To Condense, or Not to Condense? Installation Practices Leave Boiler Savings on the Table
|
|
|
- Gwendolyn Nash
- 9 years ago
- Views:
Transcription
1 To Condense, or Not to Condense? Installation Practices Leave Boiler Savings on the Table Laura Tabor, Navigant, Boulder, CO Tony Larson, National Grid, Waltham, MA Justin Spencer, Navigant, Boulder, CO Ryan Tanner, Navigant, Boulder, CO Dave Korn, The Cadmus Group, Waltham, MA ABSTRACT High-efficiency natural gas condensing boilers make up roughly half of the residential heating system replacements in Massachusetts gas efficiency programs and can produce significant energy savings for program participants. But how do these units actually perform when installed to replace very different systems? What does it take for condensing boilers to reach their rated efficiencies in the field? The purpose of this 2014 evaluation conducted for the Massachusetts Program Administrators was to rigorously quantify the natural gas savings associated with high-efficiency boilers and furnaces installed through the Massachusetts High-Efficiency Heating Equipment Rebate Program. This paper focuses specifically on highefficiency boilers. In this study, the team used a novel approach to meter 70 high-efficiency residential boilers to determine annual heating and hot water loads as well as in-situ efficiency for the average unit installed. The evaluation showed that high-efficiency boilers are not operating to their full energy savings potential. Given that only 12% of metered units operate in condensing mode for significant portions of the heating season, the results suggest that improved contractor education on quality installation practices, system and distribution sizing, and outdoor reset controls would likely improve the operating efficiency of residential condensing boilers. These findings present new challenges for program administrators to evaluate the cost-effectiveness of implementing these improved installation practices. Introduction The Massachusetts High-Efficiency Heating Equipment Rebate Program (HEHE) offers prescriptive rebates of up to $1,600 for the installation of new high-efficiency natural gas heating and water heating equipment. The objective of a 2014 evaluation of this program was to determine gross energy savings for gas furnaces and boilers installed through the HEHE program, and refine the estimates of baseline efficiency and heating consumption. The evaluation sought to answer the following researchable questions: How much energy is being saved for the average installation of efficient space heating equipment through the Massachusetts HEHE program? How does the in situ efficiency of standard efficiency furnaces and boilers that are installed outside of the program compare to their rated efficiency? How does the in situ efficiency of existing equipment that is retired early compare to its rated efficiency? How are condensing boilers being installed and controlled, as it relates to their potential savings? 1 1 The high efficiency of condensing boilers relies on a low boiler return water temperature, which means that differences in installation practices that impact return water temperature have a large impact on savings. Condensing boilers pass return water through a heat exchanger with the flue gases to recover additional heat. When return water temperatures are low enough, this process condenses the
2 This paper describes the evaluation methodology, results and implications for high-efficiency boilers. Methodology For retrofit space heating and combination heating and hot water boilers, there are three major parameters that determine energy savings: Annual home heating and combined heat and hot water load (for all types of replacements) Efficiency of the baseline space heating equipment, either existing equipment for early retirement or standard efficiency equipment for replacement on failure participants Efficiency of the new space heating equipment promoted through the program In order to assess these major parameters, the evaluation team designed the field portion of the study with two main components: 1. Spot measurement of baseline and new equipment in situ (measured) efficiency. This task provided efficiency estimates to reduce the uncertainty around new, early retirement and standard baseline boiler performance. 2. Long-term metering of post-retrofit high efficiency equipment (majority of heating season). This task refined estimates of annual heating load for furnaces and boilers. Logging of operating parameters such as supply and return water temperatures was particularly important for condensing boilers where efficiency is dependent on return water temperature. The team used a nested sampling approach in order to maximize the precision of results while keeping on-site sample sizes and associated costs low. This approach began with a low cost-per-participant billing data disaggregation analysis. (see Spencer, Greenberg & Decker 2013) The billing data disaggregation sample sizes were large and encompassed a wide range of participant behaviors, allowing for a smaller on-site sample. Figure 1 illustrates this concept. Figure 1. Nested Sampling Approach Program population = 5,741; Billing data disaggregation n = 1,688; On-site metering n = 70 water vapor in the flue gas, resulting in latent heat gains into the return water coming back to the boiler and increasing efficiency levels to upwards of 95 percent. However, boilers are not always installed with controls that optimize return water temperatures for maximum efficiency.
3 We obtained a first estimate of annual heating system consumption by disaggregating large samples of participant billing data in order to incorporate a wider range of participant home characteristics and behaviors in the final results and eliminate sample bias. Figure 2 shows how the team combined measured parameters from each of these analysis components to calculate savings. Figure 2. Savings Calculation for Heating Equipment Billing Data Disaggregation Sample On-site Sample Estimated Annual Heating Load at Home Level On-site Sample Only Metered Gas Consumption at Furnace Level In-situ Efficiency Rated Efficiency AFUE ee AFUE base All of Billing Data Disaggregation Sample Ratio of Metered to Estimated Annual Heating Load Final Estimate of Annual Heating Load (Load) Ratio of In-Situ to Rated Efficiency by Group R AFUE,ee R AFUE,base Note: Annual heating load is defined here as the total heat delivered to the home by the furnace or boiler and is calculated as actual consumption divided by actual efficiency. Long-term Metering Approach The efficiency of condensing boilers varies with return water temperature and most condensing boilers fully modulate their firing rates over a wide range of input and output. The team metered the return water temperature along with the supply temperature to monitor both the efficiency of the boiler and the temperature delta across the boiler. The team used the following equation and measurements (Table 1) to determine total gas consumption, assuming a constant flow of water through each boiler s primary loop. 2 Where: 2 Condensing boilers are designed to operate with a constant flow rate and require an installation that isolates the primary boiler pump from varying flow rates in the secondary loops serving the house zones.
