535 Infrared Spark Detector Manual. Technical Manual Revision C
|
|
- Chester Sutton
- 7 years ago
- Views:
Transcription
1 Technical Manual Revision C
2 Table of Contents 1.0 General Pg Specifications Pg General Operating Data Pg Sensitivity Pg Graph Pg Graph Pg Graph Pg Installation Pg Part Numbering Identification Pg Mounting Pg Mounting - Tools Required Pg Mounting Diagrams Pg Wiring Pg Maintenance Pg Warranty Pg 11
3 1.0 General The Argus Infrared Detector is highly sensitive, fast-acting detection unit designed to detect an ember or fire in its beginning stage. Incorporated in an Argus fire control system the Argus infrared detector will detect, react and extinguish the threat before it can cause extensive damage to the machinery or process in which it is installed. Taking advantage of the latest in high-speed detector sensor technology allows the Argus infrared detector to perform these tasks. The detector cell is capable of detecting an ember, spark or fire in 8 microseconds ( ). This speed allows several advantages to be realized in the overall detector unit design, not the least of which is discrimination, or the ability to determine whether or not the ember or spark fits a velocity profile that would be produced by the material flow in a duct or chute. The design incorporates this capability and continually monitors the duct for embers, sparks or fire, that meet the qualifications of a particular velocity/intensity profile. This feature considerably reduces the risk of false alarm due to electrical noise present in all industrial environments. In addition to velocity/intensity profile monitoring, the detector incorporates an ambient light filter to reduce the sensitivity of the system to ambient or background lighting in the visible region of the spectrum, while allowing radiation in the infrared region to be detected. The detectors are designed to latch or lock into alarm when an ember, spark or fire is visible to the detector cell. Once the detector is in alarm, it can only be reset by the control panel or by removing power from it. The recommended application is for detection in dark or semi-dark areas with less than 10 foot candles (108 lux) ambient illumination. If properly located at the sides, or top of a duct, the detector design effectively eliminates the buildup of dust on the lens. Normally, the detector is mounted flush with the duct wall, so the air traveling through the ducts tend to clean the lens surface. CAUTION: Direct or indirect exposure to ambient light could cause the detector to go into alarm, causing the system to discharge the extinguishing agent. CAUTION: If tint, dye, or other materials are added to the process, and they coat the interior of the duct, the detector lens would require periodic cleaning. The region of detector sensitivity is between the limits of 750 nanometers and 1250 nanometers, with peak sensitivity at 950 nanometers. The visible portion of the spectrum lies between the limits of 450 and 750 nanometers, making the detector less sensitive to visible light. page: 1
4 2.0 Specifications 2.1 general operating data Detector Part Number: Operation Voltage, volts DC: 24 Standby Current ma: 33 Alarm Current (Excited) ma: 41 Current Alarm (After latching into Alarm) ma: 38 Output Rating ma: 41 Alarm Indicator: Red LED Power Indicator: Green LED Spectral Range, nanometers: 750 to 1,250 Spectral Sensitivity (at 0.5 milliwatts per cm2): 17 microamps Peak Response, nanometers: 950 Response Time Output, microseconds: 8 Ember Size: 3mm at 46cm, 6mm at 1 meter Sensitivity Derating: 70% Effective at 45 from Head on. Operating Temperature, C -40 to + 85 Typically the ARGUS Infrared Detector will detect ember of glowing particles under the following conditions: Speed/Velocity: Temperature (Ember): Wavelength limits: Stationary flame flicker or embers from 150cm per second to 60 meters Typically 600 C to greater than 1,000 C for particles 3.2mm in diameter 750 nanometers to 1,250 nanometers 2.2 sensitivity 2.3 Graph 2.4 graph Relative Radiant Sensitivity vs. Angular Displacement Relative Spectral Sensitivity vs. Wavelength Srel - Relative Radiant Sensitivity ψ- Angular Displacement S(λ) φ, rel - Relative Spectral Sensitivity λ- Wavelength (nm) page: 2
5 2.5 Graph Throughput time of Argus Z-1 (single zone) panel and Argus 535 Detector. Extinguisher Vdc 25 15uS Detector 2μS Divisions graph 2.4 page: 3
6 3.0 installation 3.1 Part Numbering Identification Drawing Detector Cover M4 x 10 Screw Cover Gasket M4 Nut Circuit Board M4 x 10 Standoff LED Cover Cable Clamp Ground Strap M6 Stainless Steel Nut Detector Housing MM x 20 Stainless Steel BTN HD, Screw Bottom Seal Gasket Lens Assembly page: 4
