ESL 770 Series Projected Beam Smoke Detector Installation Instructions

Size: px
Start display at page:

Download "ESL 770 Series Projected Beam Smoke Detector Installation Instructions"

Transcription

1 ESL 770 Series Projected Beam Smoke Detector Installation Instructions U L LISTED The ESL 770 projected beam smoke detector consists of an optical transmitter and receiver and a control panel. A pulsed infrared beam is projected from the transmitter to the receiver. The beam is then continuously monitored by the control panel for interference caused by smoke. When smoke is present in the beam for 8 to 10 seconds, the detector sends an alarm. The detector is especially useful in applications where hallways and longer rooms need coverage. One detector can be used in place of several spot detectors. The detector is designed for use with a 24VDC auxiliary power supply from a main control panel. The detector can be configured for reflected beam operation for use in difficult applications. See Using eflected Beam Operation.! WANING It is important that you read, understand, and follow these instructions. If you have questions, call Sentrol at This document is intended for licensed electricians/ alarm installers. Sentrol cannot provide technical support to unqualified persons. Failure to properly install, test, and maintain a smoke detector system may cause it to fail resulting in loss of life and/or property. Selecting a Location Selecting a suitable location is critical to the operation of smoke detectors. To determine how many detectors you need and where to place them, you should follow the guidelines established by the National Fire Protection Agency (NFPA 72). In addition to NFPA 72, use the following guidelines to determine the best location for the detector components: The transmitter, receiver, and 770 control panel mount directly to walls. The 770 control panel should be located for easy access. The 770 control panel must be located so that the cable connecting it to the receiver is between 15 feet and 330 feet in length. Mount the transmitter and receiver at least 17 inches away from walls and ceilings as shown in Figure 1. The range for the transmitter/receiver is 33 to 330 feet. At 330 feet the beam has a diameter of approximately 10 feet and the detection coverage on either side of the beam is 25 feet. The maximum total coverage area is 16,500 square feet (50 feet x 330 feet). oute cables away from existing electrical cables and switchgear. The transmitter and receiver must be in clear view of each other. The receiver must be installed where strong light sources, artificial or natural, DO NOT project directly into the receiver lens. Parts List The following parts are included with the detector: Optical transmitter with clear lens Optical receiver with dark lens 770 control panel 2 angle brackets 4 screws Plastic control panel key Plastic test filter Important: In addition to the parts provided, you will need four screws for mounting the 770 control panel. 17in min. 25ft max. 50ft max. 50ft max. 17in min. 25ft max. Figure 1 - Locating the Detector 1

2 Locating in Peaked oofs A ceiling or roof with a slope in excess of 3.5 degrees should be considered a peaked roof. When the detector is installed in the tip of a peaked roof, the horizontal distance increases by 1% for each degree of ceiling slope up to 25% as shown in Figure 2. This only applies to a detector when it is installed in the tip of the peaked roof ' min. 10 Peaked oof 50'+ 2.5' 50'+2.5' 25' min. 6. Align the receiver head as close as possible with the transmitter head and carefully tighten the two thumbwheel screws on the receiver. 7. Connect system wiring as indicated in Figure 4. Both, the transmitter and receiver heads come with a 3.3 foot cable that should be connected to the system wiring. 8. Verify that the eset/test switch located in the control panel is in the ON position. 9. Turn the Signal Level potentiometer in the control panel to the midway position. 10. Connect the power supply to the control panel and verify that it is 24VDC within tolerance at the transmitter and control panel. The signal high or low LEDs may be on. 11. Align the transmitter and receiver. See Using a Voltmeter to Align the Transmitter and eceiver or Using an LED Alignment Meter to Align the Transmitter and eceiver. 12. Test the detector. See Testing the Detector. 30 Peaked oof ' max (25' + 25' +12.5') Figure 2 - Locating the Detector in Peaked oofs Installing the Detector Use the following steps to install the detector: Caution: You need to use an antistatic wrist strap when accessing the 770 control panel circuit board. 1. emove the appropriate knockouts on the 770 control panel sides to accommodate the system wiring. 2. Set the appropriate options in the 770 control panel. See Setting the Switches. 3. Mount the 770 control panel on a firm secure wall with four screws (not provided). 4. Set the transmitter range. See Setting the ange. 5. Mount the transmitter and receiver heads on the right-angle fixing brackets and position them on the line of sight. See Figure 3. Setting the Switches The options described in the following table are set from a switch pack on the 770 control panel circuit board as shown in Figure 4. Switch A larm Latch Controls the alarm reset. COMP 25%, 33%, 50% (Sensitivity) Open = Automatically resets when the alarm condition is no longer present. C losed = Manual reset. Factory Default Determines what happens compensation runs out. when the drift Open = Trouble signal is sent and further d egradation triggers an alarm. Factory Default. C losed = Trouble signal is sent. Selects the percentage of smoke density necessary to trigger an alarm. Open the switch to select a setting as follows: 25% = Used in a clean environment such as a computer room or office. 35% = Used for normal operation in most e nvironments. Factory Default. 50% = Used for reflected beam operation. 2

3 Setting the ange 1. emove the small white grommet on the transmitter head to access the range potentiometer. See Figure Use the following table to determine the appropriate range setting for an application. Thumbscrew Setting Grommet 10m 33 feet 30m 34 to 98 feet 100m 99 to 330 feet Fixing Bracket 3. Use a small flat-head screwdriver to move the potentiometer so the arrow points to the desired setting. Figure 3 - Mounting the Transmitter/eceiver elay wiring as required x Y B Signal x Low Signal Level High Trouble LED Test/eset ON OFF SW5 N/O N/C COM N/O N/C COM A L A M T O U B L E 100mA eset Test Meter Terminals Alarm Latch COMP 25% 33% 50% S U P P L Y 2 4 V B May be same power supply as for the detector control panel. emote reset switch or relay close momentarily to reset Figure 4 - Wiring Diagram 3

