SECTION K - HOT WATER SUPPLY REQUIREMENTS

Size: px
Start display at page:

Download "SECTION K - HOT WATER SUPPLY REQUIREMENTS"

Transcription

1 SECTION K - HOT WATER SUPPLY REQUIREMENTS REFERENCES (Chapter ).06 Sanitary Facilities and Controls. Amended. (1) Water (h) Capacity 2.06 Sanitary Facilities and Controls. Amended. (2) Plumbing (c) Hand Sink Installation..05 Equipment and Utensils. Amended. (6)Maintenance and Operation (j) Mechanical Warewashing 1& 2.05 Equipment and Utensils. Amended. (2)Design and Construction (bb) 1.05 Equipment and Utensils. Amended. (6) Maintenance and Operation (l) Mechanical Warewashing 1.05 Equipment and Utensils. Amended. (6) Maintenance and Operation (n) Manual & Mechanical Warewashing. I. Background: 1. Purpose: A. A critical factor in preventing foodborne illnesses in a food facility is the provision of an adequate supply of hot water for the washing of hands, utensils, equipment, and the facility itself. The installation of a properly sized water heater will ensure that a sufficient amount of hot water will be available at all times. B. The purpose of these guidelines is to provide a set of criteria that will assist architects, designers, contractors, establishment owners and food service permit applicants in the proper sizing of water heaters to adequately meet the anticipated hot water demands of food facilities in Georgia. Similarly, these guidelines are provided to aid the Health Authority or the County Environmental Health Specialist (EHS) during the plan review process to obtain reasonable assurance of the adequacy of the food establishment s water heating equipment capacity to meet the demand of the establishment. Food facilities with water heaters sized according to these criteria should be capable of complying with the requirements for providing an adequate hot water supply as required by the Georgia Food Service Rules and Regulations Chapter subsection (1) (h) General Requirements: A. All newly constructed or existing buildings being converted into a food service establishment shall be provided with a hot water supply dedicated to the food service operation sufficient to satisfy the continuous and peak hot water demands of the food establishment at all times the establishment is in operation. Hot water for hand washing shall be tempered water at a temperature between 100 F and 110 F (43 C) through a mixing valve or combination faucet. Depending upon the design of the machine, the temperature of wash solution in spray-type warewashers that use hot water to sanitize must be 150 F (66 c) to 165 F (74 c) for washing and Page K1 of K19

2 165 F (74 c) to 180 F (82 c), not to exceed 194 F (90 c), for sanitizing. The maximum sanitizing temperatures of 165 F (74 c) to 180 F (82 c), not to exceed 194 F (90 c) do not apply to high pressure and temperature systems with wandtype, hand-held, spraying devices used for in-place cleaning and sanitizing of equipment such as meat saws. The temperature of the wash solution in spray-type warewashers that use chemicals to sanitize shall not be less than 120 F (49 c). The water temperature for manual hot water sanitization must be at least 171 F (77 c). For the purposes of sizing hot water generating capability of the food service establishment, a supply temperature requirement of 140 F must be provided at each fixture and to the mechanical dishwashing machines. This is needed to enable warewashing machine booster heaters to operate satisfactory and to ensure adequate hot water for cleaning and sanitizing operations. Further, water heaters and their installation must be in compliance with all Federal, State and local building and plumbing code requirements and water heaters that use reclaimed heat from equipment to heat water must be evaluated on a case-by-case basis. II. Storage Tank Type Water Heaters: 1. Sizing Requirements for Storage Tank Water Heaters: A. For food facilities that utilize multi-service eating and drinking utensils, the water heater shall have the ability to provide hot water at a rate equal to or greater than 100% of the computed peak hourly hot water demand of the establishment, in gallons per hour (GPH). B. For food facilities that use only single-service eating and drinking utensils, or do not use utensils at all, the water heater shall have the ability to provide hot water at a rate equal to or greater than 80% of the computed hourly peak hot water demand of the establishment, in GPH. C. The hourly hot water demand for the food facility, in GPH, is based upon a twentyfour hour basis and it is calculated by adding together the estimated hot water demands for all sinks and other equipment, such as dishmachines, which utilize hot water. In the absence of specific hot water usage figures for equipment, as given within manufacturer s equipment specification sheets, Table K-1 and notes to Table K-1 shall be used to calculate peak hot water demand See Appendix J within PART- II of this Manual for Peal Hourly Hot Water Demand Calculation Worksheet. The hot water demands for automatic warewashers, such as dishmachines, glasswashers, and potwashers are found in NSF International listings or listings established by other nationally recognized testing laboratories. Page K2 of K19

3 TABLE K-1 PEAK HOURLY ESTABLISHMENT HOT WATER DEMAND Equipment Type Gallons Per Hour Quantity Gallons/hour/day Totals Vegetable sink X 15 = Single food prep sink X 20 = Double food prep sink X 40 = 3 - Compartment Pot sink X 60 = 4-Compartment Pot Sink X 80 = Pre-rinse for dishes-shower head type X 45 = Bar sink three-compartment X 25 = Chemical sanitizing glasswasher X 60 = Lavatory X 5 = Cook sink X 10 = Hot water filling faucet X 15 = Bain Marie X 10 = Coffee urn X 5 = Kettle stand X 5 = Garbage can washer X 50 = Janitor s sink X 15 = Utility or Curbed cleaning facility X 20 = Nine and twelve pound clothes washer X 45 = Sixteen pound clothes washer X 60 = **(Clothes washers See Note #2) Employee shower X 20 = **Warewashing machine (See note #1) X = **Hose Reels (See note #3) X = Other Equipment (See note #4) X = Peak Hourly Hot Water Demand = ( ) Page K3 of K19

4 Notes to Table K-1 Note #1: Hot water demand for warewashing machines shall be 100% as per ANSI/NSFI listings. Note #2: Clothes Washer Calculation: A. Limited Use/Clothes washer used one to two times per day; beginning or ending of day operation GPH = [60 (for16lb.) & 45 (for 9lb. to 12 lb.)] GPH x 25%. B. Intermediate Use/Clothes washer used three to four times per day; GPH = [60 (for16lb.) & 45 (for 9lb. to 12 lb.)] GPH x 45%. C. Heavy Use/Clothes washer used once every two hours; GPH = [60 (for16lb.) & 45 (for 9lb. to 12 lb.)] GPH x 80%. D. Continuous Use/Clothes washer used every hour; GPH = [60 (for16lb.) & 45 (for 9lb. to 12 lb.)] GPH x 100%. Note #3: Hose 20 GPH for first reel & 10 GPH for each additional reel. Note #4: Other equipment not listed in Table E-1 shall be as per the manufacturer s equipment specification sheets. D. The following examples are provided to explain how to calculate the total hourly hot water demand: (1). Food facility that utilizes only single service eating and drinking utensils: Assume: 1 X Three compartment 60 GPH = 60 GPH 2 X Hand 5 GPH each = 10 GPH (5 GPH each) 1 X Janitorial 15 GPH = 15 GPH Total hourly hot water demand = (85 GPH) (85 GPH) X 80% allowance for single-service utensils = (68 GPH) For the food facility in this example, a water heater would be required, which will have enough British Thermal Units (BTU) (if gas operated) or Kilowatts (KW) (if electrically operated) size rating to recover 68 Gallons per Hour (GPH). Page K4 of K19

5 (2). Food facility that utilizes multi-service eating and drinking utensils: Assume: 1 X Three-compartment 60 GPH = 60 GPH 1 X Warewashing dish 80 GPH = 80 GPH 1 X Hand spray 45 GPH = 45 GPH 1 X One-Compartment food prep sink (20 GPH) = 20 GPH 2 X Hand 5 GPH each = 10 GPH 1 X Janitorial 15 GPH = 15 GPH Total hourly hot water demand = (230 GPH) Since the food facility in this example uses multiservice eating and drinking utensils, 100% of the computed hourly hot water demand must be provided. Therefore, a water heater would be required that has the capability to recover 230 Gallons Per Day (GPH). E. The following are examples for determining the energy input (BTU for gas water heaters) and KW (kilowatts for electric water heaters): (1). Electric Water Heater Sizing: Given: The peak hot water demand for an establishment has been calculated to be 68 GPH. An electric water heater with a kilowatt (KW) input rating of 14 KW has been specified within the food service plans for review. We need to verify whether or not the proposed water heater is correctly sized. Formula: KW input = GPH X 100ºF Rise X 8.33 lb. per gallon of water Thermal Efficiency (See Note#1) X 3412 BTU s/ KW Note #1: The thermal efficiency for electric water heaters, unless otherwise listed by ANSI/NSFI will be assumed to be 98% or.98. Example: KW input = 68 X 100 X X 3412 = or (17 KW) In this example, you will need an electric water heater with a kilowatt rating of at least 17 KW. The foodservice plans for review did not specify such a water heater as calculated. Therefore, the heater would not be compatible with the demands of the establishment. A water heater with at least 3 KW (17 KW 14 KW = 3 KW) additional KW capacity will be needed to meet the establishment hot water peak demand. Page K5 of K19

