STANDBY PERMANENT MOUNT SERIES GENERATOR
|
|
|
- Cory Miles
- 9 years ago
- Views:
Transcription
1 PRESENTS YOUR STANDBY PERMANENT MOUNT SERIES GENERATOR OPERATORS MANUAL BALDOR GENERATORS 3815 OREGON STREET OSHKOSH, WI PHONE: FAX: FORM#: S-PSG REVISED: 2/25/02 C:\ISO9001\FORMS\S-PSG MSW EFFECTIVE: 5/3/01
2 FORWARD This manual contains the information you need to safely and efficiently operate your generator set. During the preparation of this manual every effort was made to ensure the accuracy of its contents. Never operate this generator set without first carefully reading this manual and observing all the safety warnings it presents. While safety is built into every Baldor Pow'R Gard generator set, careless or improper operation could possibly result in mechanical failure, property damage, severe injury or death. Note that this manual covers only very basic information in regards to the engine. A separate owner's manual for the engine is supplied with this unit for your use. Please refer to this manual for information relative to engine operation, maintenance, recommendations and additional safety warnings. As soon as you receive your generator set, inspect it closely for shipping damage. If you find some damage, notify the transportation company immediately and file a freight damage claim. Think of this manual as a tool to help you get the most out of your generator set. We strongly suggest that you keep this manual with your generator set and refer to it when questions arise in regards to its operation. Baldor Generators, formerly Pow'R Gard Generator Corporation has been in business since The generator sets we manufacture have earned the reputation of being of high quality and a dependable product. We take pride in this fact and continue to keep our quality standards high on our list of priorities. We are also constantly researching new technological ideas to determine if they could be used to make our generator sets even better. Thank you for purchasing your Baldor Pow'R Gard Generator Set. - i -
3 Place protective covers and guards over the rotating parts, if rotating parts such as the drive shaft, pulley, belt, etc. are left exposed, they are potentially hazardous. When cleaning, repairing or inspecting, make sure all moving parts have stopped. Prior to working on the generator set, disconnect the spark plug and battery to prevent accidental starting. Use only original equipment or authorized replacement parts. Use of correct parts will assure the operator of the safety integrity that was designed into the unit. Unauthorized modifications to the generator set may impair the function and/or safety of the unit. Do not operate the generator set without a muffler. Inspect periodically and replace if necessary. Do not touch the hot exhaust components or the high voltage spark plug and coil terminals. While Spark Plug Voltages are not normally lethal, an involuntary jerk of the hand caused by a hot surface or by an electrical shock can result in injury. Repair of electrical generating equipment requires specialized skills. Repair personnel must have a thorough understanding of generator and small engine repair procedures. Never inhale exhaust gases. They contain carbon monoxide; a colorless, odorless and extremely dangerous gas that can cause unconsciousness or death. Symptoms of carbon monoxide poisoning can include: dizziness, nausea, headaches, sleepiness, vomiting or incoherency. If you or anyone else experiences any of these symptoms, get out into the fresh air immediately. Shut the unit down and do not operate it until it has been inspected and, if necessary, repaired. Never Operate the generator set indoors or in a poorly ventilated area such as a tunnel or cave. CALIFORNIA PROPOSITION 65 WARNING: engine exhaust from this product contains chemicals known to the state of California to cause cancer, birth defects or other reproductive harm. Know how to stop the engine quickly and understand the operation of all controls. - ii -
4 Never permit anyone to operate the generator set without proper instructions. Never allow children to operate the generator set. Children and pets must be kept away from the area of operation due to the possibility of burns from hot engine components or injury from any equipment the generator set is powering. Always wear eye protection and Hearing protection when working near the generator set. Operate the generator set only with the guards, shields and other safety items in place and working properly. Do not put hands, feet, tools or other objects near rotating parts. Use reasonable care when moving or lifting the unit. The generator set may move around inside the wrap frame creating "Pinch Points". Do not run the generator set while it is being moved. Do not support the generator set from the top of the wrap frame. Do not operate the generator set while under the influence of alcohol, drugs or medication. When transporting or using a generator set with the wheel option, secure the unit to prevent it from moving around. Do not tamper with or change the engine speed as it has been preset at the factory for proper operation. Keep hands and face away from the carburetor when the air cleaner is being moved. A sudden backfire can cause serious burns. Be careful of hot parts. The muffler and other generator parts become very hot while the engine is running. Do not "jump start" the generator set. Sulfuric acid can cause severe injury and can give off gases, which are corrosive and potentially explosive. Avoid contact with skin, eyes, and clothing. In case of contact, flush area immediately with water. When transporting a generator set, secure it to prevent it from moving or shifting. Know how to stop the engine quickly and understand the operation of all controls. Do not operate electrical equipment while standing in water, on wet ground or with wet hands or shoes. Use extreme caution when working on electrical components. Potentially dangerous voltage is present when the engine is running. - iii -
5 Always treat the electrical circuits as if they were energized. Disconnect all leads plugged into the unit Prior to working on it. Have the electrical circuits serviced only by qualified technicians. Inspect wiring frequently and replace frayed, broken or poor leads. Do not connect this unit to any building's electrical system unless you utilize an approved transfer switch or the main service entrance switch has been disconnected and locked open. Circuit overload protection must be provided in accordance with national electrical codes and local regulations. Check GFCI Receptacles monthly by using the "Test" and "Reset" buttons designed into them. Depending on your application it may be mandatory to ground or not ground this unit to earth ground. Comply with local electrical codes. FOR GASOLINE OR DIESEL POWERED GENERATOR SETS Operate the generator set on a level surface. If the generator set is tilted, fuel spillage may result. Handle fuel with care. It is highly flammable. Use only clean, properly marked and approved safety containers for refueling and storing fuel. Stop the engine and allow it to cool before refueling. Do not overfill the fuel tank. Only fill the tank to within 1/2" of the top of the tank to allow space for fuel expansion. If fuel is spilled, wipe it up carefully and wait until the fuel has dried before starting the engine. Make sure the fuel cap is properly closed after refueling. Never operate the generator set while smoking. Never operate the generator set near an open flame. Never store the generator set with fuel in the tank indoors or in an enclosed, poorly ventilated enclosure where fuel fumes may reach an open flame, electrical spark or pilot light as on a furnace, water heater, clothes dryer, etc. When transporting over long distances or rough roads, drain the fuel tank to prevent leakage and spillage. - iv -
6 FOR GASOLINE OR DIESEL POWERED GENERATOR SETS Check all fuel supply piping and their connections on a monthly basis for fuel leaks. Use only approved piping and componentry in your fuel supply system. A professional, experienced technician should only install the fuel supply system. Do not run the fuel line up against any sharp objects. Comply with NFPA regulations and your local codes in regard to shut-off valves, regulators, etc. and any other recommendations or requirements they may have. Keep the generator set at least three feet away from buildings or other structures. Keep the generator set away from flammable and other hazardous materials (trash, rags, lubricants, explosives, paints, etc.) Keep the generator set free of grass, leaves and excessive grease and oils. Allow the generator set to cool before transporting it or storing it indoors. Have fire extinguisher accessible and nearby while operating the generator set. This generator set must not be used on or near any forest covered brush covered or grass covered land unless the engine's exhaust system is equipped with a spark arrester and it must be maintained in effective working order by the operator. Operation inside an enclosed compartment or building is a potential fire hazard and should not be done unless approval is obtained from Baldor Generators. Engine/Generator overheating can cause severe damage due to restricted, obstructed or improper airflow that is necessary for the proper cooling of the unit. Hot exhaust gases being discharged by the engine must never be directed toward anything that could catch fire or explode. - v -
7 STANDBY PERMANENT- MOUNT SERIES GENERATOR Table of Contents ITEM PAGE VOLTAGE RATINGS: This informational page describes features and specifications for all Standby Permanent- Mount Series 1 Units. ELECTRICAL CONNECTION INFORMATION: This information explains how to interface your generator with the AC loads and other standard and 13 optional accessories. MOUNTING AND COOLING REQUIREMENTS: This section explains the necessary requirements for mounting and ventilating your Pow'R Gard 15 Generator. EXHAUST REQUIREMENTS: this section describes recommendations made by Pow'R Gard to assure proper exhaust applications. 21 CONTROL PANEL: This includes a drawing of the control panel and a description of the components associated with it. 24 PRE-START PROCEDURE: This describes a pre-start check that should be performed prior to initial start-up. 27 OPERATION GUIDE: Information on how to start, stop, and operate the generator set is included here. Included also is information in regards to the operation of the gen set/ engine control device and the different fault shutdown circuits designed to protect the generator set from potential engine 28 operational problems. TROUBLESHOOTING GUIDE: Included in this guide are basic instructions to help troubleshoot most problems with your generator set. For more troubleshooting help please contact the service department at Pow R Gard Generator 30 Corporation POW R GARD GENERATOR CORPORATION WARRANTY: This details the warranty provided by Pow R Gard Generator Corporation for coverage for electrical generator end of the generator set. 34 INSTALLATION CHECKLIST: This checklist is provided to assure that Installation has been properly performed meeting all Pow'R Gard guidelines. It is expected that this checklist be filled out and returned to Pow'R Gard Generator Corporation. 37 Other Manuals and accessories that should accompany your Standby Permanent - Mount Series Generator: ENGINE OPERATOR S MANUAL: This operator s manual includes information in regards to the operation and maintenance of the engine utilized in this generator set. AC GENERATOR, ACCESSORIES, AND LOAD CONNECTION DIAGRAMS / ENGINE CONTROLS, ACCESSORIES, AND REMOTE CONNECTION DIAGRAMS: These diagrams contain information in regards to the internal wiring of the generator set, specifically the AC and Engine Control circuits. These diagrams will also include information for any optional AC or DC powered accessories that are included. PARTS LIST: This is a listing of all parts used by Pow R Gard Generator Corporation to build this specific generator set.
8 Farm Duty 1-Phase Baldor POWER SYSTEMS Model: DLC25 4 Cycle Diesel Liquid Cooled Assembled in USA Baldor Generator Features Baldor generators are manufactured in a certified ISO9001 facility located in Oshkosh, Wisconsin. Every generator is design, prototype, and production tested Brushless synchronous four-pole alternator Industrial grade exhaust silencer Engine block heater Baldor gensets attain one step load acceptance of nameplate rating PowerPAC 4 controller includes low oil pressure shutdown, high coolant temperature shutdown, overspeed and overcrank indicators Flexible exhaust connection Battery rack and cables Installation and operation manual Worldwide network of parts and service Options Exhaust silencer: Critical Single wall sub base fuel tank Double wall UL 142 approved sub-base fuel tank Battery charger 12V float Line circuit breaker Flexible fuel lines Weather protective enclosure Generator Ratings Standby Power Ratings 60Hz 150 C Rise Standby Rating kw 27.5 kva 27.5 Continuous Power Ratings 60Hz kw 25 kva C Rise Continuous Rating Voltage PH Hz kw/kva Amps kw/kva Amps 120/ / / Ratings: - Standby Ratings: Standby ratings are applicable for supplying emergency power for the duration of a utility power outage. Primary power to the installation is utility supplied. No overload capability for standby rating. Standby ratings in accordance with ISO 3046, BS55114, DIN Continuous Power Rating: Continuous power is the maximum power available for continuous duty. A 10% overload capacity is available for 1 hour out of 12 hours of operation. Prime power ratings in accordance with ISO 3046, BS55114, DIN For additional information, please consult factory. Manufacturer reserves the right to implement specifications or design changes without notice. Single phase: Single phase units are rated at 1.0 (Unity) power factor. WARNING: Do not connect generator to any building's electrical system unless a disconnect switch has been installed.
