Compact Solar Drainback System SECUSOL

Size: px
Start display at page:

Download "Compact Solar Drainback System SECUSOL"

Transcription

1 TECHNICAL INFORMATION / INSTALLATION INSTRUCTIONS Compact Solar Drainback System SECUSOL Operational Safety and Low Maintenance When the pump is not operating, there is no solar fluid present in the collectors. Therefore the solar fluid and any downstream system components are protected against detrimental effects from overheat. Unwanted gravitational forces as well as operational faults due to air pockets are eliminated. A service intensive membrane expansion vessel, air bleeds and check valves are not required. Operation with common anti-freeze solar fluid prevents potential frost damage. High Yield Thanks To: High transparency anti reflection glass Single surface absorber with selective vacuum coating Solid insulation of individual components Simplified Installation and Start-Up Pre-assembled unit of storage tank, solar controller and solar circulator, including all safety components. Flexible copper double-pipe with only mm cross section, for simple and time saving piping (supplied by Wagner & Co). No expansion vessel and hence no setting of pre-pressure required. Very simple flushing and filling No venting of solar circuit required Installation, startup and maintenance of the SECUSOL solar thermal installation are intended to be carried out by trained professionals only, e.g. in line with SRCC Standard OG-300 installation guidelines or NABCEP certification. They have to be licensed, must be familiar with the IAPMO Uniform Solar Energy Code and must conform to applicable federal, state and local regulations, codes, standards and meet all legal requirements related to the installation of solar hot water systems as well as plumbing, electrical wiring and roof works. Content Technical Information. Technical Data. Scope of Supply 8.3 Accessories 4 General Safety Notes 6. Symbols 6. Standards and Codes 6.3 Qualification of the Installer 7.4 Intended Use and Application 7.5 Pre Installation Notes 8.6 Function of the SECUSOL system 8 Figure SECUSOL-System 3 Installation 9 3. Preparation 9 3. On-Roof Installation Free Standing Installation General Notes about Storage Installation Setting up the Storage Tank Connection to Domestic Water Supply Laying the Solar Circuit Installing the Controller 35 4 Startup DHW System Backup Heating Circuit Solar Circuit 36 5 Connecting the storage Insulation 38 6 Advice for the User 38 7 Maintenance and Care 39 8 Troubleshooting 40 Solar thermal / Collectors EN-USA_SECUSOL_TI-MA-03-R800

2 Technical Information. Technical Data Table Technical Data Features SECUSOL 50- SECUSOL 50- Solar collectors Type EURO C0 AR-M EURO L4 or EURO C0 AR-M Gross area / aperture area sq ft (m²) EURO C0 AR-M 8. sq ft (.6 m²) / 5.7 sq ft (.39 m²) EURO L4 4. sq ft (.5 m²) /.6 sq ft (.0 m² Collector racking Orientation of collector On roof or free standing Horizontal installation only (pitch of 0 85 ), max. permitted diversion from horizontal orientation: No. of collectors (cannot be extended) SECUSOL 350- Solar circuit Collector circuit material (on site) Cu mm, order as needed from Wagner Solar, see material requirements in table 8 Insulation material (accessory) see material requirements in table 8 Length of solar circuit (sum of flow and return legs) Minimum 6.4 ft (5 m) / maximum 98.4 ft (30 m) Maximum operating pressure Installation height ) 87 psi (6 bar) Minimum 3.3 ft ( m), from the bottom of the tank to the bottom of the collector Maximum 8 ft (approx. 8.5 m), from the bottom of the tank to the top of the collector Minimum temperature Frost resistant up to.4 F (-7 C), if correctly filled ) Heat transfer fluid in collector loop Water/propylene glycol mix only with 33 % glycol ), filling capacity:.9 to.95 Gal ( liters) Solar controller Name SUNGO US plus Pump control Speed controlled Overheat protection 80 F temperature limitation for the tank Storage Nominal content 66 Gal (50 l) 9. Gal (350 l) Stand by heating volume approx. 3 Gal (0 l) approx. 4 Gal (60 l) Total height (including insulation) 6.83 in (596 mm) 7.64 in (845 mm) Diameter (including insulation) 9.53 in (750 mm) Permissible operation pressure / Permissible operating temperature 45 psi / 03 F (0 bar / 95 C) Corrosion protection of the storage cylinder Cathodic corrosion protection Cold/hot water connections Sensor connection Solar heat exchanger Enamel coating according to DIN 4753 T3 Mg sacrificial anode acc. to DIN 4753 T6 " NPT (M) Clip in lower tank area approx..39 sq ft (.5 m²) Backup heating coil none / approx. 6.0 sq ft (0.65 m²), depending on type approx. 8.6 sq ft (0.8) m² Socket for electrical immersion heater, Position: Heat insulation (PU foam, polystyrene jacket) " NPSM (F) Cylinder and lid approx..5 in (75 mm) Base.57 in (40 mm) Weight 85.5 lb (9.5 kg) lb (39.5 kg) ) See Figure 8 page3. ) Lower edge of storage cylinder to lower edge of collector (Figure 8 page3). 3) In order to achieve higher frost protection, the glycol content needs to be increased to over 33 %. However, this results in increased pressure drop and hence a reduced maximum installation height and length of solar circuit. Please also observe the technical information of the solar liquid. If required feel free to contact our technical support. EN-USA_SECUSOL_TI-MA-03-R800

3 76.0 in/933 mm 3.5 in 80 mm EURO L4 HTF in/035 mm in/63 mm in/5 mm 4.33 in 0 mm EURO C0 AR M 4.79 in/087 mm in/5 mm Figure Dimensions of solar collectors EURO L4 (upper image) and EURO C0 AR-M (lower image). Throughout this document and all other Wagner & Co documentation the term flow refers to the hot, outgoing pipe leg, while the term return refers to the the colder, incoming leg of the heating or solar circuit (the one returning to the heat generating device). EN-USA_SECUSOL_TI-MA-03-R800 3

4 Table Storage dimensions in inch (mm) Pos. Dimension SECUSOL 50 SECUSOL 350 Total height (without insulation) 55.9 in (40 mm) in (797 mm) 4 Socket ("NPSM(F)), height above ground 34.3 in (867 mm) 44.7 in (36 mm) 7 Hot water connection (stainless steel and brass, NPT(M)) ), height above groand Cold water connection (stainless steel and brass, NPT(M)) ), height above ground 5.3 in (303 mm) 66.6 in (683 mm) 8.78 in (477 mm) 3 Solar flow / hot side (G ¾) ), height 3.7in (87 mm) 5 6 Backup heating flow / hot side ) (¾ NPTM(M)) ), height Backup heating return (¾ NPTM(M)) ) /colder side, height Diameter (without insulation) Base ring openings Solar return / colder side, pump flange height above ground Legend: ) Dimension position numbers from figures 3 and 4 ) Pipe thread DIN ISO 8- (cyl.), flat sealing If present: 36.0 in (97 mm) in (86 mm) If present: in (7 mm) 57.0 in (448 mm) 3.6 in (600 mm) Ø.8 in (300 mm) 3.8 in (350) mm 3/4" NPT(F) 7 " NPT(M) SECUSOL /4" NPT(M) 4 " NPSM (F).8 in 300 mm 5 3/4" NPT(M) 3 3/4" G " NPT(M) 8.78 in (477 mm) 3.7in (87 mm) 36.0 in (97 mm) in (7 mm) 5.3 in (303 mm) 55.9 in (40 mm) 3.6 in (600 mm) Figure 3 Dimensions SECUSOL 50 solar storage tank; () Flange with sacrificial anode; Dimensions of cylinders are without insulation. SECUSOL 50 is available with and without backup heat exchanger (upper coil). The image shows the version with upper coil. The version without upper coil does not feature the connections 5 and 6. 4 EN-USA_SECUSOL_TI-MA-03-R800

5 3/4" NPT(F) 7 " NPT(M) 6 3/4" NPT(M) " NPSM (F) in / 06 mm SECUSOL in 300 mm 5 3/4" NPT(M) 3 3/4" G " NPT(M) 8.78 in (477 mm) 3.7in (87 mm) in (86) 57.0 in (448 mm) 66.6 in (683 mm) in (797 mm) 3.6 in (600 mm) Figure 4 Dimensions of SECUSOL 350 solar cylinder (without insulation). () Flange with sacrificial anode EN-USA_SECUSOL_TI-MA-03-R800 5

6 On roof 76. in / 933 mm 3 EURO L in 63mm 9.57 in 36 mm >60 in / 4060 mm in 63mm Free standing setup 76. in / 933 mm >60 in / 4060 mm 4 EURO L in 63mm in 63mm Figure 5 Connection options for the EURO L4 for on-roof and free-standing installation, with sensor positions, dimensions of the collector field and racking system. The absorber connections can point to the left or to the right. () Solar sensor; () Rail; (3) Rafter bracket or roof anchor; (4) Racking triangle. 6 EN-USA_SECUSOL_TI-MA-03-R800

7 On roof in / 5 mm 3 EURO C0 AR-M in 5mm in 433 mm >77.7 in / 4500 mm in 5mm Free standing setup in / 5 mm >77.7 in / 4500 mm 4 EURO C0 AR-M in 5mm in 5mm Figure 6 Connection options for the EURO C0 AR-M for on-roof and free-standing installation, with sensor positions, dimensions of the collector field and racking system. The absorber connections can point to the left or to the right. () Solar sensor; () Rail; (3) Rafter bracket or roof anchor; (4) Racking triangle System air Solar liquid Collector Storage Storage System air Heat exchanger Solar liquid Pump System idle System in operation Figure 7 Design principle of the SECUSOL system. Left hand side: When in idle state, the collector loop and the collctor are filled with air (light-coloured lines). The solar fluid (darker lines) is located in the heat exchanger. Right hand side: When the system is in operation the air is pushed into the upper loops of the heat exchanger by the rising solar fluid. EN-USA_SECUSOL_TI-MA-03-R800 7