6 (2). Gas Water Heater Sizing: Given: The peak hourly hot water demand for an establishment has been calculated to be 230 GPH. A gas water heater with a BTU input of rating of 218,802 BTU s has been specified within the food service plans for review. We need to verify whether or not the proposed water heater is correctly sized. Formula: BTU input = GPH X 100ºF Rise X 8.33 lb. per gallon of water Thermal Efficiency (See Note#2) Note #2: The thermal efficiency for gas water heaters, unless otherwise listed by ANSI/NSFI will be assumed to be 75% or.75. Example: BTU input = 230 X 100 X 8.33 = 255, or (255,453 BTU input).75 In this example, you will need a gas water heater with a BTU input energy rating of 255,453 BTUs. The foodservice plans for review did not specify the water heater as calculated; therefore, you cannot assume the heater would be compatible with the demand of the establishment. A water heater with at least 36,651 (255,453 BTU 218,802 BTU = 36,651 BTU) additional BTU capacity will be needed to meet the establishment s hot water peak demand. III. Requirements for Booster Heaters: 1. General Requirements: A. When a hot water sanitizing warewashing machine is used, a booster heater must be provided that will raise the incoming general-purpose hot water at a temperature of 140 Fahrenheit up to at least 180 Fahrenheit for the final sanitizing rinse cycle. Booster heaters shall be sized at a 40 Fahrenheit rise. Booster heaters may be incorporated within the design of the warewasher or be added as a separate unit at the warewashing machine. B. When sizing a booster heater, the hot water demand for the warewashing final sanitizing rinse cycle should be obtained from the NSF International listings or listings established by other nationally recognized testing laboratories. C. Use the following formulas when sizing warewashing machine booster heaters: (1). Electric Booster Heater Sizing: Page K6 of K19

7 Given: A hot water sanitizer warewashing machine with a final rinse hot water demand of 100 gallons per hour (GPH) is specified in plans for review. An electric booster heater with a kilowatt (KW) input rating of 10 KW has been specified within the food service plans for review. We need to verify whether or not the proposed booster heater is correctly sized. Formula: KW input = GPH X 40ºF Rise X 8.33 lb. per gallon of water Thermal Efficiency (Note#3) X 3412 BTU s/ KW Note#3 The thermal efficiency for electric booster heaters, unless otherwise listed by ANSI/NSFI will be assumed to be 98% or.98. Example: KW input = 100 X 40 X X 3412 = or 10 KW In this example you would need an electric booster heater with a kilowatt rating of 10 KW. The foodservice plans for review specified such a booster heater for the warewasher specified as calculated. You can now assume the booster heater would be compatible with the demand of the warewasher. 2. Gas Water Heater Sizing: Given: A hot water sanitizer warewashing machine with a final rinse hot water demand of 100 gallons per hour (GPH) is specified in plans for review. A gas booster heater with a BTU input rating of 10 KW has been specified within the food service plans for review. We need to verify whether or not the proposed booster heater is correctly sized. Formula: BTU input = GPH X 40ºF Rise X 8.33 lb. per gallon of water Thermal Efficiency (See Note#4) Note #4 The thermal efficiency for gas booster heaters, unless otherwise listed by ANSI/NSFI will be assumed to be 75% or.75. Example: BTU input = 100 X 40 X = 44, or 44,427 BTU input Page K7 of K19

8 In this example, you would need a gas booster heater with a BTU input energy rating of at least 44,427 BTU s. The foodservice plans for review specified such a booster heater for the warewasher specified as calculated. You can now assume the booster heater would be compatible with the demand of the warewasher. D. When a booster heater is installed below a drainboard, it shall be installed at least six inches above the floor and away from the wall, and in a manner that will allow accessibility for proper cleaning and servicing. IV. Installation Requirements: 1. Recirculation Pump: A. Where fixtures are located more than sixty feet from the water heater, it may become necessary to install a recirculation pump, in order to ensure that water reaches the fixture at required temperatures. Should it be shown by food service establishment planner to the satisfaction of the health authority that piping from water heaters can be effectively insulated to prevent significant heat loss before reaching fixtures, the requirement of a recirculation pump will not be necessary. 2. Water heaters shall be mounted in one of the following manners: A. On six-inch high, easily cleanable legs. B. On a four inch high coved curb base. All openings between the water heater and the base must be sealed in a watertight manner. C. On a properly finished and installed wall pedestal, positioned so that it is out of the work and traffic space. D. In an easily accessible location above a suspended ceiling. A permanently installed ladder will be required to access water heaters located above suspended ceilings; the ladder shall not be installed above food or utensil handling areas. Note: The Health Authority may allow alternate installation methods when a water heater is installed in an area separated from food and utensil handling areas, such as in a mechanical room. Local Building Codes should be consulted. 3. Common Mistakes Residential Water Heaters: Page K8 of K19

9 A. A common mistake with electric water heaters is the ordering and installing of a water heater with an upper element of 4500 watts, a bottom element of 4500 watts, and a total connected (or maximum) wattage of 4500 watts. On such a water heater only one element is operating at any one time. Many individuals do not observe the total connected wattage and assume that because each of the elements is 4500 watts their water heater has an input rating of 9000 watts. Water heater manufacturers have specific procedures for rewiring an electric water heater so that the upper and lower elements are operating simultaneously. Some manufacturers only permit rewiring in the factory. Field modifications will normally void warranties and any listings that the unit comes with. Prior to acceptance of a field modified water heater, the local health agency should ensure that the modifications were performed according to the manufacturer's recommendations and with the approval of the local building officials. The data plate on a field modified water heater must be changed to reflect the total connected wattage rating with both elements operating simultaneously. V. Instantaneous-Tankless-Water-Heaters: 1. Background: A. It is common for food service establishments to use appliances and equipment that utilize natural gas as a source of energy to operate. Equipment such as grills, deep fryers and water heaters commonly use gas to cook foods and to heat water. Over the recent years, the cost of natural gas and other energy resources coupled with rising food production cost has brought to bare an increase in the operational cost of most food service establishments. As a result, these establishments, existing and proposed, are searching to find ways to lower these costs so they can better compete in today s market. One of the ways food service establishments can cut operational cost is to utilize equipment and appliances that are energy efficient. B. Just like in the home, the cost of heating water is only second to that of operating air-conditioning. This pressure to reduce the cost of heating water within the home has created a need for innovation and as a result, industry has responded by developing a different kind of water heating appliance - one that only operates as result of demand, meaning it only heats water when it is requested to do so by the homeowner. And how does this new kind of water heating appliance reduce cost of heating water? The conventional water heater stores water in a tank and continuously consumes energy to maintain a set water temperature until the heated water is needed. The arrival of the instantaneous-tankless-water-heater only uses enough energy to heat water as it is needed; thereby, it utilizes far less energy than the traditional standard storage tank style water heater, providing the homeowner with substantial energy cost savings over time. It is this substantial energy cost savings that makes instantaneous-tankless-water-heaters attractive to current and prospective food service establishment operators and the industry has responded by manufacturing models for use in their establishments. Page K9 of K19

