1 BETA-Mk 2 Fire alarm control panel Manual 1

2 Introduction Beta / Two wire system BETA-Mk 2 Range of fire alarm control panels are designed and manufactured to meet the requirements of B.S.5839 pt4 (EN54). Standard control panel is a robust construction using plug-in cards for ease of maintenance and. There are two types of plug-in cards in the standard system. Card 1699 is an 8 zone mother board. Card 1700 is an 8 zone detection board. All fitted in a robust metal enclosure. Each detection circuit operates on an open circuit principle and is monitored using an active end of line unit (To allow removal of a detector without disconnecting rest of the circuit, See drawing AC395. In this mode detector base will require to be fitted with a Diode). Each circuit is also capable of accepting sounders up to a load of 150mA. Any short or open circuit in the detection / sounder line immediately is detected and indicated as common fault on the front of panel and individually indicate on the top board. Two common sounders are provided for standard panels. Each sounder circuit is constantly monitored for short circuit and open circuit using an active EOL. Each circuit is also protected by a 0.5A fuse. Any sounder fault will indicate as Common fault on front of panel and individually indicate on the mother board. Should an alarm condition be initiated by a detector or a manual call point, Twin red FIRE led s indicate in that zone. Internal buzzer will sound and two sounder circuits will activate. Sounder circuits can be silenced or recalled at any time during the period between fire detection and system reset. Sounders will reactivate automatically if any other zone is activated. Sounders can be tested by pressing the TEST / EVACUATE Button. D.C. Power supply and battery charger are integral part of the control panel with space for 3.2Ah S.L.A. 24volt Batteries. Standard charger is of constant voltage 27.5V Current limited at 1A (For standard panels of up to 8 zones). Charger supply and battery supply are constantly monitored for failure. Failure of mains / charger or batteries will be indicated by common fault on the front of panel and individually indicate on the mother board. 2

3 Specification Indicators Mains healthy: Battery fault, mains, charger fault Common fault Common Sounder fault: Detection line fault: Fire Engineer s walk test Twin green led s Led on board Twin Yellow led s Two led s on board (one for each sounder) Yellow led s on board for each zone Twin red led s per zone led on board Switches Reset button Test / Evacuate button Sounder silence button Internal buzzer silence button Zone isolate slide switches per zone (on board) Engineer s walk test slide switch (on board) Repeater outputs Fire output for every zone (Negative going signal 25mA max.) Fault output common (Negative going signal 25mA max.) Buzzer output (Negative going signal 25mA max.) Reset switch output Test / Evacuate switch output Sounder silence switch output Buzzer silence switch output All switches must be normally open and one side going to 0 volt Aux. 24v output: 200mA max. (Must not be used for permanently activated load). Aux. Relay volt free contacts: sets of change over contacts (Activate with any fire) Contacts rated at 1Amp / 30V DC. resistive (Do not use for mains supply switching) 3

4 Electrical Mains supply: Standby supply: Sounder circuits: Auxiliary relay: Quiescent current: Detector line voltage: V A.C. 50 Hz Fused at 1Amps 24v SLA batteries Float charged by integral supply / charger 0.5Amp current limited at 1A. Space for 3.2Ah inside the standard panel For larger supply or / and batteries External power supply / charger should be Specified. Two common sounder circuits are supplied As standard as well as any detection zone being one Fused at 0.5A each (Limited to total available power) One sets of volt free change over contacts Rated at 1A / 30VDC(Resistive) 50mA basic current plus 5mA per zone 18Volts DC in quiescent state Construction Wall mounting case. Sheet metal construction with hinged lid. Powder finished appliance white. Dimensions Control panel (Surface mount) 355mm W x 255mm H x 85mm D Control panel (Flush mount) Front panel: 395mm W x 295mm H Back box: 350mm W x 250mm H x 80mm D 4

5 Installation Information 1) Simply fix the box to an appropriate location. 2) Knock out relevant 20mm knock outs and wire according to the local fire regulation. 3) Enter appropriate cables ie. Mains supply, Alarm sounders, Detector lines and any other cables necessary. Then place chassis back in case and locate. 4) Connect cables to terminals using schematic diagram for details. (Any cable insulation testing should be carried out before cables being connected to control pane terminals). Do not switch on the power at this point. 5) Remove resistors provided in detection zone terminals and place them at the end of detection lines (Do not use the resistors if active end of lines are being used, see drawing AC395) If 2k2 end of lines are being used, do not fit diodes in the detector bases. If active end of lines are being used, do fit diodes in the detector bases. Remove resistors provided in alarm sounder terminals and place them at the end of alarm sounder lines. 6) Test should be carried out if possible using mains powered supply not batteries at this point. Batteries should be connected to the system when cable faults are removed. 2x12v rechargeable sealed lead acid batteries should be used. Please ensure that batteries are connected in series to provide 24v D.C. and avoid wrong polarity. Connecting the batteries in wrong polarity will damage the equipment. 7) Maximum alarm load must not exceed 0.5A per circuit (limited to total available power). 8) Under no circumstances should a MEGGER or any insulation tester be used once cables are connected to control panel and / or detector bases. End of line units also will be damaged by use of insulation testers. 9) BS 5839: In order to comply with BS 5839 pt1, both alarm circuits and detection lines muse be wired in an appropriate physically protected cable. All circuits must be wired in a continuous line without spurs or branches, if monitoring circuits are to be effective. 5