4 Using an LED Alignment Meter to Align the Transmitter and eceiver An alignment meter is optional and can be ordered through your distributor. Use the following steps to align the transmitter and receiver using the alignment meter: 1. Use a 3-conductor cable to connect the alignment meter to the 770 control panel as follows: Connect this on the alignment meter + V (red) +24V supply -V (black) -24V supply Meter O/P (yellow) To this on the circuit board in the detector control panel + Test meter terminal 2. Place the alignment meter so the LED indicator is within view of the transmitter. 3. Adjust the transmitter vertically and horizontally until you achieve the fastest blinking rate on the test meter LED. The LED should be on steadily when the alignment is successful. 4. At the 770 control panel, adjust the Signal Level potentiometer counter clockwise until the Sig Hi LED goes off. Both Sig Hi and Sig Lo LEDs should be off. 5. Set the eset/test switch to the OFF position. Both LEDs must be off before you set the eset/test switch to off or the drift compensation will not function. 6. Wait at least 45 seconds for the system to self calibrate before performing any tests. Testing the Detector Use the following steps to test the smoke detection: 1. Hold the plastic test filter in the beam path. After approximately 9 seconds, the alarm relay should switch and the red alarm LED should light. The alarm LED is located on the front cover of the 770 control panel. 2. emove the test filter and the alarm should reset after approximately 4 seconds. If the 770 control panel is set to manual reset, the alarm does not automatically reset. See esetting the Alarm. Use the following steps to test the trouble relay and indicator: 1. Block the beam completely. After about 10 seconds, the trouble relay should switch and the yellow trouble LED should light. The trouble LED is located inside the 770 control panel. 2. Clear the beam. After approximately 4 seconds, the trouble LED should reset. Using a Voltmeter to Align the Transmitter and eceiver Use the following steps to align the transmitter and receiver using a voltmeter: 1. Connect the leads of a DC voltmeter (set to 10V range) to the + and Test Meter terminals in the 770 control panel. 2. Adjust the transmitter vertically and horizontally until the maximum voltage is measured on the voltmeter. Maximum voltage is approximately 5V. The reading should be approximately 2.6V when no signal is present. 3. Carefully tighten the two thumbwheel screws on the transmitter securely. 4. At the 770 control panel, adjust the Signal Level potentiometer counter clockwise until the Sig Hi LED goes off. Both Sig Hi and Sig Lo LEDs should be off. 5. Set the eset/test switch to the off position. Both LEDs must be off before you set the eset/test switch to off or the drift compensation will not function. 6. Wait at least 45 seconds for the system to self calibrate before performing any tests. Troubleshooting Use the following steps to determine the cause of a trouble indication: Verify that the Test/eset switch in the 770 control panel is in the OFF position allowing normal operation. Check for beam blockage. If 93% or more of the beam is blocked for approximately ten seconds, a trouble condition is indicated. Check the drift compensation. When the detector runs out of drift compensation, a trouble condition is indicated. If the detector is out of compensation, the alignment reading from the test meter outputs will be significantly lower than 4.1V. Verify that power is present at the detector control panel and transmitter. Loss of power will cause a trouble condition. Check beam alignment. Incorrect alignment may cause a trouble condition. 4

5 Using eflected Beam Operation The detector can be used in a reflected beam configuration where the transmitter and receiver heads are mounted adjacent to each other and the beam is reflected off one or more prisms mounted on the opposite wall. eflected beam operation is used for applications where access to the opposite wall is restricted or wiring is difficult. In addition to the installation instructions (See Installing the Detector), use the following instructions to configure the detector for reflected beam operation: 1. Set the sensitivity switch to 50%. See Setting the Switches. 2. Mount the transmitter and receiver heads adjacent to one another as closely as possible. 3. Mount prism(s) on the opposite wall. Prism(s) should be mounted at right angles to the beam. There must be a clear line of sight between the transmitter head, prism(s) and receiver head. For more information, see the prism installation instructions. 4. Once the system is aligned and tested, test the reflected beam operation as follows: -Block the beam in front of the prisms. The trouble LED should light. -If no trouble is indicated, the beam may be being reflected via a surface other that the prisms. Ordering Prisms Call to order prisms. The number of prisms required for a reflected beam application varies depending on the beam range as described in the following table: Beam ange 6.5 to 82 feet 1 82 to 115 feet to 148 feet 6 Prisms required esetting the Alarm The alarm may be reset using any of the following methods: Set the Alarm Latch switch to open for automatic reset. Use the eset/test switch on the 770 control panel. Install a remote reset switch. See Figure 4. emove power to the 770 control panel for 1 second. Maintenance Very little maintenance is required for reliable operation of the ESL 770 Series smoke detector. Wipe the optical lenses with a clean, lint-free cloth once a year, depending on the environmental conditions. Limited Warranty Sentrol is a brand name of SLC Technologies, Inc. The manufacturer warrants this smoke detector (except batteries) to be free from defects in material and workmanship under conditions of normal use for a term of 3 years from the date of manufacture. During the warranty period, if a Sentrol product or any of its components becomes defective, it will be repaired or replaced without charge at the manufacturer s discretion. This warranty does not apply to units which have been subject to abuse, misuse, negligence or accident, or to which any modifications, alterations or repairs have been made or attempted. This warranty is extended only to the original purchaser of the smoke detector and may be enforced only by such person. The defective smoke detector must be returned in accordance with the following instructions: Obtain a eturn Authorization Number by calling or , then carefully pack it in a well padded and insulated carton and return, postal charges prepaid to: Customer Service Sentrol SW Leveton Drive Tualatin, O A note should be included advising the nature of the malfunction. Care must be exercised in the proper packing of detectors returned under this warranty as Sentrol will not be responsible for warranty repairs to equipment damaged because of improper packing. THE ABOVE WAANTY IS IN LIEU OF ALL OTHE EXPESS WAANTIES, AND IMPLIED WAANTIES OF MECHANTABILITY AND FITNESS FO A PATICU- LA PUPOSE AE LIMITED IN DUATION FO A PE- IOD OF 3 YEAS FOM THE DATE OF MANUFAC- TUE. UNDE NO CICUMSTANCES SHALL MANU- FACTUE BE LIABLE TO THE PUCHASE O ANY OTHE PESON FO INCIDENTAL O CONSEQUEN- TIAL DAMAGES OF ANY NATUE, INCLUDING WITH- OUT LIMITATION DAMAGES FO PESONAL INJUY O DAMAGES TO POPETY, AND HOWEVE OCCA- SIONED, WHETHE ALLEGED AS ESULTING FOM BEACH OF WAANTY BY MANUFACTUE, THE NEGLIGENCE OF MANUFACTUE O OTHEWISE. MANUFACTUE S LIABILITY WILL IN NO EVENT EX- CEED THE PUCHASE PICE OF THE PODUCT. SOME STATES DO NOT ALLOW LIMITATIONS ON HOW LONG AN IMPLIED WAANTY LASTS, O THE EXCLUSION O LIMITATION OF INCIDENTAL O CONSEQUENTIAL DAMAGES, SO THE ABOVE LIMITATIONS AND EXCLU- SIONS MAY NOT APPLY TO YOU. UNLESS A LONGE PEIOD IS EQUIED BY APPLICABLE LAW, ANY AC- TION AGAINST MANUFACTUE IN CONNECTION WITH THIS SMOKE DETECTO MUST BE COM- MENCED WITHIN ONE YEA AFTE THE CAUSE OF ACTION HAS OCCUED. No agent, employee or representative of the Manufacturer nor any other person is authorized to modify this warranty in any respect. epair or replacement as stated above is the exclusive remedy of the purchase hereunder. This warranty gives you specific legal rights and you also have other rights which vary from state to state. 5

