1 I n s t r u c t i o n M a n u a l DB Unit Braking unit 200V class 11-22kW / BU22-2C 400V class 11-22kW / BU22-4C CAUTION Deliver this instruction manual without fail to those who actually operate the equipment. Read this operation manual and understand the description before installing, connecting (wiring), operating or performing maintenance and inspection of the braking unit. Keep this instruction manual in a safe place until the braking unit is discarded. The product is subject to change without prior notice. Fuji Electric FA Components & Systems Co., Ltd. INR-SI b-E
2 Introduction Thank you for purchasing our braking unit. This equipment discharges the braking force in braking operation of Fuji s general purpose inverter to a resistor. For applicable inverter models, refer to Table A. Before starting operation, read through this operation manual to understand the handling method and operate correctly. An incorrect handling will obstruct correct operation or cause a reduced life or failure. Keep the instruction manual in a safe place even after operation is started. This operation manual does not cover the inverter handling. For the handling of the inverter, refer to the applicable inverter instruction manual. Table A. Applicable Inverter Models Class Model 200V General-purpose FRENIC5000 G11S/P11S Series Safety Precautions 400V inverter General-purpose inverter FRENIC5000 G11UD Series FRENIC5000 G11S/P11S Series FRENIC5000 G11UD Series Read through this operation manual carefully before installing, connecting, (wiring), operating or performing maintenance and inspection for correct usage. Be familiar with all the devices, safety information, and cautionary items. In this operation manual, safety precautions are described under the following titles. Wrong handling may cause danger possibly accompanying deaths or serious WARNING CAUTION injuries. Wrong handling may cause danger possibly accompanying minor or moderate injuries or material losses. Precautions described in the caution category may cause serious results in some circumstances. Both precautions are important; observe the description without fail. Application WARNING This unit discharges the braking force in braking operation of Fuji s general purpose inverter to a resistor. It cannot be used for other applications. Risk of fire This unit cannot be used for applications directly related to personal danger such as a life support system. This product is manufactured under strict quality control. However, if it is used for equipment where serious accidents or losses may occur in case of failure of this product, install a safety device. Risk of accident
3 Installation WARNING Install to nonflammable matter such as metals. Risk of fire Do not place flammable matter nearby. Risk of fire Contain the unit inside a distribution panel or the like so that it cannot be touched easily. Risk of electric shock or accident Use bolts of the specified sizes for installation without fail. Risk of accident or injuries CAUTION Do not hold the front cover when carrying. Risk of drop and injuries Do not allow lint, paper, wood dust, other dust, metallic dust or other types of foreign matter to intrude in the braking unit or do not allow them to be stuck on the heat sink. Risk of fire or accident Do not install and operate the braking unit if it is damaged or some parts are missing. Risk of injuries Wiring WARNING Use the designated size for wiring cables. Risk of fire Do not make a mistake in the polarity (+, -) of the DC terminals (P(+), N(-)) and inverter connection terminals. Risk of fire Be sure to connect the grounding cable. Risk of electric shock or fire Have the wiring work conducted by a qualified electrician. Risk of electric shock Check that the power is turned off (opened). Risk of electric shock Be sure to install the main body first before starting wiring. Risk of electric shock or injuries CAUTION Check that the rated voltage of the product conforms to the rated voltage of the inverter. Risk of injuries Do not connect the braking resistor directly to the DC terminals (P(+), N(-)). Risk of fire Noise is generated from the unit and wiring. Be careful of malfunction of nearby sensors or devices. Risk of accident
4 Operation WARNING Be sure to install the surface cover before turning the power on (closing). Do not remove the cover while the power is turned on. Risk of electric shock Do not touch the terminals of the braking unit while the power is supplied to the inverter or even if the unit is stopped. Risk of electric shock CAUTION Do not use the main circuit ON/OFF switch to start or stop the inverter. Risk of failure Do not touch the heat sink and braking resistor because they become hot. Risk of burns The braking function of this unit does not guarantee mechanical suspension. Risk of injuries Maintenance, inspection and parts replacement WARNING Turn the power off (open) and wait for at least 10 minutes before starting inspection. Check that the charge lamp is unlit and check that the DC voltage across the P(+) and N(-) terminals is 25V or lower. Risk of electric shock Do not perform maintenance, inspection or parts replacement if you are not the appointed person. Take off metallic objects such as watches and rings before starting work. Use insulated tools. Risk of electric shock or injuries Disposal CAUTION When discarding the product, handle it as an industrial waste. Risk of injuries Others Never remodel. Risk of electric shock or injuries WARNING General Precautions Schematic drawings found in this operation manual may indicate a view without covers or safety shields for explanation of details. When operating the product, restore the covers and shields and observe the operation manual.
5 Conformity to UL standards and Canadian standards (cul certification) CAUTION 1. Use 60 / 75 Cu wire only 2. Use Class 1 wire only. 3. Field wiring connection must be made by a UL Listed closed-loop terminal connector sized for the wire gauge involved Connector must be fixed using the crimp tool specified by the connector manufacturer. 4. An optional cooling fan with minimum air flow rate of 0.5 m 3 /minute must be provided when the dynamic braking unit is used at 30%ED rating. CAUTION Required torque and wire size. Required torque [lb-inch](n. m) Wire range [AWG] Unit type Main terminal Control Main terminal Control BU22-2C (1.8) BU22-4C 14 The inverter connected to the inverter is listed below. Unit type Applied Inverter BU22-2C 3Ph V 50Hz/60Hz BU22-4C 3Ph V 50Hz/60Hz
6 Table of contents 1. Before Starting Operation 1-1 Shipment Inspection Appearance of Product Handling the Product Transportation Storage Installation and Connection Operating Environment Installation Method Connection Basic Connection Connection of Main Circuit and Grounding Terminal Connection of Control Terminal Terminal Layout Standard applied device and cable size Operation Inspection and Preparation Before Operation Protective Action Protective Action Alarm Reset Maintenance and Inspection Daily inspection Periodic Inspection Insulation Test Replacement Parts Inquiry About Product and Guarantee Specifications Standard Specifications Braking Unit Braking Resistor External Dimensions Optional Fan Specifications of Optional Fan Installation of Optional Fan Unit Installation Optional Fan Wiring External Dimensions 7-2
7 1 Before Starting Operation 1-1 Shipment Inspection Unpack and check the following items. If you have any question or trouble, contact the store of purchase or nearest Fuji s sales office. Fig Rating Nameplate (1) Refer to the rating nameplate to check if the delivered product is the ordered one. TYPE : Type of braking unit BU 22-2 C Standard series : C Power source voltage class of the inverter: 2 200V class V class Standard applied motor capacity of inverter : 22 22kW Product type SOURCE : Power source rating OUTPUT : Output rating SER.No. : Serial number R0001 Serial manufacturing lot number Manufacturing month: 1 to 9 January to September X October. Y November. Z December Manufacturing year: The last one digit of year. 3 Year 2003 (2) Check if there are any missing or broken parts or dents or other transportation damage in the cover and main body. (3) The braking resistor is not attached. Prepare a suitable resistor matching the specifications separately. 1-2 Appearance of Product Fig Appearance of Product Fig