4 Table 1. Boiler Measurements and Definition of Variables Measurement Output Variable State (on/off) loggers on gas valves Indicator of when boiler is on Interval metering of supply and Supply and return water temperature at return water temperature interval i Estimate of water mass flow rate in Synchronized spot measurements of primary boiler loop (constant) efficiency, gas consumption, and Rate of gas consumption for a given supply and return temperature efficiency and n/a Specific heat of water, Spot Measurements of Boiler Efficiency The team performed combustion tests on high-efficiency and standard new and early retirement units to determine the ratio of actual performance to rated efficiency for each group. The team used one standard test protocol for standard new and early retirement equipment and a modified protocol for high-efficiency boilers. High-Efficiency Boilers As described above, condensing boiler efficiency varies with return water temperature and these boilers are designed to handle a wide range of operating temperatures. This means that a single spot measurement is not an accurate measurement of the seasonal operating efficiency of a boiler: return water temperature varies constantly as the boiler heats up and cools down, and may differ depending on which zones in the home are being served and the outdoor temperature. The team took a series of efficiency spot measurements concurrent with measurements of return water temperature as described above. We then used the long-term metered return water temperature data and the observed relationship between return temperature and efficiency from the spot measurements to estimate seasonal efficiency for each boiler. Standard Efficiency Boilers The team took a series of spot measurements on each standard efficiency boiler operating in steady state. At each site, field staff turned on the unit, waited five minutes for it to warm up, and recorded the efficiency reading from a combustion analyzer every 15 seconds for three minutes. The final result for each unit is the average of the three-minute test. Billing Data Disaggregation The team used participant billing records and program data on furnace and boiler models installed to estimate heating consumption and savings for the participants in each analysis sample. For a complete description of the disaggregation methodology, please see Appendix A of the evaluation report (Tabor et al 2015). Calibrated Simulation The evaluation team used home characteristics details collected from the on-site sample to build three energy models in the Building Energy Optimization (BEopt) software developed by the National
5 Renewable Energy Laboratory (NREL). 3 The purpose of the modeling was to accurately extrapolate the billing data from the heating season to a typical weather year. The team first built each model based on homes in the study and calibrated them such that the output aligned with the average consumption from the participant billing records when run with actual weather data from the recent heating season (to a difference of less than one percent). 4 Once the model was sufficiently calibrated, the analysis team ran the model using a Typical Meteorological Year (TMY3) file from Worcester, MA. TMY3 data represents typical weather patterns for the location. Figure 3 illustrates the alignment of the billing data and calibrated model. The lower value of the TMY3 model output indicates that was a colder than average winter with higher heating usage. 924 Heating Therms 931 Heating Therms 888 Heating Therms Figure 3. Calibrated Model Outputs for Standard Boilers: Annual Consumption Results The team exceeded the sample size target for the billing data disaggregation but fell short of the target for usable metering sites. The boiler long-term metering sites used a combination of several timesynchronized measurements. The team eliminated sites where either the long-term metered data was unusable due to logger failure (unusable for gas consumption estimates) or where the spot measurement data was unusable due to inconsistent operation of the boiler (unusable for efficiency estimates). For more detail on the quality control (QC) processes used to screen metered data, please see Appendix B of the evaluation report (Tabor et al 2015). Unfortunately, there was no overlap between these two groups of excluded sites. Table 2 summarizes the attrition for each group. 3 The evaluation team used the EnergyPlus engine with the BEopt software. 4 The evaluation team used an actual weather file from Worcester for June 2013 May 2014 to calibrate the model. The TMY3 file was also for Worcester. The TMY3 file reflects the average weather from 1991 to 2005 at a given location.
6 Table 2. Boiler Sample Dispositions Group Target Achieved Limitations Long Term Metering: Unusable metered data (16) Gas Consumption Unusable spot measurements (12) Long Term Metering: Unusable metered data (16) Efficiency Billing Data n/a 1,000 1,688 Disaggregation Standard New Efficiency Spot Measurements 30 (36 visited) 28 Efficiency >=90% AFUE (6)* Unable to take measurements (3)* Unable to verify nameplate (1) *Two of the units without spot measurements were also high-efficiency. Table 3 shows the final results for average combined annual heating and water heating consumption and loads for both standard and combination boilers. The team chose to analyze combined annual heating and water heating consumption and loads for all boilers because field verification showed that 80 percent of standard boilers serve hot water loads, making combined heating and hot water loads more representative of typical boiler loads than heating only. (Over half of the boilers listed as standalone systems in the program tracking data also served indirect water heaters.) The final ratio of metered to billing use for boilers of 1.01 demonstrates that the billing disaggregation predicted boiler combined heating and hot water consumption well. The results also showed that combination heating and hot water units tend to serve smaller annual heating and hot water loads than standalone boilers with or without indirect water heaters. 5 Table 3. Boiler Heating and Water Heating Consumption Findings Relative Metric System Type Mean n Precision at 90% Confidence Heating and DHW Therm Consumption, Billed Typical Year Heating and DHW Therm Consumption Ratio of Metered to Billed Use Final Estimate of Typical Year Heating and DHW Therm Consumption Final Estimate of Typical Year Annual Heating and DHW Therm Load Standard 1,100 1, % Combination % Description Mean of site level heating and hot water therms Standard 1, Calibrated model therm consumption for a typical weather Combination year All % Standard 1, % Combination % Mean ratio of metered heating and hot water therm use to disaggregated billing data therm use for the same period Product of typical year heating consumption therms and mean ratio of metered to billed heating and hot water use Standard Product of typical year heating consumption and average verified Combination efficiency 5 Combination heating and hot water units are a single piece of equipment serving heating and hot water loads, with the hot water heat exchanger (and sometimes a small storage tank) enclosed in the unit along with the boiler itself. An indirect water heater is a larger storage tank heated by ahot water loop from the boiler.
