deltapilot S Electronic Insert FEB 24 (P) with PROFIBUS-PA Protocol
|
|
|
- Brianne Cobb
- 10 years ago
- Views:
Transcription
1 BA 164F/00/en/09.97a Software Version deltapilot S Electronic Insert FEB 24 (P) with PROFIBUS-PA Protocol Operating Instructions Endress +Hauser The Power of Know How
2 Short Instructions Deltapilot S PA Short Instructions + V H V H Local operation Deltapilot S with display Remote operation via Commuwin II* of Deltapilot S with/ without display Matrix operation: Chapter 3 Level or pressure? Pressure Level Chapter 4.1 Calibration with empty and full tank Chapter 4.2 Dry calibration Chapter 5 Pressure and pmeasurement no Signal and display in technical units? yes % horizontal table Linearisation Chapter 4.3 Chapter 4.4/4.5/4.6 Other settings, locking and measured value display Endress+Hauser
3 Deltapilot S PA Table of Contents Table of Contents Software History Notes on Safety Introduction Measuring system Installation Installation hints Connection Device parameter file/type file Operation Operating and display module FHB Remote operation with Commuwin II Data acquisition via PLC Level Measurement Empty/full calibration Dry calibration Linearisation Other settings Locking/unlocking the matrix Measuring point information Pressure and Differential Pressure Trouble-Shooting Simulation Reset to factory settings Exchange of the electronic insert or measuring cell Repairs PROFIBUS-PA Parameters Technical Data Operating Matrix Index
4 Software History Deltapilot S PA Software History Software Change Significance 1.0 Original software DPV1 2
5 Deltapilot S PA Notes on Safety Notes on Safety The hydrostatic pressure sensor Deltapilot S with electronic insert FEB 24 (P) is a PROFIBUS PA device which is used for continuous level measurement. It can also be used to measure pressure and differential pressure (by using a PLC and second sensor). The Deltapilot S has been designed to operate safely in accordance with current technical, safety and EU standards. If installed incorrectly or used for applications for which it is not intended, however, it is possible that application-related dangers may arise, e.g. product overflow due to incorrect installation or calibration. For this reason, the instrument must be installed, connected, operated and maintained according to the instructions in this manual: personnel must be authorised and suitably qualified. The manual must have been read and understood, and the instructions followed. Modifications and repairs to the device are permissible only when they are expressly approved in the manual. If the device is to be installed in an explosion hazardous area, then the specifications in the certificate as well as all national and local regulations must be observed. The instrument can be delivered with the certificates listed in the table below. The certificate can be identified from the first letter of the order code stamped on the nameplate. Ensure that all personnel are suitably qualified Observe the specifications in the certificate as well as national and local regulations. Take special care with regard to the grounding of the bus cable screening. Recommendations are to be found in IEC Approved usage Installation, commissioning, operation Explosion hazardous areas ENDRESS+HAUSER DELTAPILOT S DB 5x Order No. DB 5x x Code Certificate Explosion protection A Standard none C PTB EEx ia IIC T6, Zone 0 FRG G PTB EEx ia IIC T6 Tabelle S.1 Certificates for applications in explosion hazardous areas Endress+Hauser 3
6 Notes on Safety Deltapilot S PA Safety Conventions and Symbols In order to highlight safety-relevant or alternative operating procedures in the manual, the following conventions have been used, each indicated by a corresponding icon in the margin. Safety conventions Symbol Note! Meaning Note! A note highlights actions or procedures which, if not performed correctly, may indirectly affect operation or may lead to an instrument response which is not planned Caution! Caution! Caution highlights actions or procedures which, if not performed correctly, may lead to personal injury or incorrect functioning of the instrument Warning! Warning! A warning highlights actions or procedures which, if not performed correctly, will lead to personal injury, a safety hazard or destruction of the instrument Explosion protection Device certified for use in explosion hazardous area If the device has this symbol embossed on its name plate it can be installed in an explosion hazardous area Explosion hazardous area Symbol used in drawings to indicate explosion hazardous areas. Devices located in and wiring entering areas with the designation explosion hazardous areas must conform with the stated type of protection Safe area (non-explosion hazardous area) Symbol used in drawings to indicate, if necessary, non-explosion hazardous areas. Devices located in safe areas stiill require a certificate if their outputs run into explosion hazardous areas. Electrical symbols Direct voltage A terminal to which or from which a direct current or voltage may be applied or supplied Alternating voltage A terminal to which or from which an alternating (sine-wave) current or voltage may be applied or supplied Grounded terminal A grounded terminal, which as far as the operator is concerned, is already grounded by means of an earth grounding system Protective grounding (earth) terminal A terminal which must be connected to earth ground prior to making any other connection to the equipment Equipotential connection (earth bonding) A connection made to the plant grounding system which may be of type e.g. neutral star or equipotential line according to national or company practice 4 Endress+Hauser
7 Deltapilot S PA 1 Introduction 1 Introduction The electronic insert FEB 24 (P) serves as transmitter for the hydrostatic pressure sensors Deltapilot S DB 50, DB 50 L, DB 51, DB 52 and DB 53. Deltapilot S sensors are used for continuous level measurement of liquids and pastes. They find application in the chemical, pharmaceutical and food industries as well as in fresh and wastewater treatment plants. Application Compact version DB 50 Version with rope extension DB 52 Version for water and wastewater industries DB 53 Version with rod extension BA164Y03 Version for food and pharmaceutical industries DB 50 L Fig. 1.1 Deltapilot pressure sensor versions The level of a column of liquid of known density ρ can be determined by measuring its hydrostatic pressure with a suitable sensor. Operating principle p atm p atm h pgas h = p hydr /ρ g The pressure sensor Delltapilot S converts the pressure acting upon its process diaphragm into an electrical signal. The electronic insert takes this signal and outputs it as a direct digital signal. BA164Y04 p hydr p atm h p hydr For level measurement in a pressurised vessel or differential pressure measurement, the head pressure must be measured with a second sensor. The hydrostatic pressure is then corrected by the connected programmable logic controller. Fig. 1.2 Principle of hydrostatic level measurement Endress+Hauser 5
8 1 Introduction Deltapilot S PA 1.1 Measuring system In the simplest case, the complete measuring system comprises a Deltapilot S with electronic insert FEB 24 (P), a bus coupler, a PLC or personal computer with the operating program Commuwin II as well as a PROFIBUS PA terminating resistor. The maximum number of transmitters on a bus segment is determined by their current consumption, the power of the bus coupler and the required bus length, see TI 260F/00/en. Normally, however: 10 Deltapilot S for EEx ia applications max. 32 Deltapilot S for non-hazardous applications can be operated on a bus segment. personal computer with operating program, e.g. Commuwin II PLC PROFIBUS DP tanks with Deltapilot S pressure sensors ENDRESS + HAUSER segment coupler Fig. 1.3 Deltapilot S measuring system with PROFIBUS PA protocol BA164Y05 fieldbus with PROFIBUS PA 6 Endress+Hauser
9 Deltapilot S PA 2 Installation 2 Installation This chapter describes: the mechanical installation of the Deltapilot S sensor the connection of the electronic insert the setting of the device address the installation of the device parameter file in the PLC 2.1 Installation hints BA164Y09 BA164Y10 Compact version The DB 50 must always be installed beneath the lowest point of measurement. It should not be installed in the filling curtain, the tank outlet or at a position in the tank which is affected by pressure pulses from a stirrer. Calibration and function testing are more easily carried out when the DB 50 is mounted downstream of a cut-off valve. Rod and rope version The rope version should be mounted at a point which is as free as possible from currents and turbulence. In order to protect the sensor from knocks due to lateral movement, it can be mounted in a stilling well (preferrably plastic) or braced from the cross-anchor provided. The zero point of the level measurement determines the length of the support cable orsensor rod. The tip of the probe should be at least 5 cm (2") below this level. When installed in a domed manhole, the sensor should be mounted in a nozzle to prevent the housing from being flooded by moisture or condensation. Location BA164Y11 The process diaphragm is not to be handled or cleaned with hard or pointed objects. Measurement is not affected by build-up, provided that it remains elastic and transmits the hydrostatic pressure. All rope and rod versions of the Deltapilot S are supplied with a plastic cap which protects the process diaphragm from mechanical damage. For media which harden when cold, the Deltapilot S must be covered by the tank insulation. Alternatively a rod or rope version can be used. Process diaphragm Effect of temperature Endress+Hauser 7
10 GREEN DAT-Modul RED FHB ma 2 Installation Deltapilot S PA Sealing G11/2 thread (BSP): The flat seal supplied must be placed on the sealing surface of the process connection when the sensor is screwed into the tank, Do not use plumber's hemp or similar materials. NPT thread: PTFE tape, wrapped around the thread, is recommended as sealing. Use the hexagonal nut to screw in the sensor, not the housing. Do not screw in too tightly: max. torque Nm. BA164Y12 Fig. 2.1 Screw in sensor at hexagonal nut only! Turning the housing The housing can be turned to position the cable entry. The cable entry must point downwards when the sensor is mounted sideways in the tank. The cable entry must be horizontal when the sensor is fitted with a protective hood Sealing the sensor housing Turn the housing as follows: Unscrew the cover Loosen the Phillips screw Turn the housing (max. 280 ) Tighten the Phillips screw. It is important that no moisture enters the housing during operatiion and when the electronic insert is being connected. Always tighten the housing cover and cable entries. The O-ring seal in the housing cover and the thread of the aluminium cover have been lubricated. If this lubricant is removed, replace it (e.g. with silicone grease or graphite paste), so that the cover seals tightly. Do not use mineral-oil-based lubricants! These will destroy the O-ring. BA164Y DAT-Modul DAT-Modul ma 4 20 ma + + FHB 20 FHB 20 GREEN GREEN RED RED x Fig. 2.2 Turning the sensor housing Housing adapter The housing adapter allows the housing and electronic insert to be mounted away from the measuring point. This enables problem-free measurement: under particularly difficult measuring conditions (very wet environment or danger of flooding). in tight or difficult to access mounting points. BA164Y14 Fig. 2.3 Use of the housing adapter 8 Endress+Hauser
