Operational Procedure: Underground Cable Testing: High and Low Voltage

Size: px
Start display at page:

Download "Operational Procedure: Underground Cable Testing: High and Low Voltage"

Transcription

1 Operational Procedure: Underground Cable Testing: High and Low Voltage 30 June 2011 Change picture according to document 30 June 2011 ISSUE 5

2 PREPARED BY: Underground Construction and Design Manager AUTHORISED BY: Group Manager Standards and Demand Management DOCUMENT NUMBER: ISSUE 5 This plan is copyright. No part may be reproduced by any process without written permission, except as permitted under the copyright act. DISCLAIMER 1 Essential Energy may change the information in this document without notice. All changes take effect on the date made by Essential Energy. A print version is always an uncontrolled copy. Before using this document, please ensure that it is still current. 2 This document may contain confidential information. Restrictions on the use and disclosure of confidential information by employees are set out in your contract of employment. Restrictions on the use and disclosure of confidential information by contractors are set out in your contract of engagement with Essential Energy. Sub-contractors are bound by the confidentiality provisions set out in their contract with the contractor engaged by Essential Energy ESSE N T I A L E N E R G Y Page 2 of 10

3 CONTENTS PAGE 1 INTRODUCTION TOOLS AND EQUIPMENT TRAINING Training, Assessment and Authorisation PRELIMINARY CHECKS Visual Check Notification Worksite Hazard Identification, Risk Assessment and Control (worksite HIRAC) METHOD High Voltage Cable Tests Insulated Resistance Test Level High Voltage Test Level 2 (Paper Lead Cables Only) Delayed Connection to Network Low Voltage Cable Test Continuity Test Serving Insulation Resistance Test Insulation Resistance Test Method Streetlighting Cable Tests Polarity Test Failure to Comply RECORDS KEY TERMS AND DEFINITIONS REFERENCES REVISIONS Page 3 of 10

4 1 INTRODUCTION This document proves the high and low voltage cable integrity after installation or jointing work is completed and before connection or reconnection to the Essential Energy s Network. Such testing and commissioning will be undertaken by people, who are both qualified and authorised, and the relevant test results will be duly entered into the relevant test report form (refer to CEOF6022 and CEOF6023). This document is intended for use by Essential Energy s Accredited Service Providers and internal staff for testing of cables before being energised. 2 TOOLS AND EQUIPMENT Danger HV Test Signs Insulating Gloves Insulated Ground Matting Suitable HV Test Equipment 1000V DC Megger 500V DC Megger Low Voltage Tester Foster Test Set (For paper cable only) 3 TRAINING 3.1 Training, Assessment and Authorisation Where there is exposure to risk from electrical apparatus a person undertaking work will be appropriately qualified, trained and assessed as competent and authorised to carry out the work. 4 PRELIMINARY CHECKS 4.1 Visual Check A visual check is carried out by the Authorised Person to ensure that the workmanship of both the installation of the cable and cable jointing work meets Essential Energy s requirements before being connected to the Network. 4.2 Notification The Quality Control Coordinator will be notified 3 working days prior to the commencement of the cable tests. The Accredited Service Provider will be responsible for ensuring that the completed work is tested and test reports are forwarded to the Quality Control Coordinator promptly. The Quality Control Coordinator may be present to witness the testing procedure. 4.3 Worksite Hazard Identification, Risk Assessment and Control (worksite HIRAC) Tests on underground cables are potentially hazardous to both personnel undertaking the test and the general public in the vicinity. A Worksite HIRAC will be carried out, by the Authorised Person, which will determine the precautions that need to be adopted. For public areas warning signs may need to be displayed and barricades erected around the test area (including all exposed cable terminations) prior to commencing any testing activity. Page 4 of 10

5 For HV and LV cable Insulation Resistance tests, a Test Access Permit is not mandatory if the Insulation Resistance test is performed at a 1000 volts DC or less and the cable is discharged to earth for a time duration equal to the test time. If an Access Permit for Testing is deemed necessary after a HIRAC evaluation it will be completed and issued in accordance with CEOP2045 Access Permits. If currently on a Work Access Permit, remove earths and cancel the Access Permit If the cable has previously been commissioned and connected to Essential Energy s System call System Operations and inform them if you require a Test Access Permit to test a high voltage cable, and at all times give full details of location, open points etc Insulating gloves and ground matting to be utilised. 5 METHOD 5.1 High Voltage Cable Tests Authorised Persons will complete the prescribed tests as specified. All cables must be fully discharged for a time duration equal to the test time upon completion of each test by means of discharge function on test equipment or an independent earth. Test results will be recorded on the HV Underground Cable Test Report form, refer to CEOF Insulated Resistance Test Level 1 Screen to Earth Test for XLPE insulated cables will record an insulation resistance as per table below at 500V after one (1) minute. This test will be performed first so as to assist in the reconnection process of the screen to earth connection Phase to Screen/Earth, and Phase to Phase testing requires the Authorised Person to measure insulation resistance at 1.kV after one (1) minute duration. Minimum IR as per table below. Insulation Resistance (IR) Values for HV Cables Cable Rated Voltage kv Minimum 1kV DC New Cables Ph-Ph, Ph-E Minimum Screen E New Cables Minimum 1kV DC Existing Cables Ph-Ph, Ph-E Minimum 500V Screen E Existing Cables 11kV 400 megohms 100 megohm 100 megohms 1.0 megohm 22kV 400 megohms 100 megohm 100 megohms 1.0 megohm 33kV 800 megohms 100 megohm 200 megohms 1.0 megohm 66kV 800 megohms 100 megohm 200 megohms 1.0 megohm 132kV 800 megohms 100 megohm 200 megohms 1.0 megohm Note: Insulation Resistance Tests will be applied for a period of 1 minute for cables less than 100 m in length and 3 minutes for cables greater than 100 m in length. Page 5 of 10