7 Table 4 shows the final adjusted ratios of in-situ to rated efficiency for standard new and highefficiency boilers. Table 4. Boiler Efficiency Findings Metric Mean n Ratio of Standard New In-situ to Rated Efficiency Ratio of High Efficiency In-situ to Rated Efficiency* Relative Precision at 90% Confidence % Description Adjusted ratio of efficiency spot measurements to rated AFUE for equipment rated <90% AFUE Ratio of efficiency spot measurements to rated AFUE for equipment rated >=95% AFUE *Since boiler efficiency was determined using long-term metering data, uncertainty for this parameter is included in the consumption findings. For details, see Appendix C of the evaluation report (Tabor et al 2015). The team found that both standard and high-efficiency boilers performed below their rated efficiencies for two different reasons. The standard efficiency boiler spot measurement tests demonstrated combustion efficiencies equal to rated AFUE on average. The team applied an adjustment factor to account for higher standby losses in gravity-vented equipment. Standby losses for standard efficiency boilers are high due to the combination of passive venting design and large thermal mass of the cast iron boilers with relatively high water capacity (as compared to high-efficiency boilers), which increases the passive stack losses in between active firing periods. 6 The team thus applied an estimated adjustment factor of three percent for standard efficiency and existing boilers measured. 7 High efficiency boilers do not experience high passive stack losses because they have sealed combustion systems with combustion air blowers running only in conjunction with a firing event. High-efficiency boilers also underperformed relative to their rated AFUE because they did not typically attain the return water temperature necessary (typically below F) to achieve condensing of the water vapor in the flue gas, which drives efficiencies above 90 percent. Figure 4 shows a typical efficiency versus return water temperature curve for a condensing boiler. 6 Some efficient boilers are designed with higher mass. If they are not passively vented, the mass may provide an efficiency benefit. 7 The team relied on internal experts to inform this value, which is based on a review of the components of the AFUE test procedure calculation method and the relative weight of cycling and steady-state efficiency.
8 Figure 4. Condensing Boiler Efficiency (Shen 2013) Over the course of the winter, metered data showed that most systems spent the majority of heating hours operating with supply and return temperatures too high to achieve condensing. This is illustrated by the distribution of return water temperatures for each site, Figure 5 shows the distribution of heating hours by return water temperature (low, varying, and high), along with the proportion of sites falling into each bin. Return water temperature is a function of supply temperature and distribution sizing in the home; higher supply temperatures generally mean that the unit was installed with higher supply set points and no or less aggressive outdoor reset controls. Figure 5. Distribution of heating hours by return water temperature (RWT) Table 5 shows the final verified savings results for each deemed boiler measure in Massachusetts. Although the high-efficiency boilers performed below their rated AFUE, verified savings ranged from percent of deemed savings values due to larger than assumed annual heating and hot water loads and below rated operating baseline efficiency. As previously noted, the verified boiler annual loads are higher than current assumptions because the annual loads account for the fact that the majority of standard boilers serve hot water as well as space heating.
9 Table 5. Standard Boiler Verified Savings Replace on Failure (ROF) Baseline Verified Deemed ROF AFUE Efficient Baseline ROF ROF Realization Measure Type AFUE AFUE Therm Therm Rate Savings Savings 90% AFUE Boiler 95% AFUE Boiler 96% AFUE Boiler Rated 92.7% Verified 87.2% Rated 95.0% Verified 89.4% Rated 96.0% Verified 90.3% Rated: 82.0% Verified: 79.3% % % % Relative Precision at 90% Confidence 10.0% While the realization rates appear high, Figure 1Figure 6 illustrates the impact of high-efficiency boilers low AFUE performance. This finding accounts for a loss of over 60 therms for all measures relative to calculating savings with a rated baseline. Figure 6. Potential and Actual Boiler Savings Program Implications and Conclusions This study demonstrated that most boilers operate well below their rated efficiency and operating efficiency could be improved through contractor and customer education. The main cause for low efficiency performance is a lack of aggressive outdoor air reset supply temperature curves: when high-efficiency boilers operate at supply temperatures above 140 F, return water temperatures often exceed the condensing range (~130 F and below) and efficiency begins to drop off significantly. Outdoor reset controls can reduce the time a boiler spends running at high supply and return temperatures by lowering supply temperature as outdoor air temperature increases and the home needs less heat. Over 50 percent of boilers in the metering sample showed no evidence of effectively programmed outdoor reset controls, and only 12 percent showed outdoor reset curves aggressive enough to demonstrate significant condensing. The team conducted a highlevel analysis of optimal outdoor reset curves and estimates that in a best-case scenario, a boiler in
10 Massachusetts with well-programmed outdoor reset controls could see a maximum operating efficiency improvement of up to 3 to 4 percentage points from the average efficiency observed in this study (Figure 7). Figure 7. Estimated potential savings from improved outdoor air temperature (OAT) reset controls The obvious programmatic solution to this problem is to improve contractor education on outdoor reset controls and enact a quality installation program component to push contractors to implement these controls more effectively. This is a simple, low-cost way to recoup some of the savings left on the table. However, this step alone will not fully capture boiler savings potential in all homes. In order to maintain effective outdoor reset schedules, two criteria must be met: 1) Distribution and terminal equipment must be sized such that boilers can meet home loads at lower supply temperatures and/or have a large enough temperature differential to consistently deliver lower return water temperatures at higher supply temperatures. 