Artificial Neural Network Controlled DSTATCOM for Power Quality Improvement
|
|
|
- Myrtle Malone
- 10 years ago
- Views:
Transcription
1 Artificial Neural Network Controlled for Power Quality Improvement S. Sherin Jasper M.E. Department of Power electronics and drives, Sri Shakthi Institute of engineering and technology, Coimbatore, Tamil Nadu. India Abstract: The paper intends to develop the artificial neural network control algorithm for the control of for the improvement of power quality. The presence of nonlinear loads makes the voltage to be deviated and current to be distorted from its sinusoidal waveform quality. Thus harmonics elimination, load balancing and voltage regulation is the heavy task that has to be accomplished to maintain the quality of the power. The performance of any device depends on the control algorithm used for the reference current estimation and gating pulse generation scheme. Thus the artificial neural network based Back Propagation (BP) algorithm has been proposed to generate the triggering pulses for the three phase H bridge inverter ().The fundamental weighted value of active and reactive power components of load currents which are required for the estimation of reference source current is calculated by using BP-based control algorithm. Based on the difference of the target voltage and the generated voltage, the triggering pulse for the inverter is obtained by the BP algorithm. Then the voltage is injected at the point of common coupling to compensate the reactive power. Thus by regulating the voltage and compensation of reactive power, the power quality can be improved. The simulation modelling of the Back propagation algorithm controlled and the PWM controlled and the comparative analysis of the algorithms is presented in this paper. Index Term:, Artificial Neural Network, Back propagation (BP) control algorithm, Reference current Estimation, Power quality. I. MOTIVATION Power quality in distribution systems affects all the electrical and electronics equipment that are connected. This measures the deviation in the measurement of frequency, current and Voltage of the system. The use of power converters in power supplies, adjustable speed drives, is continuously increasing in recent years. This equipment draws harmonics currents from AC mains and increases the supply demands. The classification of loads includes linear (lagging power factor loads), nonlinear (current or voltage source type of harmonic generating loads), unbalanced and mixed types of loads. The power quality problems associated with these loads include, load unbalancing, harmonics, high reactive power burden, voltage variation. The power quality problems are compensated in a distribution system by the Custom Power devices. These custom power devices are classified as the (Distribution Static Compensator), DVR (Dynamic Voltage Restorer) and UPQC (Unified Power Quality Conditioner). The power quality at the Point of common coupling is governed by standards such as IECSC77A, IEEE , IEEE and IEC , etc. The block diagram of the proposed system consists of the three phase supply supplying the nonlinear load, block, interfacing inductor, and the controller. The controller used in this project is the Back Propagation method, which is the neural network controlled algorithm. The effectiveness of depends upon the control algorithm used for generating the switching signals for the voltage source converter and value of interfacing inductors. Many control algorithms are reported in the literature based on the instantaneous reactive power theory, deadbeat or predictive control instantaneous symmetrical component theory nonlinear control technique, modified power balance theory, enhanced phase locked loop technique, Adaline control technique, synchronous reference frame control technique, ANN and fuzzy based controller, SVM based controller, correlation and cross-correlation coefficients based control algorithm for the control of. In this Paper, the designed system will be applied to detect transient voltage in electrical power systems. The problem of power quality is detected by artificial neural network based BP algorithm. The performance of the designed system will be tested through a simulation platform designed in MATLAB/Simulink. II. BLOCK DIAGRAM OF ANN CONTROLLED Figure 1: Block diagram of the ANN controlled Copyright to IJIREEICE DOI /IJIREEICE
2 III. The D-STATCOM is a three phase shunt connected reactive power compensation equipment, whose output can be varied so as to maintain control of specific parameters of the electric power system by the generation and /or absorption of the reactive power. The D- STATCOM consists of three phase GTO/IGBT voltage source inverter (VSI), a coupling transformer with a leakage reactance and DC capacitor. The topologies can be classified based on of switching devices, use of transformers for isolation, use of transformers for neutral current compensation. The ac voltage difference across the leakage reactance power exchange between the Power system and the at the bus bar can be regulated to improve the voltage profile of the power system. This constitutes the primary duty of the. However a secondary damping function is added in to the D- STATCOM for enhancing power system oscillation stability. The D-STATCOM employs solid state power switching devices and provides rapid controllability of magnitude and the phase angle of the phase voltages. The D- STATCOM provides operating characteristics that of the rotating Synchronous compensator without the mechanical inertia. The D-STATCOM has an inverter to convert the DC link voltage V dc on the capacitor to a voltage source of adjustable phase and magnitude. Therefore the D- STATCOM can be treated as a voltage controlled source or current controlled source. controlling the, the Back propagation, a neural network based control algorithm is used. The is operated for the compensation of lagging power factor balanced load to correct the power factor at source side or to regulate the voltage at PCC. In ZVR mode, injects currents to regulate the PCC voltage at the desired reference value of the voltage and the source currents may be leading or lagging currents depending on the reference value of PCC voltage. The three basic operation modes of the D-STATCOM for the output current, I vary depending upon V i. Figure 2: Circuit Diagram of VSC- Based A voltage source converter (VSC)-based is connected to a three phase ac mains feeding three phase linear/nonlinear loads with internal grid impedance. The device is realized using six IGBTs (insulated gate bipolar transistors) switches with anti-parallel diodes. Three phase loads may be a lagging power factor load or an unbalance load or a nonlinear load. A RC filter is connected to the system in parallel with the load and the compensator to reduce switching ripples in the PCC voltage injected by switching of. For reducing ripples in compensating current, interfacing inductors are used at AC side of VSC. The performance of depends upon the accuracy of harmonic current detection. For Figure 3: Operation of (a) No load mode (V s =V i ),(b) Capacitive mode, (c) Inductive mode The currents (i Cabc ) are injected as required compensating currents to cancel the reactive power components and harmonics of the load currents so that loading due to reactive power component/harmonics is reduced on the distribution system. The controller of the D-STATCOM is used to operate the inverter in such a way that the phase angle between the inverter voltage and the line voltage is dynamically adjusted so that the D- STATCOM generates or absorbs the desired VAR at the point of connection. The phase of the output voltage of the inverter V i, is controlled in the same way as the distribution system voltage. The is operated for the compensation of lagging power factor balanced load to correct the power factor at source side or to regulate the voltage at the point of common Coupling.. In ZVR mode, injects currents to regulate the PCC voltage at the desired reference value of the voltage and depending on the reference value of PCC voltage the source currents may be leading or lagging currents. Copyright to IJIREEICE DOI /IJIREEICE