6 Operating Instruction BETA Mk 2 Range of Fire Alarm Control Units. Normal When the unit is healthy only the green Mains Healthy lamp will be on. Line Fault Yellow Common Fault lamp on the panel is on, on board an appropriate yellow fault lamp is lit. this could mean that a detector has been removed or that the circuit has been broken or short circuited. It could also mean one or more zones are Isolated. Check that all detectors are fitted and if fault persists contact your service engineer as soon as possible. On initiation of a Detector Line Fault the internal sounder will sound. The sounder may be silenced by pressing Buzzer Silence. The Detector Line Fault lamps will stay on until the fault is corrected. Mains Failure If the electrical supply fails, the green Mains Healthy lamps will go out. supply fault led on mother board will come on. common fault led will come on the front panel. Action should be taken as soon as possible to restore the mains supply. The system will continue to operate on its own internal batteries for 24 Hrs (If appropriate size batteries are used). Battery Supply Failure and Charger Failure In the event of a failure of either the internal batteries or the associated charger unit, the supply fault led will indicate on board, common fault led will light on the front panel. internal sounder will start, and may be silenced by pressing Buzzer Silence. Your service engineer should be contacted to rectify the system fault. The system will continue to operate on mains supply only. Alarm Circuit Fault Should the wiring connecting the alarm bells become damaged or broken, the yellow common fault lamps will come on the front panel, and on board sounder fault led will 6

7 light. The internal sounder will start. The internal sounder may be silenced by pressing Buzzer Silence. Your service engineer should be contacted as soon as possible. Fire When a break glass unit is operated or an automatic detector detects, two red Zone Fire lamps will come on. Simultaneously the internal sounder will start, the bells will sound and you should now carry out your normal fire drill. To Silence The Alarms Should you wish to silence the alarm bells, press Silence Sounders button. The internal sounder remains On. The internal sounder will not silence by pressing the Buzzer Silence. To Reset The System Replace any broken glasses in the break glass units around the building and ensure that any fire condition, smoke for example, has cleared. Press the Reset button only. If active end of line units are used, after reset zone fault LED S may turn on for a period of up to 2 seconds. Testing To test that the alarm bells are working, or to operate them independently of any fire condition press Test/Evacuate button. Testing the system using engineer s walk test ( Auto reset). Switch the slide switch marked Engineer s walk test, Auto reset to ON position. Cary out test by testing call points, detectors etc. You will hear the sounders activating for a few seconds and reset automatically. Return the slide switch back to OFF position when finished. Isolating Detection Zones Detection zones can be isolated individually by sliding the isolate switches (isolate switches are located on the main PCB, directly below the terminal blocks, Isolating a detection zone is indicated by common fault two yellow fault LED S and the appropriate fault led on board and internal buzzer (internal buzzer can be silenced if necessary by pressing Buzzer Silence switch) During this time the isolated zone will not accept any incoming fire signals. Isolator switch must be put back to normal as soon as possible, and this is identified by extinguishing of yellow fault LED S. 7

INTRODUCTION. The data provided is for The Standard Products and any variation will be dealt with at the end of this manual.

INTRODUCTION. The data provided is for The Standard Products and any variation will be dealt with at the end of this manual. INTRODUCTION The information provided herein covers the range of products known as the 'Sensor 901' series. The range of equipment is designed to meet the requirements of BS 5839 parts 1 & 4 1988. The

More information

FIREDEX 2200. Conventional Fire Panels

FIREDEX 2200. Conventional Fire Panels 68 Flexible, high specification system Choice of 1, 2, 4 or 8 zones Simple one-shot auto-reset user test facility Approved to EN54 Maintenance free poly switch circuit protection, with auto reset Class

More information

BARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell

BARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell Data, installation, operation and maintenance 4 & 8 Zone Fire Panels Zircon range BARDIC by Honeywell LED flashing LED Continuous FAULT DISABLE/TEST Power General Fault Sounder Fault/ Disable System Fault

More information

CB200W Water Leak Detection Panel Application Guide

CB200W Water Leak Detection Panel Application Guide Checked by: AJC Approved by: JBJ Contents CB200W Water Leak Detection Panel Application Guide 1. Cabinet Specifications... 2 2. Panel Hardware Specifications... 3 3. Panel Configuration... 4 4. Technical

More information

GST301. (Single Protection Zone) Operation Manual

GST301. (Single Protection Zone) Operation Manual GST301 Gas Extinguishing Control Panel (Single Protection Zone) Operation Manual 2 of 19 CONTENTS 1 OVERVIEW... 4 2 TECHNICAL DATA... 4 3 STRUCTURES... 5 3.1 FRONT SURFACE DESCRIPTION... 5 3.1.1 Indicators...

More information

Fire Alarm Control Panel. Family. Operating Manual

Fire Alarm Control Panel. Family. Operating Manual Fire Alarm Control Panel Family Operating Manual CONTENTS System Description AH-03312 System Characteristics... Fire Signal Receiving Board Description-4L... Fire Signal Receiving Board Description-8L...

More information

3. MOUNTING THE FIRE ALARM PANEL... 7 3.1 PLANNING CABLE ENTRY 3.2 FIXING THE BACKBOX TO THE WALL

3. MOUNTING THE FIRE ALARM PANEL... 7 3.1 PLANNING CABLE ENTRY 3.2 FIXING THE BACKBOX TO THE WALL INSTALLATION MANUAL CONTENTS 1. INTRODUCTION. 3 1.1 HANDLING THE PCBS 1.2 USING THIS MANUAL 1.3 ABOUT THE PREMIER SX FACP & INTEGRAL PSE 1.4 DESIGNING THE SYSTEM 1.5 EQUIPMENT GUARANTEE 2. FIRST FIX GUIDELINES.