7 3.2 mounting CAUTION: Care must be taken when drilling or cutting into duct so as to make sure no metal shavings or pieces fall into the duct work. This could cause extensive damage to the machinery. Determine the number and best location of the detectors as determined by the size of the duct and the type of machinery being protected. Argus engineering can assist. Using an Argus template as a guide, position the detectors in accordance with the required spacing (Item 9 on page 6). The detectors should be positioned so that the bolt and lens holes are parallel to the direction of the duct. See page 9. The detectors should not be placed on the bottom of the duct where material could settle on the detector lens. See drawing 3.2 The detector s LED indicator light should be pointing where it is easily visible, and the cover of the detector can be removed. For each detector, three (3) holes will need to be cut into the wall of the duct. CAUTION: After drilling or cutting holes in duct make sure all sharp edges are removed and sanded smooth. Use a magnet to remove all metal from duct work. From the inside of the duct, push two (2) button head bolts through the two 7mm holes. On the outside of the duct secure each bolt with a M6 (lock) nut to the duct work. Place the detector on the two bolts with the gasket towards the duck work. Make sure LED indicator is facing the correct direction. Use two additional M6 lock nuts to secure the detector to the mounting bolts. NOTE: Never mount detectors on the bottom of the duct. page: 5
8 3.3 tools required ) File 2) Crimp Small Wire Cutters 3) Wire Cutters 4) 30mm Drill Bit 5) 7mm Drill Bit 6) Allen Wrench 7) Bent Needle Nose Pliers 8) Screw Driver 9) Mounting Template 10) Wrench 11) Terminating Ferrules 12) Sandpaper page: 6
9 3.4 mounting - Diagrams Drawing 3.2 Never mount a detector on the bottom of a duct. Vertical Mounting Horizontal Mounting Drawing 3.3 TOP VIEW Any Adjustments Void all WARRANTY 58 BOTTOM VIEW 58 Green LED - Power ON Red LED - Alarm End of Line Module Set EOL to ON for last detector in line ONLY. Remove cover, to wire for installation. Drill one 30mm diameter hole. Drill two 7mm diameter holes. page: 7
10 3.5 WIRING All wiring from control panel to the Argus Infrared detectors to be 20 to 16 AWG (0.5 to 1.5mm) Recommended wire colors are Black, White, Red and Green. Each zone of detectors (refer to specific control panel manual for allowable number of detectors per zone) is connected in series to the control panel. With the control panel and detectors properly located and all power removed, pull the required wires through the appropriate sized conduit and terminate the wire at the proper detector. Leave extra wire at both ends to allow for connecting the wires to the device. Ensure EOL is Set to OFF V- DET V+ GRD OFF ON V- DET V+ GRD V- DET V+ GRD Set Last EOL to ON OFF ON V- DET V+ GRD page: 8
11 Cross section view of detectors with duct. Infrared Detector Detector Lens Drill 6 mm hole. Cover with black tape. Hand held infrared test unit. P/N: page: 9
12 4.0 Maintenance CAUTION: Direct or indirect exposure to ambient light will cause the detector to go into alarm. All holes (for testing) and cracks must be sealed with thick black tape, or other suitable means so as to not let light into the duct. WARNING: Placing the detectors into alarm will cause the control panel to go into alarm, discharge the extinguishing agent and shut down the process being protected. Reference the control panel manual or your Argus representative as to the best way to disable the extinguisher and shutdown circuits before testing detectors. The Argus Infrared Detector sensitivity is preset at the factory. Test with an infrared test light (part number 34016) and clean the detector lens is all that is required after installation. Argus strongly recommends that each detector be tested twice a year. Lenses should be checked and wiped cleaned at this time with a soft non-abrasive cloth. In applications where tints or dyes are used the lens should be inspected more frequently and cleaned as required. Testing (See above Warning) To test the detectors, drill a small hole (6 mm) halfway between detectors. Note: on applications where more than 2 detectors are used as in filter houses, it will be necessary to drill 2 or more holes. Place the hand held test light with the LED end into the hole and push the DET Test button. On the test unit, the green LED will come on acknowledging the test unit was fired. On the IR Spark Detectors, the red LED will come on. Ensure BOTH (or all) red LEDs came on. At this point, the panel should go into alarm, horn/strobe will activate. Reset the panel to normal condition if all operates as designed. If the red LED or control panel does not indicate an alarm status, further troubleshooting should be performed to determine the source of the problem. Consult with your Argus manuals and/or Argus representative if a solution is not readily obtainable. If the panel does not indicate alarm when signaled, then the fire protection system is not operating within specifications and the protected process must be shut down. Place a piece of black electrical tape over drilled hole to ensure no light leaks into duct work which will activate the spark detectors. Log date inspected for future reference. After a fire or alarm the detector lens must be inspected for damage. If the lens or the detector shows any signs of scorching or other damage the detector should be replaced. Note, since damage to detector may not be visible, Argus highly recommends that a test of the detector be conducted. Also, before resetting detector(s) an investigation of the cause should be conducted in effort to eliminate future occurrences. No internal maintenance is required unless the unit does not respond to the test light, in which case the unit should be replaced and returned to Argus. page: 10
