(3) The requirements of this Section are supplementary to, or amendatory of, the general requirements of this Code.

Size: px
Start display at page:

Download "(3) The requirements of this Section are supplementary to, or amendatory of, the general requirements of this Code."

Transcription

1 Section 68 Pools, Tubs, and Spas Scope Scope (1) This Section applies to: Electrical installations and electrical equipment in or adjacent to pools; and Non-electrical metal accessories in a pool or within 3 m of the inside wall of a pool. (2) A pool shall be deemed to include: (c) (d) (e) (f) Permanently installed and storable swimming pools; and Hydromassage bathtubs; and Spas and hot tubs; and Wading pools; and Baptismal pools; and Decorative pools. (3) The requirements of this Section are supplementary to, or amendatory of, the general requirements of this Code. General Special Terminology In this Section the following definitions apply: Decorative pool means a pool that could be used as a wading pool, that is larger than 1.5 m in any dimension, and that is readily accessible to the public. Dry-niche luminaire means a luminaire intended for installation in the wall of the pool in a niche that is sealed against the entry of pool water by a fixed lens. Forming shell means a structure intended for mounting in a pool structure to support a wetniche luminaire assembly. Hydromassage bathtub means a permanently installed bathtub having an integral or remote water pump or air blower, and having a fill and drain water system, and includes therapeutic pools. Leakage current collector means a device designed to provide a path to ground for leakage current originating from devices in contact with pool water. Permanently installed swimming pool means a pool constructed in such a manner that it cannot be disassembled for storage.

2 Spa or hot tub means a pool or tub designed for the immersion of persons in heated water circulated in a closed system incorporating a filter, heater, pump, and with or without a motordriven blower but not intended to be filled and drained with each use. Storable swimming pool means a pool constructed in such a manner that it may be readily disassembled for storage and reassembled to its original integrity. Wet-niche luminaire means a luminaire intended for installation in a forming shell mounted in a pool structure where the luminaire will be completely surrounded by pool water Electrical Wiring or Equipment in Pool Walls or Water Electrical wiring or equipment shall not be installed in the walls nor in the water of pools except as permitted by this Section Overhead Wiring (see Appendix B ) (1) No pool shall be placed under or near overhead wiring and no overhead wiring shall be placed over or near a pool unless the installation complies with the requirements of this Rule. (2) There shall not be any overhead wiring above the pool, diving structure, observation stand, tower, or platform, or above the area extending 3 m horizontally from the pool edge except as permitted by Subrules (3) and (4). (3) Insulated communication conductors, communication antenna distribution conductors, and neutral supported cables not exceeding 750 V shall be permitted to be located over a pool, diving structure, observation stand, tower, or platform, or above the area extending 3 m horizontally from the pool edge, providing there is a clearance (measured radially) of at least 4.5 m. (4) Conductors other than those covered by Subrule (3) and operating at not more than 50 kv phase-to-phase shall be permitted to be located above a pool, diving structure, observation stand, tower, or platform, or above the area extending 3 m horizontally from the pool edge, providing there is a clearance (measured radially) of at least 7.5 m Underground Wiring The horizontal separation between the inside walls of a pool and underground conductors, except for bonding conductors or conductors supplying electrical equipment associated with the pool and protected by a ground fault circuit interrupter, shall be not less than that shown in Table Bonding to Ground (see Appendix B )

3 (1) The metal parts of the pool and of other non-electrical equipment associated with the pool such as piping, pool reinforcing steel, ladders, diving board supports, and fences within 1.5 m of the pool shall be bonded together and to non-current-carrying metal parts of electrical equipment such as decorative type pool luminaires and lighting equipment not located in a forming shell, forming shells, metal screens of shields for underwater speakers, conduit, junction boxes, and the like by a copper bonding conductor. (2) Pool reinforcing steel shall be bonded with a minimum of four connections equally spaced around the perimeter. (3) Notwithstanding Subrule (2), where reinforcing steel is encapsulated with a nonconductive compound, provisions shall be made for an alternative means to eliminate voltage gradients which would otherwise be provided by unencapsulated, bonded reinforcing steel. (4) Bonding conductors for pools shall be: Not smaller than No. 6 AWG for permanently installed pools and for all in-ground pools; or As required by Table 16 for all other pools. (5) Metal sheaths and raceways shall not be relied upon as the bonding medium and a separate copper bonding conductor shall be used, except that a metal conduit between a forming shell and its associated junction box shall be permitted to be used as the bonding medium providing the forming shell and junction box are installed in the same structural section. (6) The bonding conductor from the junction box referred to in Rule shall be run to the main distribution panelboard, and if smaller than No. 6 AWG shall be installed and mechanically protected in the same manner as the circuit conductors. (7) The bonding conductor in Subrule (4) shall be of copper and not smaller than that required by Table 16, except that the bonding conductor for an in-ground pool shall be not smaller than No. 6 AWG. (8) Notwithstanding Subrule (1), the metal parts of a pool need not be bonded to ground or to each other where the electrical equipment associated with the pool is: (c) Not located within 3 m of the pool; or Suitably separated from the pool by a fence, wall, or other barrier; or Approved without a bonding conductor Junction and Deck Boxes (see Appendix B ) (1) Junction boxes shall be permitted to be submerged in decorative pools provided the boxes are marked for such usage.

4 (2) Junction boxes installed on the supply side of conduits extending to forming shells, referred to hereinafter as deck boxes, shall be specifically approved for the purpose. (3) Deck boxes shall be provided with a means for independently terminating at least three bonding conductors inside the box and one No. 6 AWG bonding conductor outside the box. (4) Deck boxes shall not contain the conductors of any circuits other than those used exclusively to supply the underwater equipment. (5) Deck boxes shall be provided with electrical continuity between every connected metal conduit and the bonding terminals by means of copper, brass, or other corrosionresistant metal that is integral with the box. (6) Deck boxes shall be installed: (c) (d) Above the normal water level of the pool; and So that the top of the box is located at or above the finished level of the pool deck; and In such a manner or location that the box will not be an obstacle; and In such a manner that any water on the deck will drain away from the box. (7) Junction boxes and conduit shall be water-tight and provided with a packing seal that will seal around the cord and effectively prevent water from entering the box through the conduit from the forming shell Transformers and Transformer Enclosures (see Appendix B ) (1) Transformers shall not be located within 3 m of the inside wall of the pool unless suitably separated from the pool area by a fence, wall, or other permanent barrier that will make the transformer not accessible to persons using the pool area. (2) A metal shield, if provided between the primary and secondary windings of a transformer, shall be bonded to ground. (3) Audio isolation transformers shall: (c) Be connected between the audio output terminals of each amplifier and any loudspeaker that is located within 3 m of the pool wall; and Be located in or adjacent to the amplifier with which they are used; and Have an audio output voltage of not more than 75 V rms Receptacles (1) Receptacles shall not be located within 1.5 m of the inside walls of the pools. (2) Receptacles located between 1.5 m and 3 m of the inside walls of a pool shall be protected by a ground fault circuit interrupter.

