SET3M. electro-mechanical 24 programmer for heating & hot water. Installation & User Instructions

Size: px
Start display at page:

Download "SET3M. electro-mechanical 24 programmer for heating & hot water. Installation & User Instructions"

Transcription

1 SET3M electro-mechanical 24 programmer for heating & hot water Installation & User Instructions

2 Index Installation Product specification 3 Installation 4-5 Wiring 6-12 Replacement User Your programmer 16 Setting the clock 16 Programming the unit 17 Using the programmer 18 Overrides 19 Manual use 19 Contact details 20 IDEX 2

3 Installation Instructions Please ote: This product should only be installed by a qualified electrician or competent heating installer, and should be in accordance with the current edition of the IEEE wiring regulations. Product specification Specification Power supply Switch action 230 ± 15% Vac, 50/60Hz 2 x SPDT Type 1B Switch rating Max 264 Vac, 50/60Hz, 3(1) A Setting accuracy ± 5 minutes Timing accuracy ± 1 min/month Enclosure rating IP30 Max. ambient temperature 45 C Specification Dimensions, mm (W, H, D) 158 x 98 x 58 Design standard E Control Pollution Situation Degree 2 Rated Impulse Voltage 2.5kV Ball Pressure Test 75 C 3

4 Installation 1. Fix the wallplate to the wall or flush mounted box as required. The connections are at the top and the vertical centre line of the unit, at the position shown on the diagram below C/L (in line with terminal ) Outline of programmer C/L Leave sufficient space for screwdriver access Terminal block Wall or plasterbox fixing Installation Leave at least 25mm below product Rear entry cable access Cable aperture knockouts 2. Surface cables can only enter from below the unit. If mounted on a flush mounted box, cables can enter from the rear through the aperture in the wallplate. 3. For mains voltage applications a link must be fitted between terminals L, 2 and Whilst the unit does not require an Earth connection, a terminal is provided on the wallplate for Earth continuity purposes. 4

5 5. Referring to the wiring diagrams on page 6-12, connect the unit as shown. 6. The unit is supplied ready for use in systems having PUMPED primaries. Should the unit be required for use in a system having GRAVITY primaries, fit the small plastic shorting link (which can be found taped below the left hand fixing screw hole of the wallplate) over the two pins on the rear of the plug-in module. These pins can be found in the recess near to the bottom edge of the plug-in module. 7. Ensure all dust and debris are cleared from the area. 8. Locate the module on the latches at the bottom of the wallplate and hinge upwards to fully engage the unit connectors into the wallplate. Tighten the two fi xing screws to secure the unit to the wallplate. 9. Before setting the programme, check the unit and circuit. Switch O the mains supply and press both WATER and HEATIG rocker switches to the COSTAT position - both red LED s should now be illuminated. Adjust any remote thermostat to check the services operate correctly. Installation 10. Then press both WATER and HEATIG rocker switches to the OFF position and check that both services do not operate. 11. Finally, press both WATER and HEATIG rocker switches to TIMED position prior to programming the unit. 5

6 Wiring Diagrams The following pages contain typical wiring diagrams for various types of systems. ote: Whilst every attempt has been made to ensure the accuracy of this information it is recommended that the specific information relating to the ancillary controls is obtained from the manufacturers concerned. SET3M E LS A TE SET2E, 3E, 3M &FP975 ( /01) Wiring For mains voltage applications a link must be fitted between terminals L, 2 and 5. 6

7 SET3M Gravity Typical gravity DHW pumped HTG Terminals D.H.W on-com-off HTG / on-com-off L Mains Supply L 3 amp fuse Room Stat Boiler Pump Other Danfoss Randall products suitable for use with above circuit:- RMT room thermostat Wiring - Gravity systems 7

8 SET3M Pumped Typical fully pumped system with spring return zone valve in HTG Terminals D.H.W on-com-off HTG / on-com-off L Mains Supply L 3 amp fuse Room Stat Wiring - pumped systems Cylinder Stat Boiler and Pump S.R.Z.V in HTG Other Danfoss Randall products suitable for use with above circuit:- AT cylinder thermostat; RMT room thermostat; HP22 or HP28 motorised zone valve with spring return actuator and SPST auxiliary switch 8

9 Typical gravity DHW pumped HTG with spring return zone valve in DHW Terminals D.H.W on-com-off HTG / on-com-off L Mains Supply L 3 amp fuse Room Stat Cylinder Stat S.R.Z.V in DHW Boiler Other Danfoss Randall products suitable for use with above circuit:- AT cylinder thermostat; RMT room thermostat; HP28C motorised zone valve with spring return actuator and SPDT auxiliary switch Pump Wiring - pumped systems 9

10 Typical fully pumped system with 3-port midposition valve Terminals D.H.W on-com-off HTG / on-com-off L Mains Supply L 3 amp fuse Room Stat Wiring - pumped systems Cylinder Stat Boiler and Pump 3-port mid-position valve Other Danfoss Randall products suitable for use with above circuit:- AT cylinder thermostat; RMT room thermostat; HS3 3-port mid-position valve with spring return actuator 10

11 Typical fully pumped system with spring return zone valve in each service Terminals D.H.W on-com-off HTG / on-com-off L Mains Supply L 3 amp fuse Room Stat Cylinder Stat S.R.Z.V in DHW Boiler and Pump S.R.Z.V in HTG Other Danfoss Randall products suitable for use with above circuit:- AT cylinder thermostat; RMT room thermostat; 2 x HP22 or HP28 motorised zone valve with spring return actuator and SPST auxiliary switch Wiring - pumped systems 11

12 Typical fully pumped system with fully motorised zone valve in each service Terminals D.H.W on-com-off HTG / on-com-off L Mains Supply L 3 amp fuse Room Stat Wiring - pumped systems Cylinder Stat F.M.Z.V in DHW Boiler and Pump Other Danfoss Randall products suitable for use with above circuit:- AT cylinder thermostat; RMT room thermostat F.M.Z.V in HTG 12

13 Replacement Please see overleaf for a table containing replacement wiring information. Some time controls are connected in different ways depending upon the type of system and/or the controls which are fitted. Consult the column headed OTE: The conversion applies only if... to determine how the SET3M programmer s GRAVITY or PUMPED link should be set. If there is any doubt about the way in which the existing programmer is connected, please contact our Technical Services Department before proceeding with replacement. ote: The SET3M is a direct plug-in replacement for any existing programmers using the British Gas Standard Wallplate. This includes the Horstmann 425 Tiara and Diadem electro-mechanical and 525 & 527 electronic programmers. Replacement 13