3 IV. VOLTAGE CONROLLER The aim of the control scheme is to maintain constant voltage magnitude at the point where a sensitive load is connected. urbances. The control system only measures the r.m.s voltage at the load point, i.e., no reactive power measurements are required. The VSC switching order is based on a sinusoidal PWM technique which offers simplicity and good response. PWM methods offer a more flexible option for a low power application which is the existing system. Thus the new approach of using the artificial neural network controlled controller for is proposed in this project. A. EXISTING SYSTEM: Sinusoidal Pulse Width Modulation control In pulse width modulation control, the converter switches are turned on and off several times during a half cycle and IV. output voltage is controlled by varying the width of the pulses. The gate signals are generated by comparing a triangular wave with a DC signal. The lower order harmonics can be eliminated or reduced by selecting the number of pulses per half cycle. However increasing the number of pulses would also increase the magnitude of higher order harmonics which could easily be filtered out. The width of the pulses can be varied to control the output voltage. However the pulse width of pulses could be different. It is possible to choose the widths of pulses in such a way that certain harmonics can be eliminated. The most common way of varying the width of the pulses is the Sinusoidal Pulse Width Modulation. In SPWM the displacement factor is unity and the power factor is improved. The lower order harmonics are eliminated and reduced. The SPWM pulses are generated and the was controlled in the open loop response. B. PROPOSED SYSTEM: Artificial Neural architecture A BP algorithm is implemented in a three phase shunt connected custom power device known as for the extraction of the weighted value of load active power and reactive power current components in nonlinear loads. The BP algorithm is used for harmonic suppression and load balancing in PFC and zero voltage regulation (ZVR) modes with dc voltage regulation of. In this BP algorithm, the training of weights has three stages. Feed forward of the input signal training, Calculation and BP of the error signals, Upgrading of training weights. Figure 4 : Standard model of BP algorithm The BP algorithm has one or more than one layer. It is based on a mathematical formula and does not need special features of function in the learning process. It also has smooth variation on weight correction due to batch updating features on weights. It is slow during the training process due to more number of learning steps, but after the training of weights, the algorithm produces very fast trained output response. Continuity, non-decreasing monotony and differentiability are the main characteristics of BP algorithm. In this application, the proposed control algorithm on a is implemented for the compensation of nonlinear loads. The initial output pattern is compared with the desired output pattern and the weights are adjusted by the algorithm to minimize the error. The iterative process finishes when the error becomes near null. REFERENCE CURRENT GENERATION A BP training algorithm is used to estimate the three phase weighted value of load active power current components (w ap, w bp and w cp ) and reactive power current components (w aq, w bq, and w cq ) from polluted load currents using the feed forward and supervised principle. A. DERIVATION OF REFERENCE CURRENTS Figure 5 : Proposed modeling of BP algorithm In this estimation, the input layer for three phases (a, b, and c) is expressed as I Lap =w o + i La u ap + i Lb u bp + i Lc u cp (1) I Lbp =w o + i Lb u bp + i Lc u cp + i La u ap (2) I Lcp =w o + i Lc u cp + i La u ap + i Lb u bp (3) Copyright to IJIREEICE DOI /IJIREEICE
4 Where w o is the selected value of the initial weight and u ap,u bp,and u cp are the in-phase unit templates. In-phase unit templates are estimated using sensed PCC phase voltages (v sa,v sb and v sc ).It is the relation of the phase voltage and the amplitude of the PCC voltage (v t ).The amplitude of sensed PCC voltages is estimated as v t = [2 (v sa 2 + v sb 2 + v sc 2 )/3] (4) The in-phase unit templates of PCC voltages (u ap,u bp, and u cp ) are estimated as [13] u ap =v sa /v t u bp =v sb /v t u cp =v sc /v t (5) The extracted values of I Lap,I Lbp and I Lcp are passed through a sigmoid function as an activation function, and the output signals (Z ap, Z bp, and Z cp ) of the feed forward section are expressed as Z ap =f(i Lap ) = 1/(1 + e I Lap ) (6) Z bp =f(i Lbp ) = 1/(1 + e I Lbp ) (7) Z cp =f(i Lcp ) = 1/(1 + e I Lcp ) (8) The estimated values of Z ap,z bp and Z cp are fed to a hidden layer as input signals. The three phase outputs of this layer (I ap1, I bp1 and I cp1 ) before the activation function are expressed as component of the load current and the output of the feed forward section of the algorithm at the nth instant, respectively. f (I ap1 ) and μ are represented as the derivative of I ap1 components and the learning rate. Similarly, for phase b and phase c, the updated weighted values of the active power current components of the load current are expressed as w bp (n)=w p (n)+μ {w p (n) w bp1 (n)} f (I bp1 )z bp (n) (13) w cp (n)=w p (n)+μ {w p (n) w cp1 (n)} f (I cp1 )z cp (n) (14) The extracted values of I ap1, I bp1, and I cp1 are passed through a sigmoid function as an activation function to the estimation of the fundamental active components in terms of three phase weights w ap1, w bp1, and w cp1 as w ap1 =f(i ap1 ) = 1/(1 + e I ap1 ) (15) w bp1 =f(i bp1 ) = 1/(1 + e I bp1 ) (16) w cp1 =f(i cp1 ) = 1/(1 + e I cp1 ) (17) The average weighted amplitude of the fundamental active power components (w p ) is estimated using the amplitude sum of three phase load active power components (w ap1,w bp1 and w cp1 ) divided by three. It is required to realize load balancing features of. Mathematically, it is expressed as I ap1 =w o1 + w ap Z ap + w bp Z bp + w cp Z cp (9) w p = (w ap1 + w bp1 + w cp1 )/3 (18) I bp1 =w o1 + w bp Z bp + w cp Z cp + w ap Z ap (10) I cp1 =w o1 + w cp Z cp + w ap Z ap + w bp Z bp (11) Where w o1,w ap, w bp, and w cp are the selected value of the initial weight in the hidden layer and the updated values of three phase weights using the average weighted value (w p )of the active