11 Deltapilot S PA 2 Installation 2.2 Connection For new installations a cable comprising screened, twisted pairs is recommended. The following specifications must be met for explosion-hazardous applications (EN , FISCO model): Loop resistance (DC) Ω /km. specific inductance mh/km, specific capacitance nf/km, e.g. Siemens 6XV AH10 (blue) None hazardous areas, e.g. Kerpen CEL-PE/OSCR/PVC/FRLA FB-02YS(ST)YFL, Belden 3076F, Siemens 6XV BH10 (black) Information on the structure and grounding of the network are given in TI260/00/en "Planning Hints, PROFIBUS PA" and the PROFIBUS PA specification. Bus cable + V H V H Address switch Terminals The bus line also carries the power and is connected as follows: Remove housing cover Where appropriate, remove display module FHB 20 by turning with light pressure to left Thread cable through cable entry Cable connection FHB 20 DAT-Modul PA- PA+ FHB 20 Alarm LED BA164Y15 DAT data module DAT-Modul PA- PA+ FHB 20 Alarm LED Connect cable as shown: Connect cable cores to PA+ und PA. Reversed polarity has no effect on operation Connect the screen to the external ground terminal For FEB 24 P always connect external ground terminal to plant grounding system. BA164Y16 PA- PA+ Caution! The multiple grounding of the bus cable in explosion hazardous areas is permissible only under specific conditions, see TI 260F or IEC Caution! = ON OFF Every device is given a unique bus address. Normally, the bus address is set at a DIP-switch on the device. Lift protective flap Set address ( ) at switches Set switch 8 to OFF Address = address at switch ON: address = software address Switch device off and on to register the change in address. Bus address BA164Y17 OFF: Hardware address ON: Software address After connecting the bus cable and setting the address, if appropriate clip FHB 20 in position, and screw on cover. The display orientation can be changed (turn 90 anticlockwise). Endress+Hauser 9
12 2 Installation Deltapilot S PA 2.3 Device parameter file/type file A diskette with the device data base.ddb is delivered with every device type. The files must be loaded into the communications partner during the commissioning of the system. The diskette also contains a so-called TYP file for specific Siemens host system configuration tools, e.g. COM ET 200 or COM PROFIBUS. For these tools, the files should be stored as follows: all files with extender *.200 in the type file directory, e.g. ***\TYPDAT5X all files with extender *.GSD in the data parameter file directory, e.g. ***\GSD all files with extender *.BMP in the bit maps directory, e.g. ***\BITMAPS.. The significance of the individual parameters is described in the PROFIBUS-PA specification. 10 Endress+Hauser
13 Deltapilot S PA 3 Operation 3 Operation The Deltapilot S is configured and operated via a 10 x 10 matrix. Each row is allocated to a particular function, Each field sets or displays one parameter. Operating matrix The same matrix is used, irrespective of whether the operating and display module FHB or the operating program Commuwin II is used. It is to be found in Chapter 9. In the case of cyclic and acyclic scanning of parameters via PLC, the measured values are addressed by means of variable names which are defined in the PROFIBUS PA profile. 3.1 Operating and display module FHB 20 ➀ ➂ + V H Unscrew housing cover, the operating and display module is inserted and connected VH BA164Y18 ➁ ➅ V H + V H VH Operating matrix page 33 V + H ➃ ➄ Fig. 3.1 User interface of electronic insert with operating and display module FHB 20 ➀ Communication signal: lights on operation via PA interface ➁ Fault indication ➂ 41/2-figure display of measured values andentry parameters ➃ Current matrix field ➄ Bar graph of measured value ➅ Operating keys If ordered, the operating and display module is stowed away in in the housing. It functions as follows: Keys Function Selection of matrix field V Selection of vertical matrix position H Selection of horizontal matrix position V and H Display springs to V0H0 when V and H pressed simultaneously Parameter entry + or Activates selected matrix position. The selected digit flashes. + Changes value of flashing digit by +1 Changes value of flashing digit by 1 + and Resets the value entered to the original value, provided it has not yet been registered. Registering entry V or H; V and H Registers entry and quits the matrix field Locking entry + and V or and H + and V lock, and H unlock the matrix, see Section 4.6 Note! Once you have set your instrument using the operating and display module FHB 20, you can disconnect it and use it to configure other Deltapilot S sensors. Hinweis! Endress+Hauser 11
14 3 Operation Deltapilot S PA 3.2 Remote operation with Commuwin II PROFIBUS-PA FEB 24 Fig. 3.2 Parameter matrix menu in Commuwin II BA164E35 0 V0 Calibration V1 V2 Linearisation V3 Ent. calibration V4 V5 V6 V7 Sensor data 80.5% MEASURED VALUE 0 LINEARISATION 2 CALIBRATION MODE EMPTY CALIBRATION 1 TABLE NO. 0 UNITS DRY CALIBR. 100 FULL CALIBRATION 0 ENTER LEVEL 1.00 DENSITY FACTOR LOWER RANGE-LIMIT UPPER RANGE-LIMIT MAX. PRESSURE PROFIBUS-PA devices can be operated with Commuwin II operating program versions from 1.5 upwards. A full description of Commuwin II is to be found in operating instructions BA 124F. The transmitter is configured either via the operating matrix (see Fig. 3.2) or the graphic interface (Fig. 3.3). Open connection Remote operation requires the installation of the PROFIBUS-PA server and the personal computer requires a PROFIBUS-DP card. The connection in Commuwin II is made via the PROFIBUS-PA server All devices on the relevant segment appear in the live list. The transmitter configuration is entered in the device menu PROFIBUS-PA profile parameters can be viewed and set under the graphic interface Note! Note! Deltapilot S transmitters can also be configured on site via the keys. If the keys have been used to lock configuration, the transmitter cannot be remotely configured, but the parameters can be displayed. Graphic support - status Endress+Hauser Deltapilot S (FEB 24) DEVICE+SOFTW XXXX MEASURING POINT LIC 006 DIAGNOSIS CODE 0 Fig. 3.3 Graphic support menu in Commuwin II BA164E36 MEASURED VALUE Endress+Hauser
15 Deltapilot S PA 3 Operation 3.3 Data acquisition via PLC A so-called profile exists for the operation via programmable logic controller: This contains: mandatory parameters, with which the basic parameters of the device can be read or configured. application parameters, which allow a calibration and, e.g., additional functions such as a linearisation to be performed. Deltapilot S (DPV1) provides the measured value (OUT) in the cyclic service according to the PROFIBUS PA protocol, see below. Other profile parameters can be accessed acyclically. A list is to be found in Chapter 7. Parameter Type Function OUT Read Current value of the process variable in customer units together with the corresponding status Status = 0, device OK Status > 0, warning or alarm The information is transmitted bytewise in 5 bytes, whereby the last contains the status information, see overleaf. OUT_SCALE Read, Write Scaling of the output in customer units PV_SCALE Read, Write Scaling of the process variable comprising a lower and upper measuring range limit, code for proprietary units or units after calibration and number of characters after the decimal point PV_FTIME Read, Write Rise time of the function block output in s ALARM_HYS* Read, Write Hysteresis of the alarm function in % of the measuring range HI_HI_LIM* Read, Write Upper alarm limit: if the measured value exceeds this limit, a status bit is set to 1 HI_LIM* Read, Write Upper warning limit: if the measured value exceeds this limit, a status bit is set to 1 LO_LIM* Read, Write Lower warning limit: if the measured value drops below this limit, a status bit is set to 1 LO_LO_LIM* Read, Write Lower alarm limit: if the measured value drops below this limit, a status bit is set to 1 HI_HI_ALM* Read Status of the upper alarm limit 0 = OK, 1 = exceeded HI_ALM* Read Status of the upper warning limit 0 = OK, 1 = exceeded LO_ALM* Read Status of the lower warning limit 0 = OK, 1 = dropped below LO_LO_ALM* Read Status of the lower alarm limit 0 = OK, 1 = dropped below *The hysteresis and all alarm and warning limits are referenced to OUT_SCALE Endress+Hauser 13
16 3 Operation Deltapilot S PA Data format OUT Byte Data Data format 1 Measured value IEEE 754-floating point number 2 Measured value 3 Measured value 4 Measured value 5 Device status 80 HEX = Device OK 0C HEX = bad error (corresponds to alarm, see table page 25) 40 HEX = uncertain OK (target mode switched to manual) IEEE 754 float D15 D14 D13 D12 D11 D10 D9 D8 D7 D6 D5 D4 D3 D2 D1 D0 VZ Exponent (E) Fraction (F) Fraction (F) Endress+Hauser
17 Deltapilot S PA 4 Level Measurement 4 Level Measurement This chapter describes the parameters which must be entered to commission a Deltapilot S sensor with FEB 24 (P) electronic insert. Empty/full or dry calibration Linearisation Other settings Locking the operating matrix Measured value display 4.1 Empty/full calibration The empty/full calibration lays down the desired minimum and maximum levels for measurement. The entries can be made in any units. The tank must be filled. # VH Entry Remarks full 100% empty 0% V0H2 V0H1 1 V9H5 333 VH Reset 2 V3H0 0 VH Calibration mode "Level" 3 The tank is empty (0...40%) 4 V0H1 e.g. 0% H Current level = empty 5 The tank is full ( %) 6 V0H2 e.g. 100% H Current level = full 7 V0H5 0% level H Lower range-value 8 V0H6 100% level VH Upper range-value 9 V0H0 e.g. 70% Level BA164Y20 Result The measured value is displayed in V0H0 in the units of calibration. All other entries must be made in the same units. The entry of a zero offset shifts the "empty" calibration point. The offset is entered in the units of calibration. Zero offset # VH Entry Remarks 1 V3H3 e.g. 5 VH Zero offset 2 V0H0 e.g. 75% Corrected level 105 % 100 % V0H2 Result The measured value in V0H0 is corrected by the amount entered. All further entries refer to the offset zero point. +5 % 0% V3H3 V0H1 Note! The "full" calibration point in V0H2 is also shifted by the amount entered. If necessary, this must be taken into account in the calibration. Note! BA164Y21 Endress+Hauser 15
