Understand Hybrid Generator Battery Systems
|
|
|
- June Gordon
- 9 years ago
- Views:
Transcription
1 Understand Hybrid Generator Battery Systems For off-grid applications powered by diesel generators, move to cyclic operation to save costs Telecommunications operators in Africa, India and other developing countries face severe challenges in powering mobile base station (BTS) sites in remote areas. In many cases, the sites are simply too far from the AC grid for AC mains powering to be economic. Other sites have AC power, but it is extremely unreliable. These sites are often powered by small diesel generator sets, running continuously. Sealed lead acid (VRLA) batteries provide back up power to generator maintenance, start up and cover the occasional case when fuel runs out. Ongoing costs are high, and include: Direct fuel cost Truck rolls. Refueling is usually needed every one or two weeks, at a high cost for a very remote site. Generator maintenance. Generator replacement. In continuous duty a small generator may only last two years. By changing the way the generator is controlled, an operator can achieve significant savings in running costs. This is called hybrid operation, where the generator only runs part of the time, and the battery runs the load while the generator is off. This white paper explains hybrid operation and how to use it to save operating costs at sites that have with no AC or very unreliable AC, and are primarily powered by diesel generators. 1. Overview In the conventional diesel-powered system the generator has capacity for running the load and recharging the battery. To ensure a reasonable recharge time, the generator must be sized much greater than the load. But most of the time the generator is just powering the load, running at anywhere from 30% to 60% of maximum load. The hybrid system changes this so that the generator is always running at close to full load. How? It only operates to charge the batteries. Once the batteries are charged, it stops.
2 Page 2 of 7 This is the operating sequence: The system starts with a fully charged battery. The generator is turned off and the battery takes the load. Once the battery has discharged to a set level, the generator starts again and quickly recharges the battery. The generator is turned off again and the cycle repeats. Battery charge level 100 % Discharge level Fast recharge to 100% charge Generator Run Time Fuel saving Fuel saving Generator off Start generator Cycle time about 24 hours Typically the generator will run for about 50% of the time or less. For the rest of the time, the battery is discharging. A full cycle can take around one day. But this all depends on the characteristics of battery, generator and load, and how operation is optimized. More on this later. 2. Where is the saving? Direct Fuel costs Consider this example: An 11kVA generator in standard duty (full time) at a load of 40% load takes 2.2 liters per hour, or 370 liters per week. Change this to hybrid operation at 80% load, 50% duty cycle. Then the fuel use is 3.65 liters per hour, or 306 liters per week at 50% duty cycle. This gives a 17% fuel saving. Using cyclic rated batteries, it is possible to go to a smaller recharge time (a lower duty cycle) and get further cost savings, up to 30%. Refueling cost Along with the reduced fuel consumption comes a corresponding reduction in truck rolls for refueling. For remote sites, the cost of bringing fuel to a site is likely to be higher than the direct fuel cost.
3 Page 3 of 7 Generator maintenance interval Instead of running 100% of the time at moderate load, the generator runs at full load for 50% of the time or less. The generator service interval is based on run time (not load), so the service interval is now at least twice as long. This provides a direct saving in truck rolls. Generator life is similarly increased, so replacement costs are much lower. 3. Batteries Is there a downside to this fuel saving? Definitely. The battery system is now being cycled daily, leading to some reduction in the battery life. Many VRLA batteries are only rated for a few hundred deep cycles. Others can tolerant frequent cycling and still provide a long life. So here are the tradeoffs: 1. High quality batteries with a cyclic rating are needed. 2. Battery life will be somewhat reduced. But this reduction depends on the battery type, how deep the cycle is, the recharge rate, average temperature, etc. 3. Some energy is lost in the recharge process. However, this is not significant compared to the savings. In practice, with 50% depth of discharge, well controlled temperature and a good cyclic rated battery, we can expect a life of three years or more. This needs to be factored into the calculated savings as part of an overall cost benefit analysis. 4. Optimization The fuel saving is based on fine tuning the use of the generator and battery for best efficiency. To get the best out of the system, start by understanding these parameters as they relate to your application. Then look at the interactions between the parameters. Fine tune each for the best performance, bearing in mind tradeoffs between OPEX (running cost) and CAPEX (initial purchase and replacement costs). Depth of discharge Adjust the depth of discharge to balance battery life against the time running on batteries. The deeper the discharge, the longer the system runs on battery and the larger the fuel saving. But if the discharge is too deep, then the battery life is shortened too much. A good choice for a cyclic rated battery is 50% depth. Other batteries not rated for cyclic duty may need to have a shallower discharge. Generator loading In an ideal world, the generator is matched exactly to the load and battery recharge. In practice, the size is rarely exactly right, and some compromises have to be made, such as slightly over-sizing the generator. Beware of pushing the load too close to the generator rating. Start-up surges and load variation could mean that a system with no reserve capacity fails to start under some conditions.