13 5.0 warranty The Argus Fire Control (Argus) components of your Fire Protection System supplied to you by Argus are warranted to you as the original purchaser for one year from the date of delivery against defect in workmanship and material. Argus will replace or repair any Argus-supplied component which, in its opinion, is defective and has not been tampered with or subjected to misuse, abuse or exposed to highly corrosive conditions; provided that the System has been installed and maintained in accordance with the installation manual, that written notice of the alleged defect shall have been given to Argus within 30 days after discovery thereof and prior to the expiration of one (1) year after delivery, and that, if Argus so instructs, such article or part thereof is promptly returned to Argus with shipping charges prepaid. Purchased products which are supplied but not manufactured by Argus are warranted against defects resulting from the manufacturer s fabrication, process or parts for one (1) year from the date of purchase. Evaluation of each reportedly defective product returned to Argus will be made by the original manufacturer or an agent thereof and their judgment will be final. Disclaimer of liability and limitation of damages: Except as stated in the warranty above, Argus makes no other warranties whatsoever for this particular system, whether express or implied, including the warranties of merchantability and fitness for any particular purpose. Argus does not assume, or authorize any person to assume for it, any other liability in connection with the sale of this system. Under no circumstances shall argus be liable for any special, incidental, consequential, or indirect damages resulting from the use of the system. Argus s maximum liability for any direct damages shall be limited to the purchase price paid by the distributor for the system. page: 11
14
Advantium 2 Plus Alarm
ADI 9510-B Advantium 2 Plus Alarm INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Carefully Read These Controls Corporation of America 1501 Harpers Road Virginia
More informationSolar Power Systems Models: PVS220W-24 and PVS220W-48 Installation Manual
Solar Power Systems Models: PVS220W-24 and PVS220W-48 Installation Manual 255379 Rev. D0 1015 Printed in U.S.A. Copyright 2015 Federal Signal Corporation Limited Warranty The Alerting and Notification
More informationInstallation Instructions
520 Installation Instructions Thank you very much for purchasing PIAA product. Please read this entire manual before installation and use of this product. For Installers Please give this Installation Manual
More informationSOLAR ELECTRIC MODULE ES-124 & ES-62T Owners Manual and Installation Guide
SOLAR ELECTRIC MODULE ES-124 & ES-62T Owners Manual and Installation Guide circuit. Reverse connection will damage the module and may result in fire. CAUTIONS Solar electric modules produce DC electricity
More informationInstallation and Operation Manual. Digital Remote Meter for Monitoring System Performance. Version: RM-1
REMOTE METER TM Installation and Operation Manual. Digital Remote Meter for Monitoring System Performance. Version: RM-1 1098 Washington Crossing Road Washington Crossing, PA 18977 USA www.morningstarcorp.com
More informationHotLok Pass Through Blanking Panel
HotLok Pass Through Blanking Panel Part Numbers 1U - 10112 2U - 10113 Table of Contents Tools Required for Installation Page 2 Dimensions and Rack Requirements Page 2 Installation Procedures Page 3 Removal
More informationOPERATING MANUAL CONTRACTOR STYLE AXIAL FANS
Manual No. BLWR043 Rev. 4 September 2012 OPERATING MANUAL CONTRACTOR STYLE AXIAL FANS CVF-8AC CVF-8AC50 CVF-6ACAN CVF-15ACAN CVF-25ACAN CVF-8A15KIT CVF-8A25KIT MODELS: CVF-8DC CVF-6DCAN CVF-15DCAN CVF-25DCAN
More informationOwner s Manual & Safety Instructions
Owner s Manual & Safety Instructions Save This Manual Keep this manual for the safety warnings and precautions, assembly, operating, inspection, maintenance and cleaning procedures. Write the product s
More informationSSW-iLM Keypad. Wire Harness Configuration. Note: This product is designed to be installed and serviced by security and lock industry professionals
SSW-iLM Keypad Note: This product is designed to be installed and serviced by security and lock industry professionals Specifications Case dimensions: 6 1/2 L x 1 3/4 W x 1 1/8 D Electrical: 5-12VDC Only
More informationDual Laser InfraRed (IR) Thermometer
User s Manual Dual Laser InfraRed (IR) Thermometer MODEL 42511 Introduction Congratulations on your purchase of the Model 42511 IR Thermometer. This Infrared thermometer measures and displays non-contact
More informationPASSIVE INFRARED INTRUSION DETECTOR PASSIVE INFRAROOD DETECTOR DETECTEUR D INTRUSION PASSIF INFRAROUGE
MODEL HAA51 PASSIVE INFRARED INTRUSION DETECTOR PASSIVE INFRAROOD DETECTOR DETECTEUR D INTRUSION PASSIF INFRAROUGE OPERATING MANUAL HAA51 PASSIVE INFRARED INTRUDER DETECTOR INTRODUCTION HAA51 Passive Infrared
More information12 Volt 30 Amp Digital Solar Charge Controller
12 Volt 30 Amp Digital Solar Charge Controller User s Manual WARNING Read carefully and understand all INSTRUCTIONS before operating. Failure to follow the safety rules and other basic safety precautions
More informationDual Laser InfraRed (IR) Thermometer with Color Alert