18 4 Level Measurement Deltapilot S PA Density correction If the calibration has been made with water or the product changes at a later date, the calibration values can be corrected by entering a density factor. new density Density factor = current factor x old density Determining the density factor Example: A tank is filled with water and calibrated. The density of the water (old density) is 1 g/cm 3. Later the tank will be used as a storage tank and be filled with the actual medium to be measured. The new density is 1.2 g/cm 3. V3H2 still contains the factory setting 1 g/cm 3, i.e. the current factor is 1 g/cm g/cm 3 Density factor = 1 g/cm 3 x = 1.2 g/cm 1 g/cm 3 3 # VH Entry Remarks 1 V3H2 e.g. 1.2 VH Density factor 2 V0H0 e.g % Corrected level Result The measured value in V0H0 is divided by the density factor and is thus correct for the new product Measurement with product ρ = 1.2 Calibration with water ρ = 1.0 BA164Y22 Note! Note! The entry of a density factor directly affects the level measurement. If volume is to be measured by entering a linearisation curve, make sure the curve entered takes account of the current density factor. 16 Endress+Hauser
19 Deltapilot S PA 4 Level Measurement 4.2 Dry calibration The dry calibration is a theoretical calibration, which can be made with an empty tank or on the test bench. The "empty" calibration point is always at the sensor mounting point. It need not be entered. If the measurement is to begin at another level, a zero offset must be entered. The prerequisites for a dry calibration are: The level for the calibration point "full" is known. Any zero offset has already been taken into account. The density factor is known. Two dry calibration modes can be selected in V3H0: Measured value display in the selected unit (=1) Measured value display in % (=2) # VH Entry Remarks BA164Y23 4,2 m 4,0 m +0,2 m 0m V0H2 V3H3 V0H1 1 V9H5 333 VH Reset 2 V3H0 e.g. 1 H Calibration mode "dry calibration" 1 = length unit 3 V3H1 e.g. 0 H Length unit m 0 = m 1 = cm 2 = ft 3 = inch 4 V3H2 e.g. 1.2 H Density factor 5 V3H3 e.g. 0.2 m VH Zero offset 6 V0H2 e.g. 4.2 m VH Level "full" (including value in V3H3) 7 V0H5 0 H Lower range-value 8 V0H6 e.g. 4 VH Upper range-value (V0H2 V3H3) 9 V0H0 e.g. 4.2 m Measured value Result The measured value in V0H0 is corrected by the amount in V3H3. After the zero offset, all entries refer to the shifted zero point. After a dry calibration, the first filling of the tank should be carefully observed, so that any errors or uncertainties are immediately detected. By making a "normal calibration" in the units (V3H0) of the dry calibration at a later date, the entries can be corrected or the accuracy improved. Correction after installation 4,0 m 4,0 m V0H2 # VH Entry Remarks 1 V3H0 0 VH Calibration mode "Level" 2 The tank is full ( %) 3 V0H2 e.g. 4 m VH Current level = full 4 V0H0 e.g. 4 m Level Result The device characteristic is optimised to the new calibration point. 0m BA164Y24 Endress+Hauser 17
20 4 Level Measurement Deltapilot S PA 4.3 Linearisation Linearisation mode In tanks in which the volume is not directly proportional to level, a volume measurement can be made by entering a linearisation curve. The table below summarises the linearisation function. Entry V2H0 Linearisation mode 0 Linear (factory setting) Significance The tank is linear, e.g. standing cylinder If the calibration was made in volume units, the measured value can be read off in volume units without further configuration. 1 Activate table The entered linearisation table only comes into effect after it has been activated. 2 Manual entry Max. 11 pairs of values, level and volume, are entered as the linearisation curve. 3 Semi-automatic entry of a linearisation curve In the case of semi-automatic entry, the tank is filled or emptied in stages. The Deltapilot S automatically calculates the level from the hydrostatic pressure, the associated volume is entered manually. 4 Delete table Before a new linearisation table is entered, any previously active table must be deleted. On deletion the linearisation mode is automatically set to linear. 5 Horizontal cylinder The linearisation curve for a horizontal cylinder is permanently stored in the Deltapilot S. Only the tank diamenter and volume must be entered. Warnings During entry of the linearisation curve, the fault indicator appears in the FHB 20 display and the alarm LED lights. Code Type Significance E605 Alarm The manual linearisation table is incomplete. This error messsage disappears after the linearisation curve has been activated. After the curve has been entered, it is checked for plausibility.the following warnings can appear: Code Type Significance E602 Warning The linearisation curve does not rise continuously. The index of the last valid pair automatically appears in V2H1. All value pairs above this index must be checked and if necessary re-entered. E604 Warning The linearisation curve comprises less than two value pairs. Enter more value pairs. 18 Endress+Hauser
21 Deltapilot S PA 4 Level Measurement The prerequisites for a manual linearisatiion are as follows: the value pairs for the linearisation curve are known the linearisation curve rises continuously the levels for the first and last points correspond to those of the empty and full calibration the level points are entered in the units of calibration. Manual entry # VH Entry Remarks 1 If no calibration yet, see page % 6 2 V2H0 4 H Delete existing curve level 0% V min 5 volume V max 3 V2H0 2 H Linearisation mode "manual" 4 V2H1 e.g. 1 H 1st value pair 5 V2H2 e.g. 0 H Level point 1 6 V2H3 e.g. 0.6 hl H Volume point 1 7 Repeat steps for up to 10 more value pairs 8 V2H0 2 VH Activate table BA164Y25 9 V0H5 V min H Lower range-value 10 V0H6 V max VH Upper range-value 11 V0H0 V0H9 Measured value volume/level Result The volume is displayed in V0H0 The level can be read from V0H9. The tank can be filled, for example, for the calibration and gradually emptied for the linearisation The level is automatically detected from the hydrostatic pressure. The associated volume must be entered by hand. Semi-automatic entry # VH Entry Remarks 1 If no calibration yet, see page % 6 2 V2H0 4 H Delete existing curve level 0% V min 5 volume V max 3 V2H0 3 H Linearisation mode "semi-automatic" 4 V2H1 e.g. 1 H 1st value pair 5 V2H2 Read value H Current level 6 V2H3 e.g. 0.6 hl H Volume for V2H2 7 Repeat steps for up to 10 more value pairs 8 V2H0 2 VH Activate table BA164Y27 9 V0H5 V min H Lower range-value 10 V0H6 V max VH Upper range-value 11 V0H0 V0H9 Measured value volume/level Result The volume is displayed in V0H0 The level can be read from V0H9. Endress+Hauser 19
22 4 Level Measurement Deltapilot S PA Horizontal cylinder The permanently stored linearisation curve for a horizontal cylinder is activated by entering the following parameters: Tank diameter D in the units of calibration (V0H1/V0H2) Tank volume V or weight in the units of linearisation # VH Entry Remarks 1 If no calibration yet, see page 15 2 V2H0 4 H Delete existing curve 3 V2H0 5 H Linearisation mode "horizontal cylinder" 4 V2H4 D H Tank diameter 5 V2H5 V H Tank volume 6 V2H3 e.g. 0.6 hl H Volume point 1 9 V0H5 0 H Lower range-value 10 V0H6 V VH Upper range-value 11 V0H0 V0H9 Measured value volume/level D BA164Y26 V Result The volume is displayed in V0H0 The level can be read from V0H Other settings Output damping τ The output damping influences the time it takes for the displays in V0H0, V0H8 and V0H9 to react to a change in level. By increasing the output damping, the effect of a turbulent product surface on the measured value and maximum pointer displays can be damped, for example. # VH Entry Remarks 1 V0H4 e.g. 30 H Output damping ( s) 63% level signal BA164Y28 τ time Signal on alarm On an alarm, an error code is transmitted with the measured value. The display and bargraph assume the selected value. # VH Entry Remarks 1 V0H7 e.g. 0 VH Measured value on alarm 0 = = = last value Alarm V0H7 = 1 (+19999) V0H7 = 2 (hold value) V0H7 = 0 ( 19999) t BA164Y29 20 Endress+Hauser
23 Deltapilot S PA 4 Level Measurement 4.5 Locking/unlocking the matrix After all parameters have been entered, the matrix can be locked via the keys on the operating and display module FHB 20 or via the matrix by entering a three digit code 333 or 9303 in V9H9. (333 or 9303 is the code for unlocking the matrix) This protects the measuring point from accidental and unauthorised entries. BA164Y30 display ca. 2 s P--- + Unlocking Press " and "H" simultaneously V V H Locking press "+" and "V" simultaneously display ca. 2 s F--- H V H # VH Entry Remarks Lock 1 V9H9 e.g. 100 VH Matrix locked (except V9H9) Unlock 2 V9H9 333 VH Matrix unlocked Fig. 4.1 Locking and unlocking the matrix using the FHB 20 The table summarises the locking function Locking via Display/reading of parameters Changing/Writing via Unlocking via keys communication keys communication Keys yes no no yes no Communication yes no no yes yes Endress+Hauser 21
24 4 Level Measurement Deltapilot S PA 4.6 Measuring point information The following information about the measuring point can be read from the Deltapilot S. Matrix field Display or entry Measured value V0H0 Principle measured value V0H8 Sensor pressure (units selected in V3H4) V0H9 Level before linearisation Sensor data V7H0 Lower measuring limits of sensor (units selected in V3H4, see Chapter 5) V7H1 Upper measuring limit of sensor (units selected in V3H4, see Chapter 5) V7H3 Current sensor temperature (units selected in V3H5) Information about measuring point V9H3 Device and software number Trouble-shooting V9H0 Current diagnostic code V9H1 Last diagnostic code Maximum pointer function The maximum pointer function displays the maximum pressure and temperature measured since the last pointer reset. The units for pressure and temperature are selected in the matrix fields V3H4 and V3H5 respectively. Please note that any change in the pressure units in V3H4 affects all pressure entries. Matrix field V7H2 V7H4 Display Maximum measured pressure (units selected in V3H4) Maximum measured temperature (units selected in V3H5) Communication level The matrix row "VA communication" can only be accessed via the PA interface (Commuwin II). VAH0 VAH2 VAH3 VAH5 VAH6 VAH7 VAH8 VAH9 Measuring point designation. An 8-figure measuring point designation can be entered here. Selection of unit before linearisation Selection of unit after linearisation Serial number of instrument Pressure for "empty" calibration Density factor for "empty" calibration Pressure for "full" calibration Density factor for "full" calibration 22 Endress+Hauser