8 . Scope of Supply The complete system is delivered with the following components: Table 3 Components Qty. Collector EURO L4 or Collector EURO C0 AR-M or Solar storage, nominal content 50 l or 350 l, respectively (screwed onto pallet), incl. solar flow and return group with circulator and solar controller SUNGO US plus ) plug " NPSM (fixed to pallet), for closing the storage socket ) For details see Table 5 and Figure 8 Table 4 Scope of Supply Boxed components Customer information folder with instructions and system documentation Solar liquid DC0 F.5 l in 5 l canisters Collector adapter set coll. US Secusol serial connection set System with coll. side by side coll. one above the other US Secusol parallel connection set Roof anchor / rafter bracket (only for on-roof installation) ) ) Minimum no., actual no. depends on structural and geographical situation. Table 5 Scope of supply, storage SECUSOL 50 / SECUSOL 350 Position ) Components Quantity Jacket insulation Cover insulation 3 Ground insulation 4 Storage cylinder lid 5 Solar controller 6 Container 7 Socket cover with integrated protective anode 8 Solar return subassembly 9 Ventilation opening 0 Plug " NPSM Compression olive fitting mm 3 Storage cylinder connection nozzle 5 f Collector sensor k Collector sensor cable n Mains cable p Pump cable s Storage cylinder temperature sensor ) Position numbers from Figure 8. 8 EN-USA_SECUSOL_TI-MA-03-R800

9 4 7 5 f k p n s Figure 8 Scope of supply of the SECUSOL storage cylinder shown for the 50 l- (see table 5 for a position number legend). EN-USA_SECUSOL_TI-MA-03-R800 9

10 Set for single collector Figure 9 Single basic set for on-roof installation with collector EURO C0 AR-M Note The roof brackets shown throughout this document are of the type A Pro+, specifically developed for common North-American asphalt shingle roofs. For installation details refer to the separate instructions coming with the roof brackets. Other roofing types require different roof anchors. Table 6 On roof racking, set for single collector, scope of supply Single collector Pos. ) Components Quantity Part no. Rafter bracket or roof anchor (recommended)² ) (4) Collector rail 49.5 in / 57 mm (EURO C0 AR-M) with two collector clamps wire strip 4 Collector EURO C0 AR-M 5 Compression olive connection ½" - mm Gasket ½" ) Position no. from Figure 0 ) Not included in the set, to be ordered separately 0 EN-USA_SECUSOL_TI-MA-03-R800

11 Collector installation set for horizontal installation, one above the other Note The roof brackets shown throughout this document are of the type A Pro+, specifically developed for common North-American asphalt shingle roofs. For installation details refer to the separate instructions coming with the roof brackets. Other roofing types require different roof anchors. Figure 0 Set for on-roof installation of collectors installed one above the other Table 7 On roof racking, set of collectors installed one above the other, scope of supply Part no. Pos. ) Components Quantity for EURO C0 for EURO L4 Rafter bracket or roof anchor (recommended)² ) (8) 3 Collector rail 49.5 in / 57 mm (EURO C0 AR-M) or 47.3 in / 0 mm (EURO L4), respectively, with two collector clamps Collector rail 48. / 3 mm (EURO C0 AR-M) or in / 68 mm (EURO L4) with one collector clamp 4 Rail connector 5 Wire strap 6 Collector EURO C0 AR-M or L4 7 Collector interconnection hose with insulation pieces and flat seals 8 Compression olive connection ½" - mm 9 Gasket ½" 4 ) Position no. from Figure 0 ) Not included in the set, to be ordered separately EN-USA_SECUSOL_TI-MA-03-R800 EN-USA_SECUSOL_TI-MA-03-R800

12 Collector installation set for horizontal installation, next to each other Figure Set for installation of collectors next to each other Note The roof brackets shown throughout this document are of the type A Pro+, specifically developed for common North-American asphalt shingle roofs. For installation details refer to the separate instructions coming with the roof brackets. Other roofing types require different roof anchors. Table 8 On roof racking, set of collectors installed next to each other, scope of supply Part no. Pos. ) Components Quantity For EURO C0 For EURO L4 Rafter bracket or roof anchor (recommended)² ) (8) Collector rail 49.5 in / 57 mm (EURO C0 AR-M) or 47.3 in / 0 mm (EURO L4), respectively, with two collector clamps 3 Wire strap 4 Collector EURO C0 AR-M or EURO L4 5 Compression olive connection ½" - mm 4 6 Gasket ½" 4 7 Compression T-fitting mm 8 Copper tube mm 4 9 Foam insulation 4 ) Position no. from Figure ) Not included in the set, to be ordered separately EN-USA_SECUSOL_TI-MA-03-R800

13 Set for free standing rackets 8 3 Figure Set for free standing setup Table 9 Free standing racks, scope of supply Single collector; order no Position ) Components Quantity Pre-assembled racking triangle 4 Hexagonal head screw M8 x Nut M8 with locking teeth 4 4 Collector clamp lower part Collector clamp upper part Washer Ø 8.4 mm Hexagonal head screw M8 x Collector EURO C0 AR-M or EURO L4 ) ) Position numbers from Figure. ) Not included in the set Collectors next to each other; order x no EN-USA_SECUSOL_TI-MA-03-R800 3

14 .3 Accessories Table 0 Accessories Description Part no. Euro collector carrying handles ( pieces) Thermostatic Mixing Valve ¾" Twin Cu solar circuit pipe comprised of insulated double copper pipe mm with integrated temperature sensor line, 5 m coil Oval clamp set for for Twin-Cu Solar circuit insulation: flexible foam insulation 3x for single pipes (Aeroflex), 6.56 ft / m length, Flange cover gasket Magnesium sacrificial anode Temperature sensor Pt Storage cylinder height adjustment (always order 3!) Earthing clamps (order!) 0 00 US Sensor connection box SP EN-USA_SECUSOL_TI-MA-03-R800

15 Table 0 Accessories Description Part no. US Secusol parallel connection set US Secusol serial connection set Collector adapter set / -mm US_Secusol Cx-threaded elbow connection set mm x straight compression fitting mm EN-USA_SECUSOL_TI-MA-03-R800 5

16 General Safety Notes. Symbols The following symbols are used throughout these instructions and must be adhered to. READ ALL INSTRUC- TIONS CAREFULLY BEFORE BEGINNING INSTALLATION WORK: Immediate DANGER of serious personal injury, including risk of death and lifelong disability. WARNING against situations leading to possibly severe injuries and death. CAUTION against situations leading to minor injury and material damage.. Inspect for and remove frost and other slipping hazards before getting onto roof surfaces.. Cover and secure all skylights and openings, or install guardrails to keep workers from falling through the openings. 3. When the roof pitch is over 4: and up to 6:, install slide guards along the roof eave after the first 3 rows of roofing material. 4. When the pitch exceeds a 6: pitch, install slide guards along the roof eave 5. Use a safety harness system with a solid anchor point on steep roofs with a pitch greater than 8: or if the ground-to-eave height exceeds 5 feet. 6. Stop all operations on roofs when storms, high winds or other adverse weather conditions create unsafe conditions. 7. Remove or properly guard any impalement hazards. 8. Wear shoes with slip-resistant soles. Make sure to observe all federal, state, county and city regulations related to roof works and roof sealing standards as well as professional codes for plumbing work. Installers must be qualified and - where applicable - licensed to work on roofs. NOTICE of situations which may lead to property damage if no precaution is taken. Notes with additional important or useful information.. Standards and Codes Building and plumbing permits and/or inspections may be required for installation. Comply with all code requirements and applicable standards and regulations. Snow and wind loads - risk of injury from falling objects or collapsing structures Comply with federal, state, county and city regulations and standards related to snow and wind load as well as structural planning in general. Only install the installation set on roofs that can structurally support the additonal load. In case of doubt, always consult a structural engineer or a roofer. Follow the Solar Rating and Certification Organisation SRCC OG 300 guidelines for safe collector installation. Work on roofs - risk of fall and falling objects resulting in potentially serious injury and death We strongly recommend to follow the NAHB-OSHA Jobsite Safety Handbook, especially: Risk of injury and material damage resulting from improper handling of collector and storage Use soft crane straps for lifting collectors with crane (observe secure overhead transport!). Alternatively loop rope around the frame and pull collector up a secured ladder. We also recommend the use of two ladders and our special collector handles. Never attach ropes to collector connections and never use connection pipes as handles! Only use the crane hoisting lugs on top of the storage tank for crane transport. Observe good practice standards for construction sites. Object is heavy and can cause severe injuries and damage upon falling. Uniform Solar Energy Code The installation has to be carried out by a licensed professional in accordance with all professional standards, in particular all safety, health and environmental standards, as given by the IAPMO Uniform Solar Energy Code. For detailed information and to obtain the full text of the code contact IAPMO: International Association of Plumbing and Mechanical Officials 500 E. Philadelphia Street Ontario, CA USA System Integration During integration of the storage tank into the domestic water supply and connection of the solar controller, all national and local health and safety regulations must be complied with, including relevant lightning protection regulations. When installing a backup heating device please follow the manufacturer s guidelines. Follow the Uniform Solar Energy Code. 6 EN-USA_SECUSOL_TI-MA-03-R800

17 Conformity The SECUSOL solar energy system and its components were designed and manufactured in accordance with current European Union and United States laws and regulations. The system and its components are in compliance with SRCC OG 00, IAPMO and NSF testing and/or certification standards, where applicable. EN 806- and pren 77:999 Provided the system is installed correctly, the requirements of EN 806- and pren 77:999 are met. EN 976 and EN 977 The entire system was designed and manufactured according to the regulations in EN 976 and EN Qualification of the Installer Risk of injuries resulting from insufficient qualification Setup, installation and commissioning of the SECUSOL compact solar heating system must be carried out by authorized professionals (e.g. NABCEP or Wagner Academy certified or equivalent combination of knowledge and experience). The installation should be carried out following the guidelines established by the Solar Rating & Certification Corporation (SRCC). See SRCC OG 300: SOLAR WATER HEATING SYSTEM DE- SIGN AND INSTALLATION GUIDELINES, available on the SRCC website at Please note that in case of a warranty complaint the warranty is only valid if the correct start-up has been certified in a commissioning report. Contact us for further information..4 Intended Use and Application Collectors should be stored inside in a dry place. Outdoor storage can result in damage. For proper outdoor storage, remove PE film, and lay down collectors with glass pane up. Avoid direct ground contact (e.g. underlay square timber). Avoid scratches on glass panes by using spacers between collectors (e.g. wooden laths). When leaning collectors against walls or similar, use a minimum inclination of 5 and apply spacers. Do not use cardboard as underliner. If incorrectly stored, humidity can enter the collectors through the air vents. Storing collectors in foil package can damage the glass surface (Figure 3). Figure 3 Do not expose PE-film covered collector to rain mage, health risks and renders all warranty void. As operating mediums water (attention risk of freezing!) or an appropriate water-glycol mixture can be used in a closed circuit. Prolonged operation of the collector at conditions below the dew point temperature within the collector is not permitted! This can occur, for example, when collectors are integrated in the brine circuit of a heat pump. Preventing frost damage After pressure testing and flushing, collectors cannot always be completely emptied. Make sure that no pure water remains in collector during risk of frost! Unfilled collector on roof After being installed on the roof, unfilled collectors should not be exposed to the sun for more than a few days. Otherwise thermal stress on gaskets can result in damage. Alternatively postpone the installation of gaskets to just before filling the solar circuit. Maintenance only by trained professionals! Under normal operating conditions we recommend annual check and maintenance intervals. All testing, repair and maintenance work must be carried out by qualified and licensed professionals. For maintenance notes and additional information about setup and operation of the collector field, please refer to the technical information Solar Thermal Systems - Setup, Commissioning and Maintenance. Collectors: Scope and limitations of application The collector is intended for the application in solar thermal installations for hot water preparation and space heating support. ANY OTHER TYPE OF APPLICATION IS NOT PERMITTED unless explicitly permitted in writing by the manufacturer. Non compliance can lead to serious da- EN-USA_SECUSOL_TI-MA-03-R800 7