More information

INFINITY 8 INSTALLATION MANUAL FIRE ALARM CONTROL PANEL INSTALLATION MANUAL

INFINITY 8 INSTALLATION MANUAL FIRE ALARM CONTROL PANEL INSTALLATION MANUAL FIRE ALARM CONTROL PANEL INSTALLATION MANUAL Approved Document No. GLT-201-7-1 CONTENTS 1. INTRODUCTION... 1.1 HANDLING THE PCBS... 1.2 USING THIS MANUAL... 1.3 ABOUT THE INFINITY FIRE ALARM CONTROL PANEL

More information

(68.52) X. June 2000 Supercedes February 2000. xenex CONVENTIONAL FIRE DETECTION & ALARM SYSTEM. we look @ business differently

(68.52) X. June 2000 Supercedes February 2000. xenex CONVENTIONAL FIRE DETECTION & ALARM SYSTEM. we look @ business differently (68.52) X June 2000 Supercedes February 2000 xenex CONVENTIONAL FIRE DETECTION & ALARM SYSTEM.... we look @ business differently XENEX SYSTEM ARCHITECTURE Note: This schematic is for guidance only please

More information

EVC40 EMERGENCY VOICE COMMUNICATION SYSTEM

EVC40 EMERGENCY VOICE COMMUNICATION SYSTEM EVC40 EMERGENCY VOICE COMMUNICATION SYSTEM INSTALLATION MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0) 1282 717273

More information

Conventional Fire Detection and Extinguishant Control System Specification

Conventional Fire Detection and Extinguishant Control System Specification Conventional Fire Detection and Extinguishant Control System Specification Page 1 of 9 Scope Furnish a complete 24VDC Conventional, electrically supervised, combined fire detection and extinguishant release

More information

ACTIVE 5 ENGINEERING MANUAL

ACTIVE 5 ENGINEERING MANUAL ACTIVE 5 ENGINEERING MANUAL C & K Systems Ltd C031-066 Issue 3 THE ACTIVE 5 INSTALLATION MANUAL. Date: Feb 1997 INTRODUCTION. The Active 5 is a microprocessor controlled intruder alarm panel. It features

More information

USER MANUAL, MAINTENANCE GUIDE & LOG BOOK

USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Software Versions: PANEL 1.52 & LOOP CARD 2.0 ONE TO FOUR LOOPS ANALOGUE ADDRESSABLE FIRE ALARM PANEL USER MANUAL, MAINTENANCE GUIDE & LOG BOOK #Doc No. GLT.MAN-135 TABLE OF CONTENTS WHAT TO DO IF THE

More information

CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems

CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems EN Security System CM705B CM705B - Universal Expander Module The CM705B universal expander provides a cost effective way

More information

A.1. a Division of Pittway Corporation. Documento: M-010.1-MGAS-ENG. Edizione: 01/1997 Rev.:

A.1. a Division of Pittway Corporation. Documento: M-010.1-MGAS-ENG. Edizione: 01/1997 Rev.: Documento: M-010.1-MGAS-ENG Edizione: 01/1997 Rev.: A.1 a Division of Pittway Corporation FRONT PANEL & VISUAL INDICATIONS GENERAL TROUBLE GENERAL PROGRAMMING IN PROGRESS ENABLE/ALARM/TROUBLE (ZONE 1 ALARM

More information

TS510 & TS500. Installation & User Guide. Compatible Equipment

TS510 & TS500. Installation & User Guide. Compatible Equipment Installation & User Guide Compatible Equipment TS510 REM - Remote Keypad 9040 - Loudspeaker DC54/58 - Digital Communicator SD1+ - Speech Dialler 496525 Issue A 1 of 10 TS510 and TS500 Overview Introduction

More information

Installation and Operation Manual

Installation and Operation Manual GST102 GST104 Conventional Alarm Control Panel nstallation and peration Manual (ssue3.03, November 2005) nstallation and peration Manual The ntelligent Solution CNTENTS 1 General... 1 2 Technical Specifications...

More information

500r+ Installation and User Guide

500r+ Installation and User Guide 500r+ Installation and User Guide Compatible Equipment 502rUK-50 Watch/Pendant PA. 509rUK-50 Smoke Detector 515rUK-00 10 metre passive infra red movement detector. 525rUK-00 Remote Set/Unset (Full and

More information

conventional system operation

conventional system operation conventional system operation detection line operation Conventional detection systems normally operate on a 24VDC line. In the standby condition, the detectors will draw a low current, typically less than

More information

Disabled Toilet Alarm. Contractor Pack. Installation & Operating Instructions

Disabled Toilet Alarm. Contractor Pack. Installation & Operating Instructions Disabled Toilet Alarm Installation & Operating Contractor Pack Installation & Operating Instructions 1 Overview The Channel Safety Systems Disabled Toilet alarm contractor Packs are an efficient way of

More information

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10 TECHNICAL SPECIFICATIONS Page 1 of 10 FIRE DETECTION AND ALARM SYSTEM Scope Furnish a complete 24V DC conventional, electrically supervised, zone annunciated, fire detection and alarm system as specified

More information

HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions 800-09617V1 Rev A 11/12)

HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions 800-09617V1 Rev A 11/12) HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions 800-09617V1 Rev A 11/12) UL864 (Commercial Fire) Compliance General Requirements The VISTA-128FBPT/VISTA250FBPT

More information

HM-W536 Install Guide

HM-W536 Install Guide HM-W536 Install Guide 9/13/2013 IMPORTANT SAFETY INSTRUCTIONS Warning - When using electrical devices, basic safety precautions should be followed to reduce the risk of fire, electrical shock or injury.