14 Danfoss Randall SET3M (PUMPED) MAIS WATER HEATIG L O COM OFF O COM OFF OTE: This conversion only applies if... L A B C D Danfoss Randall 922/972 L Glowworm Mastermind L Pumped/Gravity link is set to pumped Horstmann 423 Amethyst 7 & 10 2, Horstmann 424 GEM 2,3 1, Terminals 5,8 & 10 are linked Horstmann Leucite 423 & Terminals 5 & 7 are linked Honeywell ST669 L Landis & Gyr RWB2 L Potterton Mini-Minder L Pumped/Gravity link is set to pumped Potterton EP2000, EP3000 L A B C D Randall , Danfoss Randall Sangamo Form & 414 4, Sangamo S409/1,- 1,3 L ,4 14

15 Sangamo S409/3 3, Satchwell Libra & DHP Satchwell ET 1401 & ET Smith Ind Centroller Smith Ind Centroller 1000 L Pumped/Gravity link is set to Pumped Switchmaster 800 & 805 L Switchmaster 900 & 9000 L Pumped/Gravity link is set to Pumped A B C Venner CHC/W2 (with stat),- 2,4 L A/S - - A/-S,- 3A- /S,3 Venner CHC/W2 (air stat linked),- 2,4 L Venner Ventrolnol 80M & 80PM (with air stat) Venner Ventrolnol 80M & 80PM (air stat linked),3 L 2-1 A/S - 4,3 L Used in a system having independent control of hot water A/-S,5 15

16 User Instructions Your programmer The SET3M programmer allows you to switch your hot water and heating on and off at times that suit you. Your Programmer & Setting the Clock Four tappets on the timing dial let you decide when you want your hot water and heating to come on and go off each day. The programmer provides 2 O times and 2 OFF times per day. Using two simple rocker switches you can control your heating and hot water separately, to suit your lifestyle. Setting the Clock Remove the dial cover Turn the dial clockwise until the correct time is lined up with the TIME setting line Day segment, covering 6.00am-6.00pm, has an aluminium finish TIME setting line Day segment ight segment, covering 6.00pm-6.00am, is coloured black ight segment! IMPORTAT: If you have a powercut you will have to reset the time - and also when the clocks change in Spring and Autumn 16

17 Programming the unit There are four TAPPETS on your timing dial, two red and two blue: the red tappets are the O switches the blue tappets are the OFF switches Tappets Tappets 1 If you have not already done so, remove the dial cover 2 Hold the black & silver knob with one hand and move the red tappet marked A clockwise to the time you want your HEATIG/HOT WATER to switch on in the morning. B. you may find the tappets quite stiff, so you may have to push them quite firmly to move them. Programming the unit 3 Hold the black knob with one hand and move the blue tappet marked B to the time you want your HEATIG/ HOT WATER to switch off in the morning. 4 You can set your other two tappets in the same way to set your HEATIG/HOT WATER for the afternoon or evening.! DO OT switch the programmer on and off with the mains switch as this will stop the clock/timer and affect the timed programme. 17

18 Using the Programmer The 2 rocker switches are used to select how the SET3M controls your hot water and heating. The heating and hot water can be operated together or independently of each other (i.e. during the summer when only hot water is required). Using the programmer WATER switch OFF - the Hot Water is manually switched OFF and will stay off until you change the position of the switch Timed - the Hot Water will come on and go off at the times you have programmed Constant - the Hot Water will come on manually and stay on constantly until you change the position of the switch A red light adjacent to the WATER switch is lit whenever the Water is switched on. HEATIG switch OFF - the Heating is manually switched OFF and will stay off until you change the position of the switch Timed - the Heating will come on and go off at the times you have programmed Constant- the Heating will come on manually and stay on constantly until you change the position of the switch A red light adjacent to the HEATIG switch is lit whenever the Heating is switched on. 18

19 Overrides Sometimes you may need to change the way you use your heating or hot water temporarily, i.e. due to unusually cold weather. The SET3M has one convenient override which can be selected without affecting the set programme. The RED/BLUE wheel on the lefthand corner of the unit is an OVERRIDE SWITCH. Override wheel When it shows RED the clock is O When it shows BLUE the clock is OFF Manual Use If you do not wish to use the timer facility, you can switch your heating and hot water on or off manually by using the OVERRIDE wheel without having to change the settings on the timer itself. Overrides To use, turn the override wheel anti-clockwise until the thumbwheel displays the setting you require. The override will automatically cancel at the next pre-set time change. 19

20 Still having problems? Call your local heating engineer: ame: Tel: Visit our website: our technical department: Call our technical department ( Mon-Thurs, Fri) For a large print version of these instructions please contact the Marketing Services Department on Part o Issue 03 05/05 Danfoss Randall Ltd Ampthill Road Bedford MK42 9ER Tel: Fax:

SET1E. Installation & User Instructions. Electronic timeswitch for heating & hot water. Certification Mark

SET1E. Installation & User Instructions. Electronic timeswitch for heating & hot water. Certification Mark SET1E Electronic timeswitch for heating & hot water Installation & User Instructions Certification Mark Index INDEX Installation Product specification 3 Installation 4-5 Wiring 5-10 Replacement 11-13 User

More information

Installation & User Instructions

Installation & User Instructions 103 electro-mechanical 24 hour timeswitch for controlling hot water and heating Installation & User Instructions including Factory Replacement Units (FRU) Certification Mark This product complies with

More information

User Operating Instructions Horstmann 425 Coronet Electro-mechanical Timeswitch

User Operating Instructions Horstmann 425 Coronet Electro-mechanical Timeswitch User Operating Instructions Horstmann 425 Coronet Electro-mechanical Timeswitch The Horstmann 425 Coronet timeswitch is a single circuit central heating timeswitch able to switch ON and OFF twice every

More information

Drayton Digistat +2RF/+3RF

Drayton Digistat +2RF/+3RF /+3RF Programmable Room Thermostat Wireless Model: RF700/22090 Model: RF701/22092 Power Supply: Battery - Thermostat Mains - Digistat SCR Invensys Controls Europe Customer Service Tel: 0845 130 5522 Customer