18 .5 Pre Installation Notes Risk of burns at collector connections! Collector connections can get very hot as soon as uncovered collector is exposed to the sun (figure 3). Wear gloves! Danger of open injuries! Always wear gloves to avoid severe cuts and lacerations when working with sharp edged metal sheets and components! Risk of damage to absorber! Remove protective plastic caps from connections before collector is exposed to the sun. Risk of molten plastic entering and damaging the absorber! Risk of suffocation! Remove glass protection PE-LD film before commencing installation work! (Figure 4) Keep plastic film out of reach of children! Figure 4 Remove glass protection film before installing collector!.6 Function of the SECUSOL system Function The SECUSOL solar thermal system is designed for domestic hot water (DHW) preparation. The solar fluid is pumped from the solar heat exchanger to the solar collector where it is heated. The thermal energy carried by the solar fluid is then transferred to the domestic water in the storage tank. Backup heating of domestic water in the upper part of the storage tank can be done via a suitable downstream continuous flow heater, an optional electrical immersion heater or via the integrated backup heating coil (not with SECUSOL 50 monovalent, i.e. only one heat exchanger), when connected to central heating. The included SUNGO US plus solar controller controls the circulation pump speed depending on the temperature difference between collector and storage. It also monitors the max. storage temperature. If the system is in stagnation, the entire solar fluid is moved to the heat exchanger, while collector field and collector circuit are filled with system air (figure 7, left hand side). When the circulation pump is switched on, the collector and the collector circuit are filled with solar fluid and the system air is pushed into the upper coils of the heat exchanger (figure 7, right hand side). Once the storage tank is heated up to the maximum temperature, the controller switches off the circulation pump. Normally the solar fluid automatically flows back to the heat exchanger. Otherwise if irradiation continues, the solar fluid vaporizes in the collector field and the system is emptied this way. As the fluid retreats, the air within the system flows into the collectors which quickly reach their stagnation temperature. The heat transport to the tank stops and the solar fluid, which is temperaturesensitive, then is safely stored in the storage tank area. Using a solar fluid with 33 % glycol content ensures permanent protection against frost damage, in addition to corrosion protection. By design heat loss from the storage tank due to overnight convective recirculation or thermosyphonic flows are impossible. Thus the installation of check valves is not required. The installation of venting equipment and a service-intensive membrane expansion vessel are unnecessary due to the special -phase operating system. Operational Limits Note that the storage tank and solar controller must not be installed outdoors and that the system may only be operated within the permitted operating conditions (Chapter : Technical Information). Due to the special system design a maximum of collectors can be integrated. Retroactive extension of the collector area is not possible. The maximum system height is 8 ft / 8.5 m, the maximum length of the solar circuit is 98 ft / 30 m (sum of flow and return legs, according to (Figure 8 page3). Other Documents that have to be Observed The following documents must be observed during installation and operation: 8 EN-USA_SECUSOL_TI-MA-03-R800

19 Operation instructions of the respective solar Controller SUNGO US plus. Technical information Solar Liquid DC0 F, the respective material safety data sheet and label on the canister. Technical information of the respective collectors Material Specifications Table Material specifications Component Parameters Requirements Solar circuit piping Pipe insulation Material Dimension Outside Inside Temperature resistance Dimensions and measurements Copper only 0.47 in / mm Cu UV-resistant No special requirements Up to 347 F /75 C for a short time Dimensions usually are indicated in both: metric and US customary units. In case of doubt the metric dimensions must be considered more precise. The required screws are included in the package and conform to ISO metric standards. For some of the components included in the delivery no exact US pendants exist. In these cases only metric dimensions are indicated. 3 Installation 3. Preparation Scope of Supply Before commencing the installation, please ensure that all components listed in table 3 and 4 are present. Material Required on Site In order to complete the installation and commissioning of the SECUSOL solar energy system, the following is required on site: Piping (copper pipe Cu) for the collector loop pipes Insulation material for the collector loop pipes (for outside use, UV-resistant), available as accessory Electric extension cable for the collector sensors ( threads with cross section of 8/ AWG.) Thermostatic DHW mixer, available as accessory Storage cylinder safety subassembly for cold water connection, available as an accessory, For reasons of corrosion protection the collector loop must be made of materials meeting the requirements of table 8. Other materials are not permitted. Suitable connecting methods are soldering, press fittings or clamp ring connectors. When installing the flat sealing connections please only use the original soft fiber sealants included in the delivery. These sealants have been specially tested for this purpose. Required Tools The following tools are required for the installation and fixing of the collector loop system: Combined wrench 3 mm / / inch (for hexagonal screw M8) Combined wrench 7 mm / /6 inch (for hexagonal screw M0) Pipe wrench 3/4" open-end ratcheting wrench (for collector connection) Electric power screw driver with star bit (e.g. TorxTM) set (for roof bracket fixation) water hoses of m / 6.56 ft length each, both with ½" hose connector on one side Water bucket with a minimum capacity of.64 gal / 0 liters Safety Note Before installing the collectors, please read the information leaflet Safety Precautions for the Installation of Collectors. Observe local statutory accident regulations as well as the technical installation rules described in these instructions. The SECUSOL system is suitable for on-roof and free standing installation. The collectors have to be mounted horizontally to allow them to empty in idle state and during stagnation. EN-USA_SECUSOL_TI-MA-03-R800 9

20 3. On-Roof Installation The on-roof racking system allows fast installation of the collectors on a pitched roof without having to open larger parts of the roof. This is achieved by positioning rafter brackets on the roof. Rafter brackets of type Apro+ for example are suitable for composition shingle roofs, as they are used in much of the north-eastern United States. There are also other bracket and roof anchor types available for a variety of roofings, including industrial metal sheet roofs. Two vertical mounting rails are fixed to the rafter brackets, and the collectors are installed horizontally on these brackets. All individual components are shown in figure 9 (see following page). 3 Fixing of the Roof-Brackets The roof brackets of the type A Pro+ shown in this manual are given as examples only. The actual type and required tools depend on the roofing. For more information refer to the installation instructions included with the roof brackets. Figure 5 Correct fixing of roof bracket type A Pro+ on rafter 0 EN-USA_SECUSOL_TI-MA-03-R800

21 Installation of the Rails C B A B.5 lb-ft (7 Nm) C. lb-ft (30 Nm) Already connect the rails while still on the ground Figure 6 Overview of rail installation (upper image; collector clamps are pre-assembled). () supporting rail fixed with two roof brackets and holding two collector clamps () supporting rail fixed with rail connector to upper rail and one roof bracket; rail holds one collector clamp. Table Distance in inch / mm Segment EURO C0 AR-M EURO L4 A 63 in in 600 mm 900 mm 59 in in 500 mm 700 mm B max. 47. in / 00 mm max. 47. in / 00 mm C max. 8 in / 00 mm max. 8 in / 00 mm For the side by side installation of two collectors the four supporting rails of type (see figure 4) must be aligned at the given distance (see figures 5 and 6). EN-USA_SECUSOL_TI-MA-03-R800

22 Installation of the Collectors Install the upper collector first!.0 lb-ft (7 Nm) Figure 7 Installation of first collector RISK of falling objects and structural damage Improperly positioned collectors can lead to insufficient fixation! Loosen collector clamp slightly, then push tightly against collector and tighten screw (.5 lb-ft / 7 Nm). After installation check for proper position. EN-USA_SECUSOL_TI-MA-03-R800

23 X Figure 8 Installation of the following collector when two collectors are installed, with one above the other RISK of falling objects and structural damage Improperly positioned collectors can lead to insufficient fixation! Loosen collector clamp slightly, then push tightly against collector and tighten screw (.5 lb-ft / 7 Nm). After installation check for proper position. EN-USA_SECUSOL_TI-MA-03-R800 3

24 3.3 Free Standing Installation inch (57 mm) inch (490 mm) 0-00 mm inch 0-00 mm inch Figure 9 EURO TRIC F horizontal for Determining the pitch Table 3 Racking pitch a [ ] A C in 863 mm 0.39 in 0 mm A EURO TRIC F in 940 mm 39.7 in 009 mm 5.79 in 47 mm.4 in 3 mm C in 070 mm 0.5 in 5 mm Figure 0 Installation pitch and setup dimensions for ground- or flat-roof installation (left) or facade installation (right) 4 EN-USA_SECUSOL_TI-MA-03-R800

25 Installation of Racking Triangles.5 lb-ft (7 Nm) M8 x 40.5 lb-ft (7 Nm) 3 Use appropriate wrench, e.g. combined wrench 3 mm / / inch, such as Metrinch MET-3, or adjustable spanner. Figure Unfold racking triangle, set correct angle and lock in position EN-USA_SECUSOL_TI-MA-03-R800 5

26 Fixing of Racking Triangles Fixing the racking triangles on different surfaces is depicted below. Local building standards and codes and structural guidelines must be observed. Assure sufficient carrying capacity of the installation surface. In case of doubt feel free to consult our technical department. max. 7.9 in (00 mm) max. 7.9 in ( 00 mm) Figure Maximum rail projections Ø 0.5 mm 0.43 in (gauge Z) Figure 3 Fixing the racking triangles on steel beams 6 EN-USA_SECUSOL_TI-MA-03-R800

27 Ø mm 0.47 in Use appropriate wrench, e.g. combined wrench 7 mm / /6 inch, such as Metrinch MET-7. or adjustable spanner. Figure 4 Fixing the racking triangles with concrete-slab installation kit (part no ) EN-USA_SECUSOL_TI-MA-03-R800 7