10 C. One of the advantages of an instantaneous-tankless-water-heater is its ability to provide a continuous supply of hot water. However, since the water passes through a heat exchanger, the water must flow through the unit slowly to assure proper heat transfer. Therefore, the quantity or rate at which the hot water is delivered can be significantly less than that provided by a storage-tank-style-water-heater. When hot water is utilized at several locations of the food facility at the same time, the flow of hot water to each fixture can be severely restricted. As a result and depending on the numbers and types of sinks and equipment utilizing hot water being present, more than one of these types of water heaters may be required to keep up with establishment demand for hot water. D. Instantaneous-tankless-water-heaters are designed to operate by injecting enough BTUs (British Thermal Units) into water as it flows by a heating coil or exchanger at a given rate. As such, their ability to meet demands placed on them for hot water depends on the design flow rates of equipment and fixtures utilizing hot water to operate properly. Therefore, it is imperative that instantaneous-tankless-waterheaters be sized to meet the peak hot water flow rate and volume demand of the hot water side of the potable water plumbing system of the proposed establishment. Once these systems have been designed to meet this stated peak demand in hot water, any future changes in equipment and fixtures, such as the act of removing aerators from faucets or the installation of a piece of equipment with a higher GPM rating by the establishment operator, will cause such systems to be undersized and a resulting inadequate hot water supply for the establishment. This occurrence of the lack of adequate hot water generation ability within the establishment will cause cleaning and sanitization problems for the establishment. To correct any under sizing effects due to an increase within the peak demand flow and volume rate of the hot water side of the establishment s potable water plumbing system, it may become necessary to increase the water heating system s design flow and volume rate to meet this new demand. The food service inspector must realize that it is the manufacturer of the food service equipment, such as warewasher and or fixtures that are installed on sinks, who determine the flow and volume rates for their equipment and fixtures. These manufacturer flow and volume rates are dependent upon the equipment and or fixture design and configuration as shipped from the manufacture and any changes made in the field could have an adverse effect on how the water heating system functions. Once an instantaneous-tankless-water-heater system has been properly designed by its manufacturer and or distributor and has been shown by the establishment s professional plans and specification preparer to meet the peak demand of the hot water side of the potable water system of the proposed food service establishment, close observation of changes made to fixtures and equipment is noted during inspections where such instantaneous-tanklesswater-heaters are installed. Page K10 of K19

11 2. General Sizing and Installation Requirements: A. If utilized instead of the traditional storage tank type water heaters and/or whether configured in single or combined units, instantaneous-tankless-water-heaters and associated distribution systems shall be sized appropriately. They shall be sized so as to be capable of generating a supply of hot water at a temperature of at least 140 Fahrenheit to all sinks, janitorial facilities, and other equipment and fixtures that use hot water, at all times. This hot water supply being generated must meet or exceed the peak hot water flow and volume rate demand, expressed as GPM (Gallons per Minute), throughout the food service establishment. Hot water at a temperature between 100 and 110 Fahrenheit shall be provided to each hand-washing lavatory through a mixing valve or combination faucet. Peak hot water flow and volume rate demand of the hot water side of the potable water plumbing system is defined as being equal to the combined total of the manufacturer s design flow and volume rate specification(s) for each piece of equipment and fixture at the potable water plumbing system s designed operating pressure in psi (pounds per square inch) utilizing hot water within the proposed establishment. B. When sizing instantaneous, tankless style water heater systems, special consideration must be given to certain fixtures, such as, pre-rinse nozzles at three compartment sinks and warewashers, mop sinks or hosebibbs, used for cleaning operations whereby hot water is used in flushing or rinsing operations. For such described fixtures, a minimum of 1 GPM will be used for each such fixture when calculating the peak demand flow and volume rate of the hot water side of the establishment s potable water plumbing system. Should more specific gallon per minute (GPM) flow and volume rate be listed within the manufacturer s specification documentation for fixtures and equipment that is greater than the minimum 1 GPM, then the greater figure will be used in sizing the water heating system. (Note: Hand lavatories and hand sinks must receive at least ½ GPM flow rate.) The following example is provided to explain how this sizing criterion is applied: (Example #1) Assume: 1 Three compartment Sink 2.0 GPM 2 Hand 0.5 GPM 1.0 GPM 1 Janitorial Sink 1.0 GPM 1 Vegetable Sink 2.0 GPM Total Peak Demand (6. 0 GPM) Page K11 of K19

12 In the Example #1, it is possible that one instantaneous-tankless-water-heater could be provided in order to supply a total peak flow and volume demand of not less than 6.0 GPM with a N-132 Model Unit. (Example #2) Assume: 1 Three compartment sink 2.0 GPM 5 Hand ½ GPM 2.5 GPM 1 Janitorial sink 1.0 GPM 1 vegetable sink 2.0 GPM 1 Warewasher (rated at 3.6 GPM) 3.6 GPM Total Peak Demand (11.1 GPM) In the Example #2, a bank of units consisting of two or more instantaneous-tanklesswater-heaters would have to be provided in order to supply a total peak flow and volume demand of not less than 11.1 GPM. C. To insure whether or not instantaneous-tankless-water-heater systems will meet hot water peak flow and volume demand throughout the food service establishment, food service plans for review must be provided with the water system manufacturer's specification sheets. These sheets must indicate the graphical performance curve(s) based on specific models, the degree rise (defined as 140 Fahrenheit water at equipment and fixtures) minus the degree Fahrenheit temperature of incoming water to the establishment at the coldest season of any year, as reported by the local water authority and gallons per minute flow rates. See Figure K-1 for an example of an instantaneous-tankless-water-heater performance flow chart. Further and in conjunction with the required graphical representation of model performance, a spreadsheet indicating numerical values for flow rates per model must be included within the instantaneous water heater specification documentation. (See Figure K-2 for an example). Page K12 of K19

13 FIGURE K Flow Chart FIGURE K-2 N-132M N-084 N-069M N-063S Flow Rate (GPM) gpm FIGURE K Temperature Rise (F) Page K13 of K19

14 FIGURE K-2 Temp Rinse N-132M N-084 N-069M N-063S Page K14 of K19

15 D. It should be noted that by examining the typical performance graph in Figure K-1 and the chart in Figure K-2, that each unit model of instantaneous-tankless-waterheaters tend to drop-off in hot water production (gallons per minute flow and volume rate) at various rates with each increase in degree rise variation. This dropoff in hot water production with each increase in degree rise variation per unit model is why you must know what the lowest temperature of incoming water to the unit or bank of units is at the coldest time of the year. Without this degree rise temperature determination, the water heating system cannot be correctly sized. It is strongly recommended that planers of these stated water-heating systems consult with the local water distribution authority servicing the location of the proposed food service establishment to document the incoming water temperature entering the establishment. In areas of Georgia where there is no water distribution system authority to consult with and or where an approved well is utilized as the establishment s potable water supply, it may become necessary to rely on published ground water data or actually measure incoming water temperature at the establishment. In these stated cases where wells are utilized for water supply to the proposed establishment, an engineer, an architect, a master plumber or well driller contractor, all licensed by the State of Georgia, will need to verify and document the incoming water temperature to the establishment and this documentation must be included within the food service plans and specifications upon submittal to the health authority for review. E. Food facilities that install an automatic warewashing machine that utilizes a large quantity of hot water may be required to provide an instantaneous-tankless-waterheater exclusively for the warewashing machine or incorporate a hot water recirculation system from the water heating system to the warewasher. instantaneous-tankless-water-heaters shall not be substituted for ware washing machine booster heaters for hot water sanitizing. ANSI/NSFI (American National Standards Institute/National Sanitation Foundation International) listings are used to determine the minimum GPM hot water demand for automatic warewashing machines - see Figure K-3 or while on the Internet, click onto for an example of such listings. Should these stated listings not be available for a particular make and model of warewashing machine or other equipment utilizing hot water, it shall be the responsibility of the food service plans preparer to provide the manufacturer s specification sheets giving the equipment design GPM flow rate operating requirements for hot water. Page K15 of K19

16 FIGURE K-3 HOBART CORPORATION WORLD HEADQUARTERS 701 SOUTH RIDGE AVENUE TROY, OH </TD< tr> Facility: DANVILLE, KY STATIONARY RACK DISHWASHING MACHINES Final Rinse (20 psi) Operating Time Model Rack Size Flow Usage (seconds) Footnotes Number Width gpm gph Wash Rinse Dwell Single Tank Chemical Sanitizing Door AM-14 20x [4] [5] [6] [7] AM-14 20x [4] [5] [6] AM-14C 20x [4] [5] [6] AM-14C 20x [4] [5] [6] [7] AM-14F 20x [4] [5] [6] AM-14F 20x [4] [5] [6] [7] AM-14T 20x [4] [5] [6] AM-14T 20x [4] [5] [6] [7] AM-14TC 20x [4] [5] [6] [7] AM-14TC 20x [4] [5] [6] LT-1 20x [4] [6] [4] Optional tabling and shelving fully complying with NSF Standard 2 may be provided. [5] Unit specified must have letter "L" following serial number on machine data plate. [6] Final rinse must contain 50 ppm minimum available chlorine. [7] Models with a shorter wash cycle (reduced 12 seconds) require a minimum wash temperature of 130 F. Page K16 of K19

