Tank Water Heaters WM-1.0 WM-2.5 WM-4.0 WM-6.0 Installation and Operating Instruction Manual Table of Contents Important Safety Instructions 3 General Information 3/6 Technical
More information3620 W 11th Streetб Houston, TX 77008 Telephone: 713-635-6291 Email: sales@kellogg-american.com Website: www.kellogg-american.com
Unpackaging & Handling Be sure to carefully inspect the unit before accepting the shipment. If any damage has occurred document it with the trucking company immediately. Contact your Kellogg Distributor
More informationSELECTION, APPLICATION AND MAINTENANCE
DIESEL PROTECTION SYSTEMS Automatic Diesel Engine Shut Down System for Safe Area Applications SELECTION, APPLICATION AND MAINTENANCE Series 300 Series 310 SYSTEM DESCRIPTION Suitable for attended engine
More informationSL280UHV SERIES GAS FURNACE WARNING
2010 Lennox Industries Inc. Dallas, Texas, USA 506677 01 11/2010 Supersedes 506409 01 SL280UHV SERIES GAS FURNACE Litho U.S.A. FIRE OR EXPLOSION HAZARD. Failure to follow safety warnings exactly could
More informationUtility Distribution Systems
Utility Distribution Systems 6/2012 A0011037 1 WARRANTY This equipment is warranted to be free from defects in materials and workmanship, under normal use and service, for a period of 12 months from date
More informationAquamax Australia Pty Ltd ABN 17 138 189 689
Aquamax Australia Pty Ltd ABN 17 138 189 689 AQUAMAX SERVICE MANUAL Stainless Steel Electric Water Heaters AQ0903010-A Revision: A Published: November 2012 E80 to E315 Series Contents Introduction... 3
More informationOperating instructions
6302 6959 02/2006 GB For the user Operating instructions Logano G215 WS Oil and gas-fired boilers Please read thoroughly before use. Overview Regulations and directives Installation: 90/396/EEC gas appliance
More informationINSTALLATION INSTRUCTIONS & HOME OWNERS MANUAL EEMAX ELECTRIC TANKLESS WATER HEATERS IMPORTANT SAFETY INFORMATION
INSTALLATION INSTRUCTIONS & HOME OWNERS MANUAL EEMAX ELECTRIC TANKLESS WATER HEATERS IMPORTANT SAFETY INFORMATION When installing or using any high voltage electrical appliance, basic safety precautions
More informationMini Tank water heater Electric undersink Water heaters GL 2.5 - GL 4 - GL 6+
Mini Tank water heater Electric undersink Water heaters GL 2.5 - GL 4 - GL 6+ IMPORTANT SAFETY INSTRUCTIONS WARNING When using electrical appliances, safety precautions to reduce the risk of fire, electric
More informationService manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.
Website: www.andico.com.au Service manual CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. - ONLY FOR AUTHORISED SERVICE PERSONNEL. MODELS: MPK1-09CR-QB8 MPK1-12ER-QB6
More informationElectric Mini Tank Water Heaters WM-2.5 & WM-4.0
Electric Mini Tank Water Heaters WM-2.5 & WM-4.0 Installation and Operating Instruction Manual Table of Contents Important Safety Instructions 2 Technical Data 3-4 General Information 5 Technical Description
More informationLight Duty Commercial Electric Water Heater
Features Heavy Duty Construction Hydrastone cement lining provides longer tank life Copper-silicon tappings cannot rust or corrode High impact composite jacket eliminates damage during installation and
More informationOperating instructions
6300 9681 02/2006 GB For the user Operating instructions Logano GE315 Boiler for oil-/gas-fired pressure jet burners Please read thoroughly before use. Operating instructions Logano GE315 Dear Customer,
More informationInstallation and User Instructions Aquaheat Unvented Water Heaters Models: AH7/2.2, AH10/2.2, AH15/2.2
Installation and User Instructions Aquaheat Unvented Water Heaters Models: AH7/2.2, AH10/2.2, AH15/2.2 Please read and understand these instructions before starting work. Please leave this leaflet with
More informationOverheating limit control
Pahlén electric heater Maxi Heat with digital control is a compact and effective heater for swimming pools. It consists of a glassfibre reinforced polypropylene tank containing resistance-type heating
More informationCOMMISSIONING OF HVAC SYSTEMS
FORM CL-01 SYSTEMS / EQUIPMENT INCLUDED : SYSTEM STARTUP CHECKLIST I - PRE - STARTUP INSPECTION EQUIPMENT MOUNTING & SETTING CONTROL, INTERLOCK & POWER WIRING ALIGNMENT OF MOTORS & DRIVES PIPING, CONNECTIONS
More informationCommercial Electric Water Heater
MODEL SE Commercial Electric Water Heater 6-120 Gallon Capacity, up to 58 KW in all Three Phase Voltages, Over 6 KW in all Single Phase Voltages Features Heavy Duty Construction Hydrastone cement lining
More informationNot required for most applications Not required for most applications High pressure (12-803 provided) High pressure (12-803 provided)
ELECTRIC FUEL PUMPS P/N 12-801-1, 712-801-1, 12-802-1, 712-802-1, 12-815-1, & 712-815-1 FUEL PRESSURE REGULATORS P/N 12-803, 12-501, 12-804, 12-500, & 15812NOS Installation Instructions THESE INSTRUCTIONS
More informationElson Coral E. Open Vented Thermal Store providing mains pressure hot water heated by electricity. Installation, Servicing and User's Instructions
Part No. 130009 Iss. 12 August 2004 Elson www.elsonhotwater.co.uk Open Vented Thermal Store providing mains pressure hot water heated by electricity Installation, Servicing and User's Instructions Read
More informationInstallation, Operating and Servicing Instructions. Electric Auto-Fill Push Button Water Boilers EB3F/PB and EB3F/PBM
Installation, Operating and Servicing Instructions Electric Auto-Fill Push Button Water Boilers EB3F/PB and EB3F/PBM Please make a note of your product details for future use: Date Purchased: Model Number:
More informationVolvo Penta Quality Line Marine Water Heaters. Owners Manual
Volvo Penta Quality Line Marine Water Heaters Owners Manual Mounting Instructions Congratulations on your choice of a new QL Water Heater. A choice that will help you bring out the best in boating pleasure.