2) Customers must understand what to expect from their systems and set thermostat schedules accordingly, or thermostats must be smart enough to adapt to condensing boilers capabilities (i.e., begin morning warm-up well in advance of scheduled morning temperature change). The following sections describe the issues behind each of these criteria and potential options that programs should consider to increase the number of installations meeting them. Distribution Sizing and Design Many heating distribution systems in Massachusetts were designed for older boilers which operated at high supply temperatures (180 F supply temperature would be typical). When new high-efficiency systems are installed, best practice is to perform a Manual J calculation to determine the loads in each zone and whether the existing distribution (i.e. radiators, panels, etc.) can meet those loads at lower supply temperatures. In order for the boiler to condense for the majority of the heating season, the distribution system must be able to meet zone loads with 140 F supply water on all but the coldest design days. This supply temperature would typically ensure a low enough return water temperature for the boiler exhaust air to condense most of the time. Many homes may have zones which would require additional distribution in order to meet peak loads or even typical winter loads at lower supply temperatures. One option for the program is to focus contractor education on understanding this issue and require distribution sizing analysis with each condensing boiler installation. This analysis would require:
11 1) Conducting a Manual J calculation for heating loads in each zone served by the new boiler 2) Calculating heat delivery for existing distribution at supply temperatures of 140 F or below 3) Installing additional distribution as needed to ensure loads can be met while returning water at temperatures in the condensing range There are several options for adding distribution, such as high-efficiency panel radiators. Figure 8 illustrates two examples of panel radiators, which come in many sizes and styles. Figure 8. Example Panel Radiators (DesignerRadiators Direct 2013, JRF) An alternative to adding distribution is reducing loads in homes with boilers. With measures like improved insulation, windows or air sealing, zone loads will decrease, meaning that the heating needs can be met with cooler supply water. However, additional distribution and envelope improvements can both be costly upgrades. The evaluation team recommended conducting additional research on the costs and benefits of these options. Homeowner Expectations Homeowners who are accustomed to a standard boiler supplying 180 F to their radiators will need to adjust to lower supply temperatures. Lower supply set points and aggressive outdoor reset programs ensure that boilers operate at a steady, relatively low output. The radiators may not feel as hot even when the heat is on, and it will take longer for rooms to come to temperature after a thermostat setback. This can lead to homeowner complaints if residents are accustomed to getting immediate responses from their heating systems. For example, when customers program a night setback the system must warm the house back up in the morning and homeowners accustomed to a system running 180 F will expect this to happen relatively quickly. A new condensing boiler can provide this kind of response if programmed to allow high supply temperatures, but will not achieve high efficiency levels while doing so. Customers experiencing these patterns for the first time will often call back contractors, who may remove any outdoor reset controls that had been programmed or increase the supply water temperature set point. Unless homeowners understand their new systems and are willing to put in the time to fine-tune them, this pattern will continue and boiler savings will not reach their full potential. Use of improved thermostats with built-in ramping of temperatures could also improve the customer experience with these systems and allow more aggressive outdoor resets to be used. The evaluation team recommended that the program consider including a customer education component to contractor training, so that contractors can educate homeowners on how to manage their new boilers: The boiler may run more efficiently without setbacks if a constant, moderate temperature set point is used
12 If setbacks are desired, customers should anticipate longer warm-up times and program temperature changes accordingly. For example, if the kitchen should be warmed up to 68 degrees at 7:00 am, the time setting on the thermostat may need to be well before then. The team also conducted research on thermostat options that could enhance homeowner experiences with proper outdoor reset controls. Unfortunately, it appears that there are not many available options. Some smart thermostats such as the Nest can learn warm-up behavior, but do not appear to interact very well with systems that have outdoor reset controls employed. (Nest, Nest Community). 8 Tekmar makes a thermostat which interacts with outdoor reset controls and can override an outdoor reset curve during morning warm-up ( boost feature). However, this feature could decrease energy savings since it is focused on comfort and increasing boiler supply temperatures beyond the reset curve. Given the uncertainty around the effects of programmed setbacks on condensing boiler performance, the team recommended considering additional research in this area to determine whether programmable thermostat savings are appropriate for homes with condensing boilers. Summary of Boiler Recommendations The evaluation team recommended adding some level of quality installation component to the HEHE program for high-efficiency boilers. The program is considering improving contractor education on outdoor reset controls. Because getting boiler controls implemented correctly is not always a prescriptive, one size fits all process, the program administrators will continue to research the benefits and costs of the additional components described above: 1) Educating homeowners on how to set thermostats for optimum performance 2) Training contractors to assess and consider the following options when installing new systems: a. Running Manual J calculations for each zone served by the new boiler to determine whether current distribution is adequate to meet home loads at 140 F supply temperature b. Adding distribution to meet home loads at 140 F supply temperature c. Making envelope improvements such that distribution can meet home loads at 140 F supply temperature 3) Exploring smart thermostat technology options 8 Nest True Radiant feature claims to adjust for lag in radiant systems and Nest customer feedback indicates lack of compatibility with outdoor reset
13 References DesignerRadiators Direct Ltd, Amazing Benefits of Flat Panel Radiators, [JRF] JRF Plumbing and Heating. Radiators and Towel Heaters Panel Radiators, Nest, What Is True Radiant? Nest Support. Nest Community, Outdoor Temperature Reset. Nest Community Product Suggestion Forum. Shen, Lester High Efficiency Should Be a Drain: A Closer Look at Condensing Boilers, Home Energy Pros. Spencer, J., Greenberg, D., Decker, T Revisiting Double Ratio Estimation for Mitigating Risk in High Rigor Evaluation. In Proceedings of IEPEC Tabor, L., Spencer, J., Tanner, R., Herring, N., Stanton, T., Seiden, K High Efficiency Heating Equipment Impact Evaluation. The Cadmus Group. Prepared for the Massachusetts Program Administrators.