5 (3) In maintaining the dimensions referred to in this Rule, the distance to be measured is the shortest path that the power supply cord of an appliance connected to the receptacle would follow without piercing a building floor, wall, or ceiling Luminaires and Lighting Equipment (1) Wet-niche or submersible luminaires shall: (c) Be mounted in forming shells that shall have provision for a suitable connection to the wiring method used; and Unless specifically approved and marked for submersion at a greater depth, not be submersed in the pool water at a depth of more than 600 mm, such distance being measured from the centre of the lens face of the luminaire to the normal water level; and Operate with neither the supply voltage to the luminaire nor its associated ballast or transformer, if applicable, nor the secondary open-circuit voltage of the ballast or transformer exceeding 150 V during either starting or operating conditions. (2) Notwithstanding Subrule (1), wet-niche or submersible luminaires installed in a decorative pool need not be mounted in a forming shell but shall have provision for a suitable connection to the wiring method used. (3) Where dry-niche luminaires are installed so as to be accessible from a walkway or a service tunnel outside the walls of the pool or from a closed, drained recess in the walls of the pool, neither the supply voltage to the fixture nor its associated ballast or transformer shall exceed 300 V during either starting or operating conditions. (4) Dry-niche luminaires shall be accessible for maintenance: From a service tunnel or walkway outside the walls of the pool; or Through a handhole in the deck of the pool to a closed, drained recess in the wall of the pool. (5) Metal parts of luminaires in contact with the pool water shall be of brass or other suitable corrosion-resistant material. (6) Luminaires installed below, or within 3 m of, the pool surface or walls, and not suitably separated from the pool area by a fence, wall, or other permanent barrier, shall be electrically protected by a ground fault circuit interrupter. (7) Standards or supports for luminaires shall not be installed within 3 m of the inside walls of a swimming pool unless such luminaires are protected by ground fault circuit interrupters. (8) Forming shells for lamps supplied from a grounded circuit or a circuit operating at a voltage exceeding 30 V shall be metal and have provision for a threaded connection to a rigid metal conduit.

6 Δ Ground Fault Circuit Interrupters (see Appendix B ) (1) Except as permitted in Subrule (2), ground fault circuit interrupters required by the Rules of this Section shall be of the Class A type. (2) Where ground fault circuit interrupters of the Class A type are not available due to rating, the equipment shall be permitted to be protected by a ground fault circuit interrupter that will clear a ground fault within the time specified for a Class A type interrupter. (3) Ground fault circuit interrupters shall be permanently connected. (4) Ground fault circuit interrupters shall be permitted to be applied to a feeder, a branch circuit, or an individual device. (5) A warning sign shall be located beside the switches controlling circuits electrically protected by ground fault circuit interrupters advising that the circuits are so protected and that the equipment shall be tested regularly. (6) Ground fault circuit interrupters shall be installed: In a location that will facilitate the testing required in Subrule (5); and Not closer than 3 m to the pool water except as permitted by Paragraph (c); and (c) Not closer than 3 m to the pool water in a spa or hot tub and not closer than 1.5 m to a hydromassage bathtub unless the ground fault circuit interrupter is an integral part of an approved factory-built spa, hot tub, or hydromassage bathtub or is located behind a barrier that will prevent the occupant of the pool from contacting the device. (7) Except as permitted by Rule , the following equipment shall be protected by a ground fault circuit interrupter: (c) Electrical equipment placed in the water in the pool; and Audio amplifiers connected to loudspeakers in the pool water; and Electrical equipment located within the confines of the pool walls or within 3 m of the inside walls of the pool and not suitably separated from the pool area by a fence, wall, or other permanent barrier; and (d) Receptacles located in wet areas of a building, and associated with the pool, such as locker and change rooms Other Electrical Equipment Loudspeakers installed beneath the pool surface: Shall be mounted in a recess in the wall or floor of the pool and shall be enclosed by a separate, rigid, corrosion-resistant metal screen; and Shall be connected to their audio isolating transformers by ungrounded wiring.

7 Permanently Installed Swimming Pools Wiring Method (1) Rigid conduit of copper or other corrosion-resistant metal or rigid PVC conduit shall be provided between the forming shell of luminaires installed below the pool surface and the junction box referred to in Rule (2) The wiring method between the wet-niche luminaires and the junction boxes referred to in Rule shall be flexible cord suitable for use in wet locations and supplied as a part of the luminaire. (3) Where Subrules (1) and (2) do not apply, any suitable wiring method specified in Section 12 shall be permitted to be used. (4) Conductors on the load side of each ground fault circuit interrupter shall be kept entirely independent of all other wiring that is not so protected and shall not enter a luminaire, raceway, box, or cabinet occupied by other wiring except for panelboards that house the interrupters. (5) Conduits in the walls and deck of a swimming pool shall be installed so that suitable drainage is provided. Storable Swimming Pools Electrical Equipment No electrical equipment shall be located in the pool water or on the pool wall unless specifically approved for the purpose Pumps (1) Swimming pool pumps shall be: Supplied from a permanently installed receptacle located not less than 1.5 m nor more than 7.5 m from the pool wall; and Protected by a ground fault circuit interrupter if located within 3 m of the inside walls of the pool and not suitably separated from the pool area by a fence, wall, or other permanent barrier. (2) Swimming pool pumps located within 3 m of the pool walls shall be specifically approved for the purpose. Hydromassage Bathtubs Protection

8 Electrical equipment forming an integral part of a hydromassage bathtub shall be protected by a ground fault circuit interrupter of the Class A type Control (1) A hydromassage bathtub shall be controlled by an on-off device located in accordance with Subrule (2). (2) Electric controls associated with a hydromassage bathtub shall be located behind a barrier or shall be located not less than 1 m horizontally from the wall of the hydromassage bathtub, unless they are an integral part of an approved factory-built hydromassage bathtub Other Electric Equipment Luminaires, switches, receptacles, and other electrical equipment not directly associated with a hydromassage bathtub shall be installed in accordance with the Rules of this Code covering the installation of that equipment in bathrooms. Spas and Hot Tubs General Rules to apply to the installation of spas and hot tubs Bonding to Ground (1) Metal parts of spas and hot tubs shall be bonded together and to ground in accordance with Rule (2) Notwithstanding Subrule (1), metal rings or bands used to secure staves of wooden hot tubs need not be bonded Controls and Other Electrical Equipment (1) Controls for a spa or hot tub shall be located behind a barrier or shall be located not less than 1 m horizontally from the spa or hot tub, unless they are an integral part of an approved factory- built spa or hot tub. (2) Receptacles shall be installed in accordance with Rule (3) Luminaires shall be installed in accordance with Rule Leakage Current Collectors (1) Leakage current collectors shall be installed in all water inlets and in all water outlets of a field- assembled spa or hot tub so that all water flows through the leakage current collectors.

9 (2) A leakage current collector shall be: A section of corrosion-resistant metal tubing at least five times as long as its diameter, provided with a corrosion-resistant lug, in a run of nonmetallic pipe; or A device providing equal protection as in Paragraph when it is an integral part of a spa or hot tub that is factory built for field installation or assembly. (3) Leakage current collectors shall be electrically insulated from the spa or hot tub and shall be bonded to the control panel or the main service ground with a copper bonding conductor. (4) Notwithstanding Subrule (1), leakage current collectors shall not be required in a system in which the only electrical component is a pump marked as an insulated wet end pump. (5) The bonding conductor for leakage current collectors shall be not smaller than required by Table 16 where the bonding conductors are mechanically protected in the same manner as the circuit conductors, or a minimum No. 6 AWG copper conductor Field-Assembled Units (see Appendix B ) (1) Spas and hot tubs field assembled with individual components shall be installed in accordance with Rules to and Subrules (2) and (3). (2) Individual components, such as pumps, heaters, and blowers, shall be specifically approved for use with spas or hot tubs. (3) Air blowers shall be installed above the tub rim, or other means used to prevent water from contacting blower live parts. ***************************************************************************** BULLETIN April 1999 Bonding Galvanized Metal Pool Shells Rule (page 228) Questions have arisen concerning the bonding of galvanized steel shells for swimming pools where the sides or sides and bottom are fabricated using galvanized sheet steel. Rule requires (1) The metal parts of the pool and of other non-electrical equipment associated with the pool such as piping, pool reinforcing steel, ladders, diving board supports, and fences within 1.5 m of the pool shall be bonded together and to non-current-carrying metal parts of electrical equipment such as decorative type pool luminaires and lighting equipment not located in a forming shell, forming shells, metal screens of shields for