28 Installation of the Collectors on the Racking Triangles X For the C0 AR-M use the lowest rivet nut and for L4 the one above the lowest. X Risk of injury from collapsing collector racks! Make sure that the collector racks are properly set up and all screws are fastened before placing the collectors. Improperly set up racking triangles could collapse and lead to injuries of limbs. Wear appropriate protective workwear! RISK of falling objects and structural damage Improperly positioned collectors can lead to insufficient fixation! Loosen collector clamp slightly, then push tightly against collector and tighten screw (.5 lb-ft / 7 Nm). After installation check for proper position. Use appropriate wrench, e.g. combined wrench 7 mm / /6 inch, such as Metrinch MET-7. or adjustable spanner. Figure 5 Connecting collector and racking triangle 8 EN-USA_SECUSOL_TI-MA-03-R800

29 3.4 General Notes about Storage Installation The pre-assembled return flow sub-assembly has a mm pipe nozzle on the solar circuit side (➊) --> Numbers in black circles refer to Figure Setting up the Storage Tank Please observe the following when setting up the storage tank (Figure 8 page9): The tank insulation consists of 3 parts, the tank insulation (), the cover insulation () and the pre-installed ground insulation (3). Remove the tank insulation, the storage cylinder lid (4) as well as the cover insulation and put safely aside. Unscrew cylinder (6) from the pallet and carry to its final position. Note that the enamel coating of the storage tank can be damaged if jolted. Remove NPSM plug (0) from the pallet and put aside. Place the storage cylinder so that the connections will face the wall. During transport a cable binder is used to secure the pre-wired controller at the cylinders hoisting lug. Cylinder temperature sensor and pump control cable also are pre-wired. 3.6 Connection to Domestic Water Supply Hot and Cold Domestic Water Cold and hot water connections must be done according to the rules and regulations of your local water supplier. We recommend the connection as shown in Figure 6 Connect a safety subassembly () with a safety valve and a non-return valve according to DIN 988 to the cold water inlet of the tank (➋). Within the United States the installation of an IAPMO compliant backflow preventer is mandatory for all installations connected to the drinking water supply. Risk of serious scalding for the end user! Water temperatures at hot water taps can reach up to 03 F / 95 C! A thermostatic mixing valve must be installed to avoid injuries to end customers! It is absolutely necessary to install a thermostatic mixing valve (3) since temperatures during the summer months can reach up to 03 F / 95 C at the hot water outlet. ➐ Without thermostatic mixing valve there is a considerable risk of scalding. The thermostatic mixing valve can be connected between safety subassembly () and the cold water connection at the storage tank ➋ using a T-piece. Close the " NPSM socket ➍ with the plug and seal thoroughly. Alternatively an electrical immersion heater is available which can be installed in this socket, as outlined in the chapter Backup Heating. Re-tighten bolts around flange cover (6) to ensure leakage-free operation. Re-Circulation The return leg (8) should be led away just before the tapping point (0). The circulation pump (9) should be controlled according to the hot water temperature at the most distant tap (sensor ). We recommend that the circulation should be returned to the cold water inlet (4) of the thermostatic mixer (3). A check valve should be installed in the circulation pipe. Please note that circulation can cause significant loss of heat. Hint: use a time, temperature or tap-event controlled circulator. EN-USA_SECUSOL_TI-MA-03-R800 9

30 Cold water supply Storage cylinder safety sub assembly 3 Thermostatic mixer 4 Cold water return 5 DHW distribution pipe 6 Socket lid 7 Protective anode 8 Re-circulation return 9 Re-circulator pump 0 DHW tap Temperature sensor Sensor clamp 3 Solar circuit pump 4 Safety valvel 5 Filling/emptying cock 6 Solar circuit flow sub -assembly 9 Backup heat exchanger 0 Solar heat exchanger Storage cylinder connections: ➊ Solar circuit return ➋ Cold water feed ➌ Solar circuit flow ➍ Electric immersion heater ➎ Backup heating flow/feed (not with SECUSOL 50 mono) ➏ Backup heating return (not with SECUSOL 50 mono) ➐ Hot water connections Figure 6 Connection example for SECUSOL storage cylinder 30 EN-USA_SECUSOL_TI-MA-03-R800

31 3.7 Laying the Solar Circuit Connecting the Solar Sub Assemblies Please note: when the pipes of the solar circuit are soldered, they must be flushed before connecting them to the storage cylinder (see chapter 4, Start-Up). Connect the inlet subassembly to the solar flow inlet of the storage tank (6) using the locking nut (5). Don t forget the flat seal (). Align the filling tap horizontally or upwards (Figure 7). Information: Here flow and return refer to the hot and cold sides at the solar collector. As a result the solar flow is the incoming leg at the solar storage heat exchanger. The return sub-assembly with solar circulation, safety sub-assembly and filling/emptying cock is pre-assembled. (Figure 6 pos. 3 5). If necessary, the screw fittings of the return and the inlet subassemblies should be re-tightened to ensure leak tightness. Operational faults can lead to a discharge of fluids from the safety valve. To avoid soaking of the cylinder insulation we recommend discharging the fluid with a " Cu pipe or similar via the back ventilation opening at the bottom of the insulation (to be provided on site) Connecting the Solar Circuit Observe the operational limits of the SECUSOL system in terms of system height and solar circuit length (Figure 8 and table ) as well as the permitted connection schemes (Figure 5 and Figure 6). Only mm copper pipes may be used for the solar circuit (included in the delivery). The collector loop pipes (figure 7) should be installed with down-grade slope from the collector connections to allow for fast emptying during times of inactivity. The collector loop can be installed without using elbow pieces. The solar circuit can be layed without penetrating the roof see Figure 9. If pipes have to be led through the roofing, ventilation tiles or other safe roof penetrations complying with local building codes are required on site (Figure 30). Place the ventilation tile or pipe duct at the lower edge of the collector, below the collector connection. The upper rim of the elbow pipe under the roof must be installed lower than the collector connection (detail A). When installing a single collector or two collectors one above the other, the upper ventilation tile or duct has to be placed higher than the upper edge of the collector (detail B). Use the included mm coupling to connect the solar circuit return and flow legs (Figure 7 for the example of the solar flow sub-assembly) to the respective subassembly. Saw off the pipe ends, deburr the ridges and fully insert into the coupling. Then tighten nuts. 6 L Figure 7 Solar circuit with flow sub-assembly Copper-Tpiece; Flat sealing gaskets; 3 Filling/emptying cock; 4 Straight compression coupling, mm; 5 Swivel nut; 6 Solar circuit pipe; 7 Storage cylinder connection nozzle of solar flow leg. H L 0 Figure 8 Solar circuit and definition of system length/height L = length of the flow pipe; L0 = length of the return pipe; H = system height (from the bottom of the tank to the top of the collector). EN-USA_SECUSOL_TI-MA-03-R800 3

32 hh B hh A Figure 9 Laying of solar circuit pipe along the outside wall. Figure 30 Laying the solar circuit with penetration of the roof; detail A: Lower collector edge, detail B: Upper collector edge; Collector connection; Venting roof-tile. 3 EN-USA_SECUSOL_TI-MA-03-R800

33 Connecting the Collectors Depending on the type of connection, solar circuit and collectors are connected according to Figure 5 and Figure 6). NOTE: When tightening the joints at the collector connections there is a risk of damaging the absorber. The absorber should not be subjected to torque forces, therefore the connection at the collector side should be secured with an open spanner when tightening! Connection variant with two collectors next to each other (Figure 3 below): Attach a compression fitting () to each of the levelled connections facing each other, and connect them with flat sealing gaskets to the collector connection nozzle ). Connect included short pieces of mm copper pipe (4) to the compression fittings (). Cut to length as needed. To avoid damage to the absorber, no pressure must be exerted onto the absorber pipe during the following insertion of the compression fitting T-piece (3). The collector therefore must be loosened for a moment at its four connection clamps and then pushed outwards. Insert compression fitting T-piece (3), return loosened collector to its previous position, and re-tighten the collector clamp screws. Tighten the lateral compression fitting nuts of the T piece and the inserted pipes (4). Connect mm copper pipe (5) of the solar circuit to the unconnected middle connection of the T-piece (3). Check all connections for tightness after completing all installation works Connection variant with two collectors one above the other (Figure 3): Slip insulation pieces (7) onto the adjacent collector connection nozzles. Then connect one connection of the collector connection hose (6) to a collector connection nozzle (flat sealing). Bend connection hose and connect it in the same fashion to the connection nozzle of the adjacent collector. Pull the ends of the connection hose rubber bellow over both connection nozzle insulation pieces (7). The connections to the solar circuit are carried out in the same fashion (see below). 6 Figure 3 Connection of two collectors, one above the other: Collector connection; 6 Collector connection with flat sealing gaskets and 7 Insulation pieces. 7 Variant with single collector (Figure 33): Connect compression fitting () to collector connection nozzle (, flat sealing). Connect mm copper pipe (5) to compression fitting (); secure with open spanner during tightening to avoid damage to the absorber. Check all connections for tightness after completing the installation work. 4 Figure 3 Connecting two collectors placed next to each other: Collector connection; Compression fitting ½" mm with flat sealing gasket; 3 Compression-fitting T-piece, mm; 4 Connecting pipes with insulation and 5 Solar circuit connections (copper pipe pieces, not part of the package). 5 Figure 33 Solar circuit connection of a single collector or of two collectors placed one above the other: Collector connection; Compression fitting ½" mm with flat sealing gasket; 5 Solar circuit copper pipe (not part of the package). EN-USA_SECUSOL_TI-MA-03-R800 33

34 Installing the Collector Sensor Insert the temperature sensor into the respective sensor sleeve, depending on collector positioning. (see Figure 5 and Figure 6) according to Figure 34. Pull rubber grommet (5) out of the sensor sleeve (7), remove from collector frame and slide onto the temperature sensor cable (6). Clear sensor sleeve from insulation material, if required (Figure 34 details), insert sensor into sensor sleeve and screw in the rubber grommet again. To avoid mechanical load on the sensor, use a wire strap to attach the sensor cable to the insulated collector connection. Extend the sensor cable with a cable to the solar controller, if required (minimum cross section 8/ AWG). Use the sensor connection box SP 0 for the extension on the collector side (accessory, see Table 0) Figure 34 Installing the collector sensor 5 Rubber grommet of sensor sleeve; 6 Collector sensor; 7 Sensor sleeve. 34 EN-USA_SECUSOL_TI-MA-03-R800