User Manual Dual Laser InfraRed (IR) Thermometer with Color Alert MODEL 42509 Introduction Congratulations on your purchase of the Model 42509 IR Thermometer with Color Alert. This Infrared thermometer
More informationDTM04 TANK MONITOR DTM08 TANK MONITOR Dtm12 TANK MONITOR. Installation and Operation Manual
DTM04 TANK MONITOR DTM08 TANK MONITOR Dtm12 TANK MONITOR Installation and Operation Manual 1 ENGLISH Safety Instructions 2 Features 2-3 Specifications 3 Installation 4-5 Wiring Diagrams 6-7 Warranty 8
More informationRI-215A Operator s Manual. Part Number: 71-0045RK Revision 0 Released: 10/3/05
RI-215A Operator s Manual Part Number: 71-0045RK Revision 0 Released: 10/3/05 Warranty RKI Instruments, Inc., warrants gas alarm equipment sold by us to be free from defects in materials and workmanship,
More informationDigital Fingerprint safe
Digital Fingerprint safe Model 96846 Operation Instructions Diagrams within this manual may not be drawn proportionally. Due to continuing improvements, actual product may differ slightly from the product
More informationWARNING: FAILURE TO FOLLOW THESE RULES MAY RESULT IN SERIOUS PERSONAL INJURY CAUTION: INSTALLATION LOCATION:
Revision Level: 01 Revision Date: 07/07/2011 Please read all instructions carefully to help ensure a correct and SAFE installation of your Second Wind Ultraviolet Germicidal Air Purifier. Failure to do
More informationSingle Station Remote Alarm
ADI 5106G Certified ISO 9001:2000 Single Station Remote Alarm 529 5106-01-120 529 5106-01-220 INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Controls Corporation
More informationModel SRMD Setra Remote Monitoring Display
Model SRMD Setra Remote Monitoring Display 1.0 GENERAL INFORMATION Thank you for purchasing the Setra Remote Monitoring Display (SRMD). The SRMD is a digital panel meter with a bright 1 LED display for
More informationWater Leak Detection System
Water Leak Detection System Installation and Operating Manual 505-334-5865 ph 505-334-5867 fax www.rodisystems.com email:info@rodisystems.com 936 Highway 516 Aztec, NM 87410-2828 Manual Revisions and Copyright
More informationInstallation Guide. WSD-100 Wind Speed and Direction Sensor For XR5 Data Loggers. February, 2011
WSD-100 Wind Speed and Direction Sensor For XR5 Data Loggers Installation Guide February, 2011 Pace Scientific Inc www.pace-sci.com Tel: 704-799-0688 sales@pace-sci.com 1 Disclaimer The following warranty
More informationFIRERAY 2000 Installation Guide
FIRERAY 2000 Installation Guide Features Range 33ft to 330 ft. 24Vdc operation Selectable alarm thresholds Low current consumption Ground level electronics Manual or Automatic reset System Description
More informationLiteAide OWNER'S MANUAL PREASSEMBLED AUTOMATIC SECURITY FLOODLIGHTS MOTION SENSOR SECURITY LIGHTING SYSTEMS
OWNER'S MANUAL PREASSEMBLED AUTOMATIC SECURITY FLOODLIGHTS MOTION SENSOR SECURITY LIGHTING SYSTEMS LiteAide HE-100B HE-100BW HE-112 HE-112W HE-117 HE-117W HE-117-2B OWNER'S MANUAL FLOOD LAMPS (BULBS) Your
More informationVARIO PROX CARD READER INSTALLATION MANUAL
VARIO PROX CARD READER INSTALLATION MANUAL TABLE OF CONTENTS 1.0 INTRODUCTION...2 1.1 Legend...3 1.2 Terminology...4 2.0 MOUNTING...5 3.0 WIEGAND CONNECTION...6 4.0 AUX BUTTON INPUT...7 5.0 INSTALLER PROGRAMMING...8
More informationRetractable Screen. Replacement Screen Instructions
Retractable Screen Patent Pending Replacement Screen Instructions For RTS, RET, & RTM Products ATTENTION! Retractable screens are not intended to provide security or provide for the retention of objects,
More informationWATERBUG@ INSTALLATION / OWNERS MANUAL MODEL WB-200. PN # D-01 l-0007
WATERBUG@ INSTALLATION / OWNERS MANUAL MODEL WB-200 PN # D-01 l-0007 REV B INTRODUCTION Thank you for your purchase of the Winland WaterBug@ mode I WB-200. The WaterBug@ is completely electronic and is
More informationDC REFRIGERATORS 12/24 VOLTS INSTALLATION AND OWNER S MANUAL
DC REFRIGERATORS 12/24 VOLTS INSTALLATION AND OWNER S MANUAL Service Information If service or parts are required, contact the nearest Norcold Service Center. To find an authorized Norcold Service Center
More informationDestiny Shower Enclosure Installation Instructions
Destiny Shower Enclosure Installation Instructions IMPORTANT Please read carefully the following instructions before installing your shower enclosure. If you have any questions on this shower enclosure
More informationDome Security Camera with IR night vision
Dome Security Camera with IR night vision EN INSTRUCTION MANUAL 1 Before you begin Limited Warranty Terms & Conditions Swann Communications warrants this product against defects in workmanship and material
More informationLCD5500Z / PKP-LCD v3.x Installation Instructions
LCD5500Z / PKP-LCD v3.x Installation Instructions TM Introduction The LCD5500Z / PKP-LCD keypad displays system status using an LCD screen. The keypad can be used on PowerSeries security systems with up
More informationInfrared Viewers. Manual
Infrared Viewers Manual Contents Introduction 3 How it works 3 IR viewer in comparison with a CCD camera 4 Visualization of infrared laser beam in mid-air 4 Power Density 5 Spectral sensitivity 6 Operation
More informationOperator s Manual. Pressure Injection Cell Model PC8500. Congratulations! Contents
Operator s Manual Pressure Injection Cell Model PC8500 Congratulations! Congratulations on your purchase of a Next Advance Pressure Injection Cell. Please read this operator s manual which explains proper