6 5.3 High Voltage Test Level 2 (Paper Lead Cables Only) If the insulation resistance results for Paper Lead (PLY) cables are below the prescribed minimum values, a high voltage DC test will be applied. See CEOF6022 HV Underground cable Test Report for the prescribed minimum values. If prescribed minimum values are required for higher voltage Paper Lead (PLY) cables, contact Quality Control Coordinator. It is performed by applying a DC voltage between phases and between phases and sheath. When making these tests, the voltage will be increased gradually to the full specified value and be maintained for 15 minutes. After 15 minutes, the leakage current should be steady or falling and less then 0.1mA with no transient spikes occurring. Higher readings may be acceptable provided they are steady. For further advice, contact Quality Control Coordinator Commissioning new cables a cable not previously energised will be tested by applying: 11kV cable 34kV DC between phases; and 25kV DC between phases and sheaths 22kV cable 68 kv DC between phases; and 50 kv DC between phases and sheath The 3 phases can be bonded for the phase to sheath test and only 1 test made unless a failure occurs. If a failure occurs, each phase will be tested individually to determine the faulty phase. Recommissioning Existing Cables where a cable that has been in service, is to be tested prior to recommissioning, it will be tested at approximately 75% of the voltages for a new cable, i.e. 11kV cable 26kV DC between phases; and 15kV DC between phases and sheath 22kV cable 52kV DC between phases; and 30kV DC between phases and sheath The phases can be bonded for the phase to sheath test, and only one test made unless a failure occurs. 5.4 Delayed Connection to Network Insulation Integrity Test If a cable is to be connected to the Network and the testing has occurred within 4 weeks preceding this, a visual inspection of the cable location will be undertaken, for any obvious signs that cable insulation integrity may have been compromised. After 4 weeks has elapsed the standard test must be repeated before connection is carried out. This time frame also applies to cables which have been removed from service for repair or have been decommissioned. If live line techniques are to be utilised for cable connection a documented cable test must be carried out (CEOF6022 HV Underground Cable Test Report) to determine the insulation integrity of the cable prior to carrying out live line technique. Page 6 of 10

7 If an Insulation Integrity test is to be undertaken the live line gang must inform System Operations of the insulation integrity test before the live line work is carried out. Once the integrity of the insulation is proven, inform System Operations of the result (if the cable fails the test, commissioning of the cable will not proceed any further and Quality Control Coordinator will be contacted for further advice). Live Line work will be carried out as per switching sheet. The Standard Tests, Phase to Phase and Phase to earth: Measure insulation resistance at 1kV after one (1) minute. Acceptable values for existing cables may be used as cable will now be connected to switchgear etc. A Phase to B Phase B Phase to C Phase C Phase to A Phase A Phase to Screen and Earth B Phase to Screen and Earth C Phase to Screen and Earth Greater than 100 megohms Greater than 100 megohms Greater than 100 megohms Greater than 100 megohms Greater than 100 megohms Greater than 100 megohms. All cables must be fully discharged for a time duration equal to the test time upon completion of each test by means of discharge function on test equipment or an independent earth. The purpose of this test is to prove that the integrity of the insulation has not been damaged since the original test date. The energising/de-energising of an underground cable which is to be directly connected to the overhead system and is isolated from the transformer must only be undertaken using a temporary EDO (cut-out tool) fitted with a 25 amp K class fuse element. 5.5 Low Voltage Cable Test Authorised Persons will complete the prescribed tests as specified. All cables must be fully discharged for a time, duration equal to the test time upon completion of each test by means of the discharge function on test equipment or an independent earth. Test results will be recorded on CEOF6023 LV Underground Cable Test Report form. 5.6 Continuity Test 1 The continuity test (DC resistance measurement) will be carried out on each low voltage circuit from the end of each branch or open point, to the origin of the circuit. Step 1 At the circuit origin, to be tested, (normally at the Padmount transformer), connect each of the phase conductors to the neutral of the cable circuit in turn, ensuring all MEN points are disconnected. Step 2 At the remote ends of the circuit, check for continuity between each phase and neutral. Results very close to a short circuit value should be obtained. Step 3 At the circuit origin (normally at the Padmount transformer) connect the phase conductors together, remaining separate from neutral conductor. Alternatively, if cable is to be energised immediately after testing, neutral polarity may be tested by lamping out conductors at each pit or pillar. Page 7 of 10

8 Step 4 Proceed to each pit or pillar on the circuit and check neutral polarity with 500V megger. If any reading other than an open circuit is recorded between the connected phases and neutral, it will mean a phase has been connected to the neutral which will be located, rectified and retested before connection to Essential Energy s Distribution System. 5.7 Serving Insulation Resistance Test 2 The integrity of the covering sheath will be proved by bonding the 4 cores and applying 500V DC for 1 minute between the bonded cores and earth. The minimum insulation resistance will be 200 Megohms for new cables and 20 Megohms for cables older than 1 year. If the cables fail this test, the point of failure will be located, rectified and retested before connection to Essential Energy s Distribution System. 5.8 Insulation Resistance Test 3 Ensuring all cores are separated from each other and using a 500V instrument measure the insulation resistance between 2 cores in rotation, i.e.: N-R, R-W, N-W, R-B, N-B, B-W. The minimum insulation resistance will be 200 Megohms for new cables and 20 Megohms for cables older than 1 year. If a cable fails to achieve the required minimum values, contact Quality Control Coordinator or the Principal s Superintendent for further advice. Ensure all MEN points have been reconnected. 5.9 Method Streetlighting Cable Tests Polarity Test CHECK all connections in the service pit/pillar and ensure they are correct ENSURE primary fuse is removed or circuit breaker is switched off, incoming neutral isolated, earths disconnected, PE cell and tubes/globes removed CONFIRM visually the colour coding of internal wiring at terminal block is correct. Ensure terminal block is not earthed at light fitting USING 500V megger measure insulation resistance between internal wiring and standard (reading to exceed 1 megohm), test for short circuits and reconnect earth if applicable TEST and identify streetlight active and neutral. Connect service neutral to streetlight neutral first, then service active to streetlight active CHECK all connections in the street light column and ensure they are correct INSERT PE cell, tube/globe, fuse or circuit breaker. Ensure streetlight operates CONDUCT final test with streetlight on measuring between an independent earth and neutral and earth or metal work for any voltage. Page 8 of 10