High Efficiency Heating
High Efficiency Heating Mike Pace Senior Engineer National Grid C&I Efficiency Programs Prescriptive Controls Energy Star Programmable Thermostats A thermostat that is able to be programmed to set back
Condensing Boiler Efficiency
Condensing Boiler Efficiency Date: July 17, 2012 PRES E NT ED BY DO N L E O NA RDI LE O N A RD I I NC. HV AC T RAI N I N G & C ON SU LT IN G Concepts 1 The current state of evolution in boiler design 2
Condensing Boilers. High Efficiency. Proven Reliability, American-Made Home Heating Comfort. ANYWHERE UNMATCHED
High Efficiency Condensing Boilers Proven Reliability, American-Made Home Heating Comfort. Look for this logo throughout this literature to see the unique features that set U.S. Boiler Company apart from
Mixing Valves. ARGUS Application Note: Mixing Valves
Mixing Valves Most radiant hot water heating systems in greenhouses use mixing valves to control the temperature of heating pipes. Both 3-way and 4- way valves are commonly used. Mixing valves provide
Printing and Publishing Energy Savings Guide
Printing and Publishing Energy Savings Guide Oregon printing and publishing plants face challenges of rising operating costs, environmental and other regulations, outdated equipment and customer demand
GAS CONVERSION PROJECT ˆAn Alternative to Oil
GAS CONVERSION PROJECT ˆAn Alternative to Oil Presented to: MORTON CIVIC ASSOCIATION Franklin Square/West Hempstead Presented by: Scialli Plumbing & Heating 130 Stewart Avenue Hicksville, NY 11801 516.334.6701
When considering your heating options, keep in mind that 60% of your energy. costs are attributed to space heating. You
Heating Options Furnaces & Boilers September 2005 CONSUMERS GUIDE - TO HOME HEATING OPTIONS CONTENTS Heat Distribution Energy Source Boilers Proper Sizing Energy Efficiency - Standards - Rating System
Natural Gas Energy Efficiency Opportunities for Commercial & Industrial Customers. Michael Pace Lead Engineer C & I Efficiency Programs
Natural Gas Energy Efficiency Opportunities for Commercial & Industrial Customers Michael Pace Lead Engineer C & I Efficiency Programs Agenda Energy Efficiency Opportunities for Small/Mid Commercial Facilities
Principals of Condensing Boiler System Design
Principals of Condensing Boiler System Design Dennis Jones, P.E. Member ASHRAE ABSTRACT Condensing boilers can provide significant energy savings due to operating efficiencies as high as 98% as compared
Case Studies: Infrared Heating in Industrial Applications
Case Studies: Infrared Heating in Industrial Applications Chao Chen, Puget Sound Energy ABSTRACT Puget Sound Energy (PSE) is a utility which serves more than one million electric customers and over 700,000
RESEARCH HIGHLIGHT. The Impact of Heat Pump Water Heaters on Whole-House Energy Consumption
RESEARCH HIGHLIGHT December 2014 Technical Series 14-104 The Impact of Heat Pump Water Heaters on Whole-House Energy Consumption INTRODUCTION Heat pump water heaters are one of the most energyefficient
Sample - Existing Building Commissioning Plan
Sample - Existing Building Commissioning Plan Version: Draft for Review Final Approved: Owner Site Address: Primary Site Contact Name and Telephone Number: Date Building Description The site consists of
White Paper Nest Learning Thermostat Efficiency Simulation for France. Nest Labs September 2014
White Paper Nest Learning Thermostat Efficiency Simulation for France Nest Labs September 2014 Introduction This white paper gives an overview of potential energy savings using the Nest Learning Thermostat
Centauri. Condensing Fire Tube Water Boiler 399 to 1000 MBH
Centauri Condensing Fire Tube Water Boiler 399 to 1000 MBH Pre-mix surface burner with up to a 7-to-1 turndown NOx levels as low a 5 ppm at full rate Operates on 4" gas pressure shown with optional gauges
(Adopted December 1, 1978)(Amended July 8, 1983)(Amended November 6, 2009) (Amended September 5, 2014)
(Adopted December 1, 1978)(Amended July 8, 1983)(Amended November 6, 2009) (Amended September 5, 2014) RULE 1111. REDUCTION OF NO x EMISSIONS FROM NATURAL-GAS- FIRED, FAN-TYPE CENTRAL FURNACES (a) (b)
Operating instructions
Operating instructions Gas condensing boilers MGK-130 MGK-170 MGK-210 MGK-250 MGK-300 Wolf GmbH Postfach 1380 D-84048 Mainburg Tel. +49 8751/74-0 Fax +49 8751/741600 Internet: www.wolf-heiztechnik.de Document
ENERGY EFFICIENT HEATING
RE-ENERGIZE YOUR HOME ENERGY EFFICIENT HEATING PSE.COM/ReENERGIZE RE-ENERGIZE YOUR HOME, YOUR HEATING, YOUR SAVINGS A warm home is a comfortable home for you and your family, and yet your heating system
Commercial Boiler Systems and Controls
Commercial Boiler Systems and Controls Condensing Non-condensing Hybrid Systems Steel Medium Mass Copper Instantaneous Electric Riverside R HYDRONICS An introduction to hybrid boiler systems What is a
Continuous flow direct water heating for potable hot water
Continuous flow direct water heating for potable hot water An independently produced White Paper for Rinnai UK 2013 www.rinnaiuk.com In the 35 years since direct hot water systems entered the UK commercial
Maximizing Boiler Plant Efficiency. Presenter: Dan Watkins, LEED BD+C Sales Engineer Bornquist, Inc.
Maximizing Boiler Plant Efficiency Presenter: Dan Watkins, LEED BD+C Sales Engineer Bornquist, Inc. Efficient Boiler Design Boiler Types Efficiency Definition Non-Condensing Condensing Maximizing Efficiency
Consolidated Edison of New York: Residential HVAC Program Process Evaluation Summary
Consolidated Edison of New York: Residential HVAC Program Process Evaluation Summary Evaluation Conducted by: Navigant Consulting, Inc., October 2013 PROGRAM SUMMARY The Residential HVAC programs promote
Building Energy Systems. - HVAC: Heating, Distribution -
* Some of the images used in these slides are taken from the internet for instructional purposes only Building Energy Systems - HVAC: Heating, Distribution - Bryan Eisenhower Associate Director Center
1. What percent of a commercial business s energy usage comes from their HVAC system? A. 13% B. 23% C. 33% D. 43% E. 53%
1 1. What percent of a commercial business s energy usage comes from their HVAC system? A. 13% B. 23% C. 33% D. 43% E. 53% 2. How much money do commercial facilities spend per square foot on energy costs
Ecodan Air Source Heat Pump and Flow Temperature Controller 2
HOMEOWNER STANDALONE Homeowner Information SEPTEMBER 2011 Ecodan Air Source Heat Pump and Flow Temperature Controller 2 Ecodan Air Source Heat Pump Model Number PUHZ-W50VHA(2)-BS PUHZ-W85VHA(2)-BS PUHZ-HW140VHA(2)-BS
The Only GUY To Call. Why are my utility bills so high? What can I do to lower my energy expenses?
