PLAN REVIEW GUIDE FIRE SPRINKLER SYSTEMS
|
|
- Jordan Hall
- 7 years ago
- Views:
Transcription
1 PLAN REVIEW GUIDE FIRE SPRINKLER SYSTEMS PROJECT NAME: PERMIT PROJECT ADDRESS: CONTACT PERSON: CONTRACTOR PHONE Fire sprinkler system installation information shall be provided on the appropriate plans. Plans are not required to be submitted for system additions or alterations involving less than 20 sprinkler heads, 40 feet of pipe, or 40 fittings; and the alteration or addition to the system; or the occupancy use does not change the hydraulic demand or density calculation requirements. All such work shall be performed by a contractor licensed by the State to do such work and who holds a current valid permit from the Fire Department to work within the City of Tolleson. The following items shall be included on the plans: Type of system to be installed High piled, in-rack or bin storage inside building Storage of flammable or combustible liquids Dispensing, use or mixing of flammable or combustible materials within building Storage of hazardous materials inside building Dispensing, use or mixing of hazardous materials within building F ire department general notes to the contractor are provided on the plans Plans shall be drawn to an indicated scale, on sheets of uniform size, with a plan of each floor, and shall show those items from the following list that pertain to the design of the system: Name of owner and occupant.
2 Name and address of contractor. Location, including correct street address. Point of compass. Full height cross section. Ceiling construction. Fire wall locations. Partition wall locations. Fire Door Locations Unprotected window openings Large unprotected floor openings. Location and dimensions of: 1. Concealed spaces 2. Bathrooms 3. Attics 4. Closets Any small enclosures in which no sprinklers are to be installed A legend list with descriptions Detail of connection to the underground fire line Shape of design area A sprinkler head table listing the manufacturer, model, orifice size, temperature rating and protection area for each head type and the number of heads per riser per floor. Detail of connection to the underground fire line. The following in a DESIGN CRITERIA box: 1. Hazard class 2. Design density
3 3. Design Area (sq. ft.) 4. Number of sprinklers in design area 5. Water supply data: a. Test date and location b. Flow PSI and GPM c. Residual PSI d. Static PSI e. Hose stream and in-rack sprinkler water allowance 6. System demand: a. PSI at riser b. GPM at riser Pipe type and schedule of wall thickness. Type and location of hangers, sleeves, braces, and methods of securing sprinklers. City main size and system elevation relative to flow test hydrant. The Building Code occupancy class of each area or room in the building are indicated on the drawings. Sprinkler heads are positioned no closer than 4 inches to any wall. The clear space below sprinklers is in accordance with NFPA 13. The placement, location and contents of the spare sprinkler head cabinet is indicated on the drawing. The type and locations of all control valves, check valves, main and auxiliary drains are indicated and identified on the drawings. The location and size of the inspectors test valve is indicated on the drawings. The maximum floor area on any single floor served by an individual riser does not exceed NFPA 13 ALLOWANCE. The location and type of local water flow alarm is indicated on the drawings. Cut sheet literature describing all systems components is included as attachments or component manufacturer, make and model data is included on the drawings when the components are listed in the
4 Underwriters Laboratories Inc. Fire Protection Equipment Directory. Sprinkler system installation under exterior combustible roofs or canopies exceeding four feet in width, attached to the building is indicated on the drawings. Sprinkler head installation under ducts (more than 4 feet in width) is indicated on the drawings. Third party monitoring of water flow is provided for systems with 20 or more sprinkler heads (Group 1 Division 1) or 100 or more sprinkler heads in other occupancies. Fire hose valves and stations (when required or provided) are spaced so that all protected areas are within 30 feet of a nozzle when attached to not more than 100 feet of hose. Fire hose valves shall be two 2½ inch male connections (NST) with a gate valve. No hose shall be attached. A detail of the hydraulic data nameplate is included on the drawings. Stamped or engraved metal or rigid plastic plates are required. Calculations for hydraulically calculated systems contains the data required in accordance with NFPA. Fire Department Connections (FDC s) NFPA 13 sprinkler systems shall be 2 ½ female swivels with national standard threads (NST). FDC s for NFPA 13D and 13R sprinkler systems shall be 1 1/2 single female swivel with national standard thread (NST). Inspections and Acceptance Testing All requests for inspections and acceptance testing shall be made by calling the Tolleson Fire Inspector s office at ext. 102, no less than 48 hours in advance. The following information is required: Permit number Address (including suite number) Name of project or company Purpose of inspection A call back number, and responsible part No inspections or acceptance tests will be conducted without an approved and stamped set of plans on site and all required permits. Sprinkler systems will be pre-tested by the contractor and all necessary corrections will be made prior to calling for an acceptance test.