4 Recharge rate The shorter the recharge cycle, the longer time on battery and potentially the higher fuel savings. But if the recharge rate is too high, an oversized generator may be needed. Also, some batteries will not accept such a high recharge rate without shortening their life. The optimum recharge rate will achieve good battery life, and at least 50% of time on battery. Accurate control of recharge rate is essential. Full recharge If the batteries are not fully recharged every cycle, their capacity will staircase down each cycle until finally the system will fail. Ensure that the length of the recharge cycle is accurately controlled in such a way that the battery is always fully charged at the end. Any time spent on charge after that is unnecessary run time for the generator, resulting in additional fuel used. Equalization Some batteries in cyclic application will benefit from an equalize charge. This is a periodic limited overcharge of the battery. It can restore capacity to some extent. But not all batteries need equalization. Check the data sheet! Monitoring Using remote management, the network operator or service organization can prove the hybrid cost savings, ensure operation remains optimal, manage the response to faults, and support battery warranty claims. This information should be available remotely: Page 4 of 7 Charge / discharge cycle logs Prove the battery is fully charged at each cycle. See also the section below on battery warranty. Fuel use logs Is the system fuel use actually as predicted? Alarms A full set of alarms on DC power, generator, fuel, and battery state enables the operator to manage site issues and prevent small problems escalating to outages. 5. System Control How do we ensure all these operating parameters are maintained accurately? The system controller must accurately manage charge and discharge cycles, including charge voltage, charge duration, charge rate and depth of discharge. Eaton DC power systems use the system controller, such as the SC200, to manage the hybrid cycle. Discharge The controller accurately integrates the amperes discharged from the battery with time, to give an ampere-hours discharged total for the discharge / charge cycle. When this reaches the planned depth of discharge (say 50% of the nominal battery capacity), the controller closes a contact to start the generator.
5 Page 5 of 7 Recharge While the generator is running, the ampere-hours of charge into the battery are counted. When the ampere-hours recharged equals the ampere-hours discharged, plus a small factor to allow for inefficiencies, the charge is terminated. During the charge, the charge voltage is elevated ( Fast Charge ) to give the minimum recharge time. This charge voltage is temperature compensated. 6. Battery Warranty Since hybrid systems cycle the batteries every day, battery manufacturers will insist on full data to support any battery warranty claim. Data that may be asked for includes Number of cycles Duration of each charge and discharge cycle Ambient and battery temperature history Maximum discharge depth A full featured controller with large data log will be needed to provide this information. It should be possible to extract the log into a spreadsheet for full analysis and warranty support. For instance, the Eaton SC200 stores 10,000 data log records, and features dual-rate logging. The normal rate log provides a long term record of ambient temperatures and other operating conditions. The fast rate log provides a detailed record of each charge and discharge. 7. Environmental control Air conditioning and other environmental issues must be considered. During discharge, there is no AC present to power air conditioners. To maintain temperature during the discharge period (which is at least 50% of the time) the options include: Use inverters from the DC bus. Use DC powered air conditioners to improve efficiency and possibly reduce total cost by eliminating inverters. Use heat exchangers to reduce energy consumption. This is only practical for smaller outdoor cabinets. Use temperature-controlled DC extractor fans to cool the equipment. This is potentially the most energy-efficient, but is not suitable for many environments. In environments with high dust or salt spray air content, this will shorten equipment life. Any solution will have trade-offs between reliability, performance, cost, and efficiency. The local climate and other environmental issues may dictate a particular solution.
6 Page 6 of 7 8. Other energy sources This paper is focused on the hybrid Diesel generator battery solution. Of course, further fuel savings are possible using solar and / or wind power combined with battery storage and diesel generator backup. However, these are not always practical. Space may not be available Capital cost may be too high Solar panels may present a tempting target to thieves. Fuel cells are another alternative, and outside the scope of this paper, as the fuel use tradeoffs will not be the same. 9. Grid-tied applications Hybrid technology can provide even larger savings if AC mains supply is available. Then the batteries can be used to ride through an AC failure, without any need to start the generator. The generator only needs to start for longer AC failures. AC On AC Fail Battery Discharge Level Generator Run Time Fuel saving Fuel saving Does not start on short outage Start delayed Switch to battery Fuel savings will depend on the frequency and duration of AC outages. In theory, if all outages are less than the battery backup time, then fuel saving is 100%. Of course, this is unlikely to be achieved. But savings of more than 50% are likely. 10. Conclusions For a remote telecom site powered by a diesel generator, the hybrid solution can provide significant fuel and other OPEX savings. Tight control and monitoring of the charge and discharge cycles is essential. A fully featured controller such as the Eaton SC200 is needed.