More information

Programmable Room Thermostat 7 Day (5-2 Day) Models: 22083 / 22087 Power Supply: Battery / Mains

Programmable Room Thermostat 7 Day (5-2 Day) Models: 22083 / 22087 Power Supply: Battery / Mains Drayton Programmable Room Thermostat 7 Day (5-2 Day) Models: 22083 / 22087 Power Supply: Battery / Mains Invensys Controls Europe Technical Helpline: +44 (0) 845 130 7722 www.draytoncontrols.co.uk Installation

More information

TP5000 Si Range Electronic 5/2 day programmable room thermostat Mains, Battery and RF versions Installation and User Instructions

TP5000 Si Range Electronic 5/2 day programmable room thermostat Mains, Battery and RF versions Installation and User Instructions TP5000 Si Range Electronic 5/2 day programmable room thermostat Mains, Battery and RF versions Certification Mark GB Installation and GB Index Index Installation Instructions 3-14 Product Specification

More information

HERZ-Thermal Actuators

HERZ-Thermal Actuators HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01

More information

Wireless 7 Day Programmable Room Thermostat

Wireless 7 Day Programmable Room Thermostat Wireless 7 Day Programmable Room Thermostat Cat. No. TRT037 Transmitter Receiver Operating & Installation Instructions What is a programmable room thermostat? an explanation for householders A programmable

More information

Fully Pumped Systems

Fully Pumped Systems Fully Pumped Systems (also see the picture gallery and System Basics) The term for any boiler that uses a pump to move all the heat from the boiler to every part of the system is fully pumped. As a rule

More information

TRANSMITTER RECEIVER THESE INSTRUCTIONS APPLY IN THE UK ONLY THESE INSTRUCTIONS ARE TO BE LEFT WITH THE USER OR AT THE APPLIANCE. Digistat Optimiser

TRANSMITTER RECEIVER THESE INSTRUCTIONS APPLY IN THE UK ONLY THESE INSTRUCTIONS ARE TO BE LEFT WITH THE USER OR AT THE APPLIANCE. Digistat Optimiser FITTING AND OPERATING INSTRUCTIONS FOR DIGISTAT OPTIMISER PROGRAMMABLE 7 DAY ROOM THERMOSTAT SYSTEM General information is given in the users instruction leaflet despatched with the appliance and/or on

More information

IMPORTANT: BEFORE INSTALLING ANY HEATING TERMINAL UNIT TO A DOMESTIC WATER HEATER, CONSULT THE LOCAL PLUMBING CODES.

IMPORTANT: BEFORE INSTALLING ANY HEATING TERMINAL UNIT TO A DOMESTIC WATER HEATER, CONSULT THE LOCAL PLUMBING CODES. QUIET-ONE Environmental Products 2000 Kickspace Heater Series Models: KS 2004, KS 2006 KS 2008, KS 2010 INSTALLATION OPERATING MAINTENANCE Please read these instructions thoroughly before beginning your

More information

User's Instructions. Alpha HE CB25/33 and HE SY25

User's Instructions. Alpha HE CB25/33 and HE SY25 User's Instructions Alpha HE CB25/33 and HE SY25 Wall Mounted, Fan Assisted, Room Sealed, Gas Fired, High Efficiency Condensing Boiler Range For Technical help or for Service call... ALPHA HELPLINE Tel:

More information

BARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell

BARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell Data, installation, operation and maintenance 4 & 8 Zone Fire Panels Zircon range BARDIC by Honeywell LED flashing LED Continuous FAULT DISABLE/TEST Power General Fault Sounder Fault/ Disable System Fault

More information

Solid-State Timer H3G

Solid-State Timer H3G ASH & ALAIN INDIA PVT LTD S-100, F.I.E.E., Okhla Industrial Area, Phase-ii, New Delhi-11000(India) Tel : 011-43797575 Fax : 011-43797574 E-mail : sales@ashalain.com Solid-State Timer Low-Cost, Plug-In

More information

OPERATING INSTRUCTIONS

OPERATING INSTRUCTIONS 24 HOUR IMMERSION HEATER TIME CONTROLLER Cat. No TS900B OPERATING INSTRUCTIONS TS900B 24 Hour Immersion Heater Time Controller 24 hour programme ring Self-cancelling and Override switch Setting pins Time

More information

ACS-30-EU-EMDR-10-MOD

ACS-30-EU-EMDR-10-MOD Multi-application heat tracing Control and Monitoring in commercial and residential buildings Roof & Gutter de-icing sensor module Technical Information Approvals Module IP rating Ambient operating temperature

More information

For installation guide see reverse of book

For installation guide see reverse of book USERS GUIDE LOGIC Combi 24, 30, 35 For installation guide see reverse of book When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance

More information

ELECTRIC CENTRAL HEATING FLOW BOILER

ELECTRIC CENTRAL HEATING FLOW BOILER ELECTRIC CENTRAL HEATING FLOW BOILER EKCO.T Used product can t be treated as general communal waste. Disassembled appliance has to be delivered to the collection point of electrical and electronic equipment

More information

Baxi Platinum Combi HE Range. User s Operating Instructions & Important Warranty Information. Gas Fired Wall Mounted Condensing Combination Boiler

Baxi Platinum Combi HE Range. User s Operating Instructions & Important Warranty Information. Gas Fired Wall Mounted Condensing Combination Boiler User s Operating Instructions & Important Warranty Information Baxi Platinum Combi HE Range Gas Fired Wall Mounted Condensing Combination Boiler Please keep these instructions safe. Should you move house,

More information

Operating Instructions DT, PRT, PRT/HW PRT-R, PRT-R2

Operating Instructions DT, PRT, PRT/HW PRT-R, PRT-R2 Operating Instructions DT, PRT, PRT/HW PRT-R, PRT-R2 Heatmiser UK td Tel: +44(0)1254 776343 Primrose House www.heatmiser.co.uk Primrose Street Darwen ancashire BB3 2DE Contents Contents 1 Installation

More information

Baxi Combi Instant 80e & 105e. User s Operating Instructions. Gas Fired Wall Mounted Combination Boiler

Baxi Combi Instant 80e & 105e. User s Operating Instructions. Gas Fired Wall Mounted Combination Boiler User s Operating Instructions Baxi Combi Instant 8e & 15e Gas Fired Wall Mounted Combination Boiler Please keep these instructions safe. Should you move house, please hand them over to the next occupier.