35 3.8 Installing the Controller Install the controller to the storage cylinder as follows (fig- Figure 35): Only work on the controller when it is not connected to mains! Do not start-up the system if the controller, the cables or the connected 0 V consumers are visibly damaged! Before connecting the solar controller, place the tank insulation () around the cylinder without closing it, as shown in Figure 35. To affix the controller, break out one of the half-moon shaped perforated sections at the upper end of the insulation mantle; hook controller into the insulation Place the lid insulation () in the tank insulation () and loosely place the tank cover (3) on the cylinder. The mains connection for the controller is preassembled. Since the cable is temperature resistant, it can be passed between the tank insulation and the cylinder and led out along the solar return. Mains power has to be connected from outside the controller via an ON/OFF switch. If a protective connector plug is used for mains connection, the switch is not a must. If the cable needs to be extended, use a cable with a minimum cross section of 5/3 AWG. Local regulations must be complied with. Installing the Sensor (Figure 36) Pass the collector sensor connection cable (k) under the insulation to the solar flow and connect to sensor cable via luster terminal. If extending the sensor cable is required we recommend to use our sensor connection box SP (see accessories tabletable 0 page4) as protection against current surges. Note that only the cables included in the delivery or cables temperature resistant up to 0 C may be used! The temperature sensor cables must not be bent or placed under tension. The minimum bending radius is 50 mm. The SUNGO US plus controller features an additional mains terminal (e.g. for controlling an additional pump) as well as an additional temperature sensor (s). It can be used to control a backup heating circulator pump or to measure the temperature of the cylinder s standbysection (Figure 34). 3 p k s s n 4 Figure 35 Connecting the sensors: () Insulation jacket; () Insulation lid; (3) Storage cover; (4) Ventilation opening; (s) Storage temperature sensor; (p) Pump connection cable; (k) Connection cable for collector sensor; (n) main cable EN-USA_SECUSOL_TI-MA-03-R800 35

36 4 Startup k System Check After fitting all components please carry out the following checks: Are all components fitted correctly? Are all fittings and connections safe and tight and fitted with the original flat seals? Were the bolts on the flange cover re-tightened? Are all electrical connections installed correctly and according to regulations? Are the temperature sensors in the right position? Does the controller show plausible values? s 4. DHW System p Figure 36 Wiring scheme of the SUNGO US plus controller: (s) storage temperature sensor; (p) Pump connection cable; (k) Connection cable for collector sensor; (n) Mains connection cable with on/off switch. n Rinsing the DHW Storage Cylinder Appropriate retainers are to be used when rising the storage cylinder in order to remove remaining particles from the piping. We also recommend to install a dirt retainer at an appropriate place of the heating circuit. Filling and Venting the DHW System To fill the storage cylinder with domestic water, open the shutoff of the safety sub-assembly at the cold-water feed and the up-stream water tap. (Figure 37). Close all water taps after the pipework was successfully vented. Check for tightness of all connections and sockets, retighten, if required, and monitor the system pressure (Figure 38). Pressure Testing of the DHW System Cary out a pressure test of the system after successful installation. : Connect the hot water taps and check all connections and welding points. Afterwards vent cylinder once again. 4. Backup Heating Circuit If a heat generator is connected to the upper heat exchanger coil, the bachup heating circuit has to be rinsed upon startup in order to remove production residues from the coil. 4.3 Solar Circuit Rinsing the Solar Circuit To avoid damage to the system or malfunctions, possible residues from production or installation have to be flushed out of the system before startup (Figure 39): Connect a suitable hose () to the cold water filling tap of the solar return sub-assembly (3) and a domestic water tap (). With a second hose (4) connect the cold water filling and emptying tap of the solar flow (feed) subassembly (5) to a waste water discharge or a container (6). Open filling and rinsing cocks (3 and 5). Open domestic water tap (). Due to the higher pressure loss in the collector loop only the heat exchanger 36 EN-USA_SECUSOL_TI-MA-03-R800

6720616592.00-1.SD. Flat roof. Rack Mounting. Installation instructions 6 720 647 036 (2010/11) AU

6720616592.00-1.SD. Flat roof. Rack Mounting. Installation instructions 6 720 647 036 (2010/11) AU 6720616592.00-1.SD Flat roof Rack Mounting AU Installation instructions 2 Contents AU Contents 1 Key to symbols and safety instructions....... 3 1.1 Explanation of symbols................ 3 1.2 Safety

More information

SunMaxx Solar Filling Station Operating Instructions

SunMaxx Solar Filling Station Operating Instructions SunMaxx Solar Filling Operating Instructions Content 1. Declaration of conformity... 2 2. Introduction... 2 3. Transportation and unpacking... 4 4. Mounting and commissioning... 5 5. End of operation...

More information

Installation and maintenance instructions

Installation and maintenance instructions Installation and maintenance instructions Indirect fired domestic hot water tank Logalux ST50/ ST300/ For heating contractors Please read carefully prior to installation and maintenance. 7 747 00 883 09/006

More information

Cooling system components, removing and installing

Cooling system components, removing and installing Engine BHW Cooling system components, removing and installing Page 1 / 24 19-1 Cooling system components, removing and installing Warning! When doing any repair work, especially in the engine compartment,

More information

Installation and Commissioning Manual Solar Stations FlowCon Max Evolution II

Installation and Commissioning Manual Solar Stations FlowCon Max Evolution II Installation and Commissioning Manual Solar Stations FlowCon Max Evolution II 1 For your safety Table of Contents 1 For your safety... 3 1.1 About this manual... 3 1.2 Designated use... 3 1.3 Qualification

More information

Installation Manual. Solar Pool Heating System. Read the complete manual before beginning the installation

Installation Manual. Solar Pool Heating System. Read the complete manual before beginning the installation Solar Pool Heating System Installation Manual Read the complete manual before beginning the installation 1. Sizing the System Visit www.techno-solis.com to size the system using the sizing calculator.

More information

ECOplus Solar Cylinder

ECOplus Solar Cylinder TECHNICAL INFORMATION Solar Cylinder Wagner& Co Connection Options for CONVECTROL II The Effective Convection Brake Technically and fluidically optimized barriers separate the water cooled in the pipes

More information

BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS

BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS PLEASE READ COMPLETE INSTRUCTIONS BEFORE YOU BEGIN LEAVE INSTALLATION INSTRUCTIONS AND USER'S GUIDE WITH OWNER ALL ELECTRIC WIRING AND PLUMBING MUST BE DONE

More information

VITOSOL r 200-T SP2A. VITOSOL 200-T Type SP2A

VITOSOL r 200-T SP2A. VITOSOL 200-T Type SP2A Technical Data Manual Model Nos. and pricing: see Price List Vacuum tube collector based on the heat pipe principle For the utilisation of solar energy VITOSOL r 200-T SP2A Product may not be exactly as

More information

Art.S001-S002 SOLAR MODULE WITH DELIVERY AND RETURN CONNECTIONS

Art.S001-S002 SOLAR MODULE WITH DELIVERY AND RETURN CONNECTIONS Art.S001-S002 SOLAR MODULE WITH DELIVERY AND RETURN CONNECTIONS Technical Information sheet 0001/07/Rev01 ENG FUNCTION Series S001 and S002 circulation units are applied to the primary circuit of solar

More information

Zenith Solar thermal 4.5m pump station Installation manual

Zenith Solar thermal 4.5m pump station Installation manual Zenith Solar thermal 4.5m pump station Installation manual Product code: 20026145 INSTALLATION MANUAL WATER RETURN GROUP This instruction manual is an integral part of the installation and maintenance

More information

Data Sheet VITOSOL 100. Flat collectors for the utilisation of solar energy. Vitosol 100. Part nos. and prices: see price list

Data Sheet VITOSOL 100. Flat collectors for the utilisation of solar energy. Vitosol 100. Part nos. and prices: see price list VITOSOL 100 Flat collectors for the utilisation of solar energy Data Sheet Part nos. and prices: see price list File in: Vitotec 1 Manual, Index 16 Vitosol 100 Type s 1.7 Vitosol 100 Type s 2.5 Vitosol

More information

DANGER DANGER. General Information. Safety Is Your Responsibility. Ordering Parts. Contact Information

DANGER DANGER. General Information. Safety Is Your Responsibility. Ordering Parts. Contact Information Safety Safety Is Your Responsibility DANGER To avoid personal injury or death, carefully read and understand all instructions pertaining to the Anthony Liftgates product. Do not attempt to install, operate,

More information

Select Radiators Installation Guide

Select Radiators Installation Guide Select Radiators Installation Guide Table of Contents Informational Symbols...3 Before You Begin...4 Select Rough-In... 5 Connection Installation...6 Optional Piping Arrangements...7 Conventional Wall

More information

Wafer Check Valve ASAHI AV VALVES. Contents. User s Manual. (1) Be sure to read the following description of our product warranty 1

Wafer Check Valve ASAHI AV VALVES. Contents. User s Manual. (1) Be sure to read the following description of our product warranty 1 Serial No. H-V066-E-2 Wafer Check Valve User s Manual Contents (1) Be sure to read the following description of our product warranty 1 (2) General operating instructions 2 (3) General instructions for

More information

Installation Manual. Thermomax Solar Water Heater ... Installation Procedure for Flatroof and Ground. Revision 8

Installation Manual. Thermomax Solar Water Heater ... Installation Procedure for Flatroof and Ground. Revision 8 . Thermomax Solar Water Heater Thermo Technologies 5560 Sterrett Place, Suite 115 Columbia, MD 21044 Thermoteks.com November 2005 Installation Manual.......... Installation Procedure for Flatroof and Ground

More information

Replacement parts. WM97+ gas-fired water boiler Boiler Manual. OBTAIN PARTS ONLY THROUGH WEIL-McLAIN THE BOILER CONTAINS CERAMIC FIBER MATERIALS

Replacement parts. WM97+ gas-fired water boiler Boiler Manual. OBTAIN PARTS ONLY THROUGH WEIL-McLAIN THE BOILER CONTAINS CERAMIC FIBER MATERIALS Replacement parts DO NOT SERVICE THE BOILER WITHOUT A WM97+ MAINTENANCE KIT AVAILABLE Failure to adhere to these guidelines can result in severe personal injury, death or substantial property damage. The

More information

Installation Instructions for Contractors. Connection Sets. Solar Twin Tube. Inox 1/2" Inox 3/4" 6 720 646 309 (2011/02) US/CA

Installation Instructions for Contractors. Connection Sets. Solar Twin Tube. Inox 1/2 Inox 3/4 6 720 646 309 (2011/02) US/CA Installation Instructions for Contractors Connection Sets Solar Twin Tube Inox 1/2" Inox 3/4" 6 720 646 309 (2011/02) US/CA Contents Contents 1 Explanation of symbols and safety information 3 1.1 Explanation