More information

FA-300 Series. LCD Fire Alarm Control Panel. User Guide. LT-954 Rev. 0.1 February 2013. FA-300 SERIES Fire Alarm Control Panel

FA-300 Series. LCD Fire Alarm Control Panel. User Guide. LT-954 Rev. 0.1 February 2013. FA-300 SERIES Fire Alarm Control Panel ABC DEF GHI JKL MNO PQR STU YZ WXY FA-300 Series LCD Fire Alarm Control Panel Advanced Life Safety Solutions System Normal 10:36AM WED 2003-10-01 SYSTEM RESET A.C. ON ALARM SUPV TRBL CPU FAIL SIGNAL SILENCE

More information

CONTENTS. GST102A/104A/108A/116A Conventional Fire Alarm Control Panel Installation and Operation Manual

CONTENTS. GST102A/104A/108A/116A Conventional Fire Alarm Control Panel Installation and Operation Manual CONTENTS Installation Precautions... 1 EN 54 Information... 2 Chapter 1 Product Overview... 3 1.1 Features... 3 1.2 Technical Specifications... 3 1.2.1 Operating Voltage... 3 1.2.2 Batteries... 4 1.2.3

More information

AC-115 Compact Networked Single Door Controller. Installation and User Manual

AC-115 Compact Networked Single Door Controller. Installation and User Manual AC-115 Compact Networked Single Controller Installation and User Manual December 2007 Table of Contents Table of Contents 1. Introduction...5 1.1 Key Features... 6 1.2 Technical Specifications... 7 2.

More information

HAM841K ALARM CONTROL PANEL FOR COMMERCIAL AND RESIDENTIAL SECURITY SYSTEMS

HAM841K ALARM CONTROL PANEL FOR COMMERCIAL AND RESIDENTIAL SECURITY SYSTEMS ALARM CONTROL PANEL FOR COMMERCIAL AND RESIDENTIAL SECURITY SYSTEMS USER MANUAL USER MANUAL ALARM CONTROL PANEL FOR COMMERCIAL AND RESIDENTIAL SECURITY SYSTEMS INTRODUCTION The (HA-841K) is a complete

More information

SFC-200 SERIES FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels. Features. Description

SFC-200 SERIES FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels. Features. Description SFC-200 SERIES FIRE ALARM CONTROL PANELS SFC-200 Series Fire Alarm Control Panels Description Summit s SFC-200 Series fire alarm control panels consist of six and twelve zone models which are equipped

More information

Repeaters and Mimics Data Sheet

Repeaters and Mimics Data Sheet Repeaters and Mimics Data Sheet IDR series repeaters and mimics allow vital information from a Notifier fire system to be communicated to points around a building remote from the fire alarm control panel.

More information

Emergency Voice Communication Systems EVCS Network 8 Data Sheet

Emergency Voice Communication Systems EVCS Network 8 Data Sheet Emergency Voice Communication Systems EVCS Network 8 Data Sheet The Emergency Voice Communications System (EVCS) Network 8 is for use as a Fire Telephone system, Disabled Refuge Call system or as a combined

More information

MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE

MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE DESCRIPTION MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE DESCRIPTION The SST Model 5010 Two Channel Smoke/Fire Detection Module provides two independent detection input channels for the NOVA-5000

More information

QCS Section 23 Part 2 Fire Alarm and Detection Systems Page 1 2. FIRE ALARM DETECTION SYSTEMS...2

QCS Section 23 Part 2 Fire Alarm and Detection Systems Page 1 2. FIRE ALARM DETECTION SYSTEMS...2 QCS Section 23 Part 2 Fire Alarm and Detection Systems Page 1 2. FIRE ALARM DETECTION SYSTEMS...2 2.1 GENERAL...2 2.1.1 Scope 2 2.1.2 References 2 2.1.3 Contractor s Responsibility 2 2.1.4 System Description

More information

INTELLIGENT FIRE ALARM CONTROL PANELS. MR-2100/MR-2200 Intelligent Fire Alarm Control Panels MEA. Features. Description

INTELLIGENT FIRE ALARM CONTROL PANELS. MR-2100/MR-2200 Intelligent Fire Alarm Control Panels MEA. Features. Description INTELLIGENT FIRE ALARM CONTROL PANELS MR-2100/MR-2200 Intelligent Fire Alarm Control Panels Description MR-2100/MR-2200 Intelligent Fire Alarm Control Panel (shown with optional LED modules) Secutron's

More information

Surveyor Excel-K. Fire Alarm Control Equipment. Installation, Commissioning and Operating Manual

Surveyor Excel-K. Fire Alarm Control Equipment. Installation, Commissioning and Operating Manual Surveyor Excel-K Fire Alarm Control Equipment Installation, Commissioning and Operating Manual CONTENTS 2 16 ZONE CONVENTIONAL & TWIN WIRE INTRODUCTION. 3 SYSTEM DESIGN & PLANNING. 3 GENERAL. 3 EXCEL-K

More information

9452/9453 Installation and User Guide

9452/9453 Installation and User Guide 9452/9453 Installation and User Guide Compatible Equipment 9425 Remote Keypad 9040 Internal Sounder 660 Speech Communicator 8440 4-Channel Minicom 496330 Issue 1 1 of 10 9452/3 Introduction The 9452 and

More information

VEGA Analogue Addressable Control Panels

VEGA Analogue Addressable Control Panels Analogue Addressable Control Panels Representing the future of fire alarm control technology, Vega's modular concept enables the tailoring of system design for the smallest to the largest system. Designed

More information

9448 Installation and User Guide

9448 Installation and User Guide 9448 Installation and User Guide Compatible Equipment 9040 Internal Sounder 660 Speech communicator 496327 Issue 1 1 of 6 9448 INTRODUCTION The 9448 is a 3 zone control panel with separate Entry/Exit and

More information

OUTPUT CABLE CONNECTIONS:

OUTPUT CABLE CONNECTIONS: Tender Plus: Models: 12V1.25A and 6V1.25A The Tender Plus 12 Volt, 1.25 Amp 6 Volt, 1.25 Amp GENERAL DESCRIPTION: The Tender Plus battery charger is a desktop, portable, linear power converter that has

More information

CSP Combined Series. Telephone Door Entry. with. Proximity Keyfob Access

CSP Combined Series. Telephone Door Entry. with. Proximity Keyfob Access CSP Combined Series Telephone Door Entry with Proximity Keyfob Access PD-094 Issue 3 General Description The CSP series systems are combined Door Entry Telephone and Proximity Access Systems. The entrance