9 Farm Duty 1-Phase Alternator Specifications Manufacturer Stamford/Newage Type 4-Pole, Revolving field Model BCI184F Leads 4 Voltage regulator AVR Voltage regulation 1/2% Insulation material: Rotor Class H Insulation material: Stator Class H Temperature rise 125 C, Standby Total harmonic distortion <5% Bearing: quantity, type 1, Sealed Coupling type Flexible disc One step load acceptance 100% of Rating Warranty: Limited 3 year warranty. 1 year or 3000 hours parts and labor. 3 years or 3000 hours parts. Baldor reserves the right to repair or replace unit. Alternator Features Model: DLC25 Brushless design Class H insulation used throughout Solid-state voltage regulation Sealed bearings All wound components impregnated with varnishes and resins to protect against harsh environment Alternator complies with temperature rise standards: NEMA, IEEE and ANSI Dynamically balanced rotors Controller Features PowerPAC 4 Hi temp, low oil pressure, overspeed and overcrank indicators AC Voltage, amperage and hertz meters Oil pressure, water temperature and battery gauges Hour meter Panel lights Engine Specifications Engine Data Manufacturer Perkins Model Cylinders 3 in-line Cycle 4-stroke Induction system Natural Displacement, L (cu. in.) 2.5 (152 cu. in.) Bore and Stroke 91.4 x Compression Ratio 16.5:1 Lubrication capacity 6.17 Quarts Cooling capacity (incl. radiator) Quarts Weight without fuel - Net 685 Weight without fuel - Shipping 950 Warranty: 2 year limited per manufacturer Size: Length x Width x Height Engine Features Mechanical governor - speed control to ISO Class A1 Spin-on full fuel flow filter Fuel pre-filter Spin-on full flow oil filter Oil cooler Thermostat controlled cooling system Gear driven water pump 12V engine alternator 12V starter motor Single side servicing Engine Performance Continuous Standby Rated RPM HZ Net BHP at rated " x 36 x 38 1 / " Baldor Generators 3815 Oregon Street Oshkosh, WI Fax Distributed by: 61.00" 36.00" Drawing is for reference only: Contact your dealer for detailed information. SAL-245-5M-DP
10 Farm Duty 1-Phase Baldor POWER SYSTEMS Model: D50 4 Cycle Diesel Liquid Cooled Assembled in USA Baldor Generator Features Baldor generators are manufactured in a certified ISO 9001 facility located in Oshkosh, Wisconsin Every generator is design, prototype, and production tested Brushless synchronous four-pole alternator Industrial-grade exhaust silencer Engine block heater Baldor gensets attain one step load acceptance of nameplate rating PowerPAC 4 controller includes low oil pressure shutdown, high coolant temperature shutdown, overspeed and overcrank indicators Flexible exhaust connection Battery rack and cables Installation and operation manual Worldwide network of parts and service Options Exhaust silencer: Critical Single wall sub-base fuel tank Double wall UL 142 approved sub-base fuel tank Battery charger 12V float Line circuit breaker Flexible fuel lines Weather protective enclosure Generator Ratings Standby Power Ratings 60Hz 50Hz kw kva Continuous Power Ratings 60Hz 50Hz kw kva C Rise Standby Rating 125 C Rise Continuous Rating Voltage PH Hz kw/kva Amps kw/kva Amps 120/ / / / / / Ratings: - Standby Ratings: Standby ratings are applicable for supplying emergency power for the duration of a utility power outage. Primary power to the installation is utility supplied. No overload capability for standby rating. Standby ratings in accordance with ISO 3046, BS55114, DIN C ontinuous Power Rating: Continuous power is the maximum power available for continuous duty. A 10% overload capacity is available for 1 hour out of 12 hours of operation. Prime Power ratings in accordance with ISO 3046, BS55114, DIN For additional information, please consult factory. Manufacturer reserves the right to implement specifications or design changes without notice. Single phase: Single phase units are rated at 1.0 (Unity) power factor. WARNING: Do not connect generator to any building s electrical system unless a disconnect switch has been installed.
11 Farm Duty 1-Phase Alternator Specifications Manufacturer Stamford/Newage Type 4-Pole, Revolving field Model UC224D Leads 4 Voltage regulator AVR Voltage regulation 1/2% Insulation material: Rotor Class H Insulation material: Stator Class H Temperature rise 125 C, Standby Total harmonic distortion <5% Bearing: quantity, type 1, Sealed Coupling type Flexible disc One step load acceptance 100% of Rating Warranty: Limited 3 year warranty. 1 year or 3000 hours parts and labor. 3 years or 3000 hours parts. Baldor reserves the right to repair or replace unit. Alternator Features Model: DLC50 Brushless design Class H insulation used throughout Solid-state voltage regulation Sealed bearings All wound components impregnated with varnishes and resins to protect against harsh environment Alternator complies with temperature rise standards: NEMA, IEEE and ANSI Dynamically balanced rotors Controller Features PowerPAC 4 Hi temp, low oil pressure, overspeed and overcrank indicators AC Voltage, amperage and hertz meters Oil pressure, water temperature and battery gauges Hour meter Panel lights Engine Specifications Engine Data Manufacturer Perkins Model T Cylinders 4 in-line Cycle 4-stroke Induction system Turbocharged Displacement, L (cu. in.) 3.99 (243.5 cu. in.) Bore and Stroke MM x MM 3.94 x 5 Compression Ratio 17.25:1 Lubrication capacity 8.4 liters (9 qts.) Cooling capacity (incl. radiator) 18.8 liters (23.4 qts.) Weight without fuel - Net 1727 Weight without fuel - Shipping 1812 Warranty: 2 year limited per manufacturer Size: Length x Width x Height " x 36" x 45" 45.00" Engine Features Mechanical governor - speed control to ISO Class A1 Spin-on full fuel flow filter Fuel pre-filter Spin-on full flow oil filter Oil cooler Thermostat controlled cooling system Gear driven water pump 12V engine alternator 12V starter motor Single side servicing Engine Performance 60 HZ Continuous Standby Rated RPM Net BHP at rated Baldor Generators 3815 Oregon Street Oshkosh, WI Fax Distributed by: 78.75" 36.00" Drawing is for reference only: Contact your dealer for detailed information. SAL M-SG
12 Farm Duty 1-Phase Baldor POWER SYSTEMS Model: D60 4 Cycle Diesel Liquid Cooled Assembled in USA Baldor Generator Features Baldor generators are manufactured in a certified ISO 9001 facility located in Oshkosh, Wisconsin Every generator is design, prototype, and production tested Brushless synchronous four-pole alternator Industrial-grade exhaust silencer Engine block heater Baldor gensets attain one step load acceptance of nameplate rating PowerPAC 4 controller includes low oil pressure shutdown, high coolant temperature shutdown, overspeed and overcrank indicators Flexible exhaust connection Battery rack and cables Installation and operation manual Worldwide network of parts and service Options Exhaust silencer: Critical Single wall sub-base fuel tank Double wall UL 142 approved sub-base fuel tank Battery charger 12V float Line circuit breaker Flexible fuel lines Weather protective enclosure Generator Ratings Standby Power Ratings 60Hz 50Hz kw kva Continuous Power Ratings 60Hz 50Hz kw kva C Rise Standby Rating 125 C Rise Continuous Rating Voltage PH Hz kw/kva Amps kw/kva Amps 120/ / / / / / Ratings: - Standby Ratings: Standby ratings are applicable for supplying emergency power for the duration of a utility power outage. Primary power to the installation is utility supplied. No overload capability for standby rating. Standby ratings in accordance with ISO 3046, BS55114, DIN C ontinuous Power Rating: Continuous power is the maximum power available for continuous duty. A 10% overload capacity is available for 1 hour out of 12 hours of operation. Prime Power ratings in accordance with ISO 3046, BS55114, DIN For additional information, please consult factory. Manufacturer reserves the right to implement specifications or design changes without notice. Single phase: Single phase units are rated at 1.0 (Unity) power factor. WARNING: Do not connect generator to any building s electrical system unless a disconnect switch has been installed.
13 Farm Duty 1-Phase Alternator Specifications Manufacturer Stamford/Newage Type 4-Pole, Revolving field Model UC224G Leads 4 Voltage regulator AVR Voltage regulation 1/2% Insulation material: Rotor Class H Insulation material: Stator Class H Temperature rise 125 C, Standby Total harmonic distortion <5% Bearing: quantity, type 1, Sealed Coupling type Flexible disc One step load acceptance 100% of Rating Warranty: Limited 3 year warranty. 1 year or 3000 hours parts and labor. 3 years or 3000 hours parts. Baldor reserves the right to repair or replace unit. Model: DLC60 Alternator Features Brushless design Class H insulation used throughout Solid-state voltage regulation Sealed bearings All wound components impregnated with varnishes and resins to protect against harsh environment Alternator complies with temperature rise standards: NEMA, IEEE and ANSI Dynamically balanced rotors Controller Features PowerPAC 4 Hi temp, low oil pressure, overspeed and overcrank indicators AC Voltage, amperage and hertz meters Oil pressure, water temperature and battery gauges Hour meter Panel lights Engine Specifications Engine Data Manufacturer Perkins Model T Cylinders 4 in-line Cycle 4-stroke Induction system Turbocharged Displacement, L (cu. in.) 3.99 (243.5 cu. in.) Bore and Stroke MM x MM 3.94 x 5 Compression Ratio 17.25:1 Lubrication capacity 8.4 liters (9 qts.) Cooling capacity (incl. radiator) 18.8 liters (23.4 qts.) Weight without fuel - Net 1945 Weight without fuel - Shipping 2030 Warranty: 2 year limited per manufacturer Size: Length x Width x Height " x 36" x 45" 45.00" Engine Features Mechanical governor - speed control to ISO Class A1 Spin-on full fuel flow filter Fuel pre-filter Spin-on full flow oil filter Oil cooler Thermostat controlled cooling system Gear driven water pump 12V engine alternator 12V starter motor Single side servicing Engine Performance 60 HZ Continuous Standby Rated RPM Net BHP at rated Baldor Generators 3815 Oregon Street Oshkosh, WI Fax Distributed by: 78.75" 36.00" Drawing is for reference only: Contact your dealer for detailed information. SAL M-SG
14 Farm Duty 1-Phase Baldor POWER SYSTEMS Model: D75 4 Cycle Diesel Liquid Cooled Assembled in USA Baldor Generator Features Baldor generators are manufactured in a certified ISO9001 facility located in Oshkosh, Wisconsin. Every generator is design, prototype, and production tested Brushless synchronous four-pole alternator Industrial grade exhaust silencer Engine block heater Baldor gensets attain one step load acceptance of nameplate rating PowerPAC 4 controller includes low oil pressure, high coolant temperature, overspeed and overcrank shutdowns with indicator lights Flexible exhaust connection Battery rack and cables Installation and operation manual Worldwide network of parts and service Options Exhaust silencer: Critical Single wall sub base fuel tank Double wall UL 142 approved sub base fuel tank Battery charger 12V float Line circuit breaker Flexible fuel lines Weather protective enclosure Generator Ratings Standby Power Ratings 60Hz 50Hz kw kva Continuous Power Ratings 60Hz 50Hz kw kva C Rise Standby Rating 125 C Rise Continuous Rating Voltage PH Hz kw/kva Amps kw/kva Amps 120/ / / / / / Ratings: - Standby Ratings: Standby ratings are applicable for supplying emergency power for the duration of a utility power outage. Primary power to the installation is utility supplied. No overload capability for standby rating. Standby ratings in accordance with ISO 3046, BS55114, DIN C ontinuous Power Rating: Continuous power is the maximum power available for continuous duty. A 10% overload capacity is available for 1 hour out of 12 hours of operation. Continuous Power ratings in accordance with ISO 3046, BS55114, DIN For additional information, please consult factory. Manufacturer reserves the right to implement specifications or design changes without notice. Single phase: Single phase units are rated at 1.0 (Unity) power factor.
15 Farm Duty 1-Phase Alternator Specifications Manufacturer Stamford/Newage Type 4-Pole, Revolving field Model UCI224G Leads 4 Voltage regulator AVR Voltage regulation 1/2% Insulation material: Rotor Class H Insulation material: Stator Class H Temperature rise 125 C Total harmonic distortion <5% Bearing: quantity, type 1, Sealed Coupling type Flexible disc One step load acceptance 100% of Rating Warranty: Limited 3 year warranty. 1 year or 3000 hours parts and labor. 3 years or 3000 hours parts. Baldor reserves the right to repair or replace unit. Model: DLC75 Alternator Features Brushless design Class H insulation used throughout Solid state voltage regulation Sealed bearings All wound components impregnated with varnishes and resins to protect against harsh environment Alternator complies with temperature rise standards: NEMA, IEEE and ANSI Dynamically balanced rotors Controller Features PowerPAC 4 Hi temp, low oil pressure, overspeed and overcrank indicators AC Voltage, amperage and hertz meters Oil pressure, water temperature and battery gauges Hour meter Panel lights Engine Specifications Engine Data Manufacturer Perkins Model TW Cylinders 4 in-line Cycle 4-stroke Induction system Turbocharged Displacement, L (cu. in.) 3.99 (243.5 cu. in.) Bore and Stroke MM x MM 3.94 x 5 Compression Ratio 17.3:1 Lubrication capacity 8.5 liters (9 qts.) Cooling capacity (inc. radiator) 22.2 liters (23.4 qts.) Weight without fuel - Net 2035 Weight without fuel - Shipping 2110 Warranty: 2 year limited per manufacturer Size: Length x Width x Height " x 36" x 45" 45.00" Engine Features Mechanical governor - speed control to ISO Class A1 Spin-on full fuel flow filter Fuel pre-filter Spin-on full flow oil filter Oil cooler Thermostat controlled cooling system Gear driven water pump 12V engine alternator 12V starter motor Single side servicing Engine Performance 60 HZ Distributed by: Continuous Standby Rated RPM Net BHP at rated Baldor Generators 3815 Oregon Street Oshkosh, WI Fax " 36.00" Drawing is for reference only: Contact your dealer for detailed information. S-SAL M-SG
16 Farm Duty 1-Phase Baldor POWER SYSTEMS Model: D100 4 Cycle Diesel Liquid Cooled Assembled in USA Baldor Generator Features Baldor generators are manufactured in a certified ISO9001 facility located in Oshkosh, Wisconsin. Every generator is design, prototype, and production tested Brushless synchronous four-pole alternator Industrial grade exhaust silencer Engine block heater Baldor gensets attain one step load acceptance of nameplate rating PowerPAC 4 controller includes low oil pressure, high coolant temperature, overspeed and overcrank shutdowns with indicator lights Flexible exhaust connection Battery rack and cables Installation and operation manual Worldwide network of parts and service Options Exhaust silencer: Critical Single wall sub base fuel tank Double wall UL 142 approved sub base fuel tank Battery charger 12V float Line circuit breaker Flexible fuel lines Weather protective enclosure Generator Ratings Standby Power Ratings 60Hz 50Hz kw kva Continuous Power Ratings 60Hz 50Hz kw kva C Rise Standby Rating 125 C Rise Continuous Rating Voltage PH Hz kw/kva Amps kw/kva Amps 120/ / / / / / Ratings: - Standby Ratings: Standby ratings are applicable for supplying emergency power for the duration of a utility power outage. Primary power to the installation is utility supplied. No overload capability for standby rating. Standby ratings in accordance with ISO 3046, BS55114, DIN C ontinuous Power Rating: Continuous power is the maximum power available for continuous duty. A 10% overload capacity is available for 1 hour out of 12 hours of operation. Continuous Power ratings in accordance with ISO 3046, BS55114, DIN For additional information, please consult factory. Manufacturer reserves the right to implement specifications or design changes without notice. Single phase: Single phase units are rated at 1.0 (Unity) power factor.