8 1-3 Handling the Product (1) Removal of terminal cover Loosen the mounting screws of the terminal cover and, while holding the terminal cover, remove it as shown in Fig Fig Removal of Terminal Cover and Surface Cover 1-4 Transportation Be sure to hold the main body when transporting. If the cover or parts are held, there is danger of braking or dropping. 1-5 Storage Store the product in an environment specified in Table Table Storage Environment Specifica Item tion Ambient 10 ~ +50 C temperature Place free from condensation or icing caused by Storage temperature NOTE1 25 ~ +65 C abrupt temperature changes Relative humidity 5 ~ 95% Note 2 Free from dust, direct sunshine, corrosive or flammable gases, oil mist, Atmosphere vapor, water drops or vibration. Free from much salt Note 1: The storage temperature indicates the temperature in short period such as during transportation. Note 2: Even if the temperature satisfies the specification values, condensation or icing occurs at places with steep temperature changes. Avoid such places. (1) Do not place directly on the floor. (2) If the ambient atmosphere is adverse, pack the unit with a vinyl sheet or the like to store. (3) If moisture may cause ill effects, place a drying agent such as silica gel inside the package before packing as described at (2). 1-2
9 2 Installation and Connection 2-1 Operating Environment Install the unit in the environment shown in Table Table Operating Environment Item Specification Site Indoors Ambient 10 ~ +50 temperature Relative 5 ~ 95% (Without condensation) humidity Atmosphere Free from dust, direct sunshine, corrosive gases, oil mist, vapor or water drops. Free from much salt. Free from condensation caused by abrupt temperature changes Altitude 1,000m maximum (If 1,000m is exceeded, reduce the inverter output according to the inverter operation manual.) Vibration 3.0mm at 2~9Hz, 9.8m/s 2 at 10~20Hz, 4.9m/s 2 at 20~55Hz, 1.0m/s 2 at 55 ~200Hz 2-2 Installation Method (1) Install the braking unit on a solid structure securely with bolts and vertically so that the label characters are seen in front. Up 上 m m (2) The braking unit generates heat during operation. Reserve space shown in Fig to assure passage of cooling air. Because the generating heat is radiated above, do not install below a device susceptible to heat. Left 左 550mm 0 m m 以 minimum 上 Main 本 体 body D B U n it Right 右 550mm 0 m m minimum 以 上 (3) The temperature of the heat sink rises up to about 90 C during operation of the braking unit. The material of the mounting face at the back of the braking unit must bear the temperature rise with a sufficient margin. Down 下 m m Fig WARNING Install on nonflammable matter such as metals. Risk of fire (4) When the unit is installed inside the control panel or the like, take sufficient care of ventilation so that the ambient temperature of the braking unit does not exceed the specification value. Do not house in an ill-ventilated small airtight container. (5) When two or more inverters and the braking unit are housed in the same equipment or inside the control panel, side-to-side installation is recommended to reduce the mutual effects of heat. If the units must be installed vertically for unavoidable reason, install a partition plate or the like so that the heat generating at the lower unit does not give ill effects on the upper unit. CAUTION Do not allow lint, paper, wood dust, other dust, metallic dust or other foreign matter to intrude inside the unit or do not allow them to be stuck on the heat sink. Risk of fire or accident 2-1
10 2-3 Connection Inside unit After the terminal cover is removed, each terminal block becomes visible (see Fig ). Take care of the following items and connect without mistakes Basic Connection (1) Connect the DC link connection terminals (P(+), N(-)) with the DC link circuit terminals (P(+), N(-)) of the inverter. The unit and the inverter will be damaged if the polarity is incorrect or other terminals are connected. As well, check that the source voltage conforms to the specification of the connected inverter. (2) Be sure to ground the grounding terminal to avoid disasters such as electric shock and fire and to reduce noise. (3) Use crimp terminals with high connection reliability for the connection between the terminal and cable. (4) After finishing connection (wiring) work, check the following. a. Correct connection b. Failure to connect c. Short circuit or ground fault of terminals and cables (5) To change connection after power application After the power is turned off, it takes time until the smoothing capacitor in the DC circuit of the main circuit is discharged. Before starting work, wait until the charge lamp is unlit and check that the DC voltage has dropped to a safe voltage (25Vdc or lower) with a multimeter or the like to avoid danger. In addition, short circuiting may cause sparks if there is a remaining voltage (charge). Wait until the voltage becomes low. WARNING Be sure to connect the grounding cable. Risk of electric shock or fire Have wiring work done by a qualified electrician. Check that the power is turned off (opened) before starting work. Risk of electric shock Fig Inside unit 2-2
11 Basic Connection Diagram (*2) Cable length: 線 長 5m 5m 以 or 下 Inverter Braking unit 5m 線 長 or 5m less 以 下 Braking インバータ 制 動 ユニット 制 動 resistor 抵 抗 器 P1 P(+) P(+)R P P(+) + DB M N(-) N(-) G (*3) Main 主 回 circuit 路 G 1 2 Cable length: DB (*3) G 1 2 オフ ション ファン*4 Optional fan*4 Control 制 御 回 circuit 路 External 外 部 alarm アラーム input 入 力 (*1) CM Fig (*1) The inverter may allow arbitrary assignment of digital input terminals. Use the function setting of the inverter to select external alarm input. (*2) Connect the batch alarm output of the braking unit and braking resistor to the external alarm input of the inverter and build a sequence that opens the electromagnetic contactor with the batch alarm output of the inverter. (*3) Be sure to twist or route in close contact (in parallel) the two cables connecting the inverter with the braking unit and that connecting the braking unit with the braking resistor. (*4) The optional fan needs separate power supply. The source voltage varies according to the optional fan to be used. BU-F1S (single-phase 100Vac), BU-F2S (single-phase 200Vac) 2-3
12 2-3-2 Connection of Main Circuit and Grounding Terminal Table Function of Main Circuit Terminals and Grounding Terminal Terminal symbol Terminal name Description P(+), N(-) DC link connection terminal The DC link circuit voltage of the inverter is connected. P(+)R, DB Terminals for connecting The braking resistor is connected. G braking resistor For grounding the braking unit 2-4 Connection terminal for chassis (case) of the braking unit (1) DC link connection terminal (P(+), N(-)) 1) Connect the DC link circuit terminals P(+) and N(-) of the inverter with the terminals P(+) and N(-) of the braking unit. 2) Arrange units so that the wiring length is within 5m. Twist or route in close contact (in parallel) the two cables. 3) Do not connect to the AC power supply. (2) Terminal for connection of braking resistor (P(+)R, DB) 1) Connect terminal P and DB of the braking resistor to terminal P(+)R and DB of the braking unit. 2) Arrange units so that the wiring length is within 5m. Twist or route in close contact (in parallel) the two cables. 3) Do not connect to the AC power supply. (3) Unit grounding terminal ( G) Be sure to ground unit grounding terminal ( G) for safety and noise reduction. The Electric Equipment Engineering Standard requires grounding work of the metallic frame of electric devices for the prevention of electric shock, fire and other disasters. Follow the procedure below to connect. 1) Connect to class D grounding electrode (200V class) or class C grounding electrode (400V class) according to Electric Equipment Engineering Standard. 2) Connect a thick and short cable between the grounding terminal and the grounding electrode exclusively provided for the inverter system. Table Voltage class Type of grounding work Grounding resistance 200V Class D grounding work 100Ω maximum 400V Class C grounding work 10Ω maximum Do not connect the AC power supply to DC link terminals (P(+), N(-)). Risk of accident Do not connect the braking resistor directly to the DC link terminals (P(+), N(-)). Check if the specifications of the product match the connected inverter. CAUTION The braking resistor may generate excessive heat if the braking unit is broken. Build a sequence for shutting off the power supply of the inverter input upon an alarm signal. Risk of fire Connection of Control Terminal The function of the control circuit terminal is described in Table Table Terminal symbol 1, 2 Terminal name Braking unit batch alarm output Description IGBT for driving the DB and overheat generation of the braking resistor are output. (1) Braking unit batch alarm output (1, 2) 1) Connect the inverter s contact input terminals assigned to external alarm input, to the braking unit and braking resistor terminals in series in order of: If there is a short bar at the inverter s target contact input terminal, remove it. (2) Others 1) Route the control terminal cables as far away as possible from the main circuit cables. Otherwise malfunction caused by noise may result. 2) Tie the control cables inside units so that they do not make contact with live parts of the main circuit (such as the terminal block of the main circuit).