10 underwater speakers, conduit, junction boxes, and the like by a copper bonding conductor. (2) Pool reinforcing steel shall be bonded with a minimum of four connections equally spaced around the perimeter. A continuous galvanized steel shell made up of individual panels securely bolted together need not be bonded in four places. (bonding to ground may be required as per Rule ) As with other pools: All deck boxes, ladder pockets drains and other exposed metal parts are to be bonded to the pool shell as in Rule (1) (above). The deck box or junction box is to be bonded to the supply panelboard as in Subrules (5) and (6). Please note that the bonding conductor required by Subrule (5) may be a separate AWG No. 6 conductor or may be smaller than No. 6 if installed and mechanically protected in the same manner as circuit conductors. Rationale: The purpose of Rule is to ensure there is an equipotential shell surrounding a pool to divert unwanted stray currents. A galvanized steel shell, interconnected together, is considered as providing that shell. Notwithstanding the above, the metal parts of a pool need not be bonded to ground or to each other where the electrical equipment associated with the pool is: (c) Not located within 3 m of the pool; or Suitably separated from the pool by a fence, wall, or other barrier; or Approved without a bonding conductor. Rule (7) Appendix B (page 480) Note: Even though no electrical equipment is located within 3m of a pool, it is recommended that metal parts of an in-ground pool be interconnected with a minimum No. 6 AWG copper conductor. This guards against the effects of stray currents in the ground and reduces the cost of meeting CE Code requirements should electrical equipment be added later ***************************************************************************** BULLETIN December 2006 Supercedes Bulletin June 2005 Swimming Pool, Hot Tub and Spa Installations Section 68

11 Pool installers, Electricians, and Electrical Inspectors in interpreting and applying Section 68 of the Ontario Electrical Safety Code have asked the following questions. The answers are based on the Code in the interest of consistency and have been organized in the following categories: General, Grounding & Bonding, Wiring Methods, Protection & Control, GFCI protection, Pool & Spa Emergency Stop Controls and Cord-connected Hydromassage Bathtubs. 1. General 1.1 Does Section 68 apply to both in ground and above ground pools? Yes, the Code does not differentiate between in-ground and above-ground pools. Subrule (2) lists the types of pools that are included in the scope of Section Grounding & Bonding 2.1 Do the requirements of Rule "Bonding to Ground" apply to above-ground pools as well as in-ground pools (where there is electrical equipment within 3m)? Yes. Rule talks about "pools", which include any of the items in (2) thru (f). 2.2 Does the Code require bonding of metal pool parts if there is no electrical equipment within 3m of the pool? No, Rule (7) provides an exception, however the App B note to this Rule still recommends bonding of metal parts for all in ground pools even where there are no electrics near the pool The App B note to Rule states: Even though no electrical equipment is located within 3 m of a pool, it is recommended that metal parts of an in-ground pool be interconnected with a minimum No. 6 AWG copper conductor. This guards against the effects of stray currents in the ground and reduces the cost of meeting CE Code requirements should electrical equipment be added later. 2.3 What is the minimum size of conductor required for bonding together the metal pool parts and for bonding from the electrical equipment back to the distribution panel? The minimum size of bonding conductor joining metal parts and pieces together shall be No. 6 AWG copper. The minimum size of bonding conductor from electrical equipment (lights, receptacles, pump motors, deck boxes, etc) to the distribution panel shall be as per Table 16 (where the bonding conductor is incorporated within a cable assembly or raceway).

12 2.4 If a pool pump is GFCI protected due to the distance from the pool, does the pool need a No. 6 AWG ground which would ground the pool, the ladder pegs and the diving board hardware? Yes. Rule requires the pump to be GFCI protected if located within 3 m of the inside walls of the pool, unless suitably separated Rule states where there is electrical equipment located within 3 m of the pool (in this case the pump), all metal parts of the pool and other non-electrical equipment associated with the pool shall be bonded together and to the metal non-current carrying parts of electrical equipment with minimum No. 6 AWG copper wire. 2.5 Can the split bolts or ground lugs be aluminum? No. In this case any split bolts or ground lugs located underground shall be approved for earth burial. Components located outdoors shall be approved as suitable for wet locations Rule requires approved electrical equipment of a kind or type and rating approved for the specific purpose for which it is to be employed. 2.6 At how many points does the pool frame need to be grounded? Rule requires concrete pool-reinforcing steel to be bonded with a minimum of four connections equally spaced around the perimeter Note: A galvanized steel pool shell made up of individual panels securely bolted together need only be bonded in one location in accordance with Bulletin 68-6-*. 2.7 If a 120 or 240V device is existing on or around the house, must it be at least 3 m from the pool or that so called device would require a GFCI breaker and the pool grounded? Yes, the device would require GFCI protection and the metal pool parts would require bonding as per the rationale in the answer to question 2.4 or the device may be suitably separated from the pool area by a fence, wall, or other permanent barrier. 2.8 At what point does a metal fence require grounding? Rule requires metal fences within 1.5 m of the inside walls of the pool to be bonded. 2.9 If an existing 120 or 240V device within 3 m of pool is changed to a GFCI due to Code, does the pool frame need to be grounded? Yes, as per the answer to question If not, why? It is metal just as in ground?

13 As stated in 2.4 above, the metal shell or frame of an above ground pool shall be bonded to other metal equipment associated with the pool, if there is electrical equipment within 3 m of the pool walls At what point do we need to attach a ground to a gas pipe outdoor? If the gas pipe is metal and is associated with the pool and is within 1.5 m of the inside walls of the pool it shall be bonded If so, why is this necessary when only 2 ft at each end is metal, the underground part is plastic and the gas installer has ran his own #12 ground from one end to the other? As per above Does the Code require bonding in four places of a metal shell type pool? No, see Bulletin 68-6-* Does Rule require bonding of the metal covers of pool drains where the drain body is of non-metallic material? No. The cover does not have provision for bonding and it is not practicable to do so. The cover is a minor metal item not a large item as described in the Rule "non-electrical equipment associated with the pool such as piping, pool reinforcing steel, ladders, diving board supports, and fences". The cover is mounted on non-conductive material and does not have a reference to remote earth. 3. Wiring Methods 3.1 Is it acceptable that an NMD7 conductor of any size be inserted in a PVC underground conduit? No, Rule states raceways installed underground or in concrete slabs in direct contact with moist earth shall comply with Section 22 Rules for Category 1 locations Rule requires individual conductors and non-metallic sheathed cables in Category 1 areas to be suitable for use in wet locations. Non-metallic sheathed cables shall be of the NMW or NMWU type NMD7 or NMD-90 non-metallic sheathed cable is suitable for use only in dry or damp locations. 3.2 Is it acceptable that an NMD7 conductor of any size be inserted in a surface mounted PVC conduit such as along the brick wall of a house? Yes, PVC raceway installed above grade is considered a dry or damp location.

