1 Part D: Code Book Questions Article 250: Grounding And Bonding 1.! A ground-fault is an unintentional, electrically conducting connection between an ungrounded! conductor of an electrical circuit and the normally non-current-carrying conductors, or! earth.! (a) metallic enclosures! (c) metallic equipment! (b) metallic raceways! (d) all of these 2.! Ground clamps, or other fittings shall be approved for general use without protection or shall be! protected.! (a)!by enclosing in wood! (c) by equivalent protective covering! (b) by enclosing in metal! (d) all of these 3.! Nonconductive coatings (such as paint, lacquer, and enamel) on equipment to be grounded shall! be removed from threads and other contact surfaces to.! (a) provide a water tight joint! (c) assure good electrical continuity! (b) provide a sealed joint! (d) lower inductance 4.! A.C. circuits of less than 50 volts shall be grounded under which of the following?! (a)!where supplied by transformers if the supply system exceeds 150 volts to ground.! (b)!where supplied by transformers if the transformer supply system is ungrounded.! (c)! Where installed as overhead conductors outside of buildings.! (d)!all of these 5.! Which of the following A.C. systems ( volts) need not be grounded?! (a) motion picture projection equipment!! (c) metal service raceways! (b) electrically operated cranes!! (d) industrial electric furnaces 6.! Circuits for electrical cranes operating in Class III locations over combustible fibers shall not! be.! (a) grounded! (c) spliced! (b) pulled in raceways! (d) THWN conductors

2 7.! Where an A.C. system operating at less than volts is grounded at any point, the grounded! conductor shall be run to each service.! (a) 300! (c) 1000! (b) 600! (d) ! The grounded service conductor shall not be smaller than the required.! (a) grounding electrode conductor! (c) ungrounded service conductor! (b) largest phase conductor! (d) largest equipment conductor 9.! When service entrance phase conductors are larger than 1100 kcmil copper, the bonding jumper! shall have an area not less than % of the area of the largest phase conductor.! (a) 6%! (c) 12-1/2%! (b) 10%! (d) 15% 10.!A bonding jumper shall be used to connect the equipment grounding conductors of the derived! system to the grounded conductor. This connection shall be made at.! (a)!any point on the separately derived system from the source to the first system disconnect! (b)!any point on the separately derived system from the source to the first overcurrent device! (c)! the source if the system has no disconnecting means or overcurrent device! (d)!all of these 11.!A grounding electrode conductor shall not be required for a system that supplies a and is! derived from a transformer not more than 1000 va, provided the system grounded conductor is! bonded to the transformer frame.! (a) Class I circuit! (c) Class III circuit! (b) Class II circuit! (d) all of these 12.!Which of the following conditions must be met for vehicle mounted generators used to supply! electrical tools on a construction site?! (a)!the frame of the generator is bonded to the vehicle frame! (b)!the generator supplies cord and plug connected equipment through receptacles mounted on!! the vehicle or on the generator! (c)! The non-current-carrying metal parts of equipment and the equipment grounding conductor!! terminals of the receptacles are bonded to the generator frame.! (d)!all of these

3 13.!Given: A metal underground water pipe is used as a grounding electrode and used to bond other! electrodes together. The grounding electrode conductor is connected to the water pipe on the! interior of the building. The connection of the grounding electrode conductor to the interior water! pipe shall be made a maximum of feet from the point where the water pipe enters the! building.! (a) 3! (c) 8! (b) 5! (d) !A metallic water system is used as a grounding means. Which of the following statements! is/are true?! (a)!must be bonded around the meter.! (b)!must bond around insulated joints.! (c)! Must be supplemented by an additional electrode.! (d)!all of these are true 15.!A bare #4 conductor may be concrete encased and serve as the grounding electrode when at least! feet in length.! (a) 10! (c)! 20! (b) 12! (d)!15 16.!Electrodes of pipe, or conduit, shall not be smaller than trade size.! (a) 1/2! (c) 3/4! (b) 5/8! (d) 1 17.!Electrodes of iron or steel shall have a diameter of at least.! (a) 1/2! (c) 1! (b) 3/4! (d) 5/8 18.!The number of square feet that each plate electrode should expose to the soil is.! (a) 4 square feet! (c) 2 square feet! (b) 3 square feet! (d) 1 square foot 19.!In using multiple grounding electrodes, they shall be separated one from the other at feet! distance apart.! (a) 6! (c) 10! (b) 8! (d) 12

4 20.!A ground ring encircling the building, in direct contact with the earth at a depth below earth! surface shall not be less than inches, consisting of at least 20 of bare copper not smaller than! #2 AWG.! (a) 24! (c) 36! (b) 30! (d) !The grounding electrode shall be installed such that of length is in contact with the soil.! (a) 6! (c) 7 6! (b) 7! (d) 8 22.!A single electrode consisting of a which does not have a resistance to ground of 25Ω or less! shall be augmented by one additional electrode.! (a) rod! (c) plate! (b) pipe! (d) any of these 23.!Where separate services supply a building and are required to be connected to a grounding! electrode, shall be used.! (a) multiple electrodes! (c) two electrodes! (b) the same grounding electrode! (d) paralleled electrodes 24.!Bonding together of all separate grounding electrodes will limit between them and between! their associated wiring systems.! (a) potential differences! (c) stray currents! (b) high frequencies! (d) arcing 25.!The grounding electrode conductor shall be and shall be installed in one continuous length! without a splice or joint.! (a) solid or stranded! (c) bare! (b) insulated or covered! (d) any of these 26.!Aluminum grounding conductors shall not be used where.! (a) within 18 of earth! (c) in direct contact with masonry! (b) subject to corrosive conditions! (d) any of these