13 WARNING CAUTION Because the sheath of the general control cable is not reinforced insulation, a high voltage of the main circuit may intrude the control signal when the insulating sheath is broken due to some reason. Risk of electric shock Noise is generated from the inverter, motor, cable and so on. Take care of malfunction of surrounding sensors and devices. Risk of accident Terminal Layout BU22-2C,4C Screw size M5 P(+) P(+)R Screw size M3 1 2 Screw size M4 G N(-) DB Voltage 200V 400V Standard applied device and cable size Applied motor (kw) Braking unit Braking resistor Tightening torque (N m) Model Qty Model BU22-2C BU22-4C Resistance (Ω) DB11-2C DB DB15-2C DB DB22-2C 5.8 DB DB22-2C DB DB11-4C DB DB15-4C DB DB22-4C 22 DB DB22-4C DB Qty Main circuit Ground ing Control DB circuit (P(+), N(-), P(+)R, DB) Recommended cable size (mm 2 ) (Note 1) Ground ( G) Control 2 Note 2 Note Note 1: The cable to be used is 600V HIV insulated cable with allowable temperature 75 C. Selection is made on assumption that the ambient temperature is 50 C. Note 2: The operation ratio is considered in 10%ED. Note 3: The operation ratio is considered in 30%ED. 2-5
14 3 Operation 3-1 Inspection and Preparation Before Operation Inspect the following items before starting operation. (1) Check for correct connection. Take care of the following points among all. a. Check if the DC link connection terminals P(+) and N(-) and braking resistor connection terminals P(+)R and DB are not connected to the AC power supply. b. Check if the braking resistor connection terminals P(+)R and DB are not connected with the DC link voltage. c. Check if the grounding terminal is securely grounded. (2) Check if there is not a short circuit or ground fault across terminals or bare live parts. (3) Check if terminals, connectors and screws are not loose. After turning the power on, check the following. Inverter (1) Check if the inverter doesn t show an external failure alarm. (2) Check if the fan rotates (for models with optional fan). P(+) N(-) G Braking unit P(+) N(-) P(+)R DB Fig Braking Unit Connection Diagram DB P Braking resistor WARNING Be sure to install the surface cover before turning the power on (closing). Do not remove the cover while the power is ON. Risk of electric shock 3-1
15 4 Protective Action 4-1 Protective Action If a fault shown in Table 4-1 occurs, the braking unit stops the DB drive signal and issues a batch alarm signal at terminals 1 and 2 (the batch alarm signal does not have a means to discriminate the description of the alarm). This alarm signal causes to actuate the protective function of the inverter to trip, and an external alarm is displayed on the keypad panel of the inverter while the motor coasts to stop. Because the braking resistor may be excessively overheated upon failure of the braking unit, build a sequence to shut off the power upon activation of a protective function of the inverter. Table 4-1 Alarm Overheated heat sink Overheated braking resistor Description The temperature of the heat sink is high because operation is at a braking frequency exceeding the specification limit, the ambient temperature is too high, or the heat sink is clogged. The temperature of the braking resistor is high because the operation frequency of the braking resistor is too high. In addition, the fuse in the braking unit prevents secondary breakage by blown out when the internal circuit is short or damaged. Regenerated inverter may have OU trip with it blown out. 4-2 Alarm Reset If the inverter has tripped, remove the cause and reset the inverter according to the instruction described in the inverter operation manual. When resetting, turn the inverter operation command off. If the operation command is on, operation will be started after the inverter is reset. WARNING If the inverter is reset from an alarm with the operation signal turned on, operation will start suddenly. Check that the operation signal is turned off before resetting. Risk of accident 4-1
16 5 Maintenance and Inspection Perform daily inspection and periodic inspection to avoid failure and maintain reliable operation over a long period. Take care of the following items when working. 5-1 Daily inspection Visually check for faults in operation state without removing cover or the like, while the power is turned on. Regular inspection includes the following criteria. (1) Check if the expected performance (satisfying the standard specifications) is obtained. (2) Check if the surrounding environment satisfies the standard specifications. (3) Check if there is any abnormal noise, excessive vibration or malodor. (4) Check if there are traces of overheat or discoloration. 5-2 Periodic Inspection Stop the operation and turn the power off and remove the surface cover to perform periodic inspection. It takes time after the power is turned off until the smoothing capacitor at the DC part of the main circuit is discharged. To avoid danger, wait until the CHARGE lamp is unlit and check that the DC voltage has dropped to a safe value (25VDC or lower), using a multimeter or the like. Turn the power off (open) and wait for at least five minutes. Further, check that the CHARGE lamp is unlit and measure the DC voltage across terminals P(+) and N(-) to check if the measurement is 25VDC or lower. Risk of electric shock Do not perform maintenance and inspection or parts replacement unless you are the appointed person. Take off metallic objects (such as watches and rings) before starting work. Use insulated tools. Never remodel. Risk of electric shock or injuries WARNING Table Periodic Inspection List Inspection point Inspection item Inspection method Judgment criteria Check the ambient temperature, humidity, vibration, The standard Visually check and measure and atmosphere (presence / absence of dust, gas, oil specification must be with measuring instruments. mist, water drops). satisfied. Surrounding environment Voltage Structural parts such as frame and cover Main circuit Common Conductors and cables Terminal block Smoothing capacitor Resistor Check if foreign matter such as a tool or dangerous matter is left nearby. Check if the voltage of the main circuit and control circuit is correct. Visual inspection Measure using a multimeter or the like. Not left. Check if there is abnormal noise or excessive Visual or auditory inspection No fault vibration. Check if bolts (tightened parts) are not loose. Retighten. No fault Check for deformation and breakage. Check for discoloration caused by overheat. Visual inspection No fault Check for stuck dirt or dust. Check if bolts are not loose or missing. Retighten. No fault Check if devices and insulating matter are deformed, cracked, broken, or discolored due to overheat or deterioration. Check for stuck dirt or dust. Check if the conductor is discolored or deformed due to overheat. Check if the sheath of the cable is broken, cracked or discolored. Visual inspection Visual inspection The standard specification value must be satisfied. No fault Note: A discolored bus bar does not indicate a problem in its characteristics. No fault Check for breakage. Visual inspection No fault Check for liquid leakage, discoloration, cracks and swollen case. Check if the safety valve protrudes or the valve is swollen excessively. Check for malodor caused by overheat and cracked insulators. Check for a broken wire. Visual inspection No fault Smelling or visual inspection No fault Visually check or disconnect either terminal and measure with a multimeter. Within +/-10% of displayed resistance 5-1