7 To ensure the potential savings are achieved, carefully review and understand tradeoffs. Optimize the charge and discharge cycles, bearing in mind the characteristics of generator, batteries and load. A detailed cost / benefit analysis should be done, covering capital costs (generator, battery, control, monitoring) and operational costs (fuel, generator servicing, battery replacement, truck rolls, etc.). Page 7 of 7 About the author Simon Sloane is a product manager in Eaton s Telecommunications Solutions Division (TSD). He has worked in the DC power field for over 20 years, moving from power supply design to controller development to his present role as managing Eaton DC power system software products, including controllers and remote management software. For more information, contact the author: [email protected], or telephone About Eaton Eaton Corporation is a diversified power management company with 2007 sales of $13 billion. Eaton is a global technology leader in electrical systems for power quality, distribution and control; hydraulics components, systems and services for industrial and mobile equipment; aerospace fuel, hydraulics and pneumatic systems for commercial and military use; and truck and automotive drive train and power train systems for performance, fuel economy and safety. Eaton has 82,000 employees and sells products to customers in more than 150 countries. For more information, visit About Eaton s Telecommunications Solutions Division Eaton's Telecommunications Solutions Division provides DC power systems; associated products and services; hydraulic-magnetic circuit breakers and distribution modules to the telecommunications and other critical power industries. DC power solutions include 24V and 48V DC power systems, battery monitoring and control systems, cabinets and enclosures, and a wide range of services including remote monitoring, turnkey integration services and site support. Eaton Corporation All Rights Reserved. Eaton and Powerware are trade names, trademarks, and/or service marks of Eaton Corporation or its subsidiaries and affiliates. Issue A November 2008.
Mixing Sodium and Lead Battery Technologies in Telecom Applications
Mixing Sodium and Lead Battery Technologies in Telecom Applications Paul Smith Shanon Kolasienski Technical Marketing Manager Application Engineer GE Critical Power GE Energy Storage Plano, TX 75074 Schenectady,
Constant Voltage Charger Selection for VRLA Batteries
TECHNICAL BULLETIN 41-2129 Constant Voltage Charger Selection for VRLA Batteries Please Note: The information in this technical bulletin was developed for C&D Dynasty 12 Volt VRLA products. While much
Advanced Fuel Cells A Reliable and Green Solution to Reduce Operating Expenses of Telecommunication Networks
Advanced Fuel Cells A Reliable and Green Solution to Reduce Operating Expenses of Telecommunication Networks White Paper Anil K. Trehan, Vice President, Energy Solutions CommScope, Inc. May 28, 2013 Contents
A Solar Powered Cellular Base Station
Technical Whitepaper SolarConnect Energy management solution for Base Stations A Solar Powered Cellular Base Station Many people in emerging markets like India live in rural areas with limited access to
The reliability of the grid
Power topic #9019 Technical information from Cummins Power Generation Power system considerations for cell tower applications White Paper By Wissam Balshe, Group Leader, Sales Application Engineering Industry
HYBRID POWER SYSTEMS for TELECOM applications
HYBRID POWER SYSTEMS HYBRID POWER SYSTEMS HYBRID POWER SYSTEM WITH AC GENSET PRAMAC has developed a new solution that allow coupling a traditional AC constant speed diesel genset with an energy storage
DC Power Solutions Overview. DC Power Solutions for EVERY Network Application.
DC Power Solutions Overview DC Power Solutions for EVERY Network Application. DC Power Solutions for Every Network Application Eaton recognizes the challenges that are unique to different customers applications.
Solar Wind Microhydro Water Pumping Inverters Batteries Professional system design and installation
Solar Wind Microhydro Water Pumping Inverters Batteries Professional system design and installation BATTERY CHARGING GUIDELINES FOR GLOBAL/DAVIDSON TUBULAR PLATE BATTERIES Introduction Your Global/Davidson
UPS Applications and VRLA Battery Sizing
TECHNICAL BULLETIN 41-7334 UPS Applications and VRLA Battery Sizing 41-7334/0213/CD www.cdtechno.com The uninterruptable power system (UPS) is used to protect critical equipment and processes from the
Definition of effective metrics for evaluating the efficiency of hybrid power systems at telecom cell sites
Power topic #NAPT-5516-EN Technical information from Cummins Power Generation Definition of effective metrics for evaluating the efficiency of hybrid power systems at telecom cell sites A system-level
LEAD ACID BATTERY working LIFETIME STUDY
LEAD ACID BATTERY working LIFETIME STUDY Valve Regulated Lead Acid (VRLA) Batteries Overview The most common type of battery used on UPS systems and for backup of telecommunications systems. VRLA batteries
A COMPARISON OF TYPICAL UNINTERRUPTIBLE POWER SUPPLY (UPS) DESIGNS IN TODAY S MARKETS
A COMPARISON OF TYPICAL UNINTERRUPTIBLE POWER SUPPLY (UPS) DESIGNS IN TODAY S MARKETS October 22, 2010 Authored by: Kevin Binnie, Senior Product Portfolio Manager ALPHA TECHNOLOGIES LTD. Executive Summary
Additional Solar System Information and Resources
Additional Solar System Information and Resources Background information a. Roughly 400 schools in NJ already have solar systems, producing more than 91 MW, out of approximately 2500 K- 12 schools in NJ.