5 There shall be a minimum of three separate inspections prior to the approval of a new sprinkler system. Underground Fire Line Two Hour Hydrostatic Test System shall be pre-tested by the contractor All joints must be fully exposed Thrust blocks must be in place and exposed A flush test witnessed by the fire inspector shall be conducted after the 200 # hydrostatic test A copy of the Contractor s Material and Test Certificate for Underground Pipe (signed by the sub-contractor and general contractor) shall be provided to the fire inspector. Overhead Rough-In Inspection and Two Hour Hydrostatic Pressure Test System shall be pr-tested by the contractor System shall be tested for two hours with all system piping visible from the floor. Any obstructions of the system piping shall be removed by the contractor prior to the inspection. A copy of the Contractors Material and Test Certificate for Overhead Pipe (signed by the sub-contractor and general contractor) shall be provided to the inspector. Final Inspection The completed Contractor s Material and Test Certificates shall be provided to the fire inspector prior to a final inspection which includes: Visual inspection of the entire system (drywall and ceiling tiles in place) Exterior alarm bell test including third party monitoring, where required Hydraulic Calculation Data Plate shall be installed on all calculated systems Sprinkler Head Box(es) shall be properly installed and stocked with the proper sprinkler heads, wrench and NFPA 25 Supervision of all valves System shall be fully operational All signage shall be installed Main drain test shall be conducted and witnessed by the inspector Inspector s test and timed water flow alarm test witnessed by the inspector Other tests or inspections that may be required Tenant Improvement Projects
6 Modifications to existing systems affecting 20 or more heads, 40 or more feet of pipe or 40 or more pipe joints require plans to be submitted. Plans must be approved and on site prior to a Certificate of Occupancy being issued. A permit is required for all sprinkler construction or modification. For those modifications which are less than 20 heads, less than 40 feet of pipe or less than 40 pipe joints, plans are not required. These modifications require an over the counter permit.
Automatic Fire Sprinkler Submittal Requirements
Automatic Fire Sprinkler Submittal Requirements All commercial and industrial buildings with a total floor area of 5000 sq. ft. shall have an approved automatic sprinkler system installed. The Windsor-Severance
More informationSPRINKLER SYSTEM PLANS AND CALCULATIONS CHECK LIST
SPRINKLER SYSTEM PLANS AND CALCULATIONS CHECK LIST 1. Working plans shall be drawn to an indicated scale, on sheets of uniform size, with a plan of each floor, and shall show those items from the following
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13R
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13R Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved;
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved;
More informationClark County Fire Prevention
Clark County Fire Prevention Mission Statement: To provide the highest level of fire protection and related services TITLE: REQUIREMENTS FOR A NEW SPRINKLER SYSTEM IN ACCORDANCE WITH THE 2002 EDITION OF
More informationCommercial Fire Inspections
Commercial Fire Inspections Fire Department Inspection Requests and Procedures The following guidelines shall be used when calling for inspection requests: 1. All inspection requests shall be coordinated
More informationFIVE YEAR CERTIFICATION REPORT