17 (Cont d) Control circuit Cooling system Control printed board and connectors Cooling fan Check if screws and connectors are not loose. Check for malodor and discoloration. Check for cracks, breakage, deformation and excessive rust. Check the capacitors for liquid leakage and traces of deformation. Check for abnormal noise and excessive vibration. Retighten. Smelling or visual inspection Visual inspection Auditory or visual inspection. Turn by hand. Turn the power off without fail. No fault Smooth rotation Check for loose bolts. Retighten. No fault Check for discoloration caused by overheat. Visual inspection No fault Ventilation Check if the heat sink or suction or exhaust ports are Visual inspection No fault path clogged or if foreign matter is stuck. Note: Wipe off dirt using chemically neutral cleaning cloth. Suck duct with a vacuum cleaner. 5-3 Insulation Test The insulation test is conducted before shipment from the factory. Avoid Megger test whenever possible. When performing a Megger test for unavoidable reason, follow the description below. A wrong test procedure may cause breakage of the product. Take sufficient care. The dielectric strength test, too, may cause breakage of the product if the test procedure is wrong. Contact the store of purchase or our nearest sales office if a pressure resistance test is necessary. (1) Megger test of main circuit 1) Use a 500Vdc Megger and make sure to conduct with a discrete breaking unit. (Disconnect both the main circuit cable and control cable) 2) Connect the main circuit terminals, using a common cable, as shown in Fig ) The Megger test must be only across the common cable of the main circuit and ground (terminal G). 4) 5MΩ or larger measurement displayed at Megger indicates a correct state. (Measurement with a discrete unit) G N(-) P(+) P(+)R DB Main 主 回 路 circuit コモン common 線 cable メガー Megger Fig Megger Test (2) Insulation test of control circuit Do not perform a Megger test or dielectric strength test of the control circuit. For the control circuit, prepare a high resistance range tester. 1) Disconnect all external cables from the control circuit terminals. 2) Perform continuity test in respect to the ground. 1MΩ or larger measurement indicates the correct state. (3) External main circuit and sequence control circuit Disconnect all terminals from the unit so that the test voltage will not be applied to the unit. 5-2
18 5-4 Replacement Parts The life of the part depends of the type of the part. The life of the part varies according to the surrounding environment and operating conditions. It is recommended to replace parts while referring to Table as a measure. For the replacement method, contact the store of purchase or our nearest sales office. Table Replacement Parts Part name Standard replacement years Replacement method and others Cooling fan 3 years Replace with a new part. Fuse 10 years Replace with a new part. Other parts - Determine after investigation. 5-5 Inquiry About Product and Guarantee (1) Notice for inquiry For breakage of the product, uncertainties, failure or inquiries, contact the store of purchase or our nearest sales office and let us know the following items. a. Model of braking unit b. SER NO. (production number) c. Purchase timing d. Description of inquiry (For example, point of breakage and scale of breakage, uncertainties, failure symptom and circumstances, etc.) (2) Guarantee of product The guarantee period of the product is one year after purchase or 18 months since the month and year of production specified on the nameplate, whichever comes earlier. However, repairs will be charged in the following cases even if they are handled in the guarantee period. 1) Failure caused by handling errors or inadequate repair or remodeling 2) Operation in the range exceeding the standard specification value 3) Failure caused by dropping after delivery or damage caused by transportation 4) Failure caused by earthquake, fire, flood or wild wind, lightning, irregular voltage, or other acts of God or secondary disaster 5-3
19 6 Specifications 6-1 Standard Specifications Braking Unit Class 200V 400V Type BU22-2C BU22-4C Minimum connecting resistance (Ω) Maximum braking power (kw) Generating loss (10%ED)(W) Rated input current (Arms) 17 9 Mass (kg) 2 2 Braking torque 150% (Instantaneous maximum torque) Operation ratio 10%ED (30%ED with optional fan) *1,*2 Braking time 10 sec.: period 100 sec. (30 sec. with optional fan) *1,*2 Action voltage (V) Blown fuse If one of faults listed on the left is sensed, IGBT inside Protective functions Overheated heat sink the braking unit is stopped. Overheated braking resistor Cooling method Self-cooling (forced air cooling with optional fan) Operation site Operating ambient temperature Indoors Altitude within 1000m Without corrosive gas, dust or direct sunshine 10 ~ +50 *1) The operation ratio (%ED) and braking time are converted under the deceleration braking conditions as shown in the figure below. Braking 制 動 power 電 力 Operation 使 用 率 ratio %ED=(T1/T0) X 100% T1 : 制 動 時 間 (10 秒 ) T1: Braking time (10 sec.) T0: Repetition period (100 sec.) T0 : 繰 り 返 し 周 期 (100 秒 ) Max. braking 最 大 制 動 power 電 力 T1 T1 T0 The rated current is the effective current in interval T0. T0 should be less than 100s. *2) For models with an optional fan, the operation ratio (%ED) is calculated on assumption that the braking time (T1) is 30 seconds. 6-1
20 6-1-2 Braking Resistor 1) Item supporting 10%ED 200V class Type DB11-2C DB15-2C DB22-2C Standard applied motor (kw) Resistance (Ω) Max. capacity (kw) Power-on current (A) Mass (kg) V class Type DB11-4C DB15-4C DB22-4C Standard applied motor (kw) Resistance (Ω) Max. capacity (kw) Power-on current (A) Mass (kg) Operation ratio 10%ED (Standard braking unit specifications; refer to *1) Braking time 10 sec.: period 100 sec. (standard braking unit specifications; refer to *1) Operating ambient temperature 10 ~ +50 2) Item supporting 5%ED 200V class Type DB11-2 DB15-2 DB DB22-2 Standard applied motor (kw) Resistance (Ω) Max. capacity (kw) Power-on current (A) Mass (kg) V class Type DB11-4 DB15-4 DB DB22-4 Standard applied motor (kw) Resistance (Ω) Max. capacity (kw) Power-on current (A) Mass (kg) Operation ratio 10%ED(Standard braking unit specifications; refer to *1) Braking time 10 sec.: period 100 sec. (standard braking unit specifications; refer to *1) Operating ambient temperature 10 ~