More information

SECTION 13850 DETECTION AND ALARM

SECTION 13850 DETECTION AND ALARM SECTION 13850 DETECTION AND ALARM PART 1 GENERAL 1.01 SUMMARY A. Section Includes 1. Control Panel 2 Associated Equipment B. Products Installed But Not Supplied Under This Section 1. Section 16140 - Wiring

More information

LPCB APPROVED CFP 2/4/8 ZONE FIRE ALARM CONTROL PANEL. installation & maintenance manual. Approved Document No. DFU7004010 Rev 1

LPCB APPROVED CFP 2/4/8 ZONE FIRE ALARM CONTROL PANEL. installation & maintenance manual. Approved Document No. DFU7004010 Rev 1 LPCB APPROVED CFP 2/4/8 ZONE FIRE ALARM CONTROL PANEL installation & maintenance manual Approved Document No. DFU7004010 Rev 1 CONTENTS EN54 Compliance Statement...3 Basic Overview & Key Features...3 Important

More information

Electronics Ltd. Presenting. Power, Intelligence... with a sense of feeling

Electronics Ltd. Presenting. Power, Intelligence... with a sense of feeling Electronics Ltd Presenting Power, Intelligence... with a sense of feeling By Appointment to Her Majesty The Queen Supplier of Fire Detection Equipment Kentec Electronics Ltd. Dartford Plug in slots K772

More information

FIRE ALARM PANEL & SYSTEM OPERATION ID50 SYSTEM. The Fire Alarm System can be activated in the following ways :~

FIRE ALARM PANEL & SYSTEM OPERATION ID50 SYSTEM. The Fire Alarm System can be activated in the following ways :~ ID50 SYSTEM The Fire Alarm System can be activated in the following ways :~ 1. By breaking the glass in a Manual Alarm Call Point 2. By a rise in temperature activating an Automatic Heat Detector 3. By

More information

TMS TANK MANAGEMENT SYSTEM

TMS TANK MANAGEMENT SYSTEM TMS TANK MANAGEMENT SYSTEM Page 1 of 9 Operating Instructions GENERAL The Tank Management System is a bespoke design to control, monitor and accommodate efficient storage and dispensing of TMS. FUNCTIONS

More information

LD2 One & Two Zone Water Detection Alarm Installation and Operation Manual

LD2 One & Two Zone Water Detection Alarm Installation and Operation Manual CMR Electrical Ltd Bolton House Five Chimneys Lane Hadlow Down East Sussex TN22 4DX Tel: 01825 733600 LD2 One & Two Zone Water Detection Alarm Installation and Operation Manual Contents 1) Operation 2)

More information

INSTALLATION MANUAL 5-051-719-00 CONTENTS

INSTALLATION MANUAL 5-051-719-00 CONTENTS INSTALLATION MANUAL CHALLENGER VIII CONTROL PANEL 5-051-719-00 CONTENTS Warnings 2 Standards 2 Product Description 2 Available Parts 2 Intended use 2 Specifications 3 Processor Version 3 Power Supply 3

More information

RP1r. Extinguishing Control Panel. User Manual (Software version 3.x) 3 zone control panel to protect 1 extinguishing risk

RP1r. Extinguishing Control Panel. User Manual (Software version 3.x) 3 zone control panel to protect 1 extinguishing risk EN12094:1/2003 Honeywell Life Safety Iberia C/Pau Vila 15-19 08911 BADALONA (BARCELONA) Tel.: 93 497 39 60 Fax: 93 465 86 35 www.honeywelllifesafety.es Extinguishing Control Panel RP1r 3 zone control panel

More information

Premier M Plus & Infinity 8

Premier M Plus & Infinity 8 25 Years of Manufacturing Excellence Premier M Plus & Infinity 8 Conventional Fire Alarm Systems 007 Assessed to ISO 9001: 2008 Certificate number 330 Premier M Plus 8-24 Zone Conventional Fire Alarm Panel

More information

Section D..General Auto Electrical Corporation

Section D..General Auto Electrical Corporation 43 Section D..General Auto Electrical Corporation 1. LED Based Signal unit GAEC manufacture LED based signaling system for use in electrified and non electrified sections of Indian railways. The exceptional

More information

TABLE OF CONTENTS FEATURES

TABLE OF CONTENTS FEATURES TABLE OF CONTENTS FEATURES 2 Keypad Programmable... 2 EEPROM Memory... 2 Static/Lightning Protection... 2 Supervision... 2 Operation... 2 SPECIFICATIONS 2 PC1550 Control Panel... 2 PC1500RK Keypad... 2

More information

SECURIT 800L+ CONTROL PANEL

SECURIT 800L+ CONTROL PANEL INSTALLATION MANUAL SECURIT 800L+ CONTROL PANEL With additional options CONTENTS Warnings 2 Standards 2 Warranty Statement 2 Product Description 2 Available Parts 2 Intended use 2 Specifications 3 Processor

More information

Fire. The Fire Installers Mate. A guide to fire alarm systems design

Fire. The Fire Installers Mate. A guide to fire alarm systems design Fire The Fire Installers Mate A guide to fire alarm systems design BS 5839 Part 1:2002 A guide to BS 5839 Part 1:2002 Disclaimer This booklet is not intended to be a comprehensive guide to all aspects

More information

INSTALLATION MANUAL PC2525. Version 1.1

INSTALLATION MANUAL PC2525. Version 1.1 INSTALLATION MANUAL PC2525 Version 1.1 TABLE OF CONTENTS FEATURES 1 SPECIFICATIONS 1 INSTALLATION 2 Mounting the Panel... 2 Mounting the Keypad... 2 Auxiliary Power Connection... 2 Bell/Siren Connection...