14 3.2.2 Note: where PVC raceway passes through a wall from a warm area to a cold area (interior to exterior of house) it shall be sealed to prevent condensation in the raceway. Rule If we drop PVC conduit in an 18 trench and after leaving site the gas installer lays his pipe along side, does the electrical code point at the Electrical Contractor to make it right? No. Provided the electrical portion of the installation was Code compliant, it would be the gas portion that would be in violation of the Code and it would be the gas installer s responsibility to correct any deficiency If so, due to the uncertainty of who got there first, how is this dealt with? Would ESA take measures to contact gas installer? Normally ESA would issue the deficiency to the holder of the application for electrical inspection. If the deficiency was as a result of work by others, the electrical permit holder should advise both ESA and the other party With an above ground pool, is there a distance that the underground PVC conduit travel near pool? Rule does not differentiate between above and in-ground pools If the PVC raceway is supplying equipment directly related to the pool (pump, lighting, etc) and the circuit is GFCI protected, there is no minimum separation required If a PVC raceway is supplying non-pool related equipment, it must be kept separated from the inside walls of the pool by the distances specified in Table 61. These are as follows: Table 61 Direct buried Buried in raceway Communication and CATV 1.5 m.75 m Electrical Conductors Volt Electrical Conductors ,000 V Electrical Conductors 15,001 25,000 V Protection & Control 4.1 Does any outdoor electric device require a separate shut off if it has controls on it that do so? It depends on the device (what it is) and the type of controls it has. In general any equipment containing a motor shall have disconnecting means in accordance with Rules , and GFCI Protection

15 5.1 If a pool pump is within 3 m of the pool, does it have to be GFCI protected if a wall or suitable barrier is installed? No, Rule does not require GFCI protection of electrical equipment that is located further than 3 m from the inside walls of a pool, or that is suitably separated from the pool area by a fence, wall, or other permanent barrier Note: If the pump were cord connected to a receptacle, Rule requires all receptacles located outdoors of a single dwelling to be protected by a ground fault circuit interrupter of the Class A Type. In this case it wouldn t matter if the pump were located further than 3 m. 5.2 Is there any specification on this wall or barrier? Rule requires a fence, wall, or other permanent barrier. The intent is the barrier prevents an occupant of the pool area from contacting the electrical equipment unless it is GFCI protected In order to assess compliance with the Rule, a 3 m piece of string with one end held at the edge of the pool should not be able to reach the electrical equipment by going around the barrier or through a door or gate in the barrier The barrier should not have any openings or gaps that would permit a person to reach through and contact the equipment. 5.3 If a 120 or 240 V device is existing on or around the house, must it be at least 3 m from the pool or that so called device would require a GFCI breaker and the pool grounded? Yes, the device would require GFCI protection and the metal pool parts would require bonding as per the rationale in the answer to question If an existing 120 or 240 V device within 3 m of pool is changed to a GFCI due to Code, does the pool frame need to be grounded? Yes, as per the answer to question If not, why? It is metal just as in ground? As stated in 2.4 above, the metal shell or frame of an above ground pool shall be bonded to other metal equipment associated with the pool, if there is electrical equipment within 3 m of the pool walls. 5.5 Is it acceptable to install a GFCI outlet and not a breaker for the plug in pump of an above ground pool? If the receptacle were further than 3 m form the pool, a GFCI outlet would be permissible.

16 5.5.2 Rule does not permit a receptacle to be located closer than 1.5 m to the pool. Rule does not permit the GFCI protection to be closer than 3 m to the pool. 5.6 Where a portable (storable) pump motor is located within 1.5 m of a pool does the Code permit the use of a GFCI type receptacle next to the pump? No. Rule permits a receptacle to be located not closer than 1.5 m to the pool, however Rule requires the GFCI to be not closer than 3 m to the pool. The GFCI protection for the receptacle would have to be located further than 3 m from the pool. 6 Pool & Spa Emergency Stop Controls The emergency shutoff switch shall be installed for each spa or hot tub except for a dwelling unit. The emergency shutoff switch is Ontario Building Code requirement for public spa. 6.1 Remote, extra low voltage, or pneumatic controls are not considered as Code compliant disconnecting means. The emergency shutoff switch shall: disconnect the motors supplying power to the closed water circulating systems: is independent of the controls for a spa or hot tub; is located at a point readily accessible to the users and within sight of and within 15m of the spa or hot tub; is labeled in a conspicuous, legible, and permanent manner identifying it as the emergency shutoff switch; and is equipped with audible and visual trouble-signal devices that give immediate warning upon actuation of the emergency shut off switch This would be accompanied by an emergency sign posted adjacent to the emergency stop button containing the words IN THE EVENT OF AN EMERGENCY PUSH EMERGENCY STOP BUTTON AND USE EMERGENCY PHONE, AUDIBLE AND VISUAL SIGNAL WILL ACTIVATE. NOTE: Rule requires controls for a spa or hot tub to be located behind a barrier or not less than 1 m horizontally from the spa or hot tub unless they are an integral part of an approved factory built unit. 6.2 Is GFCI protection required if the Estop is extra low voltage, 24 V, etc? The mandatory Electrical Code GFCI requirements apply to any Estop located within 3 m of a pool or tub as per Rule (7) irrespective of voltage.

17 6.2.2 NOTE: Where the emergency shut off switch is GFCI protected, the emergency shut off circuit shall be connected such that tripping of the GFCI protector shall also cause the pump motor to stop. 6.3 Is an Estop for an existing public pool, supervised location permitted to be located inside the life guard control room or must it be located at the pool deck? The Ontario Building Code Clause defines a "public pool". Clause (12), (13), (14) provides the requirements for Estop with the location being dependant on classification of the pool (A or B as defined in the Building Code). Advise the customer to seek advice from building officials for this question, as it is an Ontario Building Code issue. 7 Cord-connected Hydromassage Bathtubs OESC Rule requires electrical equipment forming an integral part of a hydromassage bathtub to be protected by a ground fault circuit interrupter of the Class A type. This Code Rule applies to permanently and cord connected hydromassage bathtubs. Where a cord-connected hydromassage bathtub, spa or hot tub is intended to be installed: 7.1 the receptacle located at not less than 300 mm from the floor shell be provided for the use with the hydromassage bathtub; and 7.2 the receptacle shall be inaccessible to the hydromassage bathtub occupant 7.3 The warning label shall be affixed to the receptacle. The warning label is intended to warn against and prevent the connection of any other equipment to the receptacle. 7.4 A warning label is not required where a single receptacle is used.

SWIMMING POOLS CHAPTER 41

SWIMMING POOLS CHAPTER 41 CHAPTER 41 SWIMMING POOLS SECTION E4101 GENERAL E4101.1 Scope [Section 680.1]. The provisions of this chapter shall apply to the construction and installation of electric wiring and equipment associated

More information

ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS:

ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS: ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS: Chapter 12 of the Burlington Code of ordinances allows owner occupants of single family homes to do their own wiring if they choose. If you choose to

More information

Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016. Underground branch circuit feeding a detached garage:

Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016. Underground branch circuit feeding a detached garage: Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016 * Garage construction requires permits (electrical, building) * Permits must be applied for at the time. * Dial

More information

GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264

GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264 BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used

More information

RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS:

RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS: RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS: Signed completed Electrical Permit application form. Minnesota law requires all electrical work is to be performed by licensed,

More information

Questions and Answers for Heating and A/C Contractors

Questions and Answers for Heating and A/C Contractors 1. How do we accomplish grounding of furnaces and / or water heaters on two wire circuits? 250.134 Equipment Fastened in Place or Connected by Permanent Wiring Methods (Fixed) Grounding. Unless grounded

More information

Electrical Grounding. Appendix C

Electrical Grounding. Appendix C Appendix C Electrical Grounding Low-Voltage Equipment Grounding The most frequently cited Office of Safety and Health Administration (OSHA) electrical violation is improper occupational grounding of equipment

More information

2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property

2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property 2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property A brief summary of the most used code references for residential wiring State of Idaho Division of Building Safety Electrical

More information

GUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS

GUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS GUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS This guideline has been prepared to assist the owner/occupant of a single family dwelling with compliance to the requirements of the National Electrical

More information

PLEASE NOTE. For more information concerning the history of these regulations, please see the Table of Regulations.