More information

Rain+Birdt. Simple To Set Timer (SST) Setup & Operation Instructions. English. 1-800- RAIN BIRD (800-724-6247) or visit www.rainbird.

Rain+Birdt. Simple To Set Timer (SST) Setup & Operation Instructions. English. 1-800- RAIN BIRD (800-724-6247) or visit www.rainbird. Rain+Birdt Simple To Set r (SST) Setup & Operation Instructions English Installation...2 Tools and Supplies Needed...2 Step 1. Mount r...2 Step 2. Connect Power...2 Indoor r...2 Outdoor r...2 Step 3. Connect

More information

RDJ10RF/SET. Wireless room temperature controller with 24-hour time switch and LCD. Programmable, for heating systems

RDJ10RF/SET. Wireless room temperature controller with 24-hour time switch and LCD. Programmable, for heating systems 3 072 RDJ10RF RCR10/433 Wireless room temperature controller with 24-hour time switch and LCD Programmable, for heating systems RDJ10RF/SET Operating modes: Automatic, Comfort, Energy Saving, and Frost

More information

5W LED Energy Saver PIR Bulkhead

5W LED Energy Saver PIR Bulkhead 5W LED Energy Saver PIR Bulkhead Model: LED88PIR Black I n s t a l l a t i o n & Ope r a t i n g I n s t r u c t i o n s 1. General information: The unit utilises passive infrared technology to detect

More information

CM702 PROGRAMMABLE THERMOSTAT FEATURES PRODUCT SPECIFICATION SHEET

CM702 PROGRAMMABLE THERMOSTAT FEATURES PRODUCT SPECIFICATION SHEET CM702 PROGRAMMABLE THERMOSTAT FEATURES Attractive slim, modern styling makes it ideal for location in any type of home. 24-hour heating program. Up to 4 daily independent time and temperature level changes

More information

Owner s Guide Guide du propriétaire Guía para el usuario TH115-AF-GB-10. Programmable thermostat Thermostat programmable Termostato programable

Owner s Guide Guide du propriétaire Guía para el usuario TH115-AF-GB-10. Programmable thermostat Thermostat programmable Termostato programable Owner s Guide Guide du propriétaire Guía para el usuario TH115-AF-GB-10 Programmable thermostat Thermostat programmable Termostato programable Read and save these instructions. Veuillez lire le mode d

More information

XE70 SERIES VC SERIES BALANCED HYDRONIC VALVES 2-WAY AND 3-WAY

XE70 SERIES VC SERIES BALANCED HYDRONIC VALVES 2-WAY AND 3-WAY XE70 SERIES VC SERIES BALANCED HYDRONIC VALVES 2-WAY AND 3-WAY PRODUCT SPECIFICATION SHEET switched off. This results in energy savings during mild weather. Normal control will resume when T3 fails to

More information

HEAT PUMP PROGRAMMABLE THERMOSTAT

HEAT PUMP PROGRAMMABLE THERMOSTAT HEAT PUMP PROGRAMMABLE THERMOSTAT SA PM 3 COOL TEMP Form 44014-01 r010408 Model 43168 Owners Manual 1 Congratulations! Heat Pump Programmable Thermostat Model 43168 THERMOSTAT CONTROLS Switches & Buttons...15

More information

Disabled Toilet Alarm. Contractor Pack. Installation & Operating Instructions

Disabled Toilet Alarm. Contractor Pack. Installation & Operating Instructions Disabled Toilet Alarm Installation & Operating Contractor Pack Installation & Operating Instructions 1 Overview The Channel Safety Systems Disabled Toilet alarm contractor Packs are an efficient way of

More information

COMPUTHERM Q7 Programmable, digital room thermostat. Operating Instructions

COMPUTHERM Q7 Programmable, digital room thermostat. Operating Instructions COMPUTHERM Q7 Programmable, digital room thermostat Operating Instructions GENERAL DESCRIPTION OF THE THERMOSTAT The COMPUTHERM Q7 type switched-mode room thermostat is suitable to regulate the overwhelming

More information

Baxi Combi 80e & 105e

Baxi Combi 80e & 105e Baxi Combi 8e & 15e Please keep these instructions safe. Should you move house, please hand them over to the next occupier. Gas Fired Wall Mounted Combination Boiler User s Operating Instructions Natural

More information

ecomax Instructions for use Wall hung room sealed fan assisted condensing boilers For the user

ecomax Instructions for use Wall hung room sealed fan assisted condensing boilers For the user For the user Instructions for use ecomax Wall hung room sealed fan assisted condensing boilers ecomax 63/ E ecomax 68/ E ecomax 6/ E ecomax 635 E ecomax 84/ E ecomax 88/ E ecomax 835 E GB Table of contents

More information

Data sheet ECC 12 and 22

Data sheet ECC 12 and 22 Application ECC is an electronic room temperature controller for water-based systems. ECC can control - fan-coil units - inductions units - air conditioning systems - small ventilating systems - 2-pipe

More information

60W PIR BULKHEAD LIGHT SLB88-Black/SLW89-White INSTALLATION & OPERATING INSTRUCTIONS

60W PIR BULKHEAD LIGHT SLB88-Black/SLW89-White INSTALLATION & OPERATING INSTRUCTIONS 60W PIR BULKHEAD LIGHT SLB88-Black/SLW89-White INSTALLATION & OPERATING INSTRUCTIONS SLB88 PIR BULKHEAD LIGHT - BLACK WEATHERPROOF LAMP TYPE IP44 60w ES MAXIMUM PIR SWITCHING 500w MAXIMUM TIME ON DETECTION

More information

Applied Electronics. Commercial Dimming System UPDATE NOTICE

Applied Electronics. Commercial Dimming System UPDATE NOTICE REV. A Applied Electronics Commercial Dimming System UPDATE NOTICE This notice is to inform the end user of an additional feature added to this DP12/2400 dimming unit. This unit has been outfitted with

More information

Alpha Climatic Programmable Modulating Boiler Energy Manager. Installation and User Instructions

Alpha Climatic Programmable Modulating Boiler Energy Manager. Installation and User Instructions Alpha Climatic Programmable Modulating Boiler Energy Manager Part No 3.022144 (Hard Wired) Part No 3.022143 (Radio Frequency) Installation and User Instructions 1. Description The Alpha Climatic energy

More information

Bathroom Cabinet. Installation & User Guide. Illuminated Mirrors. www.illuminated-mirrors.uk.com