21 6-2 External Dimensions 6-3
22 7 Optional Fan This braking unit can increase the braking time and operation ratio by using the optional fan. Standard specification With optional fan Braking time 10 sec. 30 sec. Operation ratio 10%ED 30%ED (Refer to *1 and *2 in Chapter 6 Standard Braking Unit Specifications. ) 7-1 Specifications of Optional Fan Type BU-F1S BU-F2S Input source voltage specification Single-phase Vac 50/60Hz Single-phase Vac 50/60Hz Mass 0.5kg Operating ambient temperature 10 ~ Installation of Optional Fan Unit Installation (Fig ) (1) Use the fan unit fixing screw at four places on the side of the unit to fix the fan unit. (The fan unit fixing screws come with the fan unit.) (2) In order to secure the air passage of the fan unit, provide the space shown in the Installation Method (Fig ) with the Fan Unit is installed. (3) The wiring port is plugged. Open a hole to pass fan power cables. Fig Installation of Optional Fan Unit Optional Fan Wiring (1) Prepare separate power supply for the fan. (The source voltage varies according to the type of the cooling fan to be used.) (2) Connect to the terminal block inside the fan unit. 1.25mm 2 wire size is recommended. 7-1
23 7-3 External Dimensions [Fan unit] BU-F1S,BU-F2S [DB Unit with Fan Unit] BU22-2C/4C, BU-F1S/F2S 7-2
24
CAUTION OPC-LM1-ID. Option Card for Frequency Divider. Fuji Electric FA Components & Systems Co., Ltd. Instruction Manual
Instruction Manual Option Card for Frequency Divider Deliver this instruction manual without fail to those who actually operate the equipment. Read this operation manual and understand the description
CAUTION OPC-LM1-IL. Option Card for Encoder of Line Driver Output. Instruction Manual
Instruction Manual OPC-LM1-IL Option Card for Encoder of Line Driver Output CAUTION Deliver this instruction manual without fail to those who actually operate the equipment. Read this operation manual
DB Unit. Instruction Manual CAUTION. Dynamic Braking Unit. INR-HF51196c-E
Instruction Manual DB Unit Dynamic Braking Unit 200V Series 37kW /BU37-2C to 90kW /BU90-2C 400V Series 37kW /BU37-4C to 220kW /BU220-4C CAUTION Ensure that this instruction manual is made available to
12. Inspection and Maintenance
12. and Maintenance Mandatory Be sure to inspect the inverter regularly and periodically to prevent it from breaking down because of the environment of use, such as temperature, humidity, dust and vibration,
/ Instruction Manual. Analog Input/Output Interface Card "OPC-G1-AIO"
/ Instruction Manual Analog Input/Output Interface Card "OPC-G1-AIO" Fuji Electric Co., Ltd. INR-SI47-1288b-JE English Version Preface Thank you for purchasing our analog input/output interface card.
Instruction Manual Copy Adapter "CPAD-C1A" "CP Fuji Electric Systems Co., Ltd. INR-SI47-0886a-EU Rev 052010
Instruction n Manual Copy Adapter "CPAD-C1A" Thank you for purchasing our Copy Adapter CPAD-C1A. This product is designed to copy function codes and their data, which are stored in the FRENIC-Mini series
User s Manual Before using the inverter, you need to read and save the safety instructions.
User s Manual Before using the inverter, you need to read and save the safety instructions. STI SERIES (STI200, STI300, STI500, STI700, STI1000) Power Frequency Pure Sine Wave Inverter The information
OPERATING MANUAL. Table of contents. 2 Phase Stepping Motor Driver 2M542. Rev. A. Introduction page 2. Specifications page 2 Timing chart page 3
2 Phase Stepping Motor Driver 2M542 OPEATING MANUAL Table of contents Introduction page 2 Specifications page 2 Timing chart page 3 Setting page 4 Current set page 4 educe current function page 4 Micro
ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013
ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 READ CAREFULLY These instructions are intended to cover good practices in
TIG INVERTER INSTRUCTION MANUAL
TIG INVERTER INSTRUCTION MANUAL Contents Warning General Description Block Diagram Main Parameters Circuit Diagram Installation and Operation Caution Maintenance Spare Parts List Troubleshooting 3 4 4
Single Phase Soft Starter
Single Phase Soft Starter Installation & Operating Manual 6/02 Table of Contents Section 1 General Information................................................... 1 1 General Description................................................
OPERATION MANUAL. Total Heat Exchanger HRV (Heat Reclaim Ventilation) (Ceiling mounted duct type)
OPERATION MANUAL (Ceiling mounted duct type) VAM50FB VAM500FB VAM650FB VAM800FB VAM000FB VAM500FB VAM000FB 8 7 6 9 5 7 5 0 6 8 6 9 0 5 5 7 7 6 7 A A B B 5 6 5 6 7 VAM50F VAM800F VAM500F VAM500F VAM000F
DLP-PU/E Instruction Manual
Instruction Manual BEFORE USING THE POWER SUPPLY UNIT Pay attention to all warnings and cautions before using the unit. Incorrect usage could lead to an electrical shock, damage to the unit or a fire hazard.
MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation
MTE SERIES RLW World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930 2009 MTE Corporation IMPORTANT USER INFORMATION NOTICE MTE Series RLW reactors are components designed to improve the reliability
Installation Instructions for Alarm Module Kit A043F059
Instruction Sheet 07-2013 Installation Instructions for Alarm Module Kit A043F059 1 Introduction The information contained within is based on information available at the time of going to print. In line
CARING FOR YOUR WATER HEATER
http://waterheatertimer.org/troubleshoot-rheem-tankless-water-heater.html Water Heater Inspections CARING FOR YOUR WATER HEATER Venting System (Direct Vent Only) The venting system should be inspected
Instruction Manual. Designed for Fan and Pump Applications
Instruction Manual Designed for Fan and Pump Applications Thank you for purchasing our FRENIC-Eco series of inverters. This product is designed to drive a three-phase induction motor. Read through this
543-0032-00, 943-0032-00. User s Manual
543-0032-00, 943-0032-00 User s Manual 1 Comfort Alert Diagnostics Faster Service And Improved Accuracy The Comfort Alert diagnostics module is a breakthrough innovation for troubleshooting heat pump and
Model 1756 Test Lead Kit
Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-888-KEITHLEY http://www.keithley.com Model 1756 Test Lead Kit Gerneral Purpose Test Lead Information Description These test leads allow you
IMPORTANT SAFETY INSTRUCTIONS WARNING READ AND SAVE THESE OPERATING AND SAFETY INSTRUCTIONS BEFORE USING THIS HEATER.
THERMAWAVE CERAMIC HEATER Model HZ-850 Series Model HZ-860 Series IMPORTANT SAFETY INSTRUCTIONS WARNING READ AND SAVE THESE OPERATING AND SAFETY INSTRUCTIONS BEFORE USING THIS HEATER. Warning Failure to
How To Use A Power Supply Unit (Upu)
BRAVER UPS (Uninterruptible Power System) User s Manual Safety CAUTION! This UPS utilizes voltages that may be hazardous. Do not attempt to disassemble the unit. The unit contains no user replaceable parts.