17 Farm Duty 1-Phase Alternator Specifications Manufacturer Stamford/Newage Type 4-Pole, Revolving field Model UCI274C Leads 4 Voltage regulator AVR Voltage regulation 1/2% Insulation material: Rotor Class H Insulation material: Stator Class H Temperature rise 125 C Total harmonic distortion <5% Bearing: quantity, type 1, Sealed Coupling type Flexible disc One step load acceptance 100% of Rating Warranty: Limited 3 year warranty. 1 year or 3000 hours parts and labor. 3 years or 3000 hours parts. Baldor reserves the right to repair or replace unit. Model: DLC100 Alternator Features Brushless design Class H insulation used throughout Solid state voltage regulation Sealed bearings All wound components impregnated with varnishes and resins to protect against harsh environment Alternator complies with temperature rise standards: per NEMA, IEEE and ANSI Dynamically balanced rotors Controller Features PowerPAC 4 Hi temp, low oil pressure, overspeed and overcrank indicators AC Voltage, amperage and hertz meters Oil pressure, water temperature and battery gauges Hour meter Panel lights Engine Specifications Engine Data Manufacturer Perkins Model T Cylinders 6 in-line Cycle 4-stroke Induction system Turbocharged Displacement, L (cu. in.) 5.99 (365.0 cu. in.) Bore and Stroke MM x MM 3.94 x 5.0 Compression Ratio 17.3:1 Lubrication capacity 16.1 liters (17.0 qts.) Cooling capacity (inc. radiator) 27.7 liters (29.2 qts.) Weight without fuel - Net 2260 Weight without fuel - Shipping 2448 Warranty: 2 year limited per manufacturer Size: Length x Width x Height 95" x 42" x 53" 53.00" Engine Features Mechanical governor - speed control to ISO Class A1 Spin-on full fuel flow filter Fuel pre-filter Spin-on full flow oil filter Oil cooler Thermostat controlled cooling system Gear driven water pump 12V engine alternator 12V starter motor Single side servicing Engine Performance 60 HZ Distributed by: Continuous Standby Rated RPM Net BHP at rated Baldor Generators 3815 Oregon Street Oshkosh, WI Fax " 42.00" Drawing is for reference only: Contact your dealer for detailed information. SAL M-SG
18 Farm Duty 1-Phase Baldor POWER SYSTEMS Model: D130 4 Cycle Diesel Liquid Cooled Assembled in USA Baldor Generator Features Baldor generators are manufactured in a certified ISO9001 facility located in Oshkosh, Wisconsin Every generator is design, prototype, and production tested Brushless synchronous four-pole alternator Industrial grade exhaust silencer Engine block heater Baldor gensets attain one step load acceptance of nameplate rating PowerPAC 4 controller includes low oil pressure, high coolant temperature, overspeed and overcrank shutdowns with indicator lights Flexible exhaust connection Battery rack and cables Installation and operation manual Worldwide network of parts and service Options Exhaust silencer: Critical Single wall sub base fuel tank Double wall UL 142 approved sub base fuel tank Battery charger 12V float Line circuit breaker Flexible fuel lines Weather protective enclosure Generator Ratings Standby Power Ratings 60Hz 50Hz kw kva Continuous Power Ratings 60Hz 50Hz kw kva C Rise Standby Rating 125 C Rise Continuous Rating Voltage PH Hz kw/kva Amps kw/kva Amps 120/ / / / / / Ratings: - Standby Ratings: Standby ratings are applicable for supplying emergency power for the duration of a utility power outage. Primary power to the installation is utility supplied. No overload capability for standby rating. Standby ratings in accordance with ISO 3046, BS55114, DIN C ontinuous Power Rating: Continuous power is the maximum power available for continuous duty. A 10% overload capacity is available for 1 hour out of 12 hours of operation. Continuous Power ratings in accordance with ISO 3046, BS55114, DIN For additional information, please consult factory. Manufacturer reserves the right to implement specifications or design changes without notice. Single phase: Single phase units are rated at 1.0 (Unity) power factor.
19 Farm Duty 1-Phase Alternator Specifications Manufacturer Stamford/Newage Type 4-Pole, Revolving field Model UCI274E Leads 4 Voltage regulator AVR Voltage regulation 1/2% Insulation material: Rotor Class H Insulation material: Stator Class H Temperature rise 125 C Total harmonic distortion <5% Bearing: quantity, type 1, Sealed Coupling type Flexible disc One step load acceptance 100% of Rating Warranty: Limited 3 year warranty. 1 year or 3000 hours parts and labor. 3 years or 3000 hours parts. Baldor reserves the right to repair or replace unit. Model: DLC130 Alternator Features Brushless design Class H insulation used throughout Solid state voltage regulation Sealed bearings All wound components impregnated with varnishes and resins to protect against harsh environment Alternator complies with temperature rise standards: per NEMA, IEEE and ANSI Dynamically balanced rotors Controller Features PowerPAC 4 Hi temp, low oil pressure, overspeed and overcrank indicators AC Voltage, amperage and hertz meters Oil pressure, water temperature and battery gauges Hour meter Panel lights Engine Specifications Engine Data Manufacturer Perkins Model TA Cylinders 6 in-line Cycle 4-stroke Induction system Turbocharged - aftercooled Displacement, L (cu. in.) 5.99 (365.0 cu. in.) Bore and Stroke MM x MM 3.94 x 5.0 Compression Ratio 17.3:1 Lubrication capacity 19.0 liters (20.0 qts.) Cooling capacity (inc. radiator) 37.2 liters (39.3 qts.) Weight without fuel - Net 2610 Weight without fuel - Shipping 3040 Warranty: 2 year limited per manufacturer Size: Length x Width x Height 95" x 42" x 53" 53.00" Engine Features Mechanical governor - speed control to ISO Class A1 Spin-on full fuel flow filter Fuel pre-filter Spin-on full flow oil filter Oil cooler Thermostat controlled cooling system Gear driven water pump 12V engine alternator 12V starter motor Single side servicing Engine Performance 60 HZ Distributed by: Continuous Standby Rated RPM Net BHP at rated Baldor Generators 3815 Oregon Street Oshkosh, WI Fax " 42.00" Drawing is for reference only: Contact your dealer for detailed information. SAL M-SG
20 STANDBY PERMANENT - MOUNT SERIES GENERATOR ELECTRICAL CONNECTION INFORMATION High voltage may be present at receptacles and load studs while engine is operating - DANGER of electrical shock is present. Use extreme care. Voltage is present at the 120V/15 Amp convenience receptacle only when generator is operating. When configured for 277/480 main output, these receptacles Will be delivering 139 VAC. Disconnection to avoid possible equipment damage is suggested. HARD WIRE LOAD TERMINAL BLOCK 1. Voltage available at load block is outlined in a chart below. 2. Cables must be brought into load block cabinet. 3. Do not start engine with load turned "on". Allow engine to come up to speed and warm up first. AVAILABLE VOLTAGE: CONNECTION OF GENERATOR LEADS STUD 120/240 4 LEAD 1-2 = 240 VAC, 1 Phase 1-N, 2-N = 120 VAC, 1 Phase 277/480 High Wye = 480 VAC, 3 Phase 1-N, 2-N, 3-N = 277 VAC, 1 Phase 120/240 Delta = 240 VAC, 3 Phase 2-3 = 240 VAC, 1 Phase 1-N, 2-N, 3-N = 120 VAC, 1 Phase 120/208 Low Wye = 208 VAC, 3 phase 2-3 = 208 VAC, 1 Phase 1-N, 2-N, 3-N = 120 VAC, 1 Phase
21 CONNECTION INFORMATION Your new Pow'R Gard Generator has all interconnecting wiring terminated at a junction box. All wiring will be clearly labeled as being load, remote start contacts and AC input terminals and are to be connected as described below. LOAD - These connections are rated and sized according to the KW of the generator. Proper lead wire from these points to the automatic transfer switch (or load switching device) is mandatory. See enclosed transfer switch information for corresponding generator input terminals. REMOTE START CONTACTS - This two wire connection, once connected to an appropriate switch, will start the generator and perform as described in the remote start/stop literature. These contacts are connected to the "Engine Start Contacts" of the automatic transfer switch. A Two Pole connection switch - normally open, closed to operate switch may also be used to start the generator. AC INPUT - These connections are for units with float type battery chargers or engine block heater combinations. A constant supply of 120 volts AC (or as specified) is needed at these terminals to power these devices. Power is not required when the unit is in operation. Internal Battery charging and radiant heat during operation eliminate the need for these devices. It is recommended that units utilizing an automatic transfer switch with adjustable time delays have the initial adjustments made prior to startup. Factory recommendations are: allow 2 second delay on startup, 15 second delay on emergency to normal.
22 STANDBY PERMANENT MOUNT SERIES GENERATOR GENERATOR MOUNTING REQUIREMENTS The generator set must be secured to a solid surface, which is non-combustible. A concrete floor is typical of this application. Wood floors should be prepared in accordance with local and state requirements for the load, heat and fluids that will be encountered with operation of this generator set. This generator base shall be anchored to the concrete floor with minimum 3/8" anchors. We do not suggest use of secondary isolators between the base and the floor surface, as durometers vary and may affect the isolation properties of the standard generator mounts. Please note that it is not recommended by the manufacturer that this generator be operated without being permanently mounted to a concrete slab or similar application in accordance with your local and state regulations. We also recommend that the generator be located 3 to 5 feet away from any permanent structure such as walls, bushes, etc. Check with your local city hall for official requirements in your area. The generator should be level for proper operation. When mounted, the generator should be properly aligned and located in a well-ventilated place where the air temperature will not exceed 40 O C or 104 O F, and should be accessible for cleaning. An open type generator should not be located where there are abrasive or conductive dusts, corrosive gasses or fumes, or where excessive moisture, standing or dripping water may be encountered. Limit dust and dirt accumulation and assure a rodent-proof environment. A totally enclosed generator should be cleaned frequently to remove accumulated dust and dirt, which may cause overheating. A dimensional diagram to aid in mounting this model is included in your Bill of Materials / Technical Diagrams Packet. ENGINE COOLING REQUIREMENTS A sufficient flow of clean, cool air is required to support combustion and to dissipate the heat produced in the combustion process of an internal combustion engine. Approximately 60% of the heat value of fuel consumed by an engine will be disbursed to the cooling air and to the exhaust. All engines are either directly or indirectly cooled by air. The Air-Cooled Engine must transfer the excess heat directly to the air surrounding it. The heated air must then be directed away from the engine so it will not overheat. If the engine is situated in an open installation there should not be a cooling problem, but when the engine is installed in a building it is essential to provide: 1. Adequate control and evacuation of the heated cooling air. 2. An adequate and constant supply of incoming cooling air. 3. Adequate control and discharge of the engine's hot exhaust gases. 4. Adequate ventilation of the building when the engine shuts down.
23 ENGINE COOLING AIR The air, which will cool the engine, must be brought in from outside the building. A forced airflow of sufficient Cubic Feet per Minute (CFM) will prevent the incoming cooling air from mixing with the air inside the building and eventually overheating and damaging the engine. To do this requires that an exhaust fan of sufficient CFM be placed near the generator set to exhaust the heated cooling air and to also draw in cool external air. The cooling air intake should be located so that the cooling air will be brought in through this intake opening, travel across the generator set, and then be evacuated from the building via the exhaust fan. It is recommended that the cooling air intake have at least twice the cross-sectional opening area as the heating cooling air exhaust fan located near the generator set. It is also recommended that the air intake opening be located as close as possible to the same level as the top of the generator set. The exhaust fan must NOT be located where it could easily become blocked by leaves, snow, water, debris, etc The cooling air intake opening of the building should be of sufficient size so as to not interfere with the cooling air intake airflow. It is recommended that the intake opening be no less than 3 times the cross sectional area of the exhaust fan opening. It is also recommended that this opening be located on a vertical plane so as to not easily become plugged with debris. If utilizing some type of covering over the intake opening (louvers, expanded metal, screening, etc ) it is very important that the combined total of the cross-sectional area openings be no less than 3 times the cross-sectional area of the exhaust fan opening. The heated cooling air coming off the engine must be directed, and evacuated out of the building. An exhaust fan of sufficient CFM will need to be used to achieve this end result. Regarding the exhaust fan size, remember that no heated cooling air must be allowed to accumulate inside the building. For aircooled units of 8-12KW we recommend an exhaust fan of 2000 CFM. Location of the exhaust fan for the engine's heated cooling air is important. It must be located so that the heated cooling air evacuated from the building not be allowed to re-circulate back into the cooling air intake of the building or generator set. It is also important that it not be located where leaves, snow, water, debris, etc could easily block it The exhaust fan should be located near the generator set on it's right or left side. If the unit has a side mounted muffler it is preferable to put the exhaust fan on this side. You must not position the exhaust fan so as to pull the incoming cooling air away from the cool air intake of either the engine or the generator end. The exhaust fan must be connected to the AC power terminals of the generator set so that when the generator set starts it will immediately engage to provide immediate cooling air flow. The fan will then stay engaged until the generator set stops. It is important to keep any and all flammable objects or materials away from this generator set, the remote muffler and it's attached piping, or any other potential hot component of the installation.