17 3. Recirculation Pumps: A. The term cold water sandwich effect is a term that is used to describe the introduction of cold water into the hot water supply line during frequent on/off operation of an instantaneous-tankless-water-heater. The cold-water sandwich effect, when present, appears as a momentary drop in hot water temperature as it is discharged from a hot water supply outlet (i.e. restaurant hand lavatories, mop sinks, warewashing machines, etc.). This phenomenon is present in the operation of all instantaneous-tankless-water-heaters and it is a direct result of their operating principles used to heat water. B. The development of instantaneous-tankless-water-heaters required a departure from the common tank type storage water heater. Tank type water heaters heat a stored volume of water slowly over a long period of time (approximately 1 hour) and then maintain this stored water at a high temperature until used. It is the elimination of stored water from hot water systems that has resulted in the cold-water sandwich effect. C. For a better understanding of why a cold-water sandwich effect exists with instantaneous-tankless-water-heaters, the operating principles and safety mechanisms involved in their operation must be understood. The basic operation of all instantaneous-tankless-water-heaters as follows: (1.) Water flow sensor senses water flow through the heater. (2.) Burner ignition is initiated resulting in the production of hot water. (3.) Water flow and temperature is monitored and used to adjust the flow of gas to the burner, so that the outlet set point temperature is maintained. (4.) When water flow ceases, the water heater shuts off. To maintain a safe ignition sequence, steps (A) and (B) typically take up to 10 seconds. During this ignition sequence, a small amount of cold-water flows through the water heater. When hot water usage is stopped briefly and then started up again, this ignition sequence is repeated, and the small amount of cold water that passes through the water heater forms a cold water sandwich. It is this sequence of operations with these water-heating systems that cause a brief cold-water discharge at sinks and equipment until the unit has caught-up with the hot water demand at the point of discharge(s) from within the hot water side of the potable water plumbing system. It should be noted that the cold-water sandwich effect cannot be removed completely from instantaneous, tankless style water heater systems. The safety standards developed to insure the safe operation of water heaters require a delay in the ignition sequence of all gas Page K17 of K19

18 water heaters. In addition, electric type, instantaneous-tankless-water-heater systems too can experience this cold-water sandwich effect due to the time it takes the heating elements to be energized and reach heating temperatures. (5.) It is for the cold water sandwich affect that where fixtures are located more than sixty feet from the water heater, a recirculation pump with reserve tank may be considered as part of the instantaneous-tankless-water-heater system installation, in order to ensure that water reaches the fixture at a temperature of at least 140 F. This requirement is applicable to all applications, unless the instantaneous-tankless-water-heating system designer can satisfactorily incorporate other means within the system design to insure a constant flow of hot water at each hot water discharge point within the hot water side of the potable water plumbing system at the plumbing system s design operating pressure. On a case- by-case basis, it may be more practical to install a separate, water heater for high hot water flow demand equipment. In other cases, it may be more practical to install a separate, smaller instantaneoustankless-water-heater at remote fixtures, such as for restroom hand sinks. 4. Installation Requirements: A. The installation of instantaneous-tankless-water-heaters must follow the following guidelines: (1). instantaneous-tankless-water-heater systems are site fixture and specific in their design; therefore, they must be designed based on equipment and fixtures specified to be installed within the proposed or for those already installed within existing food service establishment. (2). Where feasible, instantaneous-tankless-water-heaters should be located in an area of the food facility separated from all food and utensil handling areas in such a way it will not impede routine cleaning of the establishment or harbor vermin. They must be installed in a location that facilitates the ease of access to the unit or units for servicing and monitoring. (3). Instantaneous-tankless-water-heaters must be installed according to any applicable codes or laws (Federal, State, Local, etc.). (4). Instantaneous-tankless-water-heaters must be designed and built according to standards set by American National Standards Institute (ANSI) accredited certification programs and others as per applicable plumbing or building codes or laws (Federal, State, Local) this will be determined by the water heating installation passing applicable building and or plumbing inspections. Page K18 of K19

19 (5). Instantaneous-tankless-water-heaters are properly sized when the total GPM of a single unit or the combined GPM of several units (bank of units) is equal to or exceeds the peak hot water flow and volume, expressed as GPM (Gallons per Minute), demand throughout the food service establishment at the designed operating pressure of the establishment s potable water plumbing system. (6). A Flow Meter shall be permanently installed adjacent to or incorporated within the designed instantaneous-tankless-water-heater unit or units so as to provide a means to monitor the flow rate in gallons per minute (GPM) within the food service establishment s hot water side of the potable water plumbing system. The flow meter must give a numerical readout of the flow of water as it passes through the instantaneous-tankless-water-heater. The flow meter must be durable and capable of maintaining its accuracy and of withstanding the design operational temperatures and design pressures of the hot water side of the potable water plumbing system. The purpose of this flow meter is to ensure the continued compatibility of the water heating system with the hot water peak demand flow and volume rate of the establishment. (7). In the event of the replacement of a tank type water heater; or during the planning of a new proposed food service establishment with an instantaneoustankless-water-heater system; or where no data is available for existing fixtures and equipment that uses hot water, the health authority may request a report from an engineer, architect or master plumber who is licensed to do work in the State of Georgia. Within this report, the licensed professional will list each fixture and piece of equipment utilizing hot water by common name, make and model along with its corresponding flow rates in gallons per minute. In addition, said report will give the total combined gallons per minute flow rate of listed fixtures and equipment utilizing hot water at the establishment s potable water system s designed operating pressure expressed as pounds per square inch (PSI). The report will be generated on the design professional s letterhead and it will bare the designer s name, title, date of report and his State of Georgia professional license number. Page K19 of K19

FOOD ESTABLISHMENT GUIDE FOR DESIGN, INSTALLATION, AND CONSTRUCTION RECOMMENDATIONS

FOOD ESTABLISHMENT GUIDE FOR DESIGN, INSTALLATION, AND CONSTRUCTION RECOMMENDATIONS FOOD ESTABLISHMENT GUIDE FOR DESIGN, INSTALLATION, AND CONSTRUCTION RECOMMENDATIONS PART 9 - HOT WATER SUPPLY REQUIREMENTS The hot water supply shall be sufficient to satisfy the continuous and peak hot

More information

WATER HEATER SIZING GUIDELINES FOR INITIAL INSTALLATION & REPLACEMENT

WATER HEATER SIZING GUIDELINES FOR INITIAL INSTALLATION & REPLACEMENT WATER HEATER SIZING GUIDELINES FOR INITIAL INSTALLATION & REPLACEMENT COUNTY OF SAN DIEGO DEPARTMENT OF ENVIRONMENTAL HEALTH PLAN CHECK AND CONSTRUCTION 5500 OVERLAND AVE. SAN DIEGO, CA 92123 P.O. BOX

More information

Environmental Services Department

Environmental Services Department Environmental Services Department Plan Review & Construction Program Guideline to Sizing Water Heaters, Water Temperature and Potable Water Supply Requirements Plan Review Today For Success Tomorrow! Environmental

More information

PLAN REVIEW AND APPROVAL FOR FOOD ESTABLISHMENTS PLUMBING REQUIREMENTS FOR FOOD ESTABLISHMENT PREMISES

PLAN REVIEW AND APPROVAL FOR FOOD ESTABLISHMENTS PLUMBING REQUIREMENTS FOR FOOD ESTABLISHMENT PREMISES PLAN REVIEW AND APPROVAL FOR FOOD ESTABLISHMENTS PLUMBING REQUIREMENTS FOR FOOD ESTABLISHMENT PREMISES Health Systems Protection Rev. 07/2006 35-05-20/06/07/18 OFFICE OF FOOD PROTECTION 417 FEDERAL ST

More information

TARRANT COUNTY PUBLIC HEALTH DEPARTMENT 817-321-4960 fax 817-321-4961 FOOD ESTABLISHMENT REVIEW APPLICATION

TARRANT COUNTY PUBLIC HEALTH DEPARTMENT 817-321-4960 fax 817-321-4961 FOOD ESTABLISHMENT REVIEW APPLICATION TARRANT COUNTY PUBLIC HEALTH DEPARTMENT 817-321-4960 fax 817-321-4961 FOOD ESTABLISHMENT REVIEW APPLICATION Date: NEW REMODEL Name of Establishment: Category: Restaurant Institution Daycare Retail Market