power current component as a feedback signal, respectively. The updated weight of phase a active power current components of load current w ap at the nth sampling instant is expressed as w ap (n) = w p (n) + μ {w p (n) w ap1 (n)} f (I ap1 )z ap (n) (12) Where w p (n) and w ap (n) are the average weighted value of the active power component of load currents and the updated weighted value of phase a at the nth sampling instant, respectively, and w ap1 (n) and z ap (n) are the phase a fundamental weighted amplitude of the active power First-order low-pass filters are used to separate the low frequency components. k denotes the scaled factor of the extracted active power components of current in the algorithm. After separating the low-frequency components and scaling to the actual value because the output of the activation function is between 0 and 1, it is represented as w LpA. Similarly, the weighted amplitudes of the reactive power components of the load currents (w aq, w bq, and w cq ) of the fundamental load current are extracted as I Laq =w o + i La u aq + i Lb u bq + i Lc u cq (19) ILbq= w o + i La u aq + i Lb u bq + i Lc u cq (20) ILcq= w o + i La u aq + i Lb u bq + i Lc u cq (21) Where w o is the selected value of the initial weight and u aq, u bq and u cq are the quadrature components of the unit template. The quadrature unit templates (u aq, u bq, and u cq ) of the phase PCC voltage are estimated using (5) as Copyright to IJIREEICE DOI /IJIREEICE
5 u aq =( u bp + u cp )/ 3, u bq =(3u ap + u bp u cp )/2 3; u cq =( 3u ap + u bp u cp )/2 3 (22) The extracted values of I Laq, I Lbq, and I Lcq are passed through a sigmoid function as an activation function to the estimation of Z aq, Z bq, and Z cq Z aq =f(i Laq ) = 1/(1 + e I Laq ) (23) Z bq =f(i Lbq ) = 1/(1 + e I Lbq ) (24) Z cq =f(i Lcq ) = 1/(1 + e I Lcq ) (25) The estimated values of Z aq, Z bq, and Z cq are fed to the hidden layer as input signals. The three phase outputs of this layer (I aq1, I bq1, and I cq1 ) before the activation function can be represented as I aq1 =w o1 + w aq Z aq + w bq Z bq + w cq Z cq (26) Ibq1 =w o1 + w aq Z aq + w bq Z bq + w cq Z cq (27) Icq1 = w o1 + w aq Z aq + w bq Z bq + w cq Z cq (28) Where w o1, w aq, w bq, and w cq are the selected value of the initial weight in the hidden layer and the updated three weights using the average weighted value of the reactive power components of currents (w q ) as a feedback signal, respectively. The updated weight of the phase a reactive power components of load currents w aq at the nth sampling instant is expressed as w aq (n) = w q (n) + μ {w q (n) w aq1 (n)} f (I aq1 )z aq (n) (29) w q (n) and w aq (n) are the average weighted value of the active power component of load currents and the updated weight in the nth sampling instant, respectively, and w aq1 (n)and z aq (n) are the phase a weighted amplitude of the reactive power current component of load currents and the output of the feed forward section of the algorithm at the nth instant, respectively. f(i aq1 ) and μ are presented as the derivative of I aq1 components and the learning rate. Similarly, for phase b and phase c, the updated weighted values of the reactive power current components of the load current are expressed as w bq (n) =w q (n) + μ {w q (n) w bq1 (n)} f (I bq1 )z bq (n) (30) w cq (n) =w q (n) + μ {w q (n) w cq 1(n)} f (I cq 1)z cq (n) (31) The extracted values of I aq1, I bq1, and I cq1 are passed through an activation function to the estimation of the fundamental reactive component in terms of three phase weights w aq1, w bq1, and w cq1 as w aq1 =f(i aq1 ) = 1/(1 + e I aq1 ) (32) w bq1 =f(i bq1 ) = 1/(1 + e I bq1 ) (33) w cq1 =f(i cq1 ) = 1/(1 + e I cq1 ) (34) The average weight of the amplitudes of the fundamental reactive power current components (w q ) is estimated using the amplitude sum of the three phase load reactive power components of the load current (w aq1, w bq1, and w cq1 ) divided by three. Mathematically, it is expressed as w q = (w aq1 + w bq1 + w cq1 )/3 (35) First-order low-pass filters are used to separate the low frequency component. r denotes the scaled factor of the extracted reactive power components in the algorithm. After separating low-frequency components and scaling to the actual value because the output of the activation function is between 0 and 1, it is represented as w LqA. A. Amplitude of Active Power Current Components of Reference Source Currents An error in the dc bus voltage is obtained after comparing the reference dc bus voltage v dc * and the sensed dc bus voltage v dc of a VSC, and this error at the nth sampling instant is expressed as v de (n) = v dc*( n) v dc (n). (36) This voltage error is fed to a proportional integral (PI) controller whose output is required for maintaining the dc bus voltage of the. At the nth sampling instant, the output of the PI controller is as follows w dp (n)= w dp (n 1)+k pd {v de (n) v de (n 1)}+k id v de (n) (37) Where k pd and k id are the proportional and integral gain constants of the dc bus PI controller. v de (n) and v de (n 1) are the dc bus voltage errors in the nth and (n 1)th instant, and w dp (n) and w dp (n 1) are the amplitudes of the active power component of the fundamental reference current at the nth and(n 1)th instant, respectively. The amplitude of the active power current components of the reference source current (w spt ) is estimated by the addition of the output of the dc bus PI controller (w dp ) and the average magnitude of the load active currents (w LpA ) as w spt = w dp + w LpA. (38) B. Amplitude of Reactive Power Components of Reference Source Currents: An error in the ac bus voltage is achieved after comparing the amplitudes of the reference ac bus voltage v t * and the sensed ac bus voltage v t of a VSC. The extracted ac bus voltage error vt at the nth sampling instant is expressed as Copyright to IJIREEICE DOI /IJIREEICE
6 v te (n) = v t * (n) v t (n) (39) The weighted output of the ac bus PI controller w qq for regulating the ac bus terminal voltage at the nth sampling instant is expressed as w qq (n) = w qq (n 1)+k pt {v te (n) v te (n 1)}+k it v te (n) (40) Where w qq (n) is part of the reactive power component of the source current and it is renamed as wqq. K pt and k it are the proportional and integral gain constants of the ac bus voltage PI controller. The amplitude of the reactive power current components of the reference source current (w sqt ) is calculated by subtracting the output of the voltage PI controller (w qq ) and the average load reactive currents (w LqA ) as w sqt = w qq w LqA (41) C. Estimation of Reference Source Currents and Generation of IGBT Gating Pulses: Three phase reference source active and reactive current components are estimated using the amplitude of three phase (a, b and c) load active power current components, PCC voltage in-phase unit templates, reactive power current components, and PCC quadrature voltage unit templates as i sap =w spt u ap, i sbp = w spt u bp, i scp = w spt u cp (42) i saq =w sqt u aq, i sbq = w sqt u bq, i scq = w sqt u cq. (43) The addition of reference active and reactive current components is known as reference source currents, and these are given as I sa * = i sap + i saq, I sb * = i sbp + i sbq, I sc *= i scp + i scq (44) Figure 6 : Simulink modeling of PWM controlled B. RESULTS OF PWM CONTROLLED The below figure shows the waveform of source currents (i sa, i sb,i sc ) load currents (i La, i Lb, i Lc ) and compensating currents (i Ca,i Cb, i Cc ) with PCC line voltage (v ab ) under unbalanced nonlinear loads. The sensed source currents (i sa, i sb, i sc ) and the reference source currents (i sa *, i sb *, i sc * ) are compared, and current error signals are amplified through PI current regulators; their outputs are fed to a pulse width modulation (PWM) controller to generate the gating signals for insulated-gate bipolar transistors(igbts) S1 to S6 of the VSC used as a V. SIMULATION AND RESULTS Figure 7 : Dynamic performance of with PWM controller a)v Sabc b)i Sabc c)i Labc d)i Cabc e)v dc A. EXISTING SYSTEM: PWM CONTROLLED This shows the Simulink modeling of in which the gate signals are generated by the PWM controller The VSC switching strategy is based on a sinusoidal PWM technique which offers simplicity and good response. Since custom power is a relatively lowpower application, PWM methods offer a more flexible option which is the existing system. C. THD ANALYSIS OF PWM CONTROLLED Harmonic spectra of phase a voltage at PCC (v sa ), source current (i sa ) and load current (i La ) are shown in figure. THDs of the phase a at PCC voltage, source current, load current are observed 0.01%, 18.61% and 14.25% respectively. Copyright to IJIREEICE DOI /IJIREEICE
7 Figure 8: Waveforms and harmonic spectra of PCC voltage of phase a E. UNIT TEMPLATE ESTIMATION The figure shows the mathematical modeling of Unit template estimation which is essential for the reference current calculation in MATLAB/Simulink environment. Figure 12: Mathematical modeling of Unit templates Figure 9: Waveforms and harmonic spectra of Source current of phase a F. REFERENCE CURRENT CALCULATION The figure shows the mathematical modeling of reference current calculation in MATLAB/Simulink environment. Figure 10: Waveforms and harmonic spectra of load current of phase a D. PROPOSED SYSTEM: Neural Network Controlled The figure shows the modeling of artificial neural network controlled algorithm in the MATLAB/Simulink environment. Figure 13: Mathematical modeling of Reference currents calculation G. CONTROLLER Figure 14: Mathematical Modeling of controller H. RESULTS OF NEURAL NETWORK CONTROLLED Figure 11 : Simulink Modeling of Neural Network Controlled The figure shows the waveform of source currents (i sa, i sb,i sc ) load currents (i La, i Lb, i Lc ) and compensating currents (i Ca,i Cb, i Cc ) with PCC line voltage (v ab ) under unbalanced nonlinear loads. Copyright to IJIREEICE DOI /IJIREEICE
8 Figure 18 : Waveforms and harmonic spectra of load current of phase a in PFC mode VI. ANALYSIS ON THE PERFORMANCE OF Figure 15 : Dynamic Performance of under Non Linear Load in PFC mode a)v Sabc b)i Sabc c)i La d) I Lb e) I Lc f) ICa g) ICb h) ICc i)i Labc j)v dc I. THD ANALYSIS OF NEURAL NETWORK CONTROLLED VII. Harmonic spectra of phase a voltage at PCC (v sa ), source current (i sa ) and load current (i La ) are shown in figure. THDs of the phase a at PCC voltage, source current, load current are observed 0.02%, 2.46% and 11.50% respectively. Performance parameters PCC voltage (V), %THD Source current (A), % THD Load current (A),% THD Dc bus voltage (V) With PWM controller-non Linear load ( 3 Phase uncontrolled rectifier with RL load) With BP controller-non Linear load ( 3 Phase uncontrolled rectifier with RL load) V,0.01% V,0.02% A,18.61% 30.1A,2.46% 40.06A, 14.25% 36.97%, 11.50% 700V Table 1: Comparative analysis on Performance of in PFC mode PARAMETERS USED IN SIMULATION: 700V This table shows the parameters that are considered to simulate the PWM controlled and the Artificial Neural Network controlled. PARAMETERS ANN CONTROLLED PWM CONTROLLED AC Supply Source, three phase 415 V(L-L), 50 HZ 415 V(L-L), 50 HZ Figure 16: Waveforms and harmonic spectra of PCC voltage of phase a in PFC mode. Figure 17 : Waveforms and harmonic spectra of Source current of phase a in PFC mode Source Impedance L s = 15 mh L s = 15 mh Non-linear: Three phase full bridge uncontrolled rectifier Ripple filter Switching frequency of Inverter Reference dc bus voltage R= 13Ω and L= 200mH R f =5 Ω, Cf = 10μF 10kHz R= 13Ω and L= 200mH R f =5 Ω, C f = 10μF 10kHz 700 V 700 V Copyright to IJIREEICE DOI /IJIREEICE
9 Interfacing Inductor(Lf) Gains of PI controller for dc bus voltage Gains of voltage PI controller Cut off frequency of low pass filter used in dc bus voltage Cut off frequency of low pass filter used in ac bus voltage Cut off frequency of low pass filter used in dc bus voltage 2.75mH 2.75mH k pd =3.1, k id =0.9 k pd =3.1, k id =0.9 k pt =2.95, k it =4 k pt =2.95, k it =4 15 Hz 15 Hz 10Hz 10Hz 15 Hz - Learning rate (μ) Table 2: Parameters of the PWM controlled and ANN controlled VIII. CONCLUSION A three phase VSC based has been implemented for compensation of nonlinear loads using BPT control algorithm to verify its effectiveness. The proposed algorithm has been used for extraction of reference source currents to generate the switching pulses for IGBTs of VSC of. Various functions of such as, load balancing and harmonic elimination have been demonstrated in PFC mode with DC voltage regulation of. From simulation and implementation results, it is concluded that and its control algorithm have been found suitable for compensation of nonlinear loads. These results show satisfactory performance of the BP control algorithm for harmonics elimination according to IEEE-519 guidelines in order of less than 5%. The DC bus voltage of the has also been regulated to rated value without any overshoot or undershoots during load variation. Large training time in the application of complex system, selection of number of hidden layer in system is the disadvantage of this algorithm. REFERENCES [1] Bhim Singh, P. Jayaprakash, D. P. Kothari, Ambrish Chandra, Kamal Al Haddad Comprehensive Study of Configurations IEEE Transactions on Industrial Informatics, VOL. 10, NO. 2, MAY 2014 [2] Bhim Singh, Sabha Raj Arya Design and control of a for power quality improvement using cross correlation function approach International Journal of Engineering, Science and Technology Vol. 4, No. 1, 2012, pp , April 2012 [3] Alpesh Mahyavanshi, M. A. Mulla, R. Chudamani Reactive Power Compensation by Controlling the International Journal of Emerging Technology and Advanced Engineering, Volume 2, Issue 11, November 2012 [4] K.L.Sireesha, K.Bhushana Kumar Power Quality Improvement in Distribution System Using D-STATCOM IJEAR Vol. 4, Issue Spl- 1, Jan - June 2014s [5] S. L. Pinjare, Arun Kumar M, Implementation of Neural Network Back Propagation Training Algorithm on FPGA International Journal of Computer Applications Volume 52 No.6, August 2012 [6] Anju Tiwari, Prof. Minal Tomar An Extensive Literature Review on Power Quality Improvement using International Journal of Emerging Technology and Advanced Engineering, Volume 4, Issue 5, May 2014) [7] Sujin P. Ra, T. Ruban Deva Prakashb, L. Padma Sureshc ANN Based Voltage Flicker Mitigation with Using SRF Algorithm International Journal of Current Engineering and Technology, Vol.2, No.2 (June 2012) [8] R. C. Dugan, M. F. McGranaghan and H. W. Beaty, Electric Power Systems Quality, 2ed