24 When discharging the heated cooling air or the hot exhaust gases out through the side of the building or compartment please contact your local building inspector to find out what is necessary for your application to prevent a fire from occurring. You must clean and inspect both the exhaust fan and its louvers along with the building's cooling air intake on a regular basis to prevent reduction in the building's cooling air flow. This could lead to overheating and a potential fire or explosion. The direction of the discharged heating cooling air and the discharged hot exhaust gases is important as they have the potential to create brown spots on the lawn. In extreme cases this extremely hot air could cause dried grass or other debris to ignite. Once the generator set is completely installed and fully operational, the following test should be performed to help determine if the cooling airflow system you installed is performing adequately. 1. Place a thermometer as close to the cooling air intake of the engine's blower housing as you can without allowing the thermometer to touch any material surface. Secure the thermometer so it can't be drawn into the engine when it is running. 2. Place another thermometer outside of the building or compartment in the open air (Keep the thermometer out of direct sunlight or any other heat sources). 3. Run the engine under maximum load for an extended period of time (at least one hour). 4. The temperature difference between the two should not exceed 15 degrees F. Please note that opening any door, window or other opening in the building could upset the directed cooling airflow pattern and result in a significant reduction in the cooling airflow across the generator set. This could result in overheating, fire, or explosion. To find out if this is true with your specific application run the above-mentioned test with all doors and windows closed. Then repeat this test with different doors and windows open, and eventually with all the windows and doors open. If any of these tests produce results that do not meet the above-mentioned criteria, you must not run the generator set under the specific conditions that created these unappreciable results. HOT EXHAUST GASES Exhaust gases contain carbon monoxide, a poisonous and toxic Gas. Carbon Monoxide can cause illness or death. This generator set must Only be installed by qualified professionals. While it is important to supply the proper amount of clean air to the cylinder, it is equally important to discharge the gases of combustion. If these gases remain in the cylinder, poor performance or eventual engine damage may result. This condition results from excessive back- pressure, which could be caused by any one or a combination of the following conditions: 1. Exhaust pipes too long or the diameter is too small. 2. Excessive number of sharp bends in the exhaust system. 3. Obstruction in the exhaust system. Backpressure must not exceed 20" of water column. Exhaust lines should be as short and straight as possible, since extended runs and elbows tend to clog with carbon and resist the flow of gases. Each pipe fitting and elbow will hinder the exhaust flow.
25 If you are using a remote muffler it should be mounted as close to the engine as possible, since it will clog with carbon if it's operating temperature is too low. If you are using a remote muffler a flexible coupling of 12" or more must be installed between the exhaust line and the manifold to absorb the engine's vibration. However, a short, solid section of pipe between 6" and 8" long should be placed between the connection of the manifold and the flexible coupling. This nipple will reduce the possibility of the hot gases burning up the flexible coupling. Water is one of the by-products of combustion and will be present in the exhaust piping or muffler. This water must be kept from draining back into the engine. Slanting the horizontal section of the exhaust system piping downward slightly, away from the engine can do this. A water trap consisting of a tee extension with a drain cock should also be provided. This water trap should be located between the flex coupling and the muffler, but as close to the engine as possible on a horizontal section of the exhaust piping. It is also recommended that an exhaust rain cap be used whenever it is possible that rain could get into the system. This will help to prevent corrosion and damage to the exhaust system and engine. The exhaust system is subject to the engine's vibration and it must therefore be solidly secured to prevent unnecessary stress and the potential for breakage. The engine's exhaust system is the hottest component of the installation and extreme care and considerations must be given to it. Whenever possible the remote muffler should be located outside of the building or compartment. As much of the exhaust piping as possible should be located within the engine's heated cooling are exhaust flow. This will help to prevent the accumulation of radiant exhaust heat inside the building. In some cases, the idea of mounting the muffler outside the building conflicts with the idea of mounting the muffler close to the engine to prevent carbon buildup. In these cases it is best to mount the muffler near the engine and provide an air flow around the muffler to evacuate the muffler's radiant heat out of the compartment or building. However, the exhaust outlet must be extended outside of the building. Under no conditions shall the exhaust outlet be positioned so that the exhaust gases would be directed towards any openings or air entry routes (doors, windows, vents, etc...) of an occupied building. When discharging the hot exhaust gases out of the building do not direct them towards anything that could catch fire or explode. If the remote muffler cannot be located outside of the building or compartment, the next best option is to locate it in the engine's heated cooling air exhaust flow. It is extremely important that you do not allow the hot exhaust gases to re- circulate back into the engine's cooling air intake. It is important to keep any and all flammable objects or materials away from the generator set, the remote muffler and its attached piping, as well as any other potentially hot component of the installation.
26 When discharging the heated cooling air or the hot exhaust gases out through the side of the building please contact your local building inspector to find out what is necessary for your application to meet local building code requirements. Keep all fuel and its associated piping away from all components of the engine exhaust system. BUILDING VENTILATION Once the exhaust system is installed it should be inspected on a regular basis to assure there are no toxic exhaust gas leaks. In some areas this inspection may be provided by your local public service. As hot air rises you must provide some type of power ventilation at the highest possible point of the building to permit the accumulating hot air to escape. This will help to prevent engine damage and it will help to eliminate hot restart problems. An electric powered exhaust fan of sufficient size will satisfy this requirement. This fan must connect to the generator set in a manner similar to the building's main heated cooling air exhaust fan. Generator End Cooling Requirements The cooling air requirements for the generator end are very similar to the cooling air requirements for the engine. These requirements are: 1. An adequate and constant supply of cooling air. 2. Adequate control and evacuation of the heated cooling air. GENERATOR END COOLING AIR If the above exhaust fan sizing recommendation is followed there will be an adequate supply of cooling air for the generator end. Please remember to not position the exhaust fan so it will pull the incoming cooling air away from the cooling air intake of either the engine or generator end. It is important to keep any and all flammable objects or materials away from the generator set, the remote muffler and its attached piping, or any other potential hot component of the installation. When discharging the heated cooling air or the hot exhaust gases out through the side of the building please contact your local building inspector to find out what is necessary for your application to meet local building code requirements and to prevent fire from occurring. You must clean and inspect both the exhaust fan and its louvers along with the building's cooling air intake on a regular basis to prevent reduction in the building's cooling air flow. This could lead to overheating and a potential fire or explosion.
27 BUILDING VENTILATION As hot air rises you must provide some type of power ventilation at the highest possible point of the building to permit the accumulating hot air to escape. This will help to prevent engine damage and it will help to eliminate hot restart problems. An electric powered exhaust fan of sufficient size will satisfy this requirement. This fan must connect to the generator set in a manner similar to the building's main heated cooling air exhaust fan.
28 EXHAUST REQUIREMENTS While it is important to supply the proper amount of clean air to the cylinder, it is equally important to discharge the gases of combustion. If these gases remain in the cylinder, the next cycle cannot burn the fuel completely. This condition results from excessive backpressure that is caused by any one or combination of these conditions: a. Exhaust pipe diameter too small. b. Exhaust pipe too long. c. Excessive number of sharp bends in exhaust system. d. Inadequate muffler. e. Incorrect construction of muffler resulting in high resistance. f. Obstruction in exhaust system. Backpressure must not exceed 20" (water column) on naturally aspirated engines or 27" (water column) on turbo-charged models. EXHAUST PIPING Exhaust lines should be as short and straight as possible, since extended runs and elbows tend to clog with carbon and resist the flow of gases. Each pipefitting and elbow will hinder the exhaust flow. The muffler should be as close to the engine as possible, since it will clog up with carbon if operating temperature is too low. NOTE: Never mount the muffler on the manifold. A flexible coupling must be provided between the exhaust line and the manifold. However, a short, solid section of pipe between 6" or 8" long should be placed between the connection of the manifold and the flexible coupling,. Water, one of the by-products of combustion, will be present in the exhaust piping or muffler. This water must be kept from draining back into the engine. This can be done by slanting the horizontal section of the exhaust pipe downward slightly, away from the engine. A water trap consisting of a tee extension with a drain cock should be provided. FIGURE 6-1: SCHEMATIC OF EXHAUST SYSTEM
29 FIGURE 6-2: DOUBLE THIMBLE - WALL OUTLET DETAILS EXHAUST PIPING THRU WALLS AND ROOFS Always check local and state laws pertaining to hot gas pipes before making plans for running exhaust piping thru walls or roofs. If the exhaust pipe must pass thru combustible walls or roofs, use an exhaust thimble to prevent exhaust pipe heat from being transmitted to the combustible material. Construction details of a typical thru wall double sleeve thimble is shown above thimbles are not available. They are usually fabricated at local sheet metal shops to the specifications furnished by the installation engineer. The minimum outside diameter of a double thimble (inner and outer sleeves) should be at least six inches greater than the diameter of the exhaust pipe with single sleeve thimbles, the O.D. should be at least 12 inches greater than the diameter of exhaust pipe. The minimum thimble diameters for some common exhaust pipe sizes are listed in the table below. The minimum thimble diameter for some common exhaust pipe sizes are listed in the table below. The thimbles should be constructed so that they extend at least 10" both ways from the surface of the wall or roof. Holes are provided at both ends to allow cooling air to circulate thru the thimble. If screening is used on the outer end to keep birds, rodents, etc., from entering the thimble, make sure the mesh is large enough so it doesn t impair air circulation through the thimble. If the exhaust pipe must exit thru a roof, EXHAUST THIMBLE - MINIMUM O.D. EXHAUST PIPE DIAMETER MINIMUM OUTSIDE DIAMETER SINGLE SLEEVE THIMBLE* DOUBLE SLEEVE THIMBLE** EXHAUST PIPE DIAMETER MINIMUM OUTSIDE DIAMETER SINGLE SLEEVE THIMBLE* DOUBLE SLEEVE THIMBLE** 0.5" 0.75" 1.0" 1.25" 1.5" 2.0" 12.5" 12.75" 13.0" 13.25" 13.5" 14.0" 6.5" 6.75" 7.0" 7.25" 7.50" 8.0" 2.5" 3.0" 3.5" 4.0" 5.0" 14.5" 15.0" 15.5" 16.0" 17.0" 8.5" 9.0" 9.5" 10.0" 11.0" *DIAMETER OF PIPE PLUS 12". **DIAMETER OF PIPE PLUS 6"
30 FIGURE 6-3 DOUBLE THIMBLE - ROOF OUTLET DETAILS a rain shield must be included above the thimble as shown in Figure 6-3. The rain cap as shown on the end of the exhaust pipe is recommended only in areas not subject to freezing temperatures. In an area where freezing is common, extend the exhaust piping well beyond the roof and use a gradual U bend at the end to direct the exhaust outlet downward which will keep rain, snow, etc., out of the pipe. Some other important points relating to exhaust outlets are as follows: Keep exhaust outlet well away from windows, doors, passageways, air intake vents or areas where gases could accumulate. Keep exhaust piping well away from fuel lines, fuel tank filler caps and combustible materials.
31 CONTROL PANEL OPERATION AND FUNCTION A. MASTER CONTROL SWITCH - This switch controls the starting and stopping of the engine via the engine control logic circuitry. With this switch in the Manual mode, the engine will start and run immediately after a second time delay. CAUTION: Please note that once the engine has been told to start, the gen set should be treated as though it is operational, even though the start delay has not yet allowed the engine to crank. With this switch in the Automatic mode, the engine can be started and stopped from a remote contact. (Standard switch, transfer switch, etc.) There is a time delay, to cool down, of seconds when the unit is shut down from the remote contacts while the Master Control Switch is in the Automatic Mode. With this switch in the Off position, the engine will immediately stop. The position must also be utilized to clear fault shut-down conditions. B. PANEL LIGHTS - By turning on the panel light switch, the panel lights will be energized and will illuminate the control panel. The fuse next to the switch is to protect this circuit from damage due to excessive current. C. FIELD AND CONTROLLER FUSES - These fuses protect the internal workings of the generator set. D. GAUGES - These gauges monitor some of the more critical operating parameters of the engine as well as the run time of the generator set. The Voltmeter displays the charging rate that is currently being produced by the engine s alternator to facilitate the charging of the battery. This gauge should normally be above 12.5V whenever the unit is running. If you ever notice the gauge is reading below 12V while the engine is running please contact the service department at Pow R Gard Generator Corporation. The Temperature Gauge monitors and displays the operating temperature of the engines coolant. The point at which a fault shut-down will occur is 230 O F. The Oil Pressure Gauge displays and monitors the current operating pressure of the engine s oil system. The trip point at which a fault shutdown will occur is 15 PSI or below. Fuel level is checked at the tank fill, inside the generator.