More information

Request for Retail Food Establishment License

Request for Retail Food Establishment License Request for Retail Food Establishment License Thank you for notifying Boulder County Public Health (BCPH) about your plans to begin operation or change ownership of a retail food establishment, catering

More information

SINKS / DISHMACHINES. Food Preparation Sink

SINKS / DISHMACHINES. Food Preparation Sink ENVIRONMENTAL HEALTH DIVISION 2120 Diamond Blvd., Suite 200 Concord, CA 94520 Phone: (925) 692-2500 Fax: (925) 692-2505 www.cchealth.org/eh/ SINKS / DISHMACHINES Food Preparation Sink A separate stainless

More information

Licensing Permitting A. Plans B. Permits

Licensing Permitting A. Plans B. Permits City & County of Denver Community Planning & Development Agency Building Inspection Division 201 W Colfax Ave. Dept. 205 Denver, CO 80202 Phone: 720.865.2832 (Don Peluso) Fax: 720.865.2880 www.denvergov.org

More information

Plumbing Code Sections For Commercial Food Facilities

Plumbing Code Sections For Commercial Food Facilities Plumbing Code Sections For Commercial Food Facilities SCOPE The following list of requirements summarizes the plumbing issues that are commonly addressed in commercial retail food facilities by health

More information

General Information on Starting a Restaurant Business in Alabama

General Information on Starting a Restaurant Business in Alabama General Information on Starting a Restaurant Business in Alabama This information is intended to give a general idea and overview of Health Department construction requirements for starting a retail food

More information

Food Service Establishment Plan Review Application

Food Service Establishment Plan Review Application ENVIRONMENTAL SERVICES Tel 919 856 7400 Fax 919 743 4772 Plan Review & Recreational Sanitation Section 336 Fayetteville St. P.O. Box 550 Raleigh, NC 27602 www.wakegov.com Food Service Establishment Plan

More information

Element D Services Plumbing

Element D Services Plumbing PART 1 - GENERAL 1.01 OVERVIEW A. This section addresses domestic cold, hot and hot water return distribution systems within and to five feet beyond building perimeter. PART 2 - DESIGN CRITERIA 2.01 GENERAL

More information

TANKLESS WATER HEATER INSTALLATION DIAGRAMS

TANKLESS WATER HEATER INSTALLATION DIAGRAMS TANKLESS WATER HEATER INSTALLATION DIAGRAMS Installation Diagrams Tankless Installation / Optional Return Small 10-15 Gallon Point-of-Use Water Single and Optional Return : One single, small capacity water

More information

Tankless Water Heater A Primer for Contractors, Installers, Builders and Homeowners

Tankless Water Heater A Primer for Contractors, Installers, Builders and Homeowners Tankless Water Heater A Primer for Contractors, Installers, Builders and Homeowners Your Questions Answered Common applications Benefits of performance How to select, size and install Efficient water heating

More information

Montgomery County Health Department Mobile Food Guidelines. Definitions

Montgomery County Health Department Mobile Food Guidelines. Definitions Montgomery County Health Department Mobile Food Guidelines Definitions Commissary A permitted food establishment to which a mobile unit returns on a daily basis for such tasks as discarding liquid and/or

More information

New or Remodeled Food Service Establishment Checklist**

New or Remodeled Food Service Establishment Checklist** ToTo Protect and Promote the Health and the Environment of the People of Kittitas County New or Remodeled Food Service Establishment Checklist** **Some items may not be required for limited food service

More information

CHAPTER 9: WATER HEATING

CHAPTER 9: WATER HEATING Chapter 9: Water Heating 145 CHAPTER 9: WATER HEATING Energy costs for water heating can be as great as the costs for heating, for an energy efficient house, in a mild climate. Estimating hot water usage

More information

Low risk includes facilities that sell or give away non potentially hazardous food in original manufacturer packaging and do not offer samples.

Low risk includes facilities that sell or give away non potentially hazardous food in original manufacturer packaging and do not offer samples. Planning, Building &Environmental Services 1195 Third Street, Suite 210 Napa, CA 94559 www.co.napa.ca.us Main: (707) 253-4471 Fax: (707) 253-4545 PERMIT APPLICATION AND REQUIREMENTS FOR FOOD VENDORS AT

More information

Georgia State Amendments to the International Plumbing Code

Georgia State Amendments to the International Plumbing Code Georgia State Amendments to the International Plumbing Code (2006 Edition) Georgia Department of Community Affairs Local Government Assistance Division 60 Executive Park South, N.E. Atlanta, Georgia 30329-2231

More information

What to Expect From the Examination. How to Study the Plumbing Codes

What to Expect From the Examination. How to Study the Plumbing Codes Texas State Board of Plumbing Examiners Plumbing Inspector Examination Review Course The following Examination Review Course is designed to assist an applicant in preparing for the Plumbing Inspector examination.

More information

Emergency Guideline for Food Facilities during Boil Water Advisory or Other Public Notices

Emergency Guideline for Food Facilities during Boil Water Advisory or Other Public Notices Emergency Guideline for Food Facilities during Boil Water Advisory or Other Public Notices Water supply warnings are generally required when water suppliers need to provide consumers with immediate and

More information

Home comfort: water heating

Home comfort: water heating Home comfort: water heating Water heating usage Hot water. It s one of those luxuries we give little thought to until we run out. This information is provided to help you get the most value and comfort

More information

Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,

Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715, 4658.4500 PLUMBING SYSTEMS; NEW CONSTRUCTION. Subpart 1. Installation. All plumbing systems must be installed and tested according to this chapter and chapter 4715, the Minnesota Plumbing Code. Subp. 2.

More information

One of the fundamental design elements that every

One of the fundamental design elements that every Preliminary Design Information Before starting the water system design, you must assemble a collection of information. This includes information from the owner, the local utility, and the architect. Things

More information

THE PEOPLE OF THE CITY OF LOS ANGELES DO ORDAIN AS FOLLOWS: Section 1. Article V of Chapter XII of the Los Angeles Municipal Code is added to read:

THE PEOPLE OF THE CITY OF LOS ANGELES DO ORDAIN AS FOLLOWS: Section 1. Article V of Chapter XII of the Los Angeles Municipal Code is added to read: ORDINANCE NO. 1,;...8_U_8_2_2_ An ordinance adding Article V to Chapter XII, and amending Section 94.103.1.2.9, of the Los Angeles Municipal Code establishing water efficiency requirements for new development

More information

The Truth about Tankless Water Heaters Courtesy of the Cooperative Research Network

The Truth about Tankless Water Heaters Courtesy of the Cooperative Research Network STA January 2010 CRN Consumer Product Review Word Count: 915 The Truth about Tankless Water Heaters Courtesy of the Cooperative Research Network Many homeowners have seen advertisements for tankless water

More information

EMERGENCY ACTION PLAN CONTAMINATED WATER SUPPLY (BIOLOGICAL)

EMERGENCY ACTION PLAN CONTAMINATED WATER SUPPLY (BIOLOGICAL) NEW HAMPSHIRE DEPARTMENT OF HEALTH AND HUMAN SERVICES DIVISION OF PUBLIC HEALTH SERVICES FOOD PROTECTION SECTION EMERGENCY ACTION PLAN CONTAMINATED WATER SUPPLY (BIOLOGICAL) For the purpose of this Emergency

More information

SOUTH CAROLINA. Downloaded January 2011

SOUTH CAROLINA. Downloaded January 2011 SOUTH CAROLINA Downloaded January 2011 1401. General (II) B. When meals are catered to a facility, such meals shall be obtained from a meal service establishment graded by the Department, pursuant to R.61

More information

Codes and High Performance Hot Water Systems. Gary Klein Affiliated International Management, LLC 916 549 7080 gary@aim4sustainability.