6 Specifications Operating voltage...24vdc (+10% -15%) Typical average standby current...13 ma Typical average alarm current...20 ma Transmitter current ma elay 24VDC Sensitivity photoelectric...25%,35%,50% Beam tolerance to misalignment at 35%: Transmitter...+/- 1 eceiver...+/- 4 Operating range...33 to 330 feet Operating temperature...-4 F to 131 F Operating humidity % non-condensing FI 100 Khz - 1 Ghz Color...white Field wiring size AWG Number of beam sets per 770 control panel...1 Weight: Control panel lbs eceiver w/ bracket...12 oz Transmitter w/ bracket...12 oz Dimensions (w x h x d): Transmitter head w/ brackets...4"x 3¼"x 3¾" eceiver head w/ brackets...4"x 3¼" x 3¾" Control panel...8½" x 10½" x 3½" Auto reset time...< 5 sec Warranty...3 years Listing...UL 268 Ordering Model number 771-kit 4-wire projected-beam detector consisting of transmitter, receiver, and control panel Accessories 770-meter LED alignment meter ESL a product of sentrol SENTOL SW Leveton Dr., Tualatin, O Tel.: Fax: U.S. & Canada: Technical Service: FaxBack: Sentrol reserves the right to change specifications without notice Sentrol ev B 01/00

FIRERAY 2000 Installation Guide

FIRERAY 2000 Installation Guide FIRERAY 2000 Installation Guide Features Range 33ft to 330 ft. 24Vdc operation Selectable alarm thresholds Low current consumption Ground level electronics Manual or Automatic reset System Description

More information

Model SRMD Setra Remote Monitoring Display

Model SRMD Setra Remote Monitoring Display Model SRMD Setra Remote Monitoring Display 1.0 GENERAL INFORMATION Thank you for purchasing the Setra Remote Monitoring Display (SRMD). The SRMD is a digital panel meter with a bright 1 LED display for

More information

Advantium 2 Plus Alarm

Advantium 2 Plus Alarm ADI 9510-B Advantium 2 Plus Alarm INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Carefully Read These Controls Corporation of America 1501 Harpers Road Virginia

More information

LOS 2500 SUPER CEILING SENSOR. Installation Manual

LOS 2500 SUPER CEILING SENSOR. Installation Manual LOS 2500 SUPER CEILING SENSOR Installation Manual How Do RAB Occupancy Sensors Work? Selecting A Location: The L0S2500 sensor sees infrared heat changes caused by the motion of people within its detection

More information

D7050/D7050TH. Installation Instructions. Multiplex Photoelectric Smoke Detectors

D7050/D7050TH. Installation Instructions. Multiplex Photoelectric Smoke Detectors D7050/D7050TH EN Installation Instructions Multiplex Photoelectric Smoke Detectors D7050/D7050TH Installation Instructions.0 Description Notices These instructions cover the installation of the D7050/D7050TH

More information

Installation and Operation Manual. Digital Remote Meter for Monitoring System Performance. Version: RM-1

Installation and Operation Manual. Digital Remote Meter for Monitoring System Performance. Version: RM-1 REMOTE METER TM Installation and Operation Manual. Digital Remote Meter for Monitoring System Performance. Version: RM-1 1098 Washington Crossing Road Washington Crossing, PA 18977 USA www.morningstarcorp.com

More information

Installation and Operation Guide for PD5100 Automatic Transfer Switch

Installation and Operation Guide for PD5100 Automatic Transfer Switch Installation and Operation Guide for PD5100 Automatic Transfer Switch Member P r o gr e ssive Dynamics, Inc. 507 Industrial Rd Marshall, MI 49068 www.progressivedyn.com 2012 Progressive Dynamics, Inc.

More information

Indoor/Outdoor Color Camera with Built-in 2.4 GHz Wireless Transmitter, plus X10 controlled power supply, and Video Receiver.

Indoor/Outdoor Color Camera with Built-in 2.4 GHz Wireless Transmitter, plus X10 controlled power supply, and Video Receiver. Indoor/Outdoor Color Camera with Built-in 2.4 GHz Wireless Transmitter, plus X10 controlled power supply, and Video Receiver. OWNER'S MANUAL VR36A XC18A XM13A MODEL VK69A (INCLUDES XC18A CAMERA, XM13A

More information

Wireless Indoor/ Outdoor Thermometer

Wireless Indoor/ Outdoor Thermometer Wireless Indoor/ Outdoor Thermometer Owner s Manual Please read before using this equipment. ˆ Contents FCC Information... 3 FCC Declaration of Conformity... 5 Preparation... 5 Installing Batteries...

More information

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short

More information

Installation Manual. Features SMART SWITCH OCCUPANCY SENSOR. Maximum Energy savings

Installation Manual. Features SMART SWITCH OCCUPANCY SENSOR. Maximum Energy savings Features SMART SWITCH OCCUPANCY SENSOR Installation Manual Maximum Energy savings Sensitive 180º view passive infrared motion detector keeps lights on only when rooms are in use. No ON switch so lights

More information

Detector transparent with Color Inserts. FAA 500 TR P Trim Ring transparent with Color Inserts. FCA 500 / FCA 500 E Detector Bases

Detector transparent with Color Inserts. FAA 500 TR P Trim Ring transparent with Color Inserts. FCA 500 / FCA 500 E Detector Bases Detector Color Detector transparent with Color Inserts FAA 500 TR W Trim Ring FAA 500 TR P Trim Ring transparent with Color Inserts FAA 500 BB Ceiling Mount Back Box FCA 500 / FCA 500 E Detector Bases

More information

SOLAR ELECTRIC MODULE ES-124 & ES-62T Owners Manual and Installation Guide

SOLAR ELECTRIC MODULE ES-124 & ES-62T Owners Manual and Installation Guide SOLAR ELECTRIC MODULE ES-124 & ES-62T Owners Manual and Installation Guide circuit. Reverse connection will damage the module and may result in fire. CAUTIONS Solar electric modules produce DC electricity

More information

RI-215A Operator s Manual. Part Number: 71-0045RK Revision 0 Released: 10/3/05

RI-215A Operator s Manual. Part Number: 71-0045RK Revision 0 Released: 10/3/05 RI-215A Operator s Manual Part Number: 71-0045RK Revision 0 Released: 10/3/05 Warranty RKI Instruments, Inc., warrants gas alarm equipment sold by us to be free from defects in materials and workmanship,

More information

HM-W536 Install Guide

HM-W536 Install Guide HM-W536 Install Guide 9/13/2013 IMPORTANT SAFETY INSTRUCTIONS Warning - When using electrical devices, basic safety precautions should be followed to reduce the risk of fire, electrical shock or injury.