Ed., McGraw Hill, New York, [9] Alfredo Ortiz, Cristina Gherasim, Mario Manana, Carlos J. Renedo, L.Ignacio Eguiluz and Ronnie J. M. Belmans, Total harmonic distortion decomposition depending on distortion origin, IEEE Transactions on Power Delivery, vol. 20, no. 4, pp , October [10] Tzung Lin Lee and Shang Hung Hu, Discrete frequency-tuning activefilter to suppress harmonic resonances of closed-loop distribution powersystems, IEEE Transactions on Power Electronics, vol. 26, no. 1, pp , January [11] K. R. Padiyar, FACTS Controllers in Power Transmission and Distribution, New Age International, New Delhi, [12] IEEE Recommended Practices and requirement for Harmonic Control on electric power System, IEEE Std.519, [13] Tzung-Lin Lee, Shang-Hung Hu and Yu-Hung Chan, with positive-sequence admittance and negative-sequence conductance to mitigate voltage fluctuations in high-level penetration of distributed generation systems, IEEE Transactions on Industrial Electronics, vol.60, no. 4, pp , April [14] B. Singh, P. Jayaprakash and D.P. Kothari, Power factor correction and power quality improvement in the distribution system, Journal of Electrical India, pp , April, [15] Jinn-Chang Wu, Hurng Liahng Jou, Ya Tsung Feng, Wen Pin Hsu, Min Sheng Huang, and WenJet Hou, Novel circuit topology for three-phase active power filter, IEEE Transactions on Power Delivery, vol. 22, no. 1, pp , January BIOGRAPHY S. Sherin Jasper did her Bachelor of Engineering in Electrical & Electronics Engineering at Government college of Engineering, Tirunelveli and doing M.E degree in Electrical engineering with specialization in Power Electronics & Drives at Sri Shakthi Institute of Engineering and Technology, Coimbatore, India. Her research interests include Power Electronics, Power Quality. Copyright to IJIREEICE DOI /IJIREEICE
How To Improve Power Quality
Power Quality Improvement Of Three Phase Four Wire Distribution System Using VSC With A Zig-Zag Transformer Sajith Shaik *, I.Raghavendar ** *(Department of Electrical Engineering, Teegala Krishna Reddy
Harmonic Reduction and Load Balancing of Three Phase Four Wire DSTATCOM using Three Leg VSC and a Zig Zag Transformer
IJSRD - International Journal for Scientific Research & Development Vol. 3, Issue 05, 2015 ISSN (online): 2321-0613 Harmonic Reduction and Load Balancing of Three Phase Four Wire DSTATCOM using Three Leg
How To Improve Power Quality
Neutral Current compensation in three phase four wire DSTATCOM using Three Leg VSC and a Zig Zag Transformer 1 Ramya A R, 2 T.M.Vasantha Kumar, 3 K.R.Mohan 1,2,3 Dept. of Electrical and Electronics Engineering
IJESRT. Scientific Journal Impact Factor: 3.449 (ISRA), Impact Factor: 2.114 [633] [Choudhary, 3(12): December, 2014] ISSN: 2277-9655
IJESRT INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY Performance of Capacitor Supported SRF based DSTATCOM in Three-Phase Four-Wire Distribution System under Linear and Non-Linear
NEURO-FUZZY BASED POWER QUALITY IMPROVEMENTS IN A THREE PHASE FOUR WIRE DISTRIBUTION SYSTEM USING DSTATCOM
NEURO-FUZZY BASED POWER QUALITY IMPROVEMENTS IN A THREE PHASE FOUR WIRE DISTRIBUTION SYSTEM USING DSTATCOM E.Babu 1,R.Subramanian 2 1, Department of Electrical and electronics engg 2 Department of Electrical
Enhancement of load balancing for dynamic loads using D-STATCOM
Enhancement of load balancing for dynamic loads using D-STATCOM Priyanka Upadhyay 1, Baseem Khan 2 1,2 Electrical and Electronics Department, SCOPE College of Engineering Bhopal, M.P., India Abstract In
COMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS
COMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS Afshin LASHKAR ARA Azad University of Dezfoul - Iran [email protected] Seyed Ali NABAVI NIAKI University of Mazandaran
Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies
Soonwook Hong, Ph. D. Michael Zuercher Martinson Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies 1. Introduction PV inverters use semiconductor devices to transform the
Simulation and Analysis of PWM Inverter Fed Induction Motor Drive
Simulation and Analysis of PWM Inverter Fed Induction Motor Drive C.S.Sharma, Tali Nagwani Abstract Sinusoidal Pulse Width Modulation variable speed drives are increasingly applied in many new industrial
The Grid Interconnection of Renewable Energy at Distribution Level with the Features of High Power-Quality Improvement
The Grid Interconnection of Renewable Energy at Distribution Level with the Features of High Power-Quality Improvement Surendar Nagarapu 1, Shaik Khamuruddin 2, and Durgam. Kumara Swamy 3 1 M.Tech, Scholar
New Pulse Width Modulation Technique for Three Phase Induction Motor Drive Umesha K L, Sri Harsha J, Capt. L. Sanjeev Kumar
New Pulse Width Modulation Technique for Three Phase Induction Motor Drive Umesha K L, Sri Harsha J, Capt. L. Sanjeev Kumar Abstract In this paper, various types of speed control methods for the three
MODELING AND SIMULATION OF A THREE-PHASE INVERTER WITH RECTIFIER-TYPE NONLINEAR LOADS
, pp. 7-1 MODELING AND SIMULAION OF A HREE-PHASE INERER WIH RECIFIER-YPE NONLINEAR LOADS Jawad Faiz 1 and Ghazanfar Shahgholian 2 1 School of Electrical and Computer Engineering, Faculty of Engineering,
Control of a 3-phase 4-leg active power filter under non-ideal mains voltage condition
Available online at www.sciencedirect.com Electric Power Systems Research 78 (008) 58 73 Control of a 3-phase 4-leg active power filter under non-ideal mains voltage condition Mehmet Ucar, Engin Ozdemir
MICRO HYDRO POWER PLANT WITH INDUCTION GENERATOR SUPPLYING SINGLE PHASE LOADS
MICRO HYDRO POWER PLANT WITH INDUCTION GENERATOR SUPPLYING SINGLE PHASE LOADS C.P. ION 1 C. MARINESCU 1 Abstract: This paper presents a new method to supply single-phase loads using a three-phase induction
Keywords: Self-Excited Induction Generator (SEIG), Single Phase Synchronous D-Q Frame Theory, Static Synchronous Compensator (STATCOM).
ISSN 2319-8885 Vol.04,Issue.20, June-2015, Pages:3756-3762 www.ijsetr.com Power Quality Improvement by using STATCOM for Three-Phase Loads MANJULA VIJAYALAKSHMI 1, M. PRAVEEN KUMAR 2 1 PG Scholar, Dept
POWER SYSTEM HARMONICS. A Reference Guide to Causes, Effects and Corrective Measures AN ALLEN-BRADLEY SERIES OF ISSUES AND ANSWERS
A Reference Guide to Causes, Effects and Corrective Measures AN ALLEN-BRADLEY SERIES OF ISSUES AND ANSWERS By: Robert G. Ellis, P. Eng., Rockwell Automation Medium Voltage Business CONTENTS INTRODUCTION...
Control Strategy for Three Phase Shunt Active Power Filter with Minimum Current Measurements
International Journal of Electrical and Computer Engineering (IJECE) Vol.1, No.1, September 2011, pp. 31~ 42 ISSN: 2088-8708 31 Control Strategy for Three Phase Shunt Active Power Filter with Minimum Current
Fundamentals of Power Electronics. Robert W. Erickson University of Colorado, Boulder
Robert W. Erickson University of Colorado, Boulder 1 1.1. Introduction to power processing 1.2. Some applications of power electronics 1.3. Elements of power electronics Summary of the course 2 1.1 Introduction
Three leg VSC Based DSTATCOM and T-Connected Transformer for Power Quality Improvement
International Journal of Applied Sciences, Engineering and Technology Vol. 0, No. 0, Jan-Dec 0 Three leg VSC Based DSTATCOM and T-Connected Transformer for Power Quality Improvement G. KEERTHANA and S.