9 5.10 Failure to Comply If a cable or associated equipment fail a prescribed test, the Accredited Service Provider will be responsible for the location of the fault, repair or replacement of faulty cable and/or accessories, and any subsequent testing, as directed by Quality Control Coordinator. Prior to the application of any fault location methods which have the potential to affect the long-term insulation integrity of the installation, the Authorised Service Provider will submit to Essential Energy a proposed fault location methodology. No fault location work will proceed until Essential Energy s Quality Control Coordinator has given approval. 6 RECORDS The relevant test results will be duly entered on the relevant Test Report form, (See CEOF6022 and CEOF6023.) The Cable Test Report will be sighted by the person carrying out the commissioning who completes the clearance certification by signing, therefore accepting the new asset. The person carrying out the commissioning will quote the Cable Test Report No. to System Operations when requesting energisation of new asset. This will be System Operations record of compliance until paper copy is received. The Quality Control Coordinator is also responsible for correct distribution of Cable Test Report copies. 1 Quality Control Coordinator WHITE 2 Project File BLUE 3 System Operations YELLOW 4 Book copy PINK. 7 KEY TERMS AND DEFINITIONS Accredited Service Provider: refers to companies/sole traders who have gained accreditation through the Department of Fair Trading allowing them to perform contestable works. Authorised Person: means a person with technical knowledge or sufficient experience who has demonstrated competency and has been approved by Essential Energy to carry out specific duties with the supply or use of electricity. Contestable Works: those works where the customer has a choice of Service Provider. Continuity test: test to ensure correct cable core identity and continuity. Essential Energy s Network: Essential Energy Transmission and Distribution System Assets. Insulation Resistance: quantified measurement of insulation value. Polarity test: test to ascertain correct identification and connection of active and neutral conductors. Principal s Superintendent: Project Manager of the Accredited Service Provider. Quality Control Coordinator: is the person nominated by Essential Energy with the responsibility for auditing construction works to Essential Energy s standards and quality. System Operations: Essential Energy 24 hour Operational Control Centre. Page 9 of 10

10 8 REFERENCES CEOF6022 HV Underground Cable Test Report CEOF6023 LV Underground Cable Test Report CEOP2018 Polarity and Neutral Identification Testing CEOP2045 Access Permits CEOP8029 Network Management Plan CEOP8030 Electrical Safety Rules Olex Cables Technical Informative PT-I th May 2001 Electricity Supply (Safety and Network Management) Regulation REVISIONS Revision Number Section 2 All Sections 3 4 All Sections Clause Definitions Clause 5.6 Clause 6 Details of Changes in this Revision Reduction in Meggering voltages to align with Manufacturer s recommendations. Document changed to Plain English Second paragraph was.if live line techniques are to be utilised for cable connection it maybe prudent to undertake an insulation integrity test regardless of the elapsed time period. Accredited Service Provider was. refers to companies/sole traders who have gained accreditation through NSW Ministry of Energy and Utilities allowing them to perform contestable works. Step 1, Sentence 1 added,.. connect each of the phase conductors to the neutral of the cable circuit in turn Step 2 was Each phase and neutral, and Each phase Second paragraph was. The Cable Test Report will be signed by the Quality Control Coordinator.. Third paragraph, first sentence was.. The Quality Coordinator 5 All Update to rebrand to Essential Energy Page 10 of 10

CHECKING AND TESTING ELECTRICAL INSTALLING WORK

CHECKING AND TESTING ELECTRICAL INSTALLING WORK CHECKING AND TESTING ELECTRICAL INSTALLING WORK Department of Consumer and Employment Protection Energy Safety Preface It is a requirement of the Electricity (Licensing) Regulations 1991 that all electrical

More information

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV 1. SCOPE This document details PowerSystems requirements for electrical testing of HV Equipment up to and including 33kV. 2. ISSUE RECORD This is a Reference document. The current version of Controlled

More information

Circuit Electrical Testing

Circuit Electrical Testing Safe Isolation Procedure Circuit Electrical Testing Site Safety Management It is essential from the outset that effective management and control of the system, apparatus and equipment used on site is achieved

More information

High Voltage (HV) Electricity System Safety Rules and Associated Safety Guidance

High Voltage (HV) Electricity System Safety Rules and Associated Safety Guidance Annex I To Loughborough University (LU) Facilities Management (FM) Health and Safety Policy High Voltage (HV) Electricity System Safety Rules and Associated Safety Guidance 1. Introduction a. These Safety

More information

Regulation IO-6.0: Electrical Safety Regulations

Regulation IO-6.0: Electrical Safety Regulations Regulation IO-6.0: Electrical Safety Regulations 6.1 Workmanship & Material 6.2 Electrical Conductors 6.3 Overcurrent Protective Devices 6.4 Precautions against Earth Leakage and Earthfault Currents 6.5

More information

EARTHING AND BONDING AT SECONDARY SUBSTATIONS

EARTHING AND BONDING AT SECONDARY SUBSTATIONS DISTRIBUTION CONSTRUCTION MANUAL SECTION 4 - SUBSTATIONS ISSUE B SEPT 1996 4.4.4 EARTHING AND BONDING AT SECONDARY SUBSTATIONS 1 SCOPE This section of the Distribution Construction Manual lays down the

More information

Electrical safety rules

Electrical safety rules Electrical safety rules 2015 DISCLAIMER The material contained in this publication has been developed for the use of ActewAGL, its contractors and all others working on or near ActewAGL s electricity

More information

COMMISSIONING TESTS FOR HV UNDERGROUND CABLES (UP TO 33KV) SWP

COMMISSIONING TESTS FOR HV UNDERGROUND CABLES (UP TO 33KV) SWP 1. PURPOSE AND SCOPE The purpose of this Standard Work Practice (SWP) is to standardise and prescribe the method for pre commissioning and commissioning tests on high voltage underground cables. Where

More information

The Electrical Safety Regulation (pre and post 1 January 2014)

The Electrical Safety Regulation (pre and post 1 January 2014) The Electrical Safety Regulation (pre and post 1 January 2014) The following table provides an overview comparison between the Electrical Safety Regulation 2002 (the ESR 2002) current as at 1 July 2013

More information

Trouble-shoot and repair faults in low voltage electrical apparatus and circuits

Trouble-shoot and repair faults in low voltage electrical apparatus and circuits UEENEEG108A Trouble-shoot and repair faults in low voltage electrical apparatus and circuits AS3000:2007 & AS3017:2007 Summary MANUFACTURING AND ENGINEERING DIVISI M & E UEENEEG108A TESTING Before any

More information

Electrical Practices for Construction Work

Electrical Practices for Construction Work 1. Purpose Electrical Practices for Construction Work The purpose of this Code is to provide practical guidance and set minimum safety requirements for electrical practices on all construction sites in