Bathroom Cabinet. Installation & User Guide. Illuminated Mirrors. www.illuminated-mirrors.uk.com Illuminated Mirrors The UK s Largest LED Mirror Supplier to Trade and Retail Installation & User Guide Bathroom Cabinet www.illuminated-mirrors.uk.com Bathroom Cabinet Installation & User Guide Thank you

More information

225-230T-05-S2. Rotary drive without spring return. Technical data sheet. Description. Technical data. Actuators

225-230T-05-S2. Rotary drive without spring return. Technical data sheet. Description. Technical data. Actuators Actuators Technical data sheet 225-230T-05-S2 Rotary drive without spring return Description Actuator for adjusting air dampers of 90 angle of rotation to be used in HVAC installations. Torque Motor 5

More information

DS 1.102 DRTE. AIR ROOM TEMPERATURE SENSOR with fan speed control switches

DS 1.102 DRTE. AIR ROOM TEMPERATURE SENSOR with fan speed control switches DS 1.102 02/99 AIR ROOM TEMPERATURE SENSOR with fan speed control switches Specification No. 528-X-XXX* The Active Room Temperature sensor incorporating fan speed control switches is designed to give a

More information

WE-350 Series ¼ Turn Electric Actuator

WE-350 Series ¼ Turn Electric Actuator WE-350 Series ¼ Turn Electric Actuator Operation and Installation Manual Pg 1 (Rev. 020113) Table of Contents 1.0 General 1.1 Pre-Installation Inspection 1.2 Storage 1.3 Features & General Information

More information

USERS GUIDE. LOGIC Combi 24, 30, 35. For installation guide see reverse of book

USERS GUIDE. LOGIC Combi 24, 30, 35. For installation guide see reverse of book USERS GUIDE LOGIC Combi 24, 30, 35 For installation guide see reverse of book When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance

More information

Installation Guide. VisionPRO. TH8000 Series. Need Help? This manual covers the following models. System Types

Installation Guide. VisionPRO. TH8000 Series. Need Help? This manual covers the following models. System Types Installation Guide VisionPRO TH8000 Series Touch-screen Programmable Thermostat This manual covers the following models TH8110U: For 1 Heat/1 Cool systems TH8320U: For up to 3 Heat/2 Cool systems TH8321U:

More information

PROGRAMMING & OPERATING INSTRUCTIONS CL5000 AUDIT TRAIL

PROGRAMMING & OPERATING INSTRUCTIONS CL5000 AUDIT TRAIL PROGRAMMING & OPERATING INSTRUCTIONS CL5000 AUDIT TRAIL 1 CODES AND OPERATION CODES The factory set Master Code is #1234. This should be changed immediately after installation (see Program 10). The Master

More information

Table of Contents. Introduction. Radio Frequency Control. Initial setup Setting the time. Setting the temperature

Table of Contents. Introduction. Radio Frequency Control. Initial setup Setting the time. Setting the temperature LHZ USER GUIDE LHZ User Guide LHZ would like to thank you for purchasing your LHZ radiator. You have purchased a high quality, German designed and manufactured heating device, which will give you soft

More information

TIMERS AND CONTROLS ELECTRONIC 7 WATER HEATER CONTROLLER FOR ECONOMY 7 AND WHITE METER TARIFFS USERS OPERATING INSTRUCTIONS

TIMERS AND CONTROLS ELECTRONIC 7 WATER HEATER CONTROLLER FOR ECONOMY 7 AND WHITE METER TARIFFS USERS OPERATING INSTRUCTIONS TIMERS AND CONTROLS ELECTRONIC 7 WATER HEATER CONTROLLER FOR ECONOMY 7 AND WHITE METER TARIFFS USERS INSTRUCTIONS USERS OPERATING INSTRUCTIONS The Horstmann Electronic 7 Water Heater Controller has been

More information

CR9971 2 Band Auto Set Dual Alarm Clock Radio ROBERTS. Sound for Generations. Please read this manual before use

CR9971 2 Band Auto Set Dual Alarm Clock Radio ROBERTS. Sound for Generations. Please read this manual before use ROBERTS Sound for Generations CR9971 2 Band Auto Set Dual Alarm Clock Radio Please read this manual before use Contents Contents... 1 Controls...2-5 Switching on... 6 Setting the time manually... 6 Setting

More information

Installation Guide. DEVIreg 530. Electronic Thermostat. www.devi.com

Installation Guide. DEVIreg 530. Electronic Thermostat. www.devi.com Installation Guide DEVIreg 530 Electronic Thermostat www.devi.com The English language is used for the original instructions. Other languages are a translation of the original instructions. (Directive

More information

GB/DAS User Instruction

GB/DAS User Instruction GB/DAS User Instruction devireg 540/550 Table of contents Introduction 3 Introducing devireg 540/550 4 How to use your deviheat heating system 6 Daily operation 7 Setting the clock & day 10 Timer programming

More information

Users Instructions 0694 51BQ3030 THESE INSTRUCTIONS TO BE RETAINED BY USER

Users Instructions 0694 51BQ3030 THESE INSTRUCTIONS TO BE RETAINED BY USER Users Instructions 0694 51BQ3030 THESE INSTRUCTIONS TO BE RETAINED BY USER G.C. NUMBER SABRE 25 HE N 470 94 70 SABRE 29 HE N 470 94 71 SABRE 35 HE N 470 94 72 Contents Introduction Page Dear customer 2

More information

UNDERFLOOR HEATING SYSTEMS DETAILS AND NOTES

UNDERFLOOR HEATING SYSTEMS DETAILS AND NOTES UNDERFLOOR HEATING SYSTEMS DETAILS AND TES CONTENTS 1 MANIFOLD DETAILS AND DIMENSIONS 2 TYPICAL CIRCUIT LAYOUT DETAILS 3 JOISTED SYSTEM DETAIL ( PLATES FROM ABOVE ) 4 JOISTED SYSTEM DETAIL ( PLATES FROM

More information

FIRERAY 2000 Installation Guide

FIRERAY 2000 Installation Guide FIRERAY 2000 Installation Guide Features Range 33ft to 330 ft. 24Vdc operation Selectable alarm thresholds Low current consumption Ground level electronics Manual or Automatic reset System Description