More information

Fire Pump Controllers Remote Alarm Panels

Fire Pump Controllers Remote Alarm Panels Fire Pump Controllers Remote Alarm Panels Remote Alarm Panels 1.8 Remote Alarm Panels FDAP-M Electric... DFDAP-M Diesel... Product Specifications... 2 6 9 Features 1-1 DFDAP-M / FDAP-M Remote Alarm Panel

More information

CFP 2/4/8 ZONE ECONOMY FIRE ALARM CONTROL PANEL. installation & maintenance manual. Approved Document No. DFU7002030 Rev 1

CFP 2/4/8 ZONE ECONOMY FIRE ALARM CONTROL PANEL. installation & maintenance manual. Approved Document No. DFU7002030 Rev 1 CFP 2/4/8 ZONE ECONOMY FIRE ALARM CONTROL PANEL installation & maintenance manual Approved Document No. DFU7002030 Rev 1 CFP 2/4/8 ZONE ECONOMY FIRE ALARM PANEL CONTENTS Basic Overview and Key Features...3

More information

SFC-200 SERIES LCD FIRE ALARM PANEL

SFC-200 SERIES LCD FIRE ALARM PANEL SFC-200 SERIES LCD FIRE ALARM PANEL User Guide LT-954SUM SFC-200 Series LCD Version User Guide Contents Introduction... 1 About this Manual... 1 Technical Support... 1 Main Display... 1 The Buzzer and

More information

Drayton Digistat +2RF/+3RF

Drayton Digistat +2RF/+3RF /+3RF Programmable Room Thermostat Wireless Model: RF700/22090 Model: RF701/22092 Power Supply: Battery - Thermostat Mains - Digistat SCR Invensys Controls Europe Customer Service Tel: 0845 130 5522 Customer

More information

Using your LED Plus keypad

Using your LED Plus keypad Using your LED Plus keypad System 238 System 2316 System 238i System 2316i Part Number 5-051-372-00 Rev B Thank you for purchasing this C&K alarm system Your system is one of the most powerful and advanced

More information

WD-AMX Water Detection Controllers

WD-AMX Water Detection Controllers Page 1 of 5 WD-AMX Water Detection Controllers Features: Benefit: LED Status of leak status VFC output Audible alarm Auto or manual reset alarm output Uses an isolated AC signal which prevents oxidation

More information

AlarmSense 2-wire detection and alarm system. Product Guide

AlarmSense 2-wire detection and alarm system. Product Guide AlarmSense 2-wire detection and alarm system Product Guide Contents What is AlarmSense? 2 The purpose of AlarmSense 4 How AlarmSense works 4 Alarmsense Features 5 Detector removal monitoring 5 Priority/non-priority

More information

CONTENTS 4. HOW TO UNSET THE PANEL...7

CONTENTS 4. HOW TO UNSET THE PANEL...7 Pi-8 USER MANUAL CONTENTS 1. THE KEYPAD AND ITS OPERATION...3 1.1 DESCRIPTION OF THE KEYPAD LEDS... 3 1.1.1 READY LED (RED)...3 1.1.2 TAMPER LED (RED)...3 1.1.3 POWER LED (GREEN)...3 1.1.4 CIRCUIT LEDs

More information

INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930

INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930 INSTALLATION GUIDE Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930 Card Reader and Controller Model 3.5 with KIM Swipe Reader Table of Contents 1. Features..................................

More information

User s Information Guide R1A

User s Information Guide R1A HSC505-R Home Security Controller - User Manual Release R1a Pi HSC505 and Pi HSC505R Home Security Controller User s Information Guide R1A Page 1 QD Dynamics (Pty) Ltd reserves the right to make changes

More information

Communication A BRITISH MANUFACTURER. Features:

Communication A BRITISH MANUFACTURER. Features: care2 Radial Wired Emergency Voice Communication Manufacturing EVC systems since 2001 CARE2 is a radial wired emergency voice communication system built to the high standard you expect from Baldwin Boxall.

More information

ICP-CP500. User's Guide ICP-CP500 Codepads

ICP-CP500. User's Guide ICP-CP500 Codepads ICP-CP500 EN User's Guide ICP-CP500 Codepads ICP-CP500 User's Guide 1.0 ICP-CP500 Series Codepads Overview EN 2 1.0 ICP-CP500 Series Codepads Overview The codepad is the communications interface between

More information

Product Information Sheet UH28CS-12kV Hi Pot Tester

Product Information Sheet UH28CS-12kV Hi Pot Tester Product Information Sheet UH28CS-12kV ETL Prüftechnik GmbH Telefon: +49 711 83 99 39-0 E-Mail: info@etl-prueftechnik.de Carl-Peters-Straße 23 D-70825 Korntal-Münchingen Telefax: +49 711 83 99 39-9 Internet:

More information

Shunt lock function 3066

Shunt lock function 3066 Version: January 2004 Contents Alarm System Activation unit Deactivation unit Digital locking cylinder or Smart Relay 1.0 Method of Operation 4 1.1 General 4 1.2 Turning the Alarm System On 4 1.3 Turning

More information

Control/Communicator Installation Manual

Control/Communicator Installation Manual DAS NETWORX NX-8 Control/Communicator Installation Manual Page General Description... 2 Ordering Information... 2 Option Definitions... 2 Programming the LED Code Pads... 4 Programming the NX-8... 8 Types

More information

EDA-Z5008 & Z5020. Radio Fire Alarm System. User Manual

EDA-Z5008 & Z5020. Radio Fire Alarm System. User Manual EDA-Z5008 & Z5020 Radio Fire Alarm System User Manual Electro-Detectors Ltd. Electro House, Edinburgh Way Harlow, Essex, CM20 2EG UK Tel: 01279 635668. Fax 01279 450185 Email: eda@electrodetectors.co.uk