5 27.! and larger grounding electrode conductors shall be protected where exposed to severe! physical damage.! (a) #8! (c) #4! (b) #6! (d) #2 28.!Grounding electrode conductors smaller than #6 shall be in.! (a) EMT! (c) rigid metal conduit! (b) IMC! (d) any of these 29.!The #4 solid copper conductor connecting the grounding electrode to the service has been! accidentally cut. Which of the following would be acceptable connectors for splicing this! conductor?! (a) split bolt connector!! (c) wire nut! (b) irrevesible compression sleeve connector!! (d) none of these are acceptable 30.!According to the Code, ferrous metal enclosures for grounding electrode conductors shall.! (a) not be permitted! (c) be in rigid conduit! (b) be electrically continuous! (d) none of these 31.!A single-family dwelling contains a 200 amp single-phase service panel supplied with #2/0 THW! conductors. The minimum size bonding jumper for this service is.! (a) #6 aluminum! (c) #4 aluminum! (b) #6 copper! (d) #4 copper 32.!A concrete encased or buried grounding electrode connection shall.! (a) be made accessible!! (c) be a minimum #4 bare! (b) be made only by exothermic welding!! (d) not be required to be accessible 33.!The grounding or bonding conductor shall be connected to the grounding electrode by, or! other listed means.! (a) exothermic welding! (c) listed pressure connectors! (b) listed lugs! (d) any of these 34.!Connections to grounding and bonding jumpers be made dependent on soldering.! (a) shall! (c) shall not! (b) may! (d) must

6 35.!Not more than one conductor shall be connected to the grounding electrode by a single clamp or! fitting unless the clamp or fitting is.! (a) cast bronze or brass! (c) in thickness! (b) listed for multiple conductors! (d) none of these 36.!Grounding of a metal raceway used to protect fluorescent is required if the raceway is feet! or over, or within reach of ground or grounded metal.! (a) 6! (c) 10! (b) 8! (d) !Short sections of metal enclosures, or raceways, used to protect from physical damage shall! not be required to be grounded.! (a) service conductors! (c) cable assemblies! (b) feeders! (d) none of these 38.!A metal elbow installed underground in a run of nonmetallic conduit is not required to be! grounded if it is isolated by a minimum cover of at least inches to any part of the elbow.! (a) 6! (c) 18! (b) 12! (d) !Which of the following shall be provided where necessary to assure electrical continuity and the! capacity to conduct safely any fault current likely to be imposed?! (a) Grounding! (c) Jumpers! (b) Bonding! (d) Shunts 40.!A #6 copper conductor with one end bonded to the service raceway or equipment and with! inches or more of the other end made accessible on the outside wall of the dwelling is an example! of the approved means for the external connection of a bonding, or grounding conductor to the! service raceway or equipment.! (a) 6! (c) 24! (b) 12! (d) !To ensure effective continuity between enclosures shall be removed from the conduit! threads.! (a) ends! (c) galvanize finish! (b) enamel! (d) aluminum

7 42.!Expansion joints and telescoping sections of raceway shall be made electrically continuous by! equipment or other means approved for the purpose.! (a) grounding conductors! (c) bonding jumpers! (b) grounded conductor! (d) none of these 43.!A bonding jumper shall be a, or similar suitable conductor.! (a) wire! (c) bus! (b) screw! (d) any of these 44.!Service bonding jumpers must be sized.! (a) according to the fuse size!! (c) 1/3 as large as the service conductor! (b) same as the largest service conductor!! (d) according to Table !The maximum length of a bonding jumper on the outside of a raceway is feet and shall be! routed with the raceway or enclosure.! (a) 3! (c) 8! (b) 6! (d) none of these 46.!The interior metal water piping system shall be bonded to the.! (a) grounded conductor at the service!! (c) service equipment enclosure! (b) grounding electrode conductor!! (d) any of these 47.!Non-current carrying metal parts of electrical equipment typically is kept feet (through air)! from lightning protection conductors?! (a) 3! (c) 8! (b) 6! (d) !Equipment installed and likely to become energized shall be grounded at which of the following! distances?! (a)!8 feet horizontal and 5 feet vertical of grounded metal objects! (b)!5 feet vertical and 5 feet horizontal of grounded metal objects! (c)! 8 feet vertical and 5 feet horizontal of grounded metal objects! (d)!8 feet vertical and 8 feet horizontal of grounded metal objects

8 49.!Exposed non-current carrying metal parts of fixed equipment must be grounded under all of the! following conditions except (by special permission).! (a)!where supplied by metal clad wiring! (b)!electrically heated appliances with the frames insulated from ground! (c)! where in electrical contact with metal! (d)!where located in damp locations 50.!Listed equipment protected by a system of double insulation, or its equivalent, shall not be! required to be grounded. Where such a system is employed, the equipment shall be.! (a) labeled! (c) distinctively marked! (b) approved! (d) identified 51.!An electrically operated organ shall have both the generator and motor frames grounded! or.! (a)!the generator and motor shall be effectively insulated from ground and from each other! (b)!the generator and motor shall be effectively insulated from ground! (c)! the generator shall be effectively insulated from ground and from the motor driving it! (d)!both the generator and motor shall have double insulation 52.!Which appliance, in a dwelling is not required to be grounded if insulated from ground?! (a) toaster! (c) blender! (b) can opener! (d) aquarium 53.!Where extensive metal in or on buildings may become energized and is subject to personal contact! will provide additional safety.! (a) adequate bonding and grounding! (c) suitable ground detectors! (b) bonding! (d) none of these 54.!A run of flexible metal conduit may be used as an equipment grounding conductor if the! conductors are protected at, not exceeding six feet in length.! (a) 20 amps or more! (c) 30 amps or more! (b) 20 amps or less! (d) 30 amps or less 55.!The grounding conductor shall be identified by.! (a) being bare! (c) a continuous green color with yellow stripes! (b) one continuous green color! (d) any of these