v v v Keywords-- Power Quality, Shunt active filter, Indirect current control, ANN control
A Novel Shunt Active Filter Algorithms for a Three Phase System with Unbalanced Distorted-Source oltage Waveforms Feeding an Adjustable Speed Drive K. Sravanthi 1, CH. Sujatha 2 and Dr. K. Chandra Shekar
Improvements of Reliability of Micro Hydro Power Plants in Sri Lanka
Improvements of Reliability of Micro Hydro Power Plants in Sri Lanka S S B Udugampala, V Vijayarajah, N T L W Vithanawasam, W M S C Weerasinghe, Supervised by: Eng J Karunanayake, Dr. K T M U Hemapala
Parametric variation analysis of CUK converter for constant voltage applications
ISSN (Print) : 232 3765 (An ISO 3297: 27 Certified Organization) Vol. 3, Issue 2, February 214 Parametric variation analysis of CUK converter for constant voltage applications Rheesabh Dwivedi 1, Vinay
Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager
Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager Introduction There is a growing trend in the UPS industry to create a highly efficient, more lightweight and smaller UPS
Modelling, Simulation and Performance Analysis of A Variable Frequency Drive in Speed Control Of Induction Motor
International Journal of Engineering Inventions e-issn: 78-7461, p-issn: 319-6491 Volume 3, Issue 5 (December 013) PP: 36-41 Modelling, Simulation and Performance Analysis of A Variable Frequency Drive
Principles of Adjustable Frequency Drives
What is an Adjustable Frequency Drive? An adjustable frequency drive is a system for controlling the speed of an AC motor by controlling the frequency of the power supplied to the motor. A basic adjustable
A MULTILEVEL INVERTER FOR SYNCHRONIZING THE GRID WITH RENEWABLE ENERGY SOURCES BY IMPLEMENTING BATTERY CUM DC-DC CONERTER
A MULTILEVEL INVERTER FOR SYNCHRONIZING THE GRID WITH RENEWABLE ENERGY SOURCES BY IMPLEMENTING BATTERY CUM DC-DC CONERTER 1 KARUNYA CHRISTOBAL LYDIA. S, 2 SHANMUGASUNDARI. A, 3 ANANDHI.Y 1,2,3 Electrical
Analysis of AC-DC Converter Based on Power Factor and THD
Website: www.ijetae.com (SSN 50-459, SO 900:008 Certified Journal, Volume 3, ssue, February 03) Analysis of AC-DC Converter Based on Power Factor and THD Shiney.S.Varghese, Sincy George Department of Electrical
Modeling and Simulation of a Novel Switched Reluctance Motor Drive System with Power Factor Improvement
American Journal of Applied Sciences 3 (1): 1649-1654, 2006 ISSN 1546-9239 2006 Science Publications Modeling and Simulation of a Novel Switched Reluctance Motor Drive System with Power Factor Improvement
The design and performance of Static Var Compensators for particle accelerators
CERN-ACC-2015-0104 [email protected] The design and performance of Static Var Compensators for particle accelerators Karsten Kahle, Francisco R. Blánquez, Charles-Mathieu Genton CERN, Geneva, Switzerland,
How To Simulate A Multilevel Inverter
Neutral Point Potential Balance of Three Phase Three Level Diode Clamped Inverter BALAMURUGAN M GNANA PRAKASH M Dr.UMASHANKAR S School of Electrical Engineering School of Electrical Engineering School
Design a Phase Interleaving PFC Buck Boost Converter to Improve the Power Factor
International Journal of Innovation and Scientific Research ISSN 2351-8014 Vol. 11 No. 2 Nov. 2014, pp. 445-449 2014 Innovative Space of Scientific Research Journals http://www.ijisr.issr-journals.org/
Grid Interconnection of Renewable Energy Sources Using Modified One-Cycle Control Technique
Grid Interconnection of Renewable Energy Sources Using Modified One-Cycle Control Technique NKV.Sai Sunil 1, K.Vinod Kumar 2 PG Student, GITAM University, Visakhapatnam, India. Asst.Professor, Department
Line Reactors and AC Drives
Line Reactors and AC Drives Rockwell Automation Mequon Wisconsin Quite often, line and load reactors are installed on AC drives without a solid understanding of why or what the positive and negative consequences
MODELLING AND SIMULATION OF SVPWM INVERTER FED PERMANENT MAGNET BRUSHLESS DC MOTOR DRIVE
MODELLING AND SIMULATION OF SVPWM INVERTER FED PERMANENT MAGNET BRUSHLESS DC MOTOR DRIVE Devisree Sasi 1, Jisha Kuruvilla P Final Year M.Tech, Dept. of EEE, Mar Athanasius College of Engineering, Kothamangalam,
Three phase circuits
Three phase circuits THREE PHASE CIRCUITS THREE-PHASE ADVANTAGES 1. The horsepower rating of three-phase motors and the kva rating of three-phase transformers are 150% greater than single-phase motors
Modulation Strategies For Three Phase Inverters Supplying Unbalanced Three Phase Loads
ISSN (Online) : 9-875 ISSN (Print) : 47-67 International Journal of Innovative Research in Science, Engineering and Technology Volume, Special Issue, March 4 4 International Conference on Innovations in
7-41 POWER FACTOR CORRECTION
POWER FTOR CORRECTION INTRODUCTION Modern electronic equipment can create noise that will cause problems with other equipment on the same supply system. To reduce system disturbances it is therefore essential
AC/DC Power Supply Reference Design. Advanced SMPS Applications using the dspic DSC SMPS Family
AC/DC Power Supply Reference Design Advanced SMPS Applications using the dspic DSC SMPS Family dspic30f SMPS Family Excellent for Digital Power Conversion Internal hi-res PWM Internal high speed ADC Internal
Simulation of VSI-Fed Variable Speed Drive Using PI-Fuzzy based SVM-DTC Technique
Simulation of VSI-Fed Variable Speed Drive Using PI-Fuzzy based SVM-DTC Technique B.Hemanth Kumar 1, Dr.G.V.Marutheshwar 2 PG Student,EEE S.V. College of Engineering Tirupati Senior Professor,EEE dept.
Design and Simulation of Soft Switched Converter Fed DC Servo Drive
International Journal of Soft Computing and Engineering (IJSCE) ISSN: 2231-237, Volume-1, Issue-5, November 211 Design and Simulation of Soft Switched Converter Fed DC Servo Drive Bal Mukund Sharma, A.
Product Data Bulletin
Product Data Bulletin Power System Harmonics Causes and Effects of Variable Frequency Drives Relative to the IEEE 519-1992 Standard Raleigh, NC, U.S.A. INTRODUCTION This document describes power system
MODELING AND SIMULATION FOR VOLTAGE SAGS/SWELLS MITIGATION USING DYNAMIC VOLTAGE RESTORER (DVR)
MODELING AND SIMULATION FOR VOLTAGE SAGS/SWELLS MITIGATION USING DYNAMIC VOLTAGE RESTORER (DVR) 1 ROSLI OMAR, 2 NASRUDIN ABD RAHIM, 3 MARIZAN SULAIMAN 1 Rosli Omar.,Faculty Of Electrical, UTeM, Malacca,
Stand-Alone Single-Phase Power Generation Employing a Three- Phase Isolated Asynchronous Generator
Stand-Alone Single-Phase Power Generation Employing a Three- Phase Isolated Asynchronous Generator Abstract This paper deals with a stand-alone single-phase power generation using a three-phase isolated
Development of High Frequency Link Direct DC to AC Converters for Solid Oxide Fuel Cells (SOFC)
Development of High Frequency Link Direct DC to AC Converters for Solid Oxide Fuel Cells (SOFC) Dr. Prasad Enjeti Power Electronics Laboratory Department of Electrical Engineering College Station, TX -
Variable Frequency Drives - a Comparison of VSI versus LCI Systems
Variable Frequency Drives - a Comparison of VSI versus LCI Systems Introduction TMEIC is a leader in the innovative design and manufacture of large ac variable f requency drive systems. TMEIC has been
A Novel Three-Phase Active Power Filter
Rev. Energ. Ren. : Power Engineering (2001) 7784 A Novel ThreePhase Active Power Filter University of Wales, Swansea, UK Abstract The performance and dynamic characteristics of a threephase threewired
Power Electronics. Prof. K. Gopakumar. Centre for Electronics Design and Technology. Indian Institute of Science, Bangalore.