PLEASE NOTE. For more information concerning the history of these regulations, please see the Table of Regulations. PLEASE NOTE This document, prepared by the Legislative Counsel Office, is an office consolidation of this regulation, current to August 1, 2013. It is intended for information and reference purposes only.

More information

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations. DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,

More information

Residential Electrical Inspection. Checklist

Residential Electrical Inspection. Checklist 443 Lafayette Road N. St. Paul, Minnesota 55155 www.doli.state.mn.us Residential Electrical Inspection (651) 284-5064 1-800-DIAL-DLI Fax: (651) 284-5743 TTY: (651) 297-4198 Checklist Generally, Minnesota

More information

Top Commercial / Residential Electrical Requirements *

Top Commercial / Residential Electrical Requirements * Department of Community Development Building Division 4800 West 92 nd Avenue Westminster, Colorado 80031 For Information call (303) 658-2075 Fax (303) 706-3922 www.westminsterpermits.com Top Commercial

More information

SWIMMING POOL, SPA, & HOT TUB GUIDELINES

SWIMMING POOL, SPA, & HOT TUB GUIDELINES SWIMMING POOL, SPA, & HOT TUB GUIDELINES Pool permit cost is based on the total value of the project. See Permit Fee Schedule Table 1A. A. Adopted construction codes and installation requirements 1. 2015

More information

Ontario Electrical Safety Code 25 th Edition/ 2012

Ontario Electrical Safety Code 25 th Edition/ 2012 Ontario Electrical Safety Code 25 th Edition/ 2012 Ted Olechna Director, Codes and Standard Chief Engineer 1 What I Will Cover ESA s role is as the regulator Highlight of 2012 Code changes The Code and

More information

ELECTRICAL SAFETY Information Bulletin

ELECTRICAL SAFETY Information Bulletin ELECTRICAL SAFETY Information Bulletin January 2016 CEC-10 [rev-9] Page 1 of 8 CANADIAN ELECTRICAL CODE SUBJECT: Section 10 Grounding and Bonding Rule 10-204 Grounding Connections for Alternating-Current

More information

INSPECTION GUDELINES

INSPECTION GUDELINES GENERAL REQUIREMENTS Building permit and approved set of plans Building permit on the card is the same as on the route "If this is not the first inspection, read inspection records and notes on permit

More information

Residential Electrical Inspection Checklist

Residential Electrical Inspection Checklist Residential Electrical Inspection Checklist Based on the 2008 National Electrical Code Generally, Minnesota law requires all electrical work to be performed by licensed, bonded and insured electrical contractors

More information

Significant Changes in the 2011 NEC Prepared by Bryan Holland City of North Port

Significant Changes in the 2011 NEC Prepared by Bryan Holland City of North Port Significant Changes in the 2011 NEC Prepared by Bryan Holland City of North Port Code-Wide Code Change Section 90.5(C). Fine Print Notes are now referred to as "Informational Notes." The purpose, intent,

More information

EARTHING AND BONDING AT SECONDARY SUBSTATIONS

EARTHING AND BONDING AT SECONDARY SUBSTATIONS DISTRIBUTION CONSTRUCTION MANUAL SECTION 4 - SUBSTATIONS ISSUE B SEPT 1996 4.4.4 EARTHING AND BONDING AT SECONDARY SUBSTATIONS 1 SCOPE This section of the Distribution Construction Manual lays down the

More information

ELECTRICAL INSPECTION BULLETIN (Effective 2000-03-01)

ELECTRICAL INSPECTION BULLETIN (Effective 2000-03-01) ELECTRICAL INSPECTION BULLETIN (Effective 2000-03-01) Rule 28-900 Standby Generator Installations Due to the increasing number of standby generator installations being established to maintain continuity

More information

Grounding & Bonding Why it is done And How to Install Properly

Grounding & Bonding Why it is done And How to Install Properly Grounding & Bonding Why it is done And How to Install Properly The technical information provided herein is to assist qualifi ed persons in planning and installing electric service to farms and residences.

More information

Residential Electrical Inspection. Checklist

Residential Electrical Inspection. Checklist Electrical Licensing and Inspection 443 Lafayette Road North St. Paul, Minnesota 55155-4342 www.doli.state.mn.us 651-284-5064 Fax: 651-284-5743 TTY: 651-297-4198 1-800-DIAL-DLI Residential Electrical Inspection

More information

CHAPTER 4 UTILITY SYSTEMS ELECTRICAL. Utility Systems Electrical. Main Panel

CHAPTER 4 UTILITY SYSTEMS ELECTRICAL. Utility Systems Electrical. Main Panel CHAPTER 4 UTILITY SYSTEMS ELECTRICAL Utility Systems Electrical The electrical supply to your home begins outside, where you will see either an overhead feed and piping down the side of your home or (if

More information

POOL AND SPA REQUIREMENTS

POOL AND SPA REQUIREMENTS Submittal Requirements: Permit Application (2) Plot plans with setbacks provided Original pool affidavid signed & marked (1) Set of Engineered steel reinforcement plans POOL AND SPA REQUIREMENTS PERMITS

More information

GENERAL ELECTRICAL REQUIREMENTS

GENERAL ELECTRICAL REQUIREMENTS GENERAL ELECTRICAL REQUIREMENTS RECEPTACLE SPACING Within 6-feet of the edge of any door HABITABLE Not more than 12-feet apart along wall ROOMS: At all wall spaces 24 or more wide Within 24 of edge of

More information

800 Communications Circuits

800 Communications Circuits ARTICLE 800 Communications Circuits INTRODUCTION TO ARTICLE 800 COMMUNICATIONS CIRCUITS This article has its roots in telephone technology. Consequently, it addresses telephone and related systems that

More information

GENERAL WIRING RULES FOR HOUSES

GENERAL WIRING RULES FOR HOUSES GENERAL WIRING RULES FOR HOUSES 1. Romex has to be installed in drilled holes in joists or studs even above suspended ceilings - No stapling to bottom edges of joists or studs. You may staple wire to flat

More information

Homeowner Information Guide Electrical Safety. British Columbia Safety Authority

Homeowner Information Guide Electrical Safety. British Columbia Safety Authority Homeowner Information Guide Electrical Safety British Columbia Safety Authority The following information should be carefully reviewed before performing any electrical work. The information contained in

More information

ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST

ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST Name of School: OPTIONAL INFORMATION Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST Guidelines: This checklist

More information

ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS

ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS Prepared by: ABB1 ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS 052521 Asset Type: Electric Metering Function: Construction Issued by: Quoc Hoang (QxH1) Date: 07-01-16 Rev. #06: This document

More information

MISCELLANEOUS ELECTRICAL JOBS REQUIRING PERMITS

MISCELLANEOUS ELECTRICAL JOBS REQUIRING PERMITS MISCELLANEOUS ELECTRICAL JOBS REQUIRING PERMITS 01. SAFETY INSPECTION of service equipment at FPL Power Source 02. Construction GFI power outlets (Temp Pole for Construction) 03. 90 day temporary power