More informationBERMAD Fire Protection
400E-2M/700E-2M IOM Bermad Electrically Controlled Deluge Valve with EasyLock Manual Reset Model: 400E-2M/700E-2M INSTALLATION OPERATION MAINTENANCE Application Engineering BERMAD 400E-2M/700E-2M Bermad
More informationINSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected)
CHRONOMITE INSTANT-FLOW WATER HEATER INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected) TABLE 1 Model No. Wattage
More informationTABLE 1. Rugged cast aluminum alloy casing,celcon waterways with nichrome parts White (unless stainless steel housing)
CHRONOMITE INSTANT-FLOW MICRO WATER HEATER INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected) TABLE 1 Model No.
More informationRoutine and Emergency Boiler Operation
Routine and Emergency Boiler Operation Learning Outcome When you complete this module you will be able to: Describe the routine safe and efficient operation of a packaged boiler. Learning Objectives Here
More informationPET-10 INSTRUCTION MANUAL PRESSURE TANK
INSTRUCTION MANUAL PRESSURE TANK PET-10 This manual contains IMPORTANT WARNINGS and INSTRUCTIONS. Equipment in this manual is exclusively for painting purposes. Do not use for other purposes. The operator
More informationThermo Top - Troubleshooting Tree
Thermo Top - Troubleshooting Tree 07-15-2002 CAUTION Troubleshooting requires comprehensive knowledge about the structure and theory of operation of the Thermo Top heater. Troubleshooting and repairs may
More informationLAKE COUNTY ANIMAL SERVICES EXPANSION SECTION 15459
SECTION 15459 PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification sections, apply to work
More informationBoiler Preparation, Start-Up and Shutdown
Boiler Preparation, Start-Up and Shutdown Learning Outcome When you complete this module you will be able to: Describe the basic preparation of a boiler for start-up, and the start-up and shutdown procedures.
More informationIsotemp Basic, Slim/B & Slim Square
Isotemp Basic, Slim/B & Slim Square Water heater Installation and operating instructions Indel Marine S.r.l. Zona Artigianale sn IT-61019 S. Agata Feltria (PU) Italy Tel. 39 0541 848 030 Fax 39 0541 848
More informationBPW32 DN15, DN20 and DN25 Balanced Pressure Wafer Steam Trap
1263050/6 IM-P126-07 ST Issue 6 BPW32 DN15, DN20 and DN25 Balanced Pressure Wafer Steam Trap Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation
More informationENGINE COOLING SYSTEM
ENGINE COOLING SYSTEM 1988 Toyota Celica 1987-88 TOYOTA Engine Cooling Systems Celica DESCRIPTION The basic liquid cooling system consists of a radiator, water pump, thermostat, cooling fan, pressure cap,
More informationCALIFORNIA PROPOSITION 65 WARNING:
Residential Solar Water Heater USE & CARE MANUAL WITH INSTALLATION INSTRUCTIONS FOR THE CONTRACTOR LISTED 786H The purpose of this manual is twofold: one, for the installing contractor, to provide requirements
More informationZenith Solar thermal 4.5m pump station Installation manual
Zenith Solar thermal 4.5m pump station Installation manual Product code: 20026145 INSTALLATION MANUAL WATER RETURN GROUP This instruction manual is an integral part of the installation and maintenance
More informationInstallation and User Instructions Aquarius Undersink Vented Water Heaters Models: AU7/3, AU7/1, AU10/3, AU10/1.