Codes and High Performance Hot Water Systems. Gary Klein Affiliated International Management, LLC 916 549 7080 gary@aim4sustainability. Codes and High Performance Hot Water Systems Gary Klein Affiliated International Management, LLC 916 549 7080 gary@aim4sustainability.com Annual Energy Use for Heating Water Natural Gas Gallons Per Day

More information

Florida s Cottage Food Industry and Beyond

Florida s Cottage Food Industry and Beyond Florida s Cottage Food Industry and Beyond The 2012 Educational Program Committee is pleased to share conference educational materials with you under the condition that they are used without alteration

More information

Plumbing Supply Piping Planning Tool Reducing Water Wasted Waiting for Hot

Plumbing Supply Piping Planning Tool Reducing Water Wasted Waiting for Hot Plumbing Supply Piping Planning Tool Reducing Water Wasted Waiting for Hot Craig Selover Selover Consulting craig@dotmc.us H:248 542-3010 C:248 917-1380 Floor Plan Floor Plan All Piping WaterSense,HERS,

More information

FOOD ESTABLISHMENT PERMIT APPLICATION FOR NEW, REMODEL OR CHANGE OF OWNERSHIP

FOOD ESTABLISHMENT PERMIT APPLICATION FOR NEW, REMODEL OR CHANGE OF OWNERSHIP Health & Community Services San Juan County P.O. Box 607 145 Rhone, Friday Harbor, WA 98250 Phone: (360) 378-4474 Fax: (360) 378-7036 FOOD ESTABLISHMENT PERMIT APPLICATION FOR NEW, REMODEL OR CHANGE OF

More information

SIZING OF WATER PIPING SYSTEM

SIZING OF WATER PIPING SYSTEM SIZING OF WATER PIPING SYSTEM SECTION E101 GENERAL E101.1 Scope. E101.1.1 This appendix outlines two procedures for sizing a water piping system (see Sections E103.3 and E201.1). The design procedures

More information

Energy Efficiency. Energy Efficient Water Heating: Purchasing a new electric water heater. Hot water use has a significant impact on your bill.

Energy Efficiency. Energy Efficient Water Heating: Purchasing a new electric water heater. Hot water use has a significant impact on your bill. Energy Efficiency Energy Efficient Water Heating: Purchasing a new electric water heater. Water heating accounts for about 18 percent of your home energy bill. Only space heating and cooling account for

More information

Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS

Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS Contents Page Ratings and Specifications..................... 2 Installation Requirements......................

More information

STARTING A FOOD BUSINESS GUIDE

STARTING A FOOD BUSINESS GUIDE STARTING A FOOD BUSINESS A HELPFUL GUIDE To assist those who are planning to open a food business in Columbus or Worthington Developed by the Food Protection Program at Columbus Public Health Updated April

More information

Important Information for Vendors at Temporary Events

Important Information for Vendors at Temporary Events Important Information for Vendors at Temporary Events As a food vendor, you are responsible for ensuring that your operation complies with the Colorado Retail Food Establishment Rules and Regulations.

More information

Chapter 8 Water and Sewage Systems

Chapter 8 Water and Sewage Systems Chapter 8 Water and Sewage Systems Proper sanitary controls pertaining to the water supply system and sewage and liquid waste disposal systems are necessary in all types of food establishments to prevent

More information

A Do-It-Yourself Home Water Audit

A Do-It-Yourself Home Water Audit A Do-It-Yourself Home Water Audit This page is left blank intentionally. Please use the double-sided printer setting when printing. Your new Home Water Savings Kit can help you conduct a do-it-yourself

More information

Introduction. Kitchens

Introduction. Kitchens Chapter 10 Water Fixtures and Conservation Introduction Responsible use of fresh water means WATER AT-A-GLANCE ensuring that all water-consuming fixtures Introduction in public areas are operating properly,

More information

ENERGY EFFICIENCY ENERGY EFFICIENCY: Saving Dollars While Clearing the Air

ENERGY EFFICIENCY ENERGY EFFICIENCY: Saving Dollars While Clearing the Air : Saving Dollars While Clearing the Air After labor and food, energy is the largest controllable cost in a restaurant s operation. And energy is a great place to start in becoming a green restaurant because

More information

Supporting Statement

Supporting Statement WaterSense High-Efficiency Bathroom Sink Faucet Specification WaterSense High-Efficiency Bathroom Sink Faucet Specification Supporting Statement I. Introduction The WaterSense Program is developing product

More information

APPENDIX A RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYSTEM

APPENDIX A RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYSTEM APPENDIX A RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYSTEM Because of the variable conditions encountered, it is impractical to lay down definite detailed rules of procedure for determining the sizes

More information

VENDOR APPLICATION FOR TEMPORARY FOOD EVENTS

VENDOR APPLICATION FOR TEMPORARY FOOD EVENTS VENDOR APPLICATION FOR TEMPORARY FOOD EVENTS All vendors must complete and submit to Event Coordinator for each event in the Tri-County area. If no menu and no equipment change are occurring from one event

More information

Energy Efficient Heating, Delivery and Use

Energy Efficient Heating, Delivery and Use Design Guide Improving Commercial Kitchen Hot Water System Performance Energy Efficient Heating, Delivery and Use The information presented is applicable to new construction and, in many instances, retrofit

More information

WaterSense or Energy Star. Tank type toilets: WaterSense = 1.28 gpf (4.8L) with at least 350 gram waste. 1.5 gpm maximum & 0.8 gpm minimum at 20 psi

WaterSense or Energy Star. Tank type toilets: WaterSense = 1.28 gpf (4.8L) with at least 350 gram waste. 1.5 gpm maximum & 0.8 gpm minimum at 20 psi National Efficiency Standards and s for and Water Using Toilets Lavatory (Bathroom) Faucets 2.2 gpm at 60 psi 2 Kitchen Faucets Showerheads Clothes Washers, Energy Independence and Security Act of 2007

More information

LAKE COUNTY ANIMAL SERVICES EXPANSION SECTION 15459

LAKE COUNTY ANIMAL SERVICES EXPANSION SECTION 15459 SECTION 15459 PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification sections, apply to work

More information

Plumbing Code in Commercial Kitchens. NH BOA May 9, 2012

Plumbing Code in Commercial Kitchens. NH BOA May 9, 2012 Plumbing Code in Commercial Kitchens NH BOA May 9, 2012 Main Topics Grease Interceptors Indirect Waste Receptors Cleaning Chemical Dispensers Thermal Expansion IPC - Chapter 10 Traps Interceptors Separators

More information

California Solar Initiative (CSI) Thermal Program Metering Installation Guide

California Solar Initiative (CSI) Thermal Program Metering Installation Guide California Solar Initiative (CSI) Thermal Program Metering Installation Guide Purpose: The purpose of this metering installation guide is to provide participating eligible contractors in the CSI-Thermal

More information

Domestic Hot Water Recirculation Systems Application, Selection & Installation Guide

Domestic Hot Water Recirculation Systems Application, Selection & Installation Guide Water Circulation Pumps & Circulators Domestic Hot Water Recirculation Systems Application, Selection & Installation Guide Taco Catalog # 100-41 Supersedes: 08/07/15 Effective Date: 09/01/15 Printed in

More information

FACILITIES DESIGN ASSESSMENT AND PERMITTING QUESTIONNAIRE: (For use by all food risk categories 1-3 or higher)

FACILITIES DESIGN ASSESSMENT AND PERMITTING QUESTIONNAIRE: (For use by all food risk categories 1-3 or higher) FACILITIES DESIGN ASSESSMENT AND PERMITTING QUESTIONNAIRE: (For use by all food risk categories 1-3 or higher) TO BE COMPLETED BY THE OWNER/OPERATOR AND SUBMITTED TO THE SNHD ENVIRONMENTAL HEALTH DIVISION

More information

Water Pressure Reducing Valves

Water Pressure Reducing Valves F-23QA 23 Questions and Answers about Water Pressure Reducing Valves $ HOW THEY Save WATER Save ENERGY Save WASTEWATER Save MAINTENANCE Save MONEY ENERGY WATER Conserve Both Automatically with Water Pressure

More information

COMMERCIAL ELECTRIC WATER HEATER INSTALLATION & OPERATING INSTRUCTION MANUAL

COMMERCIAL ELECTRIC WATER HEATER INSTALLATION & OPERATING INSTRUCTION MANUAL COMMERCIAL ELECTRIC WATER HEATER La A version Spanish espanola language de version estas of instrucciones these instructions se puede is available obtener al by escribirle contacting a la the fábrica company

More information

How To Fix A Leaky Water Heater

How To Fix A Leaky Water Heater Preventing water damage caused by plumbing fixtures Thousands of home insurance claims are filed every year. Some losses are major, others aren t, but they re always inconvenient and usually avoidable!