More information

How To Keep An Eye On Electric Safety

How To Keep An Eye On Electric Safety Table of Contents Keep an Eye on Electric Safety................ 1 Safety in an Emergency...................... 1 Downed Power Lines...................... 1 Keep an Eye on Electric Safety Electricity is

More information

SWIMMING POOL HEAT PUMP

SWIMMING POOL HEAT PUMP SWIMMING POOL HEAT PUMP Installation & User Manual Model HP40B HP50B HP65B Hayward Pool Products Canada, Inc. T: 1-888-238-7665 www.haywardpool.ca CONTENT I. Application 4 II. Features 4 III. Technical

More information

A TO Z HOME INSPECTIONS PROFESSIONAL HOME INSPECTION SERVICES FOR HOME BUYERS AND SELLERS

A TO Z HOME INSPECTIONS PROFESSIONAL HOME INSPECTION SERVICES FOR HOME BUYERS AND SELLERS A TO Z HOME INSPECTIONS PROFESSIONAL HOME INSPECTION SERVICES FOR HOME BUYERS AND SELLERS Insurance Inspection Report 1234 Main Street Tallahassee, Florida Report Prepared For: Charles Smith Report Prepared

More information

Hyperlinks are Inactive

Hyperlinks are Inactive Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)

More information

INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1

INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1 City of Cotati Building Division 201 W. Sierra Ave. Cotati, CA 94931 707 665-3637 Fax 792-4604 INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1 Any PV system on a new structures should be included

More information

October Safety Subject

October Safety Subject October Safety Subject Electrical Hazards All electrical equipment should be kept in good repair. Replace defective equipment or have it repaired by a qualified person. Watch for wiring on appliances that

More information

Marking Guide. Swimming Pool Equipment, Spas, Fountains and Hydromassage Bathtubs

Marking Guide. Swimming Pool Equipment, Spas, Fountains and Hydromassage Bathtubs Swimming Pool Equipment, Spas, Fountains and Hydromassage Bathtubs April 2008 Copyright 2008, Underwriters Laboratories Inc. 142-04/2008 The growing popularity of home swimming and related activities has

More information

Listed are common requirements that apply to existing solar installations when altered, added to or reconfigured.

Listed are common requirements that apply to existing solar installations when altered, added to or reconfigured. SOLAR ALTERATIONS REQUIREMENTS August 2015 These requirements address typical alterations to solar installations; they cannot address every scenario. In Victoria, an alteration to a solar installation

More information

Electrical Practices for Construction Work

Electrical Practices for Construction Work 1. Purpose Electrical Practices for Construction Work The purpose of this Code is to provide practical guidance and set minimum safety requirements for electrical practices on all construction sites in

More information

Electrical Code Regulation

Electrical Code Regulation Electrical Code Regulation St. Clair County has adopted the 2005 National Electrical Code in its entirety for the unincorporated areas of the county and all communities that have contracted with the county

More information

2. What building projects are exempted? (permit not required)

2. What building projects are exempted? (permit not required) BUILDING AND SAFETY DEPARTMENT 1. What building projects require a permit? Following is a list of projects that require building permits based on Appendix chapter 1 of the California Building Code and

More information

Solar Panel Installations

Solar Panel Installations Solar Panel Installations Page 1 of 6 SINGLE-FAMILY RESIDENTIAL CHECKLIST City of Hayward Development Services Department Revised: 7-09-15 PERMIT REQUIREMENTS Permits are required for all solar panel installations.

More information

Requirements for Electrical Installations

Requirements for Electrical Installations ARTICLE 110 Requirements for Electrical Installations INTRODUCTION TO ARTICLE 110 REQUIREMENTS FOR ELECTRICAL INSTALLATIONS Article 110 sets the stage for how you ll implement the rest of the NEC. This

More information

MA BUILDING CODES ON SWIMMING POOLS SECTION 780 CMR 120.M

MA BUILDING CODES ON SWIMMING POOLS SECTION 780 CMR 120.M MA BUILDING CODES ON SWIMMING POOLS SECTION 780 CMR 120.M APPENDIX 120.M SWIMMING POOLS, SPAS AND HOT TUBS SECTION 120.M101 GENERAL 120.M101.1 General. The provisions of this appendix shall control the

More information

NEC 2014 Code Changes

NEC 2014 Code Changes NEC 2014 Code Changes Articles 400-408.55 CHANGES FROM 2011 TO 2014 CODE ARE IN RED Chapter 4 Equipment for General Use ARTICLE 400 Flexible Cords and Cables 400.4 Types Flexible cords and flexible cables

More information

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D 12 - ELECTRIC SERVICE HANDBOOK SECTION D METER REQUIREMENTS This chapter gives you information on Central Lincoln s metering requirements. It's divided into three sections: General requirements This section

More information

SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings

SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings *** Provide this document to the inspector along with ALL system installation instructions *** Project Address: Scope: Standard plan for the installation of grounded microinverter solar PV systems, not

More information

The National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables

The National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables The National Armored Cable Manufacturers Association Presents Installation Standard for Types AC and MC Cables An ANSI Standard Original document jointly produced by NECA and NACMA as Standard for Installing

More information

Electrical Wiring Methods, Components and Equipment for General Use. Approved for Public Release; Further Dissemination Unlimited

Electrical Wiring Methods, Components and Equipment for General Use. Approved for Public Release; Further Dissemination Unlimited Electrical Wiring Methods, Components and Equipment for General Use Approved for Public Release; Further Dissemination Unlimited At the completion of this unit you shall be able to: 1. Utilize section

More information

ELECTRICAL PRACTICES FOR CONSTRUCTION WORK

ELECTRICAL PRACTICES FOR CONSTRUCTION WORK CONTRACTOR S CHECKLIST ELECTRICAL PRACTICES FOR CONSTRUCTION WORK 2007 WorkCover. Watching out for you. New South Wales Government Disclaimer This publication contains information regarding occupational

More information

Charter Township of Shelby Harry Reese Building Director

Charter Township of Shelby Harry Reese Building Director Charter Township of Shelby Harry Reese Building Director Phone: (586) 731-5969 52700 Van Dyke Fax: (586) 803-2099 Shelby Township, MI 48316-3572 E-mail: building@shelbytwp.org OUTLINE PROCEDURES FOR PRIVATE

More information

First Published in The Wichita Eagle on January 2, 2015 ORDINANCE NO. 49-897

First Published in The Wichita Eagle on January 2, 2015 ORDINANCE NO. 49-897 OCA #230100 First Published in The Wichita Eagle on January 2, 2015 ORDINANCE NO. 49-897 AN ORDINANCE AMENDING SECTIONS 4.A.080, 4.1.020, 4.1.110, 4.2.010, 4.2.070, 4.2.125, 4.2.170, 4.2.175 AND 4.2.220;

More information

Electrical Installations A homeowner guide to the Winnipeg Electrical By-law requirements for a Single Family Dwelling, Detached Garage or Shed.