More information

ATS Overhead Table Shelf System INSTRUCTION MANUAL

ATS Overhead Table Shelf System INSTRUCTION MANUAL ATS Overhead Table Shelf System INSTRUCTION MANUAL ATS Overhead Table Shelf System Instruction Manual Warranty Newport Corporation warrants this product to be free of defects in material and workmanship

More information

Installation Instructions

Installation Instructions 520 Installation Instructions Thank you very much for purchasing PIAA product. Please read this entire manual before installation and use of this product. For Installers Please give this Installation Manual

More information

WATERBUG@ INSTALLATION / OWNERS MANUAL MODEL WB-200. PN # D-01 l-0007

WATERBUG@ INSTALLATION / OWNERS MANUAL MODEL WB-200. PN # D-01 l-0007 WATERBUG@ INSTALLATION / OWNERS MANUAL MODEL WB-200 PN # D-01 l-0007 REV B INTRODUCTION Thank you for your purchase of the Winland WaterBug@ mode I WB-200. The WaterBug@ is completely electronic and is

More information

ESL 500 Series. Smoke Detector. Installation Instructions

ESL 500 Series. Smoke Detector. Installation Instructions ON 1 2 Smoke Installation Instructions Description The Smoke s offer 2-wire, 4-wire, 12VDC, and 24VDC detectors for fire system applications. Depending on the model, the smoke detector provides the following

More information

AX-100TFR/AX-200 TFR INSTALLATION INSTRUCTIONS INTRODUCTION 1-1 BEFORE YOUR OPERATION BATTERY OPERATED PHOTOELECTRIC DETECTOR.

AX-100TFR/AX-200 TFR INSTALLATION INSTRUCTIONS INTRODUCTION 1-1 BEFORE YOUR OPERATION BATTERY OPERATED PHOTOELECTRIC DETECTOR. FEATURES 4 5 6 No.59-55- 09040 INSTALLATION INSTRUCTIONS N9 BATTERY OPERATED PHOTOELECTRIC DETECTOR AX-00TFR/AX-00 TFR : Detection range: 0 m (00 ft.) : Detection range: 60 m (00 ft.) Battery-operated

More information

PASSIVE INFRARED INTRUSION DETECTOR PASSIVE INFRAROOD DETECTOR DETECTEUR D INTRUSION PASSIF INFRAROUGE

PASSIVE INFRARED INTRUSION DETECTOR PASSIVE INFRAROOD DETECTOR DETECTEUR D INTRUSION PASSIF INFRAROUGE MODEL HAA51 PASSIVE INFRARED INTRUSION DETECTOR PASSIVE INFRAROOD DETECTOR DETECTEUR D INTRUSION PASSIF INFRAROUGE OPERATING MANUAL HAA51 PASSIVE INFRARED INTRUDER DETECTOR INTRODUCTION HAA51 Passive Infrared

More information

WINEGARD MOTORIZED SENSAR ANTENNA Models MA1055W & MA1055G MADE IN U.S.A. U.S. Patents D500,496 and 7,358,909 INSTALLATION MANUAL

WINEGARD MOTORIZED SENSAR ANTENNA Models MA1055W & MA1055G MADE IN U.S.A. U.S. Patents D500,496 and 7,358,909 INSTALLATION MANUAL WINEGARD MOTORIZED SENSAR ANTENNA Models MA1055W & MA1055G MADE IN U.S.A. U.S. Patents D500,496 and 7,358,909 INSTALLATION MANUAL CAUTION: This system is not for use with antenna in raised position while

More information

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MF08CESWW. Voltage rating: 115V~60Hz Power rating : 800W

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MF08CESWW. Voltage rating: 115V~60Hz Power rating : 800W MODE ALARM Portable Air Conditioner OWNER S MANUAL Read these instructions before use 8 Model: MF08CESWW Voltage rating: 115V~60Hz Power rating : 800W Customer Support : 1-800-474-2147 For product inquiries

More information

AGS. Owner's Manual. Xantrex Automatic Generator Start Control System

AGS. Owner's Manual. Xantrex Automatic Generator Start Control System AGS Owner's Manual Xantrex Automatic Generator Start Control System TABLE OF CONTENTS INTRODUCTION...3 Main Features...3 Safety Summary...3 THINGS YOU SHOULD KNOW...4 THEORY OF OPERATION...5 System...5

More information

DSM155 Digital LED Light Meter User s Manual DSM155

DSM155 Digital LED Light Meter User s Manual DSM155 DSM155 Digital LED Light Meter User s Manual DSM155 CONTENTS TABLE OF CONTENTS......3 LIMITED WARRANTY AND LIMITATION OF LIABILITY......3 Out of Box....3 Accessories....3 Safety Information....3 Certification....5

More information

PK5500 v1.1 Installation Instructions

PK5500 v1.1 Installation Instructions PK5500 v1.1 Installation Instructions 1 2 3 4 5 6 7 8 9 * 0 # WARNING: Please refer to the System Installation Manual for information on limitations regarding product use and function and information on

More information

LiteAide OWNER'S MANUAL PREASSEMBLED AUTOMATIC SECURITY FLOODLIGHTS MOTION SENSOR SECURITY LIGHTING SYSTEMS

LiteAide OWNER'S MANUAL PREASSEMBLED AUTOMATIC SECURITY FLOODLIGHTS MOTION SENSOR SECURITY LIGHTING SYSTEMS OWNER'S MANUAL PREASSEMBLED AUTOMATIC SECURITY FLOODLIGHTS MOTION SENSOR SECURITY LIGHTING SYSTEMS LiteAide HE-100B HE-100BW HE-112 HE-112W HE-117 HE-117W HE-117-2B OWNER'S MANUAL FLOOD LAMPS (BULBS) Your

More information

FIRE DETECTORS LIMITED XP95 BEAM DETECTOR INSTALLATION GUIDE

FIRE DETECTORS LIMITED XP95 BEAM DETECTOR INSTALLATION GUIDE PP2079/2002/Issue 6 FIRE DETECTORS LIMITED XP95 BEAM DETECTOR INSTALLATION GUIDE Apollo Fire Detectors, 36 Brookside Road, Havant, Hampshire, England www.apollo-fire.co.uk XP95 BEAM DETECTOR GENERAL INFORMATION