More information

Hot Water Plumbing Systems

Hot Water Plumbing Systems PDHonline Course M151 (3 PDH) Hot Water Plumbing Systems Instructor: A. Bhatia, B.E. 2012 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone & Fax: 703-988-0088 www.pdhonline.org

More information

PLUMBING CODE REQUIREMENTS AND SIZING GUIDE FOR RESIDENTIAL WATER SOFTENERS. Second Edition. Prepared by

PLUMBING CODE REQUIREMENTS AND SIZING GUIDE FOR RESIDENTIAL WATER SOFTENERS. Second Edition. Prepared by PLUMBING CODE REQUIREMENTS AND SIZING GUIDE FOR RESIDENTIAL WATER SOFTENERS Second Edition Prepared by NAHB Research Center, Inc. 400 Prince Georges Boulevard Upper Marlboro, MD 20774-8731 DISCLAIMER This

More information

Water Heater Sizing TS 100 2 2 Saturday 2:15pm 5:15pm J. Joe Scott CPD, FASPE, LEED

Water Heater Sizing TS 100 2 2 Saturday 2:15pm 5:15pm J. Joe Scott CPD, FASPE, LEED Water Heater Sizing TS 100 2 2 Saturday 2:15pm 5:15pm J. Joe Scott CPD, FASPE, LEED Water Heater Sizing (to keep you out of hot water) What is a water heater? An immersion element in a bucket works, but

More information

This presentation premiered at WaterSmart Innovations. watersmartinnovations.com

This presentation premiered at WaterSmart Innovations. watersmartinnovations.com This presentation premiered at WaterSmart Innovations watersmartinnovations.com Green Plumbing and Mechanical Code Supplement David Viola IAPMO Director of Special Services 1 IAPMO Group Association of

More information

WATER. Water Management Protect your building from water damage. Intent. Information & Tips

WATER. Water Management Protect your building from water damage. Intent. Information & Tips Water Management Protect your building from water damage If not managed properly, rain can drain into unwanted areas damaging your roof, windows, walls and facade. Eliminate water damage to your property

More information

INSTALLATION INSTRUCTIONS & HOME OWNERS MANUAL ECO 18 ECO 24 ECO 27 IMPORTANT SAFETY INFORMATION

INSTALLATION INSTRUCTIONS & HOME OWNERS MANUAL ECO 18 ECO 24 ECO 27 IMPORTANT SAFETY INFORMATION INSTALLATION INSTRUCTIONS & HOME OWNERS MANUAL ECO 18 ECO 24 ECO 27 IMPORTANT SAFETY INFORMATION As when installing or using any high voltage electrical appliance, basic safety precautions should always

More information

MA Department of Public Health

MA Department of Public Health Emergency Guideline for Food Establishments During Boil Water Order What food establishments are affected? As of 5/1/10, all food establishments including restaurants, supermarkets, caterers, food service

More information

FOG PRETREATMENT INFORMATION. New London Public Utilities F.O.G. Program 120 Broad Street New London, CT 06320

FOG PRETREATMENT INFORMATION. New London Public Utilities F.O.G. Program 120 Broad Street New London, CT 06320 FOG PRETREATMENT INFORMATION 1 New London Public Utilities F.O.G. Program 120 Broad Street New London, CT 06320 Kathryn Willis Program Coordinator Phone: 860-447-5222 Introduction This information package

More information

15430 SAFETY SHOWERS AND EYEWASHES

15430 SAFETY SHOWERS AND EYEWASHES 15430 SAFETY SHOWERS AND EYEWASHES PART 1: GENERAL 1.01 RELATED SECTIONS 01005 - ENVIRONMENTAL HEALTH 11600 LABORATORY EQUIPMENT 15020 - LABORATORIES 15130 - PIPING SPECIALITES 15400 - PLUMBING 15420 -

More information

B. Shop Drawings: Diagram power, signal, and control wiring.

B. Shop Drawings: Diagram power, signal, and control wiring. SECTION 224500 - PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Emergency showers. 2. Eyewash equipment. 3. Eye/face wash equipment. 4. Combination units. 5. Water-tempering equipment. 1.2 SUBMITTALS

More information

C I T Y O F S E L M A F I R E D E P A R T M E N T

C I T Y O F S E L M A F I R E D E P A R T M E N T C I T Y O F S E L M A F I R E D E P A R T M E N T Informational Bulletin Regarding Residential Fire Sprinkler Systems for One and Two Family Homes: Frequently Asked Questions ADMINISTRATIVE PROVISIONS:

More information

Emergency Showers and Eyewashes Mike Adkins Wednesday, October 31, 10:00-11:1511:15 a.m.

Emergency Showers and Eyewashes Mike Adkins Wednesday, October 31, 10:00-11:1511:15 a.m. Emergency Showers and Eyewashes Mike Adkins Wednesday, October 31, 10:00-11:1511:15 a.m. Safety First! How to Specify Emergency Showers and Eyewashes Presented by Mike Adkins, Guardian Equipment. ASPE

More information

Laundry Hot Water Systems

Laundry Hot Water Systems TECHNICAL BULLETIN HE-2020 Laundry Hot Water Systems Commercial/Institutional Applications using Helitherm Heat Exchangers AERCO INTERNATIONAL, INC. 159 PARIS AVE., NORTHVALE, NJ 07647 (201) 768-2400 FAX

More information

New Home Plumbing Goes Green How to create a water and energy efficient home.

New Home Plumbing Goes Green How to create a water and energy efficient home. New Home Plumbing Goes Green How to create a water and energy efficient home. Today we will cover Water Conservation vs Efficiency Hot Water System Options Selecting the Best Green Toilet High Efficiency

More information

HEAVY DUTY STORAGE GAS

HEAVY DUTY STORAGE GAS Multi-Fin flue technology Flue damper saves energy Electronic controls HEAVY DUTY STORAGE GAS Dependability The Rheem heavy duty gas range is the work horse of the industry having proved itself over many

More information

Permit Application for Mobile Food Truck

Permit Application for Mobile Food Truck Date Received / / Office Use Only By: Date Approved / / By: Comp # Element Type: Entered By: Annual Permit Fee: Check #: Receipt #: AMANDA #: Permit Application for Mobile Food Truck NOTE: This application

More information

Plumbing Installations. A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling

Plumbing Installations. A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling Plumbing Installations A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling February 2001 contents General Information 3 Inspection 4 New Drain and Vent Installations

More information

High Performance Hot Water Systems Denver July 2010

High Performance Hot Water Systems Denver July 2010 High Performance Hot Water Systems Denver July 2010 Gary Klein Affiliated International Management, LLC 916-549-7080 gary@aim4sustainability.com Gary Klein, 2010 Gaps Hot water is a system We need systemic

More information

A. Accessible Fixture: Emergency plumbing fixture that can be approached, entered, and used by people with disabilities.

A. Accessible Fixture: Emergency plumbing fixture that can be approached, entered, and used by people with disabilities. SECTION 224500 - EMERGENCY PLUMBING FIXTURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Boil Water Advisory. For Commercial/Public Facilities. Boil Water Advisory Factsheet #3

Boil Water Advisory. For Commercial/Public Facilities. Boil Water Advisory Factsheet #3 Boil Water Advisory Factsheet #3 Boil Water Advisory For Commercial/Public Facilities How to operate a commercial/ public facility under a boil water advisory Boil water advisories are issued when a municipal,

More information

Design Requirements for Eyewash and Safety Shower Units APPLICATION: Detailed Installation, Operation and Design. Eyewash Stations.

Design Requirements for Eyewash and Safety Shower Units APPLICATION: Detailed Installation, Operation and Design. Eyewash Stations. APPLICATION: Eyewash Stations must be provided in the following areas. Laboratories Plumbed emergency eyewash equipment shall be installed in every lab or room, where an MSDS for the materials used specifies

More information

8 plumbing. plumbing. 2010 PulteGroup, Inc. All Rights Reserved.