More information

VC Series Zone Valves BALANCED 2-WAY AND 3-WAY HYDRONIC VALVES

VC Series Zone Valves BALANCED 2-WAY AND 3-WAY HYDRONIC VALVES VC Series Zone Valves BALANCED 2-WAY AND 3-WAY HYDRONIC VALVES PRODUCT DATA Design VC Series zone valves consist of: 2-way or 3-way valve housing available with various connection ends Spindle and cartridge

More information

Vroom Hardware manual ver. 1.00 Code 114VROOHWE00. Vroom CANBUS USER INTERFACE WITH LCD GRAPHIC DISPLAY AND WITH TEMPERATURE AND HUMIDITY SENSOR

Vroom Hardware manual ver. 1.00 Code 114VROOHWE00. Vroom CANBUS USER INTERFACE WITH LCD GRAPHIC DISPLAY AND WITH TEMPERATURE AND HUMIDITY SENSOR Vroom CANBUS USER INTERFACE WITH LCD GRAPHIC DISPLAY AND WITH TEMPERATURE AND HUMIDITY SENSOR ENGLISH HARDWARE MANUAL ver. 1.00 CODE 114VROOHWE00 page 1 of 22 Important Important Read these instructions

More information

FIREDEX 2200. Conventional Fire Panels

FIREDEX 2200. Conventional Fire Panels 68 Flexible, high specification system Choice of 1, 2, 4 or 8 zones Simple one-shot auto-reset user test facility Approved to EN54 Maintenance free poly switch circuit protection, with auto reset Class

More information

Table of Contents. 1 - Specifications...3. 2 - Installation...3. 3 - Wiring...5. 4 - User controls...7

Table of Contents. 1 - Specifications...3. 2 - Installation...3. 3 - Wiring...5. 4 - User controls...7 THERMOSTATS Table of Contents Page 1 - Specifications...3 1.1 - Product range...3 ARTTH001 (DSL-610)...3 ARTTH002 (DSL-700)...3 ARTTH003 (DSL-600)...3 1.2 - Technical data...3 1.3 - Power failures...3

More information

ELECTRIC POSITION for electric heat, then confirm with Fan Test below.

ELECTRIC POSITION for electric heat, then confirm with Fan Test below. Troubleshooting Poor Temperature Regulation This page lists problems that may affect the temperature performance of your LUX thermostat with suggested resolutions. For more detailed information please

More information

DUAL SENSING DIGITAL THERMOSTAT PRODUCT INSTRUCTIONS. Construction Automotive Industry

DUAL SENSING DIGITAL THERMOSTAT PRODUCT INSTRUCTIONS.  Construction Automotive Industry DUAL SENSING DIGITAL THERMOSTAT PRODUCT INSTRUCTIONS www.rehau.com Construction Automotive Industry SCOPE This guide gives instruction regarding REHAU Programmable Digital Thermostat installation and operation.

More information

LIEBERT VNSA Installation Sheet

LIEBERT VNSA Installation Sheet LIEBERT VNSA Installation Sheet Description The Liebert vnsa network switch is designed for connecting multiple Ethernet-ready devices and comes in various models. The unit may have: A Liebert icom display

More information

Smile. The All-In-One Heating Controller

Smile. The All-In-One Heating Controller Smile EVERYTHING UNDER CONTROL The All-In-One Heating Controller Versatile, energy-efficient heating control. The All-In-One Heating Controller Smile controllers are ideal to gain maximum efficiency from

More information

3/2-way Solenoid Valve, direct-acting, NC or NO

3/2-way Solenoid Valve, direct-acting, NC or NO 3/2-way Solenoid Valve, direct-acting, NC or NO Electrical connection cable plug, Form A With or without manual override as standard Threaded port and sub-base s Impulse optional Type 6014 can be combined

More information

Master Time Clock MTC-200 MTC-400 MTC-600. Users Manual

Master Time Clock MTC-200 MTC-400 MTC-600. Users Manual Master Time Clock MTC-200 MTC-400 MTC-600 Users Manual Toll Free (888)713-0373 Phone (972)987-4408 FAX (877)720-9291 www.midwest-time.com sales@midwest-time.com TABLE OF CONTENTS TOPIC PAGE GENERAL DESCRIPTION

More information

V94 BULK TAPE DEGAUSSER

V94 BULK TAPE DEGAUSSER TECHNICAL MANUAL Operating and Maintenance Instructions for V94 BULK TAPE DEGAUSSER V94 BULK TAPE DEGAUSSER TECHNICAL MANUAL Document No. M000208 Production Standard ZZ 009 415 WARNING To help minimise

More information

www.the Floor Heating Warehouse.co.uk

www.the Floor Heating Warehouse.co.uk www.the Floor Heating Warehouse.co.uk Underfloor Heating Installation Guide (Grundfoss Pump System) General Overview: Our water based underfloor heating system can be installed by your own plumber or heating

More information

EK908FHL - Thermostat for floor heating

EK908FHL - Thermostat for floor heating EK908FHL - Thermostat for floor heating EK908FHL is a programmable thermostat designed for floor warming application or helping to limit floor temperature. This thermostat can be used for hot water radiant

More information

SETTING UP YOUR 6000 SERIES TIME RECORDER

SETTING UP YOUR 6000 SERIES TIME RECORDER INTRODUCTION The Pyramid 6000 Series Time Recorder is an electronic time recorder designed to make payroll processing easier and more efficient. The 6000 series will meet your business needs whether your

More information

2 Wire Electronic Time Delay Switch. 2 Wire Slave Switch. 3 Wire Electronic Time Delay Switch

2 Wire Electronic Time Delay Switch. 2 Wire Slave Switch. 3 Wire Electronic Time Delay Switch 2 Wire Electronic Time Delay Switch Cat No. DS1 2 Wire Slave Switch Cat No. DSS 3 Wire Electronic Time Delay Switch Cat No. DS2 Installation & Operating Instructions DS1/DSS Instructions for Installation

More information

INFRARED QUARTZ WALL HEATER

INFRARED QUARTZ WALL HEATER INFRARED QUARTZ WALL HEATER MODEL NO: IQ2000 PART NO: 6939004 MOUNTING & OPERATION INSTRUCTIONS GC0715 INTRODUCTION Thank you for purchasing this CLARKE Infrared Wall Heater. Before attempting to use this

More information

MOTION SENSOR PIR LIGHT SWITCH INSTALLATION & OPERATING. Cat No. ZV810 INSTRUCTIONS

MOTION SENSOR PIR LIGHT SWITCH INSTALLATION & OPERATING. Cat No. ZV810 INSTRUCTIONS MOTION SENSOR PIR LIGHT SWITCH Cat No. ZV810 INSTALLATION & OPERATING INSTRUCTIONS ZV810 Motion Sensor PIR Light Switch Please read the instructions before using the product and retain for future use.