More information

CENTERLINE Motor Control Centers Bulletin 2100 Smoke Detector Unit

CENTERLINE Motor Control Centers Bulletin 2100 Smoke Detector Unit Instructions CENTERLINE Motor Control Centers Bulletin 2100 Smoke Detector Unit Catalog Number 2100-SD1 Description The Bulletin 2100 smoke detector unit is a 0.5 space factor unit for use in Bulletin

More information

Die-Cast Metal, Motion- Activated Post Light

Die-Cast Metal, Motion- Activated Post Light TM Die-Cast Metal, Motion- Activated Post Light Model: SH-9392AU Installation and Operating Instructions FEATURES Automatically comes on when motion is detected. Automatically turns light off. Photocell

More information

GENERATOR START CONTROL MODULE - MINI (2 Wire to 3 Wire)

GENERATOR START CONTROL MODULE - MINI (2 Wire to 3 Wire) FEATURES & APPLICATIONS Inexpensive 2 wire to 3 wire start controller for electric start high speed gas generators. Optimized for use with Outback Invertors. Supports three types of 3 wire generator control

More information

FriendlyNet Hub 5-Port or 8-Port Ethernet Hub User s Manual

FriendlyNet Hub 5-Port or 8-Port Ethernet Hub User s Manual FriendlyNet Hub 5-Port or 8-Port Ethernet Hub User s Manual Asanté Technologies, Inc. 821 Fox Lane San Jose, CA 95131 Copyright Notice Copyright 1997 by Asanté Technologies, Inc. All rights reserved. No

More information

16/32 Channel 1U Rack Mount CCTV Power Supply

16/32 Channel 1U Rack Mount CCTV Power Supply 16/32 Channel 1U Rack Mount CCTV Power Supply Manual PH-A3224-GUQ Shown 16-Channel 32-Channel PTC PH-A1612-PUQ PH-A3224-PUQ Glass Fuse PH-A1612-GUQ PH-A3224-GUQ Industrial design 12 Amp 3 Amps per channel

More information

The table below lists the symbols used on the Clamp and/or in this manual. Important Information. See manual.

The table below lists the symbols used on the Clamp and/or in this manual. Important Information. See manual. i800 AC Current Clamp Instruction Sheet Introduction The i800 AC Current Clamp, the Clamp, has been designed for use with multimeters, recorders, power analyzers, safety testers, etc., for accurate non-intrusive

More information

Motion Detector 360 Degrees 5420/360. Installation Instructions REGISTERED DESIGN REGISTERED PATENT

Motion Detector 360 Degrees 5420/360. Installation Instructions REGISTERED DESIGN REGISTERED PATENT Motion Detector 360 Degrees 5420/360 Installation Instructions REGISTERED DESIGN REGISTERED PATENT Installation Instructions The Infra-red Monitor Motion Detector from Clipsal provides high performance

More information

SSW-iLM Keypad. Wire Harness Configuration. Note: This product is designed to be installed and serviced by security and lock industry professionals

SSW-iLM Keypad. Wire Harness Configuration. Note: This product is designed to be installed and serviced by security and lock industry professionals SSW-iLM Keypad Note: This product is designed to be installed and serviced by security and lock industry professionals Specifications Case dimensions: 6 1/2 L x 1 3/4 W x 1 1/8 D Electrical: 5-12VDC Only

More information

Radiant Temperature Sensor TY7321

Radiant Temperature Sensor TY7321 AB-5361-U Specifications/Instructions Radiant Temperature TY7321 General TY7321 Radiant Temperature s are designed to measure infrared radiation from perimeter windows and walls and provide a proportional

More information

Single Station Remote Alarm

Single Station Remote Alarm ADI 5106G Certified ISO 9001:2000 Single Station Remote Alarm 529 5106-01-120 529 5106-01-220 INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Controls Corporation

More information

Passive Infrared Motion Detector 5420/90. Installation Instructions

Passive Infrared Motion Detector 5420/90. Installation Instructions Passive Infrared Motion Detector Installation Instructions 5420/90 The 5420/90 Passive Infrared Motion Detector provides reliable, high performance detection at an affordable price. The Detector features

More information

Owner s Manual & Safety Instructions

Owner s Manual & Safety Instructions Owner s Manual & Safety Instructions Save This Manual Keep this manual for the safety warnings and precautions, assembly, operating, inspection, maintenance and cleaning procedures. Write the product s

More information

Part I - Installation

Part I - Installation 400 Series Pressure and Differential Pressure Switches Types: H400, H402, H403, H400K, H402K, J400, J402, J403, J400K, J402K UNITED ELECTRIC CONTROLS Installation and Maintenance Instructions Please read

More information

LCD5500Z / PKP-LCD v3.x Installation Instructions

LCD5500Z / PKP-LCD v3.x Installation Instructions LCD5500Z / PKP-LCD v3.x Installation Instructions TM Introduction The LCD5500Z / PKP-LCD keypad displays system status using an LCD screen. The keypad can be used on PowerSeries security systems with up

More information

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MN12CES / MN10CESWW

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MN12CES / MN10CESWW Portable Air Conditioner OWNER S MANUAL Read these instructions before use 8 Model: MN12CES / MN10CESWW Voltage rating: 120V~60Hz Power rating : 1100W (MN12CES) Power rating : 900W (MN10CESWW) Customer

More information

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CCS. Voltage rating: 115V~60Hz Power rating : 1400W

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CCS. Voltage rating: 115V~60Hz Power rating : 1400W Portable Air Conditioner OWNER S MANUAL Read these instructions before use Model: MM14CCS Customer Support : 1-800-474-2147 Voltage rating: 115V~60Hz Power rating : 1400W For product inquiries or support

More information

Dual Laser InfraRed (IR) Thermometer with Color Alert

Dual Laser InfraRed (IR) Thermometer with Color Alert User Manual Dual Laser InfraRed (IR) Thermometer with Color Alert MODEL 42509 Introduction Congratulations on your purchase of the Model 42509 IR Thermometer with Color Alert. This Infrared thermometer

More information

Wireless Base Station Single and Multiple Headsets

Wireless Base Station Single and Multiple Headsets Wireless Base Station Single and Multiple Headsets Operation Manual 7340 SW Durham Road Portland, OR 97224 USA Phone: 503-684-6647 1-800-527-0555 Fax: 503-620-2943 email: sales@firecom.com www.firecom.com