GARDEN GROVE FIRE DEPARTMENT FIRE PREVENTION DIVISION FIVE YEAR CERTIFICATION REPORT Service and maintenance report of automatic fire extinguishing systems, including fire sprinklers, dry, deluge, and
More informationGeneral Fire Code Requirements Within Commercial Tenant Spaces
FIRE DEPARTMENT in cooperation with Scope: General Fire Code Requirements Within Commercial Tenant Spaces This handout is designed to assist owners, architects, contractors and others in understanding
More informationMERCER ISLAND FIRE DEPARTMENT FIRE COMMERCIAL SPRINKLER STANDARDS
MERCER ISLAND FIRE DEPARTMENT FIRE COMMERCIAL SPRINKLER STANDARDS COMMERCIAL FIRE SPRINKLER SYSTEMS Page 1-5 SCOPE: Fire sprinkler systems in the City of Mercer Island shall meet the criteria as set forth
More informationAutomatic Fire Sprinkler System Checklist
Fire Prevention rd Location: 701 E. 3 Avenue Mail to: P.O. Box 1579 Moses Lake, WA 98837 (509) 765-2204 www.ci.moses-lake.wa.us Automatic Fire Sprinkler System Checklist Please print in Black or Blue ink
More informationFire Sprinkler System Maintenance and Testing Page 1 MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS
Page 1 MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS Introduction When properly installed and maintained, automatic fire sprinkler systems have proven to be the most effective means for protecting
More informationFire Alarm System Standpipes Sprinkler Systems Fire Drills Commercial Cooking Hood and more
FIRE PROTECTION SYSTEMS Fire protection systems, measures and equipment are all related to the safety of the occupants and the protection of the property. As part of a building design and its intended
More informationLOUISVILLE FIRE PROTECTION DISTRICT 895 West Via Appia, Louisville, Colorado 80027 303-666-8809
LOUISVILLE FIRE PROTECTION DISTRICT 895 West Via Appia, Louisville, Colorado 80027 303-666-8809 Contractor s Checklist and Installation Guide TABLE OF CONTENTS Fire Protection Narrative........... 3 Fire
More informationPLAN REVIEW GUIDE FOR FIRE ALARM
PLAN REVIEW GUIDE FOR FIRE ALARM PROJECT NAME: PERMIT # PROJECT ADDRESS: CONTACT PERSON: PHONE Fire alarm system installation information shall be provided on the appropriate architectural and electrical
More informationPLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS
January 1997 PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS 1.0 PERMIT 1.1 After receipt of a Building Permit from the City of San Jose Building Department, submit
More informationSELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT
SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT INTRODUCTION No matter how reliable fire protection equipment may seem, periodic maintenance is needed to ensure proper operation. Fire protection
More informationREGULATIONS for INSTALLATION, MAINTENANCE, and TESTING APPLICATION PACKET
REGULATIONS for INSTALLATION, MAINTENANCE, and TESTING FIRE SUPPRESSION SYSTEMS APPLICATION PACKET CITY OF NAPERVILLE 400 S. EAGLE STREET NAPERVILLE, Il 60540 PHONE: 630.420.6070 FAX: 630.420.6657 Fire
More informationFIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or comments regarding the
More informationFIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011, Updated March 2012 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or
More informationALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS
ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS In this document are the fire safety equipment maintenance requirements that are found in Division B of the Alberta Fire Code (AFC 2006) for
More informationNFPA 13 2002 FAQs. 3. Can plastic pipe be used on a sprinkler system complying with NFPA 13?