More information

XL PREMIUM OIL COOLER KIT

XL PREMIUM OIL COOLER KIT -J05 REV. 0-0-0 XL PREMIUM OIL COOLER KIT GENERAL Kit Number 0008 Models For model fitment information, see the P&A Retail Catalog or the Parts and Accessories section of www.harley-davidson.com (English

More information

Installation Instructions 4508 4508S

Installation Instructions 4508 4508S SYMPHONY Spread Lavatory Faucet with Speed Connect Drain Congratulations on purchasing your American Standard faucet with Speed Connect drain, a feature found only on American Standard faucets. Speed Connect

More information

Installation and Operating Instructions Installation Instructions for SS EPE-316L Series

Installation and Operating Instructions Installation Instructions for SS EPE-316L Series INSTR3010 0406 Installation and Operating Instructions Installation Instructions for SS EPE-316L Series Congratulations on your purchase of this Aqua-Pure high flow, single housing filtration system. This

More information

758 Heavy-duty Ratchet Guy Wire Cutter

758 Heavy-duty Ratchet Guy Wire Cutter INSTRUCTION MANUAL 758 Heavy-duty Ratchet Guy Wire Cutter Read and understand all of the instructions and safety information in this manual before operating or servicing this tool. Register this product

More information

SERIES ASM NEOPRENE/EPMD FLANGED SINGLE SPHERE CONNECTOR CONNECTORS. Pressures to 225 PSIG (15.51 barg) Temperatures to 230ºF (110ºC)

SERIES ASM NEOPRENE/EPMD FLANGED SINGLE SPHERE CONNECTOR CONNECTORS. Pressures to 225 PSIG (15.51 barg) Temperatures to 230ºF (110ºC) APPLICATIONS Process Industry Weak Acids Alkalies Compressed Air Pulp & Paper MODELS ASM - Flanged Connection OPTIONS Control Rods Oil & Gas Water & Waste Pump suction & discharge Sea water Chemical lines

More information

Operators manual Basic water heater

Operators manual Basic water heater Operators manual Basic water heater Isotemp Basic water heater has been designed and produced to ensure that your water heater will give long and trouble free operation for many years. It is important,

More information

PBX Series Quick Fit Connector Bimetallic Steam Traps

PBX Series Quick Fit Connector Bimetallic Steam Traps 6262100/6 IM-P626-01 ST Issue 6 PBX Series Quick Fit Connector Bimetallic Steam Traps Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Commissioning

More information

COOLING SYSTEM Section Page

COOLING SYSTEM Section Page 5 COOLING SYSTEM Section Page 5.1 COOLANT PRE-HEATER... 5-3 5.2 COOLANT PUMP NON-EGR ENGINE... 5-7 5.3 COOLANT PUMP EGR ENGINE... 5-13 5.4 FRONT CONNECTOR HOUSING NON-EGR ENGINE... 5-17 5.5 FRONT CONNECTOR

More information

Vacuum Tube Solar Water heater Non-pressure. User manual

Vacuum Tube Solar Water heater Non-pressure. User manual Vacuum Tube Solar Water heater Non-pressure User manual Please read this manual carefully before beginning installation Specification Tubes 12 --- 30 58X1800 Nominal volume tank capacity 100L --- 300L

More information

Cooling system components, removing and installing

Cooling system components, removing and installing Page 1 of 34 19-1 Cooling system components, removing and installing WARNING! The cooling system is pressurized when the engine is warm. When opening the expansion tank, wear gloves and other appropriate

More information

SBC90. Abrasive Blast Cabinet Assembly & Operating Instructions

SBC90. Abrasive Blast Cabinet Assembly & Operating Instructions SBC90 Abrasive Blast Cabinet Assembly & Operating Instructions READ ALL INSTRUCTIONS AND WARNINGS BEFORE USING THIS PRODUCT. SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE. This manual provides important

More information

Installation Manual Gravity Solar Water Heater Evacuated Tube Integrated (Direct) System, unpressurized

Installation Manual Gravity Solar Water Heater Evacuated Tube Integrated (Direct) System, unpressurized Installation Manual Gravity Solar Water Heater Evacuated Tube Integrated (Direct) System, unpressurized Gravity Solar System Installation Manual: This manual explains how to install a system of evacuated

More information

Important: Please read these instructions carefully and completely before starting the installation. TITAN Fuel Tanks

Important: Please read these instructions carefully and completely before starting the installation. TITAN Fuel Tanks TITAN pt. no.: 03 0000 0120 Important: Please read these instructions carefully and completely before starting the installation. TITAN Fuel Tanks INSTALLATION INSTRUCTIONS G e n e r a t i o n V Extended

More information

VIESMANN. Datasheet Part numbers and prices: see pricelist VITOSOL 200-F. Flat-plate collector for the utilisation of solar energy

VIESMANN. Datasheet Part numbers and prices: see pricelist VITOSOL 200-F. Flat-plate collector for the utilisation of solar energy VIESMANN VITOSOL 200-F Flat-plate collector for the utilisation of solar energy Datasheet Part numbers and prices: see pricelist File in: Vitotec folder, register 13 VITOSOL 200-F Type SV2 and SH2 Flat-plate

More information

Float and Thermostatic Traps Series H, C and X

Float and Thermostatic Traps Series H, C and X Hoffman Specialty Installation & Maintenance Instructions HS-(E) and Thermostatic Traps Series H, C and X Series C & NPT Series C NPT Series X NPT Series C NPT Series H Ratings Maximum Max. Operating NPT

More information

Volkswagen Golf 5 2004-> VW Rabbit GTI 2006->

Volkswagen Golf 5 2004-> VW Rabbit GTI 2006-> Стр. 1 из 24 Volkswagen Golf 5 2004-> VW Rabbit GTI 2006-> 19-1 Cooling system components Warning! Hot steam may escape when opening expansion tank. Wear protective goggles and protective clothing to prevent

More information

INSTRUCTIONS FOR USE, MAINTENANCE AND INSTALLATION OF THE

INSTRUCTIONS FOR USE, MAINTENANCE AND INSTALLATION OF THE SUN & HEAT SOLAR PRODUCTS INSTRUCTIONS FOR USE, MAINTENANCE AND INSTALLATION OF THE SOLAR DOMESTIC WATER HEATER THERMOSIPHON 150/2.5 (TYPICAL INSTRUCTIONS FOR A CLOSED LOOP THERMOSIPHONIC SYSTEM ON A FLAT

More information

SunMor SM-V30 Solar Water Heater Installation Manual

SunMor SM-V30 Solar Water Heater Installation Manual SunMor SM-V30 Solar Water Heater Installation Manual Rev. 1.02 Congratulations on the purchase of your new SunMor SM-V30 from Nature s Comfort LLC! You must read this entire instruction manual before beginning

More information

Making Your Home Ready For Solar Water Heating

Making Your Home Ready For Solar Water Heating Making Your Home Ready For Solar Water Heating During construction or a major renovation, making a home ready to use solar energy can be easy and inexpensive. When the time comes to install your solar

More information

Overview PARTS LIST. B. Lever mounting base C. Flush handle assembly D. Grey/Blue float stop E. Grey float (Full Flush) F. Flush valve washer

Overview PARTS LIST. B. Lever mounting base C. Flush handle assembly D. Grey/Blue float stop E. Grey float (Full Flush) F. Flush valve washer Overview READ ENTIRE INSTRUCTIONS BEFORE STARTING INSTALLATION PARTS LIST A. Flush valve B. Lever mounting base C. Flush handle assembly D. Grey/Blue float stop E. Grey float (Full Flush) F. Flush valve

More information

THERMOSTATIC MIXING VALVE TRIM K-T9493, K-T9494

THERMOSTATIC MIXING VALVE TRIM K-T9493, K-T9494 THERMOSTATIC MIXING VALVE TRIM K-T9493, K-T9494 1. BEFORE YOU BEGIN IMPORTANT INSTRUCTIONS READ AND SAVE FOR THE CONSUMER WARNING: Risk of scalding or other severe injury. Before completing installation,

More information

AA Solar and Sun Power Plus

AA Solar and Sun Power Plus AA Solar and Sun Power Plus www.aasolar.co.nz www.sunpowerplus.co.nz -1- Contents Chapter Title Page 1 General information 3 2 Safety and Installer Responsibilities 4 3 Technical Specifications 5 4 Tools

More information

Machine needle shut-off nozzle type HP

Machine needle shut-off nozzle type HP Machine needle shut-off nozzle type HP pneumatically or hydraulically controlled Index of contents Chapter Page Safety instructions... 2 Installation instructions... 3 - Installation steps... 3 Initial

More information

INSTRUCTIONS AND PARTS LIST FOR MODEL 70H & 75H HAND-OPERATED HYDRAULIC PRESS

INSTRUCTIONS AND PARTS LIST FOR MODEL 70H & 75H HAND-OPERATED HYDRAULIC PRESS INSTRUCTIONS AND PARTS LIST FOR MODEL 70H & 75H HAND-OPERATED HYDRAULIC PRESS SETTING UP THE PRESS FOR OPERATION For shipping convenience, the gauge, pump handle, hoist crank, screw nose and base angles

More information

CAST IRON THE BASICS. Heatline - Cast Iron Radiators SMOOTH FLAT FILE TO REMOVE ANY SWARF. ONE TIME. ASSEMBLY. JOINTS SHOULD BE TIGHTENED.

CAST IRON THE BASICS. Heatline - Cast Iron Radiators SMOOTH FLAT FILE TO REMOVE ANY SWARF. ONE TIME. ASSEMBLY. JOINTS SHOULD BE TIGHTENED. CAST IRON THE BASICS 1. DO NOT LIFT ON YOUR OWN. 2. ONLY LIFT THE RADIATOR VERTICALLY. 3. DO NOT LIFT MORE THAN 8/10 SECTIONS AT ANY ONE TIME. 4. POSITION THE RADIATOR BEFORE FINAL ASSEMBLY. 5. THIS PRODUCT

More information

ATS Overhead Table Shelf System INSTRUCTION MANUAL

ATS Overhead Table Shelf System INSTRUCTION MANUAL ATS Overhead Table Shelf System INSTRUCTION MANUAL ATS Overhead Table Shelf System Instruction Manual Warranty Newport Corporation warrants this product to be free of defects in material and workmanship

More information

Owner s Manual Read and keep this manual. Patents World Wide

Owner s Manual Read and keep this manual. Patents World Wide Owner s Manual Read and keep this manual. Patents World Wide S & S Industries, Inc., Sarasota, FL, USA www.trail-gator.com Copyright 2008 All Rights Reserved The following manual is provided to assist

More information

Installation Instructions

Installation Instructions Installation Instructions Built-In Dishwasher If you have questions, call 1-800-4-MY-HOME (1-800-469-4663) or visit our website at: www.sears.com BEFORE YOU BEGIN Read these instructions completely and

More information

Installation and User Instructions Unvented Electric Storage Water Heater Models: S10UNV, S15UNV.