Power Electronics Prof. K. Gopakumar Centre for Electronics Design and Technology Indian Institute of Science, Bangalore Lecture - 1 Electric Drive Today, we will start with the topic on industrial drive
Power Flow Control Using Bidirectional Dc/Dc Converter for Grid Connected Photovoltaic Power System
International Journal of Innovative Research in Electronics and Communications (IJIREC) Volume 1, Issue 8, November 2014, PP 13-24 ISSN 2349-4042 (Print) & ISSN 2349-4050 (Online) www.arcjournals.org Power
How To Swap Output Phases Of A Power Supply With A Power Converter
211 2nd Power Electronics, Drive Systems and Technologies Conference A New phase sequence Detector for the Three-Phase Rotary Loads M. Alizadeh Bidgoli, A. Soori, M. Tavakoli Bina K. N. Toosi University
An Efficient AC/DC Converter with Power Factor Correction
An Efficient AC/DC Converter with Power Factor Correction Suja C Rajappan 1, K. Sarabose 2, Neetha John 3 1,3 PG Scholar, Sri Shakthi Institute of Engineering & Technology, L&T Bypass Road, Coimbatore-62,
A Novel Control Strategy of Three-phase, Four-wire UPQC for Power Quality Improvement
Journal of Electrical Engineering & Technology Vol. 7, No. 1, pp. 1~8, 2012 1 http://dx.doi.org/10.5370/jeet.2012.7.1.1 A Novel Control Strategy of Three-phase, Four-wire UPQC for Power Quality Improvement
Single-Stage High Power Factor Flyback for LED Lighting
Application Note Stockton Wu AN012 May 2014 Single-Stage High Power Factor Flyback for LED Lighting Abstract The application note illustrates how the single-stage high power factor flyback converter uses
UNINTERRUPTIBLE POWER SUPPLIES >9900AUPS UNINTERRUPTIBLE POWER SUPPLIES
UNINTERRUPTIBLE POWER SUPPLIES 9900A >9900AUPS UNINTERRUPTIBLE POWER SUPPLIES 9900A The 9900A UPS system uses the most advanced IGBT in both the converter and inverter with Digital Signal Processor (DSP)
Laboratory 4: Feedback and Compensation
Laboratory 4: Feedback and Compensation To be performed during Week 9 (Oct. 20-24) and Week 10 (Oct. 27-31) Due Week 11 (Nov. 3-7) 1 Pre-Lab This Pre-Lab should be completed before attending your regular
Understanding Delta Conversion Online "Power Regulation" - Part 2
Application Note #40 Understanding Delta Conversion Online "Power Regulation" - Part 2 Introduction This application note is the second in a series on delta conversion theory of operation. For complete
International Journal of Power Control Signal and Computation (IJPCSC) Vol. 2 No. 2 ISSN : 0976-268X
nternational Journal of ower Control Signal and Computation (JCSC) ol. 2 No. 2 SSN : 976-268X A NOEL SHUNT ACTE FLTER ALGORTHMS FOR A THREE HASE SYSTEM WTH UNBALANCED AND DSTORTED SOURCE OLTAGE WAE FORMS
Introduction. Harmonics and IEEE 519 Page 1 of 19
Introduction In an ideal power system, the voltage supplied to customer equipment, and the resulting load current are perfect sine waves. In practice, however, conditions are never ideal, so these waveforms
Considering the effects of UPS operation with leading power factor loads
Considering the effects of UPS operation with leading power factor loads Over the past five years, a new generation of data processing and communications equipment has become prevalent in modern data centers
Analysis of Space Vector Pulse Width Modulation VSI Induction Motor on various conditions
Analysis of Space Vector Pulse Width Modulation VSI Induction Motor on various conditions Padma Chaturvedi 1, Amarish Dubey 2 1 Department of Electrical Engineering, Maharana Pratap Engineering College,
Analysis and Control of Three Phase Multi level Inverters with Sinusoidal PWM Feeding Balanced Loads Using MATLAB
Analysis and Control of Three Phase Multi level s with Sinusoidal PWM Feeding Balanced Loads Using MATLAB Rajesh Kumar Ahuja 1, Amit Kumar 2 Department of Electrical Engineering, YMCA University of Science
Application Note AN- 1095
Application Note AN- 1095 Design of the Inverter Output Filter for Motor Drives with IRAMS Power Modules Cesare Bocchiola Table of Contents Page Section 1: Introduction...2 Section 2 : Output Filter Design
AN ULTRA-CHEAP GRID CONNECTED INVERTER FOR SMALL SCALE GRID CONNECTION
AN ULTRA-CHEAP GRID CONNECTED INVERTER FOR SMALL SCALE GRID CONNECTION Pramod Ghimire 1, Dr. Alan R. Wood 2 1 ME Candidate Email: [email protected] 2 Senior Lecturer: Canterbury University
Simulation and Analysis of Parameter Identification Techniques for Induction Motor Drive
International Journal of Electronic and Electrical Engineering. ISSN 0974-2174 Volume 7, Number 10 (2014), pp. 1027-1035 International Research Publication House http://www.irphouse.com Simulation and
FREQUENCY CONTROLLED AC MOTOR DRIVE
FREQUENCY CONTROLLED AC MOTOR DRIVE 1.0 Features of Standard AC Motors The squirrel cage induction motor is the electrical motor motor type most widely used in industry. This leading position results mainly
Network Theory Question Bank
Network Theory Question Bank Unit-I JNTU SYLLABUS: Three Phase Circuits Three phase circuits: Phase sequence Star and delta connection Relation between line and phase voltages and currents in balanced
Relationship between large subject matter areas
H02M APPARATUS FOR CONVERSION BETWEEN AC AND AC, BETWEEN AC AND DC, OR BETWEEN DC AND DC, AND FOR USE WITH MAINS OR SIMILAR POWER SUPPLY SYSTEMS; CONVERSION OF DC OR AC INPUT POWER INTO SURGE OUTPUT POWER;
Chapter 4 AC to AC Converters ( AC Controllers and Frequency Converters )
Chapter 4 AC to AC Converters ( AC Controllers and Frequency Converters ) Classification of AC to AC converters Same frequency variable magnitude AC power AC controllers AC power Frequency converters (Cycloconverters)
Study Guide for the Electronics Technician Pre-Employment Examination
Bay Area Rapid Transit District Study Guide for the Electronics Technician Pre-Employment Examination INTRODUCTION The Bay Area Rapid Transit (BART) District makes extensive use of electronics technology
UNDERSTANDING POWER FACTOR AND INPUT CURRENT HARMONICS IN SWITCHED MODE POWER SUPPLIES
UNDERSTANDING POWER FACTOR AND INPUT CURRENT HARMONICS IN SWITCHED MODE POWER SUPPLIES WHITE PAPER: TW0062 36 Newburgh Road Hackettstown, NJ 07840 Feb 2009 Alan Gobbi About the Author Alan Gobbi Alan Gobbi