NFPA 13 2002 FAQs Responses to FAQs are prepared by NFPA technical staff to assist users in reading and understanding NFPA codes and standards. The responses, however, are not Formal Interpretations issued
More informationMECHANICAL PLAN REVIEW REQUIREMENTS
6. Accessibility provisions. 7. Description and details of proposed special occupancies such as a covered mall, high-rise, mezzanine, atrium, public garage, etc. 8. Adequate details to evaluate fire resistive
More informationDesign Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems. April 2013
Design Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems April 2013 The National Multi Housing Council and the National Apartment Association (NMHC/NAA) have
More informationPART II: New Construction Inspections and Acceptance Testing Procedures
Stafford County Fire Marshal s Office Handbook for Building/Fire Code Policies and Guidelines PART II: New Construction Inspections and Acceptance Testing Procedures Phone: 540-658-8648 Fax: 540-658-9128
More informationAON SPRINKLER CERTIFICATION
Form 1 Application for Approval of Basic Design Parameters for Automatic Sprinkler System Installations 1. Name of Protected Premises Site Name Address 2. Work to be Carried Out New System Extension or
More informationFire Alarm System Plans Review Checklist Property location Date of Review
Fire Alarm System Plans Review Checklist Property location Date of Review 1. Is application completed in entirety? 2. Are the plans review fee submitted with the application? 3. Does floor plan include
More informationTYPICAL FIRE SAFETY INSPECTION VIOLATIONS
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS The following is a list of typical violations often found by inspectors and a generic solution. You can use this list to improve the safety of your facility, to
More informationInspection and Testing of Water-Based Systems
Inspection and Testing of Water-Based Systems Standard Model/Computer-Based Testing Level III Content Outline The candidate for NICET certification at Level III in the Inspection and Testing of Water-Based
More informationWinnipeg Fire Department Fire Prevention Branch
Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of
More informationTECHNICAL DATA 2. LISTINGS AND APPROVALS. Spray Nozzle 11. December 20, 2013
Spray Nozzle 11 1. DESCRIPTION Viking Model C-1 Window Sprinklers are non-automatic, open, outside intended for protection of windows, walls, and roofs against exposure fires. The directional discharge
More informationEXETER TOWNSHIP DRY OR WET CHEMICAL FIRE SUPPRESSION SYSTEMS
DRY OR WET CHEMICAL FIRE SUPPRESSION SYSTEMS POLICY STATEMENT This policy applies to NEW Dry or Wet chemical fire suppression systems. The Authority Having Jurisdiction will not waive major criteria in
More informationCOMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression
More informationLIFE SAFETY UPDATE. FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc.
LIFE SAFETY UPDATE FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc. The purpose of this update is as follows: Remind all state
More informationRoland Garcia Pearland Fire Department
Roland Garcia Pearland Fire Department NFPA13D Texas Legislation Conflicting Views - Fire Service and Home Builders Incentives offered in the ICC Detect and control residential fires Prevent injury and
More informationC I T Y O F S E L M A F I R E D E P A R T M E N T
C I T Y O F S E L M A F I R E D E P A R T M E N T Informational Bulletin Regarding Residential Fire Sprinkler Systems for One and Two Family Homes: Frequently Asked Questions ADMINISTRATIVE PROVISIONS:
More informationSPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT
SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT The purpose of these specifications is to insure that there are minimum
More informationFIRE PROTECTION SYSTEMS ACCEPTANCE INSPECTION AND TESTING PROCEDURE
ACCEPTANCE INSPECTION AND TESTING PROCEDURE Wet Pipe Sprinkler Systems...2 Dry Pipe Sprinkler Systems...2 Clean Agent Fire Extinguishing System...4 Total Flooding Systems...4 Fire Dampers...5 Smoke Dampers...5
More informationBuilding Code Clarifications - 7. Fire Resistance
Building Code Clarifications - 7. Fire Resistance 7.1 (15-12-030) Use of combustibles in Type III construction roof assemblies Code Section (15-12-030) Use of Combustibles was revised on May 17, 2000,
More informationMaintaining Fire Protection Systems
Maintaining Fire Protection Systems Fire continues to be a major threat to your business and your personal safety. Each year several thousand people are injured or killed by fires and billions of dollars
More informationRequired Certification Documentation. Contractor's installation certification for range hood fire suppression systems.