Installation and User Instructions Unvented Electric Storage Water Heater Models: S10UNV, S15UNV. Installation and User Instructions Unvented Electric Storage Water Heater Models: S10UNV, S15UNV. MULTIPOINT Please read and understand these instructions before starting work. Please leave this leaflet

More information

Solar Collector Series. Product List

Solar Collector Series. Product List Solar Collector Series List FULL COLLECTORS (MANIFOLD, TUBES & ROOF FRAME) : CSR00051 Apricus Collector : AP10 10-Way Manifold, 10 Tubes and Standard Roof Frame CSR00052 Apricus Collector : AP20 20-Way

More information

Power Cube Open Source Ecology Page 1. Power Cube. Version 4

Power Cube Open Source Ecology Page 1. Power Cube. Version 4 Power Cube Open Source Ecology Page 1 Power Cube Version 4 Power Cube Open Source Ecology Page 2 Contents Table of Contents Power Cube... 1 Contents...2 Introduction... 3 Bill Of Materials...4 Discrete

More information

BACKPACK SPRAYERS. MODEL NOS: KSP16 & KSP20 Part Nos: 3402270 & 3402275 OPERATING & MAINTENANCE INSTRUCTIONS GC04/12

BACKPACK SPRAYERS. MODEL NOS: KSP16 & KSP20 Part Nos: 3402270 & 3402275 OPERATING & MAINTENANCE INSTRUCTIONS GC04/12 BACKPACK SPRAYERS MODEL NOS: KSP16 & KSP20 Part Nos: 3402270 & 3402275 OPERATING & MAINTENANCE INSTRUCTIONS GC04/12 INTRODUCTION Thank you for purchasing this CLARKE Sprayer, designed for use only with

More information

foot skylight) is enough to knock a worker off their feet. A 10 mph wind gust on a 5 x 6 skylight develops a wind force of 270 lbs.

foot skylight) is enough to knock a worker off their feet. A 10 mph wind gust on a 5 x 6 skylight develops a wind force of 270 lbs. Skylight Installation Instructions This document provides instruction and guidelines for installation of both curb mount (CM) and self flashing (SF) unit skylights on flat, pitched (> or equal to 3/12

More information

Andersen Electric Window Opener for Andersen Awning and Roof Windows

Andersen Electric Window Opener for Andersen Awning and Roof Windows W A Electric Window Opener Electric Window Opener for Awning and Roof Windows Congratulations! You have just purchased one of the many fine products. For ease of installation and continued enjoyment of

More information

HORIZONTAL INSTALLATION

HORIZONTAL INSTALLATION THERMO/SOLAR Žiar s.r.o. MANUAL FOR INSTALLATION PV SUPPORTING FRAMES HORIZONTAL INSTALLATION Technical alternation reserved A1410 1 12/2014 CONTENT ORD.NO. PAGE Mounting information 3 Mounting, flat roof

More information

MODEL G300 BRAKE BLEEDER

MODEL G300 BRAKE BLEEDER MODEL G300 BRAKE BLEEDER Installation, Operation & Repair Parts Information Branick Industries, Inc. 4245 Main Avenue P.O. Box 1937 Fargo, North Dakota 58103 REV060616 P/N: 81-0035G 1 THIS PAGE INTENTIONALLY

More information

Speedflow Undersink Unvented Water Heater. Models SF10K and SF15K. Instruction Manual

Speedflow Undersink Unvented Water Heater. Models SF10K and SF15K. Instruction Manual Speedflow Undersink Unvented Water Heater Models SF10K and SF15K Instruction Manual Version 2.0 May 2009 Hyco SpeedFLOW UnVENTED WATER HEATER Models SF10K (10 Litres) and SF15K (15 Litres) 1. Introduction

More information

Your safety and the safety of others are very important.

Your safety and the safety of others are very important. NATURAL GAS TO PROPANE CONVERSION KIT 090 INSTALLATION INSTRUCTIONS FOR ALTITUDES 0 -,00 FT. ONLY PROPANE CONVERSION KIT SAFETY... INSTALLATION REQUIREMENTS... Tools and Parts... LP Gas Requirements...

More information

Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS

Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS Contents Page Ratings and Specifications..................... 2 Installation Requirements......................

More information

OWNER S MANUAL Table Tennis Table Patent Pending

OWNER S MANUAL Table Tennis Table Patent Pending OWNER S MANUAL Table Tennis Table Patent Pending Be sure to write your model number and serial number here for future reference. You can find these numbers printed on the bottom of the table. MODEL # T8179

More information

Universal Installation and Maintenance Instructions Double Wall Spill Containment Bucket (5 and 15 gal)

Universal Installation and Maintenance Instructions Double Wall Spill Containment Bucket (5 and 15 gal) Universal Installation and Maintenance Instructions Double Wall Spill Containment Bucket (5 and 15 gal) IMPORTANT: It is imperative that the user read these warnings and use of the assembly instructions

More information

IMPORTANT SAFETY NOTICE

IMPORTANT SAFETY NOTICE IMPORTANT SAFETY NOTICE To: Our Valued Customers User safety is a major focus in the design of our products. Following the precautions outlined in this manual will minimize your risk of injury. ITT Goulds

More information

Isotemp Basic, Slim/B & Slim Square

Isotemp Basic, Slim/B & Slim Square Isotemp Basic, Slim/B & Slim Square Water heater Installation and operating instructions Indel Marine S.r.l. Zona Artigianale sn IT-61019 S. Agata Feltria (PU) Italy Tel. 39 0541 848 030 Fax 39 0541 848

More information

ITE. Indirect calorifier ITE - 400/500/600/750/1000. Installation, User and Service Manual. Innovation has a name.

ITE. Indirect calorifier ITE - 400/500/600/750/1000. Installation, User and Service Manual. Innovation has a name. ITE Indirect calorifier ITE - 400/500/600/750/1000 0310 117 Installation, User and Service Manual Innovation has a name. Read this manual carefully Warning Read this manual carefully before starting the

More information

Solar Mounting System

Solar Mounting System Xiamen Antai New Energy Tech.Co., Ltd Installation Manual Antai Rail Solar Mounting System (Flat Roof Solution) Version 1.1 Office Add: 508#, North Tower, Guangxia Building Huli Torch Hi-tech Zone, Xiamen,

More information

USE &CARE GUIDE. Remote Faucet Pump System. See Important Safeguards on page 2

USE &CARE GUIDE. Remote Faucet Pump System. See Important Safeguards on page 2 Remote Faucet Pump System USE &CARE GUIDE See Important Safeguards on page 2 An exclamation point within an equilateral triangle is intended to alert user to the presence of important operating and maintenance

More information

Engineering Specifications

Engineering Specifications PUREFLOW PEX PRODUCTS PART 1 GENERAL 1.1 SUMMARY 1.1.1 This specification covers Branch & Main, Parallel Water Distribution Systems (MANABLOC), Cross-linked Polyethylene tubing and fittings using PEX Press

More information

TITAN Fuel Tanks. INSTALLATION INSTRUCTIONS G e n e r a t i o n V

TITAN Fuel Tanks. INSTALLATION INSTRUCTIONS G e n e r a t i o n V TITAN pt. no.: 02 0000 0143 Important: Please read these instructions carefully and completely before starting the installation. TITAN Fuel Tanks INSTALLATION INSTRUCTIONS G e n e r a t i o n V Extended

More information

Installation instruction of the flat solar collectors models ES1V2.0, ES1V2.65, ES2V/2.0 AL, EM2V/2.0, ES2V/2.65, ES2H/2.65 on the inclined tile roof.

Installation instruction of the flat solar collectors models ES1V2.0, ES1V2.65, ES2V/2.0 AL, EM2V/2.0, ES2V/2.65, ES2H/2.65 on the inclined tile roof. Installation instruction of the flat solar collectors models ES1V2.0, ES1V2.65, ES2V/2.0 AL, EM2V/2.0, ES2V/2.65, ES2H/2.65 on the inclined tile roof. 04/2014 Get acquainted before starting the installation.

More information

Volkswagen B3 Passat General-Engine 4 CYL. 19 Engine - Cooling System (Page GR-19)

Volkswagen B3 Passat General-Engine 4 CYL. 19 Engine - Cooling System (Page GR-19) 19 Engine - Cooling System (Page GR-19) Cooling system draining and filling general information Body components, layout Engine components, layout Radiator fan run-on checking Recommended mixture ratios

More information

VOYAGER 570G. 744A Sprayer Control

VOYAGER 570G. 744A Sprayer Control VOYAGER 570G 744A Sprayer Control U S E R M A N U A L U S E R M A N U A L Table of Contents CHAPTER 1 - INTRODUCTION...1 SYSTEM CONFIGURATIONS...1 KIT CONTENTS...3 CONTROL HOUSING ASSEMBLY...5 CHAPTER

More information

SureSite Magnetic Liquid Level Indicator

SureSite Magnetic Liquid Level Indicator SureSite Magnetic Liquid Level Indicator Instruction Bulletin No. 177664-1 (Rev. E) Section 1: Weldments Thank you for purchasing the GEMS SureSite Magnetic Level Indicator. Please read this document prior

More information

123 Industrial Loop Road Paynesville, MN 56362 Phone: 1-800-864-1649 www.master-mfg.com MASTER MANUFACTURING MASTER GARDNER

123 Industrial Loop Road Paynesville, MN 56362 Phone: 1-800-864-1649 www.master-mfg.com MASTER MANUFACTURING MASTER GARDNER 123 Industrial Loop Road Paynesville, MN 56362 Phone: 1-800-864-1649 www.master-mfg.com MASTER MANUFACTURING MASTER GARDNER Part Number PCD E3 009B MM Rev 1 Nov. 2010 INTRODUCTION The purpose of this manual

More information

ENGINE FUEL FUEL FILTER... FUEL HEATER... INJECTOR... SUPPLY PUMP... COMMON RAIL... FUEL PRESSURE LIMITTER...