More information

USER MANUAL WARNING! CONTENTS MODEL 1 SPECIFICATIONS READ ALL INSTRUCTIONS BEFORE PROCEEDING. Non-Programmable Single Stage Heat/Cool Thermostat

USER MANUAL WARNING! CONTENTS MODEL 1 SPECIFICATIONS READ ALL INSTRUCTIONS BEFORE PROCEEDING. Non-Programmable Single Stage Heat/Cool Thermostat Builder MODEL 1010 Series Non-Programmable Single Stage Heat/Cool Thermostat USER MANUAL Compatible with low voltage single stage gas, oil or electric heating or cooling systems, including single stage

More information

Remote Alarm Monitoring System

Remote Alarm Monitoring System Remote Alarm Monitoring System Operation and Service Manual Model RA1 RA4 A A Version HELMER SCIENTIFIC 14400 Bergen Boulevard Noblesville, IN 46060 USA PH +1.317.773.9073 FAX +1.317.773.9082 USA and Canada

More information

OPL BASIC. Dosing System for Professional Laundry machines. Contents

OPL BASIC. Dosing System for Professional Laundry machines. Contents OPL BASIC Dosing System for Professional Laundry machines Contents 1 Getting Started. Page 2 2 Installation. Page 4 3 Set Up & Operation. Page 8 4 Maintenance & Accessories. Page 10 5 Troubleshooting Page

More information

SECURITY LIGHT. motion-activated. Assembly & operating instructions Solar Motion-Activated Security Light - 80 LED Lights

SECURITY LIGHT. motion-activated. Assembly & operating instructions Solar Motion-Activated Security Light - 80 LED Lights motion-activated SECURITY LIGHT Model #: 40225, 40226 Assembly & operating instructions Solar Motion-Activated Security Light - 80 LED Lights Important: Read all instructions carefully before use About

More information

8-Ohm Ceiling Speakers For Music and Home Theater

8-Ohm Ceiling Speakers For Music and Home Theater 8-Ohm Ceiling Speakers For Music and Home Theater Owners Manual INTRODUCTION M&S ceiling speakers are designed to provide clear, sharply-focused audio reproduction while remaining unobtrusively in the

More information

Dual Laser InfraRed (IR) Thermometer

Dual Laser InfraRed (IR) Thermometer User Manual Dual Laser InfraRed (IR) Thermometer MODEL 42570 Introduction Congratulations on your purchase of the Model 42570 IR Thermometer. This Infrared thermometer measures and displays non-contact

More information

Operation and Installation Manual

Operation and Installation Manual Operation and Installation Manual RCM-10 Remote Control Monitor and RSM-10 Remote Status Monitor for the CNA-100 & CNA-200 Automations Revision 1.1 9/98 WARRANTY INFORMATION The RCM-10 Remote Control

More information

ACS-30-EU-EMDR-10-MOD

ACS-30-EU-EMDR-10-MOD Multi-application heat tracing Control and Monitoring in commercial and residential buildings Roof & Gutter de-icing sensor module Technical Information Approvals Module IP rating Ambient operating temperature

More information

Instructions A622 100 Amp AC/DC Current Probe 070-8883-03

Instructions A622 100 Amp AC/DC Current Probe 070-8883-03 Instructions A622 100 Amp AC/DC Current Probe 070-8883-03 Revision A www.tektronix.com 070888303 Copyright Tektronix, Inc. All rights reserved. Tektronix products are covered by U.S. and foreign patents,

More information

VARIO PROX CARD READER INSTALLATION MANUAL

VARIO PROX CARD READER INSTALLATION MANUAL VARIO PROX CARD READER INSTALLATION MANUAL TABLE OF CONTENTS 1.0 INTRODUCTION...2 1.1 Legend...3 1.2 Terminology...4 2.0 MOUNTING...5 3.0 WIEGAND CONNECTION...6 4.0 AUX BUTTON INPUT...7 5.0 INSTALLER PROGRAMMING...8

More information

GSM Gate Opener GSM Remote Switch RTU5015 User Manual

GSM Gate Opener GSM Remote Switch RTU5015 User Manual GSM Gate, Barrier, Shutter, Garage Door and Door opener Open gate or garage door with a FREE call from your mobile phone! Remote switching machines with a FREE call from your mobile phone! GSM Gate Opener

More information

ALL WEATHER W-SERIES QUARTZ TUBE ELECTRIC INFRARED RADIANT HEATER INSTALLATION USE & CARE MANUAL

ALL WEATHER W-SERIES QUARTZ TUBE ELECTRIC INFRARED RADIANT HEATER INSTALLATION USE & CARE MANUAL ALL WEATHER W-SERIES QUARTZ TUBE ELECTRIC INFRARED RADIANT HEATER TABLE OF CONTENTS: INSTALLATION USE & CARE MANUAL IMPORTANT INFORMATION Assembly Instructions 2 Wiring Instructions 2 Outdoor Installation

More information

Automatic Phone-Out Home Monitoring Systems

Automatic Phone-Out Home Monitoring Systems Automatic Phone-Out Home Monitoring Systems Power Outage and Freeze Alarm Model Number: THP202 Power Outage, Freeze and Flood Alarm Product Description Model Number: THP201 These monitoring systems are

More information

User's Guide. Integrating Sound Level Datalogger. Model 407780. Introduction

User's Guide. Integrating Sound Level Datalogger. Model 407780. Introduction User's Guide 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com Back to the Extech 407780 Product Page Integrating Sound Level Datalogger

More information

Model RPM10 Laser Photo / Contact Tachometer with IR Thermometer Patented

Model RPM10 Laser Photo / Contact Tachometer with IR Thermometer Patented User's Guide Model RPM10 Laser Photo / Contact Tachometer with IR Thermometer Patented Introduction Congratulations on your purchase of Extech's Laser Photo/Contact Tachometer with Non- Contact IR Thermometer,

More information

Freeze Protection Thermostats MODELS SST 2. Installation and Operation Manual

Freeze Protection Thermostats MODELS SST 2. Installation and Operation Manual Freeze Protection Thermostats MODELS SST 2 Part Number 22744 MANUAL We Manage Heat Installation and Operation Manual Environmental Technology, Inc. 1850 N Sheridan Street South Bend, Indiana 46628 (574)

More information

2.0 Installation 1. Remove the cover using a small flat blade screwdriver. Figure 2: Cover Removal

2.0 Installation 1. Remove the cover using a small flat blade screwdriver. Figure 2: Cover Removal O N DS160/DS161 Installation Guide High Performance Request-to-Exit Sensors 1.0 Description The DS160/161 is a passive-infrared (PIR) detector designed for Request to Exit (REX) interior applications.