OFFICE OF UNIVERSIT BUILDING OFFICIAL PROJECT/CONSTRUCTION MAGER: Sample Manager Required Aboveground only Required Certification Documentation Contractor s material and test certifications for both above
More informationcity of edmonds development information
#B17 city of edmonds development information Commercial Kitchen Hood & Hood Fire Suppression System Permit Submittal Requirements PERMIT REQUIRED: CODES: FEES: A Commercial Kitchen Hood Mechanical Permit
More informationTechnical Article. Sprinkler Protection for High Bay and Automated Storage in Warehouse-Type Storage Facilities
Technical Article for High Bay and Automated Storage in Warehouse-Type Storage Facilities Scott Martorano, CFPS Senior Manager Technical Services February, 2010 Worldwide Fire Protection www.vikinggroupinc.com
More informationFIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS. 1. All Floors (inspect from top floor to basement): Yes No
General Inspection FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS 1. All Floors (inspect from top floor to basement): Yes are fire exits and directional signs properly illuminated? is the emergency
More informationFIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS
FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS The attached self-inspection form is intended for staff use at regular, frequent intervals. It should not take the place of two other vital measures
More informationTransformer Deluge Systems
Transformer Deluge Systems How Do Transformer Fires Ignite? Common causes of transformer failure: Weather-related events such as lightning Short circuits in electrical equipment The most common cause is
More informationImportant Ontario Fire Code Information for Building Owners in the City of Windsor
Important Ontario Fire Code Information for Building Owners in the City of Windsor This information is intended to be used a reference only. For a complete listing consult the Ontario Fire Code or contact
More informationThe following definitions apply with regard to requirements specified in this document:
GUIDELINES FOR INSTALLATION OF TEMPORARY AND PERMANENT ABOVEGROUND DIESEL FUEL TANKS FOR EMERGENCY AND STANDBY POWER SYSTEMS LOCATED OUTSIDE OF BUILDINGS For Use by Unidocs Member Agencies or where approved
More informationUniversity Design Standard. Fire Alarm Systems
University Design Standard Fire Alarm Systems 1.0 Overview This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit
More informationH O M E F I R E S P R I N K L E R S S A V E L I V E S, M O N E Y A N D W A T E R A G U I D E F O R W A T E R P U R V E Y O R S
H O M E F I R E S P R I N K L E R S S A V E L I V E S, M O N E Y A N D W A T E R A G U I D E F O R W A T E R P U R V E Y O R S HomeFireSprinkler.org F I R E T H E L A R G E ST S I N G L E C AU S E O F
More informationBold items are particular to the City of Euless
EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 2/12 Fire Chief Wes Rhodes Fire Marshal Paul Smith EFD-FMO 3-2 2009 International Fire & Building Code as Amended NFPA Standards Adopted
More informationTAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST In order to provide a comprehensive plan review in a timely manner, and to insure the design and installation of fire alarm systems
More informationBELMONT FIRE DEPARTMENT FIRE ALARM SYSTEM REQUIREMENTS BFD-OFM-10-011
Fire Alarm System plan(s) MUST be reviewed and approved by the Belmont Fire Department prior to the start of construction. The design and any changes must be fully compliant with NFPA 1, NFPA 101, NFPA
More informationCHAPTER. Standpipes and Hose Systems OVERVIEW. Standpipe and Hose Systems Defined
Standpipes and Hose Systems CHAPTER 3 This chapter, which opens with an overview of standpipe and hose systems, is intended to assist the registered design professional (RDP), commissioning agent, authority
More informationExcerpts from the Canadian National Building Code (NBC)
Excerpts from the Canadian National Building Code (NBC) Reproduced here with Permission of the Copyright Owner, the National Research Council of Canada, Institute for Research in Construction. For more
More informationWATER MEASUREMENT USING TWO INCH (50 mm) DRAIN TESTS
GAP.14.1.2.2 A Publication of Global Asset Protection Services LLC WATER MEASUREMENT USING TWO INCH (50 mm) DRAIN TESTS INTRODUCTION A hydrant or other large-volume flow test is necessary for proper water
More informationINSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT
INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT FIRE EXTINGUISHERS,SPRINKLER SYSTEMS AND FIRE ALARMS Attachment #1 Inspection of Fire Extinguishers Fire Extinguishers must be tested according
More informationChapter 19 - FIRE SPRINKLER SYSTEM INSPECTIONS
Title 153 - NEBRASKA STATE FIRE MARSHAL Chapter 19 - FIRE SPRINKLER SYSTEM INSPECTIONS Scope. Chapter 19 of Title 153 of the Nebraska Administrative Code is concerned with the certification of contractors
More informationName Of Occupancy Date. Yes No Describe
FIRE PREVENTION INSPECTION CHECKLIST For Class A Occupancy (For Assembly Buildings, Bars, Restaurants, Gyms, Churches, Arenas, Theatres or wherever people gather) Name Of Occupancy Date Physical Address
More informationFire Pump Plan Review March 2010
Fire Pump Plan Review March 2010 Date of Review: / / Permit Number: Business/Building Name: Address of Project: Designer Name: Designer s Phone: Contractor: Contractor s Phone: Occupancy Classification:
More informationEXHIBIT A SCOPE OF WORK
EXHIBIT A SCOPE OF WORK 1. (Contractor) shall provide fire alarm system maintenance/repair/testing services as described herein to the California Department of Veterans Affairs (hereinafter CDVA, CalVet,
More information2014 Limited Plan Submittal Checklist
City of Aurora Public Works Department WET AND DRY CHEMICAL HOOD SUPPRESSION SYSTEM 2014 Limited Plan Submittal Checklist Building Division 15151 E. Alameda Parkway, Ste 2400 Aurora, CO 80012 303-739-7420
More informationCommercial Fire Alarm Standards July 1, 2010 Edition Page 1 of 14
City of Mercer Island Development Services Group Fire Code Review and Inspection 9611 SE 36 th Street Mercer Island, WA 98040-3732 PHONE (206) 275-7605 FAX (206) 275-7726 www.mercergov.org Commercial Fire
More informationA. Fire Protection Plan. B. Access and Parking
Standards for Construction Site Fire Safety For Use by Unidocs Member Agencies or where approved by your Local Jurisdiction Authority Cited: California Fire Code (CFC) These standards are intended to prescribe
More informationInspection and Testing Program Fire Protection Equipment
I. Introduction Inspection and Testing Program Fire Protection Equipment State of Minnesota Emergencies seldom give warning before they strike. Thus, it is essential that fire protection equipment be inspected,
More informationMOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Pump Plan Review 2009 International Fire Code and NFPA 20 Date of Review / / BLD201 - Project Address: Project Name: Contractor s Business
More informationFire Alarm System Plans Submittal Guidelines For New and Existing Systems
Fire Alarm System Plans Submittal Guidelines For New and Existing Systems SCOPE The Temecula Fire Prevention Bureau (TFPB) has established the following requirements for the submittal of all fire alarms,
More informationFire detection, alarm, and suppression systems are installed to:
Fire detection, alarm, and suppression systems are installed to: Notify occupants to escape a fire Summon emergency responders Initiate suppression systems Supervise suppression systems for operational
More informationRiverside County Fire Protection Planning
Riverside County Fire Protection Planning Customer Building Matrix Guidelines INTRODUCTION AND PURPOSE This is a guide to assist an owner/builder, general contractor or sub-contractor in the required steps
More informationesfr pendent sprinkler vk510 (k25.2)
January 17, 2014 Sprinkler 124a 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Pendent Sprinkler VK510 incorporates the capability to suppress specific high-challenge fires. The addition
More informationFIRE INSPECTION CHECKLIST
Applicable Base Codes FIRE INSPECTION CHECKLIST Florida Fire Prevention Code, 2010 Edition NFPA 1, Uniform Fire Code, Florida 2010 Edition NFPA 101, Life Safety Code, Florida 2010 Edition NFPA 13, 2007
More informationMAINTENANCE AND SERVICE OF AUTOMATIC FIRE EXTINGUISHING SYSTEMS
FIRE DEPARTMENT Bureau of Fire Protection and Life Safety www.cityofsanmateo.org 1900 O Farrell, Suite 140 San Mateo, CA 94403-1332 (650) 522-7940 FAX: (650) 522-7941 TDD: (650) 522-7047 MAINTENANCE AND
More informationPollution CO CO 2. Carbonaceo us soot H 2 S, NOX, SO2
Pollution CO CO 2 Carbonaceo us soot H 2 S, NOX, SO2 The National Building Code (NBC) contains set of minimum provisions, designed to protect the safety of the public with regard to structural sufficiency,
More informationWarehouse Checklist. Warehouse Construction