ENGINE FUEL FUEL FILTER... FUEL HEATER... INJECTOR... SUPPLY PUMP... COMMON RAIL... FUEL PRESSURE LIMITTER... FUEL FILTER............................ FUEL HEATER.......................... INJECTOR.............................. SUPPLY PUMP.......................... COMMON RAIL.......................... FUEL PRESSURE

More information

Welding Reel ERA 4000 Service Manual

Welding Reel ERA 4000 Service Manual AERO-MOTIVE COMPANY A Woodhead Industries, Inc. Subsidiary Welding Reel ERA 4000 Service Manual IMPORTANT SAFETY INSTRUCTIONS Please read this manual carefully and follow its instructions. Improper use

More information

Volkswagen New Beetle 2.0 Liter 4-cyl General, Engine (Engine Code AEG) 17 Engine-Lubrication system (Page GR-17)

Volkswagen New Beetle 2.0 Liter 4-cyl General, Engine (Engine Code AEG) 17 Engine-Lubrication system (Page GR-17) 17 Engine-Lubrication system (Page GR-17) Lubrication system components, removing and installing Oil pan, removing and installing Oil pressure and oil pressure switch, checking Dynamic oil pressure warning

More information

Front axle components, overview

Front axle components, overview just a test. Front axle components, overview 40-1 General Information Load bearing components and parts of the suspension must not be welded or straightened. Vehicles without drive axle must not be moved,

More information

Cooling system components, servicing

Cooling system components, servicing 19-1 Cooling system components, servicing WARNING! The cooling system is pressurized when the engine is warm. When opening the expansion tank, wear gloves and other appropriate protection, cover the cap

More information

NBA Arena Portable System

NBA Arena Portable System REQUIRED TOOLS AND MATERIALS: Two (2) Capable Adults Tape Measure Wood Board 6 x 6 (scrap) N53 W24700 South Corporate Circle Sussex, WI 53089 U.S.A. NBA Arena Portable System Sawhorse or Support Table

More information

GATE VALVES ASAHI AV VALVES. Type P (Standard: Plug) Type S (Soft Seal) Contents. (1) Be sure to read the following warranty clauses of our product 1

GATE VALVES ASAHI AV VALVES. Type P (Standard: Plug) Type S (Soft Seal) Contents. (1) Be sure to read the following warranty clauses of our product 1 Serial No. H-V011-E-11 GATE VALVES Type P (Standard: Plug) Type S (Soft Seal) Contents (1) Be sure to read the following warranty clauses of our product 1 User s Manual (2) General operating instructions

More information

RayClic Connection System Installation Instructions

RayClic Connection System Installation Instructions F M -W RayClic Connection System Installation Instructions RayClic WARNING: Shock Hazard 718K Pipe Heating Cable with HWAT, IceStop, also Listed De-icing and and XL-Trace heating Snow Melting Equipment

More information

In-Ground Basketball System Owners Manual

In-Ground Basketball System Owners Manual In-Ground Basketball System Owners Manual Customer Service Center N53 W4700 South Corporate Circle Sussex, WI 53089 U.S.A. Write Model Number From Box Here: WARNING! 3 Capable Adults REQUIRED TOOLS AND

More information

BPW32 DN15, DN20 and DN25 Balanced Pressure Wafer Steam Trap

BPW32 DN15, DN20 and DN25 Balanced Pressure Wafer Steam Trap 1263050/6 IM-P126-07 ST Issue 6 BPW32 DN15, DN20 and DN25 Balanced Pressure Wafer Steam Trap Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation

More information

Rental Services Temporary Cooling - Flexible Water Hose

Rental Services Temporary Cooling - Flexible Water Hose Engineering Bulletin Rental Services Temporary Cooling - Flexible Water Hose September 2006 CHS-PRB007-EN Warnings and Cautions Warnings and Cautions. Notice that warnings and cautions appear at appropriate

More information

Thermo Siphon Solar Systems

Thermo Siphon Solar Systems Thermo Siphon Solar Systems Thermo Siphon Solar Systems are a very cost effective way of producing hot water due to their simplicity in design and installation requirements. Usually more common in hotter

More information

FASCINATION 700 HVLP TANNING PRO SYSTEM USER MANUAL

FASCINATION 700 HVLP TANNING PRO SYSTEM USER MANUAL FASCINATION 700 HVLP TANNING PRO SYSTEM USER MANUAL Congratulations on choosing the Fascination 700 HVLP Tanning Pro System! Your system includes the following items: 1 Fascination 700 HVLP Tanning Pro

More information

Coolflo Safe Touch Shower Mixing Valve ST20015CP

Coolflo Safe Touch Shower Mixing Valve ST20015CP Coolflo Safe Touch Shower Mixing Valve ST20015CP Installation and Maintenance Instructions In this procedure document we have endeavoured to make the information as accurate as possible. We cannot accept

More information

Industrial Process Pump Safety Manual IMPORTANT SAFETY NOTICE

Industrial Process Pump Safety Manual IMPORTANT SAFETY NOTICE Industrial Process Pump Safety Manual IMPORTANT SAFETY NOTICE To: Our Valued Customers User safety is a major focus in the design of our products. Following the precautions outlined in this manual will

More information

SERVICE SERVICE COMPACT MANUAL. Mod. 3000 92X Mod. 3000 93X Mod. 3000 94X. Part 2

SERVICE SERVICE COMPACT MANUAL. Mod. 3000 92X Mod. 3000 93X Mod. 3000 94X. Part 2 SERVICE COMPACT SERVICE 000 MANUAL Mod. 000 9X Mod. 000 9X Mod. 000 94X Part Forward This Service Handbook is intended to assist with servicing and fault-finding in Caravans and Motor Caravans equipped

More information

Lenntech. 1000 psi End port pressure vessels 2.5. User s Guide to: Phoenix Vessel Technology Limited. Model number: 1503

Lenntech. 1000 psi End port pressure vessels 2.5. User s Guide to: Phoenix Vessel Technology Limited. Model number: 1503 1 User s Guide to: Phoenix Vessel Technology Limited 1000 psi End port pressure vessels 2.5. Model number: 1503 Lenntech info@lenntech.com Tel. +31-152-610-900 www.lenntech.com Fax. +31-152-616-289 Phoenix

More information

OPERATING INSTRUCTIONS AND PARTS LIST FOR U075075 U100058 UNDERGROUND HOSE REELS

OPERATING INSTRUCTIONS AND PARTS LIST FOR U075075 U100058 UNDERGROUND HOSE REELS OPERATING INSTRUCTIONS AND PARTS LIST FOR U075075 U0005 FORM NO.: 3-00 REV: RAIN BIRD CORPORATION ONE REELCRAFT CENTER COLUMBIA CITY, IN 675 (00) -33 / (60) - FAX: (60) -605 U0005 MODEL NUMBER SIGNIFICANCE

More information

OPERATOR S INSTRUCTION MANUAL

OPERATOR S INSTRUCTION MANUAL POWER JACK MATERIAL MOVER OPERATOR S INSTRUCTION MANUAL WARNING: Serious injury may result if this product is misused. The manufacturer provides the following instructions for use and care of this equipment

More information

RAIL FREE SOLAR ROOF MOUNT

RAIL FREE SOLAR ROOF MOUNT RAIL FREE SOLAR ROOF MOUNT Utilizes EcoFasten Solar s patented technology Rock-it system Designed with the installer in mind. EcoFasten Solar specializes in solar roof attachments that are the easiest

More information

Trillium 40 Axis Spring Tensioner Wire Replacement Instructions

Trillium 40 Axis Spring Tensioner Wire Replacement Instructions Trillium 40 Axis Spring Tensioner Wire Replacement Instructions 1 Overview The objective is to replace the broken axis spring tensioner wire. This requires the following tasks: 1. Remove the seismometer

More information

Ergo-Pro Single Line Solar Station Installation and Operating Instructions

Ergo-Pro Single Line Solar Station Installation and Operating Instructions Rp 3/4 Ergo-Pro Single Line Solar Station Installation and Operating Instructions Item No Pump type 677.21.70 WILO ST 15/6 13 2 4 11 Technical Specifications Max. operating pressure: 6 bar Max. operating

More information

ARCOBALENO SXT Flat roof and ground level mounting system with 45 angle of inclination

ARCOBALENO SXT Flat roof and ground level mounting system with 45 angle of inclination ARCOBALENO SXT Flat roof and ground level mounting system with 45 angle of inclination Manual use and installation Cod. 6902952 page 3 Thank you for your choice of ARCOBALENO SXT. Carefully read this manual

More information

Installation Guide of Sunrise Solartech PV Modules. Term 2013. Contents. Purpose of this guide. General. Safety precaution for installing a solar

Installation Guide of Sunrise Solartech PV Modules. Term 2013. Contents. Purpose of this guide. General. Safety precaution for installing a solar Installation Guide of Sunrise Solartech PV Modules Term 2013 Contents Purpose of this guide General Safety precaution for installing a solar Photovoltaic system Product Identification Mechanical Installation

More information

Check for deteriorated, shifting or missing tie-down pads. Replace if needed.

Check for deteriorated, shifting or missing tie-down pads. Replace if needed. C C 0 5 C H A S S I S F R A M E Chassis Frame Overview The Blue Bird Vision s chassis frame consists of two main C-channel rails which run the entire length of the bus, and several different kinds of cross

More information

Cooling system components, removing and installing

Cooling system components, removing and installing Volkswagen Touareg 3.2 - Cooling system components, removing and installing Page 1 / 24 19-1 Cooling system components, removing and installing Warning! Hot steam may escape when opening expansion tank.

More information

Agri-Fab OWNERS MANUAL. Model No. 45-02931 25 GALLON "PRO" TOW SPRAYER

Agri-Fab OWNERS MANUAL. Model No. 45-02931 25 GALLON PRO TOW SPRAYER Agri-Fab OWNERS MANUAL Model No. 45-02931 CAUTION: Read Rules for Safe Operation and Instructions Carefully Assembly Operation Maintenance Repair Parts 25 GALLON "PRO" TOW SPRAYER the fastest way to purchase

More information

Accessory Manual Ventilation Section Model Comfort Circle

Accessory Manual Ventilation Section Model Comfort Circle Accessory Manual Ventilation Section Model Comfort Circle Manual version:. R a Copyright and trademarks All the information and drawings in this manual are the property of Biddle and may not be used (other

More information

METHOD STATEMENT INSTALLATION OF INSULATING FLANGE KITS

METHOD STATEMENT INSTALLATION OF INSULATING FLANGE KITS METHOD STATEMENT INSTALLATION OF INSULATING FLANGE KITS Revision Date Prepared By Approved By Method Statement IF Kits BAC Corrosion Control Limited Stafford Park 11 Telford TF3 3AY Tel: 01952 290321 Fax:

More information