More information

Operational Control of the UKPN Low Voltage Distribution Network for EPN and LPN Regions

Operational Control of the UKPN Low Voltage Distribution Network for EPN and LPN Regions Operational Control of the UKPN Low Voltage Distribution Network for EPN and LPN Regions Owner Name Title Signature Steve White Head of Network Control and Operations Date 16 February 2016 Authoriser Name

More information

Customer Installation Safety Plan. March 2015

Customer Installation Safety Plan. March 2015 Customer Installation Safety Plan March 2015 Document History Issue No. Date Approved By Summary of Changes 1 June 2014 Chief Engineer Updated and revised in line with requirement for biennial review under

More information

WORKING IN THE ELECTRIFIED AREA

WORKING IN THE ELECTRIFIED AREA Network Safety Management System SPECIFICATION SAF/SPC/5178/ELE/NET WORKING IN THE ELECTRIFIED AREA Version 1.0 Effective Date: 12 October 2014 AURIZON COMMERCIAL-IN-CONFIDENCE SAF/SPC/5178/ELE/NET Working

More information

Code of Practice Electricity transmission and distribution asset management. February 2009

Code of Practice Electricity transmission and distribution asset management. February 2009 Code of Practice Electricity transmission and distribution asset management February 2009 CONTENTS 1 PREFACE...4 2 APPLICATION AND OBJECTIVES...5 3 SCOPE...6 4 DEFINITIONS...7 5 DESIGN AND CONSTRUCTION...11

More information

DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations)

DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations) DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations) DETAILS OF THE CLEINT Client and address ADDRESS OF THE INSTALLATION Installation

More information

Contractor Connect Scheme Electrical Contractor and Worker Handbook

Contractor Connect Scheme Electrical Contractor and Worker Handbook Contractor Connect Scheme Electrical Contractor and Worker Handbook January 2016 Document release information Document number 13553681 Document title Revision status Contractor Connect Scheme handbook

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to

More information

CAPACITOR BANK TESTING SWP

CAPACITOR BANK TESTING SWP 1. PURPOSE AND SCOPE The purpose of this Standard Work Practice (SWP) is to standardise and prescribe the method for testing Capacitor Banks including capacitors, tuning reactors and inrush limiting reactors.

More information

ES 4 Service Provider Authorisation

ES 4 Service Provider Authorisation ES 4 Service Provider Authorisation June 2015 WARNING It is the responsibility of the user of this document to ensure that only the current version is being used. Ausgrid may amend this document at any

More information

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Title MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Duration 5 days Training Date MV, HV and EHV Switchgear Testing & Commissioning 5 20 24 Apr $3,750 Dubai, UAE In any of the 5 star

More information

EP 95 00 30 03 SP RAILCORP NETWORK MANAGEMENT PLAN CHAPTER 2 - CUSTOMER INSTALLATION SAFETY. Authorised by: Neal Hook Chief Engineer Electrical

EP 95 00 30 03 SP RAILCORP NETWORK MANAGEMENT PLAN CHAPTER 2 - CUSTOMER INSTALLATION SAFETY. Authorised by: Neal Hook Chief Engineer Electrical Engineering Standard Electrical RAILCORP NETWORK MANAGEMENT PLAN CHAPTER 2 - CUSTOMER INSTALLATION SAFETY Owner: Approved by: Chief Engineer, Electrical Neal Hook Chief Engineer Electrical Authorised by:

More information

GUIDE TO THE MAINTENANCE, INSPECTION AND TESTING OF PORTABLE EQUIPMENT (ELECTRICAL APPLIANCES AND TOOLS) IN THE WORKPLACE

GUIDE TO THE MAINTENANCE, INSPECTION AND TESTING OF PORTABLE EQUIPMENT (ELECTRICAL APPLIANCES AND TOOLS) IN THE WORKPLACE GUIDE TO THE MAINTENANCE, INSPECTION AND TESTING OF PORTABLE EQUIPMENT (ELECTRICAL APPLIANCES AND TOOLS) IN THE WORKPLACE ET 215:2008 ELECTRO-TECHNICAL COUNCIL OF IRELAND 2008 Page 1 of 6 Published by

More information

Electrical safety code of practice 2013. Managing electrical risks in the workplace

Electrical safety code of practice 2013. Managing electrical risks in the workplace Electrical safety code of practice 2013 Managing electrical risks in the workplace This Queensland code of practice has been approved by the Attorney-General and Minister for Justice and commences on 1

More information

Heading FACT SHEET. Overview. www.safeworkaustralia.gov.au

Heading FACT SHEET. Overview. www.safeworkaustralia.gov.au ELECTRICAL RISKS AT THE WORKPLACE Heading FACT SHEET Overview This fact sheet provides general guidance for persons conducting a business or undertaking (PCBUs) and workers on managing electrical risks

More information

A Practical Guide to Dielectric Testing

A Practical Guide to Dielectric Testing Chroma Systems Solutions, Inc. A Practical Guide to Dielectric Testing 19032 Series Electrical Safety Analyzer & 19050 Series Hipot Tester AC/DC/IR/SCAN Keywords: Dielectric tests, insulation resistance

More information

1 General Responsibility. 1.1 Participants. 1.2 Documentation. 1.3 Lockout/Tagout

1 General Responsibility. 1.1 Participants. 1.2 Documentation. 1.3 Lockout/Tagout Electrical Safety Plan This plan establishes rules for both the design and operation of the LPRDS. These rules are intended to enhance the safety of the participants in the initial project and future users

More information

Electrical Safety Policy

Electrical Safety Policy Electrical Safety Policy Version Number: V2 Name of originator/author: Director of Estates and Facilities Name of responsible committee: Estates and Facilities Committee Name of executive lead: Chief Operating

More information

CONNECTING YOU TO SPECIALIST ELECTRICAL SUPPORT services

CONNECTING YOU TO SPECIALIST ELECTRICAL SUPPORT services CONNECTING YOU TO SPECIALIST ELECTRICAL SUPPORT services SpecialistS IN ELECTRICAL SUPPORT SERVICES TO MINING, UTILITIES & industry Ampcontrol is committed to supporting our customers to maintain efficient

More information

RMM 306 Lockout/Tagout (LOTO) Program for the Control of Hazardous Energy Page 2 June 2016

RMM 306 Lockout/Tagout (LOTO) Program for the Control of Hazardous Energy Page 2 June 2016 RMM 306 Lockout/Tagout (LOTO) Program for the Control of Hazardous Energy Page 2 3 Related Documents 3.1 Occupational Health and Safety Act, R.S.O. 1990 3.2 Regulations for Industrial Establishments, R.R.O.