9 56.!The equipment grounding conductor in type NM cable for 15, 20 and 30 ampere branch! circuits.! (a)!may be at least one size smaller than the insulated circuit conductor! (b)!must be the same size as the insulated circuit conductors! (c)! is required only with aluminum cable! (d)!none of these 57.!Which of the following is not a true statement concerning an equipment grounding conductor?! (a)!equipment grounding conductors may be required to be larger than circuit conductors.! (b)!under certain conditions, equipment grounding conductors may be run in parallel.! (c)! Equipment grounding conductors shall be increased to compensate for voltage drop.! (d)!one equipment grounding conductor may serve multiple circuits. 58.!A/an shall be used to connect the grounding terminal of a grounding type receptacle to a! grounded box.! (a) neutral conductor! (c) equipment bonding jumper! (b) branch circuit! (d) bonding jumper main 59.!The arrangement of grounding connections shall be such that the disconnection or removal of a! from the box does not interfere with or interrupt the grounding continuity.!! (a) receptacle! (c) device! (b) luminaire (fixture)! (d) any of these 60.!A two-wire D.C. system supplying premises wiring and operating at less than 50 volts between! conductors shall.! (a) not be grounded! (c) not be permitted! (b) be grounded! (d) not be required to be grounded 61.!Fire protective signaling circuits shall be grounded, the only exception being D.C. power-limited! circuits having a maximum current of amperes.! (a) 0.300! (c) 0.030! (b) 1.5! (d) 2.34

10 62.!What size grounding conductor is required for a two-wire DC generator used in conjunction with! balancer sets to obtain neutrals for a 3-wire system equipped with overcurrent devices that will! disconnect the 3-wire system in case of excessive unbalancing of voltages or currents?! (a)!#10 solid copper minimum size! (b)!shall not be smaller than any system conductor! (c)! shall not be smaller than the neutral conductor! (d)!sized from Table !Secondary circuits of current and potential instrument transformers shall be grounded where the! primary windings are connected to circuits of volts or more to ground and, where on! switchboards, shall be grounded irrespective of voltage.! (a) 30! (c) 250! (b) 100! (d) !Cases or frames of current transformers, the primaries of which are not over 150 volts to ground! and which are used exclusively to supply current to meters.! (a) need to be grounded! (c) need to be insulated! (b) need to be isolated! (d) need not be grounded 65.!Mats of insulating rubber or other suitable floor insulation shall be provided for the operator! where the voltage to ground exceeds on live-front switchboards.! (a) 50! (c) 120! (b) 100! (d) !The grounding conductor for secondary circuits of instrument transformers and for instrument! cases shall not be smaller than #12.! (a) metal! (c) copper! (b) aluminum! (d) all of these 67.!The minimum insulation level for neutral conductors of solidly grounded systems shall be! volts.! (a) 600! (c) 1500! (b) 1000! (d) 2100

11 68.!The neutral of a solidly grounded neutral system shall be permitted to be grounded at more than! one point for.! (a)!transformers supplying conductors to a building or other structure! (b)!underground circuits where the neutral is exposed! (c)! overhead circuits installed outdoors! (d)!all of these 69.!The grounding electrode to which the portable or mobile equipment system neutral impedance is! connected shall be isolated from and separated in the ground by at least feet from any other! system or equipment grounding electrode.! (a) 6! (c) 12! (b) 10! (d) 20!! Article 280: Surge Arresters 70.!A surge arrester is a protective device for limiting surge voltages by or by passing surge! current.! (a) decreasing! (c) limiting! (b) discharging! (d) derating 71.!The rating of the surge arrester shall be the maximum continuous phase-to-ground power! frequency voltage available at the point application.! (a) equal to! (c) greater than! (b) less than! (d) equal to or greater than 72.!Metal oxide surge arrester ratings are based on the magnitude and duration of overvoltage at the! arrester location as affected by.! (a) switching surges! (c) phase-to-ground faults! (b) system grounding technique! (d) all of these 73.!Surge arresters shall be permitted to be located and shall be made inaccessible to! unqualified persons unless listed for installation in accessible location.! (a) indoors! (c) indoors or outdoors! (b) outdoors! (d) neither indoors or outdoors

12 74.!When installing a surge arrester at the service of less than 1000 volts, the grounding conductor! shall be connected to.! (a) the grounded service conductor!! (c) the grounding electrode for the service! (b) the grounding electrode conductor!! (d) all of these 75.!The conductor between a surge arrester and the line for installations operating at 1000 volts or! more may be.! (a) #6 copper! (c) #4 copper! (b) #6 aluminum! (d) any of these 76.!Surge arrester grounding conductors run in metal enclosures shall be.! (a) bare!! (c) bonded to both ends of such enclosure! (b) bonded on one end of the enclosure only! (d) insulated

Grounding & Bonding Why it is done And How to Install Properly

Grounding & Bonding Why it is done And How to Install Properly Grounding & Bonding Why it is done And How to Install Properly The technical information provided herein is to assist qualifi ed persons in planning and installing electric service to farms and residences.

More information

2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property

2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property 2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property A brief summary of the most used code references for residential wiring State of Idaho Division of Building Safety Electrical

More information

RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS:

RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS: RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS: Signed completed Electrical Permit application form. Minnesota law requires all electrical work is to be performed by licensed,

More information

ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS:

ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS: ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS: Chapter 12 of the Burlington Code of ordinances allows owner occupants of single family homes to do their own wiring if they choose. If you choose to

More information

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations. DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,

More information

Electrical Grounding. Appendix C

Electrical Grounding. Appendix C Appendix C Electrical Grounding Low-Voltage Equipment Grounding The most frequently cited Office of Safety and Health Administration (OSHA) electrical violation is improper occupational grounding of equipment

More information

GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264

GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264 BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used

More information

Grounding of Electrical Systems NEW CODE: Grounding and Bonding

Grounding of Electrical Systems NEW CODE: Grounding and Bonding Grounding of Electrical Systems NEW CODE: Grounding and Bonding Presented By Scott Peele PE Grounding of Electrical Systems Outline Defining the Terms Why should I Ground? Types of Grounding Systems Separately