32 The Hour Meter accumulates and displays the total running time of the generator set. E. VOLTAGE ADJUST - The rheostat allows the user to fine tune the generator set s voltage output. It is normally used to adjust output voltage after switching the output of the generator set to a different voltage. F. METERS - These meters monitor and display the current operating parameters of the generator set. The Voltmeter monitors and displays the current operating AC output of the generator set. The Hertz Meter monitors and displays the current operating frequency of the generator set. The Ammeter monitors and displays the amount of current that is being delivered by the generator set. This meter works in conjunction with the Ammeter Switch (Item G) in determining which output leg to monitor. G. AMMETER SWITCH - The switch allows the user to switch between L1, L2 and L3 to monitor the current in each output leg to monitor. H. PANEL LIGHT - By turning on the panel light switch, the panel lights ( Not pictured on diagram) will be energized and will illuminate the control panel. They will also illuminate when a fault condition or a warning condition develops. I - SYSTEM FAULT INDICATORS - These lights will come on when a fault condition or a warning condition develops. The Low Oil Pressure light will come on when the engine s oil pressure drops below 15 PSI. This condition will trigger a fault shut-down and the unit will stop. The Over-crank light will come on when the engine has failed to start after four attempted crank cycles. Each crank cycle consists of a 12 second time period followed by a 12 second rest time period. The Over-speed light will come on when the engine s operating speed rises above it s normal operating parameters. This condition will trigger a fault shut-down and the engine will stop. High Temperature light will come on when the engine s operating temperature exceeds the safety setpoint.
33
34 OPERATION - PRE-START PROCEDURE 1. Fill system fuel tank with clean, fresh diesel fuel. Wipe up any and all fuel spillage 2. Fill Engine crankcase to full mark with clean, fresh lubricating oil per attached engine operating guide. 3. Radiator Coolant should be checked at the beginning of each day and filled in compliance with the engine manufacturer's guidelines. 4. Secure the generator for operation. Skid mounted - the power generating system should be mounted to a smooth, hard surface suitable for supporting the system under all stress conditions. Adequate clearance must be provided for access doors to fully open. OPERATION - STARTING 1. Conduct Pre-start Procedures. 2. Switch the generator set to the applicable voltage setting. 3. Connect the load(s) to the circuit breaker. WARNING: High voltage is present when the generator set is running. 4. Move the Master Control Switch to the appropriate position. 5. Adjust the voltage if necessary by turning the voltage adjustment knob located on the control panel.
35 OPERATION The Prime mover utilized in this power generating system is controlled via an engine control module. Starting is accomplished by commanding the control to "start" the engine. This command can be given by a number of controls; The operator control mounted on the front panel. The remote controls via the transfer switch or remote start terminal. Initially, the system may be started and operated by placing the operation control in the "manual" position. To cease operation, return the switch to the "off" position. Clear unit of all loose objects and perform all "pre- start" procedures before operating generator system. ENGINE CONTROL MODULE The Engine Control Module (E.C.M.) is a microprocessor based module that monitors the control and safety inputs and provides all the required START and STOP functions automatically. The following front panel controls and instruments are wired into the microprocessor through the E.C.M. terminal blocks: 1. RUN / OFF / AUTO SWITCH A. "RUN" - run position causes the generator set to start and run immediately. B. "AUTO" - auto position allows unit to be controlled via any remote single-pole "dry" contact (transfer switch, etc.). Contact closure causes the unit to start and run, while contact opening causes unit to shut down after a preset cool down period. C. "OFF" - unit operation is terminated. 2. LAMP TEST A. Push button energizes all alarm lights simultaneously. This feature is disabled with the Run / stop / auto switch in the "stop" position and has no other effect on unit operation. SAFETY INPUTS 1. Low Oil Pressure Shut-down- (LOP) Monitoring of oil pressure begins for a preset time after unit starts and remains in effect until unit is shut down (except as noted in "loss of frequency input". The LOP signal is derived from an oil pressure switch gauge mounted on the control panel. 2. High Temperature Shutdown (HT) The engine temperature monitoring begins immediately with the start signal. However, if engine temperature is excessive prior to start (i.e. heat soak after shutdown), the unit is permitted to start. The High temperature condition is permitted to exist for up to 60 seconds after the unit is running before shutdown when alarm occurs. If the excessive temperature condition is corrected within that time period, the HT circuit reverts to normal monitoring. The HT signal is derived from a monitoring device located on the prime mover.
36 3. Overspeed Adjustment (OS) - Over Frequency Overspeed protection is provided by a frequency sensing network within the controller. The trip point of the frequency network is adjustable via a rheostat located on the top of the controller at the right hand side. Clockwise (CW) rotation increases the trip frequency and, thereby, raises the shutdown speed. CRANKING CONTROL 1. Overcrank Protection This feature provides a preset second crank cycle. Failure of the engine to start by the end of the crank period results in an "overcrank" shutdown and alarm indication. 2. Cranking Disconnect Adjustment (CDS Adjustment) The cranking disconnect signal is obtained by a frequency network within the controller. The trip point of the frequency network is not adjustable. LOSS OF FREQUENCY Internal protection against loss of frequency input to the cranking disconnect circuit is programmed in after the unit has started normally. In the event the frequency goes to zero (engine runs out of fuel, frequency signal source fails, etc.) the LOP shutdown circuit is bypassed and a 12-second wait period is initiated. If frequency returns within this time period, LOP monitoring resumes and operation continues normally. If frequency has not returned at the end of this time period, the engine oil pressure status is observed to determine whether the engine is actually running or stopped. If the engine has stopped (i.e. air in fuel, etc.) the cranking cycle will begin in an effort to restart the engine. If the engine has not stopped (loss of input signal, etc.) the unit is shut down with an "overcrank" indication and alarm. "Overcrank" indication can mean a loss of crank-disconnect signal during the previous run period. Attempting to restart the engine with no crankdisconnect can destroy the starter motor, which can cause serious personal injury. This is of particular note since the tendency is to pursue only cranking and start related faults. The cranking disconnect signal source is a key component in this system and must be checked out thoroughly whenever an "overcrank" shutdown occurs. The controller does not provide protection against loss of signal during startup. A shutdown with alarm, due to any of the above conditions, will prevent any subsequent operation of the generator set. The run-stop-auto selector switch on the control panel must be momentarily placed in the "stop" position to reset these functions. If a dead battery is suspected, remove controller fuse, Replace with new battery and attempt starting. Damage to engine control may result from jumpstarting.
37 TROUBLESHOOTING - GENERATOR As with any machine, trouble may develop in electrical generators. It may be due to long service or neglect of regular maintenance. Servicing, and checking. Should trouble develop, the following instructions will be helpful in tracing the cause and making repairs. SPEED DEVITIONS: The generator speed should be maintained at rated nameplate speed. The frequency and voltage of the generator output depends on speed. If the generator runs slower than rated speed, the voltage will drop off. NO VOLTAGE CAUSE Loss of residual magnetism in exciter field poles. Open in stator windings Open or short in rotating rectifiers. Short Circuited. Open in alternator field Shorted exciter armature Shorted leads between exciter armature and generator field. CHECK AND REMEDY Flash Field. Check for continuity in windings. Return to factory for repair if open Check rectifiers. Clear lead to restore voltage build-up. Check for continuity and return rotor to factory for repair if field coils are open. Check for short and replace if faulty. Test and repair LOW VOLTAGE CAUSE Excessive load. Low Speed. Line loss. CHECK AND REMEDY Reduce load. With 3 phase generators, the load on each leg should be as evenly balanced as possible and should not exceed the rated current on any leg. Check engine for malfunction or system for overload. Increase size of line lead wire.
38 LOW VOLTAGE (Continued) CAUSE High resistance connections- Connections will be warm or hot Shorted field. Low power factor CHECK AND REMEDY Make better connection electrically and mechanically. Test field coils for possible short by checking resistance with an ohmmeter or resistance bridge. Return rotor assembly to factory for repair if alternator field coils are shorted. Reduce inductive (motor) load. Some AC motors Draw approximately the same current regardless of load. Do not use motors of larger horsepower rating than is necessary to carry the mechanical load. FLUCTUATING VOLTAGE (May be indicated by flickering lights.) CAUSE Irregular speed of engine. Fluctuating speed. Loose terminal or load connections. CHECK AND REMEDY Check engine for malfunction or load for fluctuation. Stabilize load. The addition of a lamp load (resistance load) may compensate partially for load changes caused by intermittent motor operation. Do not overload. Make better connection mechanically and electrically. Defective bearing causing uneven air gap. Replace worn bearing. HIGH VOLTAGE CAUSE Excessive speed. CHECK AND REMEDY Check engine for malfunction. OVERHEATING CAUSE Generator overloaded. Clogged ventilating screens. CHECK AND REMEDY Reduce load. (Check with ammeter and compare with nameplate rating.) Clean air passages.
39 OVERHEATING (continued) CAUSE High room temperature. Insufficient circulation. Low power factory. Unbalanced load Dry bearing. CHECK AND REMEDY Improve ventilation. Provide cross-ventilation. Reduce inductive loads or install power factor improvement capacitors. The load on each leg should be as evenly balanced as possible and should not exceed the rated current on any leg. Replace bearing. MECHANICAL NOISE CAUSE Defective bearing. Rotor scrubbing on stator. Loose laminations. Loose or misaligned coupling. CHECK AND REMEDY Replace bearing. Bad bearing; replace. Bent shaft, return to factory. Loosen end bell, tighten; loose drive discs, tighten. Return to factory. Tighten or align. GENERATOR FRAME PRODUCES SHOCK WHEN TOUCHED CAUSE Static charge. Grounded armature or field coil. CHECK AND REMEDY Ground generator frame. Return to factory for repair.
40 TROUBLESHOOTING - ENGINE CODE LIST OF POSSIBLE CAUSES 1. Battery capacity low. 33. Piston rings not free or are worn or broken. 2. Bad electrical connections. 34. Valve stems and/or guide worn. 3. Fault in starter motor. 35.West type air cleaner too full or wrong oil used. 4. Fault in starter motor. 36. Crankshaft bearings worn or damaged.. 5. Wrong grade of lubricating oil. 37. Not enough lubricating oil in the pump. 6. Low engine speed from starter motor. 38. Gauge not correct. 7. Stop control fault. 39. Lubricating oil pump worn. 8. Restriction in fuel lift pipe. 40. Relief valve not free to close. 9. Fault in fuel lift pump. 41. Relief valve not free to open. 10. Dirty fuel filter element. 42. Relief valve spring broken. 11. Restriction in air filter or induction system. 43. Fault in suction pipe of lubricating oil pump. 12. Air in fuel system. 44. Dirty lubricating oil filter element. 13. Fault in fuel injection pump. 45. Piston damaged. 14. Fault in atomizers or not correct type. 46. Piston height not correct. 15. Cold start equipment not used correctly. 47. Fan damaged. 16. Fault in cold start equipment. 48. Fault in engine mounting (housing). 17. Broken fuel injection pump drive. 49. Flywheel housing or flywheel not aligned 18. Fuel injection pump timing not correct. correctly. 19. Valve timing not correct. 50. Fault in thermostat or wrong type. 20. Bad compression. 51. Restriction in coolant passages. 21. restriction in fuel tank vent. 52. Water pump drive belt loose. 22. Type or grade of fuel not correct. 53. Restriction in radiator. 23. Restriction of engine speed control movement. 54. Fault in water pump. 24. Restriction in exhaust pipe. 55. Restriction in breather pipe. 25. Cylinder head gasket leaks. 56. Damaged valve stem oil seals (where used). 26. Engine temperature too high. 57. Not enough coolant in system. 27. Engine temperature too low. 58. Restriction in sump strainer. 28. Valve tip clearances not correct. 59. Valve spring broken. 29. Valves not free. 60. Fault in exhaust or vacuum pipe leakage. 30. Wrong high pressure pipes. 61. Turbo charger impeller damage, or dirty impeller. 31. Worn cylinder bores. 62. Turbo charger lubricating oil seal leaks. 32. Valves and seats do not seal correctly. 63. Induction system leaks (turbo charged engines.)