The Only GUY To Call May 2014 412.885.2356 Why are my utility bills so high? What can I do to lower my energy expenses? Did you know... that between 2007 and 2012, the average U.S. household spent more
GAS HEATING IN COMMERCIAL PREMISES
ENERGY EFFICIENCY OFFICES GAS HEATING IN COMMERCIAL PREMISES www.energia.ie www.energia.ie Typically, energy reductions of 10% or more can be made easily through maintenance and low cost improvements.
Hot Water Boilers and Controls Why Condensing Boilers are Different. Presented Oct. 14, 2008 Long Island Chapter, ASHRAE
Hot Water Boilers and Controls Why Condensing Boilers are Different Presented Oct. 14, 2008 Long Island Chapter, ASHRAE H.W. Boilers and Controls Major types of boilers Advantages and disadvantages Resistance
Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues
Design Guide Retrofitting Options For HVAC Systems In Live Performance Venues Heating, ventilation and air conditioning (HVAC) systems are major energy consumers in live performance venues. For this reason,
Y-200 Multi-Stage Sequencer
Y-200 Multi-Stage Sequencer Designed for use with single or multiple space heating or hot water supply systems, the Y-200 is offered in 4- and 8-stage configurations and is available loose or factory-mounted
2 STEPS TO CONDUCTING YOUR HVAC ASSESSMENT
Presentation Synopsis Heating, Ventilating and Air Conditioning Building Condition Assessment Vancouver, B.C. Prepared for: EPIC Prepared by: Douglas Spratt, P.Eng Douglas Spratt & Associates Ltd. www.dspratt-associates.com
Chapter 10: Peak Demand and Time-Differentiated Energy Savings Cross-Cutting Protocols
Chapter 10: Peak Demand and Time-Differentiated Energy Savings Cross-Cutting Protocols Frank Stern, Navigant Consulting Subcontract Report NREL/SR-7A30-53827 April 2013 Chapter 10 Table of Contents 1 Introduction...2
Winter heating This winter heating guide includes ways to reduce heating costs and provides advice on choosing the right heater to suit your needs.
Winter heating This winter heating guide includes ways to reduce heating costs and provides advice on choosing the right heater to suit your needs. Fuel for thought Choosing the right heating system for
Selecting a New Water Heater
U ENERGY EFFICIENCY AND RENEWABLE ENERGY CLEARINGHOUSE Selecting a New Water Heater Many homeowners wait until their heater fails before shopping for a replacement. Because they are in a hurry to regain
Repair, Modify or Replace?? What is the right answer?? By : Joe Mozeika
Repair, Modify or Replace?? What is the right answer?? By : Joe Mozeika First you have to determine what s really wrong with what you have? Analyze how old your unit is? What are really trying to achieve
Training Course Catalog
Training Course Catalog Our courses are designed and taught by industry experts who have hands-on experience across the nation, bringing the most current and practical knowledge to our students. With 30
Beware of Exaggerated Claims and Uncertified Manufacturers Ratings Regarding Commercial Boiler Efficiency
Beware of Exaggerated Claims and Uncertified Manufacturers Ratings Regarding Commercial Boiler Efficiency For many years competent professional HVAC engineers have been aware of exaggerated or deceptive
M & V Guidelines for HUD Energy Performance Contracts Guidance for ESCo-Developed Projects 1/21/2011
M & V Guidelines for HUD Energy Performance Contracts Guidance for ESCo-Developed Projects 1/21/2011 1) Purpose of the HUD M&V Guide This document contains the procedures and guidelines for quantifying
The Effect of Schedules on HVAC Runtime for Nest Learning Thermostat Users
WHITE PAPER SUMMARY The Effect of Schedules on HVAC Runtime for Nest Learning Thermostat Users Nest Labs, Inc. September 2013! 1 1. Introduction Since the launch of the Nest Learning Thermostat in October
M&V of Hot Water Boiler Plant. Boban Ratkovich, P. Eng, CEM, BESA, LEED AP President CES Engineering Ltd
M&V of Hot Water Boiler Plant Boban Ratkovich, P. Eng, CEM, BESA, LEED AP President CES Engineering Ltd AIA Quality Assurance Learning Objectives 1. Case study examples of procedures and obstacles in measuring
Air-Conditioning Buying Guide
Air-Conditioning Buying Guide Buying a new air-conditioning system is a big decision. This Air-Conditioning Buying Guide can help you make the right choice, save energy and money. Shop with confidence
Condensing Boilers Evaluation: Retrofit and New Construction Applications
Prepared for the U.S. General Services Administration By the National Renewable Energy Laboratory June 2014 Condensing Boilers Evaluation: Retrofit and New Construction Applications Dylan Cutler Jesse
Hot Water Heating: Technologies and Use
Hot Water Heating: Technologies and Use Skip Hayden Integrated Energy Systems CanmetENERGY Better Buildings by Design 2010 Burlington Vermont February 2010 Natural Resources Canada Ressources naturelles
warm air for the healthiest, most comfortable home environment possible. This occurs with a system efficiency of up to 90%.
Lifebreath delivers a complete indoor climate control package Indoor comfort in a small package The patented Lifebreath Clean Air Furnace combines the fresh air benefits of the Heat Recovery Ventilator
Nicor Gas Business Custom Incentive Program GPY3 Evaluation Report
Nicor Gas Business Custom Incentive Program GPY3 Evaluation Report Final Energy Efficiency Plan: Gas Plan Year 3 (6/1/2013-5/31/2014) Presented to Nicor Gas Company July 28, 2015 Prepared by: Lorraine
Seeing by Degrees: Programming Visualization From Sensor Networks
Seeing by Degrees: Programming Visualization From Sensor Networks Da-Wei Huang Michael Bobker Daniel Harris Engineer, Building Manager, Building Director of Control Control Technology Strategy Development
A Class Air Source Heat Pump User Guide
A Class Air Source Heat Pump User Guide IMPORTANT THIS MANUAL MUST BE LEFT WITH THE USER AFTER INSTALLATION 8/60476/0 Issue 1.03 Contents 1: Introduction 1 2: How the Heat Pump Works 1 2.1 Tips and advice
8 716 473 216-00.3O. Gas boiler. Gaz 6000 W WBN 6000-30-H-E-N/L-S2400. Operating instructions for the end customer. 8 716 473 217 (2014/07) en
8 716 473 216-00.3O Gas boiler WBN 6000-30-H-E-N/L-S2400 Operating instructions for the end customer en 2 Contents Contents 1 Key to symbols and safety instructions................... 2 1.1 Key to symbols..................................