More information

Leak Detection System

Leak Detection System Instructions - Parts List Leak Detection System 311200A For detecting leaks in your diaphragm pump system. Not for use in explosive atmospheres. Part No. 234576 120 psi (0.8 MPa, 8 bar) Maximum Air Input

More information

Ultrasonic Distance Meter. Operation Manual

Ultrasonic Distance Meter. Operation Manual XPROTEC Ultrasonic Distance Meter Operation Manual About XProTec Pro-Installer Tools The XProTec line from XFTP is a comprehensive lineup of professionalgrade technical tools. These full-featured, field-proven,

More information

WARNING: This product contains chemicals known to the state of California to cause cancer, or birth defects or other reproductive harm.

WARNING: This product contains chemicals known to the state of California to cause cancer, or birth defects or other reproductive harm. WARNING: This product contains chemicals known to the state of California to cause cancer, or birth defects or other reproductive harm. 9780 SW Freeman Drive Wilsonville, OR 97070 USA Tel: 800-442-2406

More information

EE-SPY801/802. Photomicrosensors for detecting wafer-carrier mounting. Wafer-carrier Mounting Photomicrosensors. Ordering Information.

EE-SPY801/802. Photomicrosensors for detecting wafer-carrier mounting. Wafer-carrier Mounting Photomicrosensors. Ordering Information. Wafer-carrier Mounting Photomicrosensors EE-SPY1/ CSM_EE-SPY1 DS_E_3_ Photomicrosensors for detecting wafer-carrier mounting. The mounting position is set with a pedestal. The contact surface with the

More information

12 Volt 30 Amp Digital Solar Charge Controller

12 Volt 30 Amp Digital Solar Charge Controller 12 Volt 30 Amp Digital Solar Charge Controller User s Manual WARNING Read carefully and understand all INSTRUCTIONS before operating. Failure to follow the safety rules and other basic safety precautions

More information

SP4-LOC SAFEPATH4 REMOTE MICROPHONE AND LOCAL OPERATOR CONSOLE

SP4-LOC SAFEPATH4 REMOTE MICROPHONE AND LOCAL OPERATOR CONSOLE SP4LOC SAFEPATH4 REMOTE MICROPHONE AND LOCAL OPERATOR CONSOLE INSTALLATION AND OPERATION MANUAL MASS NOTIFICATION SYSTEM Part Number: P84767 Rev. A Copyright 2006 Cooper Wheelock, Inc. All rights reserved.

More information

Smoke Detectors Ordering Information DS230 DS230 Series Heat Detectors DS230F DS233F Peripheral Accessories EOL200 TP280 Bases Features

Smoke Detectors Ordering Information DS230 DS230 Series Heat Detectors DS230F DS233F Peripheral Accessories EOL200 TP280 Bases Features Smoke Detectors DS230 Series Heat Detectors DS230, DS230F and DS233F Heat Detectors 2-wire: See Tech Service Note P/N: 26979. 4-wire: Compatible with all UL Listed 4-wire control panels. Ordering Information

More information

Dual Laser InfraRed (IR) Thermometer

Dual Laser InfraRed (IR) Thermometer User s Manual Dual Laser InfraRed (IR) Thermometer MODEL 42511 Introduction Congratulations on your purchase of the Model 42511 IR Thermometer. This Infrared thermometer measures and displays non-contact

More information

T7560A,B,C Digital Wall Module

T7560A,B,C Digital Wall Module T7560A,B,C Digital Wall Module HONEYWELL EXCEL 5000 OPEN SYSTEM BEFORE INSTALLATION All wiring must comply with local electrical codes and ordinances or as specified on installation wiring diagrams. Digital

More information

DBF 4XL Dryer Booster Fans

DBF 4XL Dryer Booster Fans Installation and Operation Manual Item #: 401315 Rev Date: 121514 DBF 4XL Dryer Booster Fans DBF4XL Kit Includes: Dryer Booster Fan, 1 pc Fan Mounting Bracket and Hardware, 1 pc Wall Label (Mount on wasll

More information

FLEX by 3M Light Module System

FLEX by 3M Light Module System FLEX by M Light Module System Application FLEX by M (the Product ) is a modular lighting system for dry, interior use (the Application ). The Product allows easy creation of long, D lighting paths along

More information

CelluLine CGW-TS GSM Cellular Gateway. Installation and Programming Manual

CelluLine CGW-TS GSM Cellular Gateway. Installation and Programming Manual CelluLine CGW-TS GSM Cellular Gateway Installation and Programming Manual CelluLine CGW-TS GSM Cellular Gateway Installation and Programming Manual CGWTS-M001A Version 1, Release 1, December 2004 NOTICE

More information

Water Leak Detection System

Water Leak Detection System Water Leak Detection System Installation and Operating Manual 505-334-5865 ph 505-334-5867 fax www.rodisystems.com email:info@rodisystems.com 936 Highway 516 Aztec, NM 87410-2828 Manual Revisions and Copyright

More information

TABLE 1: Wiring Terminals. Connect to... 1C 1H 2C 2H 1H1C 2H1C 2H2C 3H2C

TABLE 1: Wiring Terminals. Connect to... 1C 1H 2C 2H 1H1C 2H1C 2H2C 3H2C Installation TURN OFF POWER TO THE SYSTEM AT THE MAIN POWER PANEL TO AVOID ELECTRICAL SHOCK. Installation should be carried out by an electrician or a qualified technician. 1.1 Find a Location for the

More information

MEDION LIMITED WARRANTY Medion warrants that the product accompanied by this limited warranty is free from manufacturing defects in material or workmanship for a period of 12 months from the date of original

More information

E-PDD Duct Smoke Detector Installation Sheet

E-PDD Duct Smoke Detector Installation Sheet E-PDD Duct Smoke Installation Sheet Operation The duct smoke detector's primary purpose is to provide early warning of an impending fire and shut down the HVAC unit in order to prevent smoke from circulating

More information

Solar Power Systems Models: PVS220W-24 and PVS220W-48 Installation Manual

Solar Power Systems Models: PVS220W-24 and PVS220W-48 Installation Manual Solar Power Systems Models: PVS220W-24 and PVS220W-48 Installation Manual 255379 Rev. D0 1015 Printed in U.S.A. Copyright 2015 Federal Signal Corporation Limited Warranty The Alerting and Notification

More information

BroadBand PowerShield. User Manual

BroadBand PowerShield. User Manual BroadBand PowerShield User Manual 990-0375G 12/2006 Chapter 1 General Information The PowerShield provides a power source for broadband telephony and other DC applications. Safety This Safety Guide contains