PAGE 1 Warehouse Checklist Recent NFPA statistics estimate that in 1998 approximately 36,000 fires occurred in structures used for storage, accounting for $687mm of damage (over 10% of total fire damage
More informationSUBCHAPTER 17 FIRE ALARM, DETECTION AND EXTINGUISHING EQUIPMENT
[Sub-Art. or Sec.]* SUBCHAPTER 17 FIRE ALARM, DETECTION AND EXTINGUISHING EQUIPMENT TABLE OF CONTENTS Art. or Sec.** [1700.0] Art. 1 General [1700.1] 923 Scope [1700.2] 924 Standards [1700.3] 925 Definitions
More informationConcord Department of Fire and Life Safety FIRE MARSHAL S OFFICE
Concord Department of Fire and Life Safety FIRE MARSHAL S OFFICE September 1, 2005 Fire Suppression Operations in Residential Occupancies equipped with Residential Fire Sprinkler Systems. Since human beings
More informationThis handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances.
Basement Finishing Guide Community Development Department Building Inspections Division 5200 85 th Avenue North / Brooklyn Park, MN 55443 Phone: (763) 488-6379 / Fax: (763) 493-8171 6/15 www.brooklynpark.org
More informationFraternity and Sorority House Fire Safety
Fraternity and Sorority House Fire Safety Buddy Dewar Director of Regional Operations National Fire Sprinkler Association 850-222-2070 How To Manage Greek Housing Fire Sprinkler Retrofit Brief Overview.
More informationOREGON FIRE CODE Interpretations and Technical Advisories
OREGON FIRE CODE Interpretations and Technical Advisories A collaborative service by local and state fire professionals, along with our stakeholders and customers, to provide consistent and concise application
More informationViking Residential Sprinkler Installation Guide
Viking Residential Sprinkler Installation Guide January, 2009 Trusted Above AllT M www.flowbusiness.cl Sprinkler RES1 January 9, 2009 1. DESCRIPTION Viking residential automatic sprinklers are equipped
More informationProperty Policyholder Risk Improvement Report and Hurricane Survey
Risk Engineering Property Policyholder Risk Improvement Report and Hurricane Survey Zurich Services Corporation Risk Engineering 1400 American Lane Schaumburg, IL 60196-1056 847.605.6000 Fax: 847.605.7854
More informationUnderground Piping for Private Hydrants & Sprinkler Supply Line
ORANGE COUNTYFIRE AUTHORITY Planning & Development Services Section 1 Fire Authority Road, Bldg. A, Irvine, CA 92602 714-573-6100 www.ocfa.org Underground Piping for Private Hydrants & Sprinkler Supply
More informationSuffolk County Department of Health Services. Division of Environmental Quality
Suffolk County Department of Health Services Division of Environmental Quality Guidelines For the Construction of Storage Areas for Portable Containers ~~~~ Clare B. Bradley, M.D., M.P.H. Suffolk County
More informationFighting Fire in Sprinklered Buildings. Student Guide
Fighting Fire in Sprinklered Buildings Student Guide Fighting Fire in Sprinklered Buildings Student Guide Table of Contents Purpose........................................................... 3 Instruction
More informationEducational. Educational-Existing 1/28/2014. OCCUPANT LOADS [no change] Application. Application
February 2014 Code Requirements and Inspections in Educational Occupancies Presented By: Barry W. Rickert Douglas M. Schanne Fire Marshal Training Program Supervisor Office of Education & Data Management
More informationFLAMMABLE AND COMBUSTIBLE LIQUIDS
GAP.8.1.0 A Publication of Global Asset Protection Services LLC FLAMMABLE AND COMBUSTIBLE LIQUIDS INTRODUCTION National Fire Protection Association (NFPA) documents describe a level of fire protection
More informationBuilding Codes Update: The 2009 International Fire Code and the Apartment Industry
! Building Codes Update: The 2009 International Fire Code and the Apartment Industry Apartment operators and developers should be aware of organizational changes in the 2009 edition of the International
More informationRAPID RESPONSE Model RSV-1 Residential Shut-Off Valve, 1 Inch and 2 Inch (DN25 and DN50) for Dual-Purpose Residential Water Supply General Description
Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Model RSV-1 Residential Shut-Off Valve, 1 Inch and 2 Inch (DN25 and DN50) for Dual-Purpose Residential Water Supply General Description The TYCO RAPID
More informationMOTOR FUEL DISPENSING SAFETY
STRATEGIC OUTCOMES PRACTICE TECHNICAL ADVISORY BULLETIN January 2010 MOTOR FUEL DISPENSING SAFETY Fire! Not an alarm anyone wants to hear, especially not when the fire is burning at a major fuel source.