Electrical Installations A homeowner guide to the Winnipeg Electrical By-law requirements for a Single Family Dwelling, Detached Garage or Shed. PLANNING, PROPERTY AND DEVELOPMENT DEPARTMENT Electrical Installations A homeowner guide to the Winnipeg Electrical By-law requirements for a Single Family Dwelling, Detached Garage or Shed. October 2015

More information

COMPREHENSIVE PROPERTY INSPECTIONS

COMPREHENSIVE PROPERTY INSPECTIONS COMPREHENSIVE PROPERTY INSPECTIONS Thank you for selecting CPI for your Deficiency Observation. A full home inspection was not performed on this property at the buyers request. This inspection is a limited

More information

Trial Exams C. Standards and Regulations. Examination No: GH-08-C- 1 hour and 5 minutes plus 10 minutes reading time

Trial Exams C. Standards and Regulations. Examination No: GH-08-C- 1 hour and 5 minutes plus 10 minutes reading time Trial Exams C Standards and Regulations Examination No: GH-08-C- This test is intended to gauge your knowledge of essential information contained within AS/CA S009:2013. To qualify for an allpication to

More information

2012 Canadian Electrical Code, Part I (CEC) Top Fifteen changes

2012 Canadian Electrical Code, Part I (CEC) Top Fifteen changes 2012 Canadian Electrical Code, Part I (CEC) Top Fifteen changes 1) Tamper resistant receptacles. 2009 CEC Required in dwelling units 2012 CEC Expanded to child care facilities First introduced in the 2009

More information

ELECTRICAL REQUIREMENTS Specific Information for Electrical Work Installers

ELECTRICAL REQUIREMENTS Specific Information for Electrical Work Installers ELECTRICAL REQUIREMENTS Specific Information for Electrical Work Installers This handout is intended to be a general overview of residential electrical requirements as noted in the 2014 National Electrical

More information

Crawford Inspection Services C.C.B. # 76914 www.crawfordinspections.com

Crawford Inspection Services C.C.B. # 76914 www.crawfordinspections.com Crawford Inspection Services C.C.B. # 76914 www.crawfordinspections.com Portland Area PO Box 665 West Linn, OR 97068 Ph: (503) 650-6957 Salem Area 5434 River Rd. N; #192 Keizer, OR 97303 Ph: (503) 362-5809

More information

Thermal Imaging for Home Inspectors

Thermal Imaging for Home Inspectors Thermal Imaging for Home Inspectors Structural member placement The gabled end of a cathedral ceiling. Note the studs and the ceiling joists with blocking. What is that glow in the upper right hand corner?

More information

ADOPTION OF THE NATIONAL ELECTRICAL CODE, 2005

ADOPTION OF THE NATIONAL ELECTRICAL CODE, 2005 ADOPTION OF THE NATIONAL ELECTRICAL CODE, 2005 That a certain code, three (3) copies of which are now on file and have been on file for a period of not less than 21 days in the office of the Village Clerk

More information

AMERBRITE UNDERWATER WHITE LED POOL LAMP

AMERBRITE UNDERWATER WHITE LED POOL LAMP AMERBRITE UNDERWATER WHITE LED POOL LAMP FOR USE ONLY WITH PENTAIR AMERLITE LUMINAIRE INSTALLATION AND USER S GUIDE IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS

More information

**ATTENTION** WE DO NOT PROMOTE OR ENCOURAGE YOU TO DO YOUR OWN ELECTRICAL WIRING!!! IT IS BY FAR THE MOST DANGEROUS THING YOU CAN ATTEMPT

**ATTENTION** WE DO NOT PROMOTE OR ENCOURAGE YOU TO DO YOUR OWN ELECTRICAL WIRING!!! IT IS BY FAR THE MOST DANGEROUS THING YOU CAN ATTEMPT **ATTENTION** WE DO NOT PROMOTE OR ENCOURAGE YOU TO DO YOUR OWN ELECTRICAL WIRING!!! IT IS BY FAR THE MOST DANGEROUS THING YOU CAN ATTEMPT. YOU COULD PUT YOUR FAMILY AND WORLDLY POSSESSIONS IN DANGER!!!

More information

City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov

City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov PHOTOVOLTAIC PERMITTING GUIDELINES The information provided in this document is general and is intended only as a

More information

BASIC NEC CODE RULES AND DESIGN PRACTICE

BASIC NEC CODE RULES AND DESIGN PRACTICE BASIC NEC CODE RULES AND DESIGN PRACTICE Wire Ampacity and Size Circuit Breaker Size 1. Maximum loading for any branch circuit is 80% of rating of circuit for ampacity of wire for any load. NEC 220-2,

More information

Residential Questions and Answers 2011

Residential Questions and Answers 2011 Residential Questions and Answers 2011 1. I have an above ground swimming pool 18 ft. by 4 ft. deep, with metal T bar and upper ring for supports, that is set on a plastic mat or tarp ( high grade material),

More information

How To Plan Out An Array Of Solar Panels

How To Plan Out An Array Of Solar Panels CITY OF DOWNEY COMMUNITY DEVELOPMENT, BUILDING AND SAFETY 11111 Brookshire Avenue Downey, CA 90241 562.904.7142 (www.downeyca.org) B SECTION 01/01/2011 EFFECTIVE DATE PHOTOVOLTAIC 032 FORM NUMBER 2013

More information

CONTENTS. Yale University Design Standards. Underground Electrical Duct Bank. A. Summary. B. System Design and Performance Requirements

CONTENTS. Yale University Design Standards. Underground Electrical Duct Bank. A. Summary. B. System Design and Performance Requirements 16600 Underground Electrical Duct Bank This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications

More information

Low Voltage Pool Transformer

Low Voltage Pool Transformer 092498 RevA Low Voltage Pool Transformer for ColorLogic and CrystaLogic TM Pool/Spa Lights Owner s Manual Contents Introduction...3 Installation...4 Warranty...10 Registration Card...11 LTBUY11300 Basic

More information

ELECTRICAL SAFETY. The standard unit for measuring electrical current.

ELECTRICAL SAFETY. The standard unit for measuring electrical current. ELECTRICAL SAFETY Introduction The following sections provide general safety guidelines and procedures for electrical safety. This chapter covers the following topics: TOPIC PAGE General Electrical Safety

More information

ELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1

ELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1 KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1 PART 1 - GENERAL 1.01 RELATED DOCUMENTS: SECTION 16050 A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1

More information

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT The purpose of these specifications is to insure that there are minimum

More information

DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS

DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS MIOSHA-STD-1313 (10/15) 6 Pages For further information Ph: 517-284-7740 www.michigan.gov/mioshastandards DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS

More information

Union County Public Schools. Facilities Department. Electrical. Safe Work Practices

Union County Public Schools. Facilities Department. Electrical. Safe Work Practices 1 Union County Public Schools Facilities Department Electrical Safe Work Practices 2 Purpose In accordance with OSHA Standards 1910.331-335, safety-related work practices shall be used by Union County

More information

Sub-Bid Contractor Update Statement. Tab A - Invitation for Bids. Tab B - Instructions to Bidders

Sub-Bid Contractor Update Statement. Tab A - Invitation for Bids. Tab B - Instructions to Bidders INTRODUCTORY INFORMATION TABLE OF CONTENTS 00 0101 PROJECT TITLE PAGE PROCUREMENT REQUIREMENTS (PROJECT MANUAL) Tab A - Invitation for Bids Tab B - Instructions to Bidders Tab C Bid Form for General Bids

More information

Section 43. Lead Paint Risk Factor NONE WATER HEATER STORAGE ELECTRIC

Section 43. Lead Paint Risk Factor NONE WATER HEATER STORAGE ELECTRIC WATER HEATER STORAGE ELECTRIC Lead Paint Risk Factor NONE TABLE OF CONTENTS PART 1: INSTALLATION REQUIREMENTS FOR CONVENTIONAL HOMES... 1 WATER HEATER REPAIRS... 1 1. APPLIANCE REPAIR... 1 WATER HEATER

More information

SECTION 11 78 13 MORTUARY REFRIGERATORS

SECTION 11 78 13 MORTUARY REFRIGERATORS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 11 78 13 MORTUARY REFRIGERATORS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in