More information

STREETLIGHT SYSTEM GROUNDING AND BONDING

STREETLIGHT SYSTEM GROUNDING AND BONDING Page: 1 of 8 STREETLIGHT SYSTEM GROUNDING AND BONDING 1. Scope This Construction Standard covers the grounding and bonding requirements for single phase streetlight systems served by the Looped Radial

More information

ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST

ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST Name of School: OPTIONAL INFORMATION Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST Guidelines: This checklist

More information

The National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables

The National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables The National Armored Cable Manufacturers Association Presents Installation Standard for Types AC and MC Cables An ANSI Standard Original document jointly produced by NECA and NACMA as Standard for Installing

More information

800 Communications Circuits

800 Communications Circuits ARTICLE 800 Communications Circuits INTRODUCTION TO ARTICLE 800 COMMUNICATIONS CIRCUITS This article has its roots in telephone technology. Consequently, it addresses telephone and related systems that

More information

Residential Electrical Inspection. Checklist

Residential Electrical Inspection. Checklist 443 Lafayette Road N. St. Paul, Minnesota 55155 www.doli.state.mn.us Residential Electrical Inspection (651) 284-5064 1-800-DIAL-DLI Fax: (651) 284-5743 TTY: (651) 297-4198 Checklist Generally, Minnesota

More information

2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE

2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE 2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE PAGE 1 OF 5 This Reference provides a very comprehensive list of aspects of a solar PV installation that could be reviewed, clarifying

More information

Title: Grounding and Bonding Rev-01

Title: Grounding and Bonding Rev-01 Procedure No.: BMEHS-002-012 Page: 1 of 12 Preparer: Owner: Approver: EHS Team Member S/H Manager Site Manager Signed Copy on File Signed Copy on File Signed Copy on File Document Revision Change Table

More information

Electrical Code Regulation

Electrical Code Regulation Electrical Code Regulation St. Clair County has adopted the 2005 National Electrical Code in its entirety for the unincorporated areas of the county and all communities that have contracted with the county

More information

www.klmtechgroup.com TABLE OF CONTENT

www.klmtechgroup.com TABLE OF CONTENT Page : 1 of 13 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia ELECTIRAL GROUNDING TABLE OF CONTENT

More information

DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS

DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS MIOSHA-STD-1313 (10/15) 6 Pages For further information Ph: 517-284-7740 www.michigan.gov/mioshastandards DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS

More information

ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS

ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS Prepared by: ABB1 ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS 052521 Asset Type: Electric Metering Function: Construction Issued by: Quoc Hoang (QxH1) Date: 07-01-16 Rev. #06: This document

More information

Residential Electrical Inspection Checklist

Residential Electrical Inspection Checklist Residential Electrical Inspection Checklist Based on the 2008 National Electrical Code Generally, Minnesota law requires all electrical work to be performed by licensed, bonded and insured electrical contractors

More information

CHAPTER 2 EXAMPLES AND TABLES

CHAPTER 2 EXAMPLES AND TABLES CHAPTER 2 EXAMPLES AND TABLES COMMENTARY AT 210.20(A) EXCEPTION An overcurrent device that supplies continuous and noncontinuous loads must have a rating that is not less than the sum of 100 percent of

More information

GUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS

GUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS GUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS This guideline has been prepared to assist the owner/occupant of a single family dwelling with compliance to the requirements of the National Electrical

More information

IRRIGATION PUMPING Table of Contents - Section 900

IRRIGATION PUMPING Table of Contents - Section 900 IRRIGATION PUMPING Table of Contents - Section 900 PARAGRAPH 900.1 GENERAL 1 900.2 METERING REQUIREMENTS 1 900.3 CUSTOMER S CONTROL EQUIPMENT 2 900.4 SERVICE CONDUCTOR REQUIREMENTS 2 900.5 RECOMMENDATIONS

More information

Residential Electrical Inspection. Checklist

Residential Electrical Inspection. Checklist Electrical Licensing and Inspection 443 Lafayette Road North St. Paul, Minnesota 55155-4342 www.doli.state.mn.us 651-284-5064 Fax: 651-284-5743 TTY: 651-297-4198 1-800-DIAL-DLI Residential Electrical Inspection

More information

Application Bulletin 103 - NEC Reference Guide for SolarBridge-Enabled AC Module Installers

Application Bulletin 103 - NEC Reference Guide for SolarBridge-Enabled AC Module Installers 9229 Waterford Centre Dr. Bldg C, Suite 110 Austin, Tx 78758 Application Bulletin 103 - NEC Reference Guide for SolarBridge-Enabled AC Module Installers Current Version: 13 AC Modules are a new product

More information

ELECTRICAL INSPECTION BULLETIN (Effective 2000-03-01)

ELECTRICAL INSPECTION BULLETIN (Effective 2000-03-01) ELECTRICAL INSPECTION BULLETIN (Effective 2000-03-01) Rule 28-900 Standby Generator Installations Due to the increasing number of standby generator installations being established to maintain continuity

More information

ELECTRICAL SAFETY Information Bulletin

ELECTRICAL SAFETY Information Bulletin ELECTRICAL SAFETY Information Bulletin January 2016 CEC-10 [rev-9] Page 1 of 8 CANADIAN ELECTRICAL CODE SUBJECT: Section 10 Grounding and Bonding Rule 10-204 Grounding Connections for Alternating-Current

More information

The Service Entrance. Technical Terms Drip loop Insulator Meter Meter enclosure

The Service Entrance. Technical Terms Drip loop Insulator Meter Meter enclosure This sample chapter is for review purposes only. Copyright The Goodheart-Willcox Co., Inc. All rights reserved. 10 The Entrance Objectives Information in this chapter will enable you to: List the components

More information

CONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION

CONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION Page 1 of 11 ****This Standard Supercedes BECo CS2.13-2.3 & ComElectric OH Construction Manual, System Grounding Section, drawings CGND, GRDSUM, and C2**** 1.0 Bill of Materials GROUNDING AND BONDING POLE-MOUNTED