41 LIMITED WARRANTY Unless otherwise provided, Baldor generators are warranted against defects in Baldor workmanship and materials for a period of time as set forth in the Warranty Period chart on the following page. All warranty claims must be submitted to a Baldor Generator repair facility prior to the expiration of the warranty period. Baldor Generators shall have no responsibility or liability for any defect, latent or otherwise, discovered after the expiration of the warranty period provided herein. Extended warranties are available for certain Baldor products. These warranties are described in Baldor s catalog and other sales literature. Extended warranties are subject to the terms and conditions of this Limited Warranty as modified by the additional terms of the extended warranty. If a Baldor product is defective due to Baldor workmanship or materials and the defect occurs during the warranty period, then Baldor will either repair the product or replace it with a new one, whichever Baldor believes to be appropriate under the circumstances. Warranty service is available for all Baldor Generator products from Baldor Generators Customer Service Department in Oshkosh, Wisconsin, and from Baldor Generator repair facilities. A list of Baldor s generator repair facilities may be obtained by contacting Baldor Generators at: Customer Service, Baldor Generators, 3815 Oregon Street, Oshkosh, Wisconsin 54902, (telephone), (facsimile). All Baldor products requiring warranty service shall be transported or shipped freight pre-paid, at the risk of the party requiring warranty service, to Baldor Generators Customer Service Department in Oshkosh, Wisconsin, or to a Baldor Generator repair facility. Written notification of the alleged defect in addition to a description of the manner in which the Baldor generator is used, and the name, address and telephone number of the party requiring warranty service must be included. Baldor is not responsible for removal and shipment of the Baldor product to the service center or for the reinstallation of the Baldor product upon its return to the party requiring warranty service. Customers who are unable to take or ship the Baldor product to a Baldor Generator repair facility, or who desire a repair to be made by other than a Baldor Generator repair facility, should contact Baldor Generators Customer Service Department at Baldor, in advance of such service, must approve a repair by anyone other than a Baldor Generator repair facility in writing. Problems with Baldor products can be due to improper maintenance, faulty installation, non-baldor additions or modifications, or other problems not due to defects in Baldor workmanship or materials. If a Baldor Generator repair facility determines that the problem with a Baldor product is not due to defects in Baldor workmanship or materials, then the party requiring warranty service will be responsible for the cost of any necessary repairs. Parties requiring warranty service not satisfied with a determination that a problem is outside of warranty coverage should contact Baldor Generators Customer Service Department at for further consideration. EXCEPT FOR THE EXPRESSED WARRANTY SET FORTH ABOVE, BALDOR GENERATORS DISCLAIMS ALL OTHER EXPRESSED AND IMPLIED WARRANTIES INCLUDING THE IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE AND MECHANTABILITY. NO OTHER WARRANTY, EXPRESSED OR IMPLIED, WHETHER OR NOT SIMILAR IN NATURE TO ANY OTHER WARRANTY PROVIDED HEREIN, SHALL EXIST WITH RESPECT TO THE GOODS SOLD UNDER THE PROVISIONS OF THESE TERMS AND CONDITIONS. ALL OTHER SUCH WARRANTIES ARE HEREBY EXPRESSLY WAIVED BY THE BUYER. UNDER NO CIRCUMSTANCES SHALL BALDOR GENERATORS BE LIABLE OR RESPONSIBLE IN ANY MANNER WHATSOEVER FOR ANY INCIDENTAL, CONSEQUENTIAL OR PUNATIVE DAMAGES, OR ANTICIPATED PROFITS RESULTING FROM THE DEFECT, REMOVAL, REINSTALLATION, SHIPMENT OR OTHERWISE. This is the sole warranty of Baldor Generators and no other affirmations or promises made by Baldor Generators shall be deemed to create an expressed or implied warranty. Baldor Generators has not authorized anyone to make any representations or warranties other than the warranty contained herein. Revised\Effective 6/26/03 Form # S-PSG Warranty Policy S-PSG doc
42 WARRANTY PERIOD Generator Series Labor* Parts Portable Products (Premier, PowerChief, 1 Year 3 Years DG Series, K Series) Towable Products (TS) 1 Year or 3,000 Hours Whichever comes first 3 Years or 3,000 Hours Whichever comes first 3600 RPM Standby Systems (Some AE Models) 1 Year or 1,000 Hours Whichever comes first 3 Years or 1,000 Hours Whichever comes first 1800 RPM Standby Systems 1 Year or 3,000 Hours 3 Years or 3,000 Hours (Some AE Models, DLC, Whichever comes first Whichever comes first GLC) Industrial Standby Systems 1 Year or 1,000 Hours 2 Years or 1,000 Hours Industrial Prime Power Systems International Whichever comes first 1 Year or 1,000 Hours Whichever comes first 1 Year or 1,000 Hours Whichever comes first Whichever comes first 1 Year or 1,000 Hours Whichever comes first 1 Year or 1,000 Hours Whichever comes first *Labor coverage for warrantable repairs is provided for the applicable period not to exceed published rates as contained in the Baldor Generators Warranty Policy. Mileage is allowed only for permanent installations not to exceed published rates as contained in the Baldor Generators Warranty Policy. Warranty registration within 30 days of purchase is required for portable and towable products to qualify for any warranty consideration. Proof of purchase date, serial number and model number will be required for all warranty work. For all other products, a Start-up Inspection Form / Warranty Registration must be completed in its entirety and submitted to Baldor Generators within 30 days of start-up to qualify for any warranty consideration. Owner s Responsibilities: The owner is obligated to operate and maintain the generator in accordance with the recommendations published by Baldor Generators in the Operator s Manual for the generator. The owner is responsible for the costs associated with maintenance and any adjustments that may be required. The owner is responsible for payment of any of the following expenses that might be incurred as a result of a failure under the terms of this warranty: 1. Rental equipment used to replace the equipment being repaired. 2. Telephone or other communication expenses. 3. Living and travel expenses of persons performing service, except as specifically included within the terms of specific warranty. 4. The premium costs for overtime labor requested by the owner. 5. All parts transportation costs. Revised\Effective 6/26/03 Form # S-PSG Warranty Policy S-PSG doc
43 Limitations: Baldor Generators is not responsible for the repair of generators required because of normal wear, accident, misuse, abuse, improper installation, lack of maintenance, unauthorized modifications or improper storage. Normal Wear: This warranty will not cover repair where normal use has exhausted the life of a part or generator. It should be remembered that the service life of any generator is dependent on the care it receives and the conditions under which it has to operate. Some applications are very often used in dusty or dirty conditions, which can cause what appears to be excessive wear. Such wear, when caused by dirt, dust, grit or other abrasive material, which has entered the generator because of improper maintenance, is not covered by Warranty. For all product lines, the engine manufacturer warrants engine systems. Contact Baldor Generators for current engine warranties Oregon Street Oshkosh, Wisconsin Phone: (920) Fax: (920) Revised\Effective 6/26/03 Form # S-PSG Warranty Policy S-PSG doc
44 It is required that both sides of this form be filled out completely, signed where indicated and returned to Baldor Generators within 30 days of initial Start-up and test. It is your responsibility to insure that copies are distributed to: For Standby, Automatic Emergency And Prime Power Generators Factory Distributor Customer DISTRIBUTOR INFORMATION Name: Address: END USER / OWNER INFORMATION Name: Address: Phone: Phone: Model Number: Job Number: RPM HZ P.F. Standby or Continuous Engine Model#: Engine Serial# : KW Volts KVA Amps Generator Model#: Generator Serial #: List Distributor Installed Items: List Items Installed by Others: Engine Hour Meter Power Output VOLTAGE CURRENT Oil Temp. KW HZ NO LOAD Oil Pressure Water Temp. Amb. Temp. Start-Up Performed By: Address: Date: Technician: Phone: Customer Signature:
45 Pre Start-Up Check List No Freight Damage (Components Tight, Straight, Etc.). Proper Belt Alignment And Tensions. Flex Fuel Lines Installed Between Engine And Tank. Fluid Levels (Oil, Antifreeze, Battery, Governor, Etc.) Check For Leaks, Tighten As Necessary. Correct Fuel And Exhaust Plumbing. Adequate Air Flow. Correct AC Wire Sizes And Connections. Correct DC Wire Sizes And Connections (Route Separate From AC). Block Heater Is Operational. Bleed And Prime The Fuel System; Check For Leaks. Correct As Necessary. On Natural Gas Fueled Sets, Gas Pressure Of 4-6 Oz. Of Pressure With Adequate Volume Is Available. Gas Solenoid Valve Is Properly Functioning. Exhaust Line and Flexible Connections are Properly Installed Without Excessive Bends and Restrictions. Exhaust System Termination Properly Located to Prevent Entry of Exhaust Gas Into Building. Batteries Properly Filled with Electrolyte & Properly Connected to the Engine. Battery Charger Must Be Properly Installed & Connected to the Battery. Battery Must Be Fully Charged Prior to Start-up. Generator Load Connectors of Proper Ampacity are Connected to Either the Circuit Breaker or the Emergency Side of the Transfer Switch. The Nameplate Voltage & Frequency of the Genset Matches that of ATS & Normal Source. Comments: Start-Up Procedure Check That All Applicable Warning Decals Are In Their Proper Place And Are Legible. The ATS Engine Start Wires and other DC Wires, if Any, Must be Properly Connected. All Wiring Connections are Tight. The Equipment Room is Clean & All Unrelated Materials Removed. The Equipment is Protected from Possible Fire Damage by Fire Extinguisher System. Earthquake Protection (when Applicable) is Adequate for the Equipment. Open Generator Mainline Breaker or Remove Fuses. Turn Down Speed Potentiometer (Electronic Governor) or Speed Screw (Mechanical Governor). Move Switch to "Manual". let the Engine Start & Run. After a Few Minutes, Check Oil Pressure & Check for Leaks. Adjust the Speed to 60/50hz if Equipped with Electronic Governor or 63/53 Hz with Mechanical Governor. If Speed is Unstable, Adjust Per Engine or Governor Manual. Adjust the AC Voltage to Match the Normal Source. Let the Unit Run Until Engine Reaches Proper Water Temp. Close Generator Mainline Breaker or Replace Fuses.. Manually Over-Speed the Unit Until Engine Shutdown (68-70 Hz or 60 Hz Generators ; Hz on 50 Hz Generator Sets. Test Automatic Shut-Downs (Low Oil Pressure, Low Coolant Level, High Coolant Temperature, Overspeed set to Hz Other ) **INSTRUCT END USER ON FUNCTIONS OF UNIT***. Set Times to Customer's Request and Run a Simulated Power Outage. Instruct the Customer in Proper Operation & Maintenance of the System and Make Sure They Have Correct Manuals. RETURN THIS COMPLETED FORM TO: Baldor Generators 3815 Oregon Street Oshkosh WI 54902
46 3518 Oregon Street Oshkosh WI Phone: Fax: Baldor Generators firmly believes proper installation along with proper maintenance are critical factors in assuring proper, dependable, safe and long term operation. The checklist was developed for making sure your installation is correct to help achieve these goals. If you have any questions about this checklist, please contact the Product Support Group at Many measurements, adjustments and procedures mentioned in this checklist could cause damage, injury or even death if not performed properly. Only qualified, experienced individuals may perform these measurements, adjustments and procedures. When completed, please mail this checklist to Baldor Generators.
47 CALIFORNIA PROPOSITION 65 WARNING Engine exhaust from this product contains chemicals known to the state of California to cause cancer, birth defects, and other reproductive harm. CALIFORNIA PROPOSITION 65 WARNING Diesel engine exhaust and some constituents are known to the state of California to cause cancer, birth defects, and other reproductive harm.
48 Service is just a phone call away: Oregon Street Oshkosh WI Phone: (920) Fax: (920)
Installation Instructions for Alarm Module Kit A043F059
Instruction Sheet 07-2013 Installation Instructions for Alarm Module Kit A043F059 1 Introduction The information contained within is based on information available at the time of going to print. In line
32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 113 kva, 90 kw 124 kva, 99 kw 6WDQGE\ 114 kva, 91 kw 125 kva, 100 kw
,1'8675,$/#*(16(7 6HULHV#'9#448 32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 113 kva, 90 kw 124 kva, 99 kw 6WDQGE\ 114 kva, 91 kw 125 kva, 100 kw Generator set consisting of engine and alternator mounted
26 3213.13 Diesel Engine Driven Generators Page 1 of 6
Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at
USER S, MAINTENANCE and SERVICE INFORMATION MANUAL
CONTENTS SAFETY INFORMATION................ 2 FOR YOUR SAFETY....................... 2 SYSTEM OPERATION.................. 2 THERMOSTATS........................... 2 INTERMITTENT IGNITION DEVICE...........
SL280UHV SERIES GAS FURNACE WARNING
2010 Lennox Industries Inc. Dallas, Texas, USA 506677 01 11/2010 Supersedes 506409 01 SL280UHV SERIES GAS FURNACE Litho U.S.A. FIRE OR EXPLOSION HAZARD. Failure to follow safety warnings exactly could
Oil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
P 602. This generator set has been designed to meet ISO 8528 regulation. This generator set is manufactured in facilities certified to ISO 9001.
This generator set has been designed to meet ISO 88 regulation. This generator set is manufactured in facilities certified to ISO 900. This generator set is available with CE certification. Enclosed product
Frequently Asked Questions Generators
Frequently Asked Questions Generators Fuel Related How much fuel do the generators use during normal operation? At exercise? The generator fuel consumption is given in each of the product knowledge books
CARING FOR YOUR WATER HEATER
http://waterheatertimer.org/troubleshoot-rheem-tankless-water-heater.html Water Heater Inspections CARING FOR YOUR WATER HEATER Venting System (Direct Vent Only) The venting system should be inspected
3620 W 11th Streetб Houston, TX 77008 Telephone: 713-635-6291 Email: [email protected] Website: www.kellogg-american.com
Unpackaging & Handling Be sure to carefully inspect the unit before accepting the shipment. If any damage has occurred document it with the trucking company immediately. Contact your Kellogg Distributor
BC-5000 OPERATIONS MANUAL BATTERY CAPACITY TESTER COFKO LLC.