White paper on the comparative energy efficiency of zoned electric heaters Convectair, Inc. / Convectair-NMT Inc. September 2004
White paper on the comparative energy efficiency of zoned electric heaters Convectair, Inc. / Convectair-NMT Inc. September 2004 Contents : 1. Introduction 2. Fundamentals of heating 3. Temperature distribution
TOWER RENEWAL CASE STUDY
TOWER RENEWAL CASE STUDY Energy Monitoring and Management: A Case Study of Brentwood Towers, Toronto Executive Summary Through good management, and new technologies, O Shanter Development has achieved
RHODE ISLAND SMALL BUSINESS ENERGY EFFICIENCY PROGRAM PRESCRIPTIVE LIGHTING STUDY
RHODE ISLAND SMALL BUSINESS ENERGY EFFICIENCY PROGRAM PRESCRIPTIVE LIGHTING STUDY Final Report National Grid Prepared by DNV GL Date: July, 2015 Prepared by: Jeff Zynda, Sr. Consultant I (PM) Verified
Home Energy Evaluation Report
Home Energy Evaluation Report Nate Begeman, 1550 Saint Francis Dr San Jose, CA 95125 Air Infiltration Current Air Leakage 2,852 Current Air Changes Per Hour 0.91 Recommended Air Changes Per Hour 0.35 Percent
Energy Savings from the Nest Learning Thermostat: Energy Bill Analysis Results
WHITE PAPER Energy Savings from the Nest Learning Thermostat: Energy Bill Analysis Results Nest is committed to being an industry leader in measuring and sharing energy savings results. This white paper
2014/15-2016/17 ELECTRICITY EFFICIENCY PLAN
2014/15-2016/17 ELECTRICITY EFFICIENCY PLAN PLAN OVERVIEW Prepared for the New Brunswick Department of Energy and Mines with the assistance of Dunsky Energy Consulting July 2014 This page intentionally
Corporate Energy Conservation & Demand Management Plan (CECDMP) 2014-2019
Corporate Energy Conservation & Demand Management Plan (CECDMP) 2014-2019 Table of Contents Our Commitment to Energy Conservation...1 1.0 Introduction...2 2.0 Energy Supply in Ontario...3 2.1 Energy Supply
Boiler Preparation, Start-Up and Shutdown
Boiler Preparation, Start-Up and Shutdown Learning Outcome When you complete this module you will be able to: Describe the basic preparation of a boiler for start-up, and the start-up and shutdown procedures.
Operation manual. Daikin Altherma hybrid heat pump EHYHBH05AA EHYHBH08AA EHYHBX08AA. Operation manual Daikin Altherma hybrid heat pump.
EHYHBH05AA EHYHBH08AA EHYHBX08AA English Table of contents Table of contents 1 About this document 2 2 About the system 2 2.1 Components in a typical system layout... 2 3 Operation 3 3.1 Overview: Operation...
Boiler efficiency for community heating in SAP
Technical Papers supporting SAP 2009 Boiler efficiency for community heating in SAP Reference no. STP09/B06 Date last amended 26 March 2009 Date originated 28 May 2008 Author(s) John Hayton and Alan Shiret,
CONCEPTUALIZATION OF UTILIZING WATER SOURCE HEAT PUMPS WITH COOL STORAGE ROOFS
CONCEPTUALIZATION OF UTILIZING WATER SOURCE HEAT PUMPS WITH COOL STORAGE ROOFS by Dr. Bing Chen and Prof. John Bonsell Passive Solar Research Group University of Nebraska-Lincoln Omaha campus and Richard
Buderus. Superior Equipment by Design. Comfortable. Efficient. Intelligent Heating. G315 G515 G615 Cast Iron Commercial Boilers.
[ Air ] [ Water ] [ Earth ] Buderus G315 G515 G615 [ Buderus ] Superior Equipment by Design High Efficiency Combustion Efficiencies Up To 88.2% Thermostream Design Eliminates Thermal Shock Flexible, Corrosion
FIELD TESTS OF FUEL EFFICIENCY MAGNETS J A CRABB JULY 1997 SWEEG REPORT 80
FIELD TESTS OF FUEL EFFICIENCY MAGNETS J A CRABB JULY 1997 SWEEG REPORT 80 List of symbols T f average temperature at the flow header, C T r average temperature at the return header, C f average water
Creating Efficient HVAC Systems
Creating Efficient HVAC Systems Heating and Cooling Fundamentals for Commercial Buildings Heating, ventilating, and air conditioning (HVAC) systems account for nearly half of the energy used in a typical
Ener.co & Viridian Energy & Env. Using Data Loggers to Improve Chilled Water Plant Efficiency. Randy Mead, C.E.M, CMVP
Ener.co & Viridian Energy & Env. Using Data Loggers to Improve Chilled Water Plant Efficiency Randy Mead, C.E.M, CMVP Introduction Chilled water plant efficiency refers to the total electrical energy it
HVAC Simplified Approach Option
HVAC Simplified Approach Option Part I Project Address: City: HVAC System Designer of Record: Date: Zip: Qualification The building is 2 stories or less in height and has a gross floor area is less than
Energy Efficiency and Automated Demand Response Program Integration: Time for a Paradigm Shift
Energy Efficiency and Automated Demand Response Program Integration: Time for a Paradigm Shift Christine Riker and Kitty Wang, Energy Solutions Fred Yoo, Pacific Gas and Electric Company ABSTRACT The practice
Operation manual. Daikin Altherma ground source heat pump EGSQH10S18AA9W. Operation manual Daikin Altherma ground source heat pump.