More information

Earthing Guidance Notes

Earthing Guidance Notes Central Networks Earthing Manual Section E2 Earthing Guidance Notes Version: 2 Date of Issue: September 2007 Author: Nigel Johnson Job Title: Earthing Specialist Approver: John Simpson Job Title: Head

More information

This Guideline does not address electrical equipment in the following categories:

This Guideline does not address electrical equipment in the following categories: Policy Hierarchy link Responsible Officer Contact Officer Superseded Documents HS418 Portable Electrical Equipment Inspection, Testing and Tagging Guideline Work Health and Safety Act 2011 Work Health

More information

Replacement of 600-Ampere Bushing and 200-Ampere Bushing-Well Adapters

Replacement of 600-Ampere Bushing and 200-Ampere Bushing-Well Adapters S&C Vista SD Underground Distribution Switchgear Pad-Mounted and Vault-Mounted Style Outdoor Distribution (17.5 kv and 29 kv) With Visi-Gap Load Interrupter Switches and Visi-Gap Fault Inetrrupters Replacement

More information

D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify.

D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify. SECTION 263354 STATIC UPS TESTING AND COMMISSIONING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes 1. System start-up services. 2. Battery charging. 3. Load bank testing. 4. Battery load testing. 5.

More information

Work in Substations - General

Work in Substations - General Work in Substations - General Summary: This document supports the Power System Safety Rules and its requirements assembled under Work in Substations General Category 3 and apply to all persons working

More information

Guide to the electrical parameter classifications of IEC 60950 and IEC 62368 safety standards

Guide to the electrical parameter classifications of IEC 60950 and IEC 62368 safety standards Guide to the electrical parameter classifications of IEC 60950 and IEC 62368 safety standards Abstract This Guide is an informative listing of selected terms and definitions found in IEC Glossary entry

More information

ELECTRICAL PRACTICES FOR CONSTRUCTION WORK

ELECTRICAL PRACTICES FOR CONSTRUCTION WORK CONTRACTOR S CHECKLIST ELECTRICAL PRACTICES FOR CONSTRUCTION WORK 2007 WorkCover. Watching out for you. New South Wales Government Disclaimer This publication contains information regarding occupational

More information

11. Assessment of service 12. S-phase supply 13. Water heaters NORTHERN TERRITORY OF AUSTRALIA ELECTRICITY BY-LAWS T ABLE OF PROVISIONS

11. Assessment of service 12. S-phase supply 13. Water heaters NORTHERN TERRITORY OF AUSTRALIA ELECTRICITY BY-LAWS T ABLE OF PROVISIONS NORTHERN TERRITORY OF AUSTRALIA ELECTRICITY BY-LAWS T ABLE OF PROVISIONS By-law PART I - PRELIMINARY 1. Citation 2. Repeal 3. Interpretation 4. Qualifications of inspector PART II - INSPECTORS PART III

More information

DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS

DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS MIOSHA-STD-1313 (10/15) 6 Pages For further information Ph: 517-284-7740 www.michigan.gov/mioshastandards DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS

More information

ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants. Installation instructions ESP M1/M1R mains protectors

ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants. Installation instructions ESP M1/M1R mains protectors ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants Installation instructions Contents Key points of installation Before installation Installation Installation check

More information

Fault location on power cables. Fault location on power cables

Fault location on power cables. Fault location on power cables Fault location on power cables Fault location on power cables Contents: 1. Introduction 2. Construction of power cables 3. Cable faults 01. Introduction Fault location on communication and power cables

More information

ACCREDITATION OF PROVIDERS LEVEL 1 CLASS: OF CONTESTABLE SERVICES. Clause 26 Electricity Supply (Safety and Network Management) Regulation 2014

ACCREDITATION OF PROVIDERS LEVEL 1 CLASS: OF CONTESTABLE SERVICES. Clause 26 Electricity Supply (Safety and Network Management) Regulation 2014 ACCREDITATION OF PROVIDERS OF CONTESTABLE SERVICES CLASS: LEVEL 1 Clause 26 Electricity Supply (Safety and Network Management) Regulation 2014 March 2015 CONTENTS PART 1 1 Introduction 3 2 General Information

More information

TECHNICAL SPECIFICATIONS & SPECIAL CONDITIONS OF CONTRACT FOR ELECTRICAL WORKS CHAPTER 1 SPECIAL CONDITIONS OF CONTRACT

TECHNICAL SPECIFICATIONS & SPECIAL CONDITIONS OF CONTRACT FOR ELECTRICAL WORKS CHAPTER 1 SPECIAL CONDITIONS OF CONTRACT TECHNICAL SPECIFICATIONS & SPECIAL CONDITIONS OF CONTRACT FOR ELECTRICAL WORKS CHAPTER 1 SPECIAL CONDITIONS OF CONTRACT 1.1 General 1.1.1 These Special Conditions of Contract supplement the General Instructions.

More information

Hyperlinks are Inactive

Hyperlinks are Inactive Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)

More information

Connecting to the network information pack Version 2

Connecting to the network information pack Version 2 Connecting to the network information pack Version 2 Updated: Contents 1.0 What is a new connection or connection alteration?... 3 2.0 Connection enquiry... 3 3.0 Connection application... 3 3.1 Processing

More information

Article 10 - ADMINISTRATIVE SECTION

Article 10 - ADMINISTRATIVE SECTION Article 10 - ADMINISTRATIVE SECTION 10.1 TITLE These Administrative Regulations along with the requirements included in the 2011 Edition of the National Electrical Code (NFiPA-70-2011) as adopted by the

More information

DESCRIPTION DWG DESCRIPTION DWG

DESCRIPTION DWG DESCRIPTION DWG DESCRIPTION DWG DESCRIPTION DWG Ferroresonance 3451/1 3451/2 3451/3 Electro-magnetic Fields (EMF) 3462/1 HV & LV Insulators (Links) 3463/1 A ORIGINAL ISSUE B 14.07.09 APPROVED DATE J. Brooks 25.02.03 INDEX