Evolion Li-ion battery. Saft s proven ultra-compact solution for telecom applications
Evolion Li-ion battery Saft s proven ultra-compact solution for telecom applications Saft: Providing energy for today s telecom installations Saft has a complete range of specialised batteries for a wide
IT S TIME TO EXPECT MORE FROM AN ENERGY STORAGE SOLUTION
S U P E R I O R F L Y W H E E L E N E R G Y S T O R A G E S O L U T I O N S IT S TIME TO EXPECT MORE FROM AN ENERGY STORAGE SOLUTION POWER. REDEFINED. VYCON FLYWHEEL TECHNOLOGY APPLICATIONS: BACKUP GENERATOR
Giving You the Power to Stand Alone
Cutler-Hammer Home Standby Generators Product Focus Quality Residential Products Ease of Installation Save Time and Money Giving You the Power to Stand Alone EATON CORPORATION Innovative Technology TVSS
Alternative data center power
Alternative data center power A quantitative TCO comparison of 400V AC and 600V AC power systems Abstract Power efficiency has become a critical focus for IT and facilities managers as they struggle to
Maximizing UPS Availability
Maximizing UPS Availability A comparative assessment of UPS designs and deployment configurations for the highavailability data center By Chris Loeffler Product Manager, BladeUPS & Data Center Applications
BATTERY CHARGING GUIDELINES FOR 6-VOLT DEEP CYCLE BATTERIES
BATTERY CHARGING GUIDELINES FOR 6-VOLT DEEP CYCLE BATTERIES Introduction Your 6-volt deep cycle battery set has been specially formulated for long cycle life and has particular voltage and specific gravity
PV (photovoltaic) Basics There are generally two types of PV systems. The first and easiest (though the least flexible) is a grid tie system where
PV (photovoltaic) Basics There are generally two types of PV systems. The first and easiest (though the least flexible) is a grid tie system where the power generated by the solar panel (panels) runs an
APPLICATION NOTE TESTING PV MICRO INVERTERS USING A FOUR QUADRANT CAPABLE PROGRAMMABLE AC POWER SOURCE FOR GRID SIMULATION. Abstract.
TESTING PV MICRO INVERTERS USING A FOUR QUADRANT CAPABLE PROGRAMMABLE AC POWER SOURCE FOR GRID SIMULATION Abstract This application note describes the four quadrant mode of operation of a linear AC Power
FREE iphone APP Get our FREE OPEX SAVER CALCULATOR iphone App scan code to go direct to App Store.
Text and design: Creuna/Mikla. Photo: Shutterstock, Getty Images. Document no: MMP10.0002.BR3 WWW.ELTEK.COM FREE iphone APP Get our FREE OPEX SAVER CALCULATOR iphone App scan code to go direct to App Store.
Hybrid GenSet HYBRID POWER UNIT. Hybrid GenSet. POWER RANGE 7-35 kw. APPLICATIONS Outdoor Indoor Telecom Site. www.ascotinternational.
EN POWER RANGE 7-35 kw APPLICATIONS Outdoor Indoor Telecom Site 1 Desert Border Control (Middle East) Remote Off Grid Indoor TLC Site (Africa) Remote Off Grid OutdoorTLC Site (Asia) Remote Off Grid Indoor
(EMR) system in resource-constrained settings. The use of the EMR at point-of-care (POC)
Centralized Power Backup System and Low-Power Computing A reliable power source is a core requirement for using an electronic medical record (EMR) system in resource-constrained settings. The use of the
Siemens Hybrid Power Solutions. Cost and emission reduction by integrating renewables into diesel plants
Siemens Hybrid Power Solutions Cost and emission reduction by integrating renewables into diesel plants Instrumentation, Controls & Electrical Complete, optimized solutions that minimize your risk One-stop
Solar Powered Wireless Sensors & Instrumentation: Energy Harvesting Technology Reduces Operating Cost at Remote Sites
Solar Powered Wireless Sensors & Instrumentation: Energy Harvesting Technology Reduces Operating Cost at Remote Sites Standards Certification Education & Training Publishing Conferences & Exhibits Michael
POWER YOUR TELECOM SITE WITH OLYMPIAN Hybrid Power for Telecom Applications Solar Photovoltaic Wind Diesel Battery
POWER YOUR TELECOM SITE WITH OLYMPIAN Hybrid Power for Telecom Applications Solar Photovoltaic Wind Diesel Battery For more than 85 years, Caterpillar has created products and services that support the
Reducing operating costs of telecom base stations with remote management
Reducing operating costs of telecom base stations with remote management Whitepaper How remote management can be used to cut operating expenses of existing telecom infrastructure. HMS Industrial Networks
When Do Solar Electric & Utility Back-Up Systems Make Sense?