More information

GENERAL ELECTRICAL REQUIREMENTS

GENERAL ELECTRICAL REQUIREMENTS GENERAL ELECTRICAL REQUIREMENTS RECEPTACLE SPACING Within 6-feet of the edge of any door HABITABLE Not more than 12-feet apart along wall ROOMS: At all wall spaces 24 or more wide Within 24 of edge of

More information

INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE SAFETY BULLETIN #23

INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE SAFETY BULLETIN #23 INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE SAFETY BULLETIN #23 GUIDELINES FOR WORKING WITH PORTABLE POWER DISTRIBUTION SYSTEMS AND OTHER ELECTRICAL EQUIPMENT "ADDENDUM C" WORKING WITH 480 VOLT SYSTEMS

More information

BASIC NEC CODE RULES AND DESIGN PRACTICE

BASIC NEC CODE RULES AND DESIGN PRACTICE BASIC NEC CODE RULES AND DESIGN PRACTICE Wire Ampacity and Size Circuit Breaker Size 1. Maximum loading for any branch circuit is 80% of rating of circuit for ampacity of wire for any load. NEC 220-2,

More information

Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016. Underground branch circuit feeding a detached garage:

Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016. Underground branch circuit feeding a detached garage: Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016 * Garage construction requires permits (electrical, building) * Permits must be applied for at the time. * Dial

More information

MONTGOMERY COUNTY EXECUTIVE REGULATION Offices of the County Executive. 101 Monroe Street. Rockville, Maryland 20850

MONTGOMERY COUNTY EXECUTIVE REGULATION Offices of the County Executive. 101 Monroe Street. Rockville, Maryland 20850 Montgomery County Regulation on: ADOPTION OF THE 2008 NATIONAL ELECTRICAL CODE DEPARTMENT OF PERMITTING SERVICES Issued by County Executive Regulation # 15-09 Authority: Code Section 17-2 and 17-3 Supersedes:

More information

NEC 2014 Code Changes

NEC 2014 Code Changes NEC 2014 Code Changes Articles 400-408.55 CHANGES FROM 2011 TO 2014 CODE ARE IN RED Chapter 4 Equipment for General Use ARTICLE 400 Flexible Cords and Cables 400.4 Types Flexible cords and flexible cables

More information

Questions and Answers for Heating and A/C Contractors

Questions and Answers for Heating and A/C Contractors 1. How do we accomplish grounding of furnaces and / or water heaters on two wire circuits? 250.134 Equipment Fastened in Place or Connected by Permanent Wiring Methods (Fixed) Grounding. Unless grounded

More information

Chapter 9. Bonding and Grounding

Chapter 9. Bonding and Grounding Chapter 9 Bonding and Grounding Objectives Describe why the cable should be bonded Describe bonding and grounding procedures Define Bonding and Grounding Explain Safety Benefits and intent of bonding and

More information

What are the basic electrical safety issues and remedies in solar photovoltaic installations?

What are the basic electrical safety issues and remedies in solar photovoltaic installations? What are the basic electrical safety issues and remedies in solar photovoltaic installations? Presented by: Behzad Eghtesady City of Los Angeles Department of Building and Safety Topics Covered Photovoltaic

More information

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D 12 - ELECTRIC SERVICE HANDBOOK SECTION D METER REQUIREMENTS This chapter gives you information on Central Lincoln s metering requirements. It's divided into three sections: General requirements This section

More information

BRANCH CIRCUIT AND FEEDER REQUIREMENTS

BRANCH CIRCUIT AND FEEDER REQUIREMENTS CHAPTER 36 BRANCH CIRCUIT AND FEEDER REQUIREMENTS SECTION E3601 GENERAL E3601.1 Scope. This chapter covers branch circuits and feeders and specifies the minimum required branch circuits, the allowable

More information

SECTION 22 LIGHTNING PROTECTION SYSTEM

SECTION 22 LIGHTNING PROTECTION SYSTEM SECTION 22 LIGHTNING PROTECTION SYSTEM 22.01 SCOPE: A. These Specifications shall form a part of the Contract Documents and shall govern construction work for all buildings to be built or modified for

More information

SWIMMING POOLS CHAPTER 41

SWIMMING POOLS CHAPTER 41 CHAPTER 41 SWIMMING POOLS SECTION E4101 GENERAL E4101.1 Scope [Section 680.1]. The provisions of this chapter shall apply to the construction and installation of electric wiring and equipment associated

More information

Significant Changes in the 2011 NEC Prepared by Bryan Holland City of North Port

Significant Changes in the 2011 NEC Prepared by Bryan Holland City of North Port Significant Changes in the 2011 NEC Prepared by Bryan Holland City of North Port Code-Wide Code Change Section 90.5(C). Fine Print Notes are now referred to as "Informational Notes." The purpose, intent,

More information

ELECTRIC METERING COMMERCIAL & INDUSTRIAL

ELECTRIC METERING COMMERCIAL & INDUSTRIAL ELECTRIC METERING COMMERCIAL & 1.0 INDEX 1.0 INDEX 2.0 SCOPE 3.0 GENERAL REQUIREMENTS 4.0 METER LOCATIONS 5.0 UNDERGROUND TERMINATIONS 6.0 METERING TRANSFORMER ENCLOSURES 7.0 SINGLE CUSTOMER METER INSTALLATIONS

More information

Hyperlinks are Inactive

Hyperlinks are Inactive Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)

More information

Requirements for Electrical Installations

Requirements for Electrical Installations ARTICLE 110 Requirements for Electrical Installations INTRODUCTION TO ARTICLE 110 REQUIREMENTS FOR ELECTRICAL INSTALLATIONS Article 110 sets the stage for how you ll implement the rest of the NEC. This

More information

Trade of Electrician. Three-phase Distribution Boards And Socket Circuits

Trade of Electrician. Three-phase Distribution Boards And Socket Circuits Trade of Electrician Standards Based Apprenticeship Three-phase Distribution Boards And Socket Circuits Phase 2 Module No. 2.3 Unit No. 2.3.2 COURSE NOTES Created by Charlie Walsh - Athlone TC Revision

More information

NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION 27 05 26 GROUNDING AND BONDING FOR COMMUNICATION SYSTEMS

NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION 27 05 26 GROUNDING AND BONDING FOR COMMUNICATION SYSTEMS SECTION GROUNDING AND BONDING FOR COMMUNICATION SYSTEMS RELATED SECTIONS: Section 27 00 00 General Requirements Section 27 02 00 Communication General Requirements Section 27 05 28 Pathways for Communications

More information

READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY!

READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY! READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY! The main power to any existing system must be disconnected prior to the

More information

Top Commercial / Residential Electrical Requirements *

Top Commercial / Residential Electrical Requirements * Department of Community Development Building Division 4800 West 92 nd Avenue Westminster, Colorado 80031 For Information call (303) 658-2075 Fax (303) 706-3922 www.westminsterpermits.com Top Commercial

More information

SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings

SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings *** Provide this document to the inspector along with ALL system installation instructions *** Project Address: Scope: Standard plan for the installation of grounded microinverter solar PV systems, not

More information

Entrances to and from Electrical Equipment Rooms

Entrances to and from Electrical Equipment Rooms Electrical Code Requirements for Commercial and Residential Buildings Presented by Bob Nuzzi State Electrical Inspector Entrances to and from Electrical Equipment Rooms 2005 NEC Section 110.26(C)(2) Large

More information

270526-TC Grounding and Bonding for Telecommunications Systems

270526-TC Grounding and Bonding for Telecommunications Systems 270526-TC Grounding and Bonding for Telecommunications Systems Part 1 - General Related Documents The following related sections of the OT standards shall also be applicable to this section. OT Engineer

More information

Multiple Meter Installation - 200 Amperes Per Position -Single Phase, Self-contained

Multiple Meter Installation - 200 Amperes Per Position -Single Phase, Self-contained Overhead Meters TABLE OF CONTENTS D D Consumer Service Pole for Mobile Home Park Temporary Service -wire Single Phase D. Overhead Meter Installation - Single Phase D. Connection Diagram - Single Phase

More information

Homeowner Information Guide Electrical Safety. British Columbia Safety Authority

Homeowner Information Guide Electrical Safety. British Columbia Safety Authority Homeowner Information Guide Electrical Safety British Columbia Safety Authority The following information should be carefully reviewed before performing any electrical work. The information contained in

More information

INSPECTION GUDELINES

INSPECTION GUDELINES GENERAL REQUIREMENTS Building permit and approved set of plans Building permit on the card is the same as on the route "If this is not the first inspection, read inspection records and notes on permit

More information

East Central College 14434.03 HANSEN HALL LEVEL 300/400 RENOVATIONS PACKAGE

East Central College 14434.03 HANSEN HALL LEVEL 300/400 RENOVATIONS PACKAGE SECTION 260519 - BUILDING WIRE AND CABLE PART 1 - GENERAL 1.1 WORK INCLUDES A. Base and Alternate Bids: 1. Contractor Provide: a. Building wire and cable as shown on drawings or specified including feeders,

More information

Voltage Drop (Single-Phase)

Voltage Drop (Single-Phase) Voltage Drop (Single-Phase) To Find: To Find Voltage Drop Formula: 2 x K x L x I V.D. = ------------------- C.M. Variables: C.M. = Circular Mill Area (Chapter 9, Table 8) To Find Voltage Drop Percentage

More information

Short Circuit Current Calculations

Short Circuit Current Calculations Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that

More information

Mobile Home Pre-Inspection Checklist

Mobile Home Pre-Inspection Checklist Mobile Home Pre-Inspection Checklist TWO (2) STEP INSPECTION PROCESS STEP ONE: CALL FOR THE FIRST INSPECTION WHEN THESE ITEMS ARE COMPLETE. 1. Septic tank installed and plumbing complete. (SEE PLUMBING

More information

TS 813 GROUNDING AND BONDING TTD 813.001 TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD 813.005 CONTROLLER CABINET GROUNDING

TS 813 GROUNDING AND BONDING TTD 813.001 TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD 813.005 CONTROLLER CABINET GROUNDING TORONTO TRANSPORTATION January 2012 TS 813 GROUNDING AND BONDING TABLE OF CONTENTS 1. DRAWINGS TTD 813.001 TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD 813.005 CONTROLLER CABINET

More information

Customer Substation Manual 08/05/02

Customer Substation Manual 08/05/02 Customer Substation Manual Table of Contents Section Page 2 of 85 Description 0 Preface 010.00 General 010.10 Information Required for the Review of New Customer Substations 010.20 New Customer Substation

More information

HOUSTON COMMUNITY COLLEGE HCC ALIEF CAMPUS MAIN BUILDING, FIRST, SECOND & FOURTH FLOORS RENOVATION ISSUE DATE: 10.17.12

HOUSTON COMMUNITY COLLEGE HCC ALIEF CAMPUS MAIN BUILDING, FIRST, SECOND & FOURTH FLOORS RENOVATION ISSUE DATE: 10.17.12 SECTION 27 05 26 - GROUNDING AND BONDING FOR COMMUNICATIONS SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes grounding and bonding products, design requirements and installation for communications

More information

TABLE OF CONTENTS. 437-004-2850 Temporary Lighting and Wiring... S-2 Temporary Wiring... S-2 Temporary Lighting... S-3

TABLE OF CONTENTS. 437-004-2850 Temporary Lighting and Wiring... S-2 Temporary Wiring... S-2 Temporary Lighting... S-3 Oregon Administrative Rules and Health Division ELECTRICITY S TABLE OF CONTENTS 437-004-2810 General Requirements... S-1 437-004-2850 Temporary Lighting and Wiring... S-2 Temporary Wiring... S-2 Temporary

More information

PRIMARY SERVICE LINE: The Company's conductors which connect the supply line with a transformer located on private property.