25 Deltapilot S PA 5 Pressure and Differential Pressure 5 Pressure and Differential Pressure In the calibration mode "pressure", the pressure acting on the Deltapilot S is displayed in V0H0. By using two Deltapilot S sensors, it is possible to measure the level in pressurised tanks or, for example, the differential pressure across a filter. In the pressure mode, the measuring range is that given on the sensor nameplate Various pressure units can be selected in V3H4. The Deltapilot S outputs a digital pressure signal in the units which have been set in V3H4. If necessary, the measured value is processed by the PLC. Pressure measurement, Deltapilot S processing in PLC segment coupler # VH Entry Remarks 1 V9H5 333 VH Reset 2 V3H0 3 H Calibration mode "Pressure" 3 V3H4 e.g. 4 VH Pressure unit psi see Table 4 V0H5 e.g. 0 H Lower range-value 5 V0H6 e.g. 40 VH Upper range-value 6 V0H0 e.g Measured value in e.g. psi Pressure units in V3H4 No. Unit No. Unit No. Unit 0 mbar 6 in H 2 O 12 g / cm 2 BA164Y31 1 bar 7 Pa 13 kg / cm 2 2 m H 2O 8 MPa 14 lb / ft 2 3 mm H 2O 9 hpa 15 kgf / cm 2 4 psi 10 mm Hg 5 ft H 2O 11 in Hg Note! If the pressure unit is changed in V3H4, the electronic insert converts all values to the new units. A new calibration is not necessary. For other settings and locking of the matrix see section 4.4 or 4.5. Note! Depending upon the mounting position, it is possible that the sensor measures a different pressure to that actually acting on it (for pressure measurements) or to that at the lower-range value (for level measurement). The difference can be entered as a correction in V3H7. The corrected pressure is displayed in V0H8. Mounting position # VH Entry Text 1 V3H6 VH Sensor pressure 2 V3H7 e.g. 1 psi H Enter correction 3 V0H8 Corrected pressure Endress+Hauser 23
26 5 Pressure and Differential Pressure Deltapilot S PA Differential pressure Measurement Two Deltapilot S sensors are required for the measurement of differential pressure. Sensor ➀ measures the total pressure (hydrostatic and head pressure). Sensor ➁ measures the head pressure only. The diaphragm of sensor ➁ may not be flooded. This generates an additional hydrostatic pressure and falsifies the measurement. The ratio of hydrostatic pressure to head pressure should not exceed 1:6. The calibration is made in the same units for both Deltapilot S sensors. # VH Entry Text 1 V9H5 333 VH Reset 2 V3H0 0 VH Calibration mode "Pressure" 3 V3H4 e.g. 0 VH Pressure unit bar see Table page 25 4 V0H0 e.g Measured value in e.g. mbar ➁ head pressure level via PLC Result The difference between the total pressure and head pressure is calculated by the process control system and converted into a level measurement. The pressure measured by each sensor can be read off in V0H0 Deltapilot ➀: hydrostatic pressure and head pressure; Deltapilot ➁: head pressure BA164Y32 ➀ hydrostatic pressure with head pressure segment coupler Note! Note! For other settings and locking of the matrix see section 4.4 or Endress+Hauser
27 Deltapilot S PA 6 Trouble-Shooting 6 Trouble-Shooting If the FEB 24 (P) detects an alarm: the OUT signal contains the current error code. the fault indicator appears in the FHB 20 display or the red LED lights the display and barchart assume the value selected in V0H7 Min: , Max.: or Hold holds last valid value. the current error code is displayed in V9H0, the last one in V9H1. If the FEB 24 (P) detects a warning: the OUT signal contains the current warning code. the fault indicator in the FHB 20 display or the red LED flashes, but the electronic insert continues to measure the current error code is displayed in V9H0, the last one in V9H1. If several error codes appear simultaneously, they are displayed according to their priority. Alarm Warning Error codes in V9H0 and V9H1 Code Type Cause and remedy E 101 E 114 E 117 E 121 Alarm Electronic instrument fault Contact Endress+Hauser Service. E 102 Warning Electronic instrument fault for maximum display Reset maximum display E 103 Warning Initialisation in progress, lasts approx. 6 s If fault persists E 106 Alarm Up/download active Wait until procedure completed. E 110 Alarm Transmitter data not stored Reset transmitter. E 112 Alarm Sensor data error Check whether DAT module correctly connected. E 116 Alarm Download error Restart download with corrected data or reset transmitter. E 122 Alarm Break in control signal cable Check sensor connection. If the fault persists, contact Endress+Hauser Service. E 125 Alarm Signal overflow or underflow Check sensor connection. If the fault persists, contact Endress+Hauser Service. E 602 Warning Linearisation curve does not rise continuously Check the values entered. Does the volume always increase with level? E 604 Warning Less than two value pairs entered in linearisation curve. Enter more values. E 605 Alarm Incomplete manual linearisation table (appears during entry) Activate linearisation curve after entry of all value pairs. E 610 Alarm Calibration error, same pressure for gleicher V0H1 and V0H2 Check calibration. E 613 Warning Instrument in simulation mode Switch back to desired measuring mode when simulation completed. Endress+Hauser 25
28 6 Trouble-Shooting Deltapilot S PA 6.1 Simulation Note! A simulation allows the functions of the electronic insert to be simulated and tested. The following simulations are possible: pressure level volume (after a linearisation) Note! When the simulation mode is active, the fault indicator in the FHB 20 display flashes and warning E 613 appears in V9H0. This continues until the simulation mode is quit. After the simulation is complete, the normal measuring mode is selected. Simulation off: V9H6 = 0. Pressure # VH Entry Remarks 1 V9H6 1 H Simulation pressure 2 V9H7 e.g VH Pressure in units V3H4 V9H6 = 1 Level # VH Entry Remarks 1 V9H6 2 H Simulation level 2 V9H7 e.g. 5 VH Level in units of calibration pressure Volume # VH Entry Remarks 1 V9H6 3 H Simulation volume 2 V9H7 e.g. 20 VH Volume in units of linearisation Result Level or volume is displayed in V0H0. Off # VH Entry Remarks 1 V9H6 0 H Simulation off V9H6 = 2 level level, volume or pressure BA164Y33 level or volume Fig. 6.1 Simulation of the measured value Caution! Caution! If the power fails, the device automatically returns to normal operation 26 Endress+Hauser
29 Deltapilot S PA 6 Trouble-Shooting 6.2 Reset to factory settings On commissioning, all matrix fields should be reset to preset values. The factory settings are regenerated. These are listed in the matrix "factory settings" on page 33. This matrix can also be used to note your device settings. V0 V1 V2 V3 V4 V5 V6 V7 V8 V9 VA H0 H1 H2 H3 H4 H5 H6 H7 H8 H9 # VH Entry Remarks 1 V9H5 333 or 1 VH Reset BA164Y19 Fig. 6.2 Only the fields shaded grey are excluded from the reset This reset does not affect: the linearisation curve the stored values of the maximum pointer function the fields in which units have been selected the Tag No. The values can be deleted by calling up the appropriate field. Endress+Hauser 27
30 6 Trouble-Shooting Deltapilot S PA 6.3 Exchange of the electronic insert or measuring cell Electronic insert If the electronic insert has to be exchanged, all measuring cell data can be transferred to the replacement by simply installing the old DAT module. Instructions on the exchange are delivered with the new insert. Installation and wiring is described in Section 2.2. After the exchange, the calibration and other settings must be repeated. Caution! Caution! If the electronic insert is exchanged by the user, take care that the replacement corresponds to that specified on the Deltapilot S nameplate. Measuring cell: If only the measuring cell is exchanged (instructions are supplied with the replacement), all matrix settings remain intact. They are automatically updated with the new cell data. A new DAT-module is also supplied with the replacement cell. It is installed as follows: Release the retaining loop and remove the old DAT-module from the electronic insert. Plug in the new module and secure the retaining loop once more. plug in DAT module GREEN attach wire loop BA164Y34 If lost, DAT-modules can be ordered individually from Endress+Hauser. Quote the numbers printed in the Deltapilot S housing and on the measuring cell. 6.4 Repairs If the FEB 24 (P) electronic insert or the entire Deltapilot S sensor has to be sent for repair to Endress+Hauser, please enclose a note with the following information: An exact description of the application for which it was used The chemical and physical properties of the product measured A short description of the fault. Before sending in the sensor for repair, take the following protective measures: Remove all traces of product.this is particularly important if the product can impair health, i.e. is corrosive, poisonous, carcinogenic, radioactive etc.. If the last traces of dangerous products cannot be removed, e.g. product has penetrated into fissures or diffused into plastic parts, we kindly ask you not to send the transmitter for repair. 28 Endress+Hauser
31 Deltapilot S PA 7 PROFIBUS-PA Parameters 7 PROFIBUS-PA Parameters Parameter Matrix Index (Slot = 1) Read Write Type Size bytes Directory object header 0 X OSTRING 12 Composite list directory entries 1 X OSTRING 24 Physical block block object 14 X OSTRING 20 PB Static revision 15 X UNSIGNED16 2 PB Device tag VAH0 16 X X OSTRING 32 PB Strategy 17 X X UNSIGNED16 2 PB Alert key 18 X X UNSIGNED8 1 PB Target mode 19 X X UNSIGNED8 1 PB Mode 20 X OSTRING 3 PB Alarm summary 21 X OSTRING 8 PB Software revision 22 X OSTRING 16 PB Hardware revision 23 X OSTRING 16 PB Device manufacturer identity 24 X UNSIGNED16 2 PB Device identity 25 X OSTRING 16 PB Device serial number 26 X OSTRING 16 PB Diagnosis 27 X OSTRING 4 PB Diagnosis extension 28 X OSTRING 6 PB Diagnosis mask 29 X OSTRING 4 PB Diagnosis extension mask 30 X OSTRING 6 PB Device certiffication 31 X X OSTRING 16 PB Security lock V9H9 32 X X UNSIGNED16 2 PB Factory reset V9H5 33 X UNSIGNED16 2 reserved PB Descriptor 44 X X OSTRING 32 PB Device message 45 X X OSTRING 32 PB Device installation date 46 X X OSTRING 8 reserved PB Matrix error code V9H0 52 X UNSIGNED16 2 PB Matrix last error code V9H1 53 X X UNSIGNED16 2 PB Device bus address V9H4 54 X UNSIGNED8 1 PB UpDown features supported 55 X OSTRING 1 PB UpDown control 56 X UNSIGNED8 1 PB UpDown parameter 57 X UPDOWN_PARAM 20 PB Device and software number V9H3 58 X UNSIGNED16 2 reserved Transducer block block object 64 X OSTRING 20 TB Static revision 65 X UNSIGNED16 2 TB Device tag VAH0 66 X X OSTRING 32 TB Strategy 67 X X UNSIGNED16 2 TB Alert key 68 X X UNSIGNED8 1 TB Target mode 69 X X UNSIGNED8 1 TB Mode 70 X OSTRING 3 TB Alarm summary 71 X OSTRING 8 TB Volume V0H0 72 X FLOAT 4 TB Volume unit VAH3 73 X X UNSIGNED16 2 TB Sensor hi limit V7H1 74 X FLOAT 4 TB Sensor lo limit V7H0 75 X FLOAT 4 TB Level V0H9 76 X FLOAT 4 TB Level unit VAH2 77 X X UNSIGNED16 2 TB Sensor value V3H6 78 X FLOAT 4 TB Empty calibration V0H1 79 X X FLOAT 4 TB Full calibration V0H2 80 X X FLOAT 4 TB Zero offset V3H3 81 X X FLOAT 4 TB Operating mode V3H0 82 X X UNSIGNED8 1 TB Temperature V7H3 83 X FLOAT 4 TB Temperature unit V3H5 84 X X UNSIGNED16 2 TB Max. temperature V7H4 85 X X FLOAT 4 reserved Endress+Hauser 29