When Do Solar Electric & Utility Back-Up Systems Make Sense? Oil & Gas Industry Presentation Proprietary Information 2010 SunWize Technologies When Do Solar Electric and Utility Back-Up Systems Make Sense?
CUTES Solar Power System
Solar Power System Solar power systems provide a continuous, reliable power solution that's easily deployed, cost-effective and requires little maintenance. Solar Power Systems are complete, fully integrated
Power Your Telecom site with olympian Hybrid Power for Telecom Applications Solar Photovoltaic Wind Diesel Battery
Power Your Telecom site with olympian Hybrid Power for Telecom Applications Solar Photovoltaic Wind Diesel Battery For more than 85 years, Caterpillar has created products and services that support the
Is an energy-wasting data center draining your bottom line?
Abstract Is an energy-wasting data center draining your bottom line? New technology options and power distribution strategies can dramatically reduce the cost and carbon footprint of your data center.
Containerized Infrastructure Solutions Fast and efficient deployment, anywhere, anytime
Containerized Infrastructure Solutions Fast and efficient deployment, anywhere, anytime Containerized Infrastructure for Business-Critical Continuity Are you deploying a remote site faster than you can
SODIUM-METAL HALIDE BATTERIES FOR STATIONARY APPLICATIONS
SODIUM-METAL HALIDE BATTERIES FOR STATIONARY APPLICATIONS Richard Bourgeois, P.E. Lead Systems Engineer Energy Storage Technology GE Transportation Schenectady, NY 12345 INTRODUCTION Advanced batteries
DATA CENTER UNIQUE CHARACTERISTICS AND THE ROLE OF MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS
DATA CENTER UNIQUE CHARACTERISTICS AND THE ROLE OF MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS ABSTRACT Data Centers are a critical part of the world economic systems. Billions of electronic transactions happen
Coslight Hybrid Power System with Solar
Coslight Hybrid Power System with Solar (Technical Manual Draft V1.0) Harbin Coslight Power Co., Ltd. Contents I. Overview... 2 Characteristics of System with Solar 2 II. Composition of System with Solar......
Off-grid solar and backup power installations
Off-grid solar and backup power installations A World of Power Problems... Residential Backup Power Grid-Interactive 3-Phase Commercial Buildings with Backup Power Grid-Interactive Residential with Backup
AC Coupling of Inverters for Grid Tied PV Systems
AC Coupling of Inverters for Grid Tied PV Systems AC Coupling with Conext s, Xantrex GT Inverters, and Conext TX Inverters Application Note 976-0240-01-01 Rev B DANGER RISK OF FIRE, ELECTRIC SHOCK, EXPLOSION,
Power Management of Cell Sites
International Refereed Journal of Engineering and Science (IRJES) ISSN (Online) 2319-183X, (Print) 2319-1821 Volume 2, Issue 9 (September 2013), PP.41-45 Power Management of Cell Sites K.Santhosh Kumar
Harmonics in your electrical system
Harmonics in your electrical system What they are, how they can be harmful, and what to do about them Abstract Harmonic currents, generated by non-linear electronic loads, increase power system heat losses
1.1 ANNUAL PREVENTIVE MAINTENANCE VISIT
Maintenance Service - 1 - Lead Acid Battery Frame On-Site Warranty Statement of Work 1.0 Executive Summary Lead Acid Battery Frame On-Site Warranty Service Service Table of Contents 1.0 Executive Summary
Single Phase UPS Management, Maintenance, and Lifecycle
Single Phase UPS Management, Maintenance, and Lifecycle White Paper 210 Revision 0 by Justin Solis Executive summary How long will my battery last? and what is the best practice for maintaining my UPS?