More informationAmps Per Bank. Total Output. Battery System. Model Name. 6 amps 12 amps 10 amps 20 amps 30 amps 40 amps 15 amps 30 amps 45 amps
Model Name Total Output Amps Per Bank Battery System Pro XL Dual Pro XL Pro SE Dual Pro SE Three Bank Pro SE Four Bank Pro SE Pro Charger Dual Pro Charger Three Bank Pro Charger 6 amps 12 amps 10 amps
More information12 Volt 30 Amp Digital Solar Charge Controller Installation & Operation Manual
12 Volt 30 Amp Digital Solar Charge Controller Installation & Operation Manual This 30Amp charge controller is designed to protect your 12Volt Lead-acid or Gel-cell battery from being overcharge by solar
More informationDual Laser InfraRed (IR) Thermometer
User Manual Dual Laser InfraRed (IR) Thermometer MODEL 42570 Introduction Congratulations on your purchase of the Model 42570 IR Thermometer. This Infrared thermometer measures and displays non-contact
More information6 & 12 Volt Battery and Systems Tester with 100 Amp Load
6 & 12 Volt Battery and Systems Tester with 100 Amp Load Form No. 841-731 -000 DESCRIPTION This Load Tester tests 6 or 12 volt automotive-size lead-acid batteries under load. It will also test 6 or 12
More informationDigital echo-charge. Owner s Manual. Xantrex Digital echo-charge Battery Charger
Digital echo-charge Owner s Manual Xantrex Digital echo-charge Battery Charger Thank you for purchasing a Xantrex Digital echo-charge. Xantrex Technology Inc. takes pride in manufacturing quality products
More informationE-PDD Duct Smoke Detector Installation Sheet
E-PDD Duct Smoke Installation Sheet Operation The duct smoke detector's primary purpose is to provide early warning of an impending fire and shut down the HVAC unit in order to prevent smoke from circulating
More information*PATENT PENDING. NS1100 / NS2200 Installation Manual & Owner s Guide
*PATENT PENDING NS1100 / NS2200 Installation Manual & Owner s Guide Installation Tips Contents 1 Control Panel 1 Spool of Signal Wire 2 Mounting Screws & Drywall Inserts 2 Wire Clips 3 Wire Ties Tools
More informationTS93 EMR T/PT/TDE. Surface applied door closer
TS EMR T/PT/TDE Surface applied door closer Installation instructions: Pull side track mount door closer with smoke detector (EMR T) Push side track mount door closer with smoke detector (EMR PT) Double
More informationWINEGARD MOTORIZED SENSAR ANTENNA Models MA1055W & MA1055G MADE IN U.S.A. U.S. Patents D500,496 and 7,358,909 INSTALLATION MANUAL
WINEGARD MOTORIZED SENSAR ANTENNA Models MA1055W & MA1055G MADE IN U.S.A. U.S. Patents D500,496 and 7,358,909 INSTALLATION MANUAL CAUTION: This system is not for use with antenna in raised position while
More informationcbperformance.com Please read this entire brochure prior to installing your CB Performance Products MAGNASPARK II distributor.
- Easy -wire installation with no external spark box necessary, but can be used with one. - Precision CNC machining and hand assembled construction. This is a premium product. - Accurate super hot spark
More informationRAY-MAX Integrated Solar Power Strip
RAY-MAX Integrated Solar Power Strip 600008, 600009, 600010, 600208, 600209, 600210 Owner s Manual NEXTRONEX, INC. Revision Date: 10/27/14 Contents 1. Safety Instructions... 3 2. General Equipment Warnings...
More informationCeiling Mount Air Handler Manual
www.surna.com 303.993.5271 Ceiling Mount Air Handler Manual Models: CMAH12, CMAH18, CMAH24, CMAH30, CMAH36, CMAH48, CMAH60 Revised: September 2014 Table of Contents Warranty Information 4 Limited Warranty
More informationUSE &CARE GUIDE. Remote Faucet Pump System. See Important Safeguards on page 2
Remote Faucet Pump System USE &CARE GUIDE See Important Safeguards on page 2 An exclamation point within an equilateral triangle is intended to alert user to the presence of important operating and maintenance
More informationUtility Distribution Systems
Utility Distribution Systems 6/2012 A0011037 1 WARRANTY This equipment is warranted to be free from defects in materials and workmanship, under normal use and service, for a period of 12 months from date
More informationPOOL SUNSHINE IONIZER MODELS SPD, SPD2 AND SPS INSTALLATION INSTRUCTIONS
Sunshine Pool Products, LLC Manufacturer of Quality Pool & Spa Products 902 W 2010 S, Syracuse, Utah 84075 USA Voice: 801-825-4523 Website: www.sunshinepool.com Email: info@sunshinepool.com POOL SUNSHINE
More informationLondon Farm Kitchen Sinks
INSTALLATION INSTRUCTIONS CARE AND MAINTENANCE London Farm Kitchen Sinks 24" Sink model number 35120 30" Sink model number 35130 36" Sink model number 35140 Certified to comply with ANSI A112.19.3.M CAN/C.S.A
More informationPre-Fab Easy Installation For Models: 006-CT-USK, 008-CT-USK Installation and Operating Instructions for Existing Homes with Standard Piping
Instruction Sheet 102-140 Pre-Fab Easy Installation For Models: 006-CT-USK, 008-CT-USK Installation and Operating Instructions for Existing Homes with Standard Piping Plant I.D. 001-1024 EFFECTIVE: November
More informationDSM155 Digital LED Light Meter User s Manual DSM155
DSM155 Digital LED Light Meter User s Manual DSM155 CONTENTS TABLE OF CONTENTS......3 LIMITED WARRANTY AND LIMITATION OF LIABILITY......3 Out of Box....3 Accessories....3 Safety Information....3 Certification....5
More informationGlobal Water Instrumentation, Inc.