32 7 PROFIBUS-PA Parameters Deltapilot S PA Parameter Matrix Index Read Write Type Size (Slot = 1) TB Density factor V3H2 94 X X FLOAT 4 TB Process pressure V0H8 95 X FLOAT 4 TB Pressure unit V3H4 96 X X UNSIGNED16 2 TB Max. pressure V7H2 97 X X FLOAT 4 reserved 98, 99 TB Dry calibration unit V3H1 100 X X UNSIGNED16 2 reserved TB Damping V0H4 119 X X FLOAT 4 TB Fail-safe V0H7 120 X X UNSIGNED8 1 TB Offset V3H7 121 X X FLOAT 4 TB Simulation mode V9H6 122 X X UNSIGNED8 1 TB Simulation value V9H7 123 X X FLOAT 4 TB Linearisation mode V2H0 124 X X UNSIGNED8 1 TB Linearisatiion table number V2H1 125 X X UNSIGNED8 1 TB Linearisation table level V2H2 126 X X FLOAT 4 TB Linearisation table volume V2H3 127 X X FLOAT 4 TB Linearisation cylinder diameter V2H4 128 X X FLOAT 4 TB Lineaisation cylinder volume V2H5 129 X X FLOAT 4 TB Display format V0H3 130 X X UNSIGNED8 1 TB Empty pressure VAH6 131 X FLOAT 4 TB Empty density VAH7 132 X FLOAT 4 TB Full pressure VAH8 133 X FLOAT 4 TB Full density VAH9 134 X FLOAT 4 reserved Analog input block block data 140 X OSTRING 20 AI Static revision 141 X UNSIGNED16 2 AI Device tag VAH0 142 X X OSTRING 32 AI Strategy 143 X X UNSIGNED16 2 AI Alert key 144 X X UNSIGNED8 1 AI Target mode 145 X X UNSIGNED8 1 AI Mode block 146 X OSTRING 3 AI Alarm summary 147 X OSTRING 8 reserved 148, 149 AI OUT 150 X VAL_STATUS_FLOAT 5 AI PV_SCALE V0H5/H6 151 X X SCALING 11 AI OUT_SCALE 152 X X SCALING 11 reserved 153 AI CHANNEL 154 X X UNSIGNED16 2 reserved 155 AI PV_FTIME 156 X X FLOAT 4 reserved 157, 158 AI ALARM_HYSTERESIS 159 X X FLOAT 4 reserved 160 AI HI_HI_LIMIT 161 X X FLOAT 4 reserved 162 AI HI_LIMIT 163 X X FLOAT 4 reserved 164 AI LO_LIMIT 165 X X FLOAT 4 reserved 166 AI LO_LO_LIMIT 167 X X FLOAT 4 reserved 168, 169 AI HI_HI_ALARM 170 X ALARM_FLOAT 16 AI HI_ALARM 171 X ALARM_FLOAT 16 AI LO_ALARM 172 X ALARM_FLOAT 16 AI LO_LO_ALARM 173 X ALARM_FLOAT 16 AI SIMULATE 174 X X SIMULATION_FLOAT 6 reserved View Objects Physical block 185 X OSTRING 17 Transducer block 191 X OSTRING 17 Analog input block 197 X OSTRING Endress+Hauser
33 Deltapilot S PA 8 Technical Data 8 Technical Data General specifications Manufacturer Endress+Hauser Instrument designation Deltapilot S with electronic insert FEB 24 (PROFIBUS-PA) Input Measured variable Level, derived from hydrostatic pressure Measuring range mbar mbar mbar mbar mbar mbar mbar mbar Output Output signal Digital communication signal, PROFIBUS-PA PA function Slave Transmission rate kbyte/s Response time Slave: approx. 20 ms; PLC: approx. 600 ms for approx. 30 devices Signal on alarm PROFIBUS-PA: Signal status bit is set, last valid measured value held Display: selectable , or hold (last value) Output damping 0 99 s in V0H4, Factory setting: 0 s Communication resistance none, separate PROFIBUS PA termination resistor Physical layer IEC Integrated overvoltage protection valid for FEB 24P only: protective diode gas discharger: 230 V, nominal discharge capacity: 10 ka Accuracy Reference conditions 25 C Linearity conformity error 0.2 % of set measuring range (two-point method as per DIN 16086) Effect of ambient temperature 0.1 %/10 K of cell measuring range FS (as per DIN 16086) Hysteresis ± 0.1 % of cell measuring range FS (as per DIN 16086) Long-term drift 0.1 % of set measuring range for 6 months Operating conditions Medium temperature range DB 50, DB 50 L: C (135 C, max. 30 min) DB 51, DB 52, DB 53: 10 C 80 C, see also certificate Ambient temperature C; with separate electronics C, see certificate Limiting temperature range C, see also certificate Storage temperature range C Electromagnetic compatibility Interference emission to EN , interference immunity to EN and industrial standard NAMUR at 10 V/m Ingress protection IP 66, electronic insert Mechanical contruction Material electronics: housing plastic ABS, potted electronics Deltapilot S: housing VA (F8), polyester (F10) or aluminium (F6) wetted parts and process connection: Dimensions DB 50, DB 51, DB 52: see Fig. 8.1 and 8.2 DB 50 L, DB 53, separate housing see TI 257F/00/en User interface Operating and display module FHB 20 4 ½ digit LC display, with segmented bar chart, fault and communication indicator, optional for local display and operation, plug-in unit Operation via four keys, +, V, H on the operating and display module FHB 20 Remote operation Via PROFIBUS PA with operating program Commuwin II or PA profile Communication interface PROFIBUS PA Power Supply voltage 9 32 VDC, non-hazardous ares, 9 24 VDC, EEx Current consumption 10 ma, ±1 ma, see also certificate Start-up current Corresponds to Table 4, IEC Endress+Hauser 31
34 f f f 8 Technical Data Deltapilot S PA Dimensions Deltapilot S ø86 ø86 ø86 H D ~75 ~75 H D ~66 H D Fig. 8.1 Deltapilot DB 50 left: with thread G 1 ½ A (BSP) or NPT 1 ½ centre: with flange /see Table right : Version Ex Zone 0 FRG with F8 housing BA164Y06 117,5 25 Hges. d 4 k D d b Hges. 257 Hges. Housing F10 (polyester) Housing F6 (aluminium) Cover height Overall height Htotal. Process connection Thread Flange Version Ex Zone 0 Thread Flange b b b b Housing F8 (stainless steel) 190 b b ø86 ø86 ~75 H D ~75 H D 117,5 H ges. 117,5 H ges. d 2 d 2 25 b 25 d 4 k D ø10 d 4 k D b L L ø17,2 Fig. 8.2 left: Deltapilot S DB 51 (rod version) right: Deltapilot S DB 52 (rope version) with thread G 1 ½ A (BSP) or NPT 1 ½ or flange BA164Y07 ø42,5 230 BA164Y08 ø42,5 257 Size Flange Raised face Bore D b k d4 fd No. d2 DN40 PN DN50 PN DN80 PN DN100 PN ANSI 1 1/2" ANSI 2" , ANSI 3" ANSI 4" Endress+Hauser
35 Deltapilot S PA 9 Operating Matrix 9 Operating Matrix H0 H1 H2 H3 H4 H5 H6 H7 H8 H9 V0 Calibration Measured value Full calibration Empty Calibration Output damping 0 99 s Measured value on alarm min: 0 max: 1 hold: 2 Sensor pressure (with position correction) Measured level V1 V2 Linearisation Mode linear: 0 activate table: 1 manual: 2 semiauto: 3 delete: 4 Line No. (1 11) Enter level Enter volume V3 Extended calibration Calibration mode level: 0 dry cal. H: 1 dry cal. %: 2 pressure: 3 Unit dry calibration m: 0 cm: 1 ft: 2 inch: 3 Density factor Zero offset Pressure unit mbar: 0 bar: 1 mh 2O: 2 etc Temperature unit C: 0 F: 1 Display sensor pressure Position correction V4 V6 V7 Lower Sensor data measuring limit Upper measuring limit Max. pressure Temperature Max. temperature V8 V9 Service + simulation Current diagnostic code Last diagnostic code Device and software no. Reset»333«/1 Simulation off: 0 pressure: 1 level.: 2 volume.: 3 Simulation value Matrix lock: 333 unlock:»333/9303«va Communication Tag No. Unit before linearisation Unit after linearisation Serial No. Pressure for "empty" calibration Density factor for "empty" calibration Pressure for "full" calibration Density factor for "full" calibration This matrix summarises the factory settings. You can also enter your own settings here. H0 H1 H2 H3 H4 H5 H6 H7 H8 H9 V V1 V V V4 V7 V8 V VA Endress+Hauser 33
36 Deltapilot S PA Index Index A Alarm , 25 Application Approved usage B Bus address Bus cable Bus coupler C Cable entry Calibration Certificates Communication Commuwin II Compact version Connection D DAT-module Density factor Device parameter file Differential pressure measurement E Electronic insert FEB 24 P , 28 Error codes Exchanging components Explosion protection F Factory settings H Housing adapter I Installation Installation hints N No. of transmitters Notes on Safety O Operating and display module FHB , 11 Operating matrix , 33 Operating principle Operating program Commuwin II Operation via PLC Output damping P Pressure measurement Process diaphragm PROFIBUS-PA-Parameter R Remote operation Repairs Rod version , 7 Rope version , 7 S Sealing Semi-automatic linearisatiion Sensor housing Sensor data Simulation T Technical data Terminating resistor Trouble-Shooting U Unlocking the matrix W Warning L Level measurement Linearisation , 18 Locking the matrix Z Zero offset M Maximum pointer Measured value Measuring point information Measuring system
37
38 Europe Austria Endress+Hauser Ges.m.b.H. Wien Tel. (01) , Fax (01) Belarus Belorgsintez Minsk Tel. (01 72) , Fax (0172) Belgium / Luxembourg Endress+Hauser S.A./N.V. Brussels Tel. (02) , Fax (02) Bulgaria INTERTECH-AUTOMATION Sofia Tel. (02) , Fax (02) Croatia Endress+Hauser GmbH+Co. Zagreb Tel. (01) , Fax (01) Cyprus I+G Electrical Services Co. Ltd. Nicosia Tel. (02) , Fax (02) Czech Republic Endress+Hauser GmbH+Co. Praha Tel. (0 26) , Fax (0 26) Denmark Endress+Hauser A/S Søborg Tel. (31) , Fax (31) Estonia Elvi-Aqua Tartu Tel. (7) , Fax (7) Finland Endress+Hauser Oy Espoo Tel. (90) , Fax (90) France Endress+Hauser Huningue Tel , Fax Germany Endress+Hauser Meßtechnik GmbH+Co. Weil am Rhein Tel. (0 7621) , Fax (0 7621) Great Britain Endress+Hauser Ltd. Manchester Tel. (01 61) , Fax (01 61) Greece I & G Building Services Automation S.A. Athens Tel. (01) , Fax (01) Hungary Mile Ipari-Elektro Budapest Tel. (01) , Fax (01) Iceland Vatnshreinsun HF Reykjavik Tel. (05) , Fax (05) Ireland Flomeaco Company Ltd. Kildare Tel. (0 45) , Fax (045) Italy Endress+Hauser Italia S.p.A. Cernusco s/n Milano Tel. (02) , Fax (02) Jugoslavia Meris d.o.o. Beograd Tel. (11) , Fax (11) Latvia Raita Ltd. Riga Tel. (02) , Fax (02) Lithuania Agava Ltd. Kaunas Tel. (07) , Fax (07) Netherland Endress+Hauser B.V. Naarden Tel. (0 35) , Fax (0 35) Norway Endress+Hauser A/S Tranby Tel. (0 32) , Fax (0 32) Poland Endress+Hauser Polska Sp. z o.o. Warszawy Tel. (0 22) , Fax (0 22) Portugal Tecnisis - Tecnica de Sistemas Industriais Linda-a-Velha Tel.(01) ,Fax (01) Romania Romconseng SRL Bucharest Tel.