Operating Instructions Split System Air Conditioner
Operating Instructions Split System Air Conditioner Model No. Indoor Unit Type Indoor Unit Type Nominal Capacity 26 36 F2 Low Silhouette Ducted S-26PF2U6 S-36PF2U6 Connectable outdoor unit lineup This
USER S MANUAL. MaxPower 400-600 UPS. Uninterruptible Power System 28-2MAXPO0018
USER S MANUAL MaxPower 400-600 UPS Uninterruptible Power System 28-2MAXPO0018 IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions for models MaxPower 400 and
AIR-CONDITIONER SPLIT TYPE
FILE NO. A08-016 SERVICE MANUAL AIR-CONDITIONER SPLIT TYPE RAS-M10PKVP-E, RAS-M13PKVP-E, RAS-M16PKVP-E, RAS-M18PKVP-E / RAS-M10PKVP-ND, RAS-M13PKVP-ND, RAS-M16PKVP-ND, RAS-M18PKVP-ND / RAS-3M26GAV-E1,
Installation and safety instructions for AC/DC built-in devices
The device type and date of manufacture (week/year) can be found on the device rating plate. In the event of any queries about the device, please quote all the details given on the rating plate. For further
No. : EX##-OMF0004 OPERATION MANUAL. SI unit EX12#-SMB1
No. : EX##-OMF0004 OPERATION MANUAL EX12#-SMB1 Contents 1. Safety instructions ------------------------------------------------------ P3 2. Notes ------------------------------------------------------
VLT Series 300 Watt True Sine Wave Inverter
VLT Series 300 Watt True Sine Wave Inverter PURE SINE WAVE INVERTER I ON 0 OFF REMOTE CONTROL AC OUTPUT POWER STATUS Vout Vin Models VLT12-300 VLT24-300 300 Watt VLT Series Inverter - 1 - TABLE OF CONTENTS
FLUORESCENT UV- RING LIGHT OPERATING INSTRUCTION
FLUORESCENT UV- RING LIGHT OPERATING INSTRUCTION Caution! UV-radiation of this device is in the range of UV-A (320-400 nm). Direct exposure to eyes shall therefore be avoided. UV protection glasses shall
12 Volt 30 Amp Digital Solar Charge Controller
12 Volt 30 Amp Digital Solar Charge Controller User s Manual WARNING Read carefully and understand all INSTRUCTIONS before operating. Failure to follow the safety rules and other basic safety precautions
Operating instructions
ebm-papst Mulfingen GmbH & Co. KG Bachmühle D-74673 Mulfingen Phone +49 (0) 7938 81-0 Fax +49 (0) 7938 81-110 [email protected] www.ebmpapst.com CONTENTS 1. SAFETY REGULATIONS AND S 1.1 Levels of hazard
Radiant Temperature Sensor TY7321
AB-5361-U Specifications/Instructions Radiant Temperature TY7321 General TY7321 Radiant Temperature s are designed to measure infrared radiation from perimeter windows and walls and provide a proportional
INFRARED QUARTZ WALL HEATER
INFRARED QUARTZ WALL HEATER MODEL NO: IQ2000 PART NO: 6939004 MOUNTING & OPERATION INSTRUCTIONS GC0715 INTRODUCTION Thank you for purchasing this CLARKE Infrared Wall Heater. Before attempting to use this
USER S MANUAL HSC-24A
AIRREX AIR CONDITIONER USER S MANUAL HSC-24A Thank you for purchasing an AIRREX AIR CONDITIONER. BEFORE operation please read this user s manual carefully. Keep this manual readily available. It is ESSENTIAL
Portable Air Conditioner
Portable Air Conditioner Owner's Manual Model:3 in 1 12,000 Btu/h Series 3 Please read this owner s manual carefully before operation and retain it for future reference. CONTENTS 1. SUMMARY...1 2. PORTABLE
Content. Operational manual for RBU
Content Operational manual for RBU 1 Safety Precautions...1 1.1 Safety definition... 1 1.2 Warning symbols... 1 1.3 Safety guidelines... 1 2 Inspection...4 2.1 Unpacking inspection... 4 2.2 Application
Power supply unit Model: PAC-SC50KUA
Building Air Conditioning Control System Power supply unit Model: PAC-SC50KUA Installation Manual Contents 1. Safety precautions... 1 2. Product feature... 2 1. Specification... 2 2. Appearance... 2 3.
Lithium Ion Battery Specifications
Lithium Ion Battery Specifications Type: Cylindrical Lithium Iron Phosphate Battery Mode: LFP-26650-3300 AA Portable Power Corp. Prepared by Checked by Approved by 1 . Product Specifications Type ------------
Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.
Website: www.andico.com.au Service manual CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. - ONLY FOR AUTHORISED SERVICE PERSONNEL. MODELS: MPK1-09CR-QB8 MPK1-12ER-QB6
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS ELECTRIC HEATING UNITS MODEL: ETA / EKI
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS ELECTRIC HEATING UNITS MODEL: ETA / EKI Page 2 / 16 CONTENTS 1 GENERAL... 3 2 SAFETY... 3 2.1 Safety instructions... 3 2.2 Correct use... 3 3 DESCRIPTION
Failure code manual. content
Failure code manual content 一 wall split AC series 2 二 floor standing AC series. 4 三 portable AC series.. 5 四 dehumidifer 6 五 DC inverter single split series...7 六 DC inverter multi-split series 10 1 一
MCR1900 Media Converter 19-Slot Chassis
MCR1900 Media Converter 19-Slot Chassis Installation Guide Part #5500304-11 Copyright Statement This document must not be reproduced in any way whatsoever, either printed or electronically, without the
Battery Power Inverters
Battery Power Inverters Renogy 500W 1000W 2000W Pure Sine Wave Inverter Manual 2775 E. Philadelphia St., Ontario, CA 91761 1-800-330-8678 1 Version 1.1 Important Safety Instructions Please save these instructions.
MP-4000 Alarm List (Software version 2.4.3 or later)
Service Bulletin SUBJECT: MP4000 Alarm s BULLETIN: C 100 DATE: June 19, 2013 ALARM LIST Where it is possible the alarm number is kept the same as for MP-3000. MP-3000 holds alarm number from 0 to 127.