More information

DIAMOND Retractable Rodding Robot Model SPRAYROD-R

DIAMOND Retractable Rodding Robot Model SPRAYROD-R 2004-12-21 2 1 (23) DIAMOND Retractable Rodding Robot Model SPRAYROD-R 2004-12-21 2 2 (23) Table of contents 1 TECHNICAL DESCRIPTION...4 1.1 MAIN DETAILS...5 1.2 COMPONENTS DESCRIPTION...5 1.2.1 Pneumatic

More information

ETHERNET IRRIGATION CONTROLLER. Irrigation Caddy Model: ICEthS1. User Manual and Installation Instructions

ETHERNET IRRIGATION CONTROLLER. Irrigation Caddy Model: ICEthS1. User Manual and Installation Instructions ETHERNET IRRIGATION CONTROLLER Irrigation Caddy Model: ICEthS1 User Manual and Installation Instructions I R R I G A T I O N C A D D Y M O D E L : I C E T H S 1 User Manual and Installation Instructions

More information

THERMONET UNDERFLOOR HEATING STANDARD THERMOSTAT KIT STOCK CODE 5260

THERMONET UNDERFLOOR HEATING STANDARD THERMOSTAT KIT STOCK CODE 5260 THERMONET UNDERFLOOR HEATING STANDARD THERMOSTAT KIT STOCK CODE 5260 STANDARD THERMOSTAT KIT 1.0 KIT CONTENTS Parts included: 1 x Thermostat 1 x Wall plate 2 x Mounting box screws 1 x Floor temperature

More information

User Manual THR840DUK Digital Thermostat

User Manual THR840DUK Digital Thermostat User Manual THR840DUK Digital Thermostat 50051982-001 Rev. A WARNING: This product must be correctly installed and configured to work properly (see pages 12-24). If you are not experienced in wiring electrical

More information

USERS GUIDE. LOGIC Heat 12, 15, 18, 24, 30. For installation guide see reverse of book

USERS GUIDE. LOGIC Heat 12, 15, 18, 24, 30. For installation guide see reverse of book USERS GUIDE LOGIC Heat 12, 15, 18, 24, 30 For installation guide see reverse of book When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance

More information

PRODUCT PRODUCT CODE TECHNICAL INSTRUCTIONS PAGE

PRODUCT PRODUCT CODE TECHNICAL INSTRUCTIONS PAGE Table of Contents PRODUCT PRODUCT CODE TECHNICAL INSTRUCTIONS PAGE # Electric Room Comfort Controller NEW! RDY2000 Room Comfort Controller RDY 129-905 D-3 Electric for Specialized Applications Surface

More information

Time Recorder. User Manual. PDF created with FinePrint pdffactory trial version www.pdffactory.com

Time Recorder. User Manual. PDF created with FinePrint pdffactory trial version www.pdffactory.com Time Recorder User Manual 1 (1) Specifications: 1. Power supply 100, 110, 200, 220, 230 V AC (as designated), 50/60 Hz, single phase. 2. Power consumption Normal 2W (MAX 30W) 3. Standard time signal Quartz

More information

2400W PIR LIGHT C O N T R O L L E R Cat No. SLW2400

2400W PIR LIGHT C O N T R O L L E R Cat No. SLW2400 2400W PIR LIGHT C O N T R O L L E R Cat No. SLW2400 1 Introduction The SLW2400 utilises passive infrared technology to detect heat radiation of moving human bodies. Upon detection, the attached lighting

More information

Operating Instructions. Room temperature controller

Operating Instructions. Room temperature controller Operating Instructions 1. Area of application The room temperature controller is used to regulate the temperature in closed rooms such as flats, schools, function suites, workshops, etc. Safety instructions

More information

OEM Manual MODEL 2350 ELECTRONIC DUAL CYLINDER SCALE

OEM Manual MODEL 2350 ELECTRONIC DUAL CYLINDER SCALE OEM Manual MODEL 2350 ELECTRONIC DUAL CYLINDER SCALE Scaletron Industries, Ltd. Bedminster Industrial Park 53 Apple Tree Lane P.O. Box 365 Plumsteadville, PA 18949 USA Toll Free: 1-800-257-5911 (USA &

More information

Heating Controller. Building Technologies HVAC Products

Heating Controller. Building Technologies HVAC Products 2 474 Heating Controller RVP300 Multifunctional heating controller for use in residential and non-residential buildings; suitable for weather-dependent flow temperature control of heating zones with or

More information

INSTRUCTION MANUAL FOR RECREATIONAL REFRIGERATOR/FREEZER MODEL

INSTRUCTION MANUAL FOR RECREATIONAL REFRIGERATOR/FREEZER MODEL INSTRUCTION MANUAL FOR RECREATIONAL REFRIGERATOR/FREEZER MODEL 15-LITER, 20-LITER, 35-LITER, 45-LITER, 60-LITER & 100-LITER SECTION 1 Basic Operation SECTION 2 Cleaning and Storing SECTION 3 Basic Trouble

More information

RVR Hybrid System Installer Instructions - 10052012. RVR Hybrid System Controller Installation Instructions

RVR Hybrid System Installer Instructions - 10052012. RVR Hybrid System Controller Installation Instructions RVR Hybrid System Controller Installation Instructions 1 Introduction to Hybrid Systems The RVR Hybrid system uses a combination of the Immergas Audax range of heat pumps with gas or oil boilers to create

More information

Installation & Maintenance Instructions

Installation & Maintenance Instructions (400mm) 15-3/4" (35mm) 1-3/8" (95mm) 3-3/4" K Series (Model A) Fan Forced Wall Heaters (485mm) 19-1/8" (463mm) 18-1/4" FILE #E21609 Installation & Maintenance Instructions Dear Owner, Congratulations Thank

More information

Baxi Combi 130 HE. User s Operating Instructions. Gas Fired Wall Mounted Condensing Combination Boiler

Baxi Combi 130 HE. User s Operating Instructions. Gas Fired Wall Mounted Condensing Combination Boiler User s Operating Instructions Baxi Combi 130 HE Gas Fired Wall Mounted Condensing Combination Boiler Please keep these instructions safe. Should you move house, please hand them over to the next occupier.