More information

Application of Electrical Installation Licence

Application of Electrical Installation Licence Handbook for Application of Electrical Installation Licence TABLE OF CONTENTS 1. INTRODUCTION 1 2. OBJECTIVE OF ELECTRICAL INSTALLATION LICENSING REGIME 2 3. WHAT IS AN ELECTRICAL INSTALLATION? 3 4. CLASSES

More information

SECTION 16999 ELECTRICAL ACCEPTANCE TESTS

SECTION 16999 ELECTRICAL ACCEPTANCE TESTS SECTION 16999 ELECTRICAL ACCEPTANCE TESTS PART 1 2. AND 3. COMBINED 1.1 SUMMARY A. Description of Systems 1. Furnish all labor, materials, test equipment, and technical supervision to perform and record

More information

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting 12 SOLAR PHOTOVOLTAIC POWER by John Ware IT IS PLANNED for BS 7671:2008 to include a new Section 712 providing additional requirements for safety applicable to solar photovoltaic (pv) power supply systems.

More information

Model 1756 Test Lead Kit

Model 1756 Test Lead Kit Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-888-KEITHLEY http://www.keithley.com Model 1756 Test Lead Kit Gerneral Purpose Test Lead Information Description These test leads allow you

More information

chapter8 Testing and commissioning Unit 2 outcome 2

chapter8 Testing and commissioning Unit 2 outcome 2 Testing and commissioning chapter8 Unit 2 outcome 2 It is important that electricians are not just able to construct; they should also be able to recognise faults and take action to help prevent them.

More information

Trial Exams C. Standards and Regulations. Examination No: GH-08-C- 1 hour and 5 minutes plus 10 minutes reading time

Trial Exams C. Standards and Regulations. Examination No: GH-08-C- 1 hour and 5 minutes plus 10 minutes reading time Trial Exams C Standards and Regulations Examination No: GH-08-C- This test is intended to gauge your knowledge of essential information contained within AS/CA S009:2013. To qualify for an allpication to

More information

CoDe of PRACtICe on electrical safety for work on or near high voltage electrical apparatus. the blue book

CoDe of PRACtICe on electrical safety for work on or near high voltage electrical apparatus. the blue book CoDe of PRACtICe on electrical safety for work on or near high voltage electrical apparatus the blue book VICtoRIA 2012 ISSUE SHEET Copy Number... CONTROLLED COPY UNCONTROLLED COPY Note: Uncontrolled copies

More information

Best Methods for Safe Hipot Testing

Best Methods for Safe Hipot Testing Best Methods for Safe Hipot Testing When working with electrical safety test equipment, instruments that output potentially dangerous voltages and currents, it is always important to regular review and

More information

METERING CODE. Energy Market Authority of Singapore

METERING CODE. Energy Market Authority of Singapore METERING CODE Energy Market Authority of Singapore TABLE OF CONTENTS 1 GENERAL AND ADMINISTRATIVE PROVISIONS...1 1.1 Purpose of this Code...1 1.2 To Whom this Code Applies...1 1.3 Prohibition...1 1.4 Definitions...1

More information

NZECP 14: 1995 ISSN 0114-0663 COVER PAGE

NZECP 14: 1995 ISSN 0114-0663 COVER PAGE NZECP 14: 1995 ISSN 0114-0663 COVER PAGE NZECP 14:1995 NEW ZEALAND ELECTRICAL CODE OF PRACTICE FOR CONTROL PROTECTION AND SWITCHBOARDS Issued by the Office of The Chief Electrical Engineer, Energy and

More information

PROTECTION AGAINST ELECTRIC SHOCK by John Ware

PROTECTION AGAINST ELECTRIC SHOCK by John Ware 16 become live under fault conditions. The potential of the metal enclosure is higher than that of the main earthing terminal of the installation (and that of Earth) because of a potential difference created

More information

MEGGER 210170 Insulation & Low Resistance Tester

MEGGER 210170 Insulation & Low Resistance Tester MEGGER 210170 Insulation & Low Resistance Tester User Guide SAFETY WARNINGS Safety Warnings and Precautions must be read and understood before the instrument is used. They must be observed during use.

More information

SAFETY OF SOLAR PANEL INSTALLATIONS IN VICTORIA REPORT

SAFETY OF SOLAR PANEL INSTALLATIONS IN VICTORIA REPORT SAFETY OF SOLAR PANEL INSTALLATIONS IN VICTORIA REPORT July 2010 Table of Contents Executive Summary... 3 Glossary of Acronyms and Phrases.....4 Introduction...5 Background 6 Electricity safety requirements

More information

Electricity at work Safe working practices

Electricity at work Safe working practices Electricity at work Safe working practices The guidance covers the key elements to consider when devising safe working practices and is for people who carry out work on or near electrical equipment. It

More information

ScottishPower Distribution Cables & Equipment. Metal Theft

ScottishPower Distribution Cables & Equipment. Metal Theft ScottishPower Distribution Cables & Equipment Metal Theft April 2012 As an aid to deterring to metal theft this booklet has been put together to help identify the types of utility power cables and associated

More information

TRAINING RESOURCE MANUAL NATIONAL SPECIALISED ELECTRICAL WORK RECORD OF WORK EXPERIENCE AND TRAINING UEENEEP024A UEENEEP017A. EE-Oz Training Standards

TRAINING RESOURCE MANUAL NATIONAL SPECIALISED ELECTRICAL WORK RECORD OF WORK EXPERIENCE AND TRAINING UEENEEP024A UEENEEP017A. EE-Oz Training Standards TRAINING RESOURCE MANUAL NATIONAL SPECIALISED ELECTRICAL WORK UEENEEP024A UEENEEP017A RECORD OF WORK EXPERIENCE AND TRAINING 1 CONTENTS Learner s Personal Details Page 3 Background Information Page 4 Definitions

More information

Release: 2. UEENEEJ194A Solve problems in low voltage refrigeration circuits

Release: 2. UEENEEJ194A Solve problems in low voltage refrigeration circuits Release: 2 UEENEEJ194A Solve problems in low voltage refrigeration circuits UEENEEJ194A Solve problems in low voltage refrigeration circuits Modification History Not Applicable Unit Descriptor Unit Descriptor