8 plumbing. plumbing. 2010 PulteGroup, Inc. All Rights Reserved. 8 90 2010 PulteGroup, Inc. All Rights Reserved. drains All the water you use leaves the home through a drain. Maintaining drains prevents clogging, overflows, water damage, and other problems. care and

More information

I N S T ALLATION INSTRUCTIONS & HOME OWNERS MANUAL IMPORTANT SAFETY INFORMATION

I N S T ALLATION INSTRUCTIONS & HOME OWNERS MANUAL IMPORTANT SAFETY INFORMATION I N S T ALLATION INSTRUCTIONS & HOME OWNERS MANUAL MODELS: HA018240 HA024240 HA027240 HA036240 IMPORTANT SAFETY INFORMATION As when installing or using any high voltage electrical appliance, basic safety

More information

Saving Water and Energy in Residential Hot Water Distribution Systems. Gary Klein California Energy Commission

Saving Water and Energy in Residential Hot Water Distribution Systems. Gary Klein California Energy Commission Saving Water and Energy in Residential Hot Water Distribution Systems Gary Klein California Energy Commission What Do You Want from your Hot Water System? Safety Not too hot Not too cold No harmful bacteria

More information

Case Studies in Restaurant Water Heating

Case Studies in Restaurant Water Heating Case Studies in Restaurant Water Heating Donald Fisher, Fisher-Nickel, Inc. William Pietrucha, Pacific Gas and Electric Company ABSTRACT This paper presents an overview of hot water use and the associated

More information

Residential Plumbing BCN 1058

Residential Plumbing BCN 1058 Residential Plumbing BCN 1058 CHAPTER 7 Plumbing Fixtures and Sizing the Drain, Waste, and Vent System MICHAEL KNOTEK 74 Plumbing Fixtures and Sizing the Drain, Waste, and Vent System PLUMBING FIXTURES

More information

2010 Residential Water Heater Replacement Check List

2010 Residential Water Heater Replacement Check List 2010 Residential Water Heater Replacement Check List The intent of this check list is to provide installers a general reference for the enforcement of code requirements in the Greater San Diego Area. This

More information

Energy Efficiency Business Rebates Natural Gas Catalog

Energy Efficiency Business Rebates Natural Gas Catalog Energy Efficiency Business Rebates Natural Gas Catalog RECENT NATURAL GAS CHANGES A new table has been added to the process boiler section. Please review to ensure your product meets all efficiency requirements.

More information

PLUMBING & CROSS-CONNECTION CONTROL

PLUMBING & CROSS-CONNECTION CONTROL PLUMBING & CROSS-CONNECTION CONTROL. MODULE 4 VII. Typical Retail Food Service Cross-Connections VIII. Air Gaps and Air Breaks for Drains and Waste IX. Grease Interceptors VII. TYPICAL RETAIL FOOD SERVICE

More information

Brian Coppock, Regional Compliance Officer. Office of Statewide Health Planning and Development Facilities Development Division

Brian Coppock, Regional Compliance Officer. Office of Statewide Health Planning and Development Facilities Development Division Brian Coppock, Regional Compliance Officer Office of Statewide Health Planning and Development Facilities Development Division CHAPTER 6 WATER SUPPLY AND DISTRIBUTION 601.0 Hot and Cold Water Required.

More information

Backflow Bulletin #1

Backflow Bulletin #1 Backflow Bulletin #1 FIRE PROTECTION SYSTEMS Chemicals in the System Anti-Freeze, Foam, Corrosion Inhibitors, etc. Chemicals in the System Glycerin Glycerin or similar food-grade non-toxic additive Siamese

More information

TABLE 1. Rugged cast aluminum alloy casing,celcon waterways with nichrome parts White (unless stainless steel housing)

TABLE 1. Rugged cast aluminum alloy casing,celcon waterways with nichrome parts White (unless stainless steel housing) CHRONOMITE INSTANT-FLOW MICRO WATER HEATER INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected) TABLE 1 Model No.

More information

Cost Estimation for Materials and Installation of Hot Water Piping Insulation

Cost Estimation for Materials and Installation of Hot Water Piping Insulation Cost Estimation for Materials and Installation of Hot Water Piping Insulation Prepared for Pacific Northwest National Laboratory Under Contract Number: 18O9O2 By Gary Klein, Managing Partner Affiliated

More information

FOOD ESTABLISHMENT REQUIREMENTS

FOOD ESTABLISHMENT REQUIREMENTS FOOD ESTABLISHMENT REQUIREMENTS 1. Three-compartment sink with dual drainboards A sink with at least three compartments shall be provided for manually washing, rinsing and sanitizing equipment. And shall

More information

Plumbing. Helpful Hints Residential Construction. Lincoln County. Bert Polk Plumbing Inspector

Plumbing. Helpful Hints Residential Construction. Lincoln County. Bert Polk Plumbing Inspector Plumbing Helpful Hints Residential Construction Bert Polk Plumbing Inspector Lincoln County 2015 Waste and vent fittings Vent 90 medium 90 long 90 1/16 bend,1/8 bend,1/6 bend, medium 90 san tee combination

More information

Sanitizing the Kitchen

Sanitizing the Kitchen Sanitizing the Kitchen Lesson 11 Overview Sanitizing the Kitchen Time 30 minutes Purpose To explain how to properly clean and sanitize the kitchen Objectives At the conclusion of this lesson, employees

More information

WINTERIZING YOUR HOME PLUMBING AT BLUE RIDGE SHORES

WINTERIZING YOUR HOME PLUMBING AT BLUE RIDGE SHORES WINTERIZING YOUR HOME PLUMBING AT BLUE RIDGE SHORES The following are suggestions to help you winterize your home plumbing. They are for homes where the heat is not left on during the winter months. There

More information

City of Riverside Building & Safety Division Residential Electric Vehicle (EV) Charger Guidelines

City of Riverside Building & Safety Division Residential Electric Vehicle (EV) Charger Guidelines Western Riverside County Code Uniformity Program City of Riverside Building & Safety Division Residential Electric Vehicle (EV) Charger Guidelines PHONE (951) 826-5697 3900 Main Street, Riverside, CA 92522

More information

Energy-Saving Tips. Energy Saving Tips

Energy-Saving Tips. Energy Saving Tips Energy-Saving Tips Energy Saving Tips TABLE OF CONTENTS How Do You Spend Your Energy Dollars?.. 1 Easy Ways to Save... 2 Investing in Energy Savings... 6 EarthCents... 7 How Do You Spend Your Energy Dollars?

More information

Why Water-Saving Matters. Low-Cost Water Savers

Why Water-Saving Matters. Low-Cost Water Savers The cost of a gallon of water is rising faster than the inflation rate. That means that your restaurant s water bill is going to take a bigger bite of your restaurant s budget each year. The way to keep

More information

Food Protection Program 2 North Meridian Street Indianapolis, IN 46204 http://www.in.gov/isdh/regsvcs/foodprot/index.htm.

Food Protection Program 2 North Meridian Street Indianapolis, IN 46204 http://www.in.gov/isdh/regsvcs/foodprot/index.htm. Food Protection Program 2 North Meridian Street Indianapolis, IN 46204 http://www.in.gov/isdh/regsvcs/foodprot/index.htm Sewage Backup For the purpose of this Emergency Action Plan (EAP), a sewage backup

More information

PLBG/GAS SAFETY Information Bulletin

PLBG/GAS SAFETY Information Bulletin PLBG/GAS SAFETY Information Bulletin November 2012 P/G-08-02-PLBG/GAS [Rev 3] Page 1 of 11 SUBJECT: REQUIREMENTS FOR COMBINATION HEATING SYSTEMS: DUAL PURPOSE WATER (POTABLE) HEATER (COMBO UNIT) Safety

More information

Food Service Operation/Retail Food Establishment Plan Review Application

Food Service Operation/Retail Food Establishment Plan Review Application CHRISTOPHER S. SMITH, RS, MA HEALTH COMMISSIONER DAVID BEYERS, MD MEDICAL DIRECTOR CITY OF PORTSMOUTH HEALTH DEPARTMENT 605 WASHINGTON STREET PORTSMOUTH, OH 45662 BOARD MEMBERS JIM KALB, PRESIDENT TIMOTHY

More information

PLAN CHECK CORRECTION SHEET FOR PLUMBING SYSTEMS 2014 LAPC

PLAN CHECK CORRECTION SHEET FOR PLUMBING SYSTEMS 2014 LAPC PLAN CHECK CORRECTION SHEET FOR PLUMBING SYSTEMS 2014 LAPC This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly. Section:

More information

CHAPTER 2: The Plumbing System

CHAPTER 2: The Plumbing System CHAPTER 2: The Plumbing System SECTION I: SIZING REQUIREMENTS Establish building dimensions Building height can be determined either by architectural drawings or # of floors times height/floor. (ex: 1

More information

RECON WATER HEATER INSTALLATION FORM

RECON WATER HEATER INSTALLATION FORM RECON WATER HEATER INSTALLATION FORM Please complete ONE (1) form for each SITE and return to AERCO for warranty validation within 30 days of start-up. After completion, e-mail this form to: STARTUP@AERCO.COM.

More information