More information

Standards. www.nordx.com 5 ANSI/TIA/EIA-569-A (CSA T530)

Standards. www.nordx.com 5 ANSI/TIA/EIA-569-A (CSA T530) The primary focus of this standard is to provide design specifications and guidance for all building facilities relating to telecommunications cabling systems and components. This standard identifies and

More information

Ontario Electrical Safety Code - Info Sheet

Ontario Electrical Safety Code - Info Sheet Ontario Electrical Safety Code - Info Sheet The following are the Code requirements and explanatory material for buried electrical wiring that are applicable to most residential applications. 12-012 Underground

More information

IRRIGATION PUMPING Table of Contents - Section 900

IRRIGATION PUMPING Table of Contents - Section 900 IRRIGATION PUMPING Table of Contents - Section 900 PARAGRAPH 900.1 GENERAL 1 900.2 METERING REQUIREMENTS 1 900.3 CUSTOMER S CONTROL EQUIPMENT 2 900.4 SERVICE CONDUCTOR REQUIREMENTS 2 900.5 RECOMMENDATIONS

More information

Bath Planning Guidelines With Access Standards

Bath Planning Guidelines With Access Standards Bath Planning Guidelines With s 1: Door/Entry The clear opening of a doorway should be at least 32. This would require a minimum 2-10 door. If the existing structure precludes changing the opening then

More information

Errata NFPA 70. Proposed 2014 Edition

Errata NFPA 70. Proposed 2014 Edition Errata NFPA 70 National Electrical Code (Report on Proposals) Reference: 12-109 (Log #1618) Panel Meeting Action Proposed 2014 Edition The National Electrical Code Technical Correlating Committee notes

More information

Excerpts from the Canadian National Building Code (NBC)

Excerpts from the Canadian National Building Code (NBC) Excerpts from the Canadian National Building Code (NBC) Reproduced here with Permission of the Copyright Owner, the National Research Council of Canada, Institute for Research in Construction. For more

More information

Building Permit Application

Building Permit Application Building Permit Application Administrative Use Only PARENT PERMIT NUMBER (Required if part of another project) PERMITTEE: PERMITTEE ADDRESS: E-MAIL ADDRESS: ARCHITECT/ENGINEER: PHONE: PHONE: ARCHITECT/ENGINEER

More information

Please check with your local inspection authority for any additional requirements before installation.

Please check with your local inspection authority for any additional requirements before installation. Specifications for Residential Overhead Electric Service Installation This brochure addresses most typical residential overhead service installations. Variances for the following specifications must be

More information

Title: Grounding and Bonding Rev-01

Title: Grounding and Bonding Rev-01 Procedure No.: BMEHS-002-012 Page: 1 of 12 Preparer: Owner: Approver: EHS Team Member S/H Manager Site Manager Signed Copy on File Signed Copy on File Signed Copy on File Document Revision Change Table

More information

Pre-Delivery Instructions

Pre-Delivery Instructions Congratulations on your decision to purchase a Fantasy spa. Welcome to the growing family of Fantasy spa owners. Pre-Delivery Instructions Please take the time to read this booklet carefully, as it will

More information

Article 10 - ADMINISTRATIVE SECTION

Article 10 - ADMINISTRATIVE SECTION Article 10 - ADMINISTRATIVE SECTION 10.1 TITLE These Administrative Regulations along with the requirements included in the 2011 Edition of the National Electrical Code (NFiPA-70-2011) as adopted by the

More information

READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY!

READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY! READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY! The main power to any existing system must be disconnected prior to the

More information

Application Bulletin 103 - NEC Reference Guide for SolarBridge-Enabled AC Module Installers

Application Bulletin 103 - NEC Reference Guide for SolarBridge-Enabled AC Module Installers 9229 Waterford Centre Dr. Bldg C, Suite 110 Austin, Tx 78758 Application Bulletin 103 - NEC Reference Guide for SolarBridge-Enabled AC Module Installers Current Version: 13 AC Modules are a new product

More information

PLAN REVIEW SERVICES CONSTRUCTION DOCUMENTS NECESSARY FOR A THOROUGH PLAN REVIEW

PLAN REVIEW SERVICES CONSTRUCTION DOCUMENTS NECESSARY FOR A THOROUGH PLAN REVIEW CONSTRUCTION DOCUMENTS NECESSARY FOR A THOROUGH PLAN REVIEW PRELIMINARY BUILDING REVIEW two sets of the following: Architectural/engineering design development drawings indicating size of the building,

More information

HOUSING QUALITY STANDARDS (HQS)

HOUSING QUALITY STANDARDS (HQS) HOUSING QUALITY STANDARDS (HQS) Series 5 Electrical Safety And INSPECTIONS 5.01 ELS Revised 8-17-06 Electricity is Dangerous All electrical repairs should be made by licensed professionals. Touching any

More information

CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION

CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION SPECIFICATION EO-5023 REVISION 3 MARCH 2003 REQUIREMENTS FOR

More information

Report for. Dick and Jane Homeowner. 1234 Lovers Lane, Houston, Texas 77000

Report for. Dick and Jane Homeowner. 1234 Lovers Lane, Houston, Texas 77000 Report for Dick and Jane Homeowner 1234 Lovers Lane, Houston, Texas 77000 March 17, 2004 I NI NP R Inspection Item I. STRUCTURAL SYSTEMS o o o A. Foundations (If all crawl space areas are not inspected,

More information

A. Shop Drawing submittals shall include, but not be limited to, the following:

A. Shop Drawing submittals shall include, but not be limited to, the following: SECTION 26 05 53 IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical

More information

When is a Permit Required? What Types of Permits are Required? The most common types of projects that require permits are:

When is a Permit Required? What Types of Permits are Required? The most common types of projects that require permits are: When is a Permit Required? The most common types of projects that require permits are: -New Houses or buildings -Room Additions or Expansions -Structural repairs, remodeling and alterations -Accessory

More information

Wilo SP Series Submersible Sump Pumps ECS. ECS19-15.25 ECS22-15.33 ECS24-15.50 Installation and operating instructions

Wilo SP Series Submersible Sump Pumps ECS. ECS19-15.25 ECS22-15.33 ECS24-15.50 Installation and operating instructions Wilo SP Series Submersible Sump Pumps ECS ECS19-15.25 ECS22-15.33 ECS24-15.50 Installation and operating instructions PREINSTALLATION CHECK Inspect this pump before it is used. Occasionally, pumps can

More information

Section 21. Telecommunication Hardware. www.geindustrial.com BuyLog Catalog 21-1

Section 21. Telecommunication Hardware. www.geindustrial.com BuyLog Catalog 21-1 Introduction...21-1 Fiber Closure Hardware...21-2 Cable Location Surge Protectors...21-4 Introduction GE has been manufacturing Telecommunication Hardware products for over 20 years and has become a leader

More information

MTA UNIVERSAL STATION PEDESTRIAN BRIDGE Los Angeles, CA. Project Manual and Specification 100% PE SUBMITTAL TABLE OF CONTENTS

MTA UNIVERSAL STATION PEDESTRIAN BRIDGE Los Angeles, CA. Project Manual and Specification 100% PE SUBMITTAL TABLE OF CONTENTS Los Angeles, CA Project Manual and Specification DIVISION 1 GENERAL CONDITIONS 01 01 10 STATEMENT OF WORK 01 11 00 SUMMARY OF THE WORK 01 14 05 METRO (OWNER) - DIRECTED STOPPAGES 01 20 00 PRICE AND PAYMENT

More information