Global Water Instrumentation, Inc. 11390 Amalgam Way Gold River, CA 95670 T: 800-876-1172 Int l: (916) 638-3429, F: (916) 638-3270 Solar Panels 2 Watt Solar Panel: SP101 5 Watt Solar Panel: SP102 01-752
More information3 IN 1 BATHROOM HEATER
3 IN 1 BATHROOM HEATER MODEL NO.: A515 - SH MINI FUNCTION: HEATER, EXHAUST FAN AND LIGHT Dear customers, Thank you for selecting the AUPU 3 in 1 Bathroom Heater. Please read all instructions before commencing
More informationAuto Dialer. Manual E-921APQ E-921GPQ
Troubleshooting: Auto dialer will not arm/disarm Auto dialer will not dial out Unit doesn t respond to a call-back Difficulty in activating room monitor by telephone remote control Make sure that you have
More informationMobile Data Power Model: MDP-25
Mobile Data Power Model: MDP-25 Topic Section Features... 2 Operational Features Summary... 2 Back-up Battery Power Internal Charger Voltage Spike Protection RF Noise Filtering Warning of Imminent Loss
More informationManual for Fire Suppression & Methane Detection System
Manual for Fire Suppression & Methane Detection System Fogmaker North America Post address: 150 Gordon Dr Exton, PA 19341 Delivery address: 150 Gordon Dr Exton, PA 19341 Tel: 610-265-3610 Fax: 610-265-8327
More informationAGS. Owner's Manual. Xantrex Automatic Generator Start Control System
AGS Owner's Manual Xantrex Automatic Generator Start Control System TABLE OF CONTENTS INTRODUCTION...3 Main Features...3 Safety Summary...3 THINGS YOU SHOULD KNOW...4 THEORY OF OPERATION...5 System...5
More informationCanopy Surge. User Manual
Canopy Surge Suppressor User Manual SS00-UM-en Issue 2 May 2003 2003 Motorola, Inc. All rights reserved. Printed in the U.S.A Notices Safety Precautions: Before beginning your installation, please read
More informationINSTALLER S & OWNER S MANUAL
INSTALLER S & OWNER S MANUAL HVAC INSTALLER: PLEASE LEAVE MANUAL FOR HOMEOWNER DEH 3000 DEH 3000 Part No. 4028539 Dehumidifier & Ventilation System Controller P.O. Box 8680 Madison, WI 53708 TOLL-FREE
More informationFPU SYSTEMS OPERATION MANUAL BOH OFFICE MODULE (INCLUDING REPAIR PARTS & SPECIAL TOOL LIST) BOH FPU Field Pack/up Units CHAPTER 5
FPU SYSTEMS OPERATION MANUAL BOH OFFICE MODULE (INCLUDING REPAIR PARTS & SPECIAL TOOL LIST) BOH FPU Field Pack/up Units CHAPTER 5 UNIT MAINTENANCE INSTRUCTIONS This page was intentionally left blank 0022
More informationDetector transparent with Color Inserts. FAA 500 TR P Trim Ring transparent with Color Inserts. FCA 500 / FCA 500 E Detector Bases
Detector Color Detector transparent with Color Inserts FAA 500 TR W Trim Ring FAA 500 TR P Trim Ring transparent with Color Inserts FAA 500 BB Ceiling Mount Back Box FCA 500 / FCA 500 E Detector Bases
More informationUniversal Vehicle Power Supply 9007AX01. Installation Instructions
Universal Vehicle Power Supply 9007AX01 Installation Instructions Disclaimer Honeywell International Inc. ( HII ) reserves the right to make changes in specifications and other information contained in
More informationUser Manual. Humidity-Temperature Chart Recorder. Model RH520
User Manual Humidity-Temperature Chart Recorder Model RH520 Introduction Congratulations on your purchase of the Extech RH520 Temperature + Humidity Chart Recorder. The RH520 measures and displays Temperature,
More informationRT-200 HI-TEST ROPE TESTER
RT-200 HI-TEST ROPE TESTER Operating & Instruction Manual HD ELECTRIC COMPANY 1 4 7 5 L A K E S I D E D R I V E W A U K E G A N, I L L I N O I S 6 0 0 8 5 U. S. A. P H O N E 8 4 7. 4 7 3. 4 9 8 0 FA X
More informationLST-3800. In-Dash Digital Sonar Gauge. Installation & Operation Instructions
Pub. 988-0064-351 LST-3800 In-Dash Digital Sonar Gauge Installation & Operation Instructions The LST-3800 is a depth and temperature gauge that comes with a 200 khz transducer, features deep and shallow
More informationInHome Water Leak Detection Package
InHome Water Leak Detection Package For Model Numbers ILD10A-L and ILD10A-B Installation Guide / Wiring Diagram For Creating Water Leak Detection-based Events with Line-Powered or Battery-Powered Sensors
More informationUNIVERSAL LUMBAR INSTALLATION INSTRUCTIONS
UNIVERSAL LUMBAR INSTALLATION INSTRUCTIONS CONTENTS Parts List... 2 Parts Diagram... 2 Helpful Hints... 3 Installation... 4 Operation and Troubleshooting Guide... 6 Warranty Information... 8 Form #3132,
More informationInstallation Guide 2010 BMW S1000RR Full Exhaust System