Temperature Compensated Charging of Lead Acid Batteries
Technical Note Batteries 512-0101-01-01 Rev 1 Temperature Compensated Charging of Lead Acid Batteries Introduction To ensure optimum charging of lead acid batteries, the charge voltages should be adjusted
Nokia Siemens Networks Sustainable Energy Solutions by Peter H. Hellmonds Corporate Affairs, Nokia Siemens Networks
THE PANEL OF THE UNITED NATIONS COMMISSION ON SCIENCE AND TECHNOLOGY FOR DEVELOPMENT 9-11 November 2009 Geneva Nokia Siemens Networks Sustainable Energy Solutions by Peter H. Hellmonds Corporate Affairs,
Solar Power for PC Deployments: Enabling ICT Beyond the Grid
WHITE PaPER Solar Power for PC Deployments Solar Power for PC Deployments: Technology for converting solar energy to electricity was first introduced over 130 years ago, and it has been used to power PCs
Installation and Operation Manual Back-UPS BX800CI-AS/BX1100CI-AS
+ Installation and Operation Manual Back-UPS BX800CI-AS/BX1100CI-AS Inventory Safety and General Information bu001c This unit is intended for indoor use only. Do not operate this unit in direct sunlight,
CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN
CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN 5.1 Introduction So far in the development of this research, the focus has been to estimate the available insolation at a particular location on the earth s surface
Distributed versus centralized power backup strategies
Distributed versus centralized power backup strategies Choosing the right UPS deployment architecture for your data center By Ed Spears Product Manager, Eaton Power Quality Solutions Operation Eaton Corporation
PSC-A5 Solar Charge Controller Manual
( 5A, 12V/24V Output, Double Mode ) 1. Introduction: This controller is suitable for 12V and 24V solar photovoltaic system. The charge and discharge current is 5A. The maximum solar panel for 12V system
ACHIEVING CHARGE QUALITY FOR LEAD ACID BATTERIES IN INDUSTRIAL MOTIVE APPLICATIONS
ACHIEVING CHARGE QUALITY FOR LEAD ACID BATTERIES IN INDUSTRIAL MOTIVE APPLICATIONS Delta-Q Technologies success as an industrial battery charger supplier to original equipment manufacturers (OEMs) has
Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF
Daker DK 1, 2, 3 kva Manuel d installation Installation manual Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Index 1 Introduction 24 2 Conditions of use 24 3 LCD Panel 25 4 Installation 28 5 UPS communicator
Protecting the Power Source
Protecting the Power Source The ibattery asset management system helps electric lift truck fleet owners optimize battery life and performance, increase productivity and drive down operating costs. The
Reduce the cost of communication with ComAp. Telecom tower solutions
Reduce the cost of communication with ComAp Telecom tower solutions Telecom tower solutions The world is going through a digital transformation. As subscriber penetration and data traffic continue to rise,
Telecom Energy Management
Telecom Energy Management An Independent Service provider s perspective Sharat Chandra President & COO Strategy and New Technologies Agenda Setting the Context - What Energy Challenges are we dealing with
The Quest for Energy Efficiency. A White Paper from the experts in Business-Critical Continuity
The Quest for Energy Efficiency A White Paper from the experts in Business-Critical Continuity Abstract One of the most widely discussed issues throughout the world today is the rapidly increasing price
NetXtend Flex Series Integrated Outdoor Enclosure Solution. Outside Plant for Business-Critical Continuity
NetXtend Flex Series Integrated Outdoor Enclosure Solution Outside Plant for Business-Critical Continuity Features & Benefits Full flexibility and scalability one enclosure for various telecommunication
THE PROPER CHARGING OF STATIONARY LEAD-ACID BATTERIES. (YOUR BATTERY IS ONLY AS GOOD AS HOW YOU CHARGE IT.)
THE PROPER CHARGING OF STATIONARY LEAD-ACID BATTERIES. (YOUR BATTERY IS ONLY AS GOOD AS HOW YOU CHARGE IT.) J. Allen Byrne Engineering, Training and Tech Support Manager Interstate PowerCare, a Division
Power Quality. Voltage Sag Ride-through Mitigation in Sequence by Increasing Cost
Power Quality Voltage Sag Ride-through Mitigation in Sequence by Increasing Cost A voltage sag is defined as a decrease in voltage magnitude below 90% of nominal, but not a complete interruption. The typical
Re-defining the utility-scale inverter
Re-defining the utility-scale inverter We believe in green energy in the ability to meet and contribute to growing power demands while supporting a smart grid that serves a smart society. Solution at a
Industrial Batteries / Motive Power. 2100 Chargers 2100.NET.»For improved efficiency and durability«
Industrial Batteries / Motive Power 2100 Chargers 2100.NET»For improved efficiency and durability« Motive Power > 2100 Product overview 2100 product range Energy Efficiency and Economy reduce overall operating
Tough Decision: On-Line or Line-Interactive UPS?