BC-5000 BATTERY CAPACITY TESTER OPERATIONS MANUAL COFKO LLC. COPYRIGHT 2010 1 UNPACKING As you unpack your new BC-5000 battery capacity tester, inspect the tester for signs of shipping damage. If shipping
Diesel Generating Set
MODEL Standby Power(50Hz) Prime Power(50Hz) 44KW /55KVA 40KW /50KVA Standard Features General Features: Engine( DCEC Cummins 4BTA3.9 -G) Radiator 40 O C max,fans are driven by belt, with safety guard 24V
4000 Series 4008TAG2A Diesel Engine ElectropaK 947 kwm @ 1500 rpm
The Perkins 4000 Series family of 6, 8, 12 and 16 cylinder diesel engines was designed in advance of today s uncompromising demands within the power generation industry and includes superior performance
Standby Generators FEATURES. Standby Generators Liquid-Cooled Gas Engine. Standby Generators INCLUDES:
Standby Generators Liquid-Cooled Gas Engine 1 of 9 INCLUDES: Two Line LCD Tri-Lingual Digital Nexus Controller Isochronous Electronic Governor Sound Attenuated Enclosure Closed Coolant Recovery System
Fire Pump Plan Review March 2010
Fire Pump Plan Review March 2010 Date of Review: / / Permit Number: Business/Building Name: Address of Project: Designer Name: Designer s Phone: Contractor: Contractor s Phone: Occupancy Classification:
DLW 8. POWER RATING 1500 rpm/50 Hz 1800 rpm/60 Hz Prime 7.5 kva, 6 kw 9.1 kva, 7.3 kw Standby 8.5 kva, 6.8 kw 10.1 kva, 8.1 kw
DLW 8 POWER RATING 1500 rpm/50 Hz 1800 rpm/60 Hz Prime 7.5 kva, 6 kw 9.1 kva, 7.3 kw Standby 8.5 kva, 6.8 kw 10.1 kva, 8.1 kw Generator set consisting of engine and alternator mounted on a fabricated steel
Annex-A TECHNICAL SPECIFICATION
Annex-A TECHNICAL SPECIFICATION FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF 0.4kV (2,000kVA) DIESEL GENERATOR 1 1.0 SCOPE This specification covers the requirements of design, manufacture, delivery
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Pump Plan Review 2009 International Fire Code and NFPA 20 Date of Review / / BLD201 - Project Address: Project Name: Contractor s Business
Voltmaster Trash Pumps Model TSP2, TSP3 and TSP4
Model TSP2, TSP3 and TSP4 Owner s Manual July 2010 Table of Contents 1 Introduction...................................................... 1 1.1 Read before using..............................................
BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION
Air Conditioning Central Heating & Cooling BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION INSTALLATION AND SERVICE MANUAL 2 PROJECT: ADDRESS: MODEL: SERIAL NUMBER: INSTALLER: ADDRESS: PHONE NUMBER: INSTALLATION
IMPORTANT SAFETY INSTRUCTIONS WARNING READ AND SAVE THESE OPERATING AND SAFETY INSTRUCTIONS BEFORE USING THIS HEATER.
THERMAWAVE CERAMIC HEATER Model HZ-850 Series Model HZ-860 Series IMPORTANT SAFETY INSTRUCTIONS WARNING READ AND SAVE THESE OPERATING AND SAFETY INSTRUCTIONS BEFORE USING THIS HEATER. Warning Failure to
OWNER S MANUAL BIG BEAR VORTEX FAN MODEL #BB-1 INTRODUCTION OPERATION SAFETY SERVICE WARRANTY CONTACT SPECIFICATIONS TROUBLESHOOTING
OWNER S MANUAL BIG BEAR VORTEX FAN MODEL #BB-1 INTRODUCTION OPERATION SAFETY SERVICE WARRANTY CONTACT SPECIFICATIONS TROUBLESHOOTING PLEASE READ AND SAVE THESE INSTRUCTIONS - 2 - INTRODUCTION TO THE BIG
AGP15 Perkins Series Gen Set Stand-by Specification Sheet Stand by Rating - 15KW (20KVA) Continuous Rating 13KW(18KVA) 60HZ
Stand-by Specification Sheet Stand by Rating - 15KW (20KVA) Continuous Rating 13KW(18KVA) 60HZ Standard Features 3 Cylinder Diesel Engine for maximum durability, reliability and efficiency. Brushless alternator
Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling
Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling 250_P1 R10/7/2015 Copyright 2015 Liberty Pumps Inc. All rights reserved. Specifications subject to change without notice.
THC 85 INDUSTRIAL / COMMERCIAL SPACE HEATER
THC 85 INDUSTRIAL / COMMERCIAL SPACE HEATER Certified to / Certifié à CGA 2.14 M2000 Conforms to / Conforme à ANSI std Z83.7 2000 Suitable for indoor or outdoor installation / Unvented / Unattended Type
SWIMMING POOL HEAT PUMP
SWIMMING POOL HEAT PUMP Installation & User Manual Model HP40B HP50B HP65B Hayward Pool Products Canada, Inc. T: 1-888-238-7665 www.haywardpool.ca CONTENT I. Application 4 II. Features 4 III. Technical
GNOME PELLET E.I. Pellet Heater Owner's Manual Installation and Operating Instructions. Please read this entire manual before installation.
Pellet Heater Owner's Manual Installation and Operating Instructions Please read this entire manual before installation. Save these instructions. SAFETY NOTICE HEATER MUST BE PROPERLY INSTALLED AND MAINTAINED
Spark-ignited generator set
Specification sheet Spark-ignited generator set 30 60 kw standby EPA emissions Description Cummins Power Generation commercial generator sets are fully integrated power generation systems providing optimum
15GAL STEEL OIL DRAIN WITH 110V PUMP
15GAL STEEL OIL DRAIN WITH 110V PUMP OWNER S MANUAL WARNING: Read carefully and understand all ASSEMBLY AND OPERATION INSTRUCTIONS before operating. Failure to follow the safety rules and other basic safety
UHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual
UHIR Series Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater Owner s Manual This manual covers installation, maintenance and repair parts. Read carefully before attempting to
ENGINE COOLING SYSTEM
ENGINE COOLING SYSTEM 1988 Toyota Celica 1987-88 TOYOTA Engine Cooling Systems Celica DESCRIPTION The basic liquid cooling system consists of a radiator, water pump, thermostat, cooling fan, pressure cap,
ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013
ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 READ CAREFULLY These instructions are intended to cover good practices in
400 Amp Rechargeable Jump Start System RAC-HP082
400 Amp Rechargeable Jump Start System RAC-HP082 MAINTENANCE Always inspect the tool before use to ensure the cables are in good condition and the clamps are clean and free from corrosion. Keep clean by
C18 ACERT Fire Pump Tier 3 448 bkw/600 bhp @ 1750 rpm
CATERPILLAR ENGINE SPECIFICATIONS I-6, 4-Stroke-Cycle Diesel Bore...145.0 mm (5.71 in) Stroke...183.0 mm (7.2 in) Displacement... 18.1 L (1,104.53 in3) Aspiration...Turbocharged Aftercooled Compression
Magnum Mobile Generator MMG55 Specifications
Empowering Real People Magnum Mobile Generator MMG55 Specifications ENGINE John Deere PE5030TF270 - turbocharged, diesel engine o Prime - 72 hp @ 1800 rpm o Standby - 80 hp @ 1800 rpm o 4 cylinder o 3.0
Single Phase Soft Starter
Single Phase Soft Starter Installation & Operating Manual 6/02 Table of Contents Section 1 General Information................................................... 1 1 General Description................................................
OPERATOR S MANUAL 18 VOLT, 1 HOUR CHARGER
OPERATOR S MANUAL 18 VOLT, 1 HOUR CHARGER P110 Your battery charger has been engineered and manufactured to Ryobi s high standard for dependability, ease of operation, and operator safety. When properly
32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 10.4 kva, 8.3 kw 12.9 kva, 10.3 kw 6WDQGE\ 11.3 kva, 9 kw 14.4 kva, 11.5 kw
,QGXVWULDO#*HQHUDWRU 32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 10.4 kva, 8.3 kw 12.9 kva, 10.3 kw 6WDQGE\ 11.3 kva, 9 kw 14.4 kva, 11.5 kw Generator set consisting of engine and alternator mounted
Single-Phase AC Synchronous Generator
ST Series Single-Phase AC Synchronous Generator Instructions for Operation and Maintenance English to English translation by R.G. Keen, May 2004. ST Series of Single-Phase AC Synchronous Generators Description
FOR THE FOLLOWING MODELS: EE-8075W EE-8075O EE-8075R EE-8075BK
FIREPLACE HEATER FOR THE FOLLOWING MODELS: EE-8075W EE-8075O EE-8075R EE-8075BK If you have any questions about the operation of your fireplace heater, please contact Crane Customer Care. Toll Free: 888-599-0992
LOAD BANK TESTING PROCEDURE
LOAD BANK TESTING PROCEDURE APPENDIX G SPS-G-1 of 9 I. General GENERATOR LOAD BANK TESTING AND ENGINE TESTING A. Provide all equipment, labor, materials and supervision necessary to test the stand-by diesel
TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL 387030095 AW64AL 0.8180.463.0 07/05
TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: AW52AL AW64AL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. AW52AL 387030095 AW64AL 387030096 0.8180.463.0 07/05 IMPORTANT! Please read before installation
Dennis Fire Department Fire Prevention Mark Dellner Fire Chief
Dennis Fire Department Fire Prevention Mark Dellner Fire Chief FIRE SAFETY INSPECTION GUIDELINES FOR COMMERCIAL PROPERTIES (MA Fire Prevention Regulations 527 CMR, MGL Chapter 148) FIRE PREVENTION CHECKLIST-
CDS TROUBLESHOOTING SECTION I. VACUUM. 1.0. Weak vacuum at wand. Gauge reads normal (10hg to 14hg)
CDS TROUBLESHOOTING SECTION I. VACUUM 1.0. Weak vacuum at wand. Gauge reads normal (10hg to 14hg) 1.1. Clogged hoses or wand tube. Disconnect hoses and carefully check for an obstruction. 1.2. Excessive
Operating Instructions Split System Air Conditioner
Operating Instructions Split System Air Conditioner Model No. Indoor Unit Type Indoor Unit Type Nominal Capacity 26 36 F2 Low Silhouette Ducted S-26PF2U6 S-36PF2U6 Connectable outdoor unit lineup This
12V Portable Diaphragm Compressor Operating and Maintenance Instructions
12V Portable Diaphragm Compressor Operating and Maintenance Instructions (Part No. DC2) Part No. Serial Number Date Purchased Table of Contents Page Safety Messages...2 Guidelines for Product Use...2 Operation
Portable Evaporative Air Cooler. OWNER S MANUAL Read and save these instructions before use. Model: CL30XC
Portable Evaporative Air Cooler OWNER S MANUAL Read and save these instructions before use Model: CL30XC Power rating: 250 Watts Voltage rating: 230 Volt, 50Hz Made in P.R.C. QUICK START GUIDE Fill with
Air Conditioner Water Heater - A Product of HotSpot Energy LLC
Air Conditioner Water Heater - A Product of HotSpot Energy LLC PLEASE READ THIS BEFORE YOU INSTALL THE UNIT 1. This air conditioner must be installed and/or repaired by a qualified technician. If you perform
FJ2. 2 Ton Trolley Floor Jack Assembly & Operating Instructions
FJ2 2 Ton Trolley Floor Jack Assembly & Operating Instructions READ ALL INSTRUCTIONS AND WARNINGS BEFORE USING THIS PRODUCT. This manual provides important information on proper operation & maintenance.