(01) ,Fax (01) Russia Endress+Hauser Moscow Office Moscow Tel., Fax: see Endress+Hauser GmbH+Co. Instruments International Slovak Republic Transcom Technik s.r.o. Bratislava Tel. (7) , Fax (7) Slovenia Endress+Hauser D.O.O. Ljubljana Tel. (0 61) , Fax (0 61) Spain Endress+Hauser S.A. Barcelona Tel.(93) ,Fax (93) Sweden Endress+Hauser AB Sollentuna Tel.(08) ,Fax (08) Switzerland Endress+Hauser AG Reinach/BL 1 Tel. (0 61) , Fax (0 61) Turkey Intek Endüstriyel Ölcü ve Kontrol Sistemleri Istanbul Tel. (02 12) , Fax (02 12) Ukraine Industria Ukraïna Kiev Tel.(44) ,Fax (44) Africa Egypt Anasia Heliopolis/Cairo Tel.(02) ,Fax (02) Morocco Oussama S.A. Casablanca Tel. (02) , Fax (02) Nigeria J F Technical Invest. Nig. Ltd. Lagos Tel. (1) , Fax (1) South Africa Endress+Hauser Pty. Ltd. Sandton Tel. (0 11) , Fax (0 11) Tunisia Controle, Maintenance et Regulation Tunis Tel. (01) , Fax (01) America Argentina Endress+Hauser Argentina S.A. Buenos Aires Tel.(01) ,Fax (01) Bolivia Tritec S.R.L. Cochabamba Tel. (0 42) , Fax (0 42) Brazil Samson Endress+Hauser Ltda. Sao Paulo Tel. (0 11) , Fax (0 11) Canada Endress+Hauser Ltd. Burlington, Ontario Tel. (9 05) , Fax (9 05) Chile DIN Instrumentos Ltda. Santiago Tel. (02) , Fax (02) Colombia Colsein Ltd. Bogota D.C. Tel. (01) , Fax (01) Costa Rica EURO-TEC S.A. San Jose Tel , Fax Ecuador Insetec Cia. Ltda. Quito Tel. (02) , Fax (02) Guatemala ACISA Automatizacion Y Control Industrial S.A. Ciudad de Guatemala, C.A. Tel. (02) , Fax (02) Mexico Endress+Hauser I.I. Mexico City Tel. (5) , Fax (5) Paraguay Incoel S.R.L. Asuncion Tel.(021) ,Fax (021) Uruguay Circular S.A. Montevideo Tel. (02) , Fax (02) USA Endress+Hauser Inc. Greenwood, Indiana Tel. (3 17) , Fax (3 17) Venezuela H. Z. Instrumentos C.A. Caracas Tel. (02) , Fax (02) Asia China Endress+Hauser Shanghai Instrumentation Co. Ltd. Shanghai Tel.(021) , Fax (021) Endress+Hauser Beijing Office Beijing Tel. (0 10) , Fax: (0 10) Hong Kong Endress+Hauser (H.K.) Ltd. Hong Kong Tel , Fax India Endress+Hauser India Branch Office Mumbai Tel. (0 22) , Fax (0 22) Indonesia PT Grama Bazita Jakarta Tel. (21) , Fax (21) Japan Sakura Endress Co., Ltd. Tokyo Tel. (0422) , Fax (04 22) Malaysia Endress+Hauser (M) Sdn. Bhd. Petaling Jaya, Selangor Darul Ehsan Tel. (03) , Fax (03) Pakistan Speedy Automation Karachi Tel. (0 21) , Fax (0 21) Papua-Neuguinea SBS Electrical Pty Limited Port Moresby Tel , Fax Philippines Brenton Industries Inc. Makati Metro Manila Tel. (2) , Fax (2) Singapore Endress+Hauser (S.E.A.) Pte., Ltd. Singapore Tel , Fax South Korea Endress+Hauser (Korea) Co., Ltd. Seoul Tel. (02) , Fax (02) Taiwan Kingjarl Corporation Taipei R.O.C. Tel. (02) , Fax (02) Thailand Endress+Hauser Ltd. Bangkok Tel. (2) , Fax (2) Vietnam Tan Viet Bao Co. Ltd. Ho Chi Minh City Tel. (08) , Fax (08) Iran Telephone Technical Services Co. Ltd. Tehran Tel. (0 21) , Fax(0 21) Israel Instrumetrics Industrial Control Ltd. Tel-Aviv Tel. (03) , Fax (03) Jordan A.P. Parpas Engineering S.A. Amman Tel. (06) , Fax (06) Kingdom of Saudi Arabia Anasia Jeddah Tel. (02) , Fax (02) Kuwait Kuwait Maritime & Mercantile Co. K.S.C. Safat Tel , Fax Lebanon Nabil Ibrahim Jbeil Tel. (3) , Fax (9) Sultanate of Oman Mustafa & Jawad Sience & Industry Co. L.L.C. Ruwi Tel , Fax United Arab Emirates Descon Trading EST. Dubai Tel. (04) , Fax (04) Yemen Yemen Company for Ghee and Soap Industry Taiz Tel. (04) , Fax (04) Australia + New Zealand Australia GEC Alsthom LTD. Sydney Tel. (02) , Fax (02) New Zealand EMC Industrial Instrumentation Auckland Tel. (09) , Fax (09) All other countries Endress+Hauser GmbH+Co. Instruments International D-Weil am Rhein Germany Tel. ( ) , Fax ( ) Members of the Endress+Hauser group 10.97/MTM Endress +Hauser The Power of Know How BA 164F/00/en/09.97a CCS/CV
How To Control A Power Supply With A Mini Transmitter And Switch (Power Supply)
transmitter (2 wire) / switch for continuous or On/Off Control Indication, monitoring, transmitting and continuous or On/Off control in one device Output signal 4...20 ma, 2-wire for continuous control
Plastic tube flowmeters Series PT/PS
Plastic tube flowmeters Variable area flowmeter for liquids and gases Low cost, excellent readability and light weight Simple installation (flanged, threaded or socket ends for solvent or fusion welding
Digital inductive conductivity transmitter
Digital inductive conductivity transmitter Optimal solution for conductivity measurements in difficult fluids (polluted, dirty,...) PEEK/PPA version for CIP applications Large range of process connections
Differential Pressure Sensors for air and non-corrosive gases, with calibration certificate
1 919 1919P01 1919P03 QBM65/C, QBM75-1U/C Differential Pressure Sensors for air and non-corrosive gases, with calibration certificate QBM751-1/C QBM65/C QBM75/C Highly accurate measurements with calibration
Electronic Pressure Switch EDS 300
Electronic Pressure Switch EDS 300 User manual Page 2 of 16 Content 1. Functions of the EDS 300...3 2. Mounting...3 3. Operating keys on the membrane keypad...4 4. Digital display...4 5. Output function...5
Technical Data. Dimensions
0102 Model Number Features 15 mm quasi flush Usable up to SIL2 acc. to IEC 61508 Accessories BF 30 Mounting flange, 30 mm V1-G-N-2M-PUR Female cordset, M12, 2-pin, NAMUR, PUR cable V1-W-N-2M-PUR Female
EX-TECH SAS CP/PB 150 EXPLOSIONPROOF MANUAL CALL POINT/ PUSH BOTTON TECHNICAL MANUAL
PRODUCT NAME: CP/PB -150- EXPLOSION-PROOF-MANUAL CALL POINT/ PUSH BOTTON DOC NO.: EX-TECH SAS-12-CP-PB150-TM REV01 EXPLOSION-PROOF MANUAL CALL POINT/ PUSH BOTTON II 2GD EPL Gb, Db Ex d IIC T6, IP66 Ex
Flow switches Series AD/VH
Flow switches Flow switch and indicator for liquids and gases Suitable for clear, opaque or turbid liquids (series AD & VH), and for gases (series AD) Flow switching by means of magnetic coupling, watertight,
Proportional pressure regulators VPPE
Proportional pressure regulators VPPE Proportional pressure regulators VPPE Product range overview Function Version Pneumatic connection Proportional pressure regulator Nominal size for pressurisation/
Liquid Level Limit Switch liquiphant T FTL 20
Technical Information TI 64F/4/ae Liquid Level Limit Switch liquiphant T FTL 0 Level limit switch for liquids Applications The Liquiphant T FTL 0 is a level limit switch for virtually any kind of fluid
Technical Data. General specifications Switching element function Rated operating distance s n 15 mm
0102 Model Number Features Comfort series 15 mm flush Accessories MHW 01 Modular mounting bracket MH 04-2057B Mounting aid for VariKont and +U1+ Technical Data General specifications Switching element
Technical Information RIA14
TI00143R/09/EN/04.14 71256618 Products Solutions Services Technical Information RIA14 Loop powered field indicator With explosion proof enclosure (according to Ex d) Application Oil & gas Petrochemical
ABB i-bus EIB / KNX Analogue Input AE/S 4.2
Product Manual ABB i-bus EIB / KNX Analogue Input AE/S 4.2 Intelligent Installation Systems This manual describes the functionality of Analogue Input AE/S 4.2. Subject to changes and errors excepted. Exclusion
Differential Pressure Transmitter Model DPT-10
Electronic Pressure Measurement Differential Pressure Transmitter Model DPT-10 WIKA Data Sheet PE 86.21 Applications Process engineering Pharmaceutical Food and beverage industries Special features High
WaterMAG. Electromagnetic Flowmeter for Water Applications. Model MCB10A OVERVIEW APPLICATIONS FEATURES. No. SS2-MCB100-0100
WaterMAG Electromagnetic Flowmeter for Water Applications OVERVIEW The WaterMAG is an electromagnetic flowmeter for water measurement applications based on field proven Azbil Corporation's technologies.
SITRANS F flowmeters SITRANS F M
Overview Integration The complete flowmeter consists of a flow sensor and an associated transmitter MAG 5000, 6000 or 6000 I. The flexible communication concept USM II simplifies integration and update
R4D0-FB-IA* FieldBarrier. Features. Assembly. Function. Connection IN + - S OUT ... ... Spur 2. Spur 1. Zone 1. Zone 0
FieldBarrier Features Assembly 8... 12 outputs Ex ia IIC, FISCO and Entity Advanced fault isolation and diagnostics at the spur FieldBarrier in Zone 1/Div. 2 Instruments in Zone 0...1/Div. 1 For FOUNDATION
Ferrostat Speed Sensor Series DSF Explosion Proof Versions EEx
Ferrostat Speed Sensor Series DSF Explosion Proof Versions EEx DSF..10.**.HV Ex ATEX Operating Instructions 374E-64368 Valid from lot nr. 0103 General Function Use in potentially explosive environment
VP23, 3-way proportional pressure control valves Seat valve with μp-driven pressure control
VP, -way proportional pressure control valves > > Port size: G/... G/ > > All-digital control electronics > > Variable pressure control > > Optional actuation via fieldbus (separate datasheet on request)
RHE12. Hazardous Area Coriolis Mass Flow Transmitter. Features. Applications. Benefits
RHE12 Hazardous Area Coriolis Mass Flow Transmitter Features Field mounting Compact, pressure safe housing ATEX and CSA approvals for installation in hazardous areas 24 VDC power supply Configurable analog
How To Use A Flowmeter
INLINE flowmeter for continuous flow measurement Economic integration in pipe systems without any additional piping 3-wire frequency pulse version to directly interface with PLC s (both PNP and NPN) Connection
Electronic Pressure Switch EDS 3000
For Your Information Electronic Pressure Switch EDS 3000 User Manual Revision: November 01, 2002 1. EDS 3000 Functions The EDS 3000 unit offers the following functions: Display pressure in psi, MPa, or
Series 7500 Torque Sensor
Properties PTO (Power Take-Off) shaft with integrated torque and angle measurement Non-contact measurement system, high robustness Plug & Play solution, no additional electronics required Performance Measurement
DMP 331. Industrial Pressure Transmitter for Low Pressure. Stainless Steel Sensor
DMP Industrial Pressure Transmitter for Low Pressure Stainless Steel Sensor accuracy according to IEC 60770: standard: 0.5 % FSO option: 0.5 / 0. % FSO from 0... 00 mbar up to 0... 40 bar Output signals
SIMATIC NET. CP 243-2 AS-Interface Master B C. Preface Contents. Technical Description and Installation Instructions Interface to the User Program
Preface Contents SIMATIC NET CP 243-2 AS-Interface Master Manual Technical Description and Installation Instructions Interface to the User Program 2 in the S7-200 CPU Access to the Data of the AS-i Slaves
Duct Humidity Transmitter
SDC-H Duct Humidity Transmitter Features Replaceable sensor element Humidity measurement for air ducts Minimum and maximum value memory 0 0V, 0 0mA or 0V, 4 0mA measuring signals selectable with jumpers
SIMATIC. ET 200S distributed I/O 2AO I ST analog electronic module (6ES7135-4GB01-0AB0) Preface. Properties 1. Parameters 2.