English Table of contents Table of contents 1 About this document 2 2 About the system 2 2.1 Components in a typical system layout... 2 3 Operation 3 3.1 Overview: Operation... 3 3.2 The user interface
Home Energy Efficiency and Conservation: Call to Action. July 23, 2015 Dave Blake and David Wood REEP Green Solutions
Home Energy Efficiency and Conservation: Call to Action July 23, 2015 Dave Blake and David Wood REEP Green Solutions Today s Agenda Background Understanding where you are: Energy Usage EnerGuide Home Energy
CHAPTER 9: WATER HEATING
Chapter 9: Water Heating 145 CHAPTER 9: WATER HEATING Energy costs for water heating can be as great as the costs for heating, for an energy efficient house, in a mild climate. Estimating hot water usage
Hybrid heat pumps. saving energy and reducing carbon emissions
Hybrid heat pumps saving energy and reducing carbon emissions Bart Aspeslagh Product planning and new technology manager, Daikin Europe NV. [email protected] Stefanie Debaets Design engineer,
Effects of Ultra-High Turndown in Hydronic Boilers By Sean Lobdell and Brian Huibregtse January 2014
Effects of Ultra-High Turndown in Hydronic Boilers By Sean Lobdell and Brian Huibregtse January 2014 Today, hydronic boilers are producing greater efficiencies than previously thought possible, all due
For installation guide see reverse of book
USERS GUIDE LOGIC Combi 24, 30, 35 For installation guide see reverse of book When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance
Differentiating Energy Modeling Software!
Differentiating Energy Modeling Software! What works, what doesn t, and when it matters! A Boulder Green Building Guild brownbag presentation by! Adam Stenftenagel! Principal! Sustainably Built! Heat Movement
HVAC Processes. Lecture 7
HVAC Processes Lecture 7 Targets of Lecture General understanding about HVAC systems: Typical HVAC processes Air handling units, fan coil units, exhaust fans Typical plumbing systems Transfer pumps, sump
CGC s Hybrid System Loop Control
verview The CGC Group Hybrid Heat Pump System does NT operate with the same fluid loop temperatures as a conventional reversing Water Source Heat Pump system. The CGC system differs from a WSHP system
Sample DTE Energy Rebate Programs Follow:
Sample DTE Energy Rebate Programs Follow: Refrigerator recycling (freezers, air conditioners & dehumidifiers too) Washing machines &programmable thermostats Forced air tune up Insulation and window replacement
The natural ombination
The natural ombination DAIKIN ALTHERMA HYBRID HEAT PUMP 2 A new pportunity in residential heating! There is a growing demand from home owners to replace heating systems, especially replacing of gas boilers,
RESIDENTIAL HEATING OIL SERVICE CONTRACT ANNUAL COST $276.00
RESIDENTIAL HEATING OIL SERVICE CONTRACT This service contract covers all routine service and maintenance of your residential oil fired furnace or boiler. In addition this contract covers all service calls
Rhode Island Residential Heating Program from National Grid
Rhode Island Rhode Island Residential Heating Program from National Grid Save money, improve comfort and ensure a cleaner environment with energy savings offers for residential customers. For Natural Gas
In the average American home, water heating accounts
WATER HEATING In the average American home, water heating accounts for about 20% of total household energy consumption. In Virginia, the average household spends between $200 and $500 per year for heating
Glossary of Heating, Ventilation and Air Conditioning Terms
Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment
International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS
International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES
Greenhouse Gas Implications of HVAC Upgrades in Multi-Unit Residential Buildings
Greenhouse Gas Implications of HVAC Upgrades in Multi-Unit Residential Buildings J A NUARY 2015 INTRODUCTION This Research Report explores best practices and approaches for reducing greenhouse gas (GHG)
Advanced Heating & Hot Water Systems. Ultra High Efficiency Energy Star Listed Condensing Boiler
Advanced Heating & Hot Water Systems A Trailblazing Energy Star Listed Boiler that Installs like a Mid-Efficiency Boiler with the Performance of a High-Efficiency Product Ultra High Efficiency Energy Star
The NEW Greenstar i. intuitive. innovative. improved performance. installation ease
The NEW Greenstar i innovative intuitive improved performance installation ease A NEW look, NEW features and a NEW NAME for the UK s best selling boiler, the Greenstar i Junior 1 Introducing the new Greenstar
Natural gas heating versus split system heating and the current and future viability of the Natural gas network
Natural gas heating versus split system heating and the current and future viability of the Natural gas network Discussion Paper: Energy Consumer Reference Council meeting 7. August 2015 While ActewAGL
EVALUATION OF GEOTHERMAL ENERGY AS HEAT SOURCE OF DISTRICT HEATING SYSTEMS IN TIANJIN, CHINA
EVALUATION OF GEOTHERMAL ENERGY AS HEAT SOURCE OF DISTRICT HEATING SYSTEMS IN TIANJIN, CHINA Jingyu Zhang, Xiaoti Jiang, Jun Zhou, and Jiangxiong Song Tianjin University, North China Municipal Engineering
Building Energy Management: Using Data as a Tool
Building Energy Management: Using Data as a Tool Issue Brief Melissa Donnelly Program Analyst, Institute for Building Efficiency, Johnson Controls October 2012 1 http://www.energystar. gov/index.cfm?c=comm_
QUESTIONS TO ASK WHEN REPLACING YOUR HVAC TOGETHERWESAVE.COM
QUESTIONS TO ASK WHEN REPLACING YOUR HVAC TOGETHERWESAVE.COM TOGETHERWESAVE.COM IS IT TIME TO REPLACE YOUR HVAC SYSTEM? If your heating and cooling system is 15 to 20 years old and is experiencing problems,
Daikin Altherma hybrid heat pump. The natural combination
Daikin Altherma hybrid heat pump The natural combination Daikin Altherma hybrid heat pump, the natural combination Why choose Daikin Altherma hybrid heat pump? What the customer wants: more energy efficient
The Potential for Energy Retrofits within the City of Sacramento s Rental Housing Inspection Program
PNNL-20343 Prepared for the U.S. Department of Energy under Contract DE-AC05-76RL01830 The Potential for Energy Retrofits within the City of Sacramento s Rental Housing Inspection Program MM Iverson S