More information

OZW30. Central Unit SYNERGYR

OZW30. Central Unit SYNERGYR 2 841 SYNERGYR Central Unit OZW30 Collects billing data from the apartments. Generates an image of each apartment's heat consumption and makes it available for readout. Acts on room temperature control

More information

Product and Application Description

Product and Application Description Technical Product - Information Product and Application Description The room temperature controller UP 237K and UP 252K are available in the following colors, matching the design of the wall switch design

More information

ELECTRONIC THERMOSTAT AND THERMOMETER With SPEED CONTROL

ELECTRONIC THERMOSTAT AND THERMOMETER With SPEED CONTROL 148 OLD CONCORD TURNPIKE, BARRINGTON NH 03825 USA TEL (603) 868-5720 FAX (603) 868-1040 1-800-435-6708 E-Mail:sales@seafrost.com www.seafrost.com ELECTRONIC THERMOSTAT AND THERMOMETER With SPEED CONTROL

More information

Installers and specifiers seeking information and advice on radiator thermostats and their application will find no better source than Danfoss.

Installers and specifiers seeking information and advice on radiator thermostats and their application will find no better source than Danfoss. DOMESTIC HEATING CONTROLS ARE EASY PART 5 - RADIATOR THERMOSTATS Fig.1. RAS-C 2 and RAS-D 2 radiator thermostats with RLV-D lockshield valve Radiator Thermostats (TRVs), the original and straight forward

More information

INSTRUCTIONS FOR INSTALLATION AND SERVICING TURBOmax VUW 242/1 E. TURBOmax VUW 282/1 E

INSTRUCTIONS FOR INSTALLATION AND SERVICING TURBOmax VUW 242/1 E. TURBOmax VUW 282/1 E INSTRUCTIONS FOR INSTALLATION AND SERVICING TURBOmax VUW / E TURBOmax VUW 8/ E Wall hung room sealed fan assisted combination boilers HEATING, CONTROLS, HOT WATER. Page. Introduction. Boiler Specification.

More information

Duct Humidity Transmitter

Duct Humidity Transmitter SDC-H Duct Humidity Transmitter Features Replaceable sensor element Humidity measurement for air ducts Minimum and maximum value memory 0 0V, 0 0mA or 0V, 4 0mA measuring signals selectable with jumpers

More information

Technical Guide. Thermostats Air Conditioning

Technical Guide. Thermostats Air Conditioning Technical Guide Thermostats Air Conditioning TECICA GUIDE TERMOSTATS AIR CODITIOIG Thank you for choosing our products ote: Technical information contained in this catalog may be changed or updated by

More information

DC1100 & 1400 Energy Controllers. Satchwell DC1100 & DC1400 for energy-efficient temperature control in smaller buildings.

DC1100 & 1400 Energy Controllers. Satchwell DC1100 & DC1400 for energy-efficient temperature control in smaller buildings. 1100 & 1400 Energy Controllers Satchwell 1100 & 1400 for energy-efficient temperature control in smaller buildings. 02 1100 & 1400 Energy Controllers Features he 1100 and 1400 Energy Controllers are self-configuring

More information

SECTION G2: CABLE PROCESSOR MODULE MAINTENANCE

SECTION G2: CABLE PROCESSOR MODULE MAINTENANCE SECTION G2: CABLE PROCESSOR MODULE MAINTENANCE Cable Processor Module overview WARNING! When tipping the Cable Processor Module back, (after removing the toggle arm pin), use extreme caution not to drop

More information

Water Leak Detector BA/LDT Accessories Termination and Troubleshooting

Water Leak Detector BA/LDT Accessories Termination and Troubleshooting Overview & Identification The is designed to sense the presence of water and alert a central monitoring system of the potentially destructive situation. Upon water detection, an alarm relay changes state,

More information

SLIM LINE FUME HOOD MONITOR

SLIM LINE FUME HOOD MONITOR SLIM LINE FUME HOOD MONITOR Phoenix Controls FHM420 Fume Hood Monitor is sized to fit any fume hood and includes icons for simple and universal operation. The FHM420 slim line monitor works in conjunction

More information

DEVIreg 330 (+5 to +45 C)

DEVIreg 330 (+5 to +45 C) Installation Guide DEVIreg 330 (+5 to +45 C) Electronic Thermostat www.devi.com Table of Contents 1 Introduction............... 3 1.1 Technical Specifications..... 4 1.2 Safety Instructions........ 5

More information

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2...

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2... Magnetic and Hydraulic-Magnetic Circuit Breaker 840-G2... Description Single, two and three pole magnetic circuit breakers with trip-free mechanism and push/pull on/off manual actuation. A choice of fast

More information

Integrated Presetting Valves for Normal 013G0372 and Small 013G0373 Volume Flows

Integrated Presetting Valves for Normal 013G0372 and Small 013G0373 Volume Flows Integrated Presetting Valves for Normal 013G0372 and Small 013G0373 Volume Flows Application Integrated valves, type RA-N (013G0372) and RA- U (013G0373), with built-in presetting are designed for incorporation

More information

Integrated Presetting Valves - for Normal Volume Flows RA-N and for Small Volume Flows RA-U

Integrated Presetting Valves - for Normal Volume Flows RA-N and for Small Volume Flows RA-U Integrated Presetting Valves - for Normal Volume Flows RA-N and for Small Volume Flows Application Integrated valves, type RA-N (013G1382) and RA- U (013G1383), with built-in presetting are designed for

More information

RVL470. Heating Controller. Building Technologies HVAC Products. Series B

RVL470. Heating Controller. Building Technologies HVAC Products. Series B 2 522 Heating Controller Series B RVL470 Multifunctional heating controller for use in residential and non-residential buildings; suitable for weather-dependent flow temperature control of heating zones

More information

ADS8 IP54 Direct-On-Line Starter Technical Focus. Replaces ADS7 Rated up to 9kW

ADS8 IP54 Direct-On-Line Starter Technical Focus. Replaces ADS7 Rated up to 9kW ADS8 IP54 Direct-On-Line Starter Technical Focus Replaces ADS7 Rated up to 9kW New ADS8 Motor Starter The new ADS8 range of motor starters replaces the successful ADS7 range which was introduced 20 years

More information