W H I T E P A P E R Tough Decision: On-Line or Line-Interactive UPS? How to Choose the Right Protection for Your Network Executive Summary In today s data-driven, technology-dependent world, no organization
Sunica.plus Ni-Cd batteries. The robust daily cycling solution for off-grid solar PV systems
Sunica.plus Ni-Cd batteries The robust daily cycling solution for off-grid solar PV systems Sunica.plus is the ideal energy storage choice for off-grid solar PV systems (1) The most reliable battery under
SmartPro 100/110/120V 1.5kVA 900W Line-Interactive Sine Wave UPS, Tower, SNMP, Webcard, USB, DB9 Serial
SmartPro 100/110/120V 1.5kVA 900W Line-Interactive Sine Wave UPS, Tower, SNMP, Webcard, USB, DB9 Serial MODEL NUMBER: SMART1500SLT Highlights 1.5kVA / 1500VA line interactive tower UPS; Sine wave output
Renewable Energy in Telecom 2nd India Specific working group: Green Power for Mobile
Renewable Energy in Telecom 2nd India Specific working group: Green Power for Mobile Sairam Prasad CTO, Bharti Infratel Ltd Agenda Indian Carbon Footprint Scenario Energy Management Opportunities in Energy
Tel.X Ni-Cd battery. The compact maintenance-free solution for telecom networks
Tel.X Ni-Cd battery The compact maintenance-free solution for telecom networks Tel.X, delivering high-energy performance in a compact maintenance-free package Tel.X: guaranteed power continuity for remote
Optimizing Power Distribution for High-Density Computing
Optimizing Power Distribution for High-Density Computing Choosing the right power distribution units for today and preparing for the future By Michael Camesano Product Manager Eaton Corporation Executive
26 3213.13 Diesel Engine Driven Generators Page 1 of 6
Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at
Batteries and inverters
Batteries and other energy storage devices store energy so that it can be used when needed. In a stand-alone power system, the energy stored in batteries can be used when energy demand exceeds the output
Increased power protection with parallel UPS configurations
Increased power protection with parallel UPS configurations Making the selection between Centralized Bypass and Distributed Bypass systems Janne Paananen Application Engineer, Large Systems Group Eaton
SmartOnline 200-240V 6kVA 4.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 6U Rack/Tower, DB9 Serial, Hardwire
SmartOnline 200-240V 6kVA 4.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 6U Rack/Tower, DB9 Serial, Hardwire MODEL NUMBER: SU6000RT3UHV Highlights 6000VA / 6kVA / 4200W on-line double-conversion
Harvesting Solar Energy
Harvesting Solar Energy Overview of Systems, options and benefits of Solar Energy Systems By:John Miggins Harvest Solar Energy renewable solutions to everyday needs www.harvestsolar.net 1 Solar Energy
WHOLESALE DIRECT INC. 5620 WEST 65TH STREET
Auto Pump V 200 100 0 100 Max Rating Vehicle mount compressor ensures truck air brake system is properly pressurized for immediate dispatch from station Pressure switch regulated operation automatically
Liebert GXT MT+ CX UPS, 1000VA - 3000VA Intelligent, Reliable UPS Protection. AC Power for Business-Critical Continuity
Liebert GXT MT+ CX UPS, 1000VA - 3000VA Intelligent, Reliable UPS Protection AC Power for Business-Critical Continuity Liebert GXT MT+ CX UPS, 1000VA -3000VA Intelligent, Reliable UPS Protection Liebert
The True Cost of Providing Energy to Telecom Towers in India
The True Cost of Providing Energy to Telecom Towers in India Whitepaper Contents Introduction... 2 A typical telecom tower site... 3 Telecom site operating conditions... 3 Case study: 3 BTS Site with 12
Electric Coolant Pumps. Always at the Correct Temperature
Electric Coolant Pumps Always at the Correct Temperature Electric coolant pumps Conventional pumps for engine cooling are driven by toothed belts and hence their output is coupled to engine RPM. Coolant
HOMER Software Training Guide for Renewable Energy Base Station Design. Areef Kassam Field Implementation Manager
HOMER Training Guide for Renewable Energy Base Station Design Areef Kassam Field Implementation Manager Solar Table of Contents Introduction Step Step Step Step Solar Step Step Step Step Solar Introduction
Naps Solar Systems. for Demanding Environments
Naps Solar Systems for Demanding Environments Naps Solar Systems The Sol Solar Electricity for Feeding the Grid In a grid-connected solar electricity system, DC electricity produce by the solar cells is
Technical Information Battery Management of the Sunny Island Gentle charging control for lead-acid batteries based on current state of the battery
Technical Information Battery Management of the Sunny Island Gentle charging control for lead-acid batteries based on current state of the battery Content Exact determination of the state of charge is
Using the Phoenix MultiPlus
Using the Phoenix MultiPlus to reduce operating cost of a generator www.victronenergy.com 1. The traditional AC generator system Per Watt ac-power, an inverter is generally more expensive than a generator.