Installation Guide 2010 BMW S1000RR Full Exhaust System!! THIS PRODUCT IS DESIGNED FOR USE IN CLOSED COURSE RACING AND IS NOT INTENDED FOR HIGHWAY USE!! Congratulations on the purchase of your new TaylorMade
More informationPGL5/6 - Parking Garage Luminaire Installation Instructions
P.O. Box 60080 16555 East Gale Ave. City of Industry, California 91716-0080 626/968-5666 FAX 626/330-3861 PGL5/6 - Parking Garage Luminaire Installation Instructions PGL51/61 PGL52/62 PGL53/63 PGL54/64
More informationSolar Home System. User Manual. AEH-SHS01-10W2L Solar Home System 2 Lamps
Solar Home System User Manual AEHSHS0110W2L Solar Home System 2 Lamps All rights reserved Specifications subject to change without prior notice 2 Dear Customer, Thank you for purchasing Schneider Electric
More informationAutomatic Phone-Out Home Monitoring Systems
Automatic Phone-Out Home Monitoring Systems Power Outage and Freeze Alarm Model Number: THP202 Power Outage, Freeze and Flood Alarm Product Description Model Number: THP201 These monitoring systems are
More informationHG600/HG800. Hydro-Power Unit. Installation and Operation Guide
HG600/HG800 Hydro-Power Unit Installation and Operation Guide Copyright 04 HydroSpin, All rights reserved. The data contained in this document is proprietary to HydroSpin. It is disclosed to the receiving
More informationName of Equipment Silver King Model SKMCD1P/C1. This equipment chapter is to be inserted in the appropriate section of the Equipment Manual.
Name of Equipment Silver King Model SKMCD1P/C1 This equipment chapter is to be inserted in the appropriate section of the Equipment Manual. Manufactured exclusively for McDonald s By Silver King Refrigeration,
More informationInstallation Instructions for Solar Pumps USER MANUAL FOR SPS, SPC, SPSC SPQB, SPGJ SERIES SOLAR PUMPS AND PUMP CONTROLLERS
Installation Instructions for Solar Pumps USER MANUAL FOR SPS, SPC, SPSC SPQB, SPGJ SERIES SOLAR PUMPS AND PUMP CONTROLLERS PO Box 80, Tuakau 2342 ph 0800 14 48 65 e-mail: hunkin-garden@xnet.co.nz www.hunkin.co.nz
More informationTABLE OF CONTENTS. I. TROUBLESHOOTING... 2 - Section 1.01: Common Problems/Solutions... 2
BAL Accu-Slide System I. Table of Contents TABLE OF CONTENTS I. TROUBLESHOOTING... 2 - Section 1.01: Common Problems/Solutions... 2 II. GETTING STARTED... 5 - Section 2.01: Tools You Will Need... 5 - Section
More informationUltra-Violet Products Ltd 2066 W 11th Street, Upland, CA 91786 Unit 1, Trinity Hall Farm Estate
UV/Air Circulator For the UV PCR Workstation User Instructions UVP, LLC Ultra-Violet Products Ltd 2066 W 11th Street, Upland, CA 91786 Unit 1, Trinity Hall Farm Estate Tel: (800) 452-6788 / (909) 946-3197
More informationOwner s Manual & Safety Instructions
Owner s Manual & Safety Instructions Save This Manual Keep this manual for the safety warnings and precautions, assembly, operating, inspection, maintenance and cleaning procedures. Write the product s
More informationContractors Guide Central Inverter System Installation
Contractors Guide Central Inverter System Installation Step By Step Procedures 2,200 Watt/VA 6 Step Installation 1. Mount Bottom Cabinet 2. Mount Top Cabinet 3. Install Batteries 4. Install Conduit 5.
More informationINSTALLATION & OPERATION MANUAL LED
INSTALLATION & OPERATION MANUAL LED Duo Beam TM Introduction... 2 Lightbar Unpacking & Pre-Installation... 2 Installation & Mounting... 3 Wiring Instructions... 4 Maintenance... 4 Flash Pattern Selection...
More informationAmplified High Speed Fiber Photodetectors
Amplified High Speed Fiber Photodetectors User Guide (800)697-6782 sales@eotech.com www.eotech.com Page 1 of 7 EOT AMPLIFIED HIGH SPEED FIBER PHOTODETECTOR USER S GUIDE Thank you for purchasing your Amplified
More informationIR Repeater. Operation Manual P8620
IR Repeater Operation Manual P8620 Congratulations on your purchase of the P8620 IR Repeater. This operating manual will provide a guide to installation and operation of the product. Please read thoroughly
More informationVERTICAL / FIXED BEAM CLAMP I-BEAM ANCHOR ADJUSTABLE FROM 4-14 Model # HD26249
VERTICAL / FIXED BEAM CLAMP I-BEAM ANCHOR ADJUSTABLE FROM 4-14 Model # HD26249 IMPORTANT!!! ALL PERSONS USING THIS EQUIPMENT MUST READ AND UNDERSTAND ALL INSTRUCTIONS. FAILURE TO DO SO MAY RESULT IN SERIOUS
More informationSP4-LOC SAFEPATH4 REMOTE MICROPHONE AND LOCAL OPERATOR CONSOLE
SP4LOC SAFEPATH4 REMOTE MICROPHONE AND LOCAL OPERATOR CONSOLE INSTALLATION AND OPERATION MANUAL MASS NOTIFICATION SYSTEM Part Number: P84767 Rev. A Copyright 2006 Cooper Wheelock, Inc. All rights reserved.