WWW.CALIFORNIAAIRTOOLS.COM Customer Support 1-866-409-4581
sound proof AIr CoMprEssor CAbInEt owner's MAnuAl spc03 WWW.CALIFORNIAAIRTOOLS.COM Customer Support 1-866-409-4581 TAbLe OF CONTeNTS INTROduCTION IntroductIon 2 Important Safety InStructIonS 5 components
OWNER S MANUAL. Model AE150/AE300/AE500 1.5AMP MULTI-USE SMART BATTERY CHARGER READ ENTIRE MANUAL BEFORE USING THIS PRODUCT
Model AE150/AE300/AE500 MULTI-USE SMART BATTERY CHARGER Certified by Californiia BCS Regulations AE300E AE500E 5AMP MULTI-USE AUTOMOTIVE BATTERY CHARGER 3AMP MULTI-USE SMART BATTERY CHARGER AE500E 5AMP
LAKE COUNTY ANIMAL SERVICES EXPANSION SECTION 15459
SECTION 15459 PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification sections, apply to work
IMPORTANT SAFETY NOTICE
IMPORTANT SAFETY NOTICE To: Our Valued Customers User safety is a major focus in the design of our products. Following the precautions outlined in this manual will minimize your risk of injury. ITT Goulds
Ceiling Mount Air Handler Manual
www.surna.com 303.993.5271 Ceiling Mount Air Handler Manual Models: CMAH12, CMAH18, CMAH24, CMAH30, CMAH36, CMAH48, CMAH60 Revised: September 2014 Table of Contents Warranty Information 4 Limited Warranty
Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal
Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable
Threaded Inline Air Heaters
Threaded Inline Air Heaters FOR SAFETY & LONG HEATER LIFE, CAREFULLY READ THIS MANUAL BEFORE USE. Safety SHOCK HAZARD! Only qualified individuals should install this heater and related controls. Follow
DIESEL GENERATOR SET. 60 Hz FEATURES GENERATOR SET
DIESEL SET STANDBY Model Standby Prime kw (kva) kw (kva) D40-4 40 (50) 36 (45) D40-4S 40 (40) 36 (36) D50-4 50 (62.5) 45 (56.3) D50-4S 50 (50) 45 (45) D60-4 60 (75) 54.6 (68.2) All models are Tier II EPA
Operator s Manual. PUMP Model: PAC25 SAVE THIS MANUAL FOR FUTURE REFERENCE. Distributed by: Pacer Pumps
Operator s Manual PUMP Model: PAC25 CAUTION: Before using this product, read this manual and follow all Safety Rules and Operating Instructions. SAVE THIS MANUAL FOR FUTURE REFERENCE Distributed by: Pacer
3516 Industrial Engine
CAT ENGINE SPECIFICATIONS V-16, 4-Stroke-Cycle Diesel Bore...170.0 mm (6.69 in) Stroke...190.0 mm (7.48 in) Displacement... 69.06 L (4,214.3 in 3 ) Aspiration...Turbocharged / Aftercooled Compression Ratio...13.0:1
MODEL T-4 TRENCHER. Operators Manual
DO NOT THROW AWAY IMPORTANT MANUAL MODEL TRENCHER Operators Manual P.O.BOX 290 San Bernardino, CA. 92402 Phone (909) 478-5700 (800) 922-4680 Fax (909) 478-5710 E-mail: [email protected] www.groundhoginc.com
Ducoterra Radiant Heating Panel Installation Manual
Ducoterra Radiant Heating Panel Installation Manual 1. Introduction Your new radiant heating panels are designed to heat living and working spaces rapidly and efficiently by radiant heating. Like the sun,
Trouble Shooting. Pump
Trouble Shooting Pump Trouble Possible Cause Remedy Oil leaking in the area of water pump crankshaft Worn crankshaft seal, bad bearing, grooved shaft, or failure of retainer o-ring. Excessive play on crankshaft
12 Volt 30 Amp Digital Solar Charge Controller
12 Volt 30 Amp Digital Solar Charge Controller User s Manual WARNING Read carefully and understand all INSTRUCTIONS before operating. Failure to follow the safety rules and other basic safety precautions
Industrial Process Pump Safety Manual IMPORTANT SAFETY NOTICE
Industrial Process Pump Safety Manual IMPORTANT SAFETY NOTICE To: Our Valued Customers User safety is a major focus in the design of our products. Following the precautions outlined in this manual will
Topics of the Presentation
Drill Rig Safety Topics of the Presentation Personnel safety and monitoring PPE Health (Drugs and Alcohol) Drill Rig operation Safe set up procedures Safe operation of machine Safety related accidents
INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR THREE PHASE INDUCTION MOTORS
INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR THREE PHASE INDUCTION MOTORS Frames 143T - 449TZ 5100 North IH 35 Round Rock, Texas 78681 Phone: 800-451-8798 512-255-4141 Fax: 512-244-5512 RECEIVING 1. Check
Preventing Overheated Boiler Incidents
Preventing Overheated Boiler Incidents PSE&G Appliance Service October 2012 Runaway Boiler Explosion Review Items Hazard Background Past Incidents PSE&G Emergency Response Future Process Improvements What
OPTIONAL SLENDER REMOTE CONTROL
DAIKIN ROOM AIR CONDITIONER Operation Manual OPTIONAL SLENDER REMOTE CONTROL BRC944A2B READ BEFORE OPERATION Safety Precautions...2 Names of Functions of Parts...4 Preparation before Operation...5 OPERATION
tire inflator with pressure gauge
tire inflator with pressure gauge Model 95583 Assembly And Operation Instructions Due to continuing improvements, actual product may differ slightly from the product described herein. 3491 Mission Oaks
Tankless Water Heater
Tankless Water Heater USER S INFORMATION MANUAL Models WGRTNG199 / WGRTLP199 WGRTCNG199 / WGRTCLP199 NOTICE: Westinghouse reserves the right to make product changes or updates without notice and will not
AIR-CONDITIONER SPLIT TYPE
FILE NO. A08-016 SERVICE MANUAL AIR-CONDITIONER SPLIT TYPE RAS-M10PKVP-E, RAS-M13PKVP-E, RAS-M16PKVP-E, RAS-M18PKVP-E / RAS-M10PKVP-ND, RAS-M13PKVP-ND, RAS-M16PKVP-ND, RAS-M18PKVP-ND / RAS-3M26GAV-E1,
IMPORTANT INSTRUCTIONS & OPERATING MANUAL. Houston 50 Inch Electric Wall Mounted Fireplace Black / White
IMPORTANT INSTRUCTIONS & OPERATING MANUAL Houston 50 Inch Electric Wall Mounted Fireplace Black / White Model Number:MFE5050BK Model Number:MFE5050WH Read these instructions carefully before attempting
3000W Power Inverter
3000W Power Inverter OWNER S MANUAL Model number-4573000 TO REDUCE THE RISK OF INJURY, USER MUST READ AND UNDERSTAND THIS INSTRUCTIONAL MANUAL. THIS MANUAL CONTAINS IMPORTANT INFORMATION REGARDING THE
Factory owners must ensure the boiler is:
Factory owners must ensure the boiler is: * Registered with the Boilers and Pressure Vessels Division, Labour Department * Examined by an appointed examiner and has a valid certificate of fitness * Supervised
DIESEL GENERATOR SETS
DIESEL SETS STANDBY Standby Prime Model kw (kva) kw (kva) D175-2* 175 (218.8) 157.5 (196.9) *Tier 3 EPA Approved, Emissions Certified Picture shown may not reflect actual package FEATURES SET Complete
SV710-SV740. SV810-SV840 Owner's Manual
SV710-SV740 SV810-SV840 Owner's Manual IMPORTANT: Read all safety precautions and instructions carefully before operating equipment. Refer to operating instruction of equipment that this engine powers.
GEP550 (3-Phase) 50 HZ. 500 kva / 400 kw FEATURES. Exclusively from your Caterpillar dealer
D I E S E L G E N E R A T O R S E T GEP550 (3-Phase) 50 HZ STANDBY PRIME 550 kva / 440 kw 500 kva / 400 kw FEATURES GENERATOR SET Complete system designed and built at ISO9001 certified facility Factory
PC1131 Electric Air Compressor
Senco Products Inc. 8485 Broadwell Road Cincinnati, Ohio 45244 PC1131 Electric Air Compressor Operating Instructions 2006 by Senco Products, Inc. Warnings for the safe use of this tool are included in
San josé OWNER S MANUAL
San josé OWNER S MANUAL Assembling & operating manual San josé 30 mbar - PORTABLE GAS BARBECUE 1. 2. 3. Improper installation, adjustment, alteration, service or maintenance can injury or property damage.
Portable Air Conditioner
Portable Air Conditioner Owner's Manual Model:3 in 1 12,000 Btu/h Series 3 Please read this owner s manual carefully before operation and retain it for future reference. CONTENTS 1. SUMMARY...1 2. PORTABLE
! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-217(I) Series 150S and 157S (Snap Switch, All Models except 157S-RB-P)
Series 150S and 157S (Snap Switch, All Models except 157S-RB-P) Low Water Cut-Off/Pump Controllers For Steam Boilers and Other Level Control Applications McDonnell & Miller Installation & Maintenance Instructions
Pump Specifications 405 Series Commercial Drain Pump (High-Temp) 2 Solids handling
Pump Specifications 405 Series Commercial Drain Pump (High-Temp) 2 Solids handling 405_P1 R1/27/2012 Copyright 2012 Liberty Pumps Inc. All rights reserved. Specifications subject to change without notice.
Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)
Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety
accidents which arise due to nonobservance and the safety information herein.
20 GALLON COMPRESSOR Model: 7342 CALIFORNIA PROPOSITION 65 WARNING: You can create dust when you cut, sand, drill or grind materials such as wood, paint, metal, concrete, cement, or other masonry. This
Atlas Copco Generators
Atlas Copco Generators QIX 15 - QIX 540 16 kva LTP to 549 kva LTP at 50 & 60 Hz The QIX options include Earth leakage relay Qc generating set control panels for all standby and/or paralleling applications
VLT Series 300 Watt True Sine Wave Inverter
VLT Series 300 Watt True Sine Wave Inverter PURE SINE WAVE INVERTER I ON 0 OFF REMOTE CONTROL AC OUTPUT POWER STATUS Vout Vin Models VLT12-300 VLT24-300 300 Watt VLT Series Inverter - 1 - TABLE OF CONTENTS
STANDBY 150 ekw 188 kva PRIME 135 ekw 169 kva
DIESEL GENERATOR SET FEATURES Image shown may not reflect actual package. STANDBY 150 ekw 188 kva PRIME 135 ekw 169 kva Caterpillar is leading the power generation marketplace with Power Solutions engineered
Medical Air Systems: Scroll
GENERAL The Chemetron skid mount scroll medical air system is designed to provide medical breathing air for hospital and medical institutions. This system meets NFPA 99 requirements for Level 1 breathing
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS ELECTRIC HEATING UNITS MODEL: ETA / EKI
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS ELECTRIC HEATING UNITS MODEL: ETA / EKI Page 2 / 16 CONTENTS 1 GENERAL... 3 2 SAFETY... 3 2.1 Safety instructions... 3 2.2 Correct use... 3 3 DESCRIPTION
OREGON FIRE CODE Interpretations and Technical Advisories
OREGON FIRE CODE Interpretations and Technical Advisories A collaborative service by local and state fire professionals, along with our stakeholders and customers, to provide consistent and concise application
Portable Evaporative Air Cooler for Outdoor, Indoor & Commercial Use. OWNER S MANUAL Read and save these instructions before use.
OFF COOL 0 3 2 1 OFF Portable Evaporative Air Cooler for Outdoor, Indoor & Commercial Use ON SPEED ON SWING OWNER S MANUAL Read and save these instructions before use Model: CO60PM Power rating: 220 Watts
SBC90. Abrasive Blast Cabinet Assembly & Operating Instructions
SBC90 Abrasive Blast Cabinet Assembly & Operating Instructions READ ALL INSTRUCTIONS AND WARNINGS BEFORE USING THIS PRODUCT. SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE. This manual provides important
Battery Power Inverters
Battery Power Inverters Renogy 500W 1000W 2000W Pure Sine Wave Inverter Manual 2775 E. Philadelphia St., Ontario, CA 91761 1-800-330-8678 1 Version 1.1 Important Safety Instructions Please save these instructions.
POWER TO GET THE JOB DONE
52720 1.5 AMP SLOW 12 VOLT BATTERY CHARGER OWNER S MANUAL KEEPS BATTERIES FULLY CHARGED IN STORAGE Automatic over-charging protection Short circuit protection Reverse hook-up protection Overheat protection
GENERATOR MODEL NO: FG3050 OPERATION & MAINTENANCE INSTRUCTIONS PART NO: 8857705 LS0310
GENERATOR MODEL NO: FG3050 PART NO: 8857705 OPERATION & MAINTENANCE INSTRUCTIONS LS0310 INTRODUCTION Thank you for purchasing this CLARKE Generator. Before attempting to use this product, please read this
MODEL 300505 INSTALLATION INSTRUCTIONS
WWW.BURCAM.COM 2190 Boul. Dagenais West TEL: 514.337.4415 LAVAL (QUEBEC) FAX: 514.337.4029 CANADA H7L 5X9 [email protected] Your pump has been carefully packaged at the factory to prevent damage during shipping.
PC1130 Electric Air Compressor
Senco Products Inc. 8485 Broadwell Road Cincinnati, Ohio 45244 PC1130 Electric Air Compressor Operating Instructions 2006 by Senco Products, Inc. Warnings for the safe use of this tool are included in
Chromalox. Installation, Operation. Portable Industrial Unit Blower Air Heater Type DRA RENEWAL PARTS IDENTIFICATION
Chromalox Installation, Operation RENEWAL PARTS IDENTIFICATION Portable Industrial Unit Blower Air Type DRA and DIVISION SALES REFERENCE DATE SECTION (Supersedes P-) PF-) NOVEMBER, 00 DRA PF- -0-00 Specifications
Cylinder Leak- Down Tester
Cylinder Leak- Down Tester Item 94190 INSTRUCTIONS AND PRECAUTIONS Visit our website at: http://www.harborfreight.com When unpacking, make sure that the product is intact and undamaged. If any parts are