D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify.
SECTION 263354 STATIC UPS TESTING AND COMMISSIONING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes 1. System start-up services. 2. Battery charging. 3. Load bank testing. 4. Battery load testing. 5.
Heliocentris Renewable Off-Grid Power Solutions and Efficient Energy Management
Power for the 21st Century Innovation Energy Environment Renewable Off-Grid Power Solutions and Efficient Energy Management 28. November 2015, Renewable Energy Business Seminar Rainer Grumann Company Overview
Back-UPS 650 VA 120 V with AVR (BX650CI-LM)
Back-UPS 650 VA 120 V with AVR (BX650CI-LM) Overview Do not install the unit in direct sunlight, in areas of excessive heat or humidity, or in contact with fluids ON/OFF button Battery connector Circuit
A reasonable, new furnace (mid efficiency) has the following electrical requirements:
June 2007 Power Backup Systems for Your Home. As promised from a previous safety meeting, a couple of options to protect you home in the event of a power failure. These options are for the most serious,
UPS Monitoring. Tutorial. 1-800-693-0351 www.dpstele.com. A guide from: Your partners in UPS Monitoring Systems
UPS Monitoring A guide from: Tutorial Your partners in UPS Monitoring Systems An uninterruptible power supply (UPS) is a backup power source that activates automatically when the primary source (typically
Hybrid and Off grid Systems Princeton Power Systems Inverter Technology Ken McCauley and Alan Cohen Princeton Power Systems
Hybrid and Off grid Systems Princeton Power Systems Inverter Technology Ken McCauley and Alan Cohen Princeton Power Systems Core Technologies High quality, Robust Power Electronics: Grid Tied Inverter
User s Manual Before using the inverter, you need to read and save the safety instructions.
User s Manual Before using the inverter, you need to read and save the safety instructions. STI SERIES (STI200, STI300, STI500, STI700, STI1000) Power Frequency Pure Sine Wave Inverter The information
LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification
08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and
Hybrid shunter locomotive
Hybrid shunter locomotive 1 Hervé GIRARD, Presenting Author, 2 Jolt Oostra, Coauthor, 3 Joerg Neubauer, Coauthor Alstom Transport, Paris, France 1 ; Alstom Transport, Ridderkerk, Netherlands 2 ; Alstom
Storage Battery System Using Lithium ion Batteries
Offices and schools Utilities / Renewable energy Storage Battery System Using Lithium ion Batteries Worldwide Expansion of Storage Battery System s Commercial Buildings Residential The Smart Energy System
32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 113 kva, 90 kw 124 kva, 99 kw 6WDQGE\ 114 kva, 91 kw 125 kva, 100 kw
,1'8675,$/#*(16(7 6HULHV#'9#448 32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 113 kva, 90 kw 124 kva, 99 kw 6WDQGE\ 114 kva, 91 kw 125 kva, 100 kw Generator set consisting of engine and alternator mounted
Telecel Central African Republic Feasibility Study
1 Telecel Central African Republic Feasibility African Republic (CAR) is landlocked. It is mainly savannah in the north and equatorial forest in the south. Chad borders the north of the country, with Sudan
3000W Power Inverter
3000W Power Inverter OWNER S MANUAL Model number-4573000 TO REDUCE THE RISK OF INJURY, USER MUST READ AND UNDERSTAND THIS INSTRUCTIONAL MANUAL. THIS MANUAL CONTAINS IMPORTANT INFORMATION REGARDING THE
Battery Handbook. By: RON SMITH
Battery Handbook By: RON SMITH Information compiled from the Battery Charger Handbook and the Battery Handbook written by Alvin G. Graham, Chief Engineer, Ratelco Electronics Inc. Introduction The purpose
User Manual. Hybrid 1KW-5KW INVERTER / CHARGER. Version: 1.1
User Manual Hybrid 1KW-5KW INVERTER / CHARGER Version: 1.1 Table of Contents ABOUT THIS MANUAL... 1 Purpose... 1 Scope... 1 SAFETY INSTRUCTIONS... 1 INTRODUCTION... 2 Product Overview... 3 INSTALLATION...
SmartOnline 200-240V 5kVA 4.5kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 4U Rack/Tower, USB, DB9 Serial
SmartOnline 200-240V 5kVA 4.5kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 4U Rack/Tower, USB, DB9 Serial MODEL NUMBER: SU5000RT4UHV Description Tripp Lite SU5000RT4UHV 5000VA / 5kVA /