More information

Service & Installation Rules 2014

Service & Installation Rules 2014 Victorian Electricity Distributors Service & Installation Rules 2014 These Service & Installation Rules form the following Distributors Reasonable Technical Requirements for the connection of electrical

More information

Section B: Electricity

Section B: Electricity Section B: Electricity We use mains electricity, supplied by power stations, for all kinds of appliances in our homes, so it is very important to know how to use it safely. In this chapter you will learn

More information

PUBLIC LIGHTING CODE April 2005

PUBLIC LIGHTING CODE April 2005 PUBLIC LIGHTING CODE April 2005 2nd Floor, 35 Spring Street, Melbourne Telephone: (+613) 9651 0222 Facsimile: (+613) 9651 3688 Email address: reception@esc.vic.gov.au Website: http//www.esc.vic.gov.au

More information

WA Electrical Requirements

WA Electrical Requirements WA Electrical Requirements Issued by the Director of Energy Safety January 2014 Preface Energy Safety Division (EnergySafety) of the Department of Commerce, following consultation with network operators

More information

Union County Public Schools. Facilities Department. Electrical. Safe Work Practices

Union County Public Schools. Facilities Department. Electrical. Safe Work Practices 1 Union County Public Schools Facilities Department Electrical Safe Work Practices 2 Purpose In accordance with OSHA Standards 1910.331-335, safety-related work practices shall be used by Union County

More information

2002 No. 2665 ELECTRICITY. The Electricity Safety, Quality and Continuity Regulations 2002

2002 No. 2665 ELECTRICITY. The Electricity Safety, Quality and Continuity Regulations 2002 STATUTORY INSTRUMENTS 2002 No. 2665 ELECTRICITY The Electricity Safety, Quality and Continuity Regulations 2002 Made - - - - - 24th October 2002 Laid before Parliament 28th October 2002 Coming into force

More information

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 READ CAREFULLY These instructions are intended to cover good practices in

More information

Insulation resistance

Insulation resistance The insulation resistance is particularly important for the prevention of damage and injury, and for the reliability of electrical systems and equipment. On the one hand it is basis for the protection

More information

Addendum #2 Contract UK-11-13

Addendum #2 Contract UK-11-13 Addendum #2 Contract UK-11-13 Utilities Kingston Purchase and Replacement of Switchgear at Kingston Hydro Substation MS11 March 25, 2011 Delivered to: All RFP recipients Total number of pages: Nine (9)

More information

INDUSTRIAL AND COMMERCIAL SERVICE TRANSFORMER & METERING INSTALLATION SPECIFICATION

INDUSTRIAL AND COMMERCIAL SERVICE TRANSFORMER & METERING INSTALLATION SPECIFICATION INDUSTRIAL AND COMMERCIAL SERVICE TRANSFORMER & METERING INSTALLATION SPECIFICATION February 2013 NOTE: If conflict exists between St. Thomas Energy s Conditions of Service and this document, the Conditions

More information

16. APTA PR-IM-S-016-02 Standard for Pantograph Current Collection Equipment Periodic Inspection and Maintenance

16. APTA PR-IM-S-016-02 Standard for Pantograph Current Collection Equipment Periodic Inspection and Maintenance 16. APTA PR-IM-S-016-02 Standard for Pantograph Current Collection Equipment Periodic Inspection and Maintenance Approved October 30, 2002 APTA Passenger Rail Equipment Safety Standards Task Force Authorized

More information

Title 20 PUBLIC SERVICE COMMISSION. Subtitle 50 SERVICE SUPPLIED BY ELECTRIC COMPANIES. Chapter 02 Engineering

Title 20 PUBLIC SERVICE COMMISSION. Subtitle 50 SERVICE SUPPLIED BY ELECTRIC COMPANIES. Chapter 02 Engineering Title 20 PUBLIC SERVICE COMMISSION Subtitle 50 SERVICE SUPPLIED BY ELECTRIC COMPANIES Chapter 02 Engineering Authority: Public Utility Companies Article, 2-121, 5-101 and 5-303, Annotated Code of Maryland.

More information

17. APTA PR-IM-S-017-02 Standard for Third Rail Current Collection Equipment Periodic Inspection and Maintenance

17. APTA PR-IM-S-017-02 Standard for Third Rail Current Collection Equipment Periodic Inspection and Maintenance 17. APTA PR-IM-S-017-02 Standard for Third Rail Current Collection Equipment Periodic Inspection and Maintenance Approved October 30, 2002 APTA Passenger Rail Equipment Safety Standards Task Force Authorized

More information

PLEASE NOTE. For more information concerning the history of these regulations, please see the Table of Regulations.

PLEASE NOTE. For more information concerning the history of these regulations, please see the Table of Regulations. PLEASE NOTE This document, prepared by the Legislative Counsel Office, is an office consolidation of this regulation, current to August 1, 2013. It is intended for information and reference purposes only.

More information

ELECTRICAL INSTALLATION CONDITION REPORT (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations)

ELECTRICAL INSTALLATION CONDITION REPORT (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations) Original Certificate DETAILS OF THE CLIENT Certificate reference: ELECTRICAL INSTALLATION CONDITION REPORT (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations) Name: Address: PURPOSE

More information

Annual testing programme will be reported, by the department, as part of the annual hazard review process due to be completed by 31 March each year.

Annual testing programme will be reported, by the department, as part of the annual hazard review process due to be completed by 31 March each year. HR Heath and Safety Policy Health and Safety Electrical Appliances Testing and Inspection Policy The University of Auckland provides for specific safe operating practices for the safety testing and inspection

More information

WORLDWIDE. GW400k SERIES MAINTENANCE MANUAL PROVEN PERIMETER PROTECTION

WORLDWIDE. GW400k SERIES MAINTENANCE MANUAL PROVEN PERIMETER PROTECTION ORLDIDE G400k SERIES MAINTENANCE MANUAL PROVEN PERIMETER PROTECTION GEOQUIP LIMITED Kingsfield Industrial Estate, Derby Road irksworth, Matlock, Derbyshire, DE4 4BG Tel : 01629 824891 Fax : 01629 824896