More informationADMINISTRATIVE SERVICES MANUAL
Purpose Responsibilities Proper Storage and use of flammable liquids can significantly reduce the possibility of accidental fires and injuries. To minimize risk to life and properly, the requirements of
More informationDennis Fire Department Fire Prevention Mark Dellner Fire Chief
Dennis Fire Department Fire Prevention Mark Dellner Fire Chief FIRE SAFETY INSPECTION GUIDELINES FOR COMMERCIAL PROPERTIES (MA Fire Prevention Regulations 527 CMR, MGL Chapter 148) FIRE PREVENTION CHECKLIST-
More informationDepending on your facility and the equipment contained within, all or part of the checklists/logs can be printed for use.
Large Facility Fire Safety Checklists and Logs This package contains checklists to ensure that all fire and life safety equipment are properly inspected. There are also logs on which to record the inspections
More informationFire Safety Plan University Stadium
Fire Safety Plan University Stadium Building # 53 Safety, Health, Environment Effective: March 14, 2018 Revised: December 2014 Revision: 1 Approved on: Pending Approval WILFRID LAURIER UNIVERSITY Contact:
More informationGypsum Fire Protection District. Fire Sprinkler System Submissions
Gypsum Fire Protection District Fire Sprinkler System Submissions Fire Sprinkler System Submissions for permit will fall under one of two categories: new installations or remodels. New installations or
More informationNFPA 25 FAQs. 1. When inspecting an old system (60 years or older), when/where does NFPA 25 require a system to be upgraded to present standards?
NFPA 25 FAQs Responses to FAQs are prepared by NFPA technical staff to assist users in reading and understanding NFPA codes and standards. The responses, however, are not Formal Interpretations issued
More informationRisk Control Bulletin Inspection, Testing & Maintenance (ITM) of Water-Based Fire Protection Systems
Risk Control Bulletin Inspection, Testing & Maintenance (ITM) of Water-Based Fire Protection Systems Introduction Fire protection systems are provided in or at a building to safeguard the lives of building
More informationRequirements for Hydrogen Storage and Use
Requirements for Hydrogen Storage and Use I. INTRODUCTION Fire and Life-Safety Group (FLS) The following is a summary of the fire and building code requirements for the storage and use of hydrogen. These
More informationSpray Booth Guideline
Department of Development Service 135 North D Street, Perris CA. 92570 Phone: (951) 443-1029 Fax: (951) 943-3293 PURPOSE The intent of this guideline is to provide the information necessary to ensure that
More informationRESIDENTIAL SPRINKLER INSTALLATION GUIDE
RESIDENTIAL SPRINKLER INSTALLATION GUIDE 4077 AIR PARK DRIVE STANDISH, MICHIGAN 48658 PHONE 989-846-4583 800-248-0278 FAX 989-846-9231 www.globesprinkler.com A-15 GLOBE RESIDENTIAL SPRINKLER GUIDE DESCR.,
More information