More information

AUTODIALLER / QUICKDIALLER - SA132

AUTODIALLER / QUICKDIALLER - SA132 AUTODIALLER / QUICKDIALLER - SA132 INSTRUCTION LEAFLET ENGLISH www.thermomax-group.com CONTENTS 1 SETUP AT A GLANCE... 2 2 FOREWORD....... 3 3 INSTALLATION...... 4 4 KEYPAD AND INDICATORS...... 5 SETTING

More information

CFP 2/4/8 ZONE CONVENTIONAL FIRE ALARM CONTROL PANEL. user manual & log book. Approved Document No. DFU7001020 Rev 1

CFP 2/4/8 ZONE CONVENTIONAL FIRE ALARM CONTROL PANEL. user manual & log book. Approved Document No. DFU7001020 Rev 1 CFP 2/4/8 ZONE CONVENTIONAL FIRE ALARM CONTROL PANEL user manual & log book Approved Document No. DFU7001020 Rev 1 CONTENTS Safety...3 Important information regarding the safe use of this fire alarm panel

More information

2.8. Ex-Recess-mounted, ceiling emergency light fittings in compact metal design

2.8. Ex-Recess-mounted, ceiling emergency light fittings in compact metal design .8 Ex-Recess-mounted, ceiling emergency light fittings in compact metal design RLF/RLF-INOX 50 18-58 W / RLF/RLF-INOX 50... N 18-36 W (Zone 1,, 1, ) The explosion-protected lighting concept for clean rooms

More information

Solar Home System. User Manual. AEH-SHS01-10W2L Solar Home System 2 Lamps

Solar Home System. User Manual. AEH-SHS01-10W2L Solar Home System 2 Lamps Solar Home System User Manual AEHSHS0110W2L Solar Home System 2 Lamps All rights reserved Specifications subject to change without prior notice 2 Dear Customer, Thank you for purchasing Schneider Electric

More information

welcome to our world fire alarm systems - series 600 www.staticsystems.co.uk

welcome to our world fire alarm systems - series 600 www.staticsystems.co.uk Static Systems Group PLC Heath Mill Road, Wombourne Staffordshire WV5 8AN. United Kingdom. Tel: +44 (0) 1902 895551 Fax: +44 (0) 1902 324969 www.staticsystems.co.uk welcome to our world In line with our

More information

12 Volt 30 Amp Digital Solar Charge Controller

12 Volt 30 Amp Digital Solar Charge Controller 12 Volt 30 Amp Digital Solar Charge Controller User s Manual WARNING Read carefully and understand all INSTRUCTIONS before operating. Failure to follow the safety rules and other basic safety precautions

More information

DTW Works Master Specification Version 2006

DTW Works Master Specification Version 2006 Issued 2006/08/01 Section 13852 Multiplex Fire Alarm System Page 1 of 10 PART 1 GENERAL 1.1 RELATED WORK.1 Section 01330 Submittal Procedures..2 Section 01780 Closeout Procedures..3 Section 01810 Commissioning..4

More information

PC4020CF v3.0 and higher Commercial Fire Installation Guide DLS-3 v1.3

PC4020CF v3.0 and higher Commercial Fire Installation Guide DLS-3 v1.3 PC4020CF v3.0 and higher Commercial Fire Installation Guide DLS-3 v1.3 Table of Contents Section 1: Introduction 1 1.1 Introduction...1 1.2 Hardware Description and Specifications...1 Section 2: Fire Zone

More information

CB200 1 8 Zone Conventional Control Panel

CB200 1 8 Zone Conventional Control Panel CB200 1 8 Zone Conventional Control Panel > features Built-in detector removal indication facility From 1 to 8 zones 4 Alarm circuits on 4-8 zone panels Conforms to the requirements of EN54-2 User-friendly

More information

TABLE OF CONTENTS FEATURES 2 SPECIFICATIONS 2

TABLE OF CONTENTS FEATURES 2 SPECIFICATIONS 2 TABLE OF CONTENTS FEATURES 2 SPECIFICATIONS 2 INSTALLATION 3 Mounting the Panel... 3 Mounting the Keypad... 3 Auxiliary Power Connection... 3 PGM Terminal Connections... 3 Bell/Siren Connection... 3 Keypad

More information

D200+ Auto-Dialler Installation/Operators Manual

D200+ Auto-Dialler Installation/Operators Manual D200+ Auto-Dialler Installation/Operators Manual Bell System (Telephones) Ltd. Presley Way, Crownhill, Milton Keynes, MK8 0ET D200+ Software Version 1.0 Contents General Description...3 Central Station

More information

Control Panels D9412GV3/D7412GV3/D7212GV3. UL Installation Instructions

Control Panels D9412GV3/D7412GV3/D7212GV3. UL Installation Instructions Control Panels D9412GV3/D7412GV3/D7212GV3 en UL Installation Instructions Control Panels Table of Contents en 3 Table of Contents 1 Installation 4 1.1 Installation Preparation 4 1.2 Enclosure Options

More information

Self Monitoring Power Supply (BPSM)

Self Monitoring Power Supply (BPSM) LIFETIME REPLACEMENT WARRANTY Self Monitoring Power Supply (BPSM) Application - When interfacing with a fire alarm system where the system s auxiliary relay cannot handle the full current potential of

More information

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short

More information

SYSTEM 4C. C R H Electronics Design

SYSTEM 4C. C R H Electronics Design SYSTEM 4C C R H Electronics Design SYSTEM 4C All in one modular 4 axis CNC drive board By C R Harding Specifications Main PCB & Input PCB Available with up to 4 Axis X, Y, Z, A outputs. Independent 25

More information

RADIANT PLASMA 4700 Plasma Spark Generator

RADIANT PLASMA 4700 Plasma Spark Generator RADIANT PLASMA 4700 Plasma Spark Generator Installation Guide / User Manual A S P A R K O F F R E S H A I R Aquapulser.com Contents 1 Introduction 2 1.1 About the Product....................................