More information

GUIDELINES FOR ELECTRICAL WIRING IN RESIDENTIAL BUILDINGS

GUIDELINES FOR ELECTRICAL WIRING IN RESIDENTIAL BUILDINGS GUIDELINES FOR ELECTRICAL WIRING IN RESIDENTIAL BUILDINGS 2008 EDITION www.st.gov.my CONTENTS Chapter Title Page 1. 1.1 1.2 1.3 Introduction Purpose References 4 4 5 2. Supply System 6 2.1 Electricity

More information

CHAPTER VIII LINE PLANT SYSTEM COMMUNICATION THROUGH RE CABLE

CHAPTER VIII LINE PLANT SYSTEM COMMUNICATION THROUGH RE CABLE CHAPTER VIII LINE PLANT SYSTEM COMMUNICATION THROUGH RE CABLE 8.1 SYSTEM 8.1.1 Armoured, screened underground cables are used for control communication in electrified areas to limit induction effect. 8.2

More information

Unit 4: Electricity (Part 2)

Unit 4: Electricity (Part 2) Unit 4: Electricity (Part 2) Learning Outcomes Students should be able to: 1. Explain what is meant by power and state its units 2. Discuss the importance of reducing electrical energy wastage 3. State

More information

How the National Grid System Operates. Chris Gorman Lead Account Executive Syracuse

How the National Grid System Operates. Chris Gorman Lead Account Executive Syracuse How the National Grid System Operates Chris Gorman Lead Account Executive Syracuse 2 Parts of the Electric System Parts of the Electric System 1. Generating Station: Produces Electricity. 2. Transmission

More information

270526-TC Grounding and Bonding for Telecommunications Systems

270526-TC Grounding and Bonding for Telecommunications Systems 270526-TC Grounding and Bonding for Telecommunications Systems Part 1 - General Related Documents The following related sections of the OT standards shall also be applicable to this section. OT Engineer

More information

City of San Diego Residential Photovoltaic Systems Inspection Guidelines

City of San Diego Residential Photovoltaic Systems Inspection Guidelines City of San Diego Residential Photovoltaic Systems Inspection Guidelines The purpose of inspections by DSD staff is to ensure compliance with the California Electrical Code (CEC), other applicable codes

More information

Ausgrid s Policy on Public Lighting - Contestable Projects. AUSPL CONPOL01 September 2012

Ausgrid s Policy on Public Lighting - Contestable Projects. AUSPL CONPOL01 September 2012 Ausgrid s Policy on Public Lighting - Contestable Projects AUSPL CONPOL01 September 2012 Ausgrid s Policy on Public Lighting - Contestable Projects September 2012 Contents 1 OBJECTIVE... 3 2 SCOPE AND

More information

Polarity. Electrical Quals 2007 1

Polarity. Electrical Quals 2007 1 Polarity Electrical Quals 2007 1 Polarity testing Introduction The polarity test is the 8th test in the sequence. Some people will think of it as the 4th test, (which to a certain extent they are correct).

More information

Data Sheet. Portable Appliance Testing

Data Sheet. Portable Appliance Testing Data Pack A Issued March 2003 1502621615 Data Sheet Portable Appliance Testing Why is appliance safety inspection and testing required? A quarter of all serious electrical accidents involve portable electrical

More information

Service and Installation Rules of New South Wales

Service and Installation Rules of New South Wales Service and Installation Rules of New South Wales The electricity industry standard of best practice for customer connection services and installations August 2012 Foreword This is the August 2012 edition

More information

THE ELECTRICAL CONTRACTOR SAFETY PROGRAM GUIDE

THE ELECTRICAL CONTRACTOR SAFETY PROGRAM GUIDE THE ELECTRICAL CONTRACTOR SAFETY PROGRAM GUIDE December 2013 Electrical Hazard Warning Sign Disclaimer Whilst this guide endeavours to provide general information on work health and safety issues relating

More information

Electrical Safety Tester Verification

Electrical Safety Tester Verification Ensuring Validity of Regulatory Tests Verification of electrical safety testing equipment is a procedure that is often overlooked by manufacturers. Running test verification is crucial to ensuring that

More information

MEDIUM VOLTAGE SUBSTATION PRACTICES Medium Voltage (MV) is defined as: 1000V< MV 44kV

MEDIUM VOLTAGE SUBSTATION PRACTICES Medium Voltage (MV) is defined as: 1000V< MV 44kV MEDIUM VOLTAGE SUBSTATION PRACTICES MEDIUM VOLTAGE SUBSTATION PRACTICES Medium Voltage (MV) is defined as: 1000V< MV 44kV MEDIUM VOLTAGE SUBSTATION PRACTICES This presentation covers some safety aspects

More information

GUIDANCE ON ELECTRICAL INSPECTIONS

GUIDANCE ON ELECTRICAL INSPECTIONS GUIDANCE ON ELECTRICAL INSPECTIONS Electricity Electricity is a versatile and convenient source of energy. However, it can be potentially dangerous if the system has not been properly designed, installed,

More information

The Electrical Contractor Safety Program Guide

The Electrical Contractor Safety Program Guide The Electrical Contractor Safety Program Guide September 2013 Electrical Hazard Warning Sign Disclaimer Whilst this guide endeavors to provide general information on work health and safety issues relating

More information

Sheath fault location on power cables. Sheath testing, Sheath fault location and Location of earth faults

Sheath fault location on power cables. Sheath testing, Sheath fault location and Location of earth faults Sheath fault location on power cables Sheath testing, Sheath fault location and Location of earth faults Table of Contents 1. Introduction... 3 2. Why Sheath testing... 3 2.1 Sheath test devices... 4 2.2

More information

6.0 Electrical Installations

6.0 Electrical Installations 6.0 An electrical installation is a combination of electrical equipment installed to fulfill a specific purpose and having coordinated characteristics. In dealing with the electrical installation, it is

More information

Advantages of Fixed Circuit Breaker Switchgear

Advantages of Fixed Circuit Breaker Switchgear Advantages of Fixed Circuit Breaker Switchgear by Lionel Mackay, EDF Energy, and Mike Adams, Schneider Electric Ltd Introduction The purpose of this paper is to review the advantages of fixed circuit breaker

More information

1 Introduction. 2 Hazards From Electricity

1 Introduction. 2 Hazards From Electricity Risk Assessment Application to Electrical Rigs A guide to assist the Competent Named person who will verify the safety of rigs consisting mainly of electrical equipment. 1 Introduction Every employer shall

More information