SIMATIC ET 200S distributed I/O SIMATIC ET 200S distributed I/O 2AO I ST analog electronic module (6ES7135-4GB01-0AB0) Manual Preface Properties 1 Parameters 2 Diagnostics 3 Analog value representation
DVPPF02-H2. PROFIBUS DP Slave Communication Module Application Manual
DVPPF02-H2 PROFIBUS DP Slave Communication Module Application Manual Warning Please read this instruction carefully before use and follow this instruction to operate the device in order to prevent damages
CONTOIL DFM 8EDM. Table of contents. Mounting and operating instructions
Mounting and operating instructions CONTOIL DFM 8EDM Table of contents Safety instructions 2 - Designed use - Installation, commissioning and operation - Operational safety - Return of the instruments
BLUE RIBBON CORP. BC001 Birdcage Installation Manual
Product Overview: This manual is applicable for the BC001 Birdcage Submersible Level Transmitters. If the product you have has a different prefix part number than listed above please contact the factory
Features. Picture. Specifications
Type: for level measurement Order No.: see Table 1 / Page 4 Features Picture Two wire system Piezoresistive measuring element Output signal 4-20 ma Conformity error ±0.5 % FS or Standard DIN measuring
Series DFMT Digital Paddlewheel Flowmeter
Series DFMT Digital Paddlewheel Flowmeter Bulletin F-DFMT Specifications - Installation Operating Instructions -/8 [00] -/ [8] -/8 [00] A The Series DFMT Digital Paddlewheel Flow Transmitter provides instantaneous
GREISINGER electronic GmbH
T38.0.0X.6C-03 CO2 - Transmitter Operating Manual GT10 - CO2-1R GREISINGER electronic GmbH D - 93128 Regenstauf, Hans-Sachs-Straße 26 Tel.: +49 9402 / 9383-0, Fax: +49 9402 / 9383-33, email: [email protected]
Technical data. General specifications. Signal voltage 15... 30 V DC Signal duration. 1 s Input 2. Signal voltage. 1 s Analog output.
Model Number Features Very small housing High climatic resistance 4 Bit multiturn Analog output Surge and reverse polarity protection Description This absolute rotary encoder with internal magnetic sampling
Electronic pressure switch with display Model PSD-30, standard version Model PSD-31, with flush diaphragm
Electronic pressure measurement Electronic pressure switch with display Model PSD-30, standard version Model PSD-31, with flush diaphragm WIKA data sheet PE 81.67 Applications Machine tools Hydraulics
2/8.10.01. These vacuum switches are used in measuring ranges between -1 and 0 bar.
CATALOGUE > Release 8.5 > Electronic vacuum switches Series SWM Electronic miniature vacuum switches Series SWM These vacuum switches are used in measuring ranges between -1 and 0 bar. Small dimension
HERZ-Thermal Actuators
HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01
Non-invasive CLAMP-ON ultrasonic flowmeter for liquids
Non-invasive CLAMP-ON ultrasonic flowmeter for liquids Model CU100: non-invasive installation flowmeter, with transducers installed outside the pipe Installation in horizontal or vertical pipe Easy and
ATL Fuel Level Sender Probes
T E C H N I C A L S P E C I F I C A T I O N The ATL EL-AD-151 (Resistance Output) and EL-AD-152 (Voltage Output) Fuel Level Senders are highly advanced sensors for continuously measuring the contents of
T0118 T2118 T3118. Instruction Manual
Programmable indoor transmitter of temperature T0118 Programmable indoor transmitter of atmospheric pressure T2118 Programmable indoor transmitter of temperature, relative humidity and other derived humidity
Digital pressure gauge for industrial applications Model DG-10-S, Standard version Model DG-10-E, Enhanced version
Electronic pressure measurement Digital pressure gauge for industrial applications Model DG-10-S, Standard version Model DG-10-E, Enhanced version WIKA data sheet PE 81.66 Applications Machine building
MOUNTING AND OPERATING INSTRUCTIONS
MOUNTING AND OPERATING INSTRUCTIONS CF 51/55 1. Delivery CF 51/55-1 calculator with battery (optionally with mains power supply) - 1 wall mounting bracket - package with material for sealing, screws, wall
Assisted lift operated 2/2-way solenoid valves Type EV250B
MAKING MODERN LIVING POSSIBLE Data sheet Assisted lift operated 2/2-way solenoid valves Type EV250B EV250B with assisted lift can operate from zero and up to 10 bar differential pressure. This 2/2-way
3DLevelScanner II TECHNICAL DATA SHEET
TECHNICAL DATA SHEET Changing the market from level to volume APM`s 3DLevelScanner incorporates advanced technology for accurately measuring bulk solids and powder stored in silos and open bins of all
xepi 2 Installation Guide Diagnostic Unit and Configuration Interface Doc. Version 4.0 English
xepi 2 Diagnostic Unit and Configuration Interface Doc. Version 4.0 Installation Guide English Dear Customer, This "Installation Guide" will help you to install the hardware. If you have any further questions,
Level Switch LBFS. Technical Data. ATEX data Internal inductivity Li < 10 μh Internal capacity Ci < 43 nf Barrier data. Sensor
Special Features Wetted parts in stainless steel and PEEK Compact design Precise switching point with no requirement for calibration Process temperature 0... 5 C Measures media with DKvalues >.5 (DK =
Series 6000 Torque measured metal bellow coupling
Properties Free of float metal bellow coupling with integrated torque measurement Non-contact measurement system, high robustness High torsional stiffness Limited torque of inertia Performance Measurement
ABB i-bus EIB Shutter Actuators JA/S 2.230.1, JA/S 4.230.1, JA/S 8.230.1, JA/S 4.230.1M, JA/S 8.230.1M, JA/S 4.24.1
Product Manual ABB i-bus EIB Shutter Actuators JA/S 2.230.1, JA/S 4.230.1, JA/S 8.230.1, JA/S 4.230.1M, JA/S 8.230.1M, JA/S 4.24.1 Intelligent Installation Systems Contents Page 1 Introduction.......................................
Subminiature Load Cell Model 8417
w Technical Product Information Subminiature Load Cell 1. Introduction... 2 2. Preparing for use... 2 2.1 Unpacking... 2 2.2 Using the instrument for the first time... 2 2.3 Grounding and potential connection...
DREXELBROOK. USonic-R Series. Ultrasonic Level Measurement System. User Friendly
DREXELBROOK A Leader In Level Measurement Solutions USonic-R Series Ultrasonic Level Measurement System User Friendly Set the measurement range directly in inches, feet, millimeters, centimeters, or meters
Combi switchbox with integrated 3/2 way pilot valve
H Combi switchbox with integrated 3/2 way pilot valve Construction The GEMÜ combi switchbox with integrated 3/2 way pilot valve for pneumatically operated quarter turn actuators has a micro-processor controlled
SAFETY MANUAL SIL Switch Amplifier
PROCESS AUTOMATION SAFETY MANUAL SIL Switch Amplifier KCD2-SR-(Ex)*(.LB)(.SP), HiC282* ISO9001 2 With regard to the supply of products, the current issue of the following document is applicable: The General
Proportional relief valves type AGMZO-TERS, AERS two stage, with integral or remote pressure transducer, ISO 6264 size 10, 20 and 32
www.atos.com Table F040-1/E Proportional relief valves type AGMZO-TERS, AERS two stage, with integral or remote pressure transducer, ISO 6264 size 10, 20 and 32 AGMZO are two stage poppet type proportional
www.kem-kueppers.com [email protected] Certified according to DIN EN ISO 9001 Technical Datasheet TRICOR Series Mass Flow Meters
www.kem-kueppers.com [email protected] Certified according to DIN EN ISO 9001 Technical Datasheet TRICOR Series Mass Flow Meters Description The Tricor Mass Flow Meters measure simultaneously mass
Fluid Level Gauge Fluid Level Sensor Temperature Switch FSA / FSK / TS
Fluid Level Gauge Fluid Level Sensor Temperature Switch FSA / FSK / TS up to size 381; to PN 0.5; to T = 80 C 1. Description 1.1. General FSA fluid level gauges, FSK fluid level sensors and TS temperature
Contents. Document information
User Manual Contents Document information... 2 Introduction... 3 Warnings... 3 Manufacturer... 3 Description... Installation... Configuration... Troubleshooting...11 Technical data...12 Device Scope: PCB
Practical steps for a successful. PROFIBUS Project. Presented by Dr. Xiu Ji Manchester Metropolitan University
Practical steps for a successful PROFIBUS Project Presented by Dr. Xiu Ji Manchester Metropolitan University Basics of PROFIBUS Content Practical steps in the design and installation stages Segmentation:
Pressure transmitter For general industrial applications Model A-10
Electronic pressure measurement Pressure transmitter For general industrial applications Model A-10 WIKA data sheet PE 81.60 for further approvals see page 9 Applications Machine building Shipbuilding
Floating Switch FTS 20 Füllstandgrenzschalter Level Limit Switch Détecteur de niveau
KA 180F/00/en/06.01 (a) 52010984 Floating Switch FTS 20 Füllstandgrenzschalter Level Limit Switch Détecteur de niveau Safety instructions The FTS 20 floating switch may only be used as a level limit switch
Tilt switches N3 / N4... MEMS technology, one or two axis. Use. Options. + long lifetime and highly reliability due to mechanism-free MEMS technology
Tilt switches MEMS technology, one or two axis N3 / N4... + long lifetime and highly reliability due to mechanism-free MEMS technology + combinable output signals + one or two axis measurement + tilt range
CONNECTOR AMPLIFIER FOR PROPORTIONAL VALVES (4-20 ma Input Version)
TECHNICAL DATASHEET #TD1102AX CONNECTOR AMPLIFIER FOR PROPORTIONAL VALVES (4-20 ma Input Version) Part Number: Connector Amplifier CAPV-H-4-20MA-x complete with cable CAPV-4C-yM Where: x = current output
Instruction Manual. T3111 T3111L T3111P T3111Ex
www.cometsystem.cz Instruction Manual T3111 T3111L T3111P T3111Ex Programmable transmitter of temperature, relative humidity and other calculated humidity values with external probe and 4-20 ma outputs
System 6000 Electropneumatic Converter for Direct Current Signals Type 6116 i/p Converter
System 6000 Electropneumatic Converter for Direct Current Signals Type 6116 i/p Converter Application Used to convert a direct-current input signal into a pneumatic output signal for measuring and control
DLP-PU/E Instruction Manual
Instruction Manual BEFORE USING THE POWER SUPPLY UNIT Pay attention to all warnings and cautions before using the unit. Incorrect usage could lead to an electrical shock, damage to the unit or a fire hazard.