More information

MANUAL. * Supply plugs may differ to suit your wall socket. EN 3. Continue to press the MODE-button to combine charging program with charging options.

MANUAL. * Supply plugs may differ to suit your wall socket. EN 3. Continue to press the MODE-button to combine charging program with charging options. MX MANUAL CONGRATULATIONS to the purchase of your new professional switch mode battery charger. This charger is included in a series of professional chargers from CTEK SWEDEN AB and represents the latest

More information

Alarm over IP. IRIS Touch Home Installation Manual. Version 1.0 ENGLISH. Now certified and compliant with EN50131, EN50136 Security Grade 4 ATS6

Alarm over IP. IRIS Touch Home Installation Manual. Version 1.0 ENGLISH. Now certified and compliant with EN50131, EN50136 Security Grade 4 ATS6 Alarm over IP IRIS Touch Home Installation Manual Version 1.0 ENGLISH Now certified and compliant with EN50131, EN50136 Security Grade 4 ATS6 1. Introduction No more bulky batteries, just one sleek unit

More information

WATER LEAK DETECTION SYSTEM WLDS-10 INSTALLATION & COMMISSIONING

WATER LEAK DETECTION SYSTEM WLDS-10 INSTALLATION & COMMISSIONING WATER LEAK DETECTION SYSTEM WLDS-10 INSTALLATION & COMMISSIONING DESCRIPTION: An electronic control panel used in conjunction with one pulse meter (water meter with pulse output proportional to flow rate)

More information

The Charging System. Section 5. Charging System. Charging System. The charging system has two essential functions:

The Charging System. Section 5. Charging System. Charging System. The charging system has two essential functions: The Charging System Charging System The charging system has two essential functions: Generate electrical power to run the vehicle s electrical systems Generate current to recharge the vehicle s battery

More information

SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines

SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting

More information

Secure Keypads for access control

Secure Keypads for access control torm Secure Keypads for access control Strike Master Read this manual carefully before attempting to install, program or operate the STORM AXS Strike Master Keypad. After installation the Command Summary

More information

www.ringautomotive.co.uk Instructions: Retain these instructions for future reference SmartChargePro35 RSCPR35-12v, 2 / 8 / 16 / 35A

www.ringautomotive.co.uk Instructions: Retain these instructions for future reference SmartChargePro35 RSCPR35-12v, 2 / 8 / 16 / 35A SmartChargePro7 RSCPR7-12v, 7A SmartChargePro10 RSCPR10-12v, 10A SmartChargePro15 RSCPR15-12v, 15A SmartChargePro25 RSCPR25-12v, 2 / 6 / 12 / 25A SmartChargePro35 RSCPR35-12v, 2 / 8 / 16 / 35A SmartChargePro50

More information

USER S MANUAL. MaxPower 400-600 UPS. Uninterruptible Power System 28-2MAXPO0018

USER S MANUAL. MaxPower 400-600 UPS. Uninterruptible Power System 28-2MAXPO0018 USER S MANUAL MaxPower 400-600 UPS Uninterruptible Power System 28-2MAXPO0018 IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions for models MaxPower 400 and

More information

Operating and Maintenance Instructions MEDIPOINT 125 MEDICAL GAS CENTRAL ALARM

Operating and Maintenance Instructions MEDIPOINT 125 MEDICAL GAS CENTRAL ALARM Operating and Maintenance Instructions MEDIPOINT 125 MEDICAL GAS CENTRAL ALARM CONTENTS SECTION 0. SAFETY, STORAGE AND HANDLING DATA 0.1 Indentification of symbols 0.2 Environmental conditions 0.3 Environmental

More information

Mobile Data Power Model: MDP-25

Mobile Data Power Model: MDP-25 Mobile Data Power Model: MDP-25 Topic Section Features... 2 Operational Features Summary... 2 Back-up Battery Power Internal Charger Voltage Spike Protection RF Noise Filtering Warning of Imminent Loss

More information

victron energie USER MANUAL GEBRUIKSAANWIJZING GEBRAUCHSANWEISUNG Victron Atlas 12/850

victron energie USER MANUAL GEBRUIKSAANWIJZING GEBRAUCHSANWEISUNG Victron Atlas 12/850 victron energie USER MANUAL GEBRUIKSAANWIJZING GEBRAUCHSANWEISUNG Victron Atlas 12/850 SECTIONS ENGLISH 1 NEDERLANDS 27 DEUTSCH 55 This page intentionally left blank. ENGLISH USER MANUAL Victron Atlas

More information

MSL1000 Monitored Serial Link Interface Manual V1.01

MSL1000 Monitored Serial Link Interface Manual V1.01 Audix Systems, Station Road, Wenden, Saffron Walden, Essex, CB11 4LG. Telephone: +44(0)1799 540888 Facsimile: +44(0)1799 541618 www.tycosafetyproducts-europe.com www.audixsystems.co.uk MSL1000 Monitored

More information

Fire Alarm Control Panel. Operating Manual

Fire Alarm Control Panel. Operating Manual Fire Alarm Control Panel Operating Manual CONTENTS ITEM Page Introduction and Characteristics Fire Alarm System Assembly Diagram Fire Alarm Signal Flow Chart Panel Descriptions Standard Detector Wiring

More information

Quantec Wiring Instructions

Quantec Wiring Instructions Approved Document No. DNUQ777 Rev Quantec Wiring Instructions GENERAL Quantec can be compared to a very sophisticated analogue addressable fire alarm system where the integrity of the wiring is of paramount

More information

AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL

AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL ATS-220 AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL For Use in 208 to 240 Volts Single and 3 Phase ATS Systems With 110Volt AC or DC Control Motors and selenoids 4501 NW 27 ave Miami FL 33142

More information