More informationATS Overhead Table Shelf System INSTRUCTION MANUAL
ATS Overhead Table Shelf System INSTRUCTION MANUAL ATS Overhead Table Shelf System Instruction Manual Warranty Newport Corporation warrants this product to be free of defects in material and workmanship
More informationPassive Infrared Motion Detector 5420/90. Installation Instructions
Passive Infrared Motion Detector Installation Instructions 5420/90 The 5420/90 Passive Infrared Motion Detector provides reliable, high performance detection at an affordable price. The Detector features
More information1 ELGOTEAM ADVANCED SECURITY SYSTEMS Bi-directional spike barrier. Bi-directional spike barrier Customer Information packet
1 Customer Information packet For more information: info@elgoteam.com www.elgoteam.com 2 Chapter contents Subject Page number The company 3 Background 4 Applications 5 Advantages 6 Operating positions
More informationWireless Indoor/ Outdoor Thermometer
Wireless Indoor/ Outdoor Thermometer Owner s Manual Please read before using this equipment. ˆ Contents FCC Information... 3 FCC Declaration of Conformity... 5 Preparation... 5 Installing Batteries...
More informationSECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines
PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting
More informationDORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS
Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short
More informationInstallation Instructions
Installation Instructions E19-120 (Plastic showerhead) E19-120A (Stainless steel showerhead) E19-120SS (All Stainless Steel) Drench Shower - Horizontal Supply Table of Contents Pre-Installation Information..........................2.............................3
More informationSELECTION, APPLICATION AND MAINTENANCE
DIESEL PROTECTION SYSTEMS Automatic Diesel Engine Shut Down System for Safe Area Applications SELECTION, APPLICATION AND MAINTENANCE Series 300 Series 310 SYSTEM DESCRIPTION Suitable for attended engine
More informationDome Camera with IR Night Vision
Dome Camera with IR Night Vision Instruction Manual VER.:1.0, NO.: R040687/2 Thank you for purchasing our product. Before installing this camera, please read this instruction manual carefully to ensure
More informationTriple Threat 3-in-1 Game Table 3 IN 1 GAME TABLE
NG0M Triple Threat 3-in- Game Table 3 IN GAME TABLE Thank 3 in Y Game Table Thank you for your purchase of our product. We work around the clock and around the globe to ensure that our products maintain
More informationD7050/D7050TH. Installation Instructions. Multiplex Photoelectric Smoke Detectors
D7050/D7050TH EN Installation Instructions Multiplex Photoelectric Smoke Detectors D7050/D7050TH Installation Instructions.0 Description Notices These instructions cover the installation of the D7050/D7050TH
More informationOASIS-PLUS 120V READ ALL INSTRUCTIONS BEFORE OPERATING READ ALL INSTRUCTIONS BEFORE OPERATING OZONE IS A POWERFUL OXIDIZER AND MUST BE USED WITH CARE
OASIS-PLUS 120V INFORMATION & OPERATING INSTRUCTIONS READ ALL INSTRUCTIONS BEFORE OPERATING READ ALL INSTRUCTIONS BEFORE OPERATING OZONE IS A POWERFUL OXIDIZER AND MUST BE USED WITH CARE 56041852 WARNING:
More informationOperation Manual. 150 Watt Halogen Light Source for Endoscopy Model # s ESS-150, ESS-150A ESS-220, ESS-220A
Operation Manual 150 Watt Halogen Light Source for Endoscopy Model # s ESS-150, ESS-150A ESS-220, ESS-220A Endoscopy Support Services, Inc. Croton River Executive Park Route 22, Bldg. 3 Brewster, NY 10509
More informationInstallation Instructions: (Part # SB76880) XRC Armor Front Fender Kit
WARNING: Check with Local and State laws before installing this accessory! NOTE: Carefully read entire instructions thoroughly before attempting to install this part. Parts Included: Qty Parts Included:
More informationCooktop Low-Profile Ventilation Hoods
INSTALLATION GUIDE Cooktop Low-Profile Ventilation Hoods Contents Wolf Cooktop Low-Profile Ventilation Hoods........ 3 Cooktop Low-Profile Hood Specifications.......... 4 Cooktop Low-Profile Hood Installation............
More informationMBA-MM-1040/10/13/1665 MULTI MEDIA FILTERS
MASTER Water Conditioning Corp. www.masterwater.com Installation and Operation Manual MBA-MM-1040/10/13/1665 MULTI MEDIA FILTERS with the 263/742 Logix Control Valve June 2010 Table of Contents Page No.
More informationAUTOMATIC BEST BATTERY SELECTOR INSTALLATION & OPERATION BBS-1600 BBS-1600E
AUTOMATIC BEST BATTERY SELECTOR INSTALLATION & OPERATION BBS-1600 BBS-1600E SENS part no: 101314 Document revision: F DCN No. 106811 Date 8/3/15 1840 Industrial Circle Longmont, CO 80501 Fax: (303) 678-7504
More information