PRIMARY SERVICE LINE: The Company's conductors which connect the supply line with a transformer located on private property. INTRODUCTION These rules are issued for use by Customers, builders, electrical contractors, architects, engineers, etc. The rules require the installation of safe and adequate wiring and electrical equipment,

More information

ELECTRICAL SAFETY: QUALIFIED/NON QUALIFIED

ELECTRICAL SAFETY: QUALIFIED/NON QUALIFIED Preparation: Safety Mgr Authority: Dennis Johnston Issuing Dept: Safety Page: Page 1 of 9 Purpose The purpose of the Electrical Safety program is to set forth procedures for the safe use of electrical

More information

Specifications for Lightning Protection. ASAE Engineering Practice

Specifications for Lightning Protection. ASAE Engineering Practice Chapter 8: Lightning Specifications for Lightning Protection ASAE safety standards are not laws. They are recommended voluntary standards used by designers, engineers, manufacturers and users of the equipment,

More information

PALM BEACH COUNTY AMENDMENTS TO THE NATIONAL ELECTRICAL CODE, 1999 EDITION

PALM BEACH COUNTY AMENDMENTS TO THE NATIONAL ELECTRICAL CODE, 1999 EDITION PALM BEACH COUNTY AMENDMENTS TO THE NATIONAL ELECTRICAL CODE, 1999 EDITION CODING: Words underlined are additions to the 1999 NEC Words stricken are deletions to the 1999 NEC Adopted by Ordinance 99-73

More information

Electrical Service Guidelines

Electrical Service Guidelines Electrical Service Guidelines Middle Tennessee Electric Membership Corporation Revised: May 23, 2013 MTEMC's Electrical Guidelines TABLE OF CONTENTS Right-of-Way Clearance Guide 3 MTEMC Requirements 4

More information

EARTHING AND BONDING AT SECONDARY SUBSTATIONS

EARTHING AND BONDING AT SECONDARY SUBSTATIONS DISTRIBUTION CONSTRUCTION MANUAL SECTION 4 - SUBSTATIONS ISSUE B SEPT 1996 4.4.4 EARTHING AND BONDING AT SECONDARY SUBSTATIONS 1 SCOPE This section of the Distribution Construction Manual lays down the

More information

DIVISION 26 - ELECTRICAL SECTION 26 05 20 CABLES FOR INSTRUMENTATION

DIVISION 26 - ELECTRICAL SECTION 26 05 20 CABLES FOR INSTRUMENTATION DIVISION 26 - ELECTRICAL PART 1 - GENERAL 1.01 SUMMARY A. Section Includes 1. Instrumentation Cables 1.02 SUBMITTALS A. Submit in accordance with requirements of Section 01 33 00. B. Product Data: Submit

More information

MOBILE HOME SERVICE REQUIREMENTS GAS

MOBILE HOME SERVICE REQUIREMENTS GAS ELECTRIC AND GAS 1.0 INDEX 1.0 INDEX 2.0 PURPOSE 3.0 GENERAL 4.0 REFERENCE MATERIAL 5.0 TYPICAL UNDERGROUND UTILITY LAYOUT 6.0 METER PAD DETAILS 7.0 GENERAL INSTALLATION PROCEDURES 8.0 PEDESTAL SPECIFICATIONS

More information

Requirements for the Attachment of Communication Cable Facilities on PPL Poles

Requirements for the Attachment of Communication Cable Facilities on PPL Poles Page 99 of 137 Requirements for the Attachment of Communication Cable Facilities on Replaces: URS-3002 URS-3004 URS-101C-304 A-157649 Page 100 of 137 Reference Notes for Drawings: General 1. The term communication

More information

Direction of current flow through conductor. Fig. 1 Magnetic field generated by current flow

Direction of current flow through conductor. Fig. 1 Magnetic field generated by current flow ingle Conductor Cable Copper heathed Cable heath Currents ingle conductor cables present certain application considerations that do not arise in multiconductor cable installations. These considerations

More information

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. 2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to

More information

Department of Labor and Industry Electrical Licensing

Department of Labor and Industry Electrical Licensing Department of Labor and Industry Electrical Licensing License Examination Guide The information in this guide is provided by the Licensing Unit of the Department of Labor and Industry to ensure that applicants

More information

SYSTEM 1850-SE SERVICE ENTRANCE CABLE SYSTEM

SYSTEM 1850-SE SERVICE ENTRANCE CABLE SYSTEM Pyrotenax SYSTEM 1850-SE SERVICE ENTRANCE CABLE SYSTEM Contents Introduction This section provides an overview of general circuit design considerations and installation guidelines for a Pyrotenax System

More information

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT The purpose of these specifications is to insure that there are minimum

More information

Please check with your local inspection authority for any additional requirements before installation.

Please check with your local inspection authority for any additional requirements before installation. Specifications for Residential Overhead Electric Service Installation This brochure addresses most typical residential overhead service installations. Variances for the following specifications must be

More information

GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables

GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables Engineering Department SEPTEMBER, 2007 GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables General Requirements This section applies to all public and private utilities,

More information

(3) The requirements of this Section are supplementary to, or amendatory of, the general requirements of this Code.