More information

Shunt lock function 3066

Shunt lock function 3066 Version: January 2004 Contents Alarm System Activation unit Deactivation unit Digital locking cylinder or Smart Relay 1.0 Method of Operation 4 1.1 General 4 1.2 Turning the Alarm System On 4 1.3 Turning

More information

High Temperature InfraRed Thermometer with Laser Pointer

High Temperature InfraRed Thermometer with Laser Pointer User s Manual High Temperature InfraRed Thermometer with Laser Pointer MODEL 42540A 6 42540 6 Introduction Congratulations on your purchase of the Model 42540A IR Thermometer. The 42540A is capable of

More information

AUTODIALLER / QUICKDIALLER - SA132

AUTODIALLER / QUICKDIALLER - SA132 AUTODIALLER / QUICKDIALLER - SA132 INSTRUCTION LEAFLET ENGLISH www.thermomax-group.com CONTENTS 1 SETUP AT A GLANCE... 2 2 FOREWORD....... 3 3 INSTALLATION...... 4 4 KEYPAD AND INDICATORS...... 5 SETTING

More information

LST-3800. In-Dash Digital Sonar Gauge. Installation & Operation Instructions

LST-3800. In-Dash Digital Sonar Gauge. Installation & Operation Instructions Pub. 988-0064-351 LST-3800 In-Dash Digital Sonar Gauge Installation & Operation Instructions The LST-3800 is a depth and temperature gauge that comes with a 200 khz transducer, features deep and shallow

More information

User's Manual. Heavy Duty Dissolved Oxygen Meter Model 407510

User's Manual. Heavy Duty Dissolved Oxygen Meter Model 407510 User's Manual Heavy Duty Dissolved Oxygen Meter Model 407510 Introduction Congratulations on your purchase of Extech's Heavy Duty Dissolved Oxygen / Temperature Meter which simultaneously displays Dissolved

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS LIGHTING CONTROL PANELS 4 AND 8 RELAYS INSTALLATION INSTRUCTIONS INSTALLATION OVERVIEW The installation instructions contained in this document are provided as a guide for proper and reliable installation.

More information

i410/i1010 AC/DC Current Clamp

i410/i1010 AC/DC Current Clamp /i1010 AC/DC Current Clamp Instruction Sheet Safety Information XW Read First: Safety Information To ensure safe operation and service of the current clamp, follow these instructions: Read all operating

More information

User and Installation Guide

User and Installation Guide Connect the AC adapter with the amplifier BEFORE plugging the AC adapter into an outlet to avoid spark generation! User and Installation Guide BlueFIDELITYTM Bluetooth Audio Amplifier Model 300 Contents

More information

Auto Dialer. Manual E-921APQ E-921GPQ

Auto Dialer. Manual E-921APQ E-921GPQ Troubleshooting: Auto dialer will not arm/disarm Auto dialer will not dial out Unit doesn t respond to a call-back Difficulty in activating room monitor by telephone remote control Make sure that you have

More information

EPM3. Phase Sequence and Motor Rotation Tester. Users Manual

EPM3. Phase Sequence and Motor Rotation Tester. Users Manual EPM3 Phase Sequence and Motor Rotation Tester Users Manual 1 L1 L2 L3 2 3 A B C CAT 600V 3-PHASE TESTER 5 TEST M1 M2 BATT M3 EPM3 MOTOR ROTATION TESTER EPM3 MOTOR ROTATION DETERMINED WHILE FACING MOTOR

More information

Unattended Answering Device Instruction Manual

Unattended Answering Device Instruction Manual Model 3137B Unattended Answering Device Instruction Manual Monroe Electronics 100 Housel Ave Lyndonville NY 14098 800-821-6001 585-765-2254 fax: 585-765-9330 monroe-electronics.com Printed in USA Copyright

More information

ESL 500N Series. Smoke Detector Installation Instructions L LISTED

ESL 500N Series. Smoke Detector Installation Instructions L LISTED ESL 500N Series Smoke Installation Instructions ESL 500N Series This document is intended for licensed electricians/ alarm installers. GE Interlogix cannot provide technical support to unqualified persons.

More information

Manual for Fire Suppression & Methane Detection System

Manual for Fire Suppression & Methane Detection System Manual for Fire Suppression & Methane Detection System Fogmaker North America Post address: 150 Gordon Dr Exton, PA 19341 Delivery address: 150 Gordon Dr Exton, PA 19341 Tel: 610-265-3610 Fax: 610-265-8327

More information

2-3 SAS/SATA II HDD Canister USER S MANUAL XC-23D1-SA10-0-R. Document number: MAN-00076-A

2-3 SAS/SATA II HDD Canister USER S MANUAL XC-23D1-SA10-0-R. Document number: MAN-00076-A 2-3 SAS/SATA II HDD Canister XC-23D1-SA10-0-R USER S MANUAL Document number: MAN-00076-A ii Preface Important Information Warranty Our product is warranted against defects in materials and workmanship

More information

Ceiling Mount Air Handler Manual

Ceiling Mount Air Handler Manual www.surna.com 303.993.5271 Ceiling Mount Air Handler Manual Models: CMAH12, CMAH18, CMAH24, CMAH30, CMAH36, CMAH48, CMAH60 Revised: September 2014 Table of Contents Warranty Information 4 Limited Warranty

More information

Wireless Home Security Alarm System AM 500

Wireless Home Security Alarm System AM 500 Wireless Home Security Alarm System AM 500 12 MONTH GUARANTEE Installation & Operating Instructions INTRODUCTION The AM500 is a simple self-contained alarm system. It protects the home by sounding a siren

More information

EE-SX91. Meeting Customer Needs with Compact Sensors that Mount with M3 Screws

EE-SX91. Meeting Customer Needs with Compact Sensors that Mount with M3 Screws Compact Pre-wired Photomicrosensor with Built-in Amplifier (Non-modulated) CSM DS_E_7_2 Meeting Customer Needs with Compact Sensors that Mount with M Screws Both light-on and dark-on outputs provided.

More information

Owner's Manual [ S/N LABEL HERE ] Document # BW-BCU5DOC

Owner's Manual [ S/N LABEL HERE ] Document # BW-BCU5DOC Owner's Manual [ S/N LABEL HERE ] Document # BW-BCU5DOC BAYweb Remote Model BW-BCU5 Owner's Manual Copyright 2009-2010 Bay Controls, LLC Part Number: BW-BCU5DOC Revision: 0.2 April 18, 2010 BAYweb is a

More information