Mobrey Ultrasonic. MSP900SH Level and MSP900FH Flow Transmitters. Product Data Sheet February 2015 IP2032, Rev BA
Mobrey Ultrasonic MSP900SH Level and MSP900FH Flow Transmitters Product Data Sheet February 2015 IP2032, Rev BA Non-contacting measurement with no moving parts Fast and simple to install and configure
Pressure monitoring equipment for oil-sf 6. bushings, type GOEK
Pressure monitoring equipment for oil-sf 6 bushings, type GOEK Installation and maintenance guide 5693 827-6 en, Rev. 3, 2002-01-30 This document must not be copied without our written permission, and
Temp-485-Pt100. A temperature sensor (Pt100 or Pt1000) communicating over the RS-485 bus with a simple communication protocol
Temp-485-Pt100 A temperature sensor (Pt100 or Pt1000) communicating over the RS-485 bus with a simple communication protocol Temp-485-Pt100 Box version [600 113] Temp-485-Pt100 Cable version [600 114]
Solenoid Valve Island Type 3965
Solenoid Valve Island Type 365 for the control of pneumatic actuators General The Type 365 Solenoid Valve Island is a compact solution for the centralized control of pneumatic actuators in chemical and
Toroidal Conductivity Sensor
Instruction Sheet PN 51A-/rev.C June 2012 Toroidal Conductivity Sensor For additional information, please visit our website at www.emersonprocess.com/rosemountanalytical.com SPECIFICATIONS Wetted Materials:
3/2-, 5/2- and 5/3-way Solenoid Valves for process pneumatics
3/2-, 5/2-5/3-way Solenoid Valves for process pneumatics Type 6518 stard High flow-rate capacity Reduced power consumption Single or manifold mounting stard Type 6518/6519 can be combined with... Stard-,
L5354 ControlNet Communications Interface
L5354 ControlNet Communications Interface Technical Manual HA470733 Issue 2 Copyright SSD Drives Inc 2005 All rights strictly reserved. No part of this document may be stored in a retrieval system, or
Automation System TROVIS 6400 TROVIS 6493 Compact Controller
Automation System TROVIS 6400 TROVIS 6493 Compact Controller For panel mounting (front frame 48 x 96 mm/1.89 x 3.78 inch) Application Digital controller to automate industrial and process plants for general
Control- and feedback head for integrated mounting on Robolux valves Type 2036
Control- and feedback head for integrated mounting on Robolux valves Type 203 Type 885 Type 88 can be combined with Compact stainless steel design Contactless valve position registration Coloured illuminated
Instructions Manual. Electromagnetic sensor Series FLOMID FX. instrumentation for fluids. R-MI-FlomidFX Rev.: 0 English version
instrumentation for fluids Electromagnetic sensor Series FLOMID FX Instructions Manual! Conforms with the Pressure Equipment Directive 97/23/EC. 0830 This equipment is considered as being a pressure accessory
RI-215A Operator s Manual. Part Number: 71-0045RK Revision 0 Released: 10/3/05
RI-215A Operator s Manual Part Number: 71-0045RK Revision 0 Released: 10/3/05 Warranty RKI Instruments, Inc., warrants gas alarm equipment sold by us to be free from defects in materials and workmanship,
! WARNING. Before using product, read and understand instructions.
McDonnell & Miller Installation & Maintenance Instructions MM-600G) Series FS8-W General Purpose Liquid Flow Switch OPERATION This control is an independently mounted water flow sensing device that makes
MTI10 Insertion and MTL10 In-line Thermal Mass Flowmeter and Temperature Transmitter
Thermal Mass meter and Temperature Transmitter Description The MTI10 insertion thermal mass flowmeter and the MTL10 in-line thermal mass flowmeter provide accurate mass flow measurement of clean, dry gases
Fluxi 2000/TZ Turbine Gas Meter
Gas Fluxi 2000/TZ Turbine Gas Meter Turbine gas meters are flow meters. The flow of gas turns a turbine wheel, and thus, the rotating speed of the turbine is proportional to the linear speed of the gas.
DeviceNet Bus Software Help for Programming an Allen Bradley Control System
FBP FieldBusPlug V7 DeviceNet Bus Software Help for Programming an Allen Bradley Control System DeviceNet Software Help for Programming an Allen Bradley Control System Contents Page General Purpose...
How To Use A Power Supply On A Powerline 2.2 (Ai)
KNX/EIB Product documentation Issue: 05.08.2010 629x1220 Push button sensor 3 comfort 1-gang Push button sensor 3 comfort 2-gang (1+1) Push button sensor 3 comfort 3-gang Push button sensor 3 comfort 4-gang
IFC 070 Technical Datasheet
IFC 070 Technical Datasheet Electromagnetic signal converter Battery driven with low energy consumption Quick and easy to install and operate External data logger and GSM module for remote data transfer
Operating Instructions VEGABAR 66. Submersible pressure transmitter with CERTEC measuring cell. Foundation Fieldbus - climate compensated
Operating Instructions Submersible pressure transmitter with CERTEC measuring cell VEGABAR 66 Foundation Fieldbus - climate compensated Document ID: 36793 2 Contents Contents 1 About this document 1.1
Series 510 Submersible Level Transmitters
Series 510 Submersible Level Transmitters The Series 510 Submersible Level Transmitters are solid state instruments designed for direct submergence into many types of liquid for quick, accurate and reliable
RAY-MAX Integrated Solar Power Strip
RAY-MAX Integrated Solar Power Strip 600008, 600009, 600010, 600208, 600209, 600210 Owner s Manual NEXTRONEX, INC. Revision Date: 10/27/14 Contents 1. Safety Instructions... 3 2. General Equipment Warnings...
Mounting Instructions. Torque Transducer. A0329 3.2 en
Mounting Instructions Torque Transducer T5 T5 Contents 3 Page Safety instructions.............................................. 4 1 Measuring characteristics..................................... 7 2 Mounting.....................................................
Compact pressure switch Flameproof enclosure Ex d Model PCA
Mechatronic pressure measurement Compact pressure switch Flameproof enclosure Ex d Model PCA WIKA data sheet PV 33.31 for further approvals see page 4 Process Compact Series Applications Pressure monitoring
FLOW CALCULATOR INSTRUCTION MANUAL MESURES BAMOPHOX 759 26-06-2007 759 M1 02 E MES FLOW CALCULATOR 759-02/1
BAMOPHOX 759 E - M FLOW CALCULATOR INSTRUCTION MANUAL MESURES 22, Rue de la Voie des Bans - Z.I. de la Gare - 95100 ARGENTEUIL Tél : (33) 01 30 25 83 20 - Web : www.bamo.fr Fax : (33) 01 34 10 16 05 -
UM-X Field display for continous level sensors
Technical Documentation Field display for continous level sensors 10/2007 Edition: 1 Item No.: 207120 FAFNIR GmbH Bahrenfelder Str. 19 D-22765 Hamburg Telephone: +49 (0)40-39 82 07-0 Fax: +49 (0)40-3 90
Elektromotoren und Gerätebau Barleben GmbH
Elektromotoren und Gerätebau Barleben GmbH OPERATING INSTRUCTIONS Transformer Protection Relay NM Series (Buchholz principle) Elektromotoren und Gerätebau Barleben GmbH Table of contents Page 1. Safety
Inductive sensor NI10-M18-Y1X-H1141
ATEX category II 1 G, Ex zone 0 ATEX category II 1 D, Ex zone 20 SIL2 as per IEC 61508 Threaded barrel, M18 x 1 Chrome-plated brass DC 2-wire, nom. 8.2 VDC Output acc. to DIN EN 60947-5-6 (NA- MUR) M12
I.S. 1 remote I/O system Redundant coupling via PROFIBUS DP
I.S. 1 remote I/O system Redundant coupling via PROFIBUS DP 1. Functions An I. S. 1 fieldstation can be equipped with a primary and a redundant central unit (), whereby each has its own independent PROFIBUS
4 non-safe digital I/O channels 2 IO-Link Master V1.1 slots. Figure 1. Figure 2. Type code. TBPN-L1-FDIO1-2IOL Ident no. 6814053.
PROFINET slave Integrated Ethernet switch 100 Mbps supported 2 x M12, 4-pin, D-coded, Ethernet fieldbus connection Glass-fiber reinforced housing Shock and vibration tested Potted module electronics Protection
ABB Drives. User s Manual HTL Encoder Interface FEN-31
ABB Drives User s Manual HTL Encoder Interface FEN-31 HTL Encoder Interface FEN-31 User s Manual 3AUA0000031044 Rev B EN EFFECTIVE: 2010-04-06 2010 ABB Oy. All Rights Reserved. 5 Safety instructions
Short Form Catalogue. Alarm Systems. Reliable Supervision and Control
Short Form Catalogue Alarm Systems Reliable Supervision and Control Alarm Monitors and Indicators The SELCO product range includes a number of alarm monitors and indicator panels for use in numerous applications.
Safety instructions VEGAFLEX FX8*(*).FC/ O****A/H*****
Safety instructions VEGAFLEX FX8*(*).FC/ O****A/H***** FM 3046039 Class I Div 1, Groups A, B, C and D Class II Div 1, Groups E, F and G; Class III Class I, Zone 0, AEx ia IIC Ga, Ga/Gb, Gb Document ID:
Installation Instructions for FT-10 Network PowerCommand ATS Communication Module (NCM) Kits 541 0812 and 541 0868
Instruction Sheet 10-2004 Installation Instructions for FT-10 Network PowerCommand ATS Communication Module (NCM) Kits 541 0812 and 541 0868 PowerCommand is a registered trademark of Cummins Inc. InPower
Modular I/O System Analog and Digital Interface Modules
OPERATING INSTRUCTIONS Modular I/O System Analog and Digital Interface Modules Installation Operation Maintenance Document Information Document ID Title: Operating Instructions Modular I/O System Part
Operating Instructions
Important information: These instructions contain safety information, read and follow them carefully. Dialight will not accept any responsibility for injury, damage or loss which may occur due to incorrect
Shutter Actuator Standard, 4-fold, 230 VAC, MDRC RA/S 4.230.1, GH Q631 0076 R0111. ABB i-bus EIB
, GH Q631 0076 R0111 2CDC 071 240 F0003 The Shutter Actuator Standard is used to control a maximum of four independent 230 VAC drives for positioning shutters, blinds, awnings and other hangings as well