(3) The requirements of this Section are supplementary to, or amendatory of, the general requirements of this Code. Section 68 Pools, Tubs, and Spas Scope 68-000 Scope (1) This Section applies to: Electrical installations and electrical equipment in or adjacent to pools; and Non-electrical metal accessories in a pool

More information

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

Submit shop drawings for equipment provided under this section Shop drawings shall indicate: Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,

More information

Errata NFPA 70. Proposed 2014 Edition

Errata NFPA 70. Proposed 2014 Edition Errata NFPA 70 National Electrical Code (Report on Proposals) Reference: 12-109 (Log #1618) Panel Meeting Action Proposed 2014 Edition The National Electrical Code Technical Correlating Committee notes

More information

Cable/Conduit Conversion

Cable/Conduit Conversion Cable/Conduit Conversion Busway can be used in many applications where cable and conduit are more commonly used. The question arises, Why use busway instead of conventional cable and conduit? Benefits

More information

Construction work requires electrical

Construction work requires electrical Temporary electrical wiring for construction sites Construction work requires electrical power for many purposes. However, exposure to weather, frequent relocation, rough use and other conditions not normally

More information

First Published in The Wichita Eagle on January 2, 2015 ORDINANCE NO. 49-897

First Published in The Wichita Eagle on January 2, 2015 ORDINANCE NO. 49-897 OCA #230100 First Published in The Wichita Eagle on January 2, 2015 ORDINANCE NO. 49-897 AN ORDINANCE AMENDING SECTIONS 4.A.080, 4.1.020, 4.1.110, 4.2.010, 4.2.070, 4.2.125, 4.2.170, 4.2.175 AND 4.2.220;

More information

Learning Module 13: Panelboards and Switchboards. 101 Basic Series

Learning Module 13: Panelboards and Switchboards. 101 Basic Series Learning Module 13: Panelboards and Switchboards 101 Basic Series What You Will Learn We ll step through each of these topics in detail: Introduction 4 Definitions 4 Similarities Between Panelboards and

More information

Trial Exams C. Standards and Regulations. Examination No: GH-08-C- 1 hour and 5 minutes plus 10 minutes reading time

Trial Exams C. Standards and Regulations. Examination No: GH-08-C- 1 hour and 5 minutes plus 10 minutes reading time Trial Exams C Standards and Regulations Examination No: GH-08-C- This test is intended to gauge your knowledge of essential information contained within AS/CA S009:2013. To qualify for an allpication to

More information

Services. Three Phase Service

Services. Three Phase Service Services Primary Service vs Secondary Service Overhead vs Underground Common Service Types Three Phase Wye Closed Open Delta Corner Grounded Center Tapped Open Single Phase Three Phase Service Wye Delta

More information

BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET

BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET Berthold Electric Company s Generator Connection Cabinet provides a quick and convenient station to connect a portable generator to a facility s main service

More information

Video Camera Installation Guide

Video Camera Installation Guide Video Camera Installation Guide The intent of this guide is to provide the information needed to complete or modify a video camera installation to avoid lightning and induced power surge damage. This guide

More information

A. Shop Drawing submittals shall include, but not be limited to, the following:

A. Shop Drawing submittals shall include, but not be limited to, the following: SECTION 26 05 53 IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical

More information

PLEASE NOTE. For more information concerning the history of these regulations, please see the Table of Regulations.

PLEASE NOTE. For more information concerning the history of these regulations, please see the Table of Regulations. PLEASE NOTE This document, prepared by the Legislative Counsel Office, is an office consolidation of this regulation, current to August 1, 2013. It is intended for information and reference purposes only.

More information

1. Division 26 Section "Underground Ducts and Utility Structures" for ground test wells. 2. Division 26 Section Electrical General Requirements.

1. Division 26 Section Underground Ducts and Utility Structures for ground test wells. 2. Division 26 Section Electrical General Requirements. PART 1 - GENERAL... 1 1.1 RELATED DOCUMENTS... 1 1.2 SUMMARY... 1 1.3 REFERENCES... 1 1.4 SUBMITTALS... 2 1.5 PROJECT RECORD DOCUMENTS... 2 1.6 QUALITY ASSURANCE... 3 PART 2 - PRODUCTS... 3 2.1 MANUFACTURERS...

More information

White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5

White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5 White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code June 2015 Revision 1.5 Shalhevet Bar-Asher; SolarEdge Technologies, Inc. Bill Brooks, PE; Brooks Engineering LLC

More information

Common Electrical Hazards in the Workplace Including Arc Flash. Presented by Ken Cohen, PhD, PE & CIH (Ret.)

Common Electrical Hazards in the Workplace Including Arc Flash. Presented by Ken Cohen, PhD, PE & CIH (Ret.) Common Electrical Hazards in the Workplace Including Arc Flash Presented by Ken Cohen, PhD, PE & CIH (Ret.) 1 What s New In February 1972, OSHA incorporated the 1971 edition of the National Fire Protection

More information

Photovoltaic System Grounding

Photovoltaic System Grounding Photovoltaic System Grounding Prepared by: John C. Wiles, Jr. Southwest Technology Development Institute College of Engineering New Mexico State University October 2012 Solar America Board for Codes and

More information

Security Cameras, CATV, GPS & Satellite Protection. White Paper

Security Cameras, CATV, GPS & Satellite Protection. White Paper Security Cameras, CATV, GPS & Satellite Protection White Paper Security Cameras, CATV, GPS & Satellite Protection Surge Protection Solutions for PTC 1 Security Cameras, CATV, GPS & Satellite Protection

More information

Union County Public Schools. Facilities Department. Electrical. Safe Work Practices

Union County Public Schools. Facilities Department. Electrical. Safe Work Practices 1 Union County Public Schools Facilities Department Electrical Safe Work Practices 2 Purpose In accordance with OSHA Standards 1910.331-335, safety-related work practices shall be used by Union County

More information

TYPICAL WIRING OF METER SOCKET FOR SINGLE PHASE, THREE WIRE OVERHEAD SERVICE

TYPICAL WIRING OF METER SOCKET FOR SINGLE PHASE, THREE WIRE OVERHEAD SERVICE TYPICAL WIRING OF METER SOCKET FOR SINGLE PHASE, THREE WIRE OVERHEAD SERVICE A. GENERAL NOTES: Service entrance line and load conductors, conduit straps, weatherhead, lock nuts, bushings, connectors, and

More information