YSmart Technology Co.,Ltd
YSmart Technology Co.,Ltd GWV Series Grid Tie Microinverter User Manual The copyright of this user manual belong to YSmart TechnologyCompany Limited. Without the written permission of the copyright holder,
12 Volt 30 Amp Digital Solar Charge Controller Installation & Operation Manual
12 Volt 30 Amp Digital Solar Charge Controller Installation & Operation Manual This 30Amp charge controller is designed to protect your 12Volt Lead-acid or Gel-cell battery from being overcharge by solar
5000VG7S Series. INSTRUCTION MANUAL High-Performance, Vector Control Inverter. CT Use (150%)
5000VG7S Series INSTRUCTION MANUAL High-Performance, Vector Control Inverter CT Use (150%) 200V Series 400V Series 0.75kW/FRN0.75VG7S-2 3.7kW/FRN3.7VG7S-4 ~90kW/FRN90VG7S-2 ~400kW/FRN400VG7S-4 710kW/FRN710BVG7S-4DC
User s Manual AURORA 1.2K/2.2K
User s Manual AURORA 1.2K/2.2K Uninterruptible Power System Safety CAUTION This UPS utilizes voltages that may be hazardous. Do not attempt to disassemble the unit. The unit contains no user serviceable
LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units
Multi Split Units If there is a fault on any LG Multi unit, an Error mark is indicated on the display window of the indoor unit, wired-remote controller, and LED s of outdoor unit control board. A two
3000W Power Inverter
3000W Power Inverter OWNER S MANUAL Model number-4573000 TO REDUCE THE RISK OF INJURY, USER MUST READ AND UNDERSTAND THIS INSTRUCTIONAL MANUAL. THIS MANUAL CONTAINS IMPORTANT INFORMATION REGARDING THE
NewAir AC-10000E, AC-10000H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS
NewAir AC-10000E, AC-10000H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS BEFORE USE GENERAL SAFETY INSTRUCTIONS: ALWAYS OPERATE THE UNIT IN AN UPRIGHT POSITION AND PLACE
Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw
4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and
REGULINE 600VA / 1000VA REGULATOR USER MANUAL
REGULINE 600VA / 1000VA REGULATOR USER MANUAL TUNÇMATİK REGULINE SERIES AUTOMATIC VOLTAGE REGULATOR Models: REGULINE 600VA / REGULINE 1000VA Principle of Operation Automatic Voltage Regulators regulate
User Manual DONGGUAN SHENGYANG INDUSTRIAL CO., LTD. SY WMVC Smart Grid Tie Microinverter. Dongguan Shengyang Industrial Co., Ltd.
DONGGUAN SHENGYANG INDUSTRIAL CO., LTD SY WMVC Smart Grid Tie Microinverter User Manual Dongguan Shengyang Industrial Co., Ltd. ADD: No. 1 Shangxin Road, New Village, Xin An Community, Chang An Town, Dongguan
BATHROOM HEATER. User's Manual. Page 2...A515 Page 9...A716
BATHROOM HEATER User's Manual Page 2...A515 Page 9...A716 BATHROOM HEATER User's Manual A515 SAVE THESE INSTRUCTIONS AND READ ALL INSTRUCTIONS BEFORE USING THE HEATER. Dear customers, Thank you for selecting
The table below lists the symbols used on the Clamp and/or in this manual. Important Information. See manual.
i800 AC Current Clamp Instruction Sheet Introduction The i800 AC Current Clamp, the Clamp, has been designed for use with multimeters, recorders, power analyzers, safety testers, etc., for accurate non-intrusive
15GAL STEEL OIL DRAIN WITH 110V PUMP
15GAL STEEL OIL DRAIN WITH 110V PUMP OWNER S MANUAL WARNING: Read carefully and understand all ASSEMBLY AND OPERATION INSTRUCTIONS before operating. Failure to follow the safety rules and other basic safety
AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5
AMFA-27 AMFA-29 Operator s Manual & Installation Instructions Rev. 2.5 Date: 17 July, 2010 Permanently-connected, utility Interactive, single-phase, inverters Model AMFA-27 WIND TURBINE INVERTER (240 VAC
Oil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
PANCAKE CAPACITOR GENERATOR Installation, Operation and Maintenance Manual
PANCAKE CAPACITOR GENERATOR Installation, Operation and Maintenance Manual A Regal Brand TABLE OF CONTENTS INTRODUCTION 2 General Data 2 Initial Inspection 2 SAFETY 2 INSTALLATION 3 Location / Environment
SMD Rework Station TABLE OF CONTENTS
SMD Rework Station Thank you for purchasing the Hakko 50B SMD Rework Station. The Hakko 50B is designed to solder and desolder surface mounted devices with hot air. Please read this manual before operating
TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL 387030095 AW64AL 0.8180.463.0 07/05
TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: AW52AL AW64AL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. AW52AL 387030095 AW64AL 387030096 0.8180.463.0 07/05 IMPORTANT! Please read before installation
Quartzone Infrared Quartz Tube & Metal Sheathed Electric Heaters
Quartzone Owner s Manual File E97759 COMFORT S for INDOOR* and OUTDOOR** USE *Excluding Residences ** With Quartz Elements and when mounted Underneath an Overhang by means of brackets out of the reach
with MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions.
B Installation & Maintenance Instructions MM-414 Series 150E and 157E Low Water Cut-Off/Pump Controllers For Steam Boilers and Other Level Control Applications A Typical Applications: Primary or secondary
10000HXL31/15000HXL31/20000HXL31
Table of Contents www.eaton.com/dxups USER MANUAL ON LINE UPS 10000HXL31/15000HXL31/20000HXL31 Uninterruptible Power Supply Table of Contents 1. Brief introduction 1.1 System and model description---------------------------------------------------------------------1
AIR CONDITIONER INSTALLATION MANUAL
INSTALLATION MANUAL AIR CONDITIONER Please read this installation manual completely before installing the product. Installation work must be performed in accordance with the national wiring standards by
12-Volt 10-Amp Regulated Power Supply
22-506.fm Page 1 Friday, August 6, 1999 12:55 PM Cat. No. 22-506 OWNER S MANUAL Please read before using this equipment. 12-Volt 10-Amp Regulated Power Supply 22-506.fm Page 2 Friday, August 6, 1999 12:55
Bullet Camera. Installation Guide. Hangzhou Hikvision Digital Technology Co., Ltd. http://www.hikvision.com
Bullet Camera Installation Guide Hangzhou Hikvision Digital Technology Co., Ltd. http://www.hikvision.com 1 Thank you for purchasing our product. If there are any questions, or requests, please do not
aseries A13B Mini Bullet Camera User Manual
aseries A13B Mini Bullet Camera User Manual Thank you for purchasing our product. If there are any questions, or requests, please do not hesitate to contact the dealer. This manual applies to the MicroView
Split-type Air-Conditioner INSTALLATION MANUAL CONTENTS FOR INSTALLER MXZ-3A30NA MXZ-4A36NA ATTENTION. English. Français. Español
Split-type Air-Conditioner MXZ-3A30NA MXZ-4A36NA INSTALLATION MANUAL Refer to the installation manual of each indoor unit for indoor unit installation. English Français Español ATTENTION This manual mentions
SL280UHV SERIES GAS FURNACE WARNING
2010 Lennox Industries Inc. Dallas, Texas, USA 506677 01 11/2010 Supersedes 506409 01 SL280UHV SERIES GAS FURNACE Litho U.S.A. FIRE OR EXPLOSION HAZARD. Failure to follow safety warnings exactly could
LS1024B / LS2024B/ LS3024B. Solar Charge Controller USER MANUAL
EPSOLAR LS1024B / LS2024B/ LS3024B Solar Charge Controller USER MANUAL Thank you very much for selecting our product! This manual offers important information and suggestions with respect to installation,
Air Conditioner 457915 B57915 459516 B59516 540315 540316 640312 640315
RECORD THIS INFORMATION FOR FUTURE REFERENCE: Number Serial Number ADB Number ADB Serial Number Date Purchased USA SERVICE OFFICE Dometic Corporation 2320 Industrial Parkway Elkhart, IN 46516 CANADA Dometic
USER MANUAL Stand Alone Power Supply PSQ 2909 / PSQ 3909 / PSQ 4909 PSQ 2920 / PSQ 3920 / PSQ 4920
USER MANUAL Stand Alone Power Supply PSQ 2909 / PSQ 3909 / PSQ 4909 PSQ 2920 / PSQ 3920 / PSQ 4920 [This page intentionally left blank] Warning for Your Protection 1. Read these instructions. 2. Keep these
Single-Phase AC Synchronous Generator
ST Series Single-Phase AC Synchronous Generator Instructions for Operation and Maintenance English to English translation by R.G. Keen, May 2004. ST Series of Single-Phase AC Synchronous Generators Description
Chapter 7 Hydraulic System Troubleshooting
Chapter 7 Hydraulic System Troubleshooting General The following troubleshooting information is provided as a general guide to identify, locate and correct problems that may be experienced with the hydraulic
Manual for Fire Suppression & Methane Detection System
Manual for Fire Suppression & Methane Detection System Fogmaker North America Post address: 150 Gordon Dr Exton, PA 19341 Delivery address: 150 Gordon Dr Exton, PA 19341 Tel: 610-265-3610 Fax: 610-265-8327
Pet hair clipper. Model 96822. Diagrams within this manual may not be drawn proportionally.