Variable Voltage Variable Frequency Speed Control of Induction Motor Using FPGA-Xilinx
Variable Voltage Variable Frequency Speed Control of Induction Motor Using FPGA-Xilinx Ravi Prakash 1, Prof. Rishi Kumar Singh 2, Rajeev Ranjan Kumar 3 1Ravi Prakash,Department of Electrical Engineering,
High Intensify Interleaved Converter for Renewable Energy Resources
High Intensify Interleaved Converter for Renewable Energy Resources K. Muthiah 1, S.Manivel 2, Gowthaman.N 3 1 PG Scholar, Jay Shriram Group of Institutions,Tirupur 2 Assistant Professor, Jay Shriram Group
Closed Loop PWM Control for Induction Motor Drive Using Dual Output Three Phase Inverter
Closed Loop PWM Control for Induction Motor Drive Using Dual Output Three Phase Inverter Archana.P 1, Karthick.R 2 Pg Scholar [PED], Department of EEE, CSI College of Engineering, Ketti, Tamilnadu, India
ULRASONIC GENERATOR POWER CIRCUITRY. Will it fit on PC board
ULRASONIC GENERATOR POWER CIRCUITRY Will it fit on PC board MAJOR COMPONENTS HIGH POWER FACTOR RECTIFIER RECTIFIES POWER LINE RAIL SUPPLY SETS VOLTAGE AMPLITUDE INVERTER INVERTS RAIL VOLTAGE FILTER FILTERS
A bidirectional, sinusoidal, high-frequency inverter design
A bidirectional, sinusoidal, high-frequency inverter design E.Koutroulis, J.Chatzakis, K.Kalaitzakis and N.C.Voulgaris Abstract: A new method for the design of a bidirectional inverter based on the sinusoidal
Mathematical Modeling and Dynamic Simulation of a Class of Drive Systems with Permanent Magnet Synchronous Motors
Applied and Computational Mechanics 3 (2009) 331 338 Mathematical Modeling and Dynamic Simulation of a Class of Drive Systems with Permanent Magnet Synchronous Motors M. Mikhov a, a Faculty of Automatics,
Keywords: Electric circuits, passive circuits, active circuits, voltage source inverter, reactive power theory, active filters.
ACTIVE NETWORKS Davor Vujatovic Engineering Manager, EDF Energy Services Ltd., UK Keywords: Electric circuits, passive circuits, active circuits, voltage source inverter, reactive power theory, active
Power measurement in balanced 3 phase circuits and power factor improvement. 1 Power in Single Phase Circuits. Experiment no 1
Experiment no 1 Power measurement in balanced 3 phase circuits and power factor improvement 1 Power in Single Phase Circuits Let v = m cos(ωt) = cos(ωt) is the voltage applied to a R-L circuit and i =
Submarine Cable Power Transmission using DC High-Voltage Three-Level Converters
Submarine Cable Power Transmission using DC High-Voltage Three-Level Converters João Antunes, IST ([email protected]) Astract This paper is about multilevel converters used in High Voltage Direct Current
WIND TURBINE TECHNOLOGY
Module 2.2-2 WIND TURBINE TECHNOLOGY Electrical System Gerhard J. Gerdes Workshop on Renewable Energies November 14-25, 2005 Nadi, Republic of the Fiji Islands Contents Module 2.2 Types of generator systems
Smart Grid and Renewable Energy Grid Integration. Jian Sun, Professor and Director Department of ECSE & Center for Future Energy Systems
Smart Grid and Renewable Energy Grid Integration Jian Sun, Professor and Director Department of ECSE & Center for Future Energy Systems 1 How Smart Can We Make This Grid? 2 Smart Grid Drivers Need to Use
LOW COST MOTOR PROTECTION FILTERS FOR PWM DRIVE APPLICATIONS STOPS MOTOR DAMAGE
LOW COST MOTOR PROTECTION FILTERS FOR PWM DRIVE APPLICATIONS STOPS MOTOR DAMAGE Karl M. Hink, Executive Vice President Originally presented at the Power Quality 99 Conference ABSTRACT Motor protection
How To Improve Power Quality With Dstatcom
International Journal of Engineering Inventions ISSN: 2278-7461, www.ijeijournal.com Volume 1, Issue 4 (September2012) PP: 80-90 A Modern Approach of a Three Phase Four Wire Dstatcom for Power Quality
Simulation on Micro Wind Power Generator with Battery Energy Storage for Critical Load
Simulation on Micro Wind Power Generator with Battery Energy Storage for Critical Load Pankaj Thakur*, Ms. Durga Sharma (Assistant Professor)** *(Department of Electrical and Electronics Engineering, Dr.
Knowing the FACTS. FACTS that enhance power quality in rail feeder systems
Knowing the FACTS FACTS that enhance power quality in rail feeder systems ROLF GRÜNBAUM, PER HALVARSSON, BJÖRN THORVALDSSON The increase in traffic on existing tracks combined with new high-speed rail
Chapter 12: Three Phase Circuits
Chapter 12: Three Phase Circuits 12.1 What Is a Three Phase Circuit? 12.2 Balance Three Phase Voltages 12.3 Balance Three Phase Y to Y Connection 12.4 Other Balance Three Phase Connections 12.5 Power in
New Control Strategy To Improve Power Quality Using A Hybrid Power Filter
New Control Strategy o Improve Power Quality Using A Hybrid Power Filter S. P. Litrán, P. Salmerón, R. S. Herrera, and J. R. Vázquez Department of Electrical Engineering Escuela Politécnica Superior, University
DC TRANSMISSION BASED ON VOLTAGE SOURCE CONVERTERS
DC TRANSMISSION BASED ON VOLTAGE SOURCE CONVERTERS by Gunnar Asplund, Kjell Eriksson, Hongbo Jiang, Johan Lindberg, Rolf Pålsson, Kjell Svensson ABB Power Systems AB Sweden SUMMARY Voltage Source Converters
Power Quality Issues, Impacts, and Mitigation for Industrial Customers
Power Quality Issues, Impacts, and Mitigation for Industrial Customers By Kevin Olikara, Power and Energy Management Products Rockwell Automation, Inc. Now, more than ever, electronic equipment and computing
Survey of Harmonics Measurements in Electrical Distribution Systems
Survey of Harmonics Measurements in Electrical Distribution Systems Leon M. Tolbert, Member, IEEE Oak Ridge National Laboratory* P.O. Box 28, Bldg Oak Ridge, TN 3783-6334 Alexandria, VA 2235-3862 Phone:
DOI 10.4010/2015.370 ISSN2321 3361 2015 IJESC
DOI 10.4010/2015.370 ISSN2321 3361 2015 IJESC Research Article June 2015 Issue Statcom Based Controller with PV Source for a Three-Phase Seig Feeding Single Phase Loads Neeraja Ramachandran 1, Kumar R
DC Voltage Regulation by Buck Converter Applicable for Stand Alone Micro Hydro Power Generation
International Journal of Electronic and Electrical Engineering. ISSN 0974-2174, Volume 7, Number 1 (2014), pp. 37-42 International Research Publication House http://www.irphouse.com DC Voltage Regulation