Installation and User Instructions Aquarius Undersink Vented Water Heaters Models: AU7/3, AU7/1, AU10/3, AU10/1. Please read and understand these instructions before starting work. Please leave this leaflet
More informationINSTALLATION, OPERATION & MAINTENANCE MANUAL
INSTALLATION, OPERATION & MAINTENANCE MANUAL Flanged Disk Check Valve with Strainer Ref. GENEBRE: 2450 2451 2452 1 INSTRUCTIONS FOR INSTALLATION, OPERATION & MAINTENANCE MANUAL 1. Spare parts... 3 1.1
More informationEnglish. Symbols used to mark instructions...3. Congratulations...5 Getting the best results...5. Warnings...6 Operating Procedure...
2 Contents Components Attachments Guidance Installation Operation Maintenance Service Technical Troubleshooting Symbols used to mark instructions...3 Included Attachments...4 Congratulations...5 Getting
More informationITE. Indirect calorifier ITE - 400/500/600/750/1000. Installation, User and Service Manual. Innovation has a name.
ITE Indirect calorifier ITE - 400/500/600/750/1000 0310 117 Installation, User and Service Manual Innovation has a name. Read this manual carefully Warning Read this manual carefully before starting the
More informationInstruction Manual. Ultrasonic Cleaning Tank. Advanced Ceramics Technology (M) Sdn. Bhd A Crest Group Inc. Company
Instruction Manual Ultrasonic Cleaning Tank Advanced Ceramics Technology (M) Sdn. Bhd A Crest Group Inc. Company No 1536, Jalan Perusahaan, Kawasan Perusahaan Bukit Tengah, 13600 Perai, Penang, Malaysia.
More informationSunMaxx Solar Filling Station Operating Instructions
SunMaxx Solar Filling Operating Instructions Content 1. Declaration of conformity... 2 2. Introduction... 2 3. Transportation and unpacking... 4 4. Mounting and commissioning... 5 5. End of operation...
More information"EC" Series Electric Humidifier
EC-1 Standard Water "EC" Series Electric The Electric from PURE Co. is loaded with features and options. All you need is tap water, electricity, and a sanitary drain. The humidifier does the rest. These
More informationOASIS SERVICE & TROUBLESHOOTING MANUAL (WITH DM10 OR DM12)
OASIS SERVICE & TROUBLESHOOTING MANUAL (WITH DM10 OR DM12) Revision 1.0 Page 1 of 50 THE INFORMATION CONTAINED IN THIS DOCUMENT IS THE SOLE PROPERTY OF INTERNATIONAL THERMAL RESEARCH, LTD. ANY REPRODUCTION
More informationELECTRIC WATER HEATER INSTALLATION & OPERATING INSTRUCTION MANUAL
ELECTRIC WATER HEATER A Spanish language version of these instructions is available by contacting the manufacturer listed on the rating plate. La version espanola de estas instruccions se puede obtener
More informationACCUMULATOR INSTALLATION
7001-7 ACCUMULATOR INSTALLATION BRAKE ACCUMULATORS I 308L93 Rae 7-59710 Issued 6-93 Printed in U.S.A 7001-8 Removal ACCUMULATOR VALVE 1. Park the machine on a level surface and lower the. loader bucket
More informationCompressor Service & Maintenance Manual
Compressor Service & Maintenance Manual C Series COMPRESSOR (D)C1103 (D)C1203 (D)C2106 (D)C2206 (D)C3210 Copyright 2006 DCI. All Rights Reserved. 92311, Rev. C, 08/13 1 C1000 Series Service & Maintenance
More informationIMPORTANT SAFETY NOTICE
IMPORTANT SAFETY NOTICE To: Our Valued Customers User safety is a major focus in the design of our products. Following the precautions outlined in this manual will minimize your risk of injury. ITT Goulds
More informationVOYAGER 570G. 744A Sprayer Control
VOYAGER 570G 744A Sprayer Control U S E R M A N U A L U S E R M A N U A L Table of Contents CHAPTER 1 - INTRODUCTION...1 SYSTEM CONFIGURATIONS...1 KIT CONTENTS...3 CONTROL HOUSING ASSEMBLY...5 CHAPTER
More informationCommercial Gas Water Heaters
POWERED BURNER MODELS LARGE-VOLUME POWERED BURNER FEATURES The large-volume powered burner line includes the largest, most powerful A. O. Smith tanktype gas water heaters. With tank capacities up to 600
More informationUNIT 7: PLUMBING KEY CONCEPTS. 1. Identify tools for plumbing. 2. Location of shutoff valves for the main and individual fixtures
KEY CONCEPTS 1. Identify tools for plumbing 2. Location of shutoff valves for the main and individual fixtures 3. How water is supplied to your home 4. How waste water is removed and treated 5. Common
More informationProduct Manual. CVS Type 67AFR Filter Regulator. Introduction. Installation. Description
Product Manual CVS Type 67AFR Filter Regulator Introduction This CVS Controls product manual includes instructions for the installation, adjustment, maintenance and parts ordering of the CVS Type 67AFR
More informationNexus FS Point of Use Installation Guide
Nexus FS Point of Use Installation Guide Nexus FS POU Install Guide:12152011:rev-12152011 Technical Specifications Dimensions: Height: 43.5 Width: 11.65 Depth: 15 Weight: 34.39 LBS Electrical Specs: Voltage:
More information