Pet hair clipper Model 96822 Cleaning And Operation Instructions Diagrams within this manual may not be drawn proportionally. Due to continuing improvements, actual product may differ slightly from the
Charge Regulator SCR 12 Marine
Charge Regulator SCR 12 Marine Manual Many thanks for purchasing a superwind product. The SCR 12 Marine is a charge regulator of highest quality and will perfectly and reliably charge your batteries for
UHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual
UHIR Series Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater Owner s Manual This manual covers installation, maintenance and repair parts. Read carefully before attempting to
How To Read A Pipe From A Sensor
Liquid Level Sensor Installation on pipes. Sensing by means electrostatic capacity and is not influenced by the color of the pipe or liquid. Available in 8 to mm dia. and to mm dia. models to enable sensing
Fire Protection Notice No. 9 ELECTRICAL SAFETY
Fire Protection Notice No. 9 ELECTRICAL SAFETY Because electricity is one of the most controllable forms of energy it can also be one of the safest. But, as industry and commerce draw ever more heavily
MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS)
MILLENIUM Table of contents 1. INTRODUCTION 1 2. HARDWARE DESCRIPTION 2 3. INSTALLATION 5 4. CONNECTION 6 5. USER SAFETY AND PROTECTION OF EQUIPMENT 8 1. Introduction The MILLENIUM series has been designed
12V Portable Diaphragm Compressor Operating and Maintenance Instructions
12V Portable Diaphragm Compressor Operating and Maintenance Instructions (Part No. DC2) Part No. Serial Number Date Purchased Table of Contents Page Safety Messages...2 Guidelines for Product Use...2 Operation
Uninterruptible Power Supply ERA LED 1.5 ERA LED 2.0 ERA LED 2.6. User s manual
Uninterruptible Power Supply ERA LED 1.5 ERA LED 2.0 ERA LED 2.6 User s manual Index Safety Warnings... 2 1 Introduction... 3 2 General Characteristics... 4 3 Receipt and site selection... 4 4 EXTERNAL
800-292-3279 916 638-0828
800-292-3279 916 638-0828 http://easycleansystems.com/heaters/heater-parts.html VAL6 KBE5S and KBE5L Service manual KBE5S 1 2 Specifications Type VAL6 KBE5S Heat Output 111,000BTU/h Fuel Kerosene, Diesel
Li-ion Rechargeable Battery. Specification
Customer: Specification Model: GMB043450S Prepared By/Date Checked By/Date Approved By/Date Note:1.Kindly please sign on the above and send it back to us if the sample is approved. 2.Kindly please contact
Fixture One Power Cord One User Manual One Omega Bracket One DMX Cable - One
1. INTRODUCTION AND UNPACKING Thank you for purchasing the MICROH LED NEO SPOT 60R moving head fixture. For your own safety and knowledge, please read this manual before installing or operating the device.
When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description
Samba OPLC SM35-J-R20 Installation Guide The Unitronics SM35-J-R20 offers the following onboard I/Os: 12 Digital Inputs, configurable via wiring to include: 1 HSC/Shaft-encoder Input, 2 Analog inputs (only
BC-5000 OPERATIONS MANUAL BATTERY CAPACITY TESTER COFKO LLC.
BC-5000 BATTERY CAPACITY TESTER OPERATIONS MANUAL COFKO LLC. COPYRIGHT 2010 1 UNPACKING As you unpack your new BC-5000 battery capacity tester, inspect the tester for signs of shipping damage. If shipping
ST Series POWER SUPPLIES USER INSTRUCTIONS
Introduction These instructions detail the installation and operation requirements for the ST20 & ST35 power supplies. These have been designed for operation in RV s providing a DC power system, with optional
G670 Intermittent Pilot Ignition Controls
Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin Issue Date 0300 Intermittent Pilot Ignition Controls Figure 1: Intermittent Pilot Ignition Control
Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF
Daker DK 1, 2, 3 kva Manuel d installation Installation manual Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Index 1 Introduction 24 2 Conditions of use 24 3 LCD Panel 25 4 Installation 28 5 UPS communicator
Day / Night IR Color Camera User Manual V2.1.0
Day / Night IR Color Camera User Manual V2.1.0 1 Thank you for purchasing our product. If there is any question or request, please do not hesitate to contact dealer. This manual is applicable to DS-2CC102P(N)-IR1(IR3)(IR5),
INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR THREE PHASE INDUCTION MOTORS
INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR THREE PHASE INDUCTION MOTORS Frames 143T - 449TZ 5100 North IH 35 Round Rock, Texas 78681 Phone: 800-451-8798 512-255-4141 Fax: 512-244-5512 RECEIVING 1. Check
Explosion proof enclosures
1 of 7 Explosion proof enclosures DE8 C 2 of 7 The Ex d enclosures are rugged and designed for harsh environment like: Oil and gas industry Chemical industry Pharmaceutical industry Agribusiness Without
Doc.No. NDP 192U-02. Electric Pump Controller CE-124P. Instruction Manual
Doc.No. NDP 192U-02 Electric Pump Controller CE-124P Instruction Manual 1. Parts Name and Function 1) POWER LED Indicate that CE-124P is powered up. 2) START/STOP KEY (SELECTOR KEY) Used to start and stop
Operating instructions
ebm-papst Mulfingen GmbH & Co. KG Bachmühle D-74673 Mulfingen Phone +49 (0) 7938 8-0 Fax +49 (0) 7938 8-0 [email protected] www.ebmpapst.com CONTENTS. SAFETY REGULATIONS AND NOTES. Levels of hazard
Specification. Li-ion Rechargeable Battery
Specification of Li-ion Rechargeable Battery Model No.: 18650CA-1S-3J Reported by: 陈 声 宇 Date: Oct,17,2013 Checked by: Approved by: Date: Date: 1. Scope This specification describes the definition, technical
MAINTENANCE MANUAL B-65285EN/03
FANUC AC SERVO MOTOR @*s series FANUC AC SERVO MOTOR @* series FANUC AC SPINDLE MOTOR @* series FANUC SERVO AMPLIF IER @* series MAINTENANCE MANUAL B-65